dubai cables xlpepower cat web site
TRANSCRIPT
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
1/40BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
2/40BICC
Introduction..1
Customer.Service..2-3
Product.Range..4
Specification.and.Construction..4..5.
Salient.Features.of.Ducab.Cables.Design...6
Installation.and.Electrical.Data..6..19
XLPE.Insulated.Cables.to.BS.5467:.Technical.Data.Tables...20-33
l 600/1000V.rated,.Copper.and.Aluminium.Conductors..20-31
lSingle.Core.Cables..20-21
lTwo.Core.Cables..22-23
lThree.Core.Cables..24-25
lFour.Core.Cables..26-27
lFour.Core.Cables.with.Reduced.Neutral.Conductors..28-29
lThree.and.Four.Core.Armoured.Cables..30
l 1900/3300V.rated,.Armoured.Copper.Conductors..31
l XLPE.insulated.Lead.Sheathed.Armoured.Cables.to.BS.5467..32-33.
Advantages.of.XLPE.Insulated.Cables..34
LSF.Cables..34
XLPE.Cable.Voltage.Drop.Data.for.partial.loads..35
Components.Reference.Chart..36-37
Ducab. is. listed. in. the. following. publication. issued. by. the. Department. of. Trade. and. Industry. of.
the.United.Kingdom.
THE.DTI.QA.REGISTER.-.PRODUCTS.AND.SERVICES.LIST
Only.those. companies.whose. quality. system. is. assessed. and. certified. by. UK.accredited. certification.
bodies.appear.in.the.above.publication.
CONTENTS
Pe
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
3/40BICC 1
INTRODUCTION
Dubai.Cable.Company.(Private).Limited..Ducab..is.a.joint.venture.between.the.Government.of.Dubai,.the.Government.of.Abu.Dhabi.through.General.Industry.Corporation.Ducab.is.located.on.a. site.of.54.hectares.in.Jebel.Ali,.Dubai,.in.
the.United.Arab. Emirates.A.major. factory. expansion.took. place. in. 1991.with. production.capacity.being. more.than.
doubled.In.1999,.Ducab.again.increased.production.capacity.for.low.voltage.cables.and.commissioned.a. world.class.
production.and.testing.facilities.for.Powerplus.Medium.Voltage.cables.In.2001,.Ducab.installed.the.second.Medium.
Voltage.CCV.line.The.current.factory.floor.area.is.16,000.m2.Ducab.manufactures.electric.cables.to.the.highest.quality.
standards.
This.catalogue.provides.working.information.on.Ducabs.complete.range.of.XLPE.Power.Cables.rated.up.to.33.kV.and.
also.includes.data.on.components.Separate.catalogues.are.available.for.Ducabs.range.of.Control.and.Auxiliary.Cables,.
Wiring. Cables,.Smokemaster LSF. Cables. and. Powerplus. Medium. Voltage. Cables. Details. of. PVC. Power.
Cables.are.available.on.request
Due.to.the.wide.range.of.cables.in.the.catalogue,.it.is.advisable,.when.ordering,.to..provide.as.much.information.as.possible.Please.use.the.following.table.as.a.guide:
Specialist. advice. and. assistance. on. all. matters. concerning. PVC. and. XLPE. insulated. power. cables.
is. available. from. Ducab. Sales. Offices. or. direct. from. Dubai. Cable. Company. (Private). Limited,.
P.O.Box.11529,.Dubai,.U.A.E,.Tel:.971-4-836600,.Fax:.971-4-835965
TEChNICal aDvISORy SERvICE
.........The.following.details.will.ensure.that.your.enquiries.and.orders.are.dealt.with.quickly.and.efficiently:
. 1. Length.of.cables.required.and.individual.drum.lengths*
. 2. Voltage.designation
. 3. Relevant.British.or.International.Standard
. 4. Number.of.cores
. 5. Conductor.size.and,.where.applicable,.size.of.reduced.neutral.conductor
. 6. Conductor.material.ie.copper,.aluminium
. 7. Type.of.insulation
. 8. Type.of.bedding
. 9. Type.of.armour
. 10. Type.of.outer.sheath
. 11. Any.other.special.requirement,.eg.circular.conductors,.special.PVC.sheath.material,.drum..
. . weight.limitation,.etc
. . *.Cables.are.normally.supplied.in.lengths.of.300.metres,.500.metres.and.1000.metres.. .
. . . depending.on.conductor.size.Other.lengths.can.be.supplied.if.required
. . ..
ORDERINg aDvICE
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
4/40BICC2
Dubai. is. the. premier. cable. manufacturer. in. the. United. Arab. Emirates. and,. since. 1979,. has. been. meeting. the.
requirements. of. customers. throughout. the. Middle. and. Far. East. Ducabs. cables. are. used. by. some. of. the. most. .
demanding.utilities.in.the.world,.for.the.following.reasons:
Product QuitDucab.is. committed.to. supplying. its. customers. with. the. highest. quality. of. product. and. of. service. Ducabs. Power..
cables. have. been. type. approved. by. Lloyds. Register. of. the. UK. and. have. undergone.
rigorous.type.testing.by.BASEC.(British.Approvals.Service.for.Cables).They.fully.conform.
to.BS.6004.and.BS.5467.specifications.for.PVC.and.XLPE.insulated.cables.respectively,.for.
electricity.supply,.up.to.and.including.33kV.ratings.
In.addition,. Ducab.was. presented. with. the. Dubai. Quality.Award. 1994,.for. the. best. local.
industrial.company.of.the.year.Four.years.later,.Ducab.was.presented.with.the.Dubai.Quality.
Award.98.Gold.Category.The.Gold.Award.rewards.the.most.distinguished.companies.which.
are.judged.to.be.world.class
ReibiitSpecifying. the. right. cable. for. a. particular. application. is. the. first. step. The. key. to. reliability. however,. is. in. the.
manufacturing.process.The.cable.must.be.free.from.material.and.manufacturing.defects,.and.weaknesses.that.will.be.
revealed.in.service.
Ducab.constantly.monitors.its.manufacturing.processes.and.operates.stringent.quality.assurance.procedures.to.give.long.
term.reliability.This.is.of.vital.significance.where.cables.are.to.be.installed.in.locations.where.future.access.would.be.
difficult.and.this.is.where.Ducabs.reputation.and.the.resources.give.peace.of.mind
.
PerornceOptimum.cable.performance.can.be.provided.only.by.a.company.such.as.Ducab,.with.access.to.the.latest.developments.
in.materials.technology.In.addition,.Ducabs.knowledge.of.application.requirements.throughout.the.Middle.and.Far.East.
is.an.assurance.of.high.performance
Where.required,.Ducab.can.incorporate.special.features,.for.example.to.give.the.cable.low.smoke.and.fume.(LSF).or.
reduced.flame.propagation.characteristics,.or.to.resist.abrasion.and.impacts.
Our.experienced.Technical.Staff.can.provide.guidance.on. cable.selection.and. installation.and.can. ensure.that.you.get.
the.right.cable.for.the.job
SetDucab.is.able.to.maintain.a.close.watch.on.world.developments.in.cable.technology.and.regulations.and.therefore.ensure.
that.its.products.are.designed.and.constructed.to.be.hazard-free.under.the.prescribed.conditions.
of.use
.Ducab.uses.only.tried.and.tested.materials.and.processes.in.full.compliance.with.all.relevant.
British.and.International.Standards.Our.cables.are.therefore.manufactured.for.safe.use.without.
risk. to. health. on. the. understanding. that. users.will. exercise.the. same. degree. of. care. in. their.
selection.and.application.
Safety.is.an.important.issue.for.Ducab,.and.the.strictest.standards.are.adhered.to.throughout.the.
company.Ducab.is.proud.of.its.safety.record.and.has.been.awarded.RoSPA.(Royal.Society.for.the.
Prevention.of.Accidents).Gold.Awards.for.safety.from.1991.to.1999.From.2000.onward,.Ducab.
was.awarded.the.prestigious.Presidents.Award.for.Health.and.Safety.which.is.a.recognition.of.
Ducab.winning.10.consecutive.annual.Gold.awards.and.acknowledges.Ducabs.total.commitment.to.health.and.safety.
In.2002,.Ducab.was.declared.the.joint.winner.of.the.Manufacturing.Industry.Sector.Award.from.RoSPA
Ducab.is.the.first.organisation.in.the.Middle.East.to.receive.accreditation.to.OHSAS.18001.by.the.BASEC.(British.
Approvals.Service.for.Cables).Certification.to.OHSAS.18001.provides.a.recognisable.Occupational.Health.and.Safety.
Management.standard.against.which.an.organisations.management.systems.can.be.assessed.and.certified.Based.on.the.
structure.of.ISO.14001,.the.standard.requires.continual.improvement.in.health.and.safety.related.activities.
