Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-2A OSA Ventilation Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 2: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/2.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-3A Pkg. CAV, Unitary AC Control Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 3: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/3.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-4A Air Distribution System Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 4: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/4.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-5A Air Economizer Controls Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 5: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/5.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-6A Demand Controlled Ventilation Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 6: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/6.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-7A Supply Fan Variable Flow Control Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 7: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/7.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-8A Valve Leakage Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 8: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/8.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-9A Supply Water Temperature Reset Controls Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 9: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/9.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-10A Hydronic System Variable Flow Control Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 10: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/10.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-11A Automatic Demand Shed Control Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 11: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/11.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-12A Automatic Fault Detection Diagnostics (FDD) For Packaged Direct-Expansion (DX) Units Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 12: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/12.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-13A Automatic Fault Detection Diagnostics (FDD) for Air Handler Units and Zone Terminal Units Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 13: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/13.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-14A Distribution Energy Storage DX AC Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 14: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/14.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-15A Thermal Energy Storage (TES) System Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 15: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/15.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-16A Supply Air Temperature Reset Controls Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 16: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/16.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-17A Condenser Water Temperature Reset Controls Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.
![Page 17: Title 24 Compliant · Acceptance Form per NITC and the California State Pipe Trades Council. Title 24 Acceptance Test Technician Lab/Hands-on Task Form Lab Work Performed (Mech Form)](https://reader033.vdocument.in/reader033/viewer/2022050100/5f6ff4b9dae0c1523f48fec6/html5/thumbnails/17.jpg)
Title 24 Compliant
Title 24 Acceptance Test Technician Lab/Hands-on Task Form
Lab Work Performed (Mech Form) Mech-18A Energy Management Control System Acceptance
Student Name ______________________________________________________
Student Signature ____________________________________________________
Date of Lab Exam ____________________________________________________
Instructors Name ____________________________________________________
Instructor Signature __________________________________________________
Date Witnessed ______________________________________________
The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.