BOARD OF EDUCATION Office of Capital Programs 440 North Broad Street, 3 rd Floor – Suite 371 Philadelphia, PA 19130 TELEPHONE: (215) 400-4730 Page 1 of 6 Addendum No. 2 Subject: Duckrey Flood Remediation: B-075C, B-076C, B-077C, and B-087C OF 2018/2019 Location: Duckrey Elementary School This Addendum, dated April 22, 2020, shall modify and become part of the Bid Documents. Any items not mentioned herein, or affected by, shall remain strictly in accordance with the original document. 1.VIRTUAL WALK THROUGH See the following link: https:/aec.cintoo.com/0C192F17380D29143C38 2. BID SUBMISSION AND VIDEO BID OPENING Due to restrictions in place for COVID-19 by Governor Wolf’s “stay at home” order including practicing personal distancing the School District has decided to conduct the opening of the bids virtually through a live stream until further notice. (a) BID SUBMISSION: Fully executed original copies of the complete required bid proposals will be delivered to the address below. The School District of Philadelphia 15 th Street Entrance (15 th and Hamilton) Philadelphia, PA 19130-4015 From 1:00 p.m. to 2:00 p.m. on Tuesday, April 28, 2020. NOTE: Bidders are required to comply with social distancing and other CDC and Department of Health mitigation measures when delivering bids. (b) VIDEO BID OPENING: All proposals received will be opened and read aloud by live video stream at 2:30 p.m.

Upload: others

Post on 13-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

BOARD OF EDUCATION Office of Capital Programs

440 North Broad Street, 3rd Floor – Suite 371 Philadelphia, PA 19130

TELEPHONE: (215) 400-4730

Page 1 of 6

Addendum No. 2

Subject: Duckrey Flood Remediation: B-075C, B-076C, B-077C, and B-087C OF 2018/2019 Location: Duckrey Elementary School This Addendum, dated April 22, 2020, shall modify and become part of the Bid Documents. Any items not mentioned herein, or affected by, shall remain strictly in accordance with the original document. 1.VIRTUAL WALK THROUGH See the following link: https:/aec.cintoo.com/0C192F17380D29143C38 2. BID SUBMISSION AND VIDEO BID OPENING Due to restrictions in place for COVID-19 by Governor Wolf’s “stay at home” order including

practicing personal distancing the School District has decided to conduct the opening of the bids virtually through a live stream until further notice. (a) BID SUBMISSION: Fully executed original copies of the complete required bid proposals will be delivered to the address below. The School District of Philadelphia 15th Street Entrance (15th and Hamilton) Philadelphia, PA 19130-4015

From 1:00 p.m. to 2:00 p.m. on Tuesday, April 28, 2020. NOTE: Bidders are required to comply with social distancing and other CDC and Department of Health mitigation measures when delivering bids. (b) VIDEO BID OPENING: All proposals received will be opened and read aloud by live video stream at 2:30 p.m.

Page 2: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

Addendum No. 2 (cont’d)

Page 2 of 6

The link to the video bid opening is: Join Zoom Meeting https://zoom.us/j/92485775356?pwd=SVRoN1h4SFhNbStqZWJjajFFOW1rZz09 Meeting ID: 924 8577 5356 Password: 7c86Vi

3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal Form, which includes new unit price items. 4. QUESTIONS AND ANSWERS 1. Question:

Note no. 20 on drawing EP-001 states that “all areas of this contract are considered corrosive” and calls for the use of all PVC coated “conduit, supports, fittings” and the use of stainless steel hardware in all such areas. Please confirm that this is the intent of the design. If so, please revise conduit and hardware specifications to include all stainless steel hardware and replace RGS conduit with PVC Coated RGS. Response: PVC Coating is not required. Note 20 has been deleted from EP-001.

2. Question: Specification section 260528 calls for the use of SS-316 hardware and PVC Coated U Channel in multiple areas applicable to this project. Please note that SS-316 hardware is, on average, 30% more expensive than standard SS-304. The use of the SS-316 hardware along with PVC coated U Channel will significantly increase the cost of the electrical construction. Please confirm that the materials are specified correctly. Response: Provide 316 Stainless Steel hardware per specification section 26 0528.

3. Question: Specification section 260533 calls for the use of RGS conduit for the entire project. Is the EMT conduit allowed?

Response: Refer to electrical drawings for application of RGS conduit. All conduits in Electrical Rooms, Boiler Rooms, and Mechanical Rooms shall be galvanized rigid steel. EMT conduit will only be considered for substitution in lieu of RGS if not subjectable to physical damage and not specifically noted to be RGS or other type of conduit.

4. Question: Can MTU generators be an approved manufacturer for the emergency generator? This generator manufacturer is currently in use in numerous schools.

Response: No substitutions will be evaluated during bidding. Refer to the General Conditions and Supplementary Conditions.

5. Question Is there a section 26 3600 Transfer Switches available?

Page 3: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

Addendum No. 2 (cont’d)

Page 3 of 6

Response: See attached Specification Section 26 3600.

6. Question Drawing E-001 as well as other E series drawings did not print out correctly as the symbols were distorted. Please re-issue the drawings in a PDF format.

Response: See attached resubmission of “E” Series Drawings.

7. Question: Please confirm that all conduits in the boiler room and mechanical rooms are required to be galvanized rigid steel.

Response:

Refer to question #3. 8. Question:

Drawing E-105 #2 Partial Single Line: Should the power wiring from the emergency generator be “4 #1 and a #6 ground?”

Response: Power wiring from the generator shall be 4#1 + 1#6 GND

9. Question

Can SDP re-issue Electrical Drawings? From the download link provided on the School District website it appears to be corrupted.

Response: See attached re-issued Electrical Drawings.

10. Question

Is it the designer's intent to provide a new BAS for the building or only the new mechanical equipment? If only the new equipment, is it stand alone or tied to a network? I don't see any notes mentioning an existing BAS system that new controls would tie to. What is controlling the HVAC equipment serving occupied spaces? There must be some way to coordinate the operating mode (summer/winter) of the terminal equipment with the main supply, and for schedules, setbacks, etc.

Response: No Building Automation System (BAS) currently exists and the scope of this work will not include a BAS. All equipment provided by the Mechanical Contractor per this scope of work will be standalone, unitary equipment. Provide future BAS connectivity capability on the new Chiller per Specification Section 23 6426 2.07 D.

11. Question

Will school be in session or occupied during construction? Response: We currently anticipate that school will resume as scheduled at the end of August.

12. Question

Drawing EP-102, Keyed Work Note #10: What size conduit for data entrance? Where is the Verizon equipment located. Response:

Page 4: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

Addendum No. 2 (cont’d)

Page 4 of 6

Provide one (1) 4” Conduit for Verizon Service. Provide a unit price for 300 linear feet of 4” Conduit. Coordinate routing with SDP Construction Manager, Verizon, and SDP IT Group. See Unit Price No 1 on Revised Electrical Bid Proposal Form,

13. Question

EP-102, Keyed New Work Note #22: What is the starter/disconnect on the west wall adjacent to Panels PB-1 & PB-2 feeding? Response: Boiler Room exhaust fan. Refer to M-102.

14. Question Drawing EP-102, Keyed New Work Note #26: What are the two VFDs on the south wall feeding? Response: HHWP-1 & HHWP-2. Refer to M-102.

15. Question EP-402: What does “Feeder Legend #9” on single line feed. Response: Refer to revised drawing EP-402.

16. Question Drawing EP-202, Key Note #3: What is the required amperage for the safety switches feeding the passenger and freight elevators? Response: 110A Minimum.

17. Question Drawing EP-402, Feeder Legend: What is the 4th current carrying conductor used for and where do we connect? Response: Refer to revised EP-402.

18. Question All Drawings: Can you provide electrical drawings showing the mechanical equipment disconnect? L&I requires all electrical devices shown on the “E” drawings and not buried on the mechanical drawings. Which contractor is required for load side wiring of disconnects to mechanical equipment? Response: Permit drawings will be coordinated with the awarded contractors. The electrical contractor is responsible for load side wire and conduit.

19. Question Drawing EP-104, Key Notes 8,9,10: Where do data wires terminate? Do you have a location of the IT closet in the building? Response: Provide CAT6 cable, conduit, and raceways per drawing notes. Provide 6,500 linear Provide two hundred (200) linear feet of 1” conduit for data drops. Provide three hundred (300) linear feet of 2x2x10 cable tray for data drops. Coordinate termination of CAT6 cable with SDP IT Group and SDP Construction Manager. ee Unit Prices 2, 3, and 4 on Revised Electrical Bid Proposal Form.

Page 5: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

Addendum No. 2 (cont’d)

Page 5 of 6

20. Question Drawing EP-104, EP-301 & M-601. Does DWP-1A & 1B come with a control panel or VFDs? I cannot locate this piece of equipment on Drawing M-601. Circuit calls for three #10 wires to be connected to a 50 amp, one pole circuit breaker. Is this correct? Response: Integral control panel provided with the pump skid. Refer to P-104 and P-501. Refer to revised EP-301

5. SPECIFICATIONS CHANGES ADD the following Specification Sections to the Contract Documents. 26 3600 Transfer Switches 6. DRAWING CHANGES REVISE the following Drawings. EP-001

• DELETE General Note #20.

EP-102 • REVISE DELETE Keynote #18. • DELETE Keynote #27. • Keynote #10 to “PROVIDE ONE (1) 4” CONDUIT FOR VERIZON SERVICE. PROVIDE A UNIT

PRICE FOR THREE HUNDRED (300) LINEAR FEET OF 4” CONDUIT. COORDINATE ROUTING WITH SDP CONSTRUCTION MANAGER, VERIZON, AND SDP IT GROUP.”

EP-104 • ADD Keynote #13 near northwest exit door: “INSTALL NEW EMERGENCY STOP SWITCH

FOR THE BOILER, FURNISHED BY MECHANICAL CONTRACTOR. REFERENCE DETAIL 4/EP-301.

• ADD Keynote #14 near northwest exit door: “INSTALL NEW EMERGENCY STOP SWITCH FOR THE CHILLER FURNISHED BY MECHANICAL CONTRACTOR.”

• ADD General Note #5: “PROVIDE SIX THOUSAND FIVE HUNDRED (6,500) LINEAR FEET OF CAT6 CABLE FOR DATA DROPS. PROVIDE TWO HUNDRED (200) LINEAR FEET OF 1" CONDUIT FOR DATA DROPS. PROVIDE THREE HUNDRED (300) LINEAR FEET OF 2x2x10 CABLE TRAY FOR DATA DROPS. COORDINATE TERMINATION OF CAT6 CABLE WITH SDP IT GROUP AND SDP CONSTRUCTION MANAGER.”