CUSTOmER SERvICE
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
5/40BICC 3
Quit mneent Sste Certiied to ISO 9001
Ducabs. Quality. Management. System. conforms. to. the. ISO. 9001:2000. International. Quality. System. Standard.
and.is.certified.by.BASEC.(British.Approvals.Service.for.Cables).who.are.an.internationally.recognised.quality.authority.
accredited.in.the.UK.and.throughout.the.world.
Certification. to. the. ISO. 9001. International. standard. demonstrates. that. Ducab.
has. drawn. up. written. procedures. to. ensure. full. compliance. with. all.
requirements. of. the. standard. and. that. these. procedures. are. followed. by.
every. department. in. the. company,. thus. ensuring. that. goods. leaving. Ducabs.
factory. are. of. the. highest. quality. and. meet. each. customers. requirements. in.
every.respect.
Ducab.is.particularly.proud.to.have.achieved.certification.to.the.stringent.ISO.
9001:2000.standard.as.it.is.an.independent.conformation.that.the.company.designs,.manufactures.and.tests.cables.
consistently.to.accepted.standards.ISO.9001.is.widely.used.throughout.Europe,.and.is.therefore.a.reassurance.to.
Ducabs.customers.that.the.products.and.service.supplied.by.the.company.are.equal.to.the.best.in.the.world
Enironent mneent Sste Certiied to ISO 14001
Ducabs. Environmental. Management. System. conforms. to. the. ISO. 14001:2004. International.
. Environmental. Management. Standard. and. is. certified. by. BASEC. who. are. an. internationally. recognised. .
certifying.authority.accredited.in.the.UK.and.throughout.Europe
Certification. to. the. ISO. 14001:2004. International. standard. shows. that. Ducab.
has. a. well. defined. structure. and. established. working. practices. aimed. at.
limiting. its. impact. on. the. environment. Measurement. and. monitoring. of.
effects,. issuing. work. instructions,. training. of. personnel. and. taking. corrective.
actions. are. all. essential. elements. to. limiting. the. impact. on. the. environment.
Ducab. has. set. improvement. targets. to. reduce. the. significant. environmental.
impacts.associated.with.its.activities
Ducab. is. proud. to. be. the. first. cable. manufacturer. in. the. region. to. achieve. certification. to. ISO. 14001. and.
this. certification. along. with. its. quality,. business. success. and. safety. record. demonstrates. that. Ducab. is. a.
world.class.organisation.and.can.hold.its.head.up.to.any.business.community.throughout.the.world
BaSEC Certiiction
Ducab.is.also.proud.to.hold.a. Product.Marketing.Licence.issued.by.BASEC.(British.
Approvals.Service.for.Cables).for.several.cables.in.its.product.range
Ducb Sreek
Ducabs.customer.satisfaction.programme,.The.Value.Edge.is.designed.to.ensure.that.customers.receive.a.consistently.
high.level.of.service.from.Ducabs.dedicated.staff
.
LICENSE NUMBER - 083
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
6/40BICC4
INSUlaTIONThe.rated.voltage.level.of.the.cable.depends.on.the.dielectric.strength.and.thickness.of.the.insulation
mteri:
Cross-linked.polyethylene.(XLPE).Type.GP8.as.per.BS.7655:Section.13
Coour msterbtc:
Ultra-violet. (UV).resistant.polyethylene.masterbatch.is. used.for. colouring.of. insulation. This.protects. the.insulation.
from.deterioration.when.exposed.to.continuous.sunlight.
Core.identification.is.by.colour.as.follows.(unless.otherwise.agreed):
No. o cores Core Coours
. 1. Red.or.Black
. 2. Red.and.Black
. 3. Red,.Yellow.and.Blue
. 4. Red,.Yellow,.Blue.and.Black
. 5. Red,.Yellow,.Blue,.Black.and.Green/Yellow
For.providing.circular.shape.to.the.cable.non-hygroscopic.compatible.fillers.(wherever.necessary).are.included.between.
laid.up.cores.
mETallIC SCREEN:
If.required.by.the.customer.screening.may.be.provided.for.electrical.shielding
mteri:Copper.tape
Aluminium.PE.tape.along.with.tinned.copper.drain.wire.(for.providing.screen.continuity)
Note:.Special.constructions.other.than.stated.above.may.be.provided.on.request
SPECIfICaTION aND CONSTRUCTION
CONDUCTORS
It.is.the.current.carrying.component.of.the.cable
mteri:.
Plain,.stranded,.compacted.copper.as.per.BS.6360/IEC:228.
Aluminium,.stranded,.compacted.conductors
CORE IDENTIfICaTION
fIllERS
PRODUCT RaNgE
vote rne: 06/1kV.and.19/33.kV
Cbe Tpes:.1).Armoured/unarmoured.XLPE.insulated.cables.
2).Lead.sheathed.cables.
3).Copper.or.Aluminium.PE.tape.(with.drain.wire).shielded
Cbe sizes:
Single.core.up.to.and.including.1000.mm 2.
2.core.up.to.and.including.300.mm 2.
3.core.up.to.and.including.400.mm 2.
4.core.up.to.and.including.500.mm 2
Speciiction:
BS.5467.for.XLPE..insulated.armoured.cables
BS.7889.for.XLPE.insulated.single.core.unarmoured.cables.
IEC.60502.(Part.1).for.XLPE.insulated.single/multicore.armoured/unarmoured.cablesAny.other.International.Specification.as.per.VDE/DIN,GOST.and.as.per.customers.specifications
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
7/40BICC 5
BaRRIER TaPE:
mteri:
Polypropylene/PETP.tape.is.used.as.a.barrier.tape.over.the.laid.up.cores
functions:.Holds.the.cores.together.and.prevents.them.from.opening.out
Works.as.a.separator.between.different.polymers.used.in.a.cable
lEaD ShEaTh
mteri:
Extruded.Lead.Alloy.E.Sheath
Thickness.of.applied.lead.sheath.is.as.per.EEMUA.-.133.(Engineering.Equipment.and.Material.Users.Association)
function:
Protects.insulation.from.corrosion.by.petroleum.products.in.oil.and.gas.industries
Extruded.bedding.serves.as.a.bedding.for.the.armour.and.as.a.protection.for.the.laid-up.cores.
mteri:
Extruded.PVC.Type.9.Compound.as.per.BS.7655
Reduced.propagation.flame.retardant.(RPLHCL)/RP.PVC.Compound.for.reduced.flame.propagation.characteristics
Smokemaster low soke nd ue or insttions were ire zrds exist.
Armour.provides.mechanical.protection.to.the.cable.It.also.serves.as.an.Earth.Continuity.Conductor.(ECC)
One.layer.of.round.wire.is.applied.helically.over.the.bedding.
mteri:
Galvanised.round.steel.wire.(GSW)
Galvanised.round.steel.wire.(GSW).on wit tinned copper wires (TCW) or intinin speciied conductiit
o rour (i required b te custoer).
Aluminium.round.wire.armour.(AWA).is.generally.used.for.single.core.ac.circuits.as.aluminium.is.a.non-magnetic.
material.and.this.will.reduce.losses.due.to.armour
Note:.Aluminium.glands.should.be.used.in.conjunction.with.cables.having.aluminium.wire.armour
Following.types.of.materials.may.be.specified.for.oversheathing.
lgener Purpose:.Extruded.PVC.Type.9.Compound.as.per.BS.7655
lmediu Densit Potene (mDPE):.Offers.higher.protection.from.water.ingress.and.mechanical.abrasion
lanti Terite:.Termite.resistance.can.be.built.in.both.types.described.above.by.compounding.with.proper.additives
lReduced Proption (RP):.Retards.propagation.of.flame.in.fire.situation.(Oxygen.Index. 30)lReduced Proption nd low acid fues (RPlhCl):.Retards.propagation.of.flames.and.gives.low.emission.of.
hydrochloric.acid.fumes.(OI. 30.&.acid.gas.emission.is.less.than.18.%)lSmokemaster low Soke & fue (lSf):. Smokemaster cables. are. ideal. for. installations. where. the.
dense.black.smoke.generated.by.PVC.cables.in.a.fire.are.a.danger.to.people.Smokemaster is.characterised.by.the.features.as.Oxygen.Index.greater.than.35,.acid-gas.liberation.almost.nil.(
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
8/40BICC6
INSTallaTION
Whichever.form.of.conductor.is.used,.XLPE..insulated.cables.are.simple.to.handle,.install.and.joint.All.the.cables.
described.in.this.publication.can.be.used.indoors.or.outdoors,.but.some.reservations.are.necessary.concerning.cables.
for.direct.burial.in.the.ground.or.for.use.in.sustained.wet.conditions.as.follows:
(i). Unarmoured.cables.are.not.generally.recommended.for.laying.directly.in.the.ground
(ii). Cables.laid.directly.in.the. ground,.particularly.in.sustained.wet.conditions,.should.have.extruded.bedding.and.
preferably.MDPE.-.Medium.Density.Polyethylene.-.as.the.outersheath.material.
Other.important.factors.to.be.taken.into.account.are:.
