DP Flow Engineering Guide Figure 1.1.a - The modern DP flowmeter. Chapter 1 - DP Flow 1.1 Introduction to DP Flow Differential pressure flow measurement (DP Flow) is one of the most common technologies for measuring flow in a closed pipe. There are many reasons for the wide usage of DP Flow technology. Its technology is based on well-known laws of physics, particularly around fluid dynamics and mass transport phenomena Its long history of use has also led to the development of standards for manufacture and use of DP flowmeters Manufacturers offer a large catalog of both general and application-specific instrumentation and installation choices DP Flow technologies achieve high accuracy and repeatability Video 1.1.a - How DP Flow Works

Upload: hadiep

Post on 22-Jun-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • DP Flow Engineering Guide

    Figure 1.1.a - The modern DP flowmeter.

    Chapter 1 - DP Flow

    1.1 Introduction to DP Flow

    Differential pressure flow measurement (DP Flow) is one of the most common

    technologies for measuring flow in a closed pipe.

    There are many reasons for the wide usage of DP Flow technology.

    Its technology is based on well-known laws of physics, particularly around

    fluid dynamics and mass transport phenomena

    Its long history of use has also led to the development of standards for

    manufacture and use of DP flowmeters

    Manufacturers offer a large catalog of both general and application-specific

    instrumentation and installation choices

    DP Flow technologies achieve high accuracy and repeatability

    Video 1.1.a - How DP Flow Works

    http://www2.emersonprocess.com/en-us/http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/Documents/00805-0100-1041.pdfhttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/3051sfc-hotspot-HD.pnghttp://go.emersonprocess.com/rosemount_rfq_enhttp://www2.emersonprocess.com/en-us/brands/rosemount/contact-us/pages/index.aspxhttp://bcove.me/dzih9ieohttp://bcove.me/dzih9ieohttp://videos.emersonprocess.com/detail/videos/english/video/3867778000001/how-differential-pressure-flow-works?_ga=2.123277645.73388554.1505839306-1694579551.1435777553

  • 1.2 History of DP Flow

    Flow measurement began thousands of years ago as the Egyptians began to make approximate predictions of harvests based on the

    relative level of spring floods of the Nile River. Romans later engineered aqueducts to provide water in cities for sustenance and the need

    to monitor steady flow became important. Operators used flow through an orifice or the welling of water over obstructions to roughly gauge

    flow rates. Marks on the walls of the flow stream, strength of the stream through an orifice, etc. gave a rough measurement of the flow

    rates. Newton's discovery of the law of gravitation in 1687 enabled physicists and mathematicians to formulate theories around motion and

    force, which ultimately lead to the development of the ability to quantify flow rates.

    The Bernoulli PrincipleDaniel Bernoulli was a Swiss mathematician who studied hydrodynamics. His work centered on the conservation of energy and provided

    the first key breakthrough in the development of flow measurement technology. He developed the Bernoulli principle which states that the

    sum of all energy in the flow must remain constant regardless of conditions. Specifically for DP Flow, this means that the sum of the static

    energy (pressure), kinetic energy (velocity), and potential energy (elevation) upstream equals the static, kinetic, and potential energy

    downstream.

    Reynolds Number Osbourne Reynolds was not a student of physics but rather one of mechanics, and is most famous for his study of fluid flow through a

    pipe, specifically the conditions under which the flow transitions from laminar flow to turbulent flow. The Reynolds number is a numeric

    quantification of the internal forces over the viscous forces. In short it describes the flowing characteristics of a fluid. Reynolds number is a

    key concept for designing flowmeters and is used as a constraint on the range of a flowmeter's applicability.

    1.3 Pressure

    What is pressure? Pressure is the amount of force applied over a defined area (Equation 1.1).

    Pressure increases with increasing force or decreasing area

    Pressure decreases with decreasing force or increasing area

    Measuring pressure helps prevents over pressuring of equipment that may result in damage

    Measuring pressure helps prevent unplanned pressure or process release that may cause injury

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/reynoldsformula.gifhttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/reynoldsformula.gifhttp://www2.emersonprocess.com/en-US/brands/rosemount/Pressure/DP-Flow-Products/Pages/index.aspx

  • Why Measure Pressure?The most common reasons that the process industry measures pressure are:

    Figure 1.3.a - A multivariable flowmeterfor more acurate processmeasurements.

    Safety

    Process efficiency

    Cost savings

    Measurement of other process variables

    Safety: Pressure measurement helps prevent overpressurization of pipes, tanks, valves,flanges, and other equipment, minimizes equipment damage, controls levels and flows, and

    helps prevent unplanned pressure or process release or personal injury.

    Process Efficiency: In most cases, process efficiency is highest when pressures (and otherprocess variables) are maintained at specific values or within a narrow range of values.

    Cost Savings: Pressure or vacuum equipment (e.g., pumps and compressors) usesconsiderable energy. Pressure optimization can save money by reducing energy costs.

    Measurement of Other Process Variables: Pressure is used to measure numerous processes. Pressure transmitters arefrequently used in a number of applications, including:

    Flow rates through a pipe

    Level of fluid in a tank

    Density of a substance

    Liquid interface measurement

    1.4 DP Flow 101

    Flow theory is the study of fluids in motion. A fluid is defined as any substance that can flow, and thus the term applies to both liquids and

    gases. Precise measurement and control of fluid flow through pipes requires in-depth technical understanding, and is extremely important

    in almost all process industries.

    Key Factors of Flow Through PipesThere are 6 factors that are key to understanding pipe flow:

    1. Physical piping configuration

    2. Fluid velocity

    3. Friction of the fluid along the walls of the pipe

    4. Fluid density

    5. Fluid viscosity

    6. Reynolds number

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/3051Sfca-full-hotspot-hd.png

  • Piping Configuration: The diameter and cross-sectional area of the pipe enables both the determination of fluid volume for any givenlength of pipe and is included in the determination of the Reynolds number for a given application. Velocity: Depends on the pressure or

    vacuum that forces fluid through the pipe.

    Friction: Because no pipe is perfectly smooth, fluid in contact with a pipe encounters friction, resulting in a slower flow rate near the wallsof the pipe compared to at the center. The larger, smoother, or cleaner a pipe, the less effect on the flow rate.

    Density: Density affects flow rates because the more dense a fluid, the higher the pressure required to obtain a given flow rate. Becauseliquids are (for all practical purposes) incompressible and gases are compressible, different methodologies are required to measure their

    respective flow rates.

    Viscosity: Defined as the molecular friction of a fluid, viscosity affects flow rates because in general, the higher the viscosity more work isneeded to achieve the desired flow rates. Temperature affects viscosity, but not always intuitively. For example, while higher temperatures

    reduce most fluid viscosities, some fluids actually increase in viscosity above a certain temperature.

    Reynolds Number: By factoring in the relationships between the various factors in a given system, Reynolds number can be calculated todescribe the type of flow profile. This becomes important when choosing how to measure the flow within the system.

    Video 1.4.a - A visualization of flow through a pipe.

    There are three different flow profiles that are defined by different Reynolds number regimes. Laminar flow, characterized by having a

    Reynolds number below 2000, is a smooth flow in which a fluid flows in parallel layers. It usually has low fluid velocities, very little mixing,

    and sometimes high fluid viscosity. When a fluid's flow profile has a Reynolds number between 2000 and 4000, it is considered to be

    transitional. A Reynolds number above 4000 is called turbulent flow. This is characterized by high fluid velocity, low fluid viscosity, and

    rapid and complete fluid mixing.

