Thousand Hundred Industrial Co., Ltd.
T.H www.thic.net
RC F 333AC 055 — 302(1) (2) (3) (4) (5)
Nomination of Rogowski Coil
Nomination:(1) RC : Rogowski Coil
(1) (2) (3) (4) (5)
P : PCB Rogowski coil; J :Just Coil Only;
(2) The material of Rogowski Coil:F : Flexible,with an Integrator; H : Hard;
P : PCB Rogowski coil; J :Just Coil Only;
(3) Output Signal:333AC : 333mV AC; 005AC : 5V AC;005DC : 5V DC; 420DC : 4-20mA DC;03VAC : 3V AC; 30MAC : 30mA AC; etc…
(4) Th di t f th i i l
(5) Rated Current:
(4) The diameter of the inner circle : 055 : 55mm; 305 : 305mm
(5) Rated Current:302 : 3000A; 303 : 30,000A; 301 : 300A;30R : 30A; 03R : 3A; 0R3 : 0.3A
T.H www.thic.net
T.H www.thic.net
RCJ300MV185-302
3000A AC300mV
AC185 14 /
10Hz~30kHz
/ ±1% ±0.2% ±3%
RCJ7R9MV055-102
1000A AC7.9mV
AC55 7 /
10Hz~30kHz
/ ±1% ±0.2% ±1%
RCJ004MV055-501
500A AC 4mV 55 7 /10Hz~30kHz
/ ±1% ±0.2% ±1%
RCJ0R8MV055-101
100A AC0.8mV
AC55 7 /
10Hz~30kHz
/ ±1% ±0.2% ±1%
RCJ7R9MV080-102
1000A AC7.9mV
AC80 7 /
10Hz~30kHz
/ ±1% ±0.2% ±1%
RCJ7R9MV105-102
1000A AC7.9mV
AC105 7 /
10Hz~30kHz
/ ±1% ±0.2% ±1%
RCJ7R9MV180-102
1000A AC7.9mV
AC180 7 /
10Hz~30kHz
/ ±1% ±0.2% ±1%
Thousand Hundred Industrial Co., Ltd. Rogowski Coil Series ( Only the coil )
Cross-sectionDia.Φ (mm)
Power Supply Frequency Phase ErrorAccuracy
ClassLinearity
ErrorPosition
Accuracy
Type
CharacteristicsSPEC
Download/LinkRated CurrentRatedOutput
Inner Dia.Φ
(mm)
AC
T.H www.thic.net
RCF333AC055-101
100A AC333mV
AC55 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC055-201
200A AC333mV
AC55 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC055-401
400A AC333mV
AC55 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC055-102
1000A AC333mV
AC55 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC055-122
1200A AC333mV
AC55 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC080-102
1000A AC333mV
AC80 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC080-152
1500A AC333mV
AC80 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC105-202
2000A AC333mV
AC105 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
RCF333AC180-302
3000A AC333mV
AC180 7
External12–24VDC
50/60Hz<1º
(50/60 Hz)±1% ±0.2% ±1%
Rated CurrentRatedOutput
Thousand Hundred Industrial Co., Ltd. Rogowski Coil Series ( 333mV )
Inner Dia.Φ
(mm)
Cross-sectionDia.Φ (mm)
Power Supply Frequency Phase ErrorAccuracy
ClassLinearity
ErrorPosition
Accuracy
Type
CharacteristicsSPEC
Download/Link
T.H www.thic.net
RCF 005AC185 50R
50A AC AC 5V 185 14 ±15V10Hz~30kHz
<2°(50/60 Hz)
±1% ±0.2% ±2%
RCF 005AC185 101
100A AC AC 5V 185 14 ±15V10Hz~30kHz
<2°(50/60 Hz)
±1% ±0.2% ±2%
RCF 005AC185 201
200A AC AC 5V 185 14 ±15V10Hz~30kHz