Set DeCare.should.be.taken.to.ensure.that.the.oversheath.is.not.damaged.during.installation.This.is.especially.important.where.
aluminium.wire.armour.is.used,.as.ingress.of.moisture.could.lead.to.corrosion.or.ultimate.loss.of.earth.continuity.
SalIENT fEaTURES Of DUCaB CaBlE DESIgN
(1) XlPE insution Utr-ioet (Uv) coour sterbtc:
Ultra-violet. (UV).resistant.polyethylene.masterbatch.is. used.for. colouring.of. insulation.This. protects.the. insulation.from.deterioration.when.exposed.to.continuous.sunlight.
(2) Popropene/PETP tpe oer te id up cores:
Acts.as.a.separator.between.different.polymers.used.in.a.cable
(3) fiers:
For.ensuring.proper.circular.shape.to.the.cable,.non-hygroscopic.compatible.fillers.(wherever.necessary).are.included.
between.laid.up.cores.
(4) Speci requireents:
Ducab.cables.can.be.custom.designed.to.incorporate.special.requirements.of.the.client.as.follows:
(a).Screening:.Copper.tape.or.Aluminium.PE.tape.(along.with.tinned.copper.drain.wire).can.be.used.for.shielding.purposes.
(b).Tinned.copper.wire.can.be.used.along.with.galvanised.round.steel.wires.to.maintain.specified.armour.conductivity.
requirements.
(c).Reduced. propagating. flame. retardant. bedding. (RPLHCL/RP). and. outersheath. material. can. be. offered. to. meet.
reduced.flame.propagation.characteristics.and.low.hydrogen.acid.gas.emission
(d).Cable. with. bedding. and. outersheath. material. of. special. LSF. (low. smoke. and. fume). compound.can. be. offered.
for.installations.where.fire.and.its.associated.problems.-.the.emission.of.smoke.and.toxic.fumes.-.offer.a.serious.
potential.threat.(For.details.on.LSF.cables.refer.page.34)
(e).In. water. logged. areas. or. where. the. cables. are. required. to. be. abrasion. resistant,. cable. with. medium. density.
polyethylene.(MDPE).can.be.offered.(f). For.protection.from.insects,.anti-termite.protection.can.be.added.to.the.outersheath.
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
9/40BICC 7
miniu insttion rdius
Cable.should.not.be.bent.during.installation.to.a.radius.smaller.than.that.recommended.below.Wherever.possible.larger.
installation.radii.should.be.used.
Tbe 1
Tpe o Cbe Oer Dieter (D)miniu intern
rdius o bend
Circular.copper.conductors.armoured.or.unarmoured Any 6D
Shaped.copper.or.aluminium.conductors,.armoured.
or.unarmoured
For.lead.sheathed.cables
Any
Any
8D
12D
CaBlE SUPPORT SPaCINgAs.per.Clause.522-08-04.of.16.th.Edition.of.IEE.Wiring.Regulations.where.the.cable.is.not.continuously.supported.it.
shall.be. supported.by.suitable.means.at.appropriate.intervals.in.such.a. manner.that.the.cable.does.not.suffer.damage.
by.its.own.weight
Connectors
The.use.of.compression.type.connectors.is.recommended.for.XLPE.insulated.cables.since.the.use.of.soldered.connectors.
would limit the maximum short circuit temperature of the cable to 160C (and consequently reduce the final short circuitcurrent.by.approximately.30.per.cent)
Oered terintions
Ultra. violet. resistant. sleeving. or. taping. should. be. provided. on. XLPE. insulated. cores.to. avoid. degradation. due. to.
exposure.to.solar.rays.
aroured Sine Core Cbes or aC Opertion
Single.core.cable.armour.should.not.be. bonded/earthed.at.both.ends,.otherwise.it.carries.a.circulating.current,.which.
may.cause.overheating. in.the. cables,.sometimes.resulting. in.early.failure.However.single.end. bonding.results.in.an.
induced.voltage.(of.low.magnitude).at.the.unearthed.end.of.the.armour.Ducab.strongly.recommend.use.of.an.Insulated.
Adaptor. in. the. cable. gland,. while.terminating. single. core.cables. for.AC. operation.The. insulated.adaptor. could.be.
provided.as.per.part.design.No.481.AA.-.Series.
Single.core.cables.for.AC.operation.should.not.pass.through.steel.conduit.or.steel.gland.plate,.as.it.produces.a.heating.
effect.
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
10/40BICC8
CURRENT RaTINgS
Current.ratings.for.XLPE.insulated.cables.for.ground.and.duct.installation.are.derived.from.the.latest.issue.of.ERA.
Report.69-30.Part.5.which.is.based.upon.IEC.Publication.287.The.ratings.for.In.Air.installation.are.taken.from.IEE.Wiring.Regulations,.16th.Edition.
All.the.ratings.given.are.for.single.circuits.installed.thermally.independent.of.other.circuits.or.any.other.heat.source.and.
on.the.basis.of.the.standard.conditions.of.installation.given.in.relevant.Tables.between.18.to.34.For.other.ambient.or.
ground.temperatures,.depth.of.laying,.soil.thermal.resistivity,.the.rating.must.be.multiplied.by.relevant.rating.factors.in.
Tables.2.to.6.and.8.to.12.
It.should.be.noted.that.if.XLPE.insulated.cables,.are.subjected.to.operating.temperatures.appreciably.higher.than.the.
90C permissible for continuous operation, the insulation will undergo premature ageing thus affecting the normal lifeof the cable. However, limiting maximum conductor temperature to 105C during overloads with duration not exceeding4.hours.on.any.one.occasion,.or.a.maximum.of.100.hours.in.any.12.consecutive.months,.or.a.total.of.500.hours.in.the.
cables.lifetime,.would.be.tenable.
IEE Wirin Reutions 16t edition - requireent or cbesThe.IEE.Wiring.Regulations.for.installation.and.selection.of. cables.cannot.be.approached.in.isolation.from.the.other.
equipment.in. the.installation.In. particular.the.devices.providing. protection.against.overload,.short.circuit,. shock. by.
indirect.contact.and.over-heating.of.protective.conductors.during.an.earth.fault,.affect.the.selection.of.cables.
For.guidance.and.assistance,.given.below.are.some.of.the.IEE.Wiring.Regulations.requirements.for.cables:
Protection inst oerod current: (Cuse 433-01-01 o te 16t Edition o te
IEE Wirin Reutions)
This.states.the.requirements.which.effectively.determine.the.sustained.current.ratios.of.the.cable.viz:
(i).The.current.rating.of.the.cable.should.not.be.less.than.the.nominal.current.or.current.setting.of.the.device.providing.
protection.against.overload,.which.in.turn.should.be.not.less.than.the.circuit.current.
(ii).The.overload.protection.should.operate.at.not.more.than.145.times.the.current.rating.of.the.cable.
The.second.requirement.(ii).is.met.if.the.first.(i).is.met.when.the.protective.device.is.any.of.the.standard.fuses.or.MCBs.
mentioned.in.the.regulations,except.rewirable.types.of.fuse.to.BS.3036.
With.fuses.to.BS.3036.the.current.ratings.of.the.cable.should.not.be.less.than.138.times.the.fuse.rating.to.satisfy.(ii)
Protection inst sort circuit: (Cuse 434 o te 16t Edition o te IEE
Wirin Reutions)
The.cable.has.to. have.adequate.short-circuit.capacity.for.the.current.let.through.by.the.device.providing.short.circuit.protection.for.the.time.it.will.flow.
The.formula.in.Section.434-03-03.is.effectively.that.used.by.cable.makers.to.give.the.short-circuit.ratings.in.their.
publications.
If.the.device.providing.protection.against.short.circuit.is. the.same.as.that.providing.protection.against.overload.and,.
therefore,.has.a.rating.not.higher.than.the.rating.of.the.cables,.the.short.circuit.capacity.of.the.cable.will.automatically.
be.adequate,.there.is.no.need.to.check.
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
11/40BICC 9
Protection inst indirect contct b interruption o supp: (Cuse 412 o te
16t Edition o IEE Wirin Reutions)
Protection.against.shock.due.to.contact.with.exposed.conductive.parts.of.equipment.during.a.fault.to.earth.is.deemed.to.
be.provided.if.disconnection.due.to.flow.of.the.fault.current.through.the.protective.device.will.occur,.eitherwithin. 04. seconds. for. final. circuits. supplying. socket. outlets. (Table. 41A. of. the. 16th. Edition. of. the. IEE. Wiring.
Regulations)
or
within.5.seconds.for.final.circuits.supplying.fixed.equipment.(Clause.413-02-12.of.the.16th.Edition.of.the.IEE.Wiring.
Regulations)
Regulation.413.gives.values.of.earth.fault.loop.impedances.which.satisfy.these.conditions.when.the.standard.types.of.
protective.devices.are.used.
Cables.make.the.major.contribution.to.earth.fault.loop.impedance,.but.the.impedance.of.the.supply.external.to.the.
installation.has.to.be.taken.into.account.