EP-202 • REVISE Keynote #6 from “PROVIDE TELEPHONE CONNECTION AT ELEVATOR MACHINE

ROOM…” TO “PROVIDE TELEPHONE CONNECTION AT ELEVATOR CONTOLLER…”

EP-301 • ADD Circuit 57 to NEW PANEL PB1 Schedule. • REVISE PB2 25/27/29 and 26/28/30 pole requirements.

EP-401 • ADD clarification notes. See attached drawing.

Page 6: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

Addendum No. 2 (cont’d)

Page 6 of 6

EP-402 • ADD clarification notes. See attached drawing.

“E” Series • REISSUED to correct formatting corruption.

END OF ADDENDUM #2

ATTACHMENTS: Revised Electrical Bid Form, 6 pages Added Specifications and Revised Drawings, 28 pages

Page 7: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

BID PROPOSAL FORM-ELECTRICAL (Rev) Page 1 of 6

BID PROPOSAL FORM (Revised) FLOOD REMEDIATION

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL

Contract No. B-077C of 2018/19 Electrical Construction

TO: The School District of Philadelphia OWNER Board of Education Office of Capital Programs ADDRESS

The School District of Philadelphia 440 North Broad Street Third Floor - Suite 371 Philadelphia, PA 19130-4015

FROM: __________________________________________ CONTRACTOR

__________________________________________ ADDRESS __________________________________________ __________________________________________ CITY/STATE __________________________________________ CONTACT NAME __________________________________________ PHONE NO.

BASE CONTRACT PROPOSAL:

1. Having become completely familiar with the local conditions affecting the cost of Work at the place where Work is to be executed, and having carefully examined the site conditions as they currently exist, and having carefully examined the Bidding and Contract Documents prepared for this project, together with any Addenda to such Bidding and Contract Documents as listed hereinafter, the Undersigned hereby proposes and agrees to provide all labor, materials, plant, equipment, transportation and other facilities as necessary and/or required to execute all of the Work described by the Contract Documents for the lump sum consideration of: ________________________________________ __________Dollars ($______________), said amount being hereinafter referred to as the Base Proposal Amount. Base proposal Amount includes any Allowances, Alternates or Unit Price Items listed below, if applicable.

Page 8: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

BID PROPOSAL FORM-ELECTRICAL (Rev) Page 2 of 6

ALLOWANCES: ALLOWANCE NO.1- This Allowance is for PECO work described in Section 01 1000 Summary of Work and shown on the Electrical Drawings, to be paid in accordance with Section 01 1650 ALLOWANCES.

AMOUNT OF ALLOWANCE INCLUDED IN BASE BID: $25,000.

BID ALTERNATES (Not applicable to this Contract – No Alternates)

UNIT PRICES:

UNIT PRICE NO. 1: 4” CONDUIT FOR VERIZON SERVICE 1. Provide one (1) 4” Conduit for Verizon Service. Provide a unit price for 300 linear feet of 4” Conduit per Keyed Note # 10 on Drawing EP-102. Coordinate routing with SDP Construction Manager, Verizon, and SDP IT Group. 2. Unit of Measurement: per linear foot (LF) 3. Payment: Payment to be made for the actual quantities in accordance with Section 01 1600-UNIT PRICES. 4. Estimated Quantity included in Base Bid: 300 LF 5. Unit Price Calculation (to be included in Base Bid Amount): 300 LF @ $ per LF = $ Total* *This amount included in Base Bid Amount

UNIT PRICE NO. 2: CAT 6 CABLE 1. Provide 6,500 linear of CAT 6 Cable per Keynotes 8, 9 and 10 on Drawing EP-104. Coordinate termination of CAT6 cable with SDP IT Group and SDP Construction Manager. 2. Unit of Measurement: per Linear Foot (LF) 3. Payment: Payment to be made for the actual quantities in accordance with Section 01 1600-UNIT PRICES. 4. Estimated Quantity included in Base Bid: 6,500 LF 5. Unit Price Calculation (to be included in Base Bid Amount): 6,500 LF @ $ per LF =

Page 9: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

BID PROPOSAL FORM-ELECTRICAL (Rev) Page 3 of 6

$ Total* *This amount included in Base Bid Amount

UNIT PRICE NO. 3: 1” CONDUIT FOR DATA DROPS 1. Provide two hundred (200) linear feet of 1” conduit for data drops per Keynotes 8, 9 and 10 on Drawing EP-104. Coordinate termination of CAT6 cable with SDP IT Group and SDP Construction Manager. 2. Unit of Measurement: per linear foot (LF) 3. Payment: Payment to be made for the actual quantities in accordance with Section 01 1600-UNIT PRICES. 4. Estimated Quantity included in Base Bid: 200 LF 5. Unit Price Calculation (to be included in Base Bid Amount): 200 LF @ $ per LF = $ Total* *This amount included in Base Bid Amount UNIT PRICE NO. 4: CABLE TRAY FOR DATA DROPS 1. Provide three hundred (300) linear feet of 2x2x10 cable tray for data drops per Keynotes 8, 9 and 10 on Drawing EP-104.. Coordinate termination of CAT6 cable with SDP IT Group and SDP Construction Manager. 2. Unit of Measurement: per linear foot (LF) 3. Payment: Payment to be made for the actual quantities in accordance with Section 01 1600-UNIT PRICES. 4. Estimated Quantity included in Base Bid: 300 LF 5. Unit Price Calculation (to be included in Base Bid Amount): 300 LF @ $ per LF = $ Total* *This amount included in Base Bid Amount

Page 10: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

BID PROPOSAL FORM-ELECTRICAL (Rev) Page 4 of 6

ACKNOWLEDGEMENT OF RECEIPT OF ADDENDA:

2. The Undersigned acknowledges receipt of the following Addenda (list by

number and date appearing on Addenda): Addendum No. Date Addendum No. Date ____________ ___________ ______________ _________ ____________ ___________ ______________ _________ ____________ ___________ ______________ _________ ____________ ___________ ______________ _________ TIME OF COMPLETION:

3. The Undersigned agrees to Substantially Complete all Work under this Contract within the time periods specified in Division 1, General Requirements, Section 00 1300 entitled “Time of Completion, Milestones and Phasing or Sequencing Requirements”. INSURANCE:

4. All Bidders are instructed to refer to Article GC-11 of the General Conditions. All Contractors or Subcontractors bidding Work on the Project shall include in their bids the costs of Workers Compensation and Employer’s Liability Insurance, Commercial General Liability Insurance, Automobile Liability Insurance, Excess Umbrella Liability Insurance (Commercial Umbrella Liability Insurance) and any other types of insurance identified in Division 1- General Requirements, Section 01200 (or 01 1200) entitled “ Special Insurance Requirements”. LIQUIDATED DAMAGES:

5. Upon failure by the Contractor to achieve Substantial Completion within the time specified in Article GC-8 of the General Conditions from the Date of Commencement as set forth in the Notice to Proceed, the Contractor shall pay to the School District, as liquidated damages and not as a penalty, the sum of One Thousand Dollars ($1,000.00) per day for each consecutive calendar day of delay until such time as Substantial Completion of the Work is achieved.

Page 11: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

BID PROPOSAL FORM-ELECTRICAL (Rev) Page 5 of 6

6. In addition, the Contractor shall be responsible for and pay for the cost of completion of construction of the Work, as well as for any and all additional charges of the School District, Architect/Engineer, other Project Contractors, and any other Consultants to the School District relating to the Contractor's failure to achieve Substantial Completion on a timely basis, including, but not limited to, delay damages, disruption damages, acceleration costs or expenses, investigative expenses, consulting fees, experts’ fees, and attorneys’ fees.

7. The Contractor and the School District agree that the amounts so fixed herein as liquidated damages are reasonable forecasts of just compensation for the harm that will be caused to the School District by the Contractor's breach. GENERAL STATEMENT:

8. The Undersigned declares that the person or persons signing this Proposal is/are fully authorized to sign on behalf of the firm listed and to fully bind the firm listed to all the Proposal's conditions and provisions thereof.

9. It is agreed that the Undersigned has complied or will comply with all requirements of local, state, and federal laws, and that no legal requirement has been or will be violated in making or accepting this Proposal, in awarding the Contract to it and/or in prosecution of the Work.

10. Bid Security in the amount of ten percent (10%) of the Base Bid, plus all additive Alternates Proposal amounts, is attached hereto and made a part hereof, without endorsement, in the sum of __________________ Dollars ($_________________), which shall become the property of the School District in the event the Contract and Performance Bond and Labor and Materialmen's Bond are not executed within the time set forth, as liquidated damages.

11. The Undersigned further agrees within five (5) calendar days from date of Notice of Acceptance of this Proposal or Contract award, to sign and deliver to the School District, all required copies of the School District/Contractor Agreement, the Performance Bond, the Labor and Materialmen's Bond, and the Maintenance Bond, in the forms included in the Bidding Documents, and the policies of insurance or insurance certificates as required by the General Conditions. In case the undersigned fails or neglects to deliver within the specified time the School District/Contractor Agreement, the Performance Bond, the Labor and Materialmen's Bond, and the Maintenance Bond, and the insurance policies or certificates, all as aforesaid, the undersigned shall be considered as having abandoned the Contract, and the Bid Bond accompanying this Proposal shall be forfeited to the School District by reason of such failure on the part of the undersigned, as liquidated damages and not as a penalty.

12. The Undersigned further agrees that the Bid Security may be retained by the School District and shall remain with the School District until the School

Page 12: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

BID PROPOSAL FORM-ELECTRICAL (Rev) Page 6 of 6

District/Contractor Agreement has been signed and delivered to the School District and the Performance Bond, the Labor and Materialmen's Bond, and the Maintenance Bond, and insurance policies or certificates have been made and delivered to the School District. Respectfully submitted this _____day of ____________, 201_.

Individual Proprietorship or Partnership If Contractor is an individual proprietorship or is a partnership, sign here: __________________________ (Trade Name of Firm) By: _______________________ By: ______________________ (SEAL) (Witness) (Owner or Partner)

Corporation If Contractor is a corporation, sign here: ______________________________ (Name of Corporation) ATTEST: By: _______________________ By: ______________________ (SEAL) (Secretary or Treasurer) (President or Vice President) (CORPORATE SEAL) Signature by anyone other than the President or Vice President and the Secretary or Treasurer of the Corporation must be accompanied by a power of attorney, executed by the proper corporate officers under the corporate seal indicating authority to execute this Bid.