<2°(50/60 Hz)
±1% ±0.2% ±2%
RCF 005AC185 501
500A AC AC 5V 185 14 ±15V10Hz~30kHz
<2°(50/60 Hz)
±1% ±0.2% ±2%
RCF 005AC185 102
1000A AC AC 5V 185 14 ±15V10Hz~30kHz
<2°(50/60 Hz)
±1% ±0.2% ±2%
RCF 005AC185 202
2000A AC AC 5V 185 14 ±15V10Hz~30kHz
<2°(50/60 Hz)
±1% ±0.2% ±2%
Thousand Hundred Industrial Co., Ltd. Rogowski Coil Series ( AC 5V )
Rated Current Phase ErrorAccuracy
ClassLinearity
ErrorPosition
Accuracy
Type
CharacteristicsSPEC
Download/LinkRatedOutput
Inner Dia.Φ
(mm)
Cross-sectionDia.Φ (mm)
Power Supply Frequency
T.H www.thic.net
RCF 005DC185 50R
50A AC DC5V 185 14 ±15V10Hz~30kHz
/ ±1% ±0.2% ±2%
RCF 005DC185 101
100A AC DC5V 185 14 ±15V10Hz~30kHz
/ ±1% ±0.2% ±2%
RCF 005DC185 201
200A AC DC5V 185 14 ±15V10Hz~30kHz
/ ±1% ±0.2% ±2%
RCF 005DC185 501
500A AC DC5V 185 14 ±15V10Hz~30kHz
/ ±1% ±0.2% ±2%
RCF 005DC185 102
1000A AC DC5V 185 14 ±15V10Hz~30kHz
/ ±1% ±0.2% ±2%
RCF 005DC185 202
2000A AC DC5V 185 14 ±15V10Hz~30kHz
/ ±1% ±0.2% ±2%
AccuracyClass
LinearityError
PositionAccuracy
Frequency Phase ErrorPower Supply
Thousand Hundred Industrial Co., Ltd. Rogowski Coil Series ( DC 5V )
Type
CharacteristicsSPEC
Download/LinkRated CurrentRatedOutput
Inner Dia.Φ
(mm)
Cross-sectionDia.Φ (mm)
T.H www.thic.net
RCF 420DC185 50R
50A AC 4~20mA 185 14 ±15V 5Hz~30kHz / ±1% ±0.2% ±2%
RCF 420DC185 101
100A AC 4~20mA 185 14 ±15V 5Hz~30kHz / ±1% ±0.2% ±2%
RCF 420DC185 201
200A AC 4~20mA 185 14 ±15V 5Hz~30kHz / ±1% ±0.2% ±2%
RCF 420DC185 501
500A AC 4~20mA 185 14 ±15V 5Hz~30kHz / ±1% ±0.2% ±2%
RCF 420DC185 102
1000A AC 4~20mA 185 14 ±15V 5Hz~30kHz / ±1% ±0.2% ±2%
RCF 420DC185 202
2000A AC 4~20mA 185 14 ±15V 5Hz~30kHz / ±1% ±0.2% ±2%
Thousand Hundred Industrial Co., Ltd. 4-20mA
Type
CharacteristicsSPEC
Download/LinkRated Current RatedOutput
Inner Dia.Φ
(mm)
Cross-sectionDia.Φ (mm)
Power Supply Frequency Phase ErrorAccuracy
ClassLinearity
ErrorPosition
Accuracy
The RCF005A series Flexible Rogowski coil Current Transformer can monitor AC line current in circuits up to11KVac and nominal currents up to 50KAmps.They can be opened and are flexible for ease of installation around busbars and multiple conductors.
Coil generally require a integrating conditioning circuit,since the output of the coil is the derivative of the actualcurrent.Coil are very dependent on the uniformity of the winding in the sense coil,making them more sensitive to theposition of the conductor(s) being measured in the opening and more sensitive to the magnetic fields from externalconductors.
So RCF005A series will output all of standard signal no matter current or voltage.It will satisfy all of industrialwhich supposed to connect with Rogowski coil.