It.is.not.possible.to.say.what.maximum.length.of.standard.cables.may.be.used.in.the.installation.without.exceeding.the.
requirements.for.earth.fault.loop.impedance.in.the.absence.of.information.on.the.external.impedance.for.the.particular.installation.
Table.16.gives.estimated.values.of.the.contribution.to.earth.loop.impedance.by.XLPE.insulated.copper.conductor,.steel.
wire.armoured.cables.to.BS.5467.
Cross section res o protectie conductors: (Cuse 543 o te 16t Edition
o IEE Wirin Reutions)Regulation.543.explains.how.the.cross.sectional.area.of.the.circuit.protective.conductor.should.be.calculated.to.avoid.
it.over-heating.during.a. fault.to. earth.Again.the. area.required.depends.on.the. characteristics.of.the.device.providing.
protection.against.short.circuit.
The.steel.wire.armour.of.standard.cables.to.BS.5467.(XLPE).and.BS.6346.(PVC).provides.the.required.area,.or.more,.when.the.protective.device.is.one.of.the.standard.fuses.or.MCBs.with.a.rating.not.higher.than.the.current.rating.of.the.
cable.(assuming.disconnection.within.5.seconds)
For.the.most.of.the.cables.the.armour.is. still.adequate.when.the.fuse.rating.is.one.or.two.steps,.or.even.more,.above.
the.current.rating.of.the.cable,.the.margins.being.greater.for.the.small.sizes.and.4.core.cables.than.for.the.larger.sizes.
and.two.core.cables.
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
12/40BICC10
Voltage.drop.is.normally.only.of.importance.for.cables.of.voltage.rating.600/1000V.or.below.If.the.installation.is.to.be.
incompliance.with.Regulation.525.of.the.16th.Edition.of.the.IEE.Wiring.Regulations,.it.is.stipulated.that.the.voltage.drop.within.the.installation.does.not.exceed.a.value.appropriate.to.the.safe.functioning.of.the.associated.equipment.
in.normal.service.The.requirement.is. deemed.to.be. satisfied.if.the.drop.in.voltage.from.the.origin.of.the.installation.
(usually.supply.terminals).and.the.fixed.current.using.equipment.does.not.exceed.4.per.cent.of.the.nominal.voltage.of.
the.supply,.disregarding.starting.conditions
(Note:.Diversity.can.be.taken.into.account.when.calculating.voltage.drop)
Since.the.actual.power.factor.of.the.load.is.often.not.known,.the.most.practical.approach.to.the.question.of.voltage.drop.
is.to.assume.the.worst.conditions.ie.where.the.phase.angle.of.the.load.is.equal.to.that.of.the.cable.The.voltage.drop.
values.in.the.tables.have.been.based.on.this.assumption.For.conductor.sizes.up.to.and.including.120.mm 2.the.figures.
provided.apply.with.sufficient.accuracy.where.the.power.factor.lies.between.06.lagging.and.10,.and.for.large.cables.
where.the.power.factor.of.the.load.does.not.exceed.08.lagging.Where.the.phase.angles.of.the.loads.fall.outside.this.
range,.the. voltage.drop. deduced.from.the. tables.may. be.unduly.conservative.and. more.exact.methods.of. calculation.
should.be.employed.
The.values.of.voltage.drop.for.600/1000.V.rated.cables.are.given.in.the.current.rating.tables
In.those.cases.where.the.actual.current.differs.greatly.from.the.tabulated.current.rating,.the.results.obtained.from.the.
tables.are.only.approximate;.for.a. more.accurate.assessment,.allowance.should.be.made.for. the.change.in. conductor.
resistance.with.operating.temperature.Refer.to.page.35.and.Table.32.for.details.It.should.also.be.ensured.that.the.cable.
size.ultimately.selected.is.capable.of.carrying.the.required.current.under.the.site.conditions.of.installation.
Values.of.voltage.drop.are.tabulated.for.a.current.of.one.ampere.for.a.1.metre.run,.ie.for.a.distance.of.1.metre.along.
the.route.taken.by.the.cables,.and.represent.the.effect.of.the.voltage.drop.in.all.the.circuit.conductors.For.balanced.three.
phase.ac.circuits,.the.values.relate.to.the.line.voltage.For.any.given.run.the.values.need.to.be.multiplied.by.the.length.
of.the.run.(in.metres).and.by.the.current.(in.amperes).that.the.cables.are.to.carry.
Expes:.Consider.a.route.of.200.metres.of.4.Core.armoured.cable.to.be.installed.in.air.and.to.carry.100.amperes.load.per.phase,.with.the.supply.voltage.being.415.volts,.three.phase.50.Hz.and.the.cable.to.be.Copper.XLPE/SWA/PVC.
Using.the.tables:
Let.Vd.be.the.voltage.drop.in.volts
Vd.=.mV.x.I.x.L...or.mV.=.Vd.x.1000
....... .1000. . ......I.x.L.
where.I.=.Current.in.amperes..L.=.Route.length.in.metres..mV.=.Approximate.volt.drop/ampere/metre
Assume.maximum.permissible.volt.drop.=.4.per.cent.of.415.volts.=.166.volts
Substitute.for.current,.route.length.and.maximum.permissible.volt.drop
then.mV.=.166.x.1000..=.083. .....200.x.100
Select.a.cable.from.the.relevant.Current.Rating.Table.27.such.that.the.mV.value.from.the.voltage.drop.column.is.
equal.to.or.less.than.the.083.mV.calculated,.ensuring.that.it.will.carry.the.current.It.will.be.seen.that.this.value.is.06.
giving.a.cable.size.of.70mm2.However,.100.Amp.load.could.be.less.than.80%.current.carrying.capacity.of.50mm 2.cable,.
in.which.case.of.50.mm 2.cable.will.suffice.
Note:.Please.refer.to.pages.30.and.35.for.additional.information.on.voltage.drop.
vOlTagE DROP
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
13/40BICC 11
RaTINg faCTORS
Rtin ctors or round teperture
Rtin ctors or rition in ter resistiit o soi
(ere ues)
CaBlES laID DIRECTly IN gROUND
Where.the.conditions.of.installation.differ.from.those.defined.in.the.current.rating.tables,.the.following.rating.factors.may.be.used.
for.cables.size.selection.
Ratings.for.cables.installed.directly.in.the.ground.are.based.on.values.of.soil.temperature.and.soil.thermal.resistivity.which.are.
generally.representative.of.conditions.in.the. United.Kingdom.Rating.factors.to.take. account.of. variation.in. ground.temperatures.
are.given.in.Table.2.Where.conditions.of.operation.can.be.fairly.accurately.estimated.and.knowledge.of.the.soil.along.the.route.is.
available,.it.is.possible.to.determine.the.ratings.more.precisely.by.the.use.of.the.soil.thermal.resistivity.factors,.grouping.factors,.and.
factors.for.the.depths.of.laying.given.in.Tables.3.to.6..These.factors.are.more.fully.tabulated.in.ERA.Report.69.-.30.Part.II.Tables.
61.-.71.
In.ERA.Report.69-30.Part.III,.the.types.of.load.are.classified.under.three.headings,.viz:
Tpe a. Cables.carrying.a.constant.load.throughout.the.year.
Tpe B. Cables.carrying.varying.loads,.maximum.in.summer.period
Tpe C. Cables.carrying.varying.loads,.maximum.in.winter.period.
With.knowledge.of.the.type.of.load.to.be.imposed.on.the.cable.it.is.then.possible.to.determine.the.soil.thermal.resistivity.along.the.cable.route.in.accordance.with.recommendations.in.ERA.Report.69-30.
Tbe 2
Tbe 3
Ground.temperature 15C 20C 25C 30C 35C 40C 45C
XLPE.Insulated 10 097 093 089 086 082 076
Cbe Tpe Rtin ctor
Size.of.cables
mm2
Single.core.cables
Up.to.150
From.185.to.300
From.400.to.1000
Multicore.cablesUp.to.16
From.25.to.150
From.185.to.500
116
117
117
112
112
112
107
107
107
091
091
091
081
080
080
073
073
073
066
066
066
112
114
115
108
110
110
105
106
107
093
092
092
084
082
081
077
075
074
072
069
067
Soil.thermal.resistivity in C m/W
08 09 10 15 20 25 30
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
14/40BICC12
Rtin ctors or dept o in (to centre o cbe or treoi
roup o cbes)
group rtin ctors or circuits o tree sine core cbes in
treoi or id t toucin, in orizont ortion
Tbe 4
Tbe 5
Depth.of.laying
m
050060080100125
150
175
200
250
300
or.more
100099097095094
093
092
091
090
089
100098096093092
090
089
088
087
085
100097094092089
087
086
085
084
082
--
100098096
095
094
092
091
090
--
100097095
093
091
089
088
086
Up.to.50mm2
600/1000.Volt 1900/3300.Volt
70mm2to.300mm2
Above.300mm2 Up.to.300mm2 Above.300mm2
Number.of.Circuits
600/1000
Volt.cables
1900/3300
Volt.cables
2
3
4
5
6
078
066
061
056
053
078
066059
055
052
080
068062
058
055
082
071065
061
058
086
077072
068
066
089
080077
074
072
091
083080
078
076
081
070
064
060
057
083
073
068
064
061
088
079
073
073
071
091
084
081
079
078
093
087
085
085
082
2
34
5
6
Spacing.of.Circuits
Touching.+
Trefoil Laid.flat 015.m* 030.m 0545.m 060.m
*. This.spacing.will.not.be.possible.for.some.of.the.larger.diameter.cables
+. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.
appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel
SPaCINgSPaCINg
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
15/40BICC
SPaCINg
group rtin ctors or uticore cbes in orizont ortion
Recoended duct diensions nd cbe sizes
Tbe 6
Tbe 7
Number.of.Cables.in.Group
Overall.cable.diameter
mm
Up.to.and.including.65
Above.65.up.to.and.including.90
100
125
130
160
Inside.diameter
mm
Outside.diameter
mm
Spacing
Duct
Touching+ 015.m 030.m 045.m 060.m
600/1000
volt.cables
1900/3000volt.cables
2
3
4
5
6
081
070
063
059
055
087
078
074
070
068
091
084
081
078
077
093
088
086
084
083
095
090
089
087
087
2
3
4
5
6
080
068
062
057
054
085
076
071
066
064
089
081
077
073
071
091
084
081
078
077
093
087
084
082
081
CaBlES INSTallED IN DUCTS
+. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.
appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel
The.term.ducts.applies.to.single.way.earthenware,.fibre.or.ferrous.pipes
Ratings. for. cables.installed. in.single. way. ducts,.underground,. have. been. based.on. values.of. soil. temperature. and. soil. thermal.
resistivity.which.are.generally.representative.of. conditions.in.the.United.Kingdom.Rating.factors.to.take.account.of.variations.in.
ground.temperatures.are.given.in.Table.3.Where.conditions.of.operation.can.be.fairly.accurately.estimated,.and.knowledge.of.the.
soil.along.the.route.is.available,.it.is.possible.to.determine.the.ratings.more.precisely.by.the.use.of.estimated.maximum.ground.
temperature,.the.soil.thermal.resistivity.factors,.grouping.factors,.and.factors.for.the.depths.of.laying.given.in.Tables.8.to.11.
Rtin ctors or round teperture
Note:.Same.as.for.direct.in.ground,.refer.to.Table.2.
13BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
16/40BICC14
Rtin ctors o rition in ter resistiit o soi
(ere ues)Tbe 8
Size.of.cable
mm2
Single.Core.Cable
Up.to.150
From.185.to.300
From.400.to.1000
Multicore.Cables
Up.to.16
From.25.to.150
From.185.to.500
Soil.thermal.resistivity in C m/W
08
110
111
112
104
106
107
107
108
108
103
104
105
104
105
105
102
103
103
094
093
093
097
095
095
086
085
084
092
090
088
080
079
078
088
085
083
076
075
074
086
081
078
09 10 15 20 25 30
Rtin ctors o dept o in (to centre o duct
or treoi roup o ducts)Tbe 9
Depth.in.laying
m
050
060
080
100
125
150
175
200
250
300
or.more
100
098
095
093
091
089
088
087
086
085
100
099
098
096
095
094
094
093
092
091
-
-
100
098
095
093
092
090
089
088
-
-
100
099
097
096
095
094
093
092
600/1000.Volt 1900/3300.Volt
Single.Core Multicore Single.Core Multicore
group rtin ctors or sine core cbes in treoi
sine w ducts, orizont ortion (ere ues)Tbe 10
Number.of.Circuits
600/1000
Volt.Cables
1900/3300
Volt.Cables
2
3
4
5
6
087
078
074
070
069
085
075
070
067
064
088
080
077
074
072
090
083
080
078
076
091
084
081
079
078
093
087
085
083
082
2
3
4
5
6
Spacing
Touching.+ 045.m 060.m
SPaCINg
+. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.
appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
17/40BICC 15
group rtin ctors or uticore cbes in sine w ducts,
orizont ortion (ere ues)
Rtin ctors or oter bient ir tepertures
Tbe 11
Tbe 12
Number.of.Ducts
in.GroundSpacing
Touching.+ 030.m 045.m 060.m
600/1000
volt.cables
1900/3000
volt.cables
2
3
4
5
6
090
083
079
075
073
088
080
076072
069
091
085
081078
076
093
088
085083
081
094
090
088086
085
093
088
085
083
082
095
091
089
088
087
096
093
092
091
090
2
3
45
6
+. For.high.current.carrying.cables.(ie.large.size).it.is.advisable.to.allow.spacing.between.circuits.Alternatively.the.most.
appropriate.group.rating.factor.must.be.applied.when.determining.the.cable.size.and.required.number.of.cables.in.parallel
It.is.anticipated.that.many.of.the.in.air.installations.will.be.in.buildings,.and.the.ratings.are.therefore.given.in.accordance.with.IEE.
Wiring.Regulations.for.Electrical.Installations,.16th.Edition.
It soud be noted tt rtins or cbes run in ree ir e been bsed on te ssuption tt te re sieded ro
te direct rs o te sun witout restriction o entition. Te rtin or cbes subjected to direct sunit soud bereduced to tke ccount o tis ctor nd urter uidnce on tis subject is ibe on request.
Deined conditions o insttion
The.in-air.current.ratings.given.in.relevant.Tables.between.18.to.34.are.based.on.the.installation.conditions.in.air.as.follows:
() Sine core cbes(1). Two.single.core.cables.are.installed.one.above.the.other,.fixed.to.the.vertical.surface.of.a.wall.or.open.cable.trench,.
the.distance.between.the.wall.and.the.surface.of.the.cable.being.not.less.than.20mm
.
. Cables.are.installed.at.a.distance.between.centres.of.twice.the.overall.diameter.of.the.cable,.ie.2D,.where.D.=..
overall.diameter.of.cable.
(2). Three.single.core.cables.are.installed.in.trefoil.formation,.fixed.to.the.vertical.surface.of.a.wall.or.open.cable.trench,.
the.cables.touching.throughout.and.the.distance.between.the.wall.and.the.surface.of.the.nearest.cable.being.not.less.
than.20mm
. The.cables.are.assumed.to.be.remote.from.iron,.steel.or.ferro-concrete,.other.than.the.cable.supports.Single.core.. .
armoured.cables.to.be.electrically.bonded.at.each.end.of.the.run.
(b) muticore Cbes. Cables.of.all.types.other.than.single.core.cables.are.installed.singly,.fixed.to.the.vertical.surface.of.a.wall.or.open.cable.trench,.the.distance.between.the.surface.of.the.cable.and.the.wall.being.not.less.than.20.mm.in.every.instance.
If.it.is.necessary.for.cables.to.be.installed.at.distances.less.than.those.described.above,.then.the.values.tabulated.under.the.heading.
Clipped.direct.to.a.surface.in.the.IEE.Wiring.Regulations.should.be.employed.
SPaCINg
CaBlES INSTallED IN aIR
Air.Temperature
XLPE.Insulated
25C
104 10 096 091 087 082 076
30C 35C 40C 45C 50C 55C
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
18/40BICC16
Tbe 13
ShORT CIRCUIT RaTINgS CONDUCTORS
Copper Conductors
auiniu ConductorsThe.values.of.fault.current.given.in.the.graph.are.based.on.the.cable.being.fully.loaded.at.the.start.of.the.short.circuit.(conductor.
temperature 90C) and a final conductor. temperature. of. 250.C. It should be ensured that the accessories associated withthe.cables.are.also.capable.of.operation.at.these.values.of.fault.
current.and.temperature.
Note:. With. XLPE. cables. the. use. of. soldered. type. connectors.
(instead.of.the.compression.type).is.not.recommended.since.their.
use. in.the. system. would.limit. the.final. conductor.temperature.to 160 C (and consequently reduce the fault current rating byapproximately.30.per.cent).
Conductor.size.... ....Short.circuit.ratings.for.1.second.in.KA. mm2..... .... ....Copper.conductor.. ..Aluminium.Conductor
. 15. 021. 014
. 25. 036. 024
. 4. 057. 038
. 6. 086. 056
. 10. 143. 094
. 16. 229. 150
. 25. 358. 235
. 35. 500. 329
. 50. 715. 470
. 70. 1001. 658
. 95. 1359. 893
. 120. 1716. 1128
. 150. 2145. 1410
. 185. 2646. 1739
. 240. 3432. 2256
. 300. 4290. 2820
. 400. 5720. 3760
. 630. 9009. 5922
. 800. 11440. 7520
. 1000. 14300. 9400
Note:.For.any.other.duration.t.seconds.divide.the.given.
value by t
0.5
0.1
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
19/40BICC
ShORT CIRCUIT RaTINgS aRmOUR
XlPE INSUlaTED CaBlES
arour fut currents to ert (or ut durtion o 1 second) Tbe 14
Nominal
Area.of
Conductor
mm2
. 16
. 25
. 35
. 50
. 70. 95
. 120
. 150
. 185
. 240
. 300
. 400
. 500
. 630
. 800
. 1000
Aluminium.Wire.Armour Steel.Wire.Armour
600/1000.V 1900/3300.V600/1000.V
Single.Core
amp
Single.Core
amp
Two.Core
amp
Three.Core
amp
Four.Core
amp
Four.Core
(reduced.neutral)
amp
Three.Core
amp
XLPE
. -
.