Page 13: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL - FLOOD REMEDIATION PROJECT SDP CONTRACT NO. B-075c, B-076c, B-077c and B-078c of 2018/2019

TRANSFER SWITCHES 26

3600 - 1

SECTION 26 3600

TRANSFER SWITCHES

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes automatic transfer switches rated 600 V and less.

B. See Division 21 Section "Electric-Drive, Centrifugal Fire Pumps" for automatic transfer switches for fire pumps.

C. See Division 21 Section "Electric-Drive, Vertical-Turbine Fire Pumps" for automatic transfer switches for fire pumps.

1.2 SUBMITTALS

A. Product Data: Include rated capacities, weights, operating characteristics, furnished specialties, and accessories.

B. Shop Drawings: Dimensioned plans, elevations, sections, and details showing minimum clearances, conductor entry provisions, gutter space, installed features and devices, and material lists for each switch specified.

1. Dimensioned Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

2. Detailed description of equipment anchorage devices on which the certification is based.

C. Field quality-control test reports.

D. Operation and maintenance data.

1.3 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Comply with NEMA ICS 1.

C. Comply with NFPA 70.

D. Comply with NFPA 99.

E. Comply with NFPA 110.

F. Comply with UL 1008 unless requirements of these Specifications are stricter.

Page 14: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL - FLOOD REMEDIATION PROJECT SDP CONTRACT NO. B-075c, B-076c, B-077c and B-078c of 2018/2019

TRANSFER SWITCHES 26

3600 - 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Contactor Transfer Switches:

a. AC Data Systems, Inc. b. Caterpillar; Engine Div. c. Emerson; ASCO Power Technologies, LP. d. Generac Power Systems, Inc. e. GE Zenith Controls. f. Kohler Power Systems; Generator Division. g. Onan/Cummins Power Generation; Industrial Business Group. h. Russelectric, Inc. i. Spectrum Detroit Diesel. j. Kato Light

2. Transfer Switches Using Molded-Case Switches or Circuit Breakers:

a. AC Data Systems, Inc. b. Eaton Electrical Inc.; Cutler-Hammer. c. GE Zenith Controls. d. Hubbell Industrial Controls, Inc. e. Lake Shore Electric Corporation. f. APC

2.2 GENERAL TRANSFER-SWITCH PRODUCT REQUIREMENTS

A. Indicated Current Ratings: Apply as defined in UL 1008 for continuous loading and total system transfer, including tungsten filament lamp loads not exceeding 30 percent of switch ampere rating, unless otherwise indicated.

B. Tested Fault-Current Closing and Withstand Ratings: Adequate for duty imposed by protective devices at installation locations in Project under the fault conditions indicated, based on testing according to UL 1008.

1. Where transfer switch includes internal fault-current protection, rating of switch and trip unit combination shall exceed indicated fault-current value at installation location.

C. Solid-State Controls: Repetitive accuracy of all settings shall be plus or minus 2 percent or better over an operating temperature range of minus 20 to plus 70 deg C.

D. Resistance to Damage by Voltage Transients: Components shall meet or exceed voltage-surge withstand capability requirements when tested according to IEEE C62.41. Components shall meet or exceed voltage-impulse withstand test of NEMA ICS 1.

Page 15: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL - FLOOD REMEDIATION PROJECT SDP CONTRACT NO. B-075c, B-076c, B-077c and B-078c of 2018/2019

TRANSFER SWITCHES 26

3600 - 3

E. Electrical Operation: Accomplish by a nonfused, momentarily energized solenoid or electric-motor-operated mechanism, mechanically and electrically interlocked in both directions.

F. Switch Characteristics: Designed for continuous-duty repetitive transfer of full-rated current between active power sources.

1. Limitation: Switches using molded-case switches or circuit breakers or insulated-case circuit-breaker components are not acceptable.

2. Switch Action: Double throw; mechanically held in both directions. 3. Contacts: Silver composition or silver alloy for load-current switching. Conventional

automatic transfer-switch units, rated 225 A and higher, shall have separate arcing contacts.

G. Neutral Switching. Where four-pole switches are indicated, provide neutral pole switched simultaneously with phase poles.

H. Neutral Terminal: Solid and fully rated, unless otherwise indicated.

I. Oversize Neutral: Ampacity and switch rating of neutral path through units indicated for oversize neutral shall be double the nominal rating of circuit in which switch is installed.

J. Battery Charger: For generator starting batteries.

1. Float type rated 10 A. 2. Ammeter to display charging current. 3. Fused ac inputs and dc outputs.

K. Enclosures: General-purpose NEMA 250, Type 1, complying with NEMA ICS 6 and UL 508, unless otherwise indicated.

2.3 AUTOMATIC TRANSFER SWITCHES

A. Comply with Level 1 equipment according to NFPA 110.

B. Switching Arrangement: Double-throw type, incapable of pauses or intermediate position stops during normal functioning, unless otherwise indicated.

C. Signal-Before-Transfer Contacts: A set of normally open/normally closed dry contacts operates in advance of retransfer to normal source. Interval is adjustable from 1 to 30 seconds.

D. Transfer Switches Based on Molded-Case-Switch Components: Comply with NEMA AB 1, UL 489, and UL 869A.

E. In-Phase Monitor: Factory-wired, internal relay controls transfer so it occurs only when the two sources are synchronized in phase.

F. Motor Disconnect and Timing Relay: Controls designate starters so they disconnect motors before transfer and reconnect them selectively at an adjustable time interval after transfer. Time delay for reconnecting individual motor loads is adjustable between 1 and 60 seconds, and settings are as indicated.

Page 16: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL - FLOOD REMEDIATION PROJECT SDP CONTRACT NO. B-075c, B-076c, B-077c and B-078c of 2018/2019

TRANSFER SWITCHES 26

3600 - 4

G. Programmed Neutral Switch Position: Switch operator has a programmed neutral position arranged to provide a midpoint between the two working switch positions, with an intentional, time-controlled pause at midpoint during transfer.

H. Automatic Transfer-Switch Features:

1. Undervoltage Sensing for Each Phase of Normal Source: Sense low phase-to-ground voltage on each phase. Pickup voltage shall be adjustable from 85 to 100 percent of nominal, and dropout voltage is adjustable from 75 to 98 percent of pickup value. Factory set for pickup at 90 percent and dropout at 85 percent.

2. Adjustable Time Delay: For override of normal-source voltage sensing to delay transfer and engine start signals. Adjustable from zero to six seconds, and factory set for one second.

3. Voltage/Frequency Lockout Relay: Prevent premature transfer to generator. Pickup voltage shall be adjustable from 85 to 100 percent of nominal. Factory set for pickup at 90 percent. Pickup frequency shall be adjustable from 90 to 100 percent of nominal. Factory set for pickup at 95 percent.

4. Time Delay for Retransfer to Normal Source: Adjustable from 0 to 30 minutes, and factory set for 10 minutes to automatically defeat delay on loss of voltage or sustained undervoltage of emergency source, provided normal supply has been restored.

5. Test Switch: Simulate normal-source failure. 6. Switch-Position Pilot Lights: Indicate source to which load is connected. 7. Source-Available Indicating Lights: Supervise sources via transfer-switch normal- and

emergency-source sensing circuits.

a. Normal Power Supervision: Green light with nameplate engraved "Normal Source Available."

b. Emergency Power Supervision: Red light with nameplate engraved "Emergency Source Available."

8. Unassigned Auxiliary Contacts: Two normally open, single-pole, double-throw contacts for each switch position, rated 10 A at 240-V ac.

9. Transfer Override Switch: Overrides automatic retransfer control so automatic transfer switch will remain connected to emergency power source regardless of condition of normal source. Pilot light indicates override status.

10. Engine Starting Contacts: One isolated and normally closed, and one isolated and normally open; rated 10 A at 32-V dc minimum.

11. Engine Shutdown Contacts: Instantaneous; shall initiate shutdown sequence at remote engine-generator controls after retransfer of load to normal source.

12. Engine Shutdown Contacts: Time delay adjustable from zero to five minutes, and factory set for five minutes. Contacts shall initiate shutdown at remote engine-generator controls after retransfer of load to normal source.

13. Engine-Generator Exerciser: Solid-state, programmable-time switch starts engine generator and transfers load to it from normal source for a preset time, then retransfers and shuts down engine after a preset cool-down period. Initiates exercise cycle at preset intervals adjustable from 7 to 30 days. Running periods are adjustable from 10 to 30 minutes. Factory settings are for 7-day exercise cycle, 20-minute running period, and 5-minute cool-down period. Exerciser features include the following:

a. Exerciser Transfer Selector Switch: Permits selection of exercise with and without load transfer.

b. Push-button programming control with digital display of settings. c. Integral battery operation of time switch when normal control power is not

available.

Page 17: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL - FLOOD REMEDIATION PROJECT SDP CONTRACT NO. B-075c, B-076c, B-077c and B-078c of 2018/2019

TRANSFER SWITCHES 26

3600 - 5

2.4 SOURCE QUALITY CONTROL

A. Factory test and inspect components, assembled switches, and associated equipment. Ensure proper operation. Check transfer time and voltage, frequency, and time-delay settings for compliance with specified requirements. Perform dielectric strength test complying with NEMA ICS 1.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Design each fastener and support to carry load indicated by seismic requirements and according to seismic-restraint details. See Division 26 Section "Vibration and Seismic Controls for Electrical Systems."

B. Floor-Mounting Switch: Anchor to floor by bolting.

1. Concrete Bases: 4 inches (100 mm) high, reinforced, with chamfered edges. Extend base no more than 4 inches (100 mm) in all directions beyond the maximum dimensions of switch, unless otherwise indicated or unless required for seismic support. Construct concrete bases according to Division 26 Section "Hangers and Supports for Electrical Systems."

C. Identify components according to Division 26 Section "Identification for Electrical Systems."

D. Set field-adjustable intervals and delays, relays, and engine exerciser clock.

3.2 CONNECTIONS

A. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems."

B. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors and Cables."

3.3 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. Report results in writing.

B. Perform tests and inspections and prepare test reports.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installation, including connections, and to assist in testing.