    The best accuracy in DP Flow metering occurs with turbulent flow. This is because in turbulent flow, the point at which the fluid separates

    from the edge of the flow restriction is more predictable and consistent. This separation of the fluid creates the low pressure zone on the

    downstream side of the restriction, thus allowing that restriction to function as the primary element of a DP meter. Depending on the type

    of restriction and design of the flowmeter, the minimum pipe Reynolds number at which a specific meter should be operated can be

    considerably higher than 4000.

    http://videos.emersonprocess.com/detail/video/4283665916001/a-visualization-of-flow-through-a-pipe?autoStart=true&linkBaseURL=http%3A%2F%2Fvideos.emersonprocess.com%2Fdetail%2Fvideo%2F4283665916001%2Fa-visualization-of-flow-through-a-pipe%3FautoStart%3Dtrue

  • Flow Continuity

    When liquid flows through a pipe of varying diameter, the same volume flows at all cross sectional slices. This means that the velocity of

    flow must increase as the diameter decreases and, conversely, velocity decreases when the diameter increases. Equation 1.2 highlights

    this relationship.

    Volumetric flow equates to the volume of fluid divided by time:

    Volume can be broken down to area, A, multiplied by length, s. Volumetric flow can thus be expressed as:

    Equation 1.3 can be further simplified, since length, l, divided by time yields velocity, v. Velocity can now be substituted for the term s/t

    tielding:

    Since the volumetric flow rate is the same at all cross-sectional slices:

    Substituting Equation 1.4 into Equatation 1.5:

    Figure 1.4.a - Graphical representation of the flow law where Q1 = Q2.

  • The derivation of flow continuity above describes the basic principle of energy conservation. The Bernoulli equation, which will be covered

    in more detail in Chapter 3, builds on this principle to define the energy conservation appropriate for flowing fluid.

    The DP Flowmeter

    The primary element creates a pressure drop across the flowmeter by introducing a restriction in the pipe. This pressure drop is measured

    by the secondary element, a differential pressure transmitter. The tertiary element consists of everything else within

    the system needed to make it work, including impulse piping and connectors that route the

    upstream and downstream pressures to the transmitter.

    By creating an engineered restriction in a pipe, Bernoulli's equation can be used to calculate flow

    rate because the square root of the pressure drop across the restriction is proportional to the flow

    rate.

    There are some important cautions around DP Flow metering, including:

    1. Ensuring that impulse lines do not clog with particles or sludge

    2. Orienting impulse lines correctly (they have to be sloped to prevent gas accumulation in

    liquid applications or liquid accumulations in gas applications)

    3. Ensuring that periodic calibration does not degrade accuracy (avoided by using highly

    accurate calibration equipment)

    Primary Element Types

    There are many kinds of primary elements including those shown in Figure 1.4.c. Examples include:

    Single hole and conditioning orifice plates

    Single and multiple-port pitot tubes

    Venturi tubes

    Flow nozzles

    Cones

    Segmental wedges

    Transmitter OptionsThere are two main types of pressure transmitters used to

    calculate flow using differential pressure. The first is the traditional

    differential pressure type, which only measures differential

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/flow-law-hd.pnghttp://www2.emersonprocess.com/en-us/brands/rosemount/pressure/dpflow-capabilities/pages/betterprimaryelements.aspxhttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/integrated-dp-flowmeter-hd.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Pressure/Pressure-Transmitters/Pages/index.aspx

  • pressure, with no ancillary functionality. The second is the

    multivariable transmitter. A multivariable transmitter is a

    differential pressure transmitter that is capable of measuring a

    number of independent process variables, including differential

    pressure, static pressure, and temperature. When used as a mass flow transmitter, these independent values can be used to compensate

    for changes in density, viscosity, and other flow parameters.

    Video 1.4.b - How Multivariable Transmitters Work

    1.5 DP Flow Measurement Applications

    Product Consistency: Batch-based products depend on accurate proportions of ingredients, and DP Flow meters help ensure theaccurate delivery of liquids and gases.

    Production Efficiency: Metering and measurement of flow are part of a broad range of process control variables related to efficiency,from batch control, to by-product scavenging, to emissions monitoring.

    Process Variable Control: Processes often include multiple variable inputs. Control over these variables, including flow rates, is key toquality production.

    Safety: DP Flow helps prevent a broad range of threats to safety including overfilling, reactor control, and others.

    Internal Billing & Resource Allocation: Tighter control over inventories and process rates contributes directly to profitability. For many

    http://videos.emersonprocess.com/detail/video/3867777993001/how-multivariable-transmitters-work?autoStart=true&q=multivariable

  • sophisticated producers, internal billing around process costs directly impacts the bottom line.

    Custody Transfer: Flow metering is the cash register for products sold by volume or weight. An accurate measurement on the dispensingside accounts for every drop and on the receiving side minimizes over-charging.

    1.6 Flowmeter Installations

    Traditional Installation

    The Traditional Installation Method calls for three separate component categories shown in Figure 1.6.a.

    1. Primary element (differential pressure producer)

    2. Secondary element (transmitter)

    3. Tertiary elements (impulse lines, connecting hardware, tubing, fittings,

    valves, etc.)

    The traditional form enables component-by-component engineering to meet a wide

    variety of applications and can be engineered to meet custody transfer standards.

    Traditional installation has inherent limitations and problems. These include

    multiple potential leak points at connectors, separate/incorrect piping and

    manifolding; and accuracy problems traceable to long impulse lines. In addition,

    installation is complex, requiring long straight runs (dependent on the primary

    element used) and careful configuration of components. Much work has been

    done over the years to correct for some of these issues, and thus extend the

    usefulness and value of DP Flow installations.

    Integrated Installation

    The integrated flowmeter integrates the primary element and the transmitter into a single flowmeter assembly. It was in large part

    developed to minimize the issues around installations of the older-style traditional flowmeter. As a result, its installation requires fewer

    components and less labor than traditional flowmeter installations.

    The integrated flowmeter works much the same way as that of the traditional flowmeter. It uses the same equations, works largely with the

    same primary elements, and is available with the same transmitters (both differential pressure and multivariable).

    Benefits of the Integrated Flowmeter:

    Eliminates the need for fittings, tubing, valves, adapters, manifolds, and mounting brackets

    Fewer potential leak points (factory leak checked)

    Fewer flow measurement error sources

    Simplified ordering and installation

    Decreased susceptibility to freezing and plugging

    More compact footprint

    Rosemount integrated flowmeters combine industry leading transmitters with innovative primary element technologies and connection

    systems. There are in effect 10 devices in one flowmeter, simplifying engineering, procurement, and installation.

    Figure 1.6.b - The traditional DP Flow structure vs. the integrated multivariable DP Flow structure.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/trad-dpflow-installation-hd.png

  • DP Flow remainsthe mostcommonly usedform of flowmeasurement inthe industry.

    1.7 Alternate Flow Technologies

    Flow measurement can be performed with a broad range of technologies other than pressure-based. These include open channel,

    mechanical, ultrasonic, electromagnetic, Coriolis, optical, thermal mass, and vortex types.

    Electromagnetic flowmeters, which require an electrically-conductive fluid and a means for inducing magnetic energy to the flow, use

    electrodes to sense current induction from the magnetic flux.

    Coriolis flowmeters, as the name implies, use the Coriolis effect, which induces distortion in a

    vibrating tube.

    Optical flowmeters use photodetectors to gauge the movement of particles in an illuminated fluid

    stream.

    Vortex flowmeters use electrical pulse generators-commonly a piezoelectric crystal-to measure flow

    disturbances (vortices) around a calibrated obstruction.

