ductwork submittals - the habegger corporation submittals project: project name contractor:...
TRANSCRIPT
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
DUCTWORK SUBMITTALS
PROJECT:PROJECT NAME
CONTRACTOR:CONTRACTOR NAME
PROJECT MANAGER
ENGINEER:ENGINEER NAME
CONTENTS:
SUBMITTED BY:Habegger Fabrication Division
Mike Frazier
Phone: (513) 761-0383
Fax: (513) 761-1293
Submitted: 05-07-12
23 31 13 DUCTWORK
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
1" WG POS GALVANIZED FIBERGLASS
2" WG POS 304 STAINLESS ELESTOMERIC
3" WG POS 316 STAINLESS DOUBLE-WALL
4" WG POS ALUMINUM 1/2" 2# DENSITY
6" WG POS PAINTGRIP/GALVANEEL 1" 1.5# DENSITY
10" WG POS BLACK IRON 1.5" 2# DENSITY
1" WG NEG POLY COATED 2" 3# DENSITY
2" WG NEG UNDERDUCT PERFORATED WALL
3" WG NEG SOLID WALL
4" WG NEG MYLAR
6" WG NEG TDF/TDC
10" WG NEG SLIP & DRIVE
WELD FLANGE SINGLE BLADE DAMPER
SNAP LOCK DUCTMATE ACCESS DOORS
PITTSBURGH COMPANION FLANGE REINFORCEMENTS
WELDED DUST PROTECTION
LINER COMMENTS
Engineer:
UNITS SYSTEM WG MIN GA MAT
Representative:
RECTANGULAR DUCT SUBMITTALS
Specifications: 23 31 13
Addendum(s):
System(s):
PROJECT NAME
CONTRACTOR NAME
PROJECT MANAGER
ENGINEER NAME
Project Name:
Contractor:
RECTANGULAR DUCT CONSTRUCTION BREAK-DOWNLINER MATERIAL
INCLUSIONS
CONNECTORS
METAL MATERIALPRESSURE CLASS
SEAMS
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
M.P.A.: Center angle welded per SMACNA
If duct narrow side is to be TDF/X same is to be on wide side
SHOP STANDARDS1/2”WG & 1"WG CONSTRUCTION
(NOT FOR ALUMINUM)
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)
73"-84" 20 56”
85"-96" 20 56”
DUCT
SIZE
0”-18”
25"-30"
31”-42”
43"-54"
DUCT
GAUGE
26
26
26
24
22
19"-24"
56”
56”
56”
55"-72"
97"-120"
120”-UP”
22
T-25a
TDC
T-25a
18
16
FULL
LENGTH
59”
59”/56"
56”
56”
WIDE SIDE CONNECTOR
1” Flat Slip
T-6 24GA
1-1/8” Standing Slip
T-11 26GA
TDC
T-25a
TDC w/ MPT & JTR
T-25a
TDC w/ (2)MPT & (2)JTR
T-25a
60"2”X2”X1/4” W/ MPA & (2) JTR
TDC
TDC
T-25a
TDC w/ MPT Tie-Rod
T-25a
TDC w/ MPA & (2)JTR
TDC w/ (2)MPT & (2)JTR
T-25a
T-25a
NARROW SIDE
CONNECTOR
Flat Drive
T-1 24GA
TDF/X
T-25A
TDC
T-25a
T-25a
2”X2”X1/4” W/ MPA & (2) JTR
T-25a
TDC
T-25a
TDC w/ MPT Tie-Rod
T-25a
TDC w/ MPA & (2)JTR
TDC w/ MPT & JTR
J.T.R.: Joint Tie Rod
M.P.T.: Center Tie Rod
NOTES:
If minimum is required, replace all thiner gauges with required minimum gauge
T-22 T-22
TIE RODS ARE 1/2" E.M.T.
If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
M.P.A.: Center angle welded per SMACNA
If duct narrow side is to be TDF/X same is to be on wide side
TDC w/ MPA & (2)JTR
T-25a T-25a
M.P.T.: Center Tie Rod
TIE RODS ARE 1/2" E.M.T.