2. After installing equipment and after electrical circuitry has been energized, test for compliance with requirements.

3. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

Page 18: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL - FLOOD REMEDIATION PROJECT SDP CONTRACT NO. B-075c, B-076c, B-077c and B-078c of 2018/2019

TRANSFER SWITCHES 26

3600 - 6

4. Measure insulation resistance phase-to-phase and phase-to-ground with insulation-resistance tester. Use test voltages and procedure recommended by manufacturer. Comply with manufacturer's specified minimum resistance.

a. Check for electrical continuity of circuits and for short circuits. b. Inspect for physical damage, proper installation and connection, and integrity of

barriers, covers, and safety features. c. Verify that manual transfer warnings are properly placed. d. Perform manual transfer operation.

5. After energizing circuits, demonstrate interlocking sequence and operational function for each switch at least three times.

a. Simulate power failures of normal source to automatic transfer switches and of emergency source with normal source available.

b. Simulate loss of phase-to-ground voltage for each phase of normal source. c. Verify time-delay settings. d. Verify pickup and dropout voltages by data readout or inspection of control

settings. e. Perform contact-resistance test across main contacts and correct values

exceeding 500 microhms and values for 1 pole deviating by more than 50 percent from other poles.

f. Verify proper sequence and correct timing of automatic engine starting, transfer time delay, retransfer time delay on restoration of normal power, and engine cool-down and shutdown.

6. Ground-Fault Tests: Coordinate with testing of ground-fault protective devices for power delivery from both sources.

a. Verify grounding connections and locations and ratings of sensors.

C. Coordinate tests with tests of generator and run them concurrently.

D. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation and contact resistances and time delays. Attach a label or tag to each tested component indicating satisfactory completion of tests.

E. Remove and replace malfunctioning units and retest as specified above.

F. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each switch. Remove all access panels so joints and connections are accessible to portable scanner.

1. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each switch 11 months after date of Substantial Completion.

2. Instrument: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

3. Record of Infrared Scanning: Prepare a certified report that identifies switches checked and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

Page 19: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

DR. TANNER G. DUCKREY ELEMENTARY SCHOOL - FLOOD REMEDIATION PROJECT SDP CONTRACT NO. B-075c, B-076c, B-077c and B-078c of 2018/2019

TRANSFER SWITCHES 26

3600 - 7

3.4 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain transfer switches and related equipment as specified below. Refer to Division 01 Section "Demonstration and Training."

B. Coordinate this training with that for generator equipment.

END OF SECTION 263600

Page 20: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

1. ALL ELECTRICAL WORK SHALL BE PROPERLY GROUNDED AND SHALL MEET ALL REQUIREMENTS OF THE APPLICABLE SECTION OF THE NATIONAL ELECTRICAL CODE (NEC) AND ANY AUTHORITIES HAVING JURISDICTION.

2. ALL WORK SHALL BE PERFORMED AS REQUIRED BY APPLICABLE SECTION OF THE NATIONAL ELECTRICAL CODE, LATEST EDITION, AND ALL GOVERNING LOCAL CODES, LAWS, AND/OR REGULATIONS.

3. FURNISH, INSTALL, TEST AND TURNOVER ALL ELECTRICAL EQUIPMENT, COMPONENTS, FITTINGS, DEVICES, WIRES, CABLES, RACEWAYS AND APPURTENANCES AS SHOWN ON THE DRAWINGS AND AS SPECIFIED. ANY REQUIRED ITEMS NOT SPECIFIED OR SHOWN SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL.

4. DRAWINGS ARE DIAGRAMMATIC IN NATURE, CONTRACTOR SHALL VERIFY DIMENSIONS PRIOR TO INSTALLATION. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER DIVISION TRADES TO PROVIDE A COMPLETE AND OPERABLE SYSTEM. CONTRACTOR SHALL COORDINATE LOCATION OF FIXTURES, DEVICES, ETC. WITH OTHER TRADES IN ORDER TO AVOID INTERFERENCES.

5. ARCHITECTURAL FEATURES SHOWN ON THESE DRAWINGS ARE FOR BACKGROUND INFORMATION ONLY. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ACTUAL BUILDING CONSTRUCTION OF WALLS AND CURBS. REFER TO EQUIPMENT DRAWINGS FOR ACTUAL LOCATION OF EQUIPMENT.

6. ALL CIRCUITS SHALL CONTAIN A GROUND CONDUCTOR, WHETHER OR NOT IT IS INDICATED ON THE DRAWINGS.

7. EXACT CONDUIT STUB-UP LOCATIONS ARE TO BE DETERMINED BY THE ELECTRICAL CONTRACTOR BASED ON THE CERTIFIED MANUFACTURER'S DRAWINGS OF THE RESPECTIVE EQUIPMENT. CONDUITS SHALL BE INSTALLED TO AGREE WITH THE EQUIPMENT FURNISHED.

8. WALL & FLOOR PENETRATIONS SHALL BE BY THE ELECTRICAL CONTRACTOR. PROVIDE FIRESTOP AS REQUIRED FOR ALL PENETRATIONS MADE FOR ELECTRICAL WORK.

9. ANY ELECTRICAL CABLES, WIRING DEVICES, COMPONENTS OR APPURTENANCES THAT ARE NOT SHOWN OR SPECIFIED BUT ARE REQUIRED FOR PROPER OPERATION OF A SYSTEM, SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO PURCHASING.

10. PROVIDE CONDUIT SLEEVES AND SEALS FOR ALL CONDUITS PENETRATING FLOORS OR WALLS BELOW GRADE.

11. ALL POWER AND LIGHTING CONDUITS ARE SHOWN DIAGRAMATICALLY. EXACT RUNS SHALL BE DETERMINED BY THE ELECTRICAL CONTRACTOR IN THE FIELD, EXCEPT WHERE SPECIFICALLY DIMENSIONED ON PLANS. ALL CABLE, CONDUITS, PULL BOXES, JUNCTION BOXES AND SUPPORTING DEVICES SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED TO COMPLETE EACH RUN OF CONDUIT BASED ON FIELD CONDITIONS.

12. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE OF WORK PRIOR TO PREPARING HIS BID IN ORDER TO FAMILIARIZE HIMSELF WITH DIFFICULTIES TO THIS PROJECT FROM THE STANDPOINT OF UNDERSTANDING ALL FIELD CONDITIONS. WHENEVER A CONFLICT OCCURS BETWEEN THE CONTRACT DRAWINGS, SPECIFICATIONS, AND THE REQUIREMENTS OF THE ACTUAL FIELD CONDITIONS, THE CONTRACTOR SHALL BID ON THE MOST EXPENSIVE METHOD OF CONSTRUCTION AND WILL NOT BE ENTITLED TO AN EXTRA COST UNLESS MATERIALS OR EQUIPMENT NOT SHOWN ON THE DRAWINGS OR SPECIFICATIONS OR REQUIRED BY FIELD CONDITIONS MUST BE INSTALLED.

13. ALL EXPOSED CONDUIT SHALL BE RUN PARALLEL TO BUILDING WALLS AND BEAMS EXCEPT WHERE OTHERWISE SHOWN ON PLANS.

14. EXPOSED CONDUIT SHALL BE SUPPORTED FROM WALLS AND/OR CEILING BY APPROVED HANGERS OF ANGLE OR CHANNEL CONSTRUCTION.

15. EXPANSION FITTINGS OF THE APPROVED TYPE SHALL BE FURNISHED AND INSTALLED WHERE CONDUITS EXPOSED OR CONCEALED PASS THROUGH STRUCTURAL JOINTS.

16. ALL SINGLE PHASE POWER AND LIGHTING CONDUITS SHALL BE 3/4" WITH 2#12 AWG WIRE, UNLESS NOTED OTHERWISE. IN ADDITION, ALL SUCH CONDUITS SHALL CONTAIN A SEPARATE GROUND CONDUCTOR (SIZE AS REQ'D). ALL CONTROL WIRING SHALL BE A MINIMUM OF #16 AWG.

17. ALL 3 PHASE POWER CONDUITS SHALL BE 3/4" WITH 3#12 AWG WIRE UNLESS NOTED OTHERWISE. IN ADDITION, ALL SUCH CONDUITS SHALL CONTAIN A SEPARATE GROUND CONDUCTOR (SIZE AS REQUIRED).

18. ALL CIRCUIT PROTECTIVE DEVICES SHALL HAVE THE REQUIRED RATING INTERRUPTING CAPACITY EQUAL TO OR GREATER THAN THE AVAILABLESHORT-CIRCUIT CURRENT AT ITS SUPPLY TERMINAL; MINIMUM INTERRUPTING CAPACITY SHALL BE 10,000 AMPS, SYMMETRICAL A.I.C. FOR 120/240V SYSTEMS AND 14,000 AMPS, SYMMETRICAL A.I.C. FOR 277/480V SYSTEMS. REFER TO PANEL SCHEDULES FOR A.I.C. RATINGS.

19. IN GENERAL THE FOLLOWING MOUNTING DIMENSIONS ABOVE FINISHED FLOOR SHALL BE ADHERED TO UNLESS OTHERWISE NOTED ON PLANS OR SPECIFICATIONS:

LIGHTING SWITCHES, DISCONNECT SWITCHES AND MANUAL MOTOR STARTERS 4'-0".DIMENSION SHALL BE TAKEN AT THE HIGHEST POINT OF THE OPERATING HANDLE IN IT'S UPPERMOST POSITION.

20. NOT USED.

21. ALL OUTDOOR ENCLOSURES SHALL BE TYPE NEMA 4X STAINLESS STEEL.

22. ALL CONDUCTORS AND ALL BUSES ON THIS PROJECT SHALL BE COPPER.

23. ALL SWITCHES, CIRCUIT BREAKERS AND MCC CUBICLES SHALL BE INDENTIFIED VIA NAMEPLATE.

24. ALL ANCILLARY COMPONENTS SUCH AS AUXILIARY CONTACTS, CONTACTORS, RELAYS, COILS, TERMINAL BLOCKS, TIMERS, WIRES, ETC., SHALL BE FULLY RATED IN TERMS OF VOLTAGE, AMPERAGE, VA AND INSULATION RATINGS TO OPERATE CONTINUOUSLY AND UNDER ALL MAKE/BREAK CONDITIONS AS THEY ARE INSTALLED IN THEIR ASSOCIATED SYSTEM CONFIGURATIONS, WHETHER OR NOT ALL COMPONENTS ARE SHOWN OR SPECIFIED. ANY COMPONENT FOUND PRIOR TO OR DURING THE WARRANTY PERIOD TO BE INADEQUATELY RATED TO PERFORM ITS CONTROL FUNCTION, AS INSTALLED, SHALL BE REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. THE INTENT OF THIS CLAUSE IS TO HOLD THE CONTRACTOR LIABLE FOR PROVIDING FULLY INTEGRATED SYSTEMS, MADE UP OF FULLY RATED COMPONENTS THAT WILL WORK TOGETHER RELIABLY. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, ANY ANCILLARY DEVICES DESIGNED TO FUNCTION INTEGRALLY WITHIN GIVEN LARGER COMPONENTS.