    Each of the various flow measurement technologies in existence today has its ideal range of

    applications. However, thanks to its long history, its ease of use, and its immense range of

    applicability, DP Flow remains the most-commonly used form of flow measurement in industry.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/trad-dpflow-structure-hd.pnghttp://www2.emersonprocess.com/en-us/brands/daniel/flow/ultrasonics/pages/ultrasonic.aspxhttp://www2.emersonprocess.com/en-us/brands/rosemount/flow/magnetic-flowmeters/pages/index.aspxhttp://www2.emersonprocess.com/en-us/brands/micromotion/coriolis-flow-density-meters/Pages/index.aspxhttp://www2.emersonprocess.com/en-us/brands/rosemount/flow/vortex-flowmeters/pages/index.aspxhttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/Pages/index.aspxhttps://www.facebook.com/EmersonProcessManagementhttps://www.facebook.com/EmersonProcessManagementhttp://www.linkedin.com/company/emerson-process-managementhttp://www.linkedin.com/company/emerson-process-managementhttps://twitter.com/emersonprocesshttps://twitter.com/emersonprocesshttp://www.youtube.com/user/EmersonPlantWebhttp://www.youtube.com/user/EmersonPlantWebhttps://plus.google.com/108512660059325361875https://plus.google.com/108512660059325361875http://go.emersonprocess.com/MyEmerson

  • Chapter 2 - Fluid Basics

    2.1 Introduction

    To understand the theory of measuring flow, a basic knowledge of the fundamentals is required.

    A fluid is a substance that continues to deform when subjected to a shear stress. Fluids can be liquids, vapors, or gases. For most fluids,

    some of their properties can be calculated by knowing other properties.

    There are five key fluid properties that must be known to properly size and use a DP flowmeter:

    1. Density or specific weight

    2. Static pressure

    3. Temperature

    4. Viscosity

    5. Isentropic exponent

    These properties factor into DP Flow calculations.

    2.2 Force, Mass and Weight

    Flowmeters use the concept of energy conservation to determine the rate of flow in a pipe by measuring a physical difference in

    pressures.

    http://www2.emersonprocess.com/en-us/http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/fluids_basics_concepts.pdfhttp://go.emersonprocess.com/rosemount_rfq_enhttp://www2.emersonprocess.com/en-us/brands/rosemount/contact-us/pages/index.aspx

  • To convert mass in motion to force, Newtons second law of motion is used.

    The SI unit of force is the Newton, N. It is the amount of force needed to move a kg mass at an acceleration of 1/s. The US unit of force is

    the pound force, lbf, it is the amount of force needed to move a 1 pound mass one foot at an acceleration of 32.174 ft/s.

    2.3 Density

    The density of a fluid is its mass per unit volume. Note that for the same quantity of mass, the volume occupied by that mass will vary with

    temperature and pressure. Fluctuations in density due to changes in temperature and pressure are typically small for liquids but are much

    greater for gases. Fluids whose densities change very little with moderate temperature and pressure fluctuations are considered

    incompressible. If the density changes significantly with varying pressures and temperatures, the fluid is considered compressible.

    For industrial gas measurement applications it is common to use the Real Gas Law or the Ideal Gas Law. The Ideal Gas Law is applicable

    for moderate temperatures and low pressures. However, it fails to account for the interaction between gas molecules. When assumptions

    regarding the Ideal Gas Law do not apply the Real Gas Law is applicable.

    2.4 Specific Gravity

    Specific gravity (SG) is the ratio of density of one substance to the density of a second, or reference, substance. The reference substance

    for liquids is typically water at 68F (20C). The density of distilled water at 68F is 62.316 lbm /ft3, or at 20C, 998 kg/m3. The specific

    gravity of liquids is generally obtained with hydrometers, instruments whose scales read in specific gravities, degrees Baume (B), or

    degrees API (American Petroleum Institute).

    The specific gravity of a gas is defined as the ratio of the molecular weight of the gas of interest to the molecular weight of air (defined as

    28.9644). As long as the composition of a gas does not change, the ratio of molecular weight against that of a reference gas will remain

    the same regardless of temperature, pressure, or location.

    2.5 PressureFigure 2.5.1.a - Pressure is force acting perpendicularly on anarea. Pressure is the force acting on a surface in the normal direction (i.e.,

    perpendicularly) per unit area (Figure 2.5.a).

    The US unit of pressure is pounds per square inch, or psi, where pounds

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Equation2_1.png

  • is force and not mass.

    The SI unit of pressure is the Pascal and is equal to 1 Newton per m2.

    The Pascal is a very small unit of pressure and is generally expressed in

    kPa (kiloPascals) or MPa (megaPascals). Another common SI unit of

    pressure is the bar which is equal to 100 kPa.

    Absolute and Gage Pressure

    The absolute pressure, Pabs, is the pressure relative to a perfect vacuum. The gage pressure, or Pgage, is the pressure relative to

    atmospheric pressure, Patm. Thus:

    The absolute pressure is used to compute the density of gases. The gage pressure, since it is relative to atmospheric pressure, is used to

    ensure that pressure retaining parts (i.e. the pipe or parts of flowmeters that retain the pressure when installed in the pipe) will remain

    within safe working limits.

    Standard atmospheric pressure is typically defined as 1 atm, 14.69595 psi, or 101.325 kPa. Actual atmospheric pressure at any given

    location depends on that locations elevation above sea level and day-to-day weather conditions. Typically, changes in the atmospheric

    pressure due to weather are not used when calculating absolute pressure. However, local standard atmospheric pressure adjusted for

    elevation is used to determine the atmospheric pressure for purposes of measuring the flow rate.

    The value of pressure for a flowmeter application is used to provide information for two separate but important engineering tasks:

    For the calculation of fluid parameters especially gas or vapor density and gas expansion factor

    To check the compatibility and safety margins for the mounting hardware

    Differential Pressure

    When the difference in two pressures is needed, as called for in DP Flow calculations, it is called the differential pressure or DP. The SI

    unit for DP is Pa or kPa. The US unit for DP is psi or inches of water (inH2O) at a specified temperature.

    The unit inches of water is a carryover from the past where manometers were used to measure flow rate and indicates the pressure at the

    bottom of a column of water of the specified height when the water is at a specific temperature. As an example a DP of 25 inches H2O at

    68F means that this is the pressure at the bottom of a column of water that is 25 inches high when the temperature of the water is a

    uniform 68F. There are two commonly used versions of this unit inches H2O at 68F (used in the US process control industry) and inches

    H2O at 60F (used in the US natural gas industry). The conversion factors in psi for each of these is:

    This is a difference of 0.08% between the two reference temperatures, thus it is important to know the reference temperature.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Figure2_5a.png

  • Differential pressure can be calculated with a simple relation:

    The simplest of instruments used for the measurement of a small difference in pressures is the manometer A manometer uses a U-shaped

    tube or two vertical tubes connected at the bottom, with a liquid filling the tubes part-way (Figure 2.5.b). When the two pressures are

    applied at the top of each tube, the liquid in the two tubes change height, and a scale fixed to the manometer is used to measure the

    height or elevation difference, h. The differential pressure is then calculated using the relation:

    Figure 2.5.b Example of how a manometer works.

    Current best practices exploit electronic differential pressure and static pressure transmitters (Figure 2.5.c), which provide extremely

    accurate readings over very large ranges of pressure or DP, and can operate over a wide range of ambient temperatures without external

    correction. The electronic signal output is easily fed into microprocessors for calculating the flow rate or logging data.

    Figure 2.5.c A modern differential pressure transmitter.

    The standard manometer fluid for gas flow DP measurement is water, with the height indicated in inches, and the DP expressed as

    Inches of Water Column. Of course, if water or other liquids are being measured, a heavier manometer fluid is needed. Typically,

    mercury (S.G. = 13.5), or bromide-based fluids are used (S.G. = 2.5 to 3.0). Any fluid that is heavier than water could be used, but it must

    be immiscible, or unable to mix with the fluid in contact with the manometer.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Figure2_5b.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Figure2_5c.png

  • 2.6 Temperature

    Industrial methods of measuring temperature are based on substances that change electrical resistance with temperature, such as RTDs

    (resistance temperature detectors), or thermocouples that generates a voltage at the junction of dis-similar metals that is based on

    temperature.