97"-120" 18 56”TDC w/ MPA & (2)JTR
2”X2”X1/4” W/ MPA & (2) JTR
T-22
TDC w/ (2)MPT & (2)JTR TDC w/ (2)MPT & (2)JTR
T-25a T-25a
120”-UP” 16 60"2”X2”X1/4” W/ MPA & (2) JTR
T-22
85"-96" 20 56”
TDC
T-25a T-25a
TDC w/ MPT & JTR
56”TDC w/ (2)MPT & JTR TDC w/ (2)MPT & JTR
T-25a T-25a
T-25a
T-25a
(NOT FOR ALUMINUM)
1-1/8” Standing Slip TDF/X
T-11 26GA T-25A
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)
0”-16” 26 59”1” Flat Slip Flat Drive
T-6 24GA T-1 24GA
17"-22" 26 59”/56"
TDC
24 56”
23"-26" 26 56”TDC
T-25a
TDC
NARROW SIDE
CONNECTOR
27"-30"
T-25a
73"-84" 20
T-25a T-25a
TDC w/ MPT & JTR
56”TDC w/ MPT & JTR
56”TDC
31"-37" 22
SHOP STANDARDS2”WG CONSTRUCTION
DUCT
SIZE
DUCT
GAUGE
FULL
LENGTHWIDE SIDE CONNECTOR
TDC
T-25a T-25a
T-25a T-25a
TDC w/ MPT Tie-Rod TDC w/ MPT Tie-Rod
56”TDC w/ MPT & JTR
55"-60" 20
38"-54" 22 56”
61"-72" 20
NOTES:
If minimum is required, replace all thiner gauges with required minimum gauge
J.T.R.: Joint Tie Rod
If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
M.P.A.: Center angle welded per SMACNA
If duct narrow side is to be TDF/X same is to be on wide side
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)
(NOT FOR ALUMINUM)
NARROW SIDE
CONNECTOR
SHOP STANDARDS3”WG CONSTRUCTION
T-25a
17"-22" 24 59"/56”
T-1 24GA
0”-12” 26 59”1” Flat Slip Flat Drive
43"-54" 22 56”
T-25a
27"-30" 22 56”TDC TDC
T-25a
DUCT
SIZE
DUCT
GAUGE
FULL
LENGTHWIDE SIDE CONNECTOR
T-25a
61"-84" 20 56”
T-6 24GA T-1 24GA
13"-16" 24 59”1” Flat Slip Flat Drive
T-6 24GA
1-1/8” Standing Slip TDC
T-11 26GA T-25a
23"-26" 24 56”TDC TDC
T-25a
T-25a
31"-42" 22 56”TDC w/ MPT Tie-Rod TDC w/ MPT Tie-Rod
T-25a
TDC w/ MPT & JTR TDC w/ MPT & JTR
T-25a T-25a
55"-60" 20 56”TDC w/ MPT & JTR TDC w/ MPT & JTR
T-25a
TDC w/ (2)MPT & JTR TDC w/ (2)MPT & JTR
T-25a T-25a
85"-96" 18 56”TDC w/ (2)MPT & (2)JTR TDC w/ (2)MPT & (2)JTR
T-25a T-25a
97"-120" 18 56”TDC w/ MPA & (2)JTR TDC w/ MPA & (2)JTR
T-25a T-25a
120”-UP” 16 60"2”X2”X1/4” W/ MPA & (2) JTR 2”X2”X1/4” W/ MPA & (2) JTR
T-22 T-22
NOTES:
If minimum is required, replace all thiner gauges with required minimum gauge
J.T.R.: Joint Tie Rod
M.P.T.: Center Tie Rod
TIE RODS ARE 1/2" E.M.T.