25. ALL DISTRIBUTION PANELS, POWER PANELS, LIGHTING PANELS, ETC., SHALL HAVE COPPER BUSSES, BOLT-ON CIRCUIT BREAKERS, AND MAIN AND FEEDER BREAKERS AS SHOWN ON PANELBOARD SCHEDULES.

26. THE SYMBOLS AND ABBREVIATIONS LISTED REPRESENT A COMPREHENSIVE STANDARD GUIDE INTENDED FOR GENERAL USE ON THE PROJECT. THEREFORE, NOT ALL OF THE SYMBOLS AND ABBREVIATIONS CONTAINED IN THIS LIST ARE NECESSARILY USED ON THIS PARTICULAR CONTRACT.

27. DARKENED & DASHED LINES INDICATE DEMOLITION AND REMOVAL BY ELECTRICAL CONTRACTOR.

28. WHEREVER THE INSTALLATION OF ELECTRICAL EQUIPMENT AS SHOWN ON THE DRAWINGS IS IMPRACTICAL DUE TO LOCAL INTERFERENCE OR OTHER REASONS, THE CONTRACTOR SHALL INSTALL THE EQUIPMENT AT NEW LOCATIONS AS DIRECTED BY THE ENGINEER, AT NO EXTRA COST, PROVIDED DISTANCES AND REQUIRED INSTALLATION EFFORT IS EQUIVALENT.

29. ALL 3 PHASE MOTOR STARTERS SHALL BE NEMA SIZE 1 MINIMUM.

30. UNDERGROUND ELECTRICAL DUCT BANKS SHALL BE REINFORCED AS INDICATED IN DRAWING DETAILS.

31. CONTRACTOR SHALL MOUNT DISCONNECT SWITCHES, MOTOR STARTERS AND PUMP CONTROL PANELS ON KINDORF CHANNEL STANDS WHERE REQUIRED.

32. ALL EXISTING ELECTRICAL EQUIPMENT AND ASSOCIATED WIRING AND CONDUITS INDICATED AS DEMOLITION WORK SHALL BE REMOVED ENTIRELY BACK TO THE SOURCE UNLESS OTHERWISE NOTED.

33. CONTRACTOR SHALL FURNISH AND INSTALL ALL ELECTRIC WIRE AND CABLE FOR ALL ELECTRICAL EQUIPMENT AND ALL INTERCONNECTING WIRES FOR COMPONENTS PROVIDED UNDER ALL SECTIONS OF THIS CONTRACT.

34. ALL WIRING SHALL BE INSTALLED IN CONDUIT UNLESS OTHERWISE NOTED. CONDUIT SHALL BE OF TYPE AND MATERIAL AS INDICATED IN THE SPECIFICATIONS.

35. THE CONTRACTOR SHALL ENSURE THAT NO MECHANICAL DUCTWORK OR PIPING IS LOCATED OVER ELECTRICAL PANELS.

GENERAL NOTES:

S

S4

SD

S

S3

S

T

S

SM

S T

MISCELLANEOUS:

CONDUIT FEEDERS & BRANCH CIRCUITS:

EMERGENCY BATTERY PACK FIXTURE WITH

TWO HEADS

REMOTE HEAD FOR EMERGENCY BATTERY

PACK UNIT

D

ACCESS/INTRUSION ALARM CONTROL PANEL

DOOR CONTACT

ACCESS KEYPAD

ACCESS CARD READER

ELECTRIC DOOR STRIKE

GATE RELEASE

REQUEST TO EXIT

CLOSED CIRCUIT TELEVISION CAMERA

ACR

KP

ACCESS CONTROL/INTRUSION ALARM:

COMMUNICATIONS:PANELBOARD-208/120V, 3-PHASE

PANELBOARD-480/277V, 3-PHASE

PANELBOARD-120/240V

CEILING SPEAKER

WALL MOUNTED SPEAKER

WALL MOUNTED DOUBLE SPEAKER

POLE MOUNTED SPEAKER

POLE MOUNTED DOUBLE SPEAKER

DATA OUTLET

TELEPHONE OUTLET

PAY TELEPHONE OUTLET

TELEPHONE TERMINAL CABINET

DESKTOP HAND SET

WALL MOUNTED HAND SET

TTC

D

AICP

P

S S

PANELBOARDS:

S

S

S

S

S

(NOTE: LETTER @ SYMBOL DENOTES FIXTURE TYPE, TYPICAL)

CEILING MOUNT 2x2 LED FIXTURE

CEILING MOUNT 2x4 LED FIXTURE

4' CEILING MOUNT LED FIXTURE

8' CEILING MOUNT LED FIXTURE

WALL MOUNT LED FIXTURE

LED LIGHT FIXTURE DEDICATED FOR

EMERGENCY/STANDBY ILLUMINATION

CEILING MOUNT LED FIXTURE

WALL MOUNT LED FIXTURE

LED SPOT/FLOOD LIGHT FIXTURE

WALL MOUNT LED SPOT/FLOOD LIGHT FIXTURE

LED LIGHT FIXTURE DEDICATED FOR

EMERGENCY/STANDBY ILLUMINATION

POLE STANDARD LIGHT FIXTURE (ONE LUMINAIRE INDICATED)

EXIT SIGN FIXTURE (SINGLE FACE UNIVERSAL MOUNT INDICATED)

EXIT SIGN FIXTURE W/DIRECTIONAL ARROWS (DOUBLE FACE UNIVERSAL

MOUNT INDICATED)

SWITCH, SINGLE POLE

SWITCH, 3-WAY

SWITCH, 4-WAY

SWITCH, DIMMER

DIRECTIONAL MOTION DETECTOR LIGHT CONTROL

MULTI-DIRECTIONAL MOTION DETECTOR LIGHT CONTROL

SPECIAL PURPOSE LIGHT SWITCH; DESCRIPTION OF

SWITCH WILL BE AS NOTED ON DRAWINGS

PHOTOELECTRIC CONTROL

LIGHTING CONTACTOR:

REPRESENTS LIGHTING CONTACTOR IDENTIFICATION

LIGHTING CONTACTOR REMOTE CONTROL:

REPRESENTS LIGHTING CONTACTOR TO BE CONTROLLED

EMERGENCY LIGHTING:

LC1

LC1

LIGHTING:

OHE

DENOTES MOUNTED 6" ABOVE COUNTER TOP

SINGLE RECEPTACLE

GROUND FAULT CIRCUIT INTERRUPTER

WEATHER RESISTANT RECEPTACLE W/IN-USE COVER (WET LOCATION)

DUPLEX RECEPTACLE, 20 AMP RATED

QUADRUPLEX RECEPTACLE

DUPLEX RECEPTACLE DEDICATED FOR EMERGENCY/STANDBY

POWER

SPECIAL PURPOSE RECEPTACLE (AMPACITY AS NOTED)

DUPLEX RECEPTACLE FLOOR MOUNTED

SPECIAL PURPOSE RECEPTACLE FLOOR MOUNTED (AMPACITY

AS NOTED)

PLUGMOLD DEVICE; LENGTH AND QUANTITY OF RECEPTACLES

AS NOTED

JUNCTION BOX

NON FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

MOTOR STARTER

COMBINATION MOTOR STARTER

CONTACTOR

TIME CLOCK SWITCH CONTROL

TIME SWITCH

MANUAL MOTOR STARTER SWITCH WITHOUT OVERLOADS

MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOADS

MANUAL MOTOR STARTER SWITCH WITHOUT OVERLOADS WITH

PILOT LIGHT

PUSHBUTTON STATION TYPE AS NOTED

MUSHROOM SWITCH

MOTOR (HORSEPOWER INDICATED ON PLANS)

TRANSFORMER

GENERATOR

MOTOR OPERATED DAMPER

THERMOSTAT

UNINTERRUPTIBLE POWER SUPPLY

SURGE PROTECTION DEVICE

UNIT HEATER

UPS

SPD

MOD

T

PB

J

TS

F

10

MH-x

HH-x

OHT

G

GENERAL POWER:

WP

C

T

E

E

C

CONDUIT - EXPOSED

CONDUIT - CONCEALED IN WALL OR CEILING

CONDUIT - EMBEDDED IN FLOOR OR EARTH

CONDUIT TURNED

CONDUIT TURNED UP

CONDUIT TURNED DOWN

CONDUIT CAPPED

CIRCUIT HOME RUN

CONDUIT FEEDER IDENTIFICATION

(SEE FEEDER LEGEND ON DRAWING)

CONDUIT FEEDER IDENTIFICATION

TYPICAL FEEDER WITH NO SIZE IDENTIFICATION....

BY DEFAULT; (2)#12, (1)#12 GRD-3/4"

CONDUIT FOR SINGLE PHASE CIRCUITS.

-OR-

BY DEFAULT; (3)#12, (1)#12 GRD-3/4"

CONDUIT FOR THREE PHASE CIRCUITS.

ALL OTHER FEEDERS WILL BE INDENTIFIED.

COMMUNICATION

ELECTRIC

ELECTRIC SERVICE/DUCTBANK-UNDERGROUND

TELEPHONE

OVERHEAD ELECTRIC

OVERHEAD TELEPHONE

GROUNDING

UTILITY POLE

HANDHOLE

MANHOLE

(3)#8, (1)#10 GRD-1"C.

JUNCTION BOX INDICATION; ON POWER AND LIGHTINGJUNCTION BOX SIZED IN ACCORDANCE WITH NATIONALELECTRICAL CODE

CONDUIT FEEDERS (TYP)

THIS DRAWING REFLECTS A GANNETT FLEMING STANDARD SYMBOL ANDABBREVIATIONS DRAWING. SYMBOLS AND ABBREVIATIONS ON THISDRAWING MAY OR MAY NOT REFLECT EVERY CONDITION OF THIS PROJECT.