    Outside of the engineering world, measurements are generally done on the relative Fahrenheit or Celsius scales, which were originally

    devised to measure the earths temperate range. However, flow engineering problems require a different temperature scale, one that

    represents an absolute temperature. Absolute temperature has units of Kelvin in SI units and Rankine in US customary units. The

    relationships between absolute temperature and the conventionally used units of F and C are:

    Absolute zero Rankine and absolute zero Kelvin are equivalent. The Rankine scale increments by degrees Fahrenheit, while the Kelvin

    scale increments by degrees Celsius.

    2.7 ViscosityTable 2.7.1 Viscosity symbols and common units.

    Absolute viscosity defines the resistance to movement of a fluid (Figure 2.7.a). It is a measure of the resistance of fluid molecules to

    velocity change due to shear stress.

    Figure 2.7.a Viscosity defines the resistance to movement of a fluid.

    The absolute temperature is required in the calculation of the fluid properties (i.e. density, viscosity and insentropic exponent). The

    calculation of thermal expansion effects involves temperature differences so it is common to use F or C.

  • Stated differently, viscosity tends to resist one particle from moving faster than an adjacent particle. Absolute viscosity is defined as:

    Kinematic viscosity is the absolute viscosity divided by the density of the fluid at the same temperature, or:

    Fluids are classified by the relationship between fluid stress (the force needed to overcome viscosity) and the strain (the fluid velocity).

    Figure 2.7.b shows the plot for different types of fluids based on the behavior of . DP flowmeters are restricted to Newtonian type fluids,

    or those where the slope of the fluid stress/strain curve () is constant. Shear-thinning fluid viscosities decrease with increasing shear

    stress; examples include ketchup, lava, or polymer solutions and molten polymers. Shear thickening (with viscosity increasing as shear

    stress increases) include suspensionscorn starch in water for example. Bingham plastics do not flow until a critical stress yield is

    exceeded; examples of this type of fluid include toothpaste.

    Figure 2.7.b Viscosity defines the resistance to movement of a fluid.

    Every real fluid has viscosity, which changes primarily with temperature. For this reason, fluid viscosity is usually plotted against

    temperature, and equations are developed that allow the calculation of viscosity once the temperature is known. For a liquid, the viscosity

    decreases with temperature; for a gas, the viscosity increases with temperature.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Figure2_7_1.png

  • 2.8 Fluid Velocity

    Velocity is not a fluid property, but can be used to predict the behavior of fluids in motion and will frame the application of DP flowmeters.

    In general, velocity is the rate of change of an objects position relative to a reference, and is equivalent to the specification of speed and

    direction of an object. As applied to fluid dynamics, velocity defines the speed of a particle of fluid with respect to a stationary reference

    such as a pipe. When a fluid flows around an object or through a pipe, the viscosity of the fluid creates a velocity profile. If there were no

    viscosity, the velocity of a flowing fluid in a pipe would be uniform across a pipe section. With the slightest of viscosity, however, shearing

    between adjacent fluid particles produces a non-uniform velocity profile in the pipe, with a velocity of zero at the pipe wall and maximum at

    the pipe centerline for developed flow.

    Fluid flow in a pipe also defines a velocity field. The flow of fluids through pipes has been studied extensively and velocity fields can be

    predicted when the rate of flow and fluid properties are known.

    2.9 Mass and Volume FlowTable 2.9.1 Mass and volumetric flow rate symbols and common units.

    Volumetric flow is measured in terms of volume, as the name implies, yielding how much volume is passing through a given area, as

    follows:

    Mass flow is dependent on density and the volumetric flow rate, as follows:

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Figure2_7b.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Figure2_9a.png

  • Volumetric flow and mass flow can be related by the following:

    In other words, when the mass flow rate (units of mass/unit time) is divided by the density at reference conditions, the flow rate is

    equivalent to the volume the fluid would occupy if its pressure and temperature were adjusted from the flowing conditions to reference

    conditions. If the flowing pressure is 146.96 psia, the temperature is 68F, and the reference conditions are 14.696 psia and 68F, then the

    mass flow rate is converted to standard volume flow rate (by dividing by the density of the fluid at reference conditions) the numerical

    value will increase by a factor of 10. The mass will remain the same, but in order for the pressure to be at 14.696 psia it must occupy 10

    times the volume as it did under flowing conditions.

    For a given quantity of liquid, mass does not change, but volume can with changes in pressure and temperature (Figure 2.9.a).

    Figure 2.9.a Volume, unlike mass, changes with changes in pressure and temperature. This illustration depicts an example of how muchvolume of a fluid can change with temperature.

    The measurement of mass flow is preferred for most gases and liquids, while volumetric flow can be acceptable for stable liquids.

    Flowmeters suitable for mass flow include multivariable DP flowmeters or Coriolis meters. Volumetric flowmeters include DP flowmeters,

    turbine, vortex, magmeter, or variable area meters.

    2.10 Isentropic Exponent

    As gases flow through a restriction in a pipe the density changes due to pressure changes. The expansion of the gas is assumed to be an

    isentropic process and the effect of the density changes on the flow rate can be determined theoretically for some obstructions or

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-02/lightbox-images/Figure%202_9a.jpg

  • empirically for others. The relevant fluid property is the isentropic exponent of the gas, designated by k (sometimes designated by g) and

    primarily is a function of temperature. It is common practice to determine k at a nominal temperature and use this value for all flow rates.

    Typical values of k can range from 1.0 to 1.4.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/Pages/chapter-01.aspxhttps://www.facebook.com/EmersonProcessManagementhttps://www.facebook.com/EmersonProcessManagementhttp://www.linkedin.com/company/emerson-process-managementhttp://www.linkedin.com/company/emerson-process-managementhttps://twitter.com/emersonprocesshttps://twitter.com/emersonprocesshttp://www.youtube.com/user/EmersonPlantWebhttp://www.youtube.com/user/EmersonPlantWebhttps://plus.google.com/108512660059325361875https://plus.google.com/108512660059325361875http://go.emersonprocess.com/MyEmerson

  • Chapter 3 - Flow Theory

    3.1 Introduction

    Chapter 3 covers the theoretical and computational details for DP Flow. Its purpose is two-fold:

    Introduce industry users to some of the many aspects of fluid flow in general and of DP

    Flow technologies specifically

    Explain the underlying assumptions and approaches behind the engineering of

    Rosemount DP Flow products

    Note that an in-depth understanding of the chemical and physical relationships that affect DP

    Flow are useful to help technical personnel to cover all the bases in the engineering of a specific

    application, but is not required for the installation and daily operation of DP flowmeters. What is

    important to understand is that there is a great deal of complexity that exists under the surface of

    even the simplest application.

    What is importantto understand isthat there is a greatdeal of complexitythat exists underthe surface ofeven the simplestapplication.

    Available Resources

    There are many readily available resources that allow engineers to resolve complexities.

    Among these resources are the following:

    Application and sales engineering resources available from the vendor of a given product

    Industry training and discussion by both experts and peers at user group and formal workshop sessions

    Software toolboxes and utilities usually developed by vendors and designed to streamline the engineering of a given application

    http://www2.emersonprocess.com/en-us/http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/Theory_of_DP_Flow.pdfhttp://www2.emersonprocess.com/en-us/brands/rosemount/pressure/dp-flow-products/pages/index.aspxhttp://go.emersonprocess.com/rosemount_rfq_enhttp://www2.emersonprocess.com/en-us/brands/rosemount/contact-us/pages/index.aspx

  • A large body of technical articles and books on the subject

    The following chapters discuss the practical side of DP Flowwhich technologies serve for a given class of application (gases, liquids,

    steam), insight into the hardware and software of available products (transmitters, primary elements), and considerations for installation

    and use.