. -
. -
. 4000*...
. 4700*. 5200*
. 5700*
. 6400
. 7100
. 7900
. 8800
. 12400
. 13800
. 15400
. 21300
. 23400
XLPE
. -
. -
. -
. .4700*
. .5200*. .5700*
. 6100
. .6400
. 7100
. ..7800
. ..8500
. 12000
. 13300
. 14900
........-
........-
XLPE
1800
1900
2800
3100
36005100
-
-
-
-
-
-
-
-
-
-
XLPE
. 2000
. 2800
. 3200
. 3500
. 4100
. 5800
. 6400
. 9200
.10100
. 11500
.12300
. -
. -
. -
. -
. -
XLPE
. 2200
. 3200
. 3600
. 4100
. 6000. 6700
. 9400
. 10500
. 11700
. 13200
.
. 14600
. 20700
. 22500
. -
. -
. -
XLPE
.......-
3200
3400
3900
59006600
7500
10000
11500
12800
13900
20700
22500
......-
......-
......-
XLPE
3700
4200
4700
5600
62006900
9400
10100
10800
11900
13000
......-
......-
......-
......-
......-
1900/3300.V
*. Based.on.wire.diameters.larger.than.those.specified.in.BS.5467.Refer.to.Table.17,.33.and.35.for.single.core.cable.armour.
wire.diameter
Notes:. . 1. The.ratings.given.in.the.Table.above.are.based.on.a.fault.duration.of.one.second.and.an.armour.temperature.rise..
from 80C at commencement of the fault to a final temperature of 200C..
. . 2. The.asymmetrical.fault.rating.of.the.smaller.sizes.may.be.decided.by.the.short.circuit.capability.of.the.. .
. . conductor.rather.than.the.armour.rating.It.is.therefore.necessary.to.compare.the.two.ratings
17BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
20/40BICC
Withstranded
aluminium
conductor
600/1000V
Withstranded
copper
conductor
600/1000V
18
Tbe15
600/1000v
MaximumresistanceofCable-Armourinohms/kmat20C
N
om
inal
Area
o
fCon
ductor
mm
216
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
11
5
07
27
05
24
03
87
02
68
01
93
01
53
01
24
00
991
00
754
00
601
00
470
00
366
00
283
00
221
00
176
1910
1200
0868
0641
0443
0320
0253
0206
0164
0125
0100
00
778
00
605
00
469
00
367
00
291
- - -1
30
07
5
06
7
06
1
04
2
03
8
03
4
03
1
02
2
02
0
01
8
01
3
01
2
- - -0
75
06
7
06
1
04
2
03
9
03
7
03
4
03
1
02
2
02
0
01
8
01
3
01
2
37
0
37
0
26
0
23
0
20
0
14
0
13
0
12
0
08
2
07
3
06
7
05
9- - -
35
0
25
0
23
0
20
0
18
0
13
0
12
0
07
8
07
1
06
3
05
8
05
2- - -
19
0
17
0
18
0
13
0
12
0
11
0
07
6
07
1
06
5
05
9
05
5
05
0- - -
31
0
23
0
20
0
18
0
12
0
11
0
07
6
06
8
06
1
05
4
04
9
03
5- - -
-2
30
21
0
19
0
13
0
11
0
09
6
07
1
06
3
05
6
.0
52
04
6- - -
Copper
Con
ductor
*
Alum
inium
Con
ductor
Sing
leCore
600/1000V
600/1000V
600/1000V
600/1000V
1900/3300V
ThreeC
ore
Twocore
Four
Core
**
(equalneutral)
Four
Core
(reducedneutral)
Aluminiumwirearmour
Withstrandedcoppercon
ductor&GalvanisedSteelWireArmour
CONDU
CTORaNDaRmOURRESISTaNCEvalUES
SINglEaNDmUlTICORECa
BlEShavINgWIREaRmOUR
*
Thevaluesg
ivenare
forp
lainannea
ledcoppercon
ductors
For
tinnedcon
ductors
referenceshou
ldbemade
toBS6360
**
Mu
lticoreca
blesw
ithstran
ded
Alum
iniumcon
ductor
havesame
Armourresistan
cesas
thosew
ithCoppercon
ductors
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
21/40BICC 19
CONTRIBUTION By CaBlE TO EaRTh faUlT lOOP ImPEDaNCE
Copper conductor, XlPE insuted roured cbes to BS 5467/BS6724
Tbe 16600/1000 v
Conductor
mm2
16
253550
7095
120
150
185
240
300
400
667
587402355
298
211
-
-
--
-
-
642
435377317
273
198
179
123
110
097
089
-
591
410339292
198173
125
110
098
086
078
060
-
410352305
210173
149
114
100
088
081
072
2.core
Contribution.by.cable.to.earth.fault.loop.impedance.milli.ohms/metre
4.core3.core 4.core(with.reduced.neutral)
The.following.table.gives.the.estimated.impedance.of.copper.phase.conductor.and.steel.wire.armour.in.series,.ie.the.
contribution.to.earth.fault.loop.impedance.by.the.cable,.allowing.for.the.estimated.increase.in.temperature.due.to.the.
flow.of.the.earth.fault.current.The.earth.fault.current.is.taken.to.be.that.which.gives.interruption.in.5.seconds.when.the.protective.device.is.a.standard.type.having.a.rating.not.higher.than.the.current.rating.of.the.cable
Note:.For.information.on.maximum.length.of.cable.that.meets.the.earth.fault.loop.impedance.requirement.for.5.second.
disconnection,.refer.to.Ducabs.Technical.Department
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
22/40BICC20
XlPE INSUlaTED CaBlES TO BS 5467
DImENSIONS aND WEIghTS
STRaNDED COPPER & alUmINIUm CONDUCTORS
SINglE CORE CaBlES
600/1000 v Tbe 17Unroured nd roured, PvC seted cbes
Nominal
area.of
conductor
mm2
50
70
95
120
150
185
240
300
400
500
630
800
1000
10
11
11
12
14
16
17
18
20
22
24
26
28
142
162
183
202
224
247
277
306
342
380
429
478
530
250
330
430
510
630
760
970
1190
1500
1900
2420
3120
3780
540
760
1020
1270
1560
1930
2510
3120
3970
4980
6400
8210
10275
126
145
164
180
198
220
246
273
312
360
400
458
508
16*
16*
16*
16*
16
16
16
16
20
20
20
25
25
184
202
223
242
274
300
328
356
405
442
488
554
606
460
560
690
800
970
1150
1380
1640
2130
2610
3180
4230
5000
800
990
1280
1550
1900
2320
2930
3580
4600
5680
7160
9315
11490
Thickness
of
insulation
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Diameter
under
armour
mm
Armourh
wire
diameter
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)
Single.core.unarmoured.cables.are.as.per.BS.7889*.Wire.diameters.are.larger.than.those.specified.in.BS.5467hAluminium.wire.armour.for.AC.system
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
23/40BICC 21
Stranded.Aluminium.Conductors
600/1000 v
50
70
95
120
150
185
240
300
400
500
630
800
1000
235
290
345
390
435
490
560
630
700
770
840
888
942
235
280
330
370
405
440
500
550
580
620
670
692
735
222
285
346
402
463
529
625
720
815
918
1027
1119
1214
087
062
047
039
033
028
024
021
020
018
017
017
016
093
070
056
048
043
039
035
032
030
028
026
025
024
087
062
047
039
033
028
024
021
020
018
017
017
016
175
220
260
295
330
375
435
490
540
580
630
180
220
260
295
330
365
410
455
480
510
540
162
207
252
292
337
391
465
540
625
714
801
140
098
072
058
048
039
031
027
035
031
028
160
100
079
066
057
049
042
038
038
035
032
140
098
074
060
049
041
034
029
025
022
020
Tbe 18
CURRENT RaTINgS (aC)
Stranded.Copper.Conductors
Nominal.
area.of
conductor
....mm2.