REX

GR

ES

ABBREVIATIONS

A OR AMP AMPEREAFF/A.F.F. ABOVE FINISHED FLOORAIC AMPERE INTERRUPTING CAPACITYBMS BUILDING MANAGEMENT SYSTEMC./CND CONDUITCB CIRCUIT BREAKERCKT CIRCUITCTRL CONTROLDISC. DISCONNECTEC/E.C. ELECTRICAL CONTRACTORGND GROUNDIG ISOLATED GROUNDJB JUNCTION BOXKVA KILOVOLT AMPEREKW KILOWATTLCP LOCAL CONTROL PANELMF MAIN FUSENEC/N.E.C. NATIONAL ELECTRIC CODEPVC POLYVINAL CHLORIDE CONDUIT, SCHEDULE 40PH PHASESB SPLICE BOXSEB SERVICE ENTRANCE BOXSPD SURGE PROTECTION DEVICESW SWITCHSWBD SWITCHBOARDTYP/TYP. TYPICALUL UNDERWRITER LABORATORIESUON/U.O.N. UNLESS OTHERWISE NOTEDUPS UNINTERRUPTIBLE POWER SUPPLYV VOLTVFD VARIABLE FREQUENCY DRIVEW WIREWP WATERPROOFXFMR TRANSFORMER

GFCI

DATE

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,

PHILADELPHIA, PA 19121

PERMIT SET

25 MARCH 2020

ARCHITECTURAL

GANNETT FLEMING, INC.

ONE PENN PLAZA, SUITE 630

250 WEST 34TH STREET

NEW YORK, NY 10119

Phone: 212.967.9833

Fax: 212.232.5791

Email: [email protected]

Attn: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.

232 CECELIA ACRES DRIVE

IVYLAND, PA 18974

Phone: 215.354.9161

Fax: 215.354.9163

Email: [email protected]

Attn: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.

1010 ADAMS AVENUE

VALLEY FORGE, PA 19403

Phone: 610.650.8156

Fax: 610.650.8190

Email: [email protected]

Attn: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.

1801 MARKET STREET, SUITE 2600

PHILADELPHIA, PA 19103

Phone: 215.557.0106

Fax: 215.557.0337

Email: [email protected]

Attn: Mark D. DeCocinis, CEI

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)

www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-087c OF 2018/19

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.

207 SENATE AVENUE

CAMP HILL, PA 17011

Phone: 717.763.7211

Fax: 717.763.8150

Email: [email protected]

Attn: Brian Seip, PE

SHEET OF

As indicated

ELECTRICAL POWERSYMBOLS, GENERAL NOTES

AND ABBREVIATIONS

Author CJG

EP-00149 58

1 4-17-2020 ADDENDUM 1

1

2

ADDENDUM #220 APRIL 2020

Page 21: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

T

PB

PB

T

PB

PB

T

NEWPANEL'PB-1'

DTWP-2

CWP-2

CWP-1

DTWP-1

SP-1A

SP-1B

HHWP-1 HHWP-2

FOP-1A

CH-1

(E)WH

(TEMP)WH

(E)EF

B-1 B-2

GUH-1

CO NG

CKTS: PB2-1,3,5

CKTS: PB2-7,9,11

CKTS: PB2-13,15,17

CKTS: PB2-14,16,18

CKTS: PB2-8,10,12

CKTS: PB2-19,21,23

CKTS: PB2-20,22,24

CKTS: PB1-11

JOCKEY PUMPCKT: PB1-13

JOCKEY PUMPCKT: PB1-14

BOILER ROOM

TELECOM ROOM

FREIGHT ELEVATORMACHINE ROOM

FREIGHT ELEVATOR

CKTS: PB1-18,20,22

CKTS: PB1-12

CK

T: P

B1-2

8

CK

T: P

B1-1

0

CK

T: P

B1-9

NEWPANEL'PB-2'

CKTS: PB2-31,33,35

CKT: PB1-27GFCI

CKT: PB1-27

GFCI

CKT: PB1-27

GFCI

CKT: PB1-16

GFCI

CKT: PB1-38

CKT: PB1-40

GFCIGFCI

MOD

CKT: PB1-39

MBCP

CKT: SA (MAIN SWITCHBOARD)

CKT: PB1-27

CKT: PB1-27GFCI

CKT: PB1-27

GFCI

CKT: PB1-41

MODCKT: PB1-41

BOILER BURNERCKT: PB1-1,3,5

BOILER BURNERCKT: PB1-2,4,6

REFER TO SHEET EP-202 FOR ENLARGEDFREIGHT ELEVATOR NEW WORK PLAN.

FOP-1B

CK

T: P

B1-5

0

MCP

(BELOW)

(BELOW)

CKTS: PB1-17,19,21

DATE

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,

PHILADELPHIA, PA 19121

PERMIT SET

25 MARCH 2020

ARCHITECTURAL

GANNETT FLEMING, INC.

ONE PENN PLAZA, SUITE 630

250 WEST 34TH STREET

NEW YORK, NY 10119

Phone: 212.967.9833

Fax: 212.232.5791

Email: [email protected]

Attn: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.

232 CECELIA ACRES DRIVE

IVYLAND, PA 18974

Phone: 215.354.9161

Fax: 215.354.9163

Email: [email protected]

Attn: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.

1010 ADAMS AVENUE

VALLEY FORGE, PA 19403

Phone: 610.650.8156

Fax: 610.650.8190

Email: [email protected]

Attn: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.

1801 MARKET STREET, SUITE 2600

PHILADELPHIA, PA 19103

Phone: 215.557.0106

Fax: 215.557.0337

Email: [email protected]

Attn: Mark D. DeCocinis, CEI

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)

www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DIAMOND ST.N. 16

TH S

T.

N. 15

TH S

T.

N

KEYPLAN

B-075c OF 2018/19

B-076c OF 2018/19B-077c OF 2018/19

B-087c OF 2018/19

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.

207 SENATE AVENUE

CAMP HILL, PA 17011

Phone: 717.763.7211

Fax: 717.763.8150

Email: [email protected]

Attn: Brian Seip, PE

SHEET OF

1/4" = 1'-0"

ELECTRICAL POWERSUB-BASEMENT NEW WORK

PLAN

FJR CJG

EP-10251 58

SCALE: 1/4" = 1'-0"

ELECTRICAL SUB-BASEMENT NEW WORK PLAN1

KEYED NEW WORK NOTES

NEW DUPLEX SUMP PUMP CONTROL PANEL.

NEW DUAL TEMPERATURE PUMPS.

NEW CONDENSER WATER PUMPS.

NEW HEATING HOT WATER PUMPS.

NEW DUPLEX FUEL OIL PUMPSET CONTROL PANEL (BELOW).

NEW WATER-COOLED CHILLER.

NEW PANELBOARDS 'PB1' & 'PB2'. REFER TO PANEL SCHEDULES AND ONE-LINE DIAGRAM.

PROVIDE NEW ELEVATOR CIRCUIT. PROVIDE CONDUIT AND WIRING FROM NEW PANEL.

PROVIDE NEW GFCI RECEPTACLE, WIRING AND CONDUIT.

PROVIDE RACEWAY BETWEEN BUILDING ENTRANCE AND LOCATION OF VERIZON'S EQUIPMENT.

NOT USED.

NEW GAS-FIRED UNIT HEATER.

NEW BOILER BURNER.

NEW FUEL OIL JOCKEY PUMP.

NEW BOILER CONTROL PANEL.

NEW REFRIGERANT DETECTION PANEL.

NEW GAS DETECTOR PANEL.

NOT USED.

NEW TEMPORARY WATER HEATER.

NEW DOMESTIC HOT WATER CIRCULATOR.

NEW COMBUSTION AIR MOTOR OPERATED DAMPER.

COMBINATION MOTOR STARTER/ DISCONNECT SWITCH, FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED AND WIRED BY EC.

WIRE SUMP PUMPS SP-1A & SP-1B TO DUPLEX SUMP PUMP CONTROL PANEL.

WIRE FUEL OIL PUMPS FOP-1A & FOP-1B TO DUPLEX FUEL OIL PUMP CONTROL PANEL.

PROVIDE NEW QUAD RECEPTACLE, WIRING AND CONDUIT.

VARIABLE FREQUENCY DRIVE (VFD), FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED AND WIRED BY EC.

1

GENERAL NOTES:

1. REFER TO CONCEPTUAL FIRE ALARM LAYOUTS ON DRAWING E-204 FOR ADDITIONAL INFORMATION ON FIRE ALARM DEVICE LOCATIONS AND REQUIRED OPERATION OF THE FIRE ALARM SYSTEM IN CONJUNCTION WITH ELEVATOR OPERATIONS.

2. SEE DRAWING EP-001 FOR SYMBOLS, ABBREVIATIONS AND GENERAL NOTES.

3. INSTALL ALL DISCONNECT SWITCHES AND MOTOR STARTERS FURNISHED BY MECHANICAL CONTRACTOR. PROVIDE WIRING AND CONDUIT THROUGH DISCONNECT SWITCHES AND MOTOR STARTERS TO EQUIPMENT.

4. PERFORM SHORT CIRCUIT COORDINATION AND ARC FLASH STUDIES. FURNISH REPORT TO OWNER.

2

3

4

5

8

10

9

26

4 4

6

9

2

3

3

2

1

7

12

5

6

7

8

9

10

11

12

21

21

19

20

16

9

9

13

14

15

16

17

18

19

20

21

18

15 15 15

13 13

14 14

18

26

22

26

26

26

26

17

99

25

23

24

24

24

25

23 23

22

22

22 2222 22

26

27

27

15

9

22

1

1

1

1 4-17-2020ADDENDUM 1 MOVED ITEMS TO ANOTHER SHEET1 4-17-2020 ADDENDUM 1 2

ADDENDUM #220 APRIL 2020

PROVIDE ONE (1) 4” CONDUIT FOR VERIZON SERVICE. PROVIDE A UNITPRICE FOR THREE HUNDRED (300) LINEAR FEET OF 4” CONDUIT.COORDINATE ROUTING WITH SDP CONSTRUCTION MANAGER,VERIZON, AND SDP IT GROUP.VERIZON'S EQUIPMENT.

NOT USED.

NEW GAS-FIRED UNIT HEATER.

NEW BOILER BURNER.

NEW FUEL OIL JOCKEY PUMP.

NEW BOILER CONTROL PANEL.

NEW REFRIGERANT DETECTION PANEL.

NEW GAS DETECTOR PANEL.

NOT USED.

NEW TEMPORARY WATER HEATER.

NEW DOMESTIC HOT WATER CIRCULATOR.

NEW COMBUSTION AIR MOTOR OPERATED DAMPER.