    3.2 The Physics and Engineering of Fluids and Flow

    The concepts used in DP Flow theory and calculations originate mainly in two divisions of fluid mechanics: fluid kinematics, the study offluids in motion; and fluid dynamics, the study of the effects of forces due to fluid motion. The basic DP Flow equation is based on theconservation of energy, and applies to the measurement of almost every type of fluid found in industry or commercial use.

    The advantages of using DP devices to measure flow rate are the simplicity of the sensing system, the availability of many types of

    primary devices, the ability to verify the measurement, and the wide range of applications that are suitable for DP Flow.

    The challenges for using DP flowmeters are overcome by becoming familiar with the theory and operation of the devices used for DP

    Flow measurement.

    3.3 Developed and Underdeveloped Flow

    When evaluating the performance of flowmeters and in assessing their uses in a potential

    application, the condition of the velocity profile at the plane of measurement should be

    considered. A flow rate is considered developed when the velocity profile does not change

    significantly as it travels downstream. Achieving developed flow requires either a sufficient

    length of straight piping, or devices installed upstream that remove excessive turbulence or

    straighten the flow. Since flowmeters are primarily tested in developed flows, the potential

    effects on the performance of a meter must be considered separately if the flow at the

    measuring point is not developed.

    A flow rate isconsidered developedwhen the velocity profiledoes not changesignificantly as ittravels downstream.

    Different types of flowmeters are affected differently by undeveloped flows. Undeveloped flow can result from the additional turbulence in a

    pipe caused by piping fittings and types of valves installed upstream of the measurement location. Because of this, manufacturers usually

    provide a chart that shows how the flowmeter device should be installed to achieve the stated performance.

    3.4 Reynolds Number

    Reynolds number is an important non-dimensional parameter used in fluid mechanics. It is defined as the ratio of the inertial force of a

    fluid to the viscous force. The Reynolds number allows modeling of a fluid flow so that specific operational characteristics can be indexed

    to a common value. For flow metering, the Reynolds number is used to define a universal measuring range for all types of fluids. This

    ability greatly simplifies the evaluation, sizing, and use of flowmeters.

    For flow through a pipe the Reynolds Number is given by:

  • The flow through a pipe is characterized by ranges of the Reynolds number. The identification of these ranges, or regimes, is the result of

    extensive studies by scientists and engineers researching the belief that fluids flowing in pipes go through a transition from low to high

    velocities. This transition causes a change in the velocity profile in a pipe, which greatly affects the dynamics of the fluid and the ability to

    measure the flow rate.

    The initial regime at very low Reynolds numbers is referred to as laminar flow, or flow where the fluid remains in layers. The velocity

    increases consistently from the pipe wall to the pipe axis. The velocity profile for laminar flow is represented by a parabola. In this case,

    fluid viscosity plays a major role in driving the flow pattern to remain in steady layers.

    As the velocity increases, this laminar condition begins to change and the flow transitions. The layers breakdown into smaller eddies as

    the parabolic shape of the velocity profile begins to flatten. At higher velocities, the laminar region exists only at the wall and is very thin.

    The fluid throughout the rest of the pipe becomes turbulent. Although, the velocity profile flattens, the highest velocity is still at the center.

    Figure 3.4.a shows the profiles for the two types of flow. In Reynolds number values, the regimes are as follows:

    Re < 2000 = laminar flow

    Re 2000 4000 = transition flow

    Re > 4000 = turbulent flow

    The turbulent regime covers the majority of the range of velocities seen for fluids used in industrial and commercial flow in pipes. It is rare

    that piping is sized such that flows to be read are in the laminar regime unless the fluid has a high viscosity. For this reason, the

    application of DP flowmeter technology can be restricted to turbulent flow which in turn means they can be used in the majority of

    applications.

    Figure 3.4.a Flow profiles of laminar and turbulent flow.

    Calculating the Pipe Reynolds Number

    The basic Reynolds Number equation is described by a velocity, pipe ID, the fluid density, and viscosity. Since the Reynolds number is

    dimensionless, the units must be given in a consistent mass, volume/length, and time basis. The following base units are needed to

    calculate the pipe Reynolds number for US and SI units:

    Table 3.4.1: Reynolds number base units

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-4a.png

  • The poise is the unit of measurement for dynamic viscosity. Viscosity is commonly measured using centipoise (cP) in US units and Pas in

    the SI system of measurement. To convert to the viscosity units shown above use:

    While the density and viscosity can usually be found, the velocity is not typically on the specification sheet for a flowmeter. Instead the

    desired minimum and maximum flow rates are given. It is possible to calculate the Reynolds number using the flow rate rather than the

    velocity. We start with the area for a circular pipe or duct:

    For units other than the base units, a conversion factor is needed. The following are the equations for converting to the pipe average

    velocity, and calculating the Reynolds Number:

    Table 3.4.2: Reynolds number equation for different flow types

  • Special Case: Non-Circular Ducts

    For non-circular ducts (Figure 3.4.b), the hydraulic diameter is used in place of pipe diameter. This is defined as 4 times the cross-

    sectional area divided by the wetted perimeter. The equation is:

    Figure 3.4.b Rosemount Annubar primary element remote-mounted in a non-circular duct.

    3.5 The Bernoulli Principle

    In fluid dynamics, the Bernoulli Principle and the equations derived from it are a special form of the conservation of energy. More

    specifically, they are a special form of the general fluid flow energy conservation equation first described mathematically by Leonhard

    Euler in 1757. It is in actuality a collection of related equations whose forms can differ for different kinds of flow. The basic Bernoulli

    Equation for steady, incompressible flow is:

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-4b.png

  • This equation applies to a fluid that is moving along a streamline (denoted as s), or a continuous path that the fluid follows. All changes

    in the fluid will only occur along the streamline, and no fluid will flow out of or into the streamline. For the application of this concept to fluid

    meters, the fluid is flowing in a conduit or pipe, and the pipe is now the streamline. For steady-state conditions with developed flow, this

    one-dimensional model is sufficient to describe the flow field in a pipe.

    The Bernoulli Equation acts as the operating equation for DP Flowthat is, the transfer function between the input: the flow rate and fluid

    condition, and the output: the differential pressure. The benefit of the Bernoulli Equation is that it is simple, well defined, and accepted in

    the engineering community as a viable method for measuring fluid flow.

    For flow metering, the flow of fluid must be considered steady-state, meaning that there is no appreciable change in the rate or

    conditions while measurements are made. While these conditions might seem restrictive, in reality most fluid systems are designed to

    operate at a steady state with changes occurring slowly to prevent excessive pressure transients or vibration in the system.

    For an energy balance, the assumption is that no heat is added to the system and no work is done to or by the system. In reality work is

    done to the fluidotherwise pumps and fans would not be needed. However, when the system boundary is drawn around the meter, it is a

    good approximation to eliminate the system energy terms. In the applied form for fluid flow, the Bernoulli Equation represents an energy

    difference at two points in the fluid flow stream. In this description, Point 1 records the higher pressure; point 2 records the lower pressure

    (Figure 3.5.a), due to a transformation of energy from potential (pressure) to kinetic (velocity) energy.

    If Bernoullis Equation is appplied to two points along the same stream line equation and an energy balance is applied around the area

    change or restriction within the pipe, the equation becomes:

    Equation 3.6 shows the sum of the energy terms going into the restriction at point 1 must equal the sume of the energy terms after the

    restriction at point 2.