Thousand Hundred Industrial CO.,LTD.
equipment
RCF005A
Advantages Simple to install(especially in limited space) Wide dynamic current range No magnetic saturation No open circuit danger,No overload
danger,Intrinsically safe. Wide bandwidth Low current measurable High protection class IP68
Applications Power meters Energy sub-meters Power quality monitoring Condition monitoring Distributed measurement systems. Lighting current Electric furnace Harmonic management Relay Protection
Specification
MODEL
Window size 60mm 90mm 105mm 125mm 150mm 185mm
Coil length 200mm 300mm 350mm 420mm 510mm 620mm
Lead length 2meter
Currentarrange
100A-50000A
RatedCurrent
100A,200A300A,400A500A,600A
500A,1000A1500A,2000A2500A,3000A
1000A,2000A3000A,4000A5000A,6000A
1000A,2000A3000A,4000A5000A,6000A
1000A,3000A5000A,7000A9000A,10000A
2000A,5000A8000A,10000A30000A,50000A
Output 0-5AAccuracy(typ.)
<1% typical at 20% to 120% of ratedcurrent (most accurate position, 25℃)
Phase error <0.5°
Linearity(10% to100% ofrange)
±0.2% of reading
Bandwidth(-3dB)
20Hz to 10kHz
Conductorpositionsensitivity
±1% of reading
Operatingtemperature
-20℃ to 70℃
Thousand Hundred Industrial CO.,LTD.
RCF005A-200 RCF005A-300 RCF005A-350 RCF005A-420 RCF005A-510 RCF005A-620
Position sensitivity
Materials
Coil & cableThermoplastic rubberflame retardant UL 94 V-0 rated
Couplings PA6 UL 94 V-O ratedColor(coil) Black, Yellow, Red, Green, BlueShielded 100% coil, 100% output cable
Safety
CertificationsCE markedComplies with EMC EN 61326-1 2006
Conductor Position Typical Error(%)
Measured bus0.2%
Ext. field influence<0.4%
Temperature sensitivity (max) <0.6%
Thousand Hundred Industrial CO.,LTD.
Dimensions(mm)
A.Windows size 60 90 105 125 150 185B.Coils O.D. 72 106 117 141 166 201C.Coil Length 200 300 350 420 510 620D.Locking Connector O.D 9.8 12.2 14.75E.Coil diameter 6 8 11F.Lead Cable Total Length 2meterG.Locking Connectorlength
19 23 24
H.Plug diameter 7.5 10 12.5I. Plug height 8.7 11 14
Thousand Hundred Industrial CO.,LTD.
RCF005A-200 RCF005A-300 RCF005A-350 RCF005A-420 RCF005A-510 RCF005A-620
Safety and warning notesIn order to guarantee safe operation of the transducer and to be able to make proper use of all features andfunctions,please read these instructions thoroughly!Safe operation can only be guaranteed if the transducer is used forthe purpose it has been designed for and within the limits of the technical specifications.Ensure you get up-to-datetechnical information that can be found in the latest acssociated datasheet under
Caution!Risk of dangerIgnoring the warnings can lead to serious injury and/or cause damage!The electric measuring transducer may only be installed and put into operation by qualified personnel that havereceived an appropriate training,The corresponding national regulations shall be observed during installation andoperation of the transducer and any electrical conductor.The transducer shall be used in electric/electronic equipmentthe respect to applicable standards and safety requirements and in accordance with all the reated systems andcomponents manufacturers’ operating instructions.
Caution!Risk of electrical shockWhen operating the transducer,certain parts of the module may carry hazardous live voltage(e.g.primaryconductor).The user shall ensure to take all measures necessary to protect against electrical shock.The transducer is abuild-in device containing conducting parts that shall not be accessible after installation.A protective enclosure oradditional insulation barrier may be necessary.Installation and maintenance shall be done with the main power supplydisconnected except if there are no hazardous live parts in or in close proximity to the system and if the applicablenational regulations are fully observed.
Safe and trouble-free operation of this transducer can only be guaranteed if transport,storage and installation arecarried out correctly and operation and maintenance are carried out with care.
WARING!Do not stress the coil by applying any kind of mechanical force(ie.twisting,puncturing,excessive pressure,tightbending,etc.) which will dramatically degrade the device’s accuracy.
Thousand Hundred Industrial CO.,LTD.