dubai cables xlpepower cat web site

Upload: waelroustom

Post on 03-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    1/40BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    2/40BICC

    Introduction..1

    Customer.Service..2-3

    Product.Range..4

    Specification.and.Construction..4..5.

    Salient.Features.of.Ducab.Cables.Design...6

    Installation.and.Electrical.Data..6..19

    XLPE.Insulated.Cables.to.BS.5467:.Technical.Data.Tables...20-33

    l 600/1000V.rated,.Copper.and.Aluminium.Conductors..20-31

    lSingle.Core.Cables..20-21

    lTwo.Core.Cables..22-23

    lThree.Core.Cables..24-25

    lFour.Core.Cables..26-27

    lFour.Core.Cables.with.Reduced.Neutral.Conductors..28-29

    lThree.and.Four.Core.Armoured.Cables..30

    l 1900/3300V.rated,.Armoured.Copper.Conductors..31

    l XLPE.insulated.Lead.Sheathed.Armoured.Cables.to.BS.5467..32-33.

    Advantages.of.XLPE.Insulated.Cables..34

    LSF.Cables..34

    XLPE.Cable.Voltage.Drop.Data.for.partial.loads..35

    Components.Reference.Chart..36-37

    Ducab. is. listed. in. the. following. publication. issued. by. the. Department. of. Trade. and. Industry. of.

    the.United.Kingdom.

    THE.DTI.QA.REGISTER.-.PRODUCTS.AND.SERVICES.LIST

    Only.those. companies.whose. quality. system. is. assessed. and. certified. by. UK.accredited. certification.

    bodies.appear.in.the.above.publication.

    CONTENTS

    Pe

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    3/40BICC 1

    INTRODUCTION

    Dubai.Cable.Company.(Private).Limited..Ducab..is.a.joint.venture.between.the.Government.of.Dubai,.the.Government.of.Abu.Dhabi.through.General.Industry.Corporation.Ducab.is.located.on.a. site.of.54.hectares.in.Jebel.Ali,.Dubai,.in.

    the.United.Arab. Emirates.A.major. factory. expansion.took. place. in. 1991.with. production.capacity.being. more.than.

    doubled.In.1999,.Ducab.again.increased.production.capacity.for.low.voltage.cables.and.commissioned.a. world.class.

    production.and.testing.facilities.for.Powerplus.Medium.Voltage.cables.In.2001,.Ducab.installed.the.second.Medium.

    Voltage.CCV.line.The.current.factory.floor.area.is.16,000.m2.Ducab.manufactures.electric.cables.to.the.highest.quality.

    standards.

    This.catalogue.provides.working.information.on.Ducabs.complete.range.of.XLPE.Power.Cables.rated.up.to.33.kV.and.

    also.includes.data.on.components.Separate.catalogues.are.available.for.Ducabs.range.of.Control.and.Auxiliary.Cables,.

    Wiring. Cables,.Smokemaster LSF. Cables. and. Powerplus. Medium. Voltage. Cables. Details. of. PVC. Power.

    Cables.are.available.on.request

    Due.to.the.wide.range.of.cables.in.the.catalogue,.it.is.advisable,.when.ordering,.to..provide.as.much.information.as.possible.Please.use.the.following.table.as.a.guide:

    Specialist. advice. and. assistance. on. all. matters. concerning. PVC. and. XLPE. insulated. power. cables.

    is. available. from. Ducab. Sales. Offices. or. direct. from. Dubai. Cable. Company. (Private). Limited,.

    P.O.Box.11529,.Dubai,.U.A.E,.Tel:.971-4-836600,.Fax:.971-4-835965

    TEChNICal aDvISORy SERvICE

    .........The.following.details.will.ensure.that.your.enquiries.and.orders.are.dealt.with.quickly.and.efficiently:

    . 1. Length.of.cables.required.and.individual.drum.lengths*

    . 2. Voltage.designation

    . 3. Relevant.British.or.International.Standard

    . 4. Number.of.cores

    . 5. Conductor.size.and,.where.applicable,.size.of.reduced.neutral.conductor

    . 6. Conductor.material.ie.copper,.aluminium

    . 7. Type.of.insulation

    . 8. Type.of.bedding

    . 9. Type.of.armour

    . 10. Type.of.outer.sheath

    . 11. Any.other.special.requirement,.eg.circular.conductors,.special.PVC.sheath.material,.drum..

    . . weight.limitation,.etc

    . . *.Cables.are.normally.supplied.in.lengths.of.300.metres,.500.metres.and.1000.metres.. .

    . . . depending.on.conductor.size.Other.lengths.can.be.supplied.if.required

    . . ..

    ORDERINg aDvICE

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    4/40BICC2

    Dubai. is. the. premier. cable. manufacturer. in. the. United. Arab. Emirates. and,. since. 1979,. has. been. meeting. the.

    requirements. of. customers. throughout. the. Middle. and. Far. East. Ducabs. cables. are. used. by. some. of. the. most. .

    demanding.utilities.in.the.world,.for.the.following.reasons:

    Product QuitDucab.is. committed.to. supplying. its. customers. with. the. highest. quality. of. product. and. of. service. Ducabs. Power..

    cables. have. been. type. approved. by. Lloyds. Register. of. the. UK. and. have. undergone.

    rigorous.type.testing.by.BASEC.(British.Approvals.Service.for.Cables).They.fully.conform.

    to.BS.6004.and.BS.5467.specifications.for.PVC.and.XLPE.insulated.cables.respectively,.for.

    electricity.supply,.up.to.and.including.33kV.ratings.

    In.addition,. Ducab.was. presented. with. the. Dubai. Quality.Award. 1994,.for. the. best. local.

    industrial.company.of.the.year.Four.years.later,.Ducab.was.presented.with.the.Dubai.Quality.

    Award.98.Gold.Category.The.Gold.Award.rewards.the.most.distinguished.companies.which.

    are.judged.to.be.world.class

    ReibiitSpecifying. the. right. cable. for. a. particular. application. is. the. first. step. The. key. to. reliability. however,. is. in. the.

    manufacturing.process.The.cable.must.be.free.from.material.and.manufacturing.defects,.and.weaknesses.that.will.be.

    revealed.in.service.

    Ducab.constantly.monitors.its.manufacturing.processes.and.operates.stringent.quality.assurance.procedures.to.give.long.

    term.reliability.This.is.of.vital.significance.where.cables.are.to.be.installed.in.locations.where.future.access.would.be.

    difficult.and.this.is.where.Ducabs.reputation.and.the.resources.give.peace.of.mind

    .

    PerornceOptimum.cable.performance.can.be.provided.only.by.a.company.such.as.Ducab,.with.access.to.the.latest.developments.

    in.materials.technology.In.addition,.Ducabs.knowledge.of.application.requirements.throughout.the.Middle.and.Far.East.

    is.an.assurance.of.high.performance

    Where.required,.Ducab.can.incorporate.special.features,.for.example.to.give.the.cable.low.smoke.and.fume.(LSF).or.

    reduced.flame.propagation.characteristics,.or.to.resist.abrasion.and.impacts.

    Our.experienced.Technical.Staff.can.provide.guidance.on. cable.selection.and. installation.and.can. ensure.that.you.get.

    the.right.cable.for.the.job

    SetDucab.is.able.to.maintain.a.close.watch.on.world.developments.in.cable.technology.and.regulations.and.therefore.ensure.

    that.its.products.are.designed.and.constructed.to.be.hazard-free.under.the.prescribed.conditions.

    of.use

    .Ducab.uses.only.tried.and.tested.materials.and.processes.in.full.compliance.with.all.relevant.

    British.and.International.Standards.Our.cables.are.therefore.manufactured.for.safe.use.without.

    risk. to. health. on. the. understanding. that. users.will. exercise.the. same. degree. of. care. in. their.

    selection.and.application.

    Safety.is.an.important.issue.for.Ducab,.and.the.strictest.standards.are.adhered.to.throughout.the.

    company.Ducab.is.proud.of.its.safety.record.and.has.been.awarded.RoSPA.(Royal.Society.for.the.

    Prevention.of.Accidents).Gold.Awards.for.safety.from.1991.to.1999.From.2000.onward,.Ducab.

    was.awarded.the.prestigious.Presidents.Award.for.Health.and.Safety.which.is.a.recognition.of.

    Ducab.winning.10.consecutive.annual.Gold.awards.and.acknowledges.Ducabs.total.commitment.to.health.and.safety.

    In.2002,.Ducab.was.declared.the.joint.winner.of.the.Manufacturing.Industry.Sector.Award.from.RoSPA

    Ducab.is.the.first.organisation.in.the.Middle.East.to.receive.accreditation.to.OHSAS.18001.by.the.BASEC.(British.

    Approvals.Service.for.Cables).Certification.to.OHSAS.18001.provides.a.recognisable.Occupational.Health.and.Safety.

    Management.standard.against.which.an.organisations.management.systems.can.be.assessed.and.certified.Based.on.the.

    structure.of.ISO.14001,.the.standard.requires.continual.improvement.in.health.and.safety.related.activities.

    CUSTOmER SERvICE

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    5/40BICC 3

    Quit mneent Sste Certiied to ISO 9001

    Ducabs. Quality. Management. System. conforms. to. the. ISO. 9001:2000. International. Quality. System. Standard.

    and.is.certified.by.BASEC.(British.Approvals.Service.for.Cables).who.are.an.internationally.recognised.quality.authority.

    accredited.in.the.UK.and.throughout.the.world.

    Certification. to. the. ISO. 9001. International. standard. demonstrates. that. Ducab.

    has. drawn. up. written. procedures. to. ensure. full. compliance. with. all.

    requirements. of. the. standard. and. that. these. procedures. are. followed. by.

    every. department. in. the. company,. thus. ensuring. that. goods. leaving. Ducabs.

    factory. are. of. the. highest. quality. and. meet. each. customers. requirements. in.

    every.respect.