    Figure 3.5.a - Typical energy and flow diagram for a restriction in a pipe.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-5a.png

  • To determine the flow rate in mass/time or volume/time the continuity equation must be used which assures that mass is conserved

    (Equation 3.7):

    For an incompressible fluid, 1 = 2, and the continuity equation becomes:

    To reach the above form of the continuity equation and Bernoullis equation, some assumptions were made:

    Steady flow the equations represent constant velocity flowNeglible viscous effects represents a fluid with perfect uniformity while flowing and a consistent flow profileNo work is added to the system Bernoullis equation was derived from an energy balance on a system boundary around themeter. As a result, the simplified equation form shown in Equation 3.9 is not applicable in flow sections that involves pumps,

    turbines, fans, or other machinery since they disrupt the streamlines and ultimately cause energy interactions with the fluid

    Incompressible fluid it is assumed that density remains constant across the streamlineNegligable heat transfer effects the simplified Bernoulli energy balance excludes frictional effects which create local energytransfer in the form of heat

    Deriving the DP Flow Equation

    Beginning with Bernoullis equation (Equation 3.5) and re-writing where z = h for height, the equation becomes (see Figure 3.5.b for

    categorization of the terms):

    Figure 3.5.b Categorization of the energy terms in the Bernoulli equation.

    When its assumed the fluid is flowing horizontally and there is no change in height, the potential energy terms are equal. Combined with

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-5b.png

  • the continuity equation (Equation 3.9), the change in pressure at two points is represented as:

    For an incompressible fluid Equation 3.8 is true. The velocity multiplied by the cross-sectional area at points 1 and 2 are equal.

    The cross-sectional area for a circular pipe and a circular restriction (such as an orifice plate) is:

    Then re-writing Equation 3.10 substituting Equations 3.11 and 3.12 for A1 and A2,

    Combining Equation 3.9, the continuity equation, with Equation 3.13, results in an equation that relates the velocity at the restriction to a

    differential pressure:

    To calculate a volumetric flowrate multiply both sides of the equation by the area of the restriction:

    To calculate a mass flow rate, multiply both sides of the velocity equation by the density:

  • Equations 3.15 and 3.16 are the theoretical mass and volumetric flow equations based on the assumptions listed in Section 3.5. These are

    not representative of real-world fluid interactions. As a result two correction factors were developed, the discharge coefficient and the gas

    expansion factor.

    The discharge coefficient corrects for the following assumptions:

    No viscous effects

    No heat transfer

    Pressure taps at ideal locations

    Beta Ratio

    Instead of a restriction, this type of meter is called an area meter, as the meter is based on a change in area. For convenience, the ratio

    d/D is called Beta, or . The term d4/D4 would then be 4. Area meters such as orifice plates or venturis are defined by Beta, and

    the result of calibrations is classified by the type of area meter. To further simplify the flow equation, the term for Beta replaces the

    diameter ratio:

    The parameter: is defined as "E", so that the equation simplifies to:

    This is still the theoretical equation for incompressible flow, as it does not account for energy losses for a real fluid. When the discharge

    coefficient is added to the equation, it is called the Actual Mass Flow Equation for an incompressible flow and is:

    Figure 3.5.c Flow lab set-up for onedischarge coefficient data point.

    Assume that an orifice plate is installed in a flow lab so that a steady flow of water can be

    collected in a weigh tank. A flow calculation based on the theoretical equation shows that

    a total 1000 pounds of water flowed through the orifice during the test period and was

  • collected in the tank.

    However, during the same period, the weigh tank actually collected 607 pounds of water

    (Figure 3.5.c). This means that the discharge coefficient (Equation 3.20) for this orifice

    plate was 0.607 at the steady flow rate that was observed. This discharge coefficient

    represents just one data point on the graph in Figure 3.5.d.

    Since the discharge coefficient for most primary elements varies with Reynolds number, this test is done over a range of Reynolds

    numbers to determine the Cd vs. Re curve, or the meter characteristic. For area meters the same curve is also determined for various beta

    ratios. This body of data characterizes the discharge coefficient over a wide range of possible flow conditions for a range of area ratios, or

    Beta. This will result in hundreds or thousands of data points depending on the extent of the parameters to be tested.

    Once all of the data is collected, an equation can be developed to fit the curve of the data, as represented by the black line in Figure 3.5.d.

    This equation can then be used to predict the discharge coefficient of any geometrically similar primary element. In this way, the equation

    serves as a calibration constant so that primary elements of similar construction donot need to each be calibrated in a laboratory. The

    uncertainty for this variable can then be determined as shown by the orange dotted line in Figure 3.5.d. The uncertainty of a curve that is

    fitted to data is done using the Standard Estimate of the Error (SEE), which is the standard deviation of the data sample referenced to the

    calculated (curve) values.

    Figure 3.5.d The curve fit uncertainty of the discharge coefficient data collected.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-5c.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-5d.png

  • The Gas Expansion Factor (Y1)

    The gas expansion factor is also derived from laboratory testing where a gaseous fluid (typically air) can be used to generate a known flow

    rate. The reason it does not hold true in actual flowing conditions is because as a gas flows through a restriction, there is a decrease in

    pressure which results in the expansion of the gas and a decreased density, so 1 2. With a lowered density, the velocity will be slightly

    higher than predicted by the theoretical flow equation.

    Given:

    Figure 3.5.e Flow lab set-up for one gas expansion datapoint using air flow.

    Solving for Y1 is now possible.

    It is possible to determine Y1. For example, the lab testing for the gas

    expansion factor determines that 90 lbs should be collected according to

    the theoretical equation and 54.1 lbs was actually collected. The 54.1 lbs

    represents the mass flow including the discharge coefficient and the gas

    expansion factor.

    So:

    Since the same pipe and beta ratio was used for this test, Cd= 0.607.

    For gas or vapor flows, the density is determined at the upstream tap. For liquid flows, Y1 = 1.000. Figure 3.5.f below shows a plot of the

    expansion factor vs. the ratio P : Pabs for gases with a ratio of specific heats = 1.4 for the typical concentric, square-edged orifice plate.

    The gas expansion factor is plotted this way because the slight change in density is proportional to the percent change in line pressure.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-5e.png

  • Because the calculated flow rate depends on Cd and Y1 and these factors depend on the flow rate, it is necessary to re-calculate the flow

    rate, and then calculate new values for Cd and Y1, or iterate, until the difference between subsequent calculations is small.

    Figure 3.5.f After data is collected a line can be fit and the uncertainty of the gas expansion factor determined.

    3.6 The DP Flow Equation

    By adding the discharge coefficient and gas expansion factor, the flow equation now can accurately calculate flow applications. Recall the

    theoretical mass flow equation:

    Substituting the terms:

    The flow equation is simplified to become:

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-5f.png

  • Based on Bernoullis equation and an energy balance (Continuity Equation), this is the basic flow equation that uses the physical fluid

    properties mentioned above. d2, E, are geometrical terms and are determined by the primary element geometry. Cd, Y1 are empirical

    terms and are calculated using the test-derived equations either for a fixed set of flow equation parameters, or when a microprocessor-

    based flow computer is used, are continuously calculated DP, and vary with changing process conditions such as flow, temperature, and

    pressure.

    Difference Between Emperical and Geometric Terms

    As mentioned above d2 and E are geometric terms that change depending on the primary element geometry. Orifice plates, venturis, and

    flow nozzles are considered area-change primary elements or throated meters. Averaging pitot tubes use a velocity calculated by

    measuring the stagnation pressure (see Section 3.8 for details).

    Figure 3.6.a Types of area meters, also known asthroated meters, include Conditioning and standard orificeplates, nozzles, and venturis.