If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
M.P.A.: Center angle welded per SMACNA
If duct narrow side is to be TDF/X same is to be on wide side
SHOP STANDARDS4”WG CONSTRUCTION
TDC
T-25a T-25a
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCT)
(NOT FOR ALUMINUM)
DUCT
SIZE
DUCT
GAUGE
FULL
LENGTHWIDE SIDE CONNECTOR
NARROW SIDE
CONNECTOR
43"-54" 22 56”
T-25a
27"-28" 24 56"TDC TDC
T-25a
13"-26" 24 56"TDC
61"-84" 20 56”
T-25a
0”-12” 26 56"TDC TDC
T-25a T-25a
T-25a
29"-42" 24 56”TDC w/ MPT Tie-Rod TDC w/ MPT Tie-Rod
T-25a
TDC w/ MPT & JTR Tie-Rod TDC w/ MPT & JTR Tie-Rod
T-25a T-25a
55"-60" 20 56”TDC w/ MPT & JTR Tie-Rod TDC w/ MPT & JTR Tie-Rod
T-25a
TDC w/ (2)MPT & JTR TDC w/ (2)MPT & JTR
T-25a T-25a
85"-96" 18 56”TDC w/ (2)MPT & (2)JTR TDC w/ (2)MPT & (2)JTR
T-25a T-25a
97"-120" 18 56”TDC w/ MPA & (2)JTR TDC w/ MPA & (2)JTR
T-25a T-25a
120”-UP” 16 60"2”X2”X1/4” W/ MPA & (2) JTR 2”X2”X1/4” W/ MPA & (2) JTR
T-22 T-22
NOTES:
If minimum is required, replace all thiner gauges with required minimum gauge
J.T.R.: Joint Tie Rod
M.P.T.: Center Tie Rod
TIE RODS ARE 1/2" E.M.T.
If M.P.T. (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
`
WASHER BOLT
WASHER
BOLT
LIGHT WALL CONDUIT DUCT
T-1 26GA T-6 24GA T-11 26GA T-25A
SEAMS, JOINTS AND TIE RODS
PITTSBURGH SNAP LOCK WELD SEAM
TIE ROD SECTION VIEW
TIE ROD ASSEMBLY DETAIL
WELD SEAMCOMPANION
FLANGE
STANDING SEAM
FLAT DRIVE FLAT SLIP TDF/X
1/2" OR 3/4"
CONDUIT
STANDING SLIP
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
Operating Temperature
Maximum Air Velocity
Water Vapor
Fungi Resistance
Bacteria Resistance
Corrosiveness
Thermal Conductivity
K @ 75 degrees F - Type 200
R-4.2
R-6.3
R-8.0
Surface Burning Characteristics
Flame Spread
Smoke Developed
LINER INFORMATION
20
ASTM C518 0.23
0.24
0.24
0.24
25
ASTM C665
250 degrees F
6,000 FPM (30.5 M/SEC)
<3% AT 120 Degrees F, 95% RH
Meets Requirements
Meets Requirements
Meets Requirements
Btu*in/hr*ft2*degrees F
Value
ASTM C411
ASTM C1104
ASTM C1338
ASTM G21
ASTM G22
ASTM E84, UL 723
CAN/ULC SI02
UL 181 Erosion Test
ASTM C1071
Owens Corning "QuietR Rotary DuctLiner"
Will not cause corrosion greater then by sterile
cotton on alum. or steel*
NOTE: Metal nosing will only be used where required by S.M.A.C.N.A. or as required by
specifications.