    Ducab.is.particularly.proud.to.have.achieved.certification.to.the.stringent.ISO.

    9001:2000.standard.as.it.is.an.independent.conformation.that.the.company.designs,.manufactures.and.tests.cables.

    consistently.to.accepted.standards.ISO.9001.is.widely.used.throughout.Europe,.and.is.therefore.a.reassurance.to.

    Ducabs.customers.that.the.products.and.service.supplied.by.the.company.are.equal.to.the.best.in.the.world

    Enironent mneent Sste Certiied to ISO 14001

    Ducabs. Environmental. Management. System. conforms. to. the. ISO. 14001:2004. International.

    . Environmental. Management. Standard. and. is. certified. by. BASEC. who. are. an. internationally. recognised. .

    certifying.authority.accredited.in.the.UK.and.throughout.Europe

    Certification. to. the. ISO. 14001:2004. International. standard. shows. that. Ducab.

    has. a. well. defined. structure. and. established. working. practices. aimed. at.

    limiting. its. impact. on. the. environment. Measurement. and. monitoring. of.

    effects,. issuing. work. instructions,. training. of. personnel. and. taking. corrective.

    actions. are. all. essential. elements. to. limiting. the. impact. on. the. environment.

    Ducab. has. set. improvement. targets. to. reduce. the. significant. environmental.

    impacts.associated.with.its.activities

    Ducab. is. proud. to. be. the. first. cable. manufacturer. in. the. region. to. achieve. certification. to. ISO. 14001. and.

    this. certification. along. with. its. quality,. business. success. and. safety. record. demonstrates. that. Ducab. is. a.

    world.class.organisation.and.can.hold.its.head.up.to.any.business.community.throughout.the.world

    BaSEC Certiiction

    Ducab.is.also.proud.to.hold.a. Product.Marketing.Licence.issued.by.BASEC.(British.

    Approvals.Service.for.Cables).for.several.cables.in.its.product.range

    Ducb Sreek

    Ducabs.customer.satisfaction.programme,.The.Value.Edge.is.designed.to.ensure.that.customers.receive.a.consistently.

    high.level.of.service.from.Ducabs.dedicated.staff

    .

    LICENSE NUMBER - 083

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    6/40BICC4

    INSUlaTIONThe.rated.voltage.level.of.the.cable.depends.on.the.dielectric.strength.and.thickness.of.the.insulation

    mteri:

    Cross-linked.polyethylene.(XLPE).Type.GP8.as.per.BS.7655:Section.13

    Coour msterbtc:

    Ultra-violet. (UV).resistant.polyethylene.masterbatch.is. used.for. colouring.of. insulation. This.protects. the.insulation.

    from.deterioration.when.exposed.to.continuous.sunlight.

    Core.identification.is.by.colour.as.follows.(unless.otherwise.agreed):

    No. o cores Core Coours

    . 1. Red.or.Black

    . 2. Red.and.Black

    . 3. Red,.Yellow.and.Blue

    . 4. Red,.Yellow,.Blue.and.Black

    . 5. Red,.Yellow,.Blue,.Black.and.Green/Yellow

    For.providing.circular.shape.to.the.cable.non-hygroscopic.compatible.fillers.(wherever.necessary).are.included.between.

    laid.up.cores.

    mETallIC SCREEN:

    If.required.by.the.customer.screening.may.be.provided.for.electrical.shielding

    mteri:Copper.tape

    Aluminium.PE.tape.along.with.tinned.copper.drain.wire.(for.providing.screen.continuity)

    Note:.Special.constructions.other.than.stated.above.may.be.provided.on.request

    SPECIfICaTION aND CONSTRUCTION

    CONDUCTORS

    It.is.the.current.carrying.component.of.the.cable

    mteri:.

    Plain,.stranded,.compacted.copper.as.per.BS.6360/IEC:228.

    Aluminium,.stranded,.compacted.conductors

    CORE IDENTIfICaTION

    fIllERS

    PRODUCT RaNgE

    vote rne: 06/1kV.and.19/33.kV

    Cbe Tpes:.1).Armoured/unarmoured.XLPE.insulated.cables.

    2).Lead.sheathed.cables.

    3).Copper.or.Aluminium.PE.tape.(with.drain.wire).shielded

    Cbe sizes:

    Single.core.up.to.and.including.1000.mm 2.

    2.core.up.to.and.including.300.mm 2.

    3.core.up.to.and.including.400.mm 2.

    4.core.up.to.and.including.500.mm 2

    Speciiction:

    BS.5467.for.XLPE..insulated.armoured.cables

    BS.7889.for.XLPE.insulated.single.core.unarmoured.cables.

    IEC.60502.(Part.1).for.XLPE.insulated.single/multicore.armoured/unarmoured.cablesAny.other.International.Specification.as.per.VDE/DIN,GOST.and.as.per.customers.specifications

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    7/40BICC 5

    BaRRIER TaPE:

    mteri:

    Polypropylene/PETP.tape.is.used.as.a.barrier.tape.over.the.laid.up.cores

    functions:.Holds.the.cores.together.and.prevents.them.from.opening.out

    Works.as.a.separator.between.different.polymers.used.in.a.cable

    lEaD ShEaTh

    mteri:

    Extruded.Lead.Alloy.E.Sheath

    Thickness.of.applied.lead.sheath.is.as.per.EEMUA.-.133.(Engineering.Equipment.and.Material.Users.Association)

    function:

    Protects.insulation.from.corrosion.by.petroleum.products.in.oil.and.gas.industries

    Extruded.bedding.serves.as.a.bedding.for.the.armour.and.as.a.protection.for.the.laid-up.cores.

    mteri:

    Extruded.PVC.Type.9.Compound.as.per.BS.7655

    Reduced.propagation.flame.retardant.(RPLHCL)/RP.PVC.Compound.for.reduced.flame.propagation.characteristics

    Smokemaster low soke nd ue or insttions were ire zrds exist.

    Armour.provides.mechanical.protection.to.the.cable.It.also.serves.as.an.Earth.Continuity.Conductor.(ECC)

    One.layer.of.round.wire.is.applied.helically.over.the.bedding.

    mteri:

    Galvanised.round.steel.wire.(GSW)

    Galvanised.round.steel.wire.(GSW).on wit tinned copper wires (TCW) or intinin speciied conductiit

    o rour (i required b te custoer).

    Aluminium.round.wire.armour.(AWA).is.generally.used.for.single.core.ac.circuits.as.aluminium.is.a.non-magnetic.

    material.and.this.will.reduce.losses.due.to.armour

    Note:.Aluminium.glands.should.be.used.in.conjunction.with.cables.having.aluminium.wire.armour

    Following.types.of.materials.may.be.specified.for.oversheathing.

    lgener Purpose:.Extruded.PVC.Type.9.Compound.as.per.BS.7655

    lmediu Densit Potene (mDPE):.Offers.higher.protection.from.water.ingress.and.mechanical.abrasion

    lanti Terite:.Termite.resistance.can.be.built.in.both.types.described.above.by.compounding.with.proper.additives

    lReduced Proption (RP):.Retards.propagation.of.flame.in.fire.situation.(Oxygen.Index. 30)lReduced Proption nd low acid fues (RPlhCl):.Retards.propagation.of.flames.and.gives.low.emission.of.

    hydrochloric.acid.fumes.(OI. 30.&.acid.gas.emission.is.less.than.18.%)lSmokemaster low Soke & fue (lSf):. Smokemaster cables. are. ideal. for. installations. where. the.

    dense.black.smoke.generated.by.PVC.cables.in.a.fire.are.a.danger.to.people.Smokemaster is.characterised.by.the.features.as.Oxygen.Index.greater.than.35,.acid-gas.liberation.almost.nil.(

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    8/40BICC6

    INSTallaTION

    Whichever.form.of.conductor.is.used,.XLPE..insulated.cables.are.simple.to.handle,.install.and.joint.All.the.cables.

    described.in.this.publication.can.be.used.indoors.or.outdoors,.but.some.reservations.are.necessary.concerning.cables.

    for.direct.burial.in.the.ground.or.for.use.in.sustained.wet.conditions.as.follows:

    (i). Unarmoured.cables.are.not.generally.recommended.for.laying.directly.in.the.ground

    (ii). Cables.laid.directly.in.the. ground,.particularly.in.sustained.wet.conditions,.should.have.extruded.bedding.and.

    preferably.MDPE.-.Medium.Density.Polyethylene.-.as.the.outersheath.material.

    Other.important.factors.to.be.taken.into.account.are:.

    Set DeCare.should.be.taken.to.ensure.that.the.oversheath.is.not.damaged.during.installation.This.is.especially.important.where.

    aluminium.wire.armour.is.used,.as.ingress.of.moisture.could.lead.to.corrosion.or.ultimate.loss.of.earth.continuity.

    SalIENT fEaTURES Of DUCaB CaBlE DESIgN

    (1) XlPE insution Utr-ioet (Uv) coour sterbtc:

    Ultra-violet. (UV).resistant.polyethylene.masterbatch.is. used.for. colouring.of. insulation.This. protects.the. insulation.from.deterioration.when.exposed.to.continuous.sunlight.

    (2) Popropene/PETP tpe oer te id up cores:

    Acts.as.a.separator.between.different.polymers.used.in.a.cable

    (3) fiers:

    For.ensuring.proper.circular.shape.to.the.cable,.non-hygroscopic.compatible.fillers.(wherever.necessary).are.included.

    between.laid.up.cores.

    (4) Speci requireents:

    Ducab.cables.can.be.custom.designed.to.incorporate.special.requirements.of.the.client.as.follows:

    (a).Screening:.Copper.tape.or.Aluminium.PE.tape.(along.with.tinned.copper.drain.wire).can.be.used.for.shielding.purposes.