    Figure 3.6.b Discharge coefficient curves for three typesof DP flowmeters.

    Each meter will have different levels of energy loss, so the values of the

    discharge coefficient will be different. Figure 3.6.b shows the values of Cd

    for three throated primary elements plotted against the pipe Reynolds

    Number. When the primary meter calibration factor is plotted over the

    operating range, it is called the signature curve of the meter. Note that the

    venturi shown in the figure approximates the path taken by the streamlines

    of the flow. For this reason, there is little energy loss, so the value of the

    discharge coefficient is nearly 1.00. The nozzle has more energy loss as

    the streamlines separate from the walls, but the orifice has the most

    because it is an abrupt change in area that creates more turbulence in the

    fluid.

    For a DP flowmeter, there are two primary design drivers:

    1. The geometry of the meter including the pipe, the location and

    size of the openings to read the DP signal (also called the taps,

    and the condition of the components that make up the meter.

    2. The discharge coefficients assigned to the appropriate meter

    geometry.

    Primary elements such as the orifice plate or venturi shown in Figure 3.6.a

    have been tested for over a hundred years, and there have been many

    standards created to establish the value of the discharge coefficients as

    well as the design requirements for fabricating and installing each type of

    meter. Among these efforts are the resulting equations that were derived

    from a series of calibrations for a range of pipe sizes and beta values to

    allow the calculation of the discharge coefficient. Different types of Cd

    prediction equations have been developed with varying degrees of

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-6a.png

  • success. Because the orifice plate is the simplest, least expensive and

    easiest to retrofit and maintain, it is the most widely used of the four types

    of primary elements shown above. Each primary element type has a slightly

    different flow coefficient, but the equation used to calculate the flow rate is

    the same.

    3.7 Types of Area Meters

    There are many design variations of the four types of primary elements shown above. These variations allow the application of a DP Flow

    installation to types of fluid conditions that would not be possible with the standard designs. In every case, the modification to the standard

    design will use the same basic Bernoulli equation form, but with a modified the discharge coefficient, and expansion factor. These types of

    primary elements include Rosemount Conditioning Orifice plates, standard orifice plates, venturis, and nozzles.

    Figure 3.7.a Standard orifice plate.

    As discussed in Chapter 1, the type of flowmeter most often specified in

    industry is the orifice plate (Figure 3.7.a). The diameter of the orifice bore or

    throat is less than the diameter of the pipe, creating differential pressure as it

    restricts flow. As with all differential pressure producing flowmeters, the

    underlying theoretical principle for orifice flowmeters is the Bernoulli Equation,

    and the calculation of actual flow rates depends on Cd and Y1.

    Note that the discussion in the next section is generic and applicable to

    square-edge concentric orifice plates.

    ISO, ASME, and AGA Standards Provide a Basis for Calculating Discharge Coefficients

    Three major standards have been written to detail the Cd and Y1 coefficients, as well as the detailed construction, installation requirements

    and uncertainty factors. They are ISO 5167 Parts 1-4 from the International Organization for Standardization; ASME MFC-3M from the

    American Society of Mechanical Engineers; and AGA Report No. 3 for Natural Gas and Hydrocarbon fluids from the American Gas

    Association.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-6b.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-7a.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/Pages/chapter-01.aspx

  • Many independent test laboratories both public and private have contributed to the test data to correlate Reynolds Number, discharge

    coefficient, and gas expansion factor.

    Each standards organization continuously examines the equation structure to be used for their standard, usually when more data

    becomes available or a new analysis of the original data has been completed. For example, the ASME MFC-3M committee in 2004

    updated its equation structure to one virtually identical to ISO 5167.

    Rosemount Conditioning Orifice Plates

    The Rosemount Conditioning Orifice Plate design is an orifice plate with four bores (Figure 3.7.b). The primary purpose of this type of

    orifice is to condition the flow being measured within the area. This self-conditioning eliminates the need to install separate flow

    conditioners or the need for, in some cases, 40+ diameters of straight run after a flow disturbance.

    Figure 3.7.b Rosemount Conditioning Orifice Plateshowing its characteristic four holes orthogonallyarranged around the center.

    The Rosemount Conditioning Orifice Plate (COP) technology is based on

    the same Bernoulli equation as is used for standard orifice plates. As a

    result, the conditioning orifice plate follows the same general discharge

    coefficient versus Reynolds Number relationship as standard orifice plates

    with a slight shift in value, depending on the Beta ratio.

    The four holes in the plate are placed equally around the plate center.

    When a kinetic energy balance is done at the conditioning orifice plate and

    the continuity equation is applied, the result requires energy be conserved

    or the rate of the flow through the four holes must be the same. This

    pattern forces a distribution of the flow through the holes, creating a

    consistent downstream dynamic even when the upstream fluid velocity

    distribution is highly asymmetric or cyclonic. Since most of the orifice DP

    signal is created downstream, the COP provides equivalent results when

    installed in very close proximity to typical piping components as when

    installed in long runs of straight pipe. This removes the requirement for a

    flow conditioner and provides superior performance in short straight pipe

    runs.

    Figure 3.7.c Illustration of how the four holes in the Rosemount Conditioning Orifice Plate conditions irregular flow profiles to provideaccurate flow measurement with little straight run.

    Rosemount Conditioning Orifice flowmeters meet the intent of three main standards, ISO 5167/ASME MFC 3M and AGA Report Number

    http://www2.emersonprocess.com/en-us/brands/rosemount/flow/dp-flow-products/conditioning-orifice-flowmeter/pages/index.aspxhttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-7b.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-7c.png

  • 3. See Table 3.7.1 for details of compliance and deviations from the standards.

    Table 3.7.1 Comparison of the Rosemount Conditioning Orifice Plate to single-hole concentric orifice plates.

    Video 3.7.a How Conditioning Orifice Plates Work.

    3.8 Averaging Pitot TubesFigure 3.8.a Pressure points for a single point pitot tube. Pitot tubes calculate velocity by measuring the stagnation pressure, or the

    pressure due to the fluid velocity. The pressure at the impact pressure is

    called the total or stagnation pressure (Figure 3.8.a). If the pressure at the

    low static pressure tap is considered the pipe or conduit static pressure,

  • the DP is called the dynamic pressure of the fluid at that point. This form is

    used for the Pitot tube, invented and first used by Henri de Pitot in 1784.

    The modern incarnation of the Pitot tube used to measure flow rate is the

    Averaging Pitot Tube, or APT. The purpose of the APT is to measure the

    flow rate in a pipe or duct by measuring the velocity pressure, and average

    the pressure over the diameter of the pipe.

    A pitot tube measures only a point velocity. Unless the velocity profile is known or the flow is considered developed, a single velocity

    measurement will not represent an average velocity needed to calculate the flow rate with reasonable precision. For this reason, a pitot

    traverse can be done, a procedure which involves moving the pitot tube across the pipe or duct while taking samples. The average

    velocity can be calculated from these sample values. The sampling locations provide positions in a pipe or duct so that the average

    velocity can be obtained.

    The APT was developed to provide a faster method to obtain a velocity average. Figure 3.8.b depicts a Rosemount 485 averaging pitot

    tube. The main benefits of an APT over a traditional Area Meter such as a nozzle or an orifice plate are:

    The APT can be installed through a pipe coupling which requires less welding and expense

    The APT can be hot-tapped, or installed while the pipeline is under pressure

    The APT creates a much lower permanent pressure loss than a typical area meter

    Figure 3.8.b The Rosemount Annubar 485Averaging Pitot Tube design.

    When compared to a single-point Pitot tube, the following are the important distinctions

    for the APT:

    1. The velocity profile is sampled at the slots or holes in the front of the tube, which

    is installed across the pipe plane. This is equivalent to a continuous Pitot-

    traverse.

