Three-phase UPS DELPHYS MX
from 250 to 900 kVAthe Mega Power protection up to 5.4 MVA
DELPHYS MX range is capable of a maximum system size of up to 5.4 MVA and specifically designed for demanding Data centre applications such as large DTC of banks / insurances, IDC, Telecom
datacentres, semiconductor production lines and big automation manufactures, airports, big air traffic control centres, tunnels.DELPHYS MX, is a true-online “double conversion” UPS system which protects
the load from power grid pollution or power failure, from utility power supply and diesel generators.
> Data center> Industry> Telecommunications> Processes
Your protection for
De
fyS
176
A
FlywheelCOMPLIANT
B U R E A UV E R I T A S
DELPHYS MX series is attested by Bureau Veritas.
61
Three-phase UPS DELPHYS MX
from 250 to 900 kVA
• Parallel system with modular units.• Powerful central bypass for power extension
or redundancy.• Tier 3 and Tier 4 compatible.• Designed for optimal use with STS in
downstream network.
Easy to Service and Maintain
• Specially designed graphic touch screen for easy and ergonomic operation.
• 7 com-slots plug-in communication interfaces for upgrading your operating requirements.
• easy remote monitoring via web browser or via customer’s supervision systems (web, intranet, extranet…).
• Very open connectivity (Modbus / Jbus, Jbus tunnelling, LAN…).
• front accessibility for all components.• Reduced MTTR thanks to extractible power
bridges or fans on “cassette”.
User-friendly operation and remote communication
Flexible architecture
• Internal fault tolerant architecture with internal redundancies and fan failure localisation.
• Intelligent embedded battery monitoring with failed block localisation and preventative remote alarm.
• Able to withstand an output short circuit and overload, ensuring the systems safety under extreme conditions.
• Reliable and robust paralleling mode.• Multisystem automatic cross synchronisation
(ACS) for an optimised use with STS.• Output isolation transformer to reduce
the influence of N-GND (Neutral Line-to-Ground) voltage and load harmonic current on UPS inverter.
• Minimised running costs, by: - Very high efficiency of up to 93.5 %
(lower energy dissipation and cooling costs) equals energy saving in full on line conversion,
- ‘energy saver’ on-line mode allows the number of running units of the system to adapt automatically to the real load,
- free cooling compatible to save cooling costs.
• Valuable space saving with its reduced footprint and exceptional high power density (the most compact unit of its class): 900 kVA in less than 3.2 meters (width) per unit including the by-pass. DELPHYS MX units can also be installed without side or rear access (dependant on requirements).
• Lower infrastructure installation costs benefit from PfC “clean input” rectifier (without filters) with a lasting high input power factor whatever the operation conditions. It means lower input current, in comparison with traditional UPS, therefore no need to oversize upstream transformers or generator sets.
• Intelligent built-in battery monitoring system interacts with “charging mode” to prolong battery lifetime (reduced battery stress thanks to a very low ripple current). The independent charger permanently isolates the batteries from the inverter DC bus in normal mode.
• Designed to match latest IT load requirement.
• Leading power factor load compatible without derating.
High reliability and availability Lower Total Cost of Ownership
AP
PLI
406
A
62
Three-phase UPS DELPHYS MX
from 250 to 900 kVA
Fault tolerant architecture
DELPHYS MX integrates internal redundancy that ensures permanent power supply even during system failure:• redundant ventilation system,• ring bus synchronisation,• no single point of failure since the
synchronisation bus uses a fault tolerant token ring topology that accepts an accidental opening of the synchronisation loop, without UPS malfunctioning or load losses and an alarm is given to the operator at the first fault.
• “Cascade failure” protection function eliminates fault propagation downstream of a module in parallel system when configured with central bypass,
• internal or external “backfeed” protection eliminates any risk of energy feedback upstream of the UPS,
• hardware and software watchdog ensures that the power supplied to applications is secure in case of a circuit and control software fault,
• redundancy of the power supplied to the electronics, locating ventilation faults, preventative detection of faults on a battery component on request.
Protecting your battery investment
EBS (expert Battery System) technology significantly prolongs the battery life:• charge according to an algorithm which
adapts to the environment and the condition of the battery,
• eliminates overloading effects due to permanent floating, which accelerates the corrosion of the positive plates and causes the separators to dry out,
• isolation of the DC battery bus, (independent charger function). Premature ageing, caused by residual ripple from the inverter bridge is eliminated.