    (b).Tinned.copper.wire.can.be.used.along.with.galvanised.round.steel.wires.to.maintain.specified.armour.conductivity.

    requirements.

    (c).Reduced. propagating. flame. retardant. bedding. (RPLHCL/RP). and. outersheath. material. can. be. offered. to. meet.

    reduced.flame.propagation.characteristics.and.low.hydrogen.acid.gas.emission

    (d).Cable. with. bedding. and. outersheath. material. of. special. LSF. (low. smoke. and. fume). compound.can. be. offered.

    for.installations.where.fire.and.its.associated.problems.-.the.emission.of.smoke.and.toxic.fumes.-.offer.a.serious.

    potential.threat.(For.details.on.LSF.cables.refer.page.34)

    (e).In. water. logged. areas. or. where. the. cables. are. required. to. be. abrasion. resistant,. cable. with. medium. density.

    polyethylene.(MDPE).can.be.offered.(f). For.protection.from.insects,.anti-termite.protection.can.be.added.to.the.outersheath.

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    9/40BICC 7

    miniu insttion rdius

    Cable.should.not.be.bent.during.installation.to.a.radius.smaller.than.that.recommended.below.Wherever.possible.larger.

    installation.radii.should.be.used.

    Tbe 1

    Tpe o Cbe Oer Dieter (D)miniu intern

    rdius o bend

    Circular.copper.conductors.armoured.or.unarmoured Any 6D

    Shaped.copper.or.aluminium.conductors,.armoured.

    or.unarmoured

    For.lead.sheathed.cables

    Any

    Any

    8D

    12D

    CaBlE SUPPORT SPaCINgAs.per.Clause.522-08-04.of.16.th.Edition.of.IEE.Wiring.Regulations.where.the.cable.is.not.continuously.supported.it.

    shall.be. supported.by.suitable.means.at.appropriate.intervals.in.such.a. manner.that.the.cable.does.not.suffer.damage.

    by.its.own.weight

    Connectors

    The.use.of.compression.type.connectors.is.recommended.for.XLPE.insulated.cables.since.the.use.of.soldered.connectors.

    would limit the maximum short circuit temperature of the cable to 160C (and consequently reduce the final short circuitcurrent.by.approximately.30.per.cent)

    Oered terintions

    Ultra. violet. resistant. sleeving. or. taping. should. be. provided. on. XLPE. insulated. cores.to. avoid. degradation. due. to.

    exposure.to.solar.rays.

    aroured Sine Core Cbes or aC Opertion

    Single.core.cable.armour.should.not.be. bonded/earthed.at.both.ends,.otherwise.it.carries.a.circulating.current,.which.

    may.cause.overheating. in.the. cables,.sometimes.resulting. in.early.failure.However.single.end. bonding.results.in.an.

    induced.voltage.(of.low.magnitude).at.the.unearthed.end.of.the.armour.Ducab.strongly.recommend.use.of.an.Insulated.

    Adaptor. in. the. cable. gland,. while.terminating. single. core.cables. for.AC. operation.The. insulated.adaptor. could.be.

    provided.as.per.part.design.No.481.AA.-.Series.

    Single.core.cables.for.AC.operation.should.not.pass.through.steel.conduit.or.steel.gland.plate,.as.it.produces.a.heating.

    effect.

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    10/40BICC8

    CURRENT RaTINgS

    Current.ratings.for.XLPE.insulated.cables.for.ground.and.duct.installation.are.derived.from.the.latest.issue.of.ERA.

    Report.69-30.Part.5.which.is.based.upon.IEC.Publication.287.The.ratings.for.In.Air.installation.are.taken.from.IEE.Wiring.Regulations,.16th.Edition.

    All.the.ratings.given.are.for.single.circuits.installed.thermally.independent.of.other.circuits.or.any.other.heat.source.and.

    on.the.basis.of.the.standard.conditions.of.installation.given.in.relevant.Tables.between.18.to.34.For.other.ambient.or.

    ground.temperatures,.depth.of.laying,.soil.thermal.resistivity,.the.rating.must.be.multiplied.by.relevant.rating.factors.in.

    Tables.2.to.6.and.8.to.12.

    It.should.be.noted.that.if.XLPE.insulated.cables,.are.subjected.to.operating.temperatures.appreciably.higher.than.the.

    90C permissible for continuous operation, the insulation will undergo premature ageing thus affecting the normal lifeof the cable. However, limiting maximum conductor temperature to 105C during overloads with duration not exceeding4.hours.on.any.one.occasion,.or.a.maximum.of.100.hours.in.any.12.consecutive.months,.or.a.total.of.500.hours.in.the.

    cables.lifetime,.would.be.tenable.

    IEE Wirin Reutions 16t edition - requireent or cbesThe.IEE.Wiring.Regulations.for.installation.and.selection.of. cables.cannot.be.approached.in.isolation.from.the.other.

    equipment.in. the.installation.In. particular.the.devices.providing. protection.against.overload,.short.circuit,. shock. by.

    indirect.contact.and.over-heating.of.protective.conductors.during.an.earth.fault,.affect.the.selection.of.cables.

    For.guidance.and.assistance,.given.below.are.some.of.the.IEE.Wiring.Regulations.requirements.for.cables:

    Protection inst oerod current: (Cuse 433-01-01 o te 16t Edition o te

    IEE Wirin Reutions)

    This.states.the.requirements.which.effectively.determine.the.sustained.current.ratios.of.the.cable.viz:

    (i).The.current.rating.of.the.cable.should.not.be.less.than.the.nominal.current.or.current.setting.of.the.device.providing.

    protection.against.overload,.which.in.turn.should.be.not.less.than.the.circuit.current.

    (ii).The.overload.protection.should.operate.at.not.more.than.145.times.the.current.rating.of.the.cable.

    The.second.requirement.(ii).is.met.if.the.first.(i).is.met.when.the.protective.device.is.any.of.the.standard.fuses.or.MCBs.

    mentioned.in.the.regulations,except.rewirable.types.of.fuse.to.BS.3036.

    With.fuses.to.BS.3036.the.current.ratings.of.the.cable.should.not.be.less.than.138.times.the.fuse.rating.to.satisfy.(ii)

    Protection inst sort circuit: (Cuse 434 o te 16t Edition o te IEE

    Wirin Reutions)

    The.cable.has.to. have.adequate.short-circuit.capacity.for.the.current.let.through.by.the.device.providing.short.circuit.protection.for.the.time.it.will.flow.

    The.formula.in.Section.434-03-03.is.effectively.that.used.by.cable.makers.to.give.the.short-circuit.ratings.in.their.

    publications.

    If.the.device.providing.protection.against.short.circuit.is. the.same.as.that.providing.protection.against.overload.and,.

    therefore,.has.a.rating.not.higher.than.the.rating.of.the.cables,.the.short.circuit.capacity.of.the.cable.will.automatically.

    be.adequate,.there.is.no.need.to.check.

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    11/40BICC 9

    Protection inst indirect contct b interruption o supp: (Cuse 412 o te

    16t Edition o IEE Wirin Reutions)

    Protection.against.shock.due.to.contact.with.exposed.conductive.parts.of.equipment.during.a.fault.to.earth.is.deemed.to.

    be.provided.if.disconnection.due.to.flow.of.the.fault.current.through.the.protective.device.will.occur,.eitherwithin. 04. seconds. for. final. circuits. supplying. socket. outlets. (Table. 41A. of. the. 16th. Edition. of. the. IEE. Wiring.

    Regulations)

    or

    within.5.seconds.for.final.circuits.supplying.fixed.equipment.(Clause.413-02-12.of.the.16th.Edition.of.the.IEE.Wiring.

    Regulations)

    Regulation.413.gives.values.of.earth.fault.loop.impedances.which.satisfy.these.conditions.when.the.standard.types.of.

    protective.devices.are.used.

    Cables.make.the.major.contribution.to.earth.fault.loop.impedance,.but.the.impedance.of.the.supply.external.to.the.

    installation.has.to.be.taken.into.account.

    It.is.not.possible.to.say.what.maximum.length.of.standard.cables.may.be.used.in.the.installation.without.exceeding.the.

    requirements.for.earth.fault.loop.impedance.in.the.absence.of.information.on.the.external.impedance.for.the.particular.installation.

    Table.16.gives.estimated.values.of.the.contribution.to.earth.loop.impedance.by.XLPE.insulated.copper.conductor,.steel.

    wire.armoured.cables.to.BS.5467.

    Cross section res o protectie conductors: (Cuse 543 o te 16t Edition

    o IEE Wirin Reutions)Regulation.543.explains.how.the.cross.sectional.area.of.the.circuit.protective.conductor.should.be.calculated.to.avoid.

    it.over-heating.during.a. fault.to. earth.Again.the. area.required.depends.on.the. characteristics.of.the.device.providing.

    protection.against.short.circuit.

    The.steel.wire.armour.of.standard.cables.to.BS.5467.(XLPE).and.BS.6346.(PVC).provides.the.required.area,.or.more,.when.the.protective.device.is.one.of.the.standard.fuses.or.MCBs.with.a.rating.not.higher.than.the.current.rating.of.the.

    cable.(assuming.disconnection.within.5.seconds)

    For.the.most.of.the.cables.the.armour.is. still.adequate.when.the.fuse.rating.is.one.or.two.steps,.or.even.more,.above.

    the.current.rating.of.the.cable,.the.margins.being.greater.for.the.small.sizes.and.4.core.cables.than.for.the.larger.sizes.

    and.two.core.cables.