    2. The fluid that comes to rest (or stagnates) in front of each slot or hole creates a

    pressure that represents the velocity at that point in the velocity field. In addition,

    the opening at the front of the Pitot tube must be perpendicular to the fluid velocity

    vector to achieve a proper stagnation pressure.

    3. If the APT is properly designed, the pressure sensed at the top of the APT front

    chamber is the averaged stagnation pressure for the sampling slots or holes.

    4. The rear chamber measures the pressure at the rear of the tube, or the suction

    pressure. This pressure will be below the pipe static pressure due to the fact that

    for real fluids in the turbulent flow regime, separation of the fluid from the tube has

    occurred. This is advantageous because the DP signal is higher than that

    obtained with a standard pitot. However, unless the APT is properly designed, the

    value of the base pressure may not be predictable at all operating flow rates.

    Although the pressure sensed at the top of the rear chamber is the average suction pressure, in most cases, the pressure created behind

    the tube is nearly the same across the pipe diameter, due to the span-wise vortex-shedding or separation of the flowing fluid from the tube

    surface of the APT along the length.

    Figure 3.8.c Depiction of how vortices are shed off the Rosemount Annubar sensor. Rosemount Annubar T-shape design has a flatupstream surface which creates a fixed separation point which improves the performance over a wider flow range over other APT sensordesigns as well as stabilize the low pressure measurement.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-8a.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-8b.png

  • Video 3.8.a How an Averaging Pitot Tube Works

    Figure 3.8.d Various averaging pitot tube sensor shapes. The aboveshapes can result in weaker DP signal strengths due to lack ofseparation point.

    The sensor shape design of averaging pitot tubes varies

    greatly from manufacturer to manufacturer. The sensor shape

    has a great deal of impact on performance. Generally, sensor

    shapes such as the bullet shape, round, scalloped or ellipse

    shapes (Figure 3.8.d) will perform more poorly over a flow

    range, especially at lower Re numbers because the signal

    strength of the DP signal is weaker with no fixed separation

    point.

    Sensor shapes like the Rosemount 485 Annubar T-shape,

    have a flat upstream surface which creates a fixed separation

    point (Figure 3.8.c), resulting in a strong DP signal.

    Additionally, the T-shape design includes frontal slots (Figure

    3.8.f) which capture more of flow profile for a more

    comprehensive averaging and higher accuracy. The fixed

    separation point also creates a stagnation zone (Figure 3.8.c)

    in the back of the T-shape, which stabilizes the low pressure

    measurement for overall less signal noise.

    Figure 3.8.e Cutaway of the Rosemount Annubar T-shaped sensor. Holes Figure 3.8.f The 485 Annubar T-Shape APT design

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-8c.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-8d.pnghttp://www2.emersonprocess.com/en-us/brands/rosemount/flow/dp-flow-products/annubar-flowmeters/pages/index.aspx

  • in the backside of the Rosemount 485 Annubar T-Shape average the lowpressure measurement.

    includes frontal slots that average the high pressureside measurements.

    Averaging Pitot Tube Flow Equation

    Recall Bernoullis Equation assuming a horizontal pipe:

    For pitot style DP meters, the velocity at the sensing port is stagnated, meaning the velocity, V22, is actually zero.

    And solving for velocity:

    Mulitplying the velocity by the cross-sectional area of the pipe the theoretical volumetric flow equation is obtained:

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-8e.pnghttp://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-8f.png

  • And multiplying by flowing density to obtain the theoretical mass flow equation:

    To become:

    Again the theoretical equations are based on the following assumptions:

    No viscous effects

    No heat transfer

    Incompressible fluid

    For averaging pitot tubes the flow coefficient (K) corrects for the following assumptions:

    Negligible viscous effects

    Negligible heat transfer

    Pressure taps at ideal locations

    The gas expansion factor corrects for the incompressible fluid assumption.

    So the full flow equation for averaging pitot tubes becomes:

    Flow Coefficient, K, for Averaging Pitot Tubes

    Figure 3.8.g Cross section of pipe with APT installed,showing terms of the blockage equation.

    The K factor has been determined by extensive laboratory testing, similar to

    that of the discharge coefficent for orifice plates. Empirical equations have

    been created to calculate the K factor based on the test data. To calculate

    the K factor for an averaging pitot tube, it is a function of blockage. Blockage

    is the ratio of the area of the pitot tube to the area of the pipe.

  • And subsituting terms shown in Figure 3.8.g (B is the blockage factor and is unitless)

    Once the blockage is known, the K factor can be calculated.

    For a blockage, B 0.25, use the following K factor equation and C1 and C2 values from Table 3.8.1:

    For a blockage, B > 0.25 use Equation 3.38 below and Table 3.8.1:

    Table 3.8.1 Constants for determining the flow coefficient for the Rosemount 485 Annubar primary element.

    http://www2.emersonprocess.com/en-US/brands/rosemount/Rosemount-Site-Map/engineering-guides/PublishingImages/chapter-03/lightbox-images/figure3-8g.png

  • Gas Expansion Factor for Averaging Pitot Tubes

    The gas expansion factor for averaging pitot tubes is calculated slightly differently than area meters such as orifice plates. It is a function

    of blockage, DP, static line pressure, and the ratio of specific heats. Again, this factor is determined by laboratory testing.

    The equation for the gas expansion factor is as follows note this form requires the pressure and differential pressure to be in the same

    units so that Ya will be unitless.

    3.9 Things to Consider

    Computational Software

    Flow computers are often used to calculate flow utilizing the variables from the DP Flow installation or other measurement points. Flow

    computers are configured to calculate the flow based on the fluid properties and installation specifics such as line size and process

    variables either from individual pressure and temperature measurements or a multivariable transmitter such as the Rosemount 4088.

    The other option is to utilize multivariable transmitters with the ability to calculate flow specifically the Rosemount 3051SMV. Rosemount

    Engineering Assistant is a PC-based software program used for configuring Rosemount MultiVariable devices with mass flow output. In

    addition to being able to configure and calibrate the device, Engineering Assistant also performs configuration of the mass flow equation

    inside the transmitter. This software makes setting up a compensated flow equation simpler than manually setting up the flow equation in

    the control system. This is because the configuration of the flow equation all happens within Engineering Assistant and the flow calculation

    is done with the transmitter. The user only needs to enter their basic flowmeter and process information to configure their transmitter for

    fully compensated mass or energy flow.

    Engineering Assistant can be used as a Stand-Alone Windows based program, or as a SNAP-ON to AMS. The SNAP-ON version runs

    within AMS, while the stand-alone version can be run without an AMS installation.

    A common error in DP Flow installations is performing a double square root, or taking the square root of the Differential Pressure in the

    flow equation in both the transmitter and in the control system. The square root should only be taken once, either in the control system or

    in the transmitter.

    http://www2.emersonprocess.com/en-us/brands/rosemount/pressure/pressure-transmitters/multivariable-transmitters/3051s-multivariable/pages/index.aspxhttp://www2.emersonprocess.com/en-us/brands/rosemount/pressure/pressure-transmitters/multivariable-transmitters/3051s-multivariable/engineering-assistant6/pages/index.aspxhttps://www.facebook.com/EmersonProcessManagementhttps://www.facebook.com/EmersonProcessManagementhttp://www.linkedin.com/company/emerson-process-managementhttp://www.linkedin.com/company/emerson-process-managementhttps://twitter.com/emersonprocesshttps://twitter.com/emersonprocesshttp://www.youtube.com/user/EmersonPlantWebhttp://www.youtube.com/user/EmersonPlantWebhttps://plus.google.com/108512660059325361875https://plus.google.com/108512660059325361875http://go.emersonprocess.com/MyEmerson