Direct.in
ground
amps
Installed
in.airamps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.airamps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
Direct.in.ground..Trefoil.touching
Single.way.ducts.-.ducts.touching
Spacing.in.air.-.As.shown.above.(D.=.Cable.diameter)
Installation.conditions.for.above.ratings:
Ambient air temperature:30C
Ground temperature: 15CDepth.of.laying:05.m
Soil thermal resistivity: 1.2C m/W
Maximum conductor operating temperature at rated current is 90C
For.rating.factors.see.Tables.2.to.6.and.8.to.12
.Aluminium.Conductors
600/1000 v
50
70
95
120
150
185
240
300
400
500
630
800
1000
230
285
335
385
435
490
570
650
740
840
960
1120
1300
240
295
345
395
445
500
580
650
750
850
960
1130
1320
209
270
330
385
445
511
606
701
820
936
1069
1214
1349
085
061
045
036
031
026
022
019
017
016
015
015
014
093
070
056
048
043
039
035
032
030
028
026
025
024
087
061
045
037
031
026
022
020
018
016
015
015
014
175
215
255
295
325
370
430
490
550
620
690
180
220
260
300
335
375
440
510
570
640
730
159
206
253
296
343
395
471
544
638
743
849
140
098
071
057
047
039
031
026
036
033
028
150
110
079
066
057
049
042
038
038
035
032
145
098
073
059
047
039
032
027
023
020
019
Tbe 19
Stranded.Copper.Conductors
Nominal.
area.of
conductor
mm2
Direct.in
ground
amps
Installedin.airamps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installedin.airamps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
STRaNDED COPPER & alUmINIUm CONDUCTORS
SINglE CORE CaBlES
aroured PvC seted cbes
Unroured PvC seted cbes
3D 3D
3D3D
BICC
In.single
way.ducts
amps
In.single
way.ducts
amps
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
24/40BICC22
XlPE INSUlaTED CaBlES TO BS 5467
DImENSIONS aND WEIghTS
600/1000 v Tbe 20Unroured nd roured, PvC seted cbes
Nominal
area.of
conductor
mm2
16*
25*
35*
50
70
95
120
150
185
240
300
07
09
09
10
11
11
12
14
16
17
18
170
202
225
204
231
265
284
317
351
403
443
415
480
497
690
850
1170
1450
1810
2280
2760
475
740
955
1100
1520
2050
2610
3220
4030
5200
6430
152
185
215
187
215
246
268
297
333
381
423
. 125
. 125
. 160
. 160
. 160
. 200
. 200
. 200
. 250
. 250
. 250
204
241
277
258
290
331
361
393
447
490
535
915
1255
1430
1780
1950
2440
3050
3690
4380
5100
900
1240
1710
1800
2320
3150
3880
4820
5920
7300
8770
Thickness
of
insulation
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Diameter
under
armour
mm
Armour
wire
diameter
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)
STRaNDED COPPER & alUmINIUm CONDUCTORS
TWO CORE CaBlES
*.Circular.conductor,.all.others.are.sector.shaped
Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
25/40BICC
In.single
way.ducts
amps
In.single
way.ducts
amps
23
Aluminium.Conductors.
600/1000 v
16*
25*35*
50
70
95
120
150
185
240
300
140
180215
255
315
381
410
472
539
636
732
115
145175
210
260
313
344
384
432
504
560
115
152188
228
291
354
430
480
540
630
700
29
1913
10
07
05
04
04
03
02
02
29
1913
10
07
05
04
04
03
02
02
29
1913
10
07
05
04
04
03
02
02
135165
195
240
288
110130
155
195
237
112138
166
211
254
3122
17
11
08
3122
17
11
08
3122
17
11
08
Tbe 21
CURRENT RaTINgS (aC)
Stranded.Copper.Conductors
Nominal.
area.of
conductor
mm2
Direct.in
ground
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
.Aluminium.Conductors
600/1000 v
16*
25*
35*
50
70
95120
150
185
240
300
140
180
215
255
315
380410
473
542
641
741
115
140
170
205
255
311344
384
432
504
560
115
149
185
225
289
352430
480
540
630
700
29
19
13
10
07
0504
04
03
02
02
29
19
13
10
07
0504
04
03
02
02
29
19
13
10
07
0504
04
03
02
02
135
165
195
240
285
105
130
150
195
235
108
135
164
211
257
31
22
17
12
08
31
22
17
12
08
31
22
17
12
08
Tbe 22
Stranded.Copper.Conductors
Nominal.
area.of
conductor
mm2
Direct.in
ground
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
STRaNDED COPPER & alUmINIUm CONDUCTORS
TWO CORE CaBlES
aroured PvC seted cbes
Unroured PvC seted cbes
Direct.in.ground..Cables.touching
Single.way.ducts.-.ducts.touching
*.Circular.conductors,.all.others.are.sector.shaped
Note:. (1).50.mm2.and.above.are.with.D-shaped.conductor
. . (2).Unarmoured.cables.are.as.per.IEC:60502.(part.1)
Installation.conditions.for.above.ratings:
Ambient air temperature:30C
Ground temperature: 15C
Depth.of.laying:05.m
Soil thermal resistivity: 1.2C m/W
Maximum conductor operating temperature at rated current is 90C
For.rating.factors.see.Tables.2.to.6.and.8.to.12
*.Circular.conductor,.all.others.are.sector.shaped
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
26/40BICC24
XlPE INSUlaTED CaBlES TO BS 5467
DImENSIONS aND WEIghTS
600/1000 v Tbe 23
Nominal
area.of
conductor
mm2
16*
25*
35*
50
70
95
120
150
185
240
300
400
07
09
09
10
11
11
12
14
16
17
18
20
180
215
240
246
280
310
348
385
440
495
535
592
500
610
740
1050
1170
1440
2300
2750
3020
3660
3730
675
990
1295
1640
2220
2980
3730
5195
6470
8380
10420
11575
160
200
227
230
260
300
328
368
415
460
515
564
..125
16
16
16
16
20
20
25
25
25
25
25
216
267
294
285
322
370
404
455
498
551
602
666
1220
1415
1550
1810
2500
2870
3660
4320
5170
6100
7050
1130
1710
2100
2450
3120
4310
5160
7160
8600
10755
13080
15810
Thickness
of
insulation
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Diameter
under
armour
mm
Armour
wire
diameter
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)
STRaNDED COPPER & alUmINIUm CONDUCTORS
ThREE CORE CaBlES
Unroured nd roured, PvC seted cbes
*.Circular.conductors,.all.others.are.sector.shaped
Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
27/40BICC 25
. Stranded.Aluminium.Conductors.
600/1000 v
16
2535
50
70
95
120
150
185
240
300
400
115
150180
215
265
315
360
405
460
530
590
667
94
125150
175
215
260
300
335
380
440
495
570
99
131162
197
251
304
353
406
463
546
628
728
25
1712
09
06
05
04
03
03
02
02
02
25
1712
09
06
05
04
03
03
02
02
02
25
1712
09
06
05
04
03
03
02
02
02
89
115135
165
200
240
275
310
350
410
460
520
72
94110
135
165
200
230
255
295
340
385
443
74
98120
145
185
224
264
305
350
418
488
562
42
2719
14
10
07
06
05
04
03
03
02
42
2719
14
10
07
06
05
04
03
03
02
42
2719
14
10
07
06
05
04
03
03
02
Tbe 24
CURRENT RaTINgS (aC)
Stranded.Copper.Conductors
Nominal.
area.of
conductor
mm2
Direct.in
ground
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metreApproximate.voltage.drop.per.
ampere.per.metre
Direct.in.ground..Cables.touching
Single.way.ducts.-.ducts.touching
Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)
Installation.conditions.for.above.ratings:
Ambient air temperature:30C
Ground temperature: 15C
Depth.of.laying:05.m
Soil thermal resistivity: 1.2C m/W
Maximum conductor operating temperature at rated current is 90C
For.rating.factors.see.Tables.2.to.6.and.8.to.12
Stranded.Copper.Conductors Stranded.Aluminium.Conductors
600/1000 v
16
25
35
50
70
95
120
150
185
240
300
400
120
145
180
215
265
315
365
405
465
540
600
675
93
125
145
175
215
255
300
330
380
440
500
575
100
127
158
192
246
298
346
399
456
538
621
741
25
17
12
09
06
05
04
03
03
02
02
02
25
17
12
09
06
05
04
03
03
02
02
02
25
17
12
09
06
05
04
03
03
02
02
02
115
135
165
200
240
275
310
350
415
465
523
92
110
135
165
195
225
255
290
340
385
443
97
120
146
187
227
263
304
347
409
471
570
27
19
1410
07
06
05
04
03
03
02
27
19
14
10
07
06
05
04
03
03
02
27
19
14
10
07
06
05
04
03
03
02
Tbe 25
Nominal.
