Power Quality Disturbances
• Voltage Sag • Voltage Swell• Interruptions
• -----------------• Aditi Kanjolia• 1200202
![Page 2: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/2.jpg)
These three are categorised on the basis of duration-
Short –duration rms variations Long-duration rms variations
Categorisation based on duration
![Page 3: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/3.jpg)
Short –duration rms variations ( < 1 min)
Long-duration rms variations--sustained interruptions ( > 1 min)
![Page 4: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/4.jpg)
One of the most common power quality problems.
A sag is a decrease in rms voltage to between 0.1 pu and 0.9 pu for durations from 0.5 cycles to 1 min.
Sag durations are subdivided into three categories (instantaneous, momentary, and temporary)
Voltage Sag
![Page 5: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/5.jpg)
Sag+harmonic+ Transient
Sag+Harmonic+Flicker
Swell+harmonic+ Transient
Swell+Harmonic+Flicker
Sag+Flicker+
Transient
Swell+Flicker+ Transient
Harmonic+Inter-harmonic
Flicker+ Transient+Harmonic
Combination 3Disturbances
![Page 6: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/6.jpg)
Sag
SwellTransient
Flicker
Notch
Spike
Harmonics
Interrupt
Single Disturbances
![Page 7: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/7.jpg)
Interrupt+Transient
Swell+Flicker
Sag+Harmonic
Sag+Flicker
Sag+Transient
Swell+Harmonic
Swell+Transient
Transient+Harmonic
Combination of 2Disturbances
![Page 8: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/8.jpg)
Fig- Instantaneous voltage sag – SLG fault
![Page 9: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/9.jpg)
Depth / Magnitude Duration Overshoot after sag Phase Angle Jump – voltage is afterall
complex. Not generally a problem but matters when we are considering power electronics converters for eg.
During-sag voltage contains a rather large amount of higher frequency components.
Characteristics
![Page 10: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/10.jpg)
usually associated with system faults like short -circuits
switching heavy loads or starting large motors
A fault on a parallel feeder circuit will result in a voltage drop at the substation bus, which affects all of the other feeders until the fault is cleared
Bad Weather – thunderstorms and lightning.
Causes of Voltage Sags
![Page 11: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/11.jpg)
Fig- Voltage Sag
Fig – In terms of rms voltage
![Page 12: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/12.jpg)
Single Phase Sags > 70 % cases lightning strikes, tree branches, animal contact etc
Phase to Phase Sags – like earlier but The two phase voltage sag will typically appear on other feeders from the same substation.
3 Phase Sags- < 20% either by switching or tripping of a 3 phase circuit breaker, switch or recloser which will create a 3 phase voltage sag on other lines fed from the same substation
also be caused by starting large motors
Another classification :Multi Phase Sags and Single Phase Sags
![Page 13: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/13.jpg)
Occurence Utility Systems-
o @ transmission systems - due to lighting , construction or transportation accidents.
o @ distribution systems -Similar to the transmission system causes, weather (lightning, wind, ice), animal
contact, contamination of insulators, construction accidents, motor vehicle accidents, falling or contact with tree limbs can result in voltage sags
At facility ( consumer level )- These sags are typically caused by starting large motors or by electrical faults inside the facility.
![Page 14: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/14.jpg)
Affects several equipments like adjustable- speed drives, process-control equipment and computers are notorious for their sensitivity
Computer lockups, Even relays and contactors in motor starters
On Production - Both single phase and multiphase voltage sags can cause unplanned production stoppages.
Single phase - control devices and electronic sensors can be very vulnerable to voltage sags.
Impact
![Page 15: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/15.jpg)
Voltage Swell A swell is an increase in rms voltage above
1.1 pu to 1.8 pu for durations from 0.5 cycle to 1 min. Typical Magnitudes are between 1.1 pu and 1.2 pu.
Less frequent then sags, but more damaging. Are gradual, accumulative and hence noticeable.
Sag for about > 3 sec – light output affected.
![Page 16: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/16.jpg)
Figure Rms variations and instantaneous values
![Page 17: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/17.jpg)
System faults Swells can also be caused by switching off a
large load, load shedding, or switching on a large capacitor bank. Due to single – phase to ground fault in
ungrounded condn
Causes
![Page 18: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/18.jpg)
breakdown of components on the power supplies of the equipment due to over voltage
The increase in output from incandescent lighting may be noticeable, if the duration is longer than three cycles.
Impacts
![Page 19: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/19.jpg)
-Origin of Long & Short interruption - Influence on various equipments
Interruptions- Long And Short
![Page 20: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/20.jpg)
Only duration is measured since the voltage magnitude is always less than 10% of nominal.
Fig-Momentary interruption due to fault and subsequent recloser operation
![Page 21: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/21.jpg)
Short duration variations
Momentary Interruption < 1 min , <0.1 puTemporary Interruption < 1 min , <0.1 pu
Long duration variations
Interruption, sustained > 1 min , 0.0 pu
Classifications
![Page 22: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/22.jpg)
Interruption time = time of power supply return – moment of interrution
Interrruption frequency = number of interruption/ reference time
Relative amplitude
Parameters of Interruptions
![Page 23: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/23.jpg)
Can be scheduled or accidental.
-scheduled, the customers are announced before doing any programmed actions into the distribution Network
-accidentals – power system faults – equipment failures – control system malfunctions–.
Causes / Origin
![Page 24: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/24.jpg)
Duration of the interruption depends on the reclosing capability of the protective device.
The duration of an interruption can be irregular due to equipment malfunctions or loose connections.
Eg- Delayed reclosing of the protective device may cause a momentary or temporary interruption whereas Instantaneous reclosing generally will limit the interruption caused by a nonpermanent fault to less than 30 cycles.
Duration of Interruption
![Page 25: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/25.jpg)
In an industrial environment, disruption in production by increasing the number of reject or material wastage, adding to substantial additional costs.
Impacts
Stoppage of sensitive equipment (i.e. computers, PLC, ASD)
Unnecessary tripping of protective devices Loss of data Malfunction of data processing equipment.
![Page 26: Volatge variation disturbances in power quality](https://reader036.vdocument.in/reader036/viewer/2022081520/5695d18c1a28ab9b0296f8c7/html5/thumbnails/26.jpg)