COMBINATION MOTOR STARTER/ DISCONNECT SWITCH, FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED AND WIRED BY EC.

WIRE SUMP PUMPS SP-1A & SP-1B TO DUPLEX SUMP PUMP CONTROL PANEL.

WIRE FUEL OIL PUMPS FOP-1A & FOP-1B TO DUPLEX FUEL OIL PUMP CONTROL PANEL.

PROVIDE NEW QUAD RECEPTACLE, WIRING AND CONDUIT.

VARIABLE FREQUENCY DRIVE (VFD), FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED AND WIRED BY EC.

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

1

1

Page 22: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

T

PB

PB

DWBP-1A

NGBP-1

NGBP-2

SSOU-1

SSOU-2

FCU-B15

CKTS: PB1-23,25

CKTS: PB1-24,26

CKTS: PB2-25,27,29

CKTS: PB1-30,32,34

CKTS: PB1-29,31,33

REFER TO SHEET EP-201 FOR ENLARGED TRANSFORMER ROOM NEW WORK PLANS

CKT: PB1-15

CKTS: PB2-26,28,30

DWP-1B

CKT: PB1-37

CKT: PB1-35

GFCI

LTG. PNL 'LA'

(E)

MUSIC ROOM

MUSIC EQUIPMENT

INSTRUMENTS

ENSEMBLE PRACTICE

TEACHERS' LOUNGE

STAIRS

STORAGE

TEACHER STORAGE

CLASSROOM

PRACTICE ROOM NO.1

PRACTICE ROOM NO.2

MUSIC OFFICE

CORRIDOR NO.2

PASSAGE

TRANSFORMER &SWITCH ROOM

AREAWAY

PUPIL EQUIP'T

RECEIVING AREA

CORRIDOR NO.1

PASSENGERELEVATOR

PASS. ELEV. MACHINEROOM

STORAGE

BR

LOCKER ROOM

JANITOR SUPPLIES

LOCKER ROOM

BLDG ENGINEER'SOFFICE

METER ROOM

UNEXCAVATED

CRAWL SPACE 'C'

UNEXCAVATED

CRAWL SPACE 'A'

POWER PNL 'PA'

(E)

REFER TO SHEET EP-202 FOR ENLARGED PASSENGER ELEVATOR NEW WORK PLAN.

GFCI

WP/GFCI

WP/GFCI

REFER TO ENLARGEDPLAN ON THIS SHEET

REFER TO ENLARGEDPLAN ON THIS SHEET

CKTS: PB1-57

CKTS: PB1-57

1

GFCICKT: PB1-55

CKT: PB1-55

GFCI

CKT: PB1-53

GFCI

CKT: PB1-53

GFCI

GFCI

CKT: PB1-51

HOUSE PHONE

CLASSROOMB-21

LAPTOP CART CHARGING

WIRELESS ACCESSPOINT AT CEILING

MUSIC ROOMB-3

HOUSE PHONE

CKT:PB1-56

GFCI GFCI

CKT:PB1-56

CKT: PB1-52GFCI

CKT: PB1-54

GFCI

CKT: PB1-54

GFCI

LAPTOP CARTCHARGING

WIRELESS ACCESS POINT AT CEILING

DATE

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,

PHILADELPHIA, PA 19121

PERMIT SET

25 MARCH 2020

ARCHITECTURAL

GANNETT FLEMING, INC.

ONE PENN PLAZA, SUITE 630

250 WEST 34TH STREET

NEW YORK, NY 10119

Phone: 212.967.9833

Fax: 212.232.5791

Email: [email protected]

Attn: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.

232 CECELIA ACRES DRIVE

IVYLAND, PA 18974

Phone: 215.354.9161

Fax: 215.354.9163

Email: [email protected]

Attn: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.

1010 ADAMS AVENUE

VALLEY FORGE, PA 19403

Phone: 610.650.8156

Fax: 610.650.8190

Email: [email protected]

Attn: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.

1801 MARKET STREET, SUITE 2600

PHILADELPHIA, PA 19103

Phone: 215.557.0106

Fax: 215.557.0337

Email: [email protected]

Attn: Mark D. DeCocinis, CEI

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)

www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DIAMOND ST.N. 16

TH S

T.

N. 15

TH S

T.

N

KEYPLAN

B-075c OF 2018/19

B-076c OF 2018/19B-077c OF 2018/19

B-087c OF 2018/19

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.

207 SENATE AVENUE

CAMP HILL, PA 17011

Phone: 717.763.7211

Fax: 717.763.8150

Email: [email protected]

Attn: Brian Seip, PE

SHEET OF

1/8" = 1'-0"

ELECTRICAL POWERBASEMENT NEW WORK PLAN

FJR CJG

EP-10453 58

SCALE: 1/8" = 1'-0"

ELECTRICAL BASEMENT NEW WORK PLAN1

KEYED NEW WORK NOTES

NEW HERMETIC NATURAL GAS BOOSTER PUMP SKID PACKAGE.

NEW DUPLEX DOMESTIC WATER BOOSTER PUMPSET.

NEW WALL-MOUNTED SPLIT SYSTEM HEAT PUMP OUTDOOR UNIT.

PROVIDE NEW RECEPTACLES AND WIRING WITHIN THIS ROOM. REUSE EXISTING CIRCUIT.

NEW FAN COIL UNIT (FCU-1).

PROVIDE NEW QUAD RECEPTACLE ON A DEDICATED CIRCUIT FOR EACH GAS METER.

PROVIDE NEW WP/GFCI DUPLEX RECEPTACLE WITHIN 25' OF HVAC EQUIPMENT.

PROVIDE (1) CAT 6 DATA CABLE DROP AT THIS LOCATION.

PROVIDE (2) CAT 6 DATA CABLE DROP AT THIS LOCATION.

PROVIDE (4) CAT 6 DATA CABLE DROP AT THIS LOCATION.

PROVIDE NEW TAMPER RESISTANT DUPLEX ELECTRICAL OUTLET.

PROVIDE NEW TAMPER RESISTANT QUAD ELECTRICAL OUTLET.

INSTALL NEW EMERGENCY STOP SWITCH FOR THE BOILER, FURNISHEDBY MECHANICAL CONTRACTOR. REFERENCE DETAIL 4/EP-301.

INSTALL NEW EMERGENCY STOP SWITCH FOR THE CHILLER FURNISHED BY MECHANICAL CONTRACTOR.

1

GENERAL NOTES:

1. REFER TO CONCEPTUAL FIRE ALARM LAYOUTS ON DRAWING E-204 FOR ADDITIONAL INFORMATION ON FIRE ALARM DEVICE LOCATIONS AND REQUIRED OPERATION OF THE FIRE ALARM SYSTEM IN CONJUNCTION WITH ELEVATOR OPERATIONS.

2. SEE DRAWING EP-001 FOR SYMBOLS, ABBREVIATIONS AND GENERAL NOTES.

3. INSTALL ALL DISCONNECT SWITCHES FURNISHED BY MECHANICAL CONTRACTOR. PROVIDE WIRING AND CONDUIT THROUGH DISCONNECT SWITCHES TO EQUIPMENT.

4. PERFORM A SHORT CIRCUIT COORDINATION AND ARC FLASH STUDIES. FURNISH REPORT TO OWNER.

2

3

1

2 1

4

4

5

3

3

5

4

4

4

4

4

4 4

4

4

4

4

4

4

4

4 4

44

4

4

4

6

6

7

7

7

4

4

SCALE: 1/8" = 1'-0"

CLASSROOM TECH/ INFRAST. PLAN2

8

8

SCALE: 1/8" = 1'-0"

MUSIC ROOM TECH/ INFRAST. PLAN3

8

9

10

10

9

8

9

10

9

9 10

11

12

11

12 12

12

12

11

12 12

1212

4

4

8

8

8

13

14

13

14

1

1 4-17-2020ADDENDUM 1 ITEMS FROM ANOTHER SHEET1 4-17-2020 ADDENDUM 1 2

ADDENDUM #220 APRIL 2020

KEYED NEW WORK NOTES

NEW HERMETIC NATURAL GAS BOOSTER PUMP SKID PACKAGE.

NEW DUPLEX DOMESTIC WATER BOOSTER PUMPSET.

NEW WALL-MOUNTED SPLIT SYSTEM HEAT PUMP OUTDOOR UNIT.

PROVIDE NEW RECEPTACLES AND WIRING WITHIN THIS ROOM. REUSE EXISTING CIRCUIT.

NEW FAN COIL UNIT (FCU-1).

PROVIDE NEW QUAD RECEPTACLE ON A DEDICATED CIRCUIT FOR EACH GAS METER.

PROVIDE NEW WP/GFCI DUPLEX RECEPTACLE WITHIN 25' OF HVAC EQUIPMENT.

PROVIDE (1) CAT 6 DATA CABLE DROP AT THIS LOCATION.

PROVIDE (2) CAT 6 DATA CABLE DROP AT THIS LOCATION.

PROVIDE (4) CAT 6 DATA CABLE DROP AT THIS LOCATION.

PROVIDE NEW TAMPER RESISTANT DUPLEX ELECTRICAL OUTLET.

PROVIDE NEW TAMPER RESISTANT QUAD ELECTRICAL OUTLET.

INSTALL NEW EMERGENCY STOP SWITCH FOR THE BOILER, FURNISHEDBY MECHANICAL CONTRACTOR. REFERENCE DETAIL 4/EP-301.

INSTALL NEW EMERGENCY STOP SWITCH FOR THE CHILLER FURNISHED BY MECHANICAL CONTRACTOR.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

1

PROVIDE SIX THOUSAND FIVE HUNDRED (6,500) LINEAR FEET OF CAT6CABLE FOR DATA DROPS. PROVIDE TWO HUNDRED (200) LINEAR FEETOF 1" CONDUIT FOR DATA DROPS. PROVIDE THREE HUNDRED (300)LINEAR FEET OF 2x2x10 CABLE TRAY FOR DATA DROPS. COORDINATETERMINATION OF CAT6 CABLE WITH SDP IT GROUP AND SDPCONSTRUCTION MANAGER.

5.

1

Page 23: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

FS

S

F

TFF

TF

FT

PASS. ELEV. MACHINEROOM

PASSENGERELEVATOR

(NON SPRINKLERED HOISTWAY)

125A/3P

KEYED DEMOLITION NOTES:REMOVE EXISTING PIT LIGHT FIXTURES, LIGHT SWITCH, RECEPTACLES AND ASSOCIATED WIRING IN THE IMMEDIATE PIT AREA. ALL EXPOSED CONDUIT SHALL BE REPLACED IN ENTIRETY WITHIN ELEVATOR PITS.