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    12/40BICC10

    Voltage.drop.is.normally.only.of.importance.for.cables.of.voltage.rating.600/1000V.or.below.If.the.installation.is.to.be.

    incompliance.with.Regulation.525.of.the.16th.Edition.of.the.IEE.Wiring.Regulations,.it.is.stipulated.that.the.voltage.drop.within.the.installation.does.not.exceed.a.value.appropriate.to.the.safe.functioning.of.the.associated.equipment.

    in.normal.service.The.requirement.is. deemed.to.be. satisfied.if.the.drop.in.voltage.from.the.origin.of.the.installation.

    (usually.supply.terminals).and.the.fixed.current.using.equipment.does.not.exceed.4.per.cent.of.the.nominal.voltage.of.

    the.supply,.disregarding.starting.conditions

    (Note:.Diversity.can.be.taken.into.account.when.calculating.voltage.drop)

    Since.the.actual.power.factor.of.the.load.is.often.not.known,.the.most.practical.approach.to.the.question.of.voltage.drop.

    is.to.assume.the.worst.conditions.ie.where.the.phase.angle.of.the.load.is.equal.to.that.of.the.cable.The.voltage.drop.

    values.in.the.tables.have.been.based.on.this.assumption.For.conductor.sizes.up.to.and.including.120.mm 2.the.figures.

    provided.apply.with.sufficient.accuracy.where.the.power.factor.lies.between.06.lagging.and.10,.and.for.large.cables.

    where.the.power.factor.of.the.load.does.not.exceed.08.lagging.Where.the.phase.angles.of.the.loads.fall.outside.this.

    range,.the. voltage.drop. deduced.from.the. tables.may. be.unduly.conservative.and. more.exact.methods.of. calculation.

    should.be.employed.

    The.values.of.voltage.drop.for.600/1000.V.rated.cables.are.given.in.the.current.rating.tables

    In.those.cases.where.the.actual.current.differs.greatly.from.the.tabulated.current.rating,.the.results.obtained.from.the.

    tables.are.only.approximate;.for.a. more.accurate.assessment,.allowance.should.be.made.for. the.change.in. conductor.

    resistance.with.operating.temperature.Refer.to.page.35.and.Table.32.for.details.It.should.also.be.ensured.that.the.cable.

    size.ultimately.selected.is.capable.of.carrying.the.required.current.under.the.site.conditions.of.installation.

    Values.of.voltage.drop.are.tabulated.for.a.current.of.one.ampere.for.a.1.metre.run,.ie.for.a.distance.of.1.metre.along.

    the.route.taken.by.the.cables,.and.represent.the.effect.of.the.voltage.drop.in.all.the.circuit.conductors.For.balanced.three.

    phase.ac.circuits,.the.values.relate.to.the.line.voltage.For.any.given.run.the.values.need.to.be.multiplied.by.the.length.

    of.the.run.(in.metres).and.by.the.current.(in.amperes).that.the.cables.are.to.carry.

    Expes:.Consider.a.route.of.200.metres.of.4.Core.armoured.cable.to.be.installed.in.air.and.to.carry.100.amperes.load.per.phase,.with.the.supply.voltage.being.415.volts,.three.phase.50.Hz.and.the.cable.to.be.Copper.XLPE/SWA/PVC.

    Using.the.tables:

    Let.Vd.be.the.voltage.drop.in.volts

    Vd.=.mV.x.I.x.L...or.mV.=.Vd.x.1000

    ....... .1000. . ......I.x.L.

    where.I.=.Current.in.amperes..L.=.Route.length.in.metres..mV.=.Approximate.volt.drop/ampere/metre

    Assume.maximum.permissible.volt.drop.=.4.per.cent.of.415.volts.=.166.volts

    Substitute.for.current,.route.length.and.maximum.permissible.volt.drop

    then.mV.=.166.x.1000..=.083. .....200.x.100

    Select.a.cable.from.the.relevant.Current.Rating.Table.27.such.that.the.mV.value.from.the.voltage.drop.column.is.

    equal.to.or.less.than.the.083.mV.calculated,.ensuring.that.it.will.carry.the.current.It.will.be.seen.that.this.value.is.06.

    giving.a.cable.size.of.70mm2.However,.100.Amp.load.could.be.less.than.80%.current.carrying.capacity.of.50mm 2.cable,.

    in.which.case.of.50.mm 2.cable.will.suffice.

    Note:.Please.refer.to.pages.30.and.35.for.additional.information.on.voltage.drop.

    vOlTagE DROP

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    13/40BICC 11

    RaTINg faCTORS

    Rtin ctors or round teperture

    Rtin ctors or rition in ter resistiit o soi

    (ere ues)

    CaBlES laID DIRECTly IN gROUND

    Where.the.conditions.of.installation.differ.from.those.defined.in.the.current.rating.tables,.the.following.rating.factors.may.be.used.

    for.cables.size.selection.

    Ratings.for.cables.installed.directly.in.the.ground.are.based.on.values.of.soil.temperature.and.soil.thermal.resistivity.which.are.

    generally.representative.of.conditions.in.the. United.Kingdom.Rating.factors.to.take. account.of. variation.in. ground.temperatures.

    are.given.in.Table.2.Where.conditions.of.operation.can.be.fairly.accurately.estimated.and.knowledge.of.the.soil.along.the.route.is.

    available,.it.is.possible.to.determine.the.ratings.more.precisely.by.the.use.of.the.soil.thermal.resistivity.factors,.grouping.factors,.and.

    factors.for.the.depths.of.laying.given.in.Tables.3.to.6..These.factors.are.more.fully.tabulated.in.ERA.Report.69.-.30.Part.II.Tables.

    61.-.71.

    In.ERA.Report.69-30.Part.III,.the.types.of.load.are.classified.under.three.headings,.viz:

    Tpe a. Cables.carrying.a.constant.load.throughout.the.year.

    Tpe B. Cables.carrying.varying.loads,.maximum.in.summer.period

    Tpe C. Cables.carrying.varying.loads,.maximum.in.winter.period.

    With.knowledge.of.the.type.of.load.to.be.imposed.on.the.cable.it.is.then.possible.to.determine.the.soil.thermal.resistivity.along.the.cable.route.in.accordance.with.recommendations.in.ERA.Report.69-30.

    Tbe 2

    Tbe 3

    Ground.temperature 15C 20C 25C 30C 35C 40C 45C

    XLPE.Insulated 10 097 093 089 086 082 076

    Cbe Tpe Rtin ctor

    Size.of.cables

    mm2

    Single.core.cables

    Up.to.150

    From.185.to.300

    From.400.to.1000

    Multicore.cablesUp.to.16

    From.25.to.150

    From.185.to.500

    116

    117

    117

    112

    112

    112

    107

    107

    107

    091

    091

    091

    081

    080

    080

    073

    073

    073

    066

    066

    066

    112

    114

    115

    108

    110

    110

    105

    106

    107

    093

    092

    092

    084

    082

    081

    077

    075

    074

    072

    069

    067

    Soil.thermal.resistivity in C m/W

    08 09 10 15 20 25 30

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    14/40BICC12

    Rtin ctors or dept o in (to centre o cbe or treoi

    roup o cbes)

    group rtin ctors or circuits o tree sine core cbes in

    treoi or id t toucin, in orizont ortion

    Tbe 4

    Tbe 5

    Depth.of.laying

    m

    050060080100125

    150

    175

    200

    250

    300

    or.more

    100099097095094

    093

    092

    091

    090

    089

    100098096093092

    090

    089

    088

    087

    085

    100097094092089

    087

    086

    085

    084

    082

    --

    100098096

    095

    094

    092

    091

    090

    --

    100097095

    093

    091

    089

    088

    086

    Up.to.50mm2

    600/1000.Volt 1900/3300.Volt

    70mm2to.300mm2

    Above.300mm2 Up.to.300mm2 Above.300mm2

    Number.of.Circuits

    600/1000

    Volt.cables

    1900/3300

    Volt.cables

    2

    3

    4

    5

    6

    078

    066

    061

    056

    053

    078

    066059

    055

    052

    080

    068062

    058

    055

    082

    071065

    061

    058

    086

    077072

    068

    066

    089

    080077

    074

    072

    091

    083080

    078

    076

    081

    070

    064

    060

    057

    083

    073

    068

    064

    061

    088

    079

    073

    073

    071

    091

    084

    081

    079

    078

    093

    087

    085

    085

    082

    2

    34

    5

    6

    Spacing.of.Circuits

    Touching.+

    Trefoil Laid.flat 015.m* 030.m 0545.m 060.m

    *. This.spacing.will.not.be.possible.for.some.of.the.larger.diameter.cables

    +. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.

    appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel

    SPaCINgSPaCINg

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    15/40BICC

    SPaCINg

    group rtin ctors or uticore cbes in orizont ortion

    Recoended duct diensions nd cbe sizes

    Tbe 6

    Tbe 7

    Number.of.Cables.in.Group

    Overall.cable.diameter

    mm

    Up.to.and.including.65

    Above.65.up.to.and.including.90

    100

    125

    130

    160

    Inside.diameter

    mm

    Outside.diameter

    mm

    Spacing

    Duct

    Touching+ 015.m 030.m 045.m 060.m

    600/1000

    volt.cables

    1900/3000volt.cables

    2

    3

    4

    5

    6

    081

    070

    063

    059

    055

    087

    078

    074

    070

    068

    091

    084

    081

    078

    077

    093

    088

    086

    084

    083

    095

    090

    089

    087

    087

    2

    3

    4

    5

    6

    080

    068

    062

    057

    054

    085

    076

    071

    066

    064

    089

    081

    077

    073

    071

    091

    084

    081

    078

    077

    093

    087

    084

    082

    081

    CaBlES INSTallED IN DUCTS

    +. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.

    appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel

    The.term.ducts.applies.to.single.way.earthenware,.fibre.or.ferrous.pipes

    Ratings. for. cables.installed. in.single. way. ducts,.underground,. have. been. based.on. values.of. soil. temperature. and. soil. thermal.

    resistivity.which.are.generally.representative.of. conditions.in.the.United.Kingdom.Rating.factors.to.take.account.of.variations.in.

    ground.temperatures.are.given.in.Table.3.Where.conditions.of.operation.can.be.fairly.accurately.estimated,.and.knowledge.of.the.

    soil.along.the.route.is.available,.it.is.possible.to.determine.the.ratings.more.precisely.by.the.use.of.estimated.maximum.ground.

    temperature,.the.soil.thermal.resistivity.factors,.grouping.factors,.and.factors.for.the.depths.of.laying.given.in.Tables.8.to.11.