area.of
conductor
mm2
Direct.in
ground
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
STRaNDED COPPER & alUmINIUm CONDUCTORS
ThREE CORE CaBlES
aroured PvC seted cbes
Unroured PvC seted cbes
BICC
In.single
way.ducts
amps
In.single
way.ducts
amps
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
28/40BICC26
XlPE INSUlaTED CaBlES TO BS 5467
DImENSIONS aND WEIghTS
600/1000 v Tbe 26Unroured nd roured, PvC seted cbes
Nominal
area.of
conductor
mm2
16*
25
35
50
70
95
120
150
185
240
300
400
500#
07
09
09
10
11
11
12
14
16
17
18
20
22
200
210
245
265
310
352
390
435
490
545
610
675
742
-
520
650
900
1210
1550
1910
2410
2990
3890
4730
5780
7500
780
1160
1540
2100
2950
3970
4960
6160
7690
10070
12490
15620
19900
180
200
228
255
295
335
375
415
460
525
575
650
726
..125
16
16
16
20
20
25
25
25
25
25
..315
..315
234
261
286
320
377
417
471
514
566
630
688
781
820
........-
1200
1420
1770
2500
2980
3950
4600
5430
6660
7770
10380
12200
1320
1840
2310
2970
4240
5400
7000
8350
10130
12840
15530
19950
24360
Thickness
of
insulation
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Diameter
under
armour
mm
Armour
wire
diameter
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)
STRaNDED COPPER & alUmINIUm CONDUCTORS
fOUR CORE CaBlES
*.Circular.conductors,.all.others.are.sector.shaped
#Cable.as.per.IEC.60502.(Part.1)
Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
29/40BICC 27
Direct.in.ground..Cables.touching
Single.way.ducts.-.ducts.touching
Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)
Installation.conditions.for.above.ratings:
Ambient air temperature: 30C
Ground temperature: 15C
Depth.of.laying:.05.mSoil thermal resistivity: 1.2C m/W
Maximum conductor operating temperature at rated current is 90C
For.rating.factors.see.Tables..2.to.6.and.8.to.12
Stranded.Copper.Conductors .Aluminium.Conductors
600/1000 v
16
25
3550
70
95
120
150
185
240
300
400
500
120
145
180215
265
315
365
405
465
540
600
675
730
93
125
145175
215
255
300
330
380
440
500
575
610
100
127
158192
246
298
346
399
456
538
621
741
814
25
17
1209
06
05
04
03
03
02
02
02
02
25
17
1209
06
05
04
03
03
02
02
02
02
25
17
1209
06
05
04
03
03
02
02
02
02
.89
115
135165
200
240
275
310
350
415
465
523
565
72
92
110135
165
195
225
255
290
340
385
443
470
74
97
120146
187
227
263
304
347
409
471
570
626
42
27
1914
10
07
06
05
04
03
03
02
02
42
27
1914
10
07
06
05
04
03
03
02
02
42
27
1914
10
07
06
05
04
03
03
02
02
Tbe 28Unroured PvC seted cbes
Nominal.
area.of
conductor
mm2
Direct.in
ground
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
600/1000 vTbe 27
CURRENT RaTINgS (aC)
Stranded.Aluminium.Conductors.
1625
35
50
70
95
120
150
185
240
300
400
500
115150
180
215
265
315
360
405
460
530
590
667
720
94125
150
175
215
260
300
335
380
440
495
570
605
99131
162
197
251
304
353
406
463
546
628
728
800
2517
12
09
06
05
04
03
03
02
02
02
02
2517
12
09
06
05
04
03
03
02
02
02
02
2517
12
09
06
05
04
03
03
02
02
02
02
89115
135
165
200
240
275
310
350
410
460
520
561
7294
110
135
165
200
230
255
295
340
385
443
470
7498
120
145
185
224
264
305
350
418
488
562
618
4227
19
14
10
07
06
05
04
03
03
02
02
4227
19
14
10
07
06
05
04
03
03
02
02
4227
19
14
10
07
06
05
04
03
03
02
02
Stranded.Copper.Conductors
Nominal.
area.of
conductor
mm2
Direct.in
ground
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
STRaNDED COPPER & alUmINIUm CONDUCTORS
fOUR CORE CaBlES
aroured PvC seted cbes
In.single
way.ducts
amps
In.single
way.ducts
amps
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
30/40BICC28
XlPE INSUlaTED CaBlES TO BS 5467
DImENSIONS aND WEIghTS
600/1000 v Tbe 29Unroured nd roured, PvC seted cbes
Nominal
area.of
conductor
mm2
Nominal
area.of
neutralconductor
mm2
25
35
50
70
95
120
150
185
240
300
400
500#
16*
16*
25*
35
50
70
70*
95
120*
150*
185*
240*
09
09
10
11
11
12
14
16
17
18
20
22
214
232
261
304
348
394
425
477
534
590
670
740
-
-
860
1080
1390
1820
2190
2630
3500
4240
5560
6700
1070
1360
1920
2610
3500
4540
5440
6760
8900
11000
13900
17560
191
220
245
285
320
355
395
435
502
550
625
688
16
16
16
20
20
20
25
25
25
25
..315
..315
261
279
312
366
410
453
500
553
611
667
738
839
-
-
1710
2340
2800
3340
4360
5020
6220
7220
9950
11200
1750
2130
2770
3870
4910
6060
7610
9150
11620
13980
18250
22000
Thickness
of
insulation(phase)
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Diameter
under
armour
mm
Armour
wire
diameter
mm
Cable
diameter
overall
mm
Cable
weight
Aluminium
kg/km
Cable
weight
Copper
kg/km
Unarmoured.Cables.(approximate.values) Armoured.Cables.(approximate.values)
STRaNDED COPPER & alUmINIUm CONDUCTORS
fOUR CORE CaBlES WITh REDUCED NEUTRal CONDUCTOR
*.Circular.stranded.conductors,.all.others.are.sector.shaped
#Cable.as.per.IEC.60502.(Part.1)
Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
31/40BICC 29
600/1000 v
25
35
50
70
95
120
150
185
240
300
400
500
16*
16*
25*
35
50
70
70*
95
120*
150*
185*
240*
150
180
215
265
315
360
405
460
530
590
667
720
125
150
175
215
260
300
335
380
440
495
570
605
131
162
197
251
304
353
406
463
546
628
728
800
17
12
09
06
05
04
03
03
02
02
02
02
17
12
09
06
05
04
03
03
02
02
02
02
17
12
09
06
05
04
03
03
02
02
02
02
115
135
165
200
240
275
310
350
410
460
520
561
94
110
135
165
200
230
255
295
340
385
443
470
98
120
145
185
224
264
305
350
418
488
562
618
27
19
14
10
07
06
05
04
03
03
02
02
27
19
14
10
07
06
05
04
03
03
02
02
27
19
14
10
07
06
05
04
03
03
02
02
Tbe 30
CURRENT RaTINgS (aC)
aroured PvC seted cbes
Nominal.
area.of
conductor
mm2
Nominal.
area.of
neutral
conductor
mm2
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
Nominal.
area.of
conductor
mm2
Direct.in.ground..Cables.touching
Single.way.ducts.-.ducts.touching
*.Circular.conductors,.all.others.are.sector.shaped
Note:.Unarmoured.cables.are.as.per.IEC.60502.(Part.1)
Installation.conditions.for.above.ratings:
Ambient air temperature:30C
Ground temperature: 15C
Depth.of.laying:05.mSoil thermal resistivity: 1.2C m/W
Maximum conductor operating temperature at rated current is 90C
For.rating.factors.see.Tables.2.to.6.and.8.to.12
600/1000 v Tbe 31Unroured PvC seted cbes
Stranded.Copper.Conductors Stranded.Aluminium.Conductors.
25
35
50
70
95
120
150
185
240
300
400
500
16*
16*
25*
35
50
70
70*
95
120*
150*
185*
240*
145
180
215
265
315
365
405
465
540
600
675
730
125
145
175
215
255
300
330
380
440
500
575
610
127
158
192
246
298
346
399
456
538
621
741
814
17
12
09
06
05
04
03
03
02
02
02
02
17
12
09
06
05
04
03
03
02
02
02
02
17
12
09
06
05
04
03
03
02
02
02
02
115
135
165
200
240
275
310
350
415
465
523
565
92
110
135
165
195
225
255
290
340
385
443
470
97
120
146
187
227
263
304
347
409
471
570
626
27
19
14
10
07
06
05
04
03
03
02
02
27
19
14
10
07
06
05
04
03
03
02
02
27
19
14
10
07
06
05
04
03
03
02
02
Nominal.
area.of
neutral
conductor
mm2
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Direct.in
ground
amps
In.single
way.ducts
amps
Installed
in.air
amps
Ground
mV
Duct
mV
Air
mV
Current.Ratings Current.RatingsApproximate.voltage.drop.per.
ampere.per.metre
Approximate.voltage.drop.per.
ampere.per.metre
STRaNDED COPPER & alUmINIUm CONDUCTORS
fOUR CORE CaBlES WITh REDUCED NEUTRal CONDUCTOR
Stranded. Copper. Conductors Stranded.Aluminium. Conductors.
*.Circular.conductors,.all.others.are.sector.shaped
BICC
-
7/28/2019 Dubai Cables XLPEpower Cat Web Site
32/40BICC
215
210
200
195
190
185
175
165
155
150
145
140
135
130
125120
115
110
99
97
93
89
8480
74
68
62
16
265
260
250
245
235225
215
205
195
115
112
110
105
10097
94
89
84
70
251
240
230
220
210195
185
170
150
0607
0599
0589
0580
05720562
0554
0545
0536
185
463
450
430
415
395370
345
320
290
0255
0252
0249
0246
02430240
0237