Operating voltage 24 .. 300V AC/DC24V AC/DC or 180..265V AC (T1-100S, T1-30S)
Output contact 1 C/O
Protection class IP20
Storage temperature -40°C .. 75°C
Connection Rail mounted
Maximum switching current 10A
Operating temperature -20°C .. 60°C
Maximum switching voltage 250V AC
Maximum switching power 1250VA
Time range :(T1-M4)
time range : 1 .. 60 seconds (T1-60S, T1-60S2)1 .. 100 seconds (T1-100S)1 .. 30 seconds (T1-30S)
t, t , t timer :on off (time range) x (multiplier value)
87654321
modetontoff
ON (1)
OFF (0)
mode (7,8)
00011011
on delayoff delayon flasheroff flasher:
:::
t (4,5,6), t (1,2,3) on off
000001010011
10 seconds30 seconds100 seconds10 minutes:
:::
100101110111
60 minutes10 hours100 hours10 days:
:::
Adjustment values1s10s100s1m10m
: 1 second: 10 seconds: 100 seconds: 1 minute: 10 minutes
1h10h100h1d10d
: 1 hour: 10 hours: 100 hours: 1 day: 10 days
Time range :(T1-M5,
T1-FLASH, T1-K)10
1
1
1
1100
10
10100 10
s
m
hd
0.4
0.6
0.8 1
0.2
t , t multiplier value :on off(T1-M5, T1-FLASH)
0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.80.9 - 1
t multiplier value :(T1-K)
0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.80.9 - 1
OPERATION MODE
on delay(mode: a, ND)
off delay(mode: b, FD)
on-offdelay(mode: NFD)
FUNCTION STATEMENTFUNCTION ILLUSTRATION
on flasher(mode: Fon)
off flasher(mode: g, Foff)
R: TON
M2:
M1:
R: TOFF
M2:
M1:
On/t:
M2:
M1:
R: TOFF TON
R: TONTOFF TON
TOFF
M2:
M1:
On/t:
The output relay is initially de-energized andenergized after an adjustable time delay, t .off
The output relay is initially energized andde-energized after an adjustable time delay, t .on
The output relays is initially de-energized andenergized after an adjustable time delay, t , andoff
stays energized for an adjustable period, t , andon
then de-energized.
The output relays is initially energized and de-energized after an adjustable time delay, t , andon
stays de-energized for an adjustable period, t ,off
and then energized. This loop is repeated untilthe device is powered off. “On/t” led flashes at Fonand Foff mode for “T1-M4” product.
The output relay is initially de-energized andenergized after an adjustable time delay, t , andoff
stays energized for an adjustable period, t , andon
then de-energized. This loop is repeated until thedevice is powered off. “On/t” led flashes at Fonand Foff mode for “T1-M4” product.
on delay with control input(mode: c)
The output relay is initially de-energized. A contactclosure on T contact triggers an adjustable timedelay, t, which energizes the output relay whenexpired. The output relay stays energized as longas the T contact is active. Delay time, t, is clearedwhen the contact on T contact opens.
off delay with control input(mode: d)
The output relay is initially de-energized andenergized when a contact closure on T contact isdetected. A contact release on T contact triggersan adjustable time delay, t, which de-energizes theoutput relay when expired. Reclosure of the contacton T contact before the time delay is expired restartstime delay, t, and keeps the output relay energized.
rising edge triggered off delay(mode: e)
The output relay is initially de-energized. A contactclosure on T contact both energizes the outputrelay and triggers an adjustable time delay, t, whichde-energizes the output relay when expired.During the time delay, T contact is insensitive tostate changes and becomes sensitive when timedelay, t, expired.
falling edgetriggered off delay(mode: f)
The output relay is initially de-energized. A statechange of the contact on T contact from closed toopen both energizes the output relay and triggersan adjustable time delay, t, which de-energizesthe output relay when expired. During the timedelay, T contact is insensitive to state changesand becomes sensitive when time delay, t, expired.
on and off delaywith control input(mode: h)
The output relay is initially de-energized. A contactclosure on T contact triggers an adjustable timedelay, t, which energizes the output relay whenexpired. Similarly contact release of T contacttriggers the time delay, t, which de-energizes theoutput relay when expired. Delay time, t, is clearedwhen the contact state of T contact changes.
adjustable pulseoutput with control input(mode: i)
The output relay is initially de-energized. A statechange on T contact both energizes the outputrelay and triggers an adjustable time delay, t,which de-energizes the output relay when expired.During the time delay, T contact is insensitive tostate changes and becomes sensitive when timedelay, t, expired.
on delaywith memory(mode: k)
The output relay is initially de-energized. If Tcontact is open, adjustable time delay, t, countsdown and output relay energizes when t is expired.Any contact closure on T contact pauses the countdown process, and the process continues when thecontact release on T contact occurs. A contactrelease is needed to restart the cycle, after theoutput relay is energized.
R: TONTOFFTOFF
M2:
M1:
On/t:
On/t:
On/t:
R:
M1:
M2:
T: < tt
On/t:
R:
M1:
M2:
T: < ttOn/t:
R:
M1:
M2:
T:
tt
On/t:
R:
M1:
M2:
T:
tt
On/t:
R:
M1:
M2:
T:
t tt
On/t:
R:
M1:
M2:
T:t
t <t
On/t:
R:
M1:M2:
T: t1
t=t +t +t1 2 3
t2 t3 t1On/t:
Timers
type order no270 350
270 351
T1-60S
T1-FLASH
T1-M5 270 353
modetime
range1 .. 60sec
0.1sec .. 10days
0.1sec .. 10days
T1-K 270 3540.1sec .. 10days
ND
a,b,c,d,e,f,g,h,i,k
ND,FD,NFD,Fon,Foff
Foff
controlinput
T1-M4 270 3551sec .. 10daysND,FD,Fon,Foff
270 359T1-100S 1 .. 100secND
31mm
53.6mm
66.5mm
45mm
68.5mm
90.4mm
90.4mm
17.5mm
Warning : If adjustments are accomplished after Timer is turned on, operator should powerdown the device, wait at least 0.3 seconds and power up the device.
270 363T1-30S 1 .. 30secND
270 352T1-60S2 1 .. 60secND
1 32
U2 U1
24..300V ac/dc+-
T
T1-K
T
1 32
U2 U1
24..300V ac/dc
T1-M5, T1-FLASH, T1-M4, T1-60S T1-100S, T1-30S
1 32
U1 U3
24V ac/dc
U2
1 32
U2 U1
24..300V ac/dc
T1-60S2
4 65
Revision
No:
080
3201
7