    Rtin ctors or round teperture

    Note:.Same.as.for.direct.in.ground,.refer.to.Table.2.

    13BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    16/40BICC14

    Rtin ctors o rition in ter resistiit o soi

    (ere ues)Tbe 8

    Size.of.cable

    mm2

    Single.Core.Cable

    Up.to.150

    From.185.to.300

    From.400.to.1000

    Multicore.Cables

    Up.to.16

    From.25.to.150

    From.185.to.500

    Soil.thermal.resistivity in C m/W

    08

    110

    111

    112

    104

    106

    107

    107

    108

    108

    103

    104

    105

    104

    105

    105

    102

    103

    103

    094

    093

    093

    097

    095

    095

    086

    085

    084

    092

    090

    088

    080

    079

    078

    088

    085

    083

    076

    075

    074

    086

    081

    078

    09 10 15 20 25 30

    Rtin ctors o dept o in (to centre o duct

    or treoi roup o ducts)Tbe 9

    Depth.in.laying

    m

    050

    060

    080

    100

    125

    150

    175

    200

    250

    300

    or.more

    100

    098

    095

    093

    091

    089

    088

    087

    086

    085

    100

    099

    098

    096

    095

    094

    094

    093

    092

    091

    -

    -

    100

    098

    095

    093

    092

    090

    089

    088

    -

    -

    100

    099

    097

    096

    095

    094

    093

    092

    600/1000.Volt 1900/3300.Volt

    Single.Core Multicore Single.Core Multicore

    group rtin ctors or sine core cbes in treoi

    sine w ducts, orizont ortion (ere ues)Tbe 10

    Number.of.Circuits

    600/1000

    Volt.Cables

    1900/3300

    Volt.Cables

    2

    3

    4

    5

    6

    087

    078

    074

    070

    069

    085

    075

    070

    067

    064

    088

    080

    077

    074

    072

    090

    083

    080

    078

    076

    091

    084

    081

    079

    078

    093

    087

    085

    083

    082

    2

    3

    4

    5

    6

    Spacing

    Touching.+ 045.m 060.m

    SPaCINg

    +. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.

    appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    17/40BICC 15

    group rtin ctors or uticore cbes in sine w ducts,

    orizont ortion (ere ues)

    Rtin ctors or oter bient ir tepertures

    Tbe 11

    Tbe 12

    Number.of.Ducts

    in.GroundSpacing

    Touching.+ 030.m 045.m 060.m

    600/1000

    volt.cables

    1900/3000

    volt.cables

    2

    3

    4

    5

    6

    090

    083

    079

    075

    073

    088

    080

    076072

    069

    091

    085

    081078

    076

    093

    088

    085083

    081

    094

    090

    088086

    085

    093

    088

    085

    083

    082

    095

    091

    089

    088

    087

    096

    093

    092

    091

    090

    2

    3

    45

    6

    +. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.

    appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel

    It.is.anticipated.that.many.of.the.in.air.installations.will.be.in.buildings,.and.the.ratings.are.therefore.given.in.accordance.with.IEE.

    Wiring.Regulations.for.Electrical.Installations,.16th.Edition.

    It soud be noted tt rtins or cbes run in ree ir e been bsed on te ssuption tt te re sieded ro

    te direct rs o te sun witout restriction o entition. Te rtin or cbes subjected to direct sunit soud bereduced to tke ccount o tis ctor nd urter uidnce on tis subject is ibe on request.

    Deined conditions o insttion

    The.in-air.current.ratings.given.in.relevant.Tables.between.18.to.34.are.based.on.the.installation.conditions.in.air.as.follows:

    () Sine core cbes(1). Two.single.core.cables.are.installed.one.above.the.other,.fixed.to.the.vertical.surface.of.a.wall.or.open.cable.trench,.

    the.distance.between.the.wall.and.the.surface.of.the.cable.being.not.less.than.20mm

    .

    . Cables.are.installed.at.a.distance.between.centres.of.twice.the.overall.diameter.of.the.cable,.ie.2D,.where.D.=..

    overall.diameter.of.cable.

    (2). Three.single.core.cables.are.installed.in.trefoil.formation,.fixed.to.the.vertical.surface.of.a.wall.or.open.cable.trench,.

    the.cables.touching.throughout.and.the.distance.between.the.wall.and.the.surface.of.the.nearest.cable.being.not.less.

    than.20mm

    . The.cables.are.assumed.to.be.remote.from.iron,.steel.or.ferro-concrete,.other.than.the.cable.supports.Single.core.. .

    armoured.cables.to.be.electrically.bonded.at.each.end.of.the.run.

    (b) muticore Cbes. Cables.of.all.types.other.than.single.core.cables.are.installed.singly,.fixed.to.the.vertical.surface.of.a.wall.or.open.cable.trench,.the.distance.between.the.surface.of.the.cable.and.the.wall.being.not.less.than.20.mm.in.every.instance.

    If.it.is.necessary.for.cables.to.be.installed.at.distances.less.than.those.described.above,.then.the.values.tabulated.under.the.heading.

    Clipped.direct.to.a.surface.in.the.IEE.Wiring.Regulations.should.be.employed.

    SPaCINg

    CaBlES INSTallED IN aIR

    Air.Temperature

    XLPE.Insulated

    25C

    104 10 096 091 087 082 076

    30C 35C 40C 45C 50C 55C

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    18/40BICC16

    Tbe 13

    ShORT CIRCUIT RaTINgS CONDUCTORS

    Copper Conductors

    auiniu ConductorsThe.values.of.fault.current.given.in.the.graph.are.based.on.the.cable.being.fully.loaded.at.the.start.of.the.short.circuit.(conductor.

    temperature 90C) and a final conductor. temperature. of. 250.C. It should be ensured that the accessories associated withthe.cables.are.also.capable.of.operation.at.these.values.of.fault.

    current.and.temperature.

    Note:. With. XLPE. cables. the. use. of. soldered. type. connectors.

    (instead.of.the.compression.type).is.not.recommended.since.their.

    use. in.the. system. would.limit. the.final. conductor.temperature.to 160 C (and consequently reduce the fault current rating byapproximately.30.per.cent).

    Conductor.size.... ....Short.circuit.ratings.for.1.second.in.KA. mm2..... .... ....Copper.conductor.. ..Aluminium.Conductor

    . 15. 021. 014

    . 25. 036. 024

    . 4. 057. 038

    . 6. 086. 056

    . 10. 143. 094

    . 16. 229. 150

    . 25. 358. 235

    . 35. 500. 329

    . 50. 715. 470

    . 70. 1001. 658

    . 95. 1359. 893

    . 120. 1716. 1128

    . 150. 2145. 1410

    . 185. 2646. 1739

    . 240. 3432. 2256

    . 300. 4290. 2820

    . 400. 5720. 3760

    . 630. 9009. 5922

    . 800. 11440. 7520

    . 1000. 14300. 9400

    Note:.For.any.other.duration.t.seconds.divide.the.given.

    value by t

    0.5

    0.1

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    19/40BICC

    ShORT CIRCUIT RaTINgS aRmOUR

    XlPE INSUlaTED CaBlES

    arour fut currents to ert (or ut durtion o 1 second) Tbe 14

    Nominal

    Area.of

    Conductor

    mm2

    . 16

    . 25

    . 35

    . 50

    . 70. 95

    . 120

    . 150

    . 185

    . 240

    . 300

    . 400

    . 500

    . 630

    . 800

    . 1000

    Aluminium.Wire.Armour Steel.Wire.Armour

    600/1000.V 1900/3300.V600/1000.V

    Single.Core

    amp

    Single.Core

    amp

    Two.Core

    amp

    Three.Core

    amp

    Four.Core

    amp

    Four.Core

    (reduced.neutral)

    amp

    Three.Core

    amp

    XLPE

    . -

    .

    . -

    . -

    . 4000*...

    . 4700*. 5200*

    . 5700*

    . 6400

    . 7100

    . 7900

    . 8800

    . 12400

    . 13800

    . 15400

    . 21300

    . 23400

    XLPE

    . -

    . -

    . -

    . .4700*

    . .5200*. .5700*

    . 6100

    . .6400

    . 7100

    . ..7800

    . ..8500

    . 12000

    . 13300

    . 14900

    ........-

    ........-

    XLPE

    1800

    1900

    2800

    3100

    36005100

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    XLPE

    . 2000

    . 2800

    . 3200

    . 3500

    . 4100

    . 5800

    . 6400

    . 9200

    .10100

    . 11500

    .12300

    . -

    . -

    . -

    . -

    . -

    XLPE

    . 2200

    . 3200

    . 3600

    . 4100

    . 6000. 6700

    . 9400

    . 10500

    . 11700

    . 13200

    .