Guaranteed battery availability
• the battery and DC circuit are regularly tested automatically and the operator is notified of their condition,
• Available as option, BHC Interactive (Battery Health Check), a battery monitoring system that provides permanent monitoring of the battery system, simplifies maintenance (either preventative or curative) and optimises battery lifetime.
Interacting proactively with the battery charger recharging system (EBS), it optimises battery capacity, increases charger precision, performs automatic battery testing and automatic procedure to recover a block when becoming weaken before it is totally unusable.
DELPHYS MX ensures your power supply is of the utmost quality by using Space Vector Modulation (SVM) digital regulation:• perfectly sinusoidal output voltage THDV < 2 % with linear loads and < 3 % with non-linear loads,
• output voltage precision even when load is completely unbalanced between phases,
• an immediate response to major variations in load, without deviating the output voltage (± 2% in less than 5 ms),
• a very high short circuit capacity up to 4 In (Ph / N) allows selectivity.
Components and power bridges (integrating the latest high performance IGBT) enable the supply:• non-linear loads with high crest factor up
to 3,• loads with a leading power factor up to
0.9 lagging without de-rating of the active power (900 kVA / 800 kW).
The voltage you require: whatever the load
De
fyS
153
A G
B
Without derating
cos ϕ 0,9
0,25
0,50
0,75
1
cos ϕ 1100% kW
kW
-1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1
cos ϕ 0,9 cos ϕ 0,9cos ϕ 0,9
0,25
0,50
0,75
1
cos ϕ 1100% kW
kVAr
kWLEADINGLEADING LAGGINGLAGGING
Without derating
100% kva
100% kVA
H5 H7 H11 H13 H17 H19
Traditional three-phase rectifier with thyristor
12 pulse rectifier
Low distortion rectifier DELPHYS MX
HARMONICS
THDI %
28 %
1 %
8 %7 %
9 %
5 % 6 %
3,2 % 2,5 %4,7 %
2 %
DELPHYS MX guarantees total compatibility with your low voltage electrical power supply system and, in particular, with generating sets:• sinusoidal current at rectifier THDI input:
4.5 % without filter,• increased power factor upstream of the
rectifier: 0.93 without filter, reducing the current consumed, and therefore the size of cables and protective devices,
• gradual, sequential start-up of the rectifiers in parallel, facilitating take up by the generating set,
• delayed battery recharge when running on generating set to reduce power consumption.
Integration into your electrical network: a “clean” and economical rectifier
UPSDELPHYS Green Power V
I
T°
GR
ee
N 0
66 A
De
fyS
171
A G
B
63
Three-phase UPS DELPHYS MX
from 250 to 900 kVA
AutomaticBypass
MaintenanceBypass
Rectifier
Charger
Inverter
Battery
Q4
Q5
Q3
Q20
Q1
Double conversion architecture
De
fyS
088
B G
B
Parallel architectures
STS 3
STS 1
STS 2
Load 1
Load 2
Load 3
DELPHYS MX
DELPHYS MX
To fulfil the most demanwding needs for power supply availability, for flexibility and for the installation to be upgraded.
• DELPHYS MX modular, growth without constraints (up to 6).
De
fyS
167
A
• DELPHYS MX centralised bypass, programmed growth.
De
fyS
168
B
• DELPHYS MX double bypass, for easier operation.
De
fyS
169
A
• DELPHYS MX with Stat ic Transfer Systems: IT SWITCH and STATYS to provide security as close to the applications as possible.
De
fyS
180
A G
B
De
fyS
093
AD
efy
S 0
94 A
De
fyS
059
B
64
Three-phase UPS DELPHYS MX
from 250 to 900 kVA
De
fyS
111
A G
B
Graphic display
Design adapted to the user: control panel with LeDs and LCD display.
Graphic touch screen (GTS)
The operator has access to the control functions with only a few intuitive touches of the screen.
Quick access to each installation module
Direct access zones to sub-unit menus
Status bar
Help menu for correct operation
UPS load rate (bar graph)
Access to installation mimic panel
De
fyS
102
A
Operating mode icons
Preventative maintenance request
Communication options
• Remote access panel.• ADC (Advanced Dry Contacts) data input
and output by dry contacts.• RS232, RS422, RS485 serial connection
JBUS / MODBUS, PROfIBUS.• MODBUS TCP interface (JBUS / MODBUS
tunneling).• NET VISION ethernet Network interface
(http web pages, email, SNMP, servers shutdown).
