Transcript
Page 1: Timers - Klemsan SERIES_M5_60S...an adjustable time delay, t, which de-energizes the output relay when expired. Reclosure of the contact on T contact before the time delay is expired

Operating voltage 24 .. 300V AC/DC24V AC/DC or 180..265V AC (T1-100S, T1-30S)

Output contact 1 C/O

Protection class IP20

Storage temperature -40°C .. 75°C

Connection Rail mounted

Maximum switching current 10A

Operating temperature -20°C .. 60°C

Maximum switching voltage 250V AC

Maximum switching power 1250VA

Time range :(T1-M4)

time range : 1 .. 60 seconds (T1-60S, T1-60S2)1 .. 100 seconds (T1-100S)1 .. 30 seconds (T1-30S)

t, t , t timer :on off (time range) x (multiplier value)

87654321

modetontoff

ON (1)

OFF (0)

mode (7,8)

00011011

on delayoff delayon flasheroff flasher:

:::

t (4,5,6), t (1,2,3) on off

000001010011

10 seconds30 seconds100 seconds10 minutes:

:::

100101110111

60 minutes10 hours100 hours10 days:

:::

Adjustment values1s10s100s1m10m

: 1 second: 10 seconds: 100 seconds: 1 minute: 10 minutes

1h10h100h1d10d

: 1 hour: 10 hours: 100 hours: 1 day: 10 days

Time range :(T1-M5,

T1-FLASH, T1-K)10

1

1

1

1100

10

10100 10

s

m

hd

0.4

0.6

0.8 1

0.2

t , t multiplier value :on off(T1-M5, T1-FLASH)

0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.80.9 - 1

t multiplier value :(T1-K)

0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.80.9 - 1

OPERATION MODE

on delay(mode: a, ND)

off delay(mode: b, FD)

on-offdelay(mode: NFD)

FUNCTION STATEMENTFUNCTION ILLUSTRATION

on flasher(mode: Fon)

off flasher(mode: g, Foff)

R: TON

M2:

M1:

R: TOFF

M2:

M1:

On/t:

M2:

M1:

R: TOFF TON

R: TONTOFF TON

TOFF

M2:

M1:

On/t:

The output relay is initially de-energized andenergized after an adjustable time delay, t .off

The output relay is initially energized andde-energized after an adjustable time delay, t .on

The output relays is initially de-energized andenergized after an adjustable time delay, t , andoff

stays energized for an adjustable period, t , andon

then de-energized.

The output relays is initially energized and de-energized after an adjustable time delay, t , andon

stays de-energized for an adjustable period, t ,off

and then energized. This loop is repeated untilthe device is powered off. “On/t” led flashes at Fonand Foff mode for “T1-M4” product.

The output relay is initially de-energized andenergized after an adjustable time delay, t , andoff

stays energized for an adjustable period, t , andon

then de-energized. This loop is repeated until thedevice is powered off. “On/t” led flashes at Fonand Foff mode for “T1-M4” product.

on delay with control input(mode: c)

The output relay is initially de-energized. A contactclosure on T contact triggers an adjustable timedelay, t, which energizes the output relay whenexpired. The output relay stays energized as longas the T contact is active. Delay time, t, is clearedwhen the contact on T contact opens.

off delay with control input(mode: d)

The output relay is initially de-energized andenergized when a contact closure on T contact isdetected. A contact release on T contact triggersan adjustable time delay, t, which de-energizes theoutput relay when expired. Reclosure of the contacton T contact before the time delay is expired restartstime delay, t, and keeps the output relay energized.

rising edge triggered off delay(mode: e)

The output relay is initially de-energized. A contactclosure on T contact both energizes the outputrelay and triggers an adjustable time delay, t, whichde-energizes the output relay when expired.During the time delay, T contact is insensitive tostate changes and becomes sensitive when timedelay, t, expired.

falling edgetriggered off delay(mode: f)

The output relay is initially de-energized. A statechange of the contact on T contact from closed toopen both energizes the output relay and triggersan adjustable time delay, t, which de-energizesthe output relay when expired. During the timedelay, T contact is insensitive to state changesand becomes sensitive when time delay, t, expired.

on and off delaywith control input(mode: h)

The output relay is initially de-energized. A contactclosure on T contact triggers an adjustable timedelay, t, which energizes the output relay whenexpired. Similarly contact release of T contacttriggers the time delay, t, which de-energizes theoutput relay when expired. Delay time, t, is clearedwhen the contact state of T contact changes.

adjustable pulseoutput with control input(mode: i)

The output relay is initially de-energized. A statechange on T contact both energizes the outputrelay and triggers an adjustable time delay, t,which de-energizes the output relay when expired.During the time delay, T contact is insensitive tostate changes and becomes sensitive when timedelay, t, expired.

on delaywith memory(mode: k)

The output relay is initially de-energized. If Tcontact is open, adjustable time delay, t, countsdown and output relay energizes when t is expired.Any contact closure on T contact pauses the countdown process, and the process continues when thecontact release on T contact occurs. A contactrelease is needed to restart the cycle, after theoutput relay is energized.

R: TONTOFFTOFF

M2:

M1:

On/t:

On/t:

On/t:

R:

M1:

M2:

T: < tt

On/t:

R:

M1:

M2:

T: < ttOn/t:

R:

M1:

M2:

T:

tt

On/t:

R:

M1:

M2:

T:

tt

On/t:

R:

M1:

M2:

T:

t tt

On/t:

R:

M1:

M2:

T:t

t <t

On/t:

R:

M1:M2:

T: t1

t=t +t +t1 2 3

t2 t3 t1On/t:

Timers

type order no270 350

270 351

T1-60S

T1-FLASH

T1-M5 270 353

modetime

range1 .. 60sec

0.1sec .. 10days

0.1sec .. 10days

T1-K 270 3540.1sec .. 10days

ND

a,b,c,d,e,f,g,h,i,k

ND,FD,NFD,Fon,Foff

Foff

controlinput

T1-M4 270 3551sec .. 10daysND,FD,Fon,Foff

270 359T1-100S 1 .. 100secND

31mm

53.6mm

66.5mm

45mm

68.5mm

90.4mm

90.4mm

17.5mm

Warning : If adjustments are accomplished after Timer is turned on, operator should powerdown the device, wait at least 0.3 seconds and power up the device.

270 363T1-30S 1 .. 30secND

270 352T1-60S2 1 .. 60secND

1 32

U2 U1

24..300V ac/dc+-

T

T1-K

T

1 32

U2 U1

24..300V ac/dc

T1-M5, T1-FLASH, T1-M4, T1-60S T1-100S, T1-30S

1 32

U1 U3

24V ac/dc

U2

1 32

U2 U1

24..300V ac/dc

T1-60S2

4 65

Revision

No:

080

3201

7