    . 14600

    . 20700

    . 22500

    . -

    . -

    . -

    XLPE

    .......-

    3200

    3400

    3900

    59006600

    7500

    10000

    11500

    12800

    13900

    20700

    22500

    ......-

    ......-

    ......-

    XLPE

    3700

    4200

    4700

    5600

    62006900

    9400

    10100

    10800

    11900

    13000

    ......-

    ......-

    ......-

    ......-

    ......-

    1900/3300.V

    *. Based.on.wire.diameters.larger.than.those.specified.in.BS.5467.Refer.to.Table.17,.33.and.35.for.single.core.cable.armour.

    wire.diameter

    Notes:. . 1. The.ratings.given.in.the.Table.above.are.based.on.a.fault.duration.of.one.second.and.an.armour.temperature.rise..

    from 80C at commencement of the fault to a final temperature of 200C..

    . . 2. The.asymmetrical.fault.rating.of.the.smaller.sizes.may.be.decided.by.the.short.circuit.capability.of.the.. .

    . . conductor.rather.than.the.armour.rating.It.is.therefore.necessary.to.compare.the.two.ratings

    17BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    20/40BICC

    Withstranded

    aluminium

    conductor

    600/1000V

    Withstranded

    copper

    conductor

    600/1000V

    18

    Tbe15

    600/1000v

    MaximumresistanceofCable-Armourinohms/kmat20C

    N

    om

    inal

    Area

    o

    fCon

    ductor

    mm

    216

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    630

    800

    1000

    11

    5

    07

    27

    05

    24

    03

    87

    02

    68

    01

    93

    01

    53

    01

    24

    00

    991

    00

    754

    00

    601

    00

    470

    00

    366

    00

    283

    00

    221

    00

    176

    1910

    1200

    0868

    0641

    0443

    0320

    0253

    0206

    0164

    0125

    0100

    00

    778

    00

    605

    00

    469

    00

    367

    00

    291

    - - -1

    30

    07

    5

    06

    7

    06

    1

    04

    2

    03

    8

    03

    4

    03

    1

    02

    2

    02

    0

    01

    8

    01

    3

    01

    2

    - - -0

    75

    06

    7

    06

    1

    04

    2

    03

    9

    03

    7

    03

    4

    03

    1

    02

    2

    02

    0

    01

    8

    01

    3

    01

    2

    37

    0

    37

    0

    26

    0

    23

    0

    20

    0

    14

    0

    13

    0

    12

    0

    08

    2

    07

    3

    06

    7

    05

    9- - -

    35

    0

    25

    0

    23

    0

    20

    0

    18

    0

    13

    0

    12

    0

    07

    8

    07

    1

    06

    3

    05

    8

    05

    2- - -

    19

    0

    17

    0

    18

    0

    13

    0

    12

    0

    11

    0

    07

    6

    07

    1

    06

    5

    05

    9

    05

    5

    05

    0- - -

    31

    0

    23

    0

    20

    0

    18

    0

    12

    0

    11

    0

    07

    6

    06

    8

    06

    1

    05

    4

    04

    9

    03

    5- - -

    -2

    30

    21

    0

    19

    0

    13

    0

    11

    0

    09

    6

    07

    1

    06

    3

    05

    6

    .0

    52

    04

    6- - -

    Copper

    Con

    ductor

    *

    Alum

    inium

    Con

    ductor

    Sing

    leCore

    600/1000V

    600/1000V

    600/1000V

    600/1000V

    1900/3300V

    ThreeC

    ore

    Twocore

    Four

    Core

    **

    (equalneutral)

    Four

    Core

    (reducedneutral)

    Aluminiumwirearmour

    Withstrandedcoppercon

    ductor&GalvanisedSteelWireArmour

    CONDU

    CTORaNDaRmOURRESISTaNCEvalUES

    SINglEaNDmUlTICORECa

    BlEShavINgWIREaRmOUR

    *

    Thevaluesg

    ivenare

    forp

    lainannea

    ledcoppercon

    ductors

    For

    tinnedcon

    ductors

    referenceshou

    ldbemade

    toBS6360

    **

    Mu

    lticoreca

    blesw

    ithstran

    ded

    Alum

    iniumcon

    ductor

    havesame

    Armourresistan

    cesas

    thosew

    ithCoppercon

    ductors

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    21/40BICC 19

    CONTRIBUTION By CaBlE TO EaRTh faUlT lOOP ImPEDaNCE

    Copper conductor, XlPE insuted roured cbes to BS 5467/BS6724

    Tbe 16600/1000 v

    Conductor

    mm2

    16

    253550

    7095

    120

    150

    185

    240

    300

    400

    667

    587402355

    298

    211

    -

    -

    --

    -

    -

    642

    435377317

    273

    198

    179

    123

    110

    097

    089

    -

    591

    410339292

    198173

    125

    110

    098

    086

    078

    060

    -

    410352305

    210173

    149

    114

    100

    088

    081

    072

    2.core

    Contribution.by.cable.to.earth.fault.loop.impedance.milli.ohms/metre

    4.core3.core 4.core(with.reduced.neutral)

    The.following.table.gives.the.estimated.impedance.of.copper.phase.conductor.and.steel.wire.armour.in.series,.ie.the.

    contribution.to.earth.fault.loop.impedance.by.the.cable,.allowing.for.the.estimated.increase.in.temperature.due.to.the.

    flow.of.the.earth.fault.current.The.earth.fault.current.is.taken.to.be.that.which.gives.interruption.in.5.seconds.when.the.protective.device.is.a.standard.type.having.a.rating.not.higher.than.the.current.rating.of.the.cable

    Note:.For.information.on.maximum.length.of.cable.that.meets.the.earth.fault.loop.impedance.requirement.for.5.second.

    disconnection,.refer.to.Ducabs.Technical.Department

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    22/40BICC20

    XlPE INSUlaTED CaBlES TO BS 5467

    DImENSIONS aND WEIghTS

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    SINglE CORE CaBlES

    600/1000 v Tbe 17Unroured nd roured, PvC seted cbes

    Nominal

    area.of

    conductor

    mm2

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    630

    800

    1000

    10

    11

    11

    12

    14

    16

    17

    18

    20

    22

    24

    26

    28

    142

    162

    183

    202

    224

    247

    277

    306

    342

    380

    429

    478

    530

    250

    330

    430

    510

    630

    760

    970

    1190

    1500

    1900

    2420

    3120

    3780

    540

    760

    1020

    1270

    1560

    1930

    2510

    3120

    3970

    4980

    6400

    8210

    10275

    126

    145

    164

    180

    198

    220

    246

    273

    312

    360

    400

    458

    508

    16*

    16*

    16*

    16*

    16

    16

    16

    16

    20

    20

    20

    25

    25

    184

    202

    223

    242

    274

    300

    328

    356

    405

    442

    488

    554

    606

    460

    560

    690

    800

    970

    1150

    1380

    1640

    2130

    2610

    3180

    4230

    5000

    800

    990

    1280

    1550

    1900

    2320

    2930

    3580

    4600

    5680

    7160

    9315

    11490

    Thickness

    of

    insulation

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Diameter

    under

    armour

    mm

    Armourh

    wire

    diameter

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)

    Single.core.unarmoured.cables.are.as.per.BS.7889*.Wire.diameters.are.larger.than.those.specified.in.BS.5467hAluminium.wire.armour.for.AC.system

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    23/40BICC 21

    Stranded.Aluminium.Conductors

    600/1000 v

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    630

    800

    1000

    235

    290

    345

    390

    435

    490

    560

    630

    700

    770

    840

    888

    942

    235

    280

    330

    370

    405

    440

    500

    550

    580

    620

    670

    692

    735

    222

    285

    346

    402

    463

    529

    625

    720

    815

    918

    1027

    1119

    1214

    087

    062

    047

    039

    033

    028

    024

    021

    020

    018

    017

    017

    016

    093

    070

    056

    048

    043

    039

    035

    032

    030

    028

    026

    025

    024

    087

    062

    047

    039

    033

    028

    024

    021

    020

    018

    017

    017

    016

    175

    220

    260

    295

    330

    375

    435

    490

    540

    580

    630

    180

    220

    260

    295

    330

    365

    410

    455

    480

    510

    540

    162

    207

    252

    292

    337

    391

    465

    540

    625

    714

    801

    140

    098

    072

    058

    048

    039

    031

    027

    035

    031

    028

    160

    100

    079

    066

    057

    049

    042

    038

    038

    035

    032

    140

    098

    074

    060

    049

    041

    034

    029

    025

    022

    020

    Tbe 18

    CURRENT RaTINgS (aC)

    Stranded.Copper.Conductors

    Nominal.

    area.of

    conductor

    ....mm2.