• Alarm notification via SMS.
Standard equipment
• Slots for 7 communication cards.• Backfeed protection: detection circuit.• Standard interface - 3 inputs (emergency stop, generating
set, battery protection) - 4 outputs (general alarm, back-up, bypass,
preventative maintenance needs).• EBS (expert Battery System).
Accessories
• BHC Interactive battery monitoring system.• Graphic touch screen.• ACS function for synchronisation with an
external source.• Reinforced IP protection degree.• Ventilation filters.• Ventilation control.
Remote maintenance
• T.SERVICE for continuous 24/7 monitoring via the SOCOMEC UPS maintenance service.
65
Three-phase UPS DELPHYS MX
from 250 to 900 kVA
UPS and batteries
A compact and integrated system.
De
fyS
181
A G
B
1930
845W2
Technical data
Sn [kVA] 250 300 400 500 800 900Pn [kW] 225 270 360 450 720 800RECTIFIER INPUTRated input voltage(1) 380/400/415 Vac
Voltage tolerance 340 to 460 V 360 to 460 VRated input frequency 50/60 HzFrequency tolerance ± 5 HzInput current distortion THDI at rated input current < 4.5% < 5%Input power factor 0.93 0.94
OUTPUTRated output voltage 380/400/415 VNominal output frequency 50/60 HzOutput frequency tolerance ± 0.2%Total output voltage distortion - linear load < 2%Total output voltage distortion - reference non-linear load (lEC 62043-3) < 4% < 3%
Short-circuit capability - 3.5 In 100 msOverload capabilìty 125% 10 min - 150% 1 minOutput power factor without derating in kVA or kW 0.9 lagging to 0.9 leading
BYPASSRated input voltage 380/400/415 VInput voltage tolerance ± 10%Rated input frequency 50/60 Hzlnput frequency tolerance ± 2 Hz (0.2 Hz to 4 Hz settable)
EFICIENCYNormal mode up to 93.5%ECO-MODE 98%
ENVIRONMENTAmbient storage temperature -20 °C to +70 °CAmbient service temperature 25 °C (recommended) ; 0 to 35 °C without deratingAltitude ≤ 1000 m without deratingRelative humidity range 95% max without condensationAcoustic noise at 1 m (ISO 3746)(2) ≤ 70 dBA ≤ 72 dBA ≤ 75 dBA
UPS CABINETDimensions (W x D x H) (mm) 1600 x 995 x 1930 3200 x 995 x 2210Weight (kg) 2300 2650 3000 5900Degree of protection (IEC 60529) IP20 standard
STANDARD COMPLIANCESafety IEC 62040-1; EN 62040-1; IEC 60950-1EMC IEC 62040-2; EN 62040-2Performance and test IEC 62040-3
Product comformity CE
(1) DELPHYS MX 250-500: three-phase 220-230-240 V on demand. (2) As per power range.
UPS Battery for back-up time Battery for back-up time Battery for back-up time5 minutes 10 minutes 15 minutes
UPS power Width Weight W2 Weight W2 Weight W2kVA / kW mm kg mm kg mm kg mm250 / 225 1600 - - 3670 2400 3770 2400300 / 270 1600 - - 3670 2400 4600 3200400 / 360 1600 - - 4890 3200 6110 4000500 / 450 1600 - - 5560 3200 7115 4800800 / 720 3200 7565 4800 9640 5000 - -900 / 800 3200 8735 4800 11568 6000 - -
De
fyS
087
A G
B
Central bypass cabinet
Coupling cabinet including the central static switch and the maintenance bypass.
1930
DWD
efy
S 0
86 A
GB
Power(1)
kVAW
mmD
mmWeight
kg300 600 800 270400 600 800 300600 1000 800 420800 1000 800 4501200 1200 800 6002000 2600 1200 21002400 4000 1245 N/D3200 5800 1245 N/D
(1) For other power ranges, please contact us.
Bypass transformer
for galvanic isolation.
1930
800W
Power(1)
kVAW
mmWeight
kg300 1000 800400 1200 1000500 1200 1500600 1200 1800800 1200 20001000 1200 25001200 1600 2700
(1) For other power ranges, please contact us.