Property Test Method
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
3.25" - 6.5"
3.25"
45 45 45 45
6" 9" 6"
7" 7"
5" 5"
5" 5"
6"
18" DUCT (AND
SMALLER) 1 REQD
48" DUCT 3
REQD
36" DUCT 3
REQD
24" DUCT 2
REQD
TDF CONNECTION RECOMMENDED CLIP SPACING
DOUBLE WALL VANES
TDF/X CONNECTION AND DUCT DETAILS
SINGLE WALL VANES
60" DUCT 4
REQD
TURNING VANE INSTALLATION DETAILS
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
BEADS @ 12"
Finished Length (see below)
59" - FINISHED LENGTH WITH SLIP & DRIVE CONNECTIONS
56" - FINISH LENGTH WITH TDF/X CONNECTIONS
60" - FINISH LENGTH WITH RAW (UNFINISHED) CONNECTIONS
All ductwork is G-90 hat dipped Galvanized material unless otherwise noted
All ductwork is beaded per S.M.A.C.N.A, requirements unless otherwise noted
STRAIGHT DUCT LENGTH DESCRIPTIONS
GENERAL DUCTWORK INFORMATION
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
W2
W2 W2 X C2
X C2 X C2 D2
D2 D2 STR2
THR1
THR2 C1 THR2 C1 STR1 C1
THR1 THR1
W1 X D1 W1 X D1 W1 X D1
W2 X D2 W2 X D2 W2 X D2
C2 C2 C2
STR2
THR2 C1 THR2 C1 THR1 C1
THR1 THR1 STR1
W1 X D1 W1 X D1 W1 X D1
W2 X D2 W2 X D2 W2 X D2
O2 O2 THR2
L L
BOT BOT STR
O1 C1 O1 THR1
W1 X D1 W1 X D1 W1 X D1
L L L
S
W1 X D1 W1 X D1 W1 X D1
C2
C1
SQ THR/HEEL 90
SQ THR/RAD HEEL 45
SQ THR/RAD HEEL 90
SQ THR/HEEL 45
C2
RAD THR/HEEL 90
GENERAL FITTING INFORMATION
SQ THR/HEEL 45
OGEE OFFEST SQ OFFSET
C1
C2
EL OFFSET
CANVAS STR TAP SHOE/BOOT TAP
C2
C1
C1
C2
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
STR2 STR3
C2
W2 C2 C3 W3 O1 W2 W3
X X X C2 C3 X
D2 W3 L BOT D2 D3
THR2 THR3 C1 THR1 THR2
THR1 W1 X D1 STR1 W1 X D1
W2 X D2
C2 C3 C2 STR1 STR1
W3 W3 W4
L BOT1 BOT2 L C3 X X X
D3 D3 C3 C4 D4
O1 O2 C1 THR1 THR1 THR2
W1 X D1 W1 X D1 W1 X D1
W2 X D2
C2
C1
L
C1
W2 X D2
W1 X D1
C1
W2 X D2 W3 X D3
SQ TEE SQ TO RND RAD TEE
SQ PANTS RAD LAT TEE RAD CROSS
C1
O3
The Habegger Corporation
Sheet Metal Fabrication Division
925 Redna Terrace, Cincinnati, Ohio 45215
PH: (513) 761-0383
THE HABEGGER CORPORATION Fax: (513) 761-1451
SHEET METAL FABRICATION E-Mail:[email protected]
STANDARD CONSTRUCTION DETAILS STANDARD CONSTRUCTION DETAILS
FRAME: 16 GAUGE GALVANIZED STEEL FRAME: 16 GAUGE GALVANIZED STEEL
DIE FORMED AND WELDED FOR DIE FORMED AND WELDED FOR
STRUCTURAL INTEGRITY 6" WIDE STRUCTURAL INTEGRITY 6" WIDE
BLADES: 16 GAUGE GALVANIZED STEEL BLADES: 16 GAUGE GALVANIZED STEEL
AXELS: DIE CAST ZINC BOLTED WITH AXELS: DIE CAST ZINC BOLTED WITH
1/4" BOLT AND NUT 1/4" BOLT AND NUT
BUSHINGS: BRASS BUSHINGS: BRASS
LINKAGE: N/A LINKAGE: INTERNALLY MOUNTED PLATE
STEEL AND CRANK PLATES
BLADE STOPS: 16 GAUGE ANGLES AT HEAD BLADE STOPS: 16 GAUGE ANGLES AT HEAD
AND SILL AND SILL
HEAVY DUTY METAL QUAD ON 1.5" STAND-OFF HEAVY DUTY METAL QUAD ON 1.5" STAND-OFF
OPTIONAL FEATURES OPTIONAL FEATURES
JAMB AND BLADE SEALS JAMB AND BLADE SEALS
2” STANDOFF 2” STANDOFF
1/2" CONTROL ROD FOR MOTORIZED APPLICATION 1/2" CONTROL ROD FOR MOTORIZED APPLICATION
SINGLE-BLADE DAMPER MULTI-BLADE DAMPER