    Direct.in

    ground

    amps

    Installed

    in.airamps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.airamps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    Direct.in.ground..Trefoil.touching

    Single.way.ducts.-.ducts.touching

    Spacing.in.air.-.As.shown.above.(D.=.Cable.diameter)

    Installation.conditions.for.above.ratings:

    Ambient air temperature:30C

    Ground temperature: 15CDepth.of.laying:05.m

    Soil thermal resistivity: 1.2C m/W

    Maximum conductor operating temperature at rated current is 90C

    For.rating.factors.see.Tables.2.to.6.and.8.to.12

    .Aluminium.Conductors

    600/1000 v

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    630

    800

    1000

    230

    285

    335

    385

    435

    490

    570

    650

    740

    840

    960

    1120

    1300

    240

    295

    345

    395

    445

    500

    580

    650

    750

    850

    960

    1130

    1320

    209

    270

    330

    385

    445

    511

    606

    701

    820

    936

    1069

    1214

    1349

    085

    061

    045

    036

    031

    026

    022

    019

    017

    016

    015

    015

    014

    093

    070

    056

    048

    043

    039

    035

    032

    030

    028

    026

    025

    024

    087

    061

    045

    037

    031

    026

    022

    020

    018

    016

    015

    015

    014

    175

    215

    255

    295

    325

    370

    430

    490

    550

    620

    690

    180

    220

    260

    300

    335

    375

    440

    510

    570

    640

    730

    159

    206

    253

    296

    343

    395

    471

    544

    638

    743

    849

    140

    098

    071

    057

    047

    039

    031

    026

    036

    033

    028

    150

    110

    079

    066

    057

    049

    042

    038

    038

    035

    032

    145

    098

    073

    059

    047

    039

    032

    027

    023

    020

    019

    Tbe 19

    Stranded.Copper.Conductors

    Nominal.

    area.of

    conductor

    mm2

    Direct.in

    ground

    amps

    Installedin.airamps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installedin.airamps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    SINglE CORE CaBlES

    aroured PvC seted cbes

    Unroured PvC seted cbes

    3D 3D

    3D3D

    BICC

    In.single

    way.ducts

    amps

    In.single

    way.ducts

    amps

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    24/40BICC22

    XlPE INSUlaTED CaBlES TO BS 5467

    DImENSIONS aND WEIghTS

    600/1000 v Tbe 20Unroured nd roured, PvC seted cbes

    Nominal

    area.of

    conductor

    mm2

    16*

    25*

    35*

    50

    70

    95

    120

    150

    185

    240

    300

    07

    09

    09

    10

    11

    11

    12

    14

    16

    17

    18

    170

    202

    225

    204

    231

    265

    284

    317

    351

    403

    443

    415

    480

    497

    690

    850

    1170

    1450

    1810

    2280

    2760

    475

    740

    955

    1100

    1520

    2050

    2610

    3220

    4030

    5200

    6430

    152

    185

    215

    187

    215

    246

    268

    297

    333

    381

    423

    . 125

    . 125

    . 160

    . 160

    . 160

    . 200

    . 200

    . 200

    . 250

    . 250

    . 250

    204

    241

    277

    258

    290

    331

    361

    393

    447

    490

    535

    915

    1255

    1430

    1780

    1950

    2440

    3050

    3690

    4380

    5100

    900

    1240

    1710

    1800

    2320

    3150

    3880

    4820

    5920

    7300

    8770

    Thickness

    of

    insulation

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Diameter

    under

    armour

    mm

    Armour

    wire

    diameter

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    TWO CORE CaBlES

    *.Circular.conductor,.all.others.are.sector.shaped

    Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    25/40BICC

    In.single

    way.ducts

    amps

    In.single

    way.ducts

    amps

    23

    Aluminium.Conductors.

    600/1000 v

    16*

    25*35*

    50

    70

    95

    120

    150

    185

    240

    300

    140

    180215

    255

    315

    381

    410

    472

    539

    636

    732

    115

    145175

    210

    260

    313

    344

    384

    432

    504

    560

    115

    152188

    228

    291

    354

    430

    480

    540

    630

    700

    29

    1913

    10

    07

    05

    04

    04

    03

    02

    02

    29

    1913

    10

    07

    05

    04

    04

    03

    02

    02

    29

    1913

    10

    07

    05

    04

    04

    03

    02

    02

    135165

    195

    240

    288

    110130

    155

    195

    237

    112138

    166

    211

    254

    3122

    17

    11

    08

    3122

    17

    11

    08

    3122

    17

    11

    08

    Tbe 21

    CURRENT RaTINgS (aC)

    Stranded.Copper.Conductors

    Nominal.

    area.of

    conductor

    mm2

    Direct.in

    ground

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    .Aluminium.Conductors

    600/1000 v

    16*

    25*

    35*

    50

    70

    95120

    150

    185

    240

    300

    140

    180

    215

    255

    315

    380410

    473

    542

    641

    741

    115

    140

    170

    205

    255

    311344

    384

    432

    504

    560

    115

    149

    185

    225

    289

    352430

    480

    540

    630

    700

    29

    19

    13

    10

    07

    0504

    04

    03

    02

    02

    29

    19

    13

    10

    07

    0504

    04

    03

    02

    02

    29

    19

    13

    10

    07

    0504

    04

    03

    02

    02

    135

    165

    195

    240

    285

    105

    130

    150

    195

    235

    108

    135

    164

    211

    257

    31

    22

    17

    12

    08

    31

    22

    17

    12

    08

    31

    22

    17

    12

    08

    Tbe 22

    Stranded.Copper.Conductors

    Nominal.

    area.of

    conductor

    mm2

    Direct.in

    ground

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    TWO CORE CaBlES

    aroured PvC seted cbes

    Unroured PvC seted cbes

    Direct.in.ground..Cables.touching

    Single.way.ducts.-.ducts.touching

    *.Circular.conductors,.all.others.are.sector.shaped

    Note:. (1).50.mm2.and.above.are.with.D-shaped.conductor

    . . (2).Unarmoured.cables.are.as.per.IEC:60502.(part.1)

    Installation.conditions.for.above.ratings:

    Ambient air temperature:30C

    Ground temperature: 15C

    Depth.of.laying:05.m

    Soil thermal resistivity: 1.2C m/W

    Maximum conductor operating temperature at rated current is 90C

    For.rating.factors.see.Tables.2.to.6.and.8.to.12

    *.Circular.conductor,.all.others.are.sector.shaped

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    26/40BICC24

    XlPE INSUlaTED CaBlES TO BS 5467

    DImENSIONS aND WEIghTS

    600/1000 v Tbe 23

    Nominal

    area.of

    conductor

    mm2

    16*

    25*

    35*

    50

    70

    95

    120

    150

    185

    240

    300

    400

    07

    09

    09

    10

    11

    11

    12

    14

    16

    17

    18

    20

    180

    215

    240

    246

    280

    310

    348

    385

    440

    495

    535

    592

    500

    610

    740

    1050

    1170

    1440

    2300

    2750

    3020

    3660

    3730

    675

    990

    1295

    1640

    2220

    2980

    3730

    5195

    6470

    8380

    10420

    11575

    160

    200

    227

    230

    260

    300

    328

    368

    415

    460

    515

    564

    ..125

    16

    16

    16

    16

    20

    20

    25

    25

    25

    25

    25

    216

    267

    294

    285

    322

    370

    404

    455

    498

    551

    602

    666

    1220

    1415

    1550

    1810

    2500

    2870

    3660

    4320

    5170

    6100

    7050

    1130

    1710

    2100

    2450

    3120

    4310

    5160

    7160

    8600

    10755

    13080

    15810

    Thickness

    of

    insulation

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Diameter

    under

    armour

    mm

    Armour

    wire

    diameter

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    ThREE CORE CaBlES

    Unroured nd roured, PvC seted cbes

    *.Circular.conductors,.all.others.are.sector.shaped

    Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    27/40BICC 25

    . Stranded.Aluminium.Conductors.

    600/1000 v

    16

    2535

    50

    70

    95

    120

    150

    185

    240

    300

    400

    115

    150180

    215

    265

    315

    360

    405

    460

    530

    590

    667

    94

    125150

    175

    215

    260

    300

    335

    380

    440

    495

    570

    99

    131162

    197

    251

    304

    353

    406

    463

    546

    628

    728

    25

    1712

    09

    06

    05

    04

    03

    03

    02

    02

    02

    25

    1712

    09

    06

    05

    04

    03

    03

    02

    02

    02

    25

    1712

    09

    06

    05

    04

    03

    03

    02

    02

    02

    89

    115135

    165

    200

    240

    275

    310

    350

    410

    460

    520

    72

    94110

    135

    165

    200

    230

    255

    295

    340

    385

    443

    74

    98120

    145

    185

    224

    264

    305

    350

    418

    488

    562

    42

    2719

    14

    10

    07

    06

    05

    04

    03

    03

    02

    42

    2719

    14

    10

    07

    06

    05

    04

    03

    03

    02

    42

    2719

    14

    10

    07

    06

    05

    04

    03

    03

    02

    Tbe 24

    CURRENT RaTINgS (aC)

    Stranded.Copper.Conductors

    Nominal.

    area.of

    conductor

    mm2

    Direct.in

    ground

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metreApproximate.voltage.drop.per.

    ampere.per.metre

    Direct.in.ground..Cables.touching

    Single.way.ducts.-.ducts.touching

    Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)

    Installation.conditions.for.above.ratings:

    Ambient air temperature:30C

    Ground temperature: 15C

    Depth.of.laying:05.m

    Soil thermal resistivity: 1.2C m/W

    Maximum conductor operating temperature at rated current is 90C

    For.rating.factors.see.Tables.2.to.6.and.8.to.12

    Stranded.Copper.Conductors Stranded.Aluminium.Conductors

    600/1000 v

    16

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    400

    120

    145

    180

    215

    265

    315

    365

    405

    465

    540

    600

    675

    93

    125

    145

    175

    215

    255

    300

    330

    380

    440

    500

    575

    100

    127

    158

    192

    246

    298

    346

    399

    456

    538

    621

    741

    25

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    25

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    25

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    115

    135

    165

    200

    240

    275

    310

    350

    415

    465

    523

    92

    110

    135

    165

    195

    225

    255

    290

    340

    385

    443

    97

    120

    146

    187

    227

    263

    304

    347

    409

    471

    570

    27

    19

    1410

    07

    06

    05

    04

    03

    03

    02

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    Tbe 25

    Nominal.

    area.of

    conductor

    mm2

    Direct.in

    ground

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    ThREE CORE CaBlES

    aroured PvC seted cbes

    Unroured PvC seted cbes

    BICC

    In.single

    way.ducts

    amps

    In.single

    way.ducts

    amps

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    28/40BICC26

    XlPE INSUlaTED CaBlES TO BS 5467

    DImENSIONS aND WEIghTS

    600/1000 v Tbe 26Unroured nd roured, PvC seted cbes

    Nominal

    area.of

    conductor

    mm2

    16*

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500#

    07

    09

    09

    10

    11

    11

    12

    14

    16

    17

    18

    20

    22

    200

    210

    245

    265

    310

    352

    390

    435

    490

    545

    610

    675

    742

    -

    520

    650

    900

    1210

    1550

    1910

    2410

    2990

    3890

    4730

    5780

    7500

    780

    1160

    1540

    2100

    2950

    3970

    4960

    6160

    7690

    10070

    12490

    15620

    19900

    180

    200

    228

    255

    295

    335

    375

    415

    460

    525

    575

    650

    726

    ..125

    16

    16

    16

    20

    20

    25

    25

    25

    25

    25

    ..315

    ..315

    234

    261

    286

    320

    377

    417

    471

    514

    566

    630

    688

    781

    820

    ........-

    1200

    1420

    1770

    2500

    2980

    3950

    4600

    5430

    6660

    7770

    10380

    12200

    1320

    1840

    2310

    2970

    4240

    5400

    7000

    8350

    10130

    12840

    15530

    19950

    24360

    Thickness

    of

    insulation

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Diameter

    under

    armour

    mm

    Armour

    wire

    diameter

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    fOUR CORE CaBlES

    *.Circular.conductors,.all.others.are.sector.shaped

    #Cable.as.per.IEC.60502.(Part.1)

    Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    29/40BICC 27

    Direct.in.ground..Cables.touching

    Single.way.ducts.-.ducts.touching

    Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)

    Installation.conditions.for.above.ratings:

    Ambient air temperature: 30C

    Ground temperature: 15C

    Depth.of.laying:.05.mSoil thermal resistivity: 1.2C m/W

    Maximum conductor operating temperature at rated current is 90C

    For.rating.factors.see.Tables..2.to.6.and.8.to.12

    Stranded.Copper.Conductors .Aluminium.Conductors

    600/1000 v

    16

    25

    3550

    70

    95

    120

    150

    185

    240

    300

    400

    500

    120

    145

    180215

    265

    315

    365

    405

    465

    540

    600

    675

    730

    93

    125

    145175

    215

    255

    300

    330

    380

    440

    500

    575

    610

    100

    127

    158192

    246

    298

    346

    399

    456

    538

    621

    741

    814

    25

    17

    1209

    06

    05

    04

    03

    03

    02

    02

    02

    02

    25

    17

    1209

    06

    05

    04

    03

    03

    02

    02

    02

    02

    25

    17

    1209

    06

    05

    04

    03

    03

    02

    02

    02

    02

    .89

    115

    135165

    200

    240

    275

    310

    350

    415

    465

    523

    565

    72

    92

    110135

    165

    195

    225

    255

    290

    340

    385

    443

    470

    74

    97

    120146

    187

    227

    263

    304

    347

    409

    471

    570

    626

    42

    27

    1914

    10

    07

    06

    05

    04

    03

    03

    02

    02

    42

    27

    1914

    10

    07

    06

    05

    04

    03

    03

    02

    02

    42

    27

    1914

    10

    07

    06

    05

    04

    03

    03

    02

    02

    Tbe 28Unroured PvC seted cbes

    Nominal.

    area.of

    conductor

    mm2

    Direct.in

    ground

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    600/1000 vTbe 27

    CURRENT RaTINgS (aC)

    Stranded.Aluminium.Conductors.

    1625

    35

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    115150

    180

    215

    265

    315

    360

    405

    460

    530

    590

    667

    720

    94125

    150

    175

    215

    260

    300

    335

    380

    440

    495

    570

    605

    99131

    162

    197

    251

    304

    353

    406

    463

    546

    628

    728

    800

    2517

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    2517

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    2517

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    89115

    135

    165

    200

    240

    275

    310

    350

    410

    460

    520

    561

    7294

    110

    135

    165

    200

    230

    255

    295

    340

    385

    443

    470

    7498

    120

    145

    185

    224

    264

    305

    350

    418

    488

    562

    618

    4227

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    4227

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    4227

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    Stranded.Copper.Conductors

    Nominal.

    area.of

    conductor

    mm2

    Direct.in

    ground

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    fOUR CORE CaBlES

    aroured PvC seted cbes

    In.single

    way.ducts

    amps

    In.single

    way.ducts

    amps

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    30/40BICC28

    XlPE INSUlaTED CaBlES TO BS 5467

    DImENSIONS aND WEIghTS

    600/1000 v Tbe 29Unroured nd roured, PvC seted cbes

    Nominal

    area.of

    conductor

    mm2

    Nominal

    area.of

    neutralconductor

    mm2

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500#

    16*

    16*

    25*

    35

    50

    70

    70*

    95

    120*

    150*

    185*

    240*

    09

    09

    10

    11

    11

    12

    14

    16

    17

    18

    20

    22

    214

    232

    261

    304

    348

    394

    425

    477

    534

    590

    670

    740

    -

    -

    860

    1080

    1390

    1820

    2190

    2630

    3500

    4240

    5560

    6700

    1070

    1360

    1920

    2610

    3500

    4540

    5440

    6760

    8900

    11000

    13900

    17560

    191

    220

    245

    285

    320

    355

    395

    435

    502

    550

    625

    688

    16

    16

    16

    20

    20

    20

    25

    25

    25

    25

    ..315

    ..315

    261

    279

    312

    366

    410

    453

    500

    553

    611

    667

    738

    839

    -

    -

    1710

    2340

    2800

    3340

    4360

    5020

    6220

    7220

    9950

    11200

    1750

    2130

    2770

    3870

    4910

    6060

    7610

    9150

    11620

    13980

    18250

    22000

    Thickness

    of

    insulation(phase)

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Diameter

    under

    armour

    mm

    Armour

    wire

    diameter

    mm

    Cable

    diameter

    overall

    mm

    Cable

    weight

    Aluminium

    kg/km

    Cable

    weight

    Copper

    kg/km

    Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    fOUR CORE CaBlES WITh REDUCED NEUTRal CONDUCTOR

    *.Circular.stranded.conductors,.all.others.are.sector.shaped

    #Cable.as.per.IEC.60502.(Part.1)

    Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    31/40BICC 29

    600/1000 v

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    16*

    16*

    25*

    35

    50

    70

    70*

    95

    120*

    150*

    185*

    240*

    150

    180

    215

    265

    315

    360

    405

    460

    530

    590

    667

    720

    125

    150

    175

    215

    260

    300

    335

    380

    440

    495

    570

    605

    131

    162

    197

    251

    304

    353

    406

    463

    546

    628

    728

    800

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    115

    135

    165

    200

    240

    275

    310

    350

    410

    460

    520

    561

    94

    110

    135

    165

    200

    230

    255

    295

    340

    385

    443

    470

    98

    120

    145

    185

    224

    264

    305

    350

    418

    488

    562

    618

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    Tbe 30

    CURRENT RaTINgS (aC)

    aroured PvC seted cbes

    Nominal.

    area.of

    conductor

    mm2

    Nominal.

    area.of

    neutral

    conductor

    mm2

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    Nominal.

    area.of

    conductor

    mm2

    Direct.in.ground..Cables.touching

    Single.way.ducts.-.ducts.touching

    *.Circular.conductors,.all.others.are.sector.shaped

    Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)

    Installation.conditions.for.above.ratings:

    Ambient air temperature:30C

    Ground temperature: 15C

    Depth.of.laying:05.mSoil thermal resistivity: 1.2C m/W

    Maximum conductor operating temperature at rated current is 90C

    For.rating.factors.see.Tables.2.to.6.and.8.to.12

    600/1000 v Tbe 31Unroured PvC seted cbes

    Stranded.Copper.Conductors Stranded.Aluminium.Conductors.

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    16*

    16*

    25*

    35

    50

    70

    70*

    95

    120*

    150*

    185*

    240*

    145

    180

    215

    265

    315

    365

    405

    465

    540

    600

    675

    730

    125

    145

    175

    215

    255

    300

    330

    380

    440

    500

    575

    610

    127

    158

    192

    246

    298

    346

    399

    456

    538

    621

    741

    814

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    17

    12

    09

    06

    05

    04

    03

    03

    02

    02

    02

    02

    115

    135

    165

    200

    240

    275

    310

    350

    415

    465

    523

    565

    92

    110

    135

    165

    195

    225

    255

    290

    340

    385

    443

    470

    97

    120

    146

    187

    227

    263

    304

    347

    409

    471

    570

    626

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    27

    19

    14

    10

    07

    06

    05

    04

    03

    03

    02

    02

    Nominal.

    area.of

    neutral

    conductor

    mm2

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Direct.in

    ground

    amps

    In.single

    way.ducts

    amps

    Installed

    in.air

    amps

    Ground

    mV

    Duct

    mV

    Air

    mV

    Current.Ratings Current.RatingsApproximate.voltage.drop.per.

    ampere.per.metre

    Approximate.voltage.drop.per.

    ampere.per.metre

    STRaNDED COPPER & alUmINIUm CONDUCTORS

    fOUR CORE CaBlES WITh REDUCED NEUTRal CONDUCTOR

    Stranded. Copper. Conductors Stranded.Aluminium. Conductors.

    *.Circular.conductors,.all.others.are.sector.shaped

    BICC

  • 7/28/2019 Dubai Cables XLPEpower Cat Web Site

    32/40BICC

    215

    210

    200

    195

    190

    185

    175

    165

    155

    150

    145

    140

    135

    130

    125120

    115

    110

    99

    97

    93

    89

    8480

    74

    68

    62

    16

    265

    260

    250

    245

    235225

    215

    205

    195

    115

    112

    110

    105

    10097

    94

    89

    84

    70

    251

    240

    230

    220

    210195

    185

    170

    150

    0607

    0599

    0589

    0580

    05720562

    0554

    0545

    0536

    185

    463

    450

    430

    415

    395370

    345

    320

    290

    0255

    0252

    0249

    0246

    02430240

    0237