REMOVE EXISTING ELEVATOR MACHINE ROOM DISCONNECT SWITCH

REMOVE EXISTING ELEVATOR MACHINE ROOM RECEPTACLES AND WIRING TO POINT OF ORIGIN.

#

GENERAL DEMOLITION NOTES:1. THE DEMOLITION PLAN IS DIAGRAMATIC IN NATURE AND INTENDED TO

REPRESENT ONLY THE GENERAL SCOPE OF DEMOLITION. THE ELECTRICAL CONTRATOR SHALL REVIEW THE EXISTING FACILITY ALONG WITH THE DEMOLITION PLAN AND SHALL BE RESPONSIBLE TO DETERMINE THE EXACT EXTENT OF THE ELECTRICAL DEMOLITION WORK REQUIRED UNDER THE SCOPE OF THIS PROJECT.

2. EQUIPMENT AND/OR DEVICES SHOWN AS DARKENED AND DASHED ON THE PLANS SHALL BE REMOVED IN ITS ENTIRETY.

3. FOR EQUIPMENT TO BE DEMOLISHED REMOVE ALL WIRING IN CONDUIT BACK TO SOURCE ELECTRICAL PANEL AND UPDATE PANEL SCHEDULE. RECONNECT ANY DISTURBED FACILITIES WHICH ARE TO REMAIN AND PLACE IN OPERATING CONDITION.

4. TRACE OUT ALL EXISTING WIRING TO BE DEMOLISHED FROM THE PROJECT AREA. ALL EXISTING WIRING TO BE DEMOLISHED SHALL BE REMOVED TO ITS POINT OF ORIGIN.

5. RELOCATE OR EXTEND EXISTING CIRCUITS NOT BEING ABANDONED AS REQUIRED TO ACCOMODATE NEW WORK AND MAINTAIN CIRCUIT INTEGRITY.

6. REFERENCE DRAWING EP-401 FOR DEMOLITION ONE-LINE DIAGRAMS .

7. ALL EMPTY AND ABANDONED CONDUIT SHALL BE REMOVED FROM WITHIN THE PROJECT BOUNDARIES. SEVER AND CAP CONDUIT A MINIMUM OF 6" OUTSIDE THE PROJECT BOUNDARIES. INSTALL PULL CORD IN EACH SPARE CONDUIT. PROVIDE CUTTING AND PATCHING OF ALL CEILINGS, FLOORS AND WALLS AS REQUIRED.

8. THE CONTRACTOR SHALL PROVIDE CAPS, COVERS AND PLUGS FOR ALL EXISTING PULL BOXES, JUNCTION BOXES AND PANELS WITHIN THE PROJECT BOUNDARIES.

9. REMOVE ALL ABANDONED RECEPTACLES, JUNCTION BOXES, CONDUIT, WIRING AND ASSOCIATED HANGERS. CIRCUITS TO BE REUSED FOR NEW WORK.

FREIGHT ELEVATOR

FREIGHT ELEVATORMACHINE ROOM

TELECOM ROOM

125A/3P

PASS. ELEV. MACHINEROOM

PASSENGERELEVATOR

(NON SPRINKLERED HOISTWAY)

GFCI

GFCI

GFCI

GFCI

SSIU-2

CKT:PB1-43

CKT:PB1-48

CKT:PB1-48

CKT:PB1-48

CKT:PB1-45

FREIGHT ELEVATOR

FREIGHT ELEVATORMACHINE ROOM

TELECOM ROOM

GFCI

GFCI

GFCI

GFCI

SSIU-1

CKT:PB1-49

CKT:PB1-46

CKT:PB1-49

CKT:PB1-49

CKT:PB1-44

#KEYED NEW WORK NOTES:PROVIDE NEW DUPLEX GFCI RECEPTACLE IN THE ELEVATOR PIT. COORDINATE MOUNTING HEIGHT AND EXACT LOCATION WITH ELEVATOR INSTALLER.

NEW DUCTLESS SPLIT SYSTEM UNIT. INTERCONNECT WITH ASSOCIATED OUTDOOR UNIT PER MANUFACTURERS RECOMMENDATIONS..

PROVIDE NEW ELEVATOR FUSED SHUNT TRIP DISCONNECT SWITCH. REFER TO RISER DIAGRAM EP-402.

PROVIDE NEW 30A, 120V ELEVATOR CAB LIGHTS FUSED DISCONNECT SWITCH.

PROVIDE NEW DUPLEX GFCI RECEPTACLE IN THE ELEVATOR MACHINE ROOM.

PROVIDE TELEPHONE CONNECTION AT ELEVATOR CONTROLLER. COORDINATE EXACT LOCATION WITH ELEVATOR CONTRACTOR.

DATE

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,

PHILADELPHIA, PA 19121

PERMIT SET

25 MARCH 2020

ARCHITECTURAL

GANNETT FLEMING, INC.

ONE PENN PLAZA, SUITE 630

250 WEST 34TH STREET

NEW YORK, NY 10119

Phone: 212.967.9833

Fax: 212.232.5791

Email: [email protected]

Attn: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.

232 CECELIA ACRES DRIVE

IVYLAND, PA 18974

Phone: 215.354.9161

Fax: 215.354.9163

Email: [email protected]

Attn: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.

1010 ADAMS AVENUE

VALLEY FORGE, PA 19403

Phone: 610.650.8156

Fax: 610.650.8190

Email: [email protected]

Attn: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.

1801 MARKET STREET, SUITE 2600

PHILADELPHIA, PA 19103

Phone: 215.557.0106

Fax: 215.557.0337

Email: [email protected]

Attn: Mark D. DeCocinis, CEI

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)

www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DIAMOND ST.N. 16

TH S

T.

N. 15

TH S

T.

N

KEYPLAN

B-075c OF 2018/19

B-076c OF 2018/19B-077c OF 2018/19

B-087c OF 2018/19

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.

207 SENATE AVENUE

CAMP HILL, PA 17011

Phone: 717.763.7211

Fax: 717.763.8150

Email: [email protected]

Attn: Brian Seip, PE

SHEET OF

As indicated

ELECTRICAL PASSENGER &FREIGHT ELEVATORS

FJR CJG

EP-20255 58

SCALE: 1/2" = 1'-0"

PARTIAL PASSENGER ELEVATOR - DEMO PLAN1

1

2

3

SCALE: 1/2" = 1'-0"

PARTIAL FREIGHT ELEVATOR - DEMO PLAN2

SCALE: 1/2" = 1'-0"

PARTIAL PASSENGER ELEVATOR - NEW WORK PLAN3

SCALE: 1/2" = 1'-0"

PARTIAL FREIGHT ELEVATOR - NEW WORK PLAN4

1

2

3

4

5

1

2

1

2

3

3

3

3

1

1

3 4

5

3

4

2

5

5

5

5

5

6

6

2

6

1

1

1

1 4-17-2020ADDENDUM 1 MODIFIED LOCATION OF TELEPHONE CONNECTION1 4-17-2020 ADDENDUM 1 2

ADDENDUM #220 APRIL 2020

Page 24: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

CKT. # PB1-41(120VAC)

L

N

2 4

1RL

N

BURNER CONTROL PANEL

BOILER #2

MODCOMB. AIR

DAMPER MTR #1

MODCOMB. AIR

DAMPER MTR #2

2 4

1RL

N

BURNER CONTROL PANEL

BOILER #1

MODCOMB. AIRDAMPER MTR #3

MODCOMB. AIRDAMPER MTR #4

SCHEMATIC WIRING DIAGRAM

NOTES:

1. INTERCONNECT WITH EXHAUST FAN EF-1 (CONTROL RELAY/DAMPER MOTORS 1-4 ENERGIZED WHEN EF-1 IS RUNNNING).

CR

(NOTE 1)

NOTES:

1. EMERGENCY SHUTDOWN (E-STOP) SWITCHES FURNISHED BY MC, INSTALLED AND WIRED BY EC.

2. CONTROL RELAYS 'CRE1 AND 'CRE2' PROVIDED BY EC. LOCATE CONTROL RELAY ADJACENT TO MAIN BOILER CONTROL PANEL.

3. CONNECT E-STOP SWITCHES TO 120VAC CIRCUIT PROVIDING CTRL POWER FOR THE MAIN BOILER CONTROL PANEL

E-STOP #1 E-STOP #2

CRE1

TO BURNER CONTROL PANEL #1 (N.O. E-STOP CONTACT IN CONTROL CKT.)

L

N

SCHEMATIC WIRING DIAGRAM

CRE2TO BURNER CONTROL PANEL #2 (N.O. E-STOP CONTACT IN CONTROL CKT.)

CKT. # PB1-42(120VAC)

E-STOP #3

PANEL DESIGNATION

NEW PANEL 'PB1'

TYPE: BRANCH CIRCUIT LOCATION: BOILER ROOM

NUMBER OF POLES: 72 VOLTAGE: 208Y/120V, 3-PHASE, 4-WIRE

MAIN BUS RATING: 225A PANEL MOUNTING: SURFACE

MAIN RATING: 225A PANEL ENCLOSURE (NEMA): 1

SHORT CIRCUIT: 22kAIC

CIR. No.

CIR. BKR.

DESCRIPTION WIRE GROUND CONDUITLOAD - KVA LOAD - KVA

CONDUIT GROUND WIRE DESCRIPTIONCIR. BKR.

CIR. No.ΦA ΦB ΦC ΦA ΦB ΦC

1

20/3 BOILER BURNER (B-1) #12 #12 3/4"

0.90 0.90

3/4" #12 #12 BOILER BURNER (B-2) 20/3

2

3 0.90 0.90 4

5 0.90 0.90 6

7 20/1 SPARE #12 #12 3/4" 3/4" #12 #12 SPARE 20/1 8

9 20/1 MBCP-1 #12 #12 3/4" 0.50 0.20 3/4" #12 #12 GAS DETECTION PANEL (CGD-1) 20/1 10

11 30/1 GAS UNIT HEATER (GUH-1) #10 #10 3/4# 3.34 1.50 3/4" #12 #12 GAS WATER HEATER (E) WH 20/1 12

13 30/1 JOCKEY PUMP (B-1) #10 #10 3/4" 1.20 1.20 3/4" #10 #10 JOCKEY PUMP (B-2) 30/1 14

15 20/1 FAN COIL UNIT (FCU-1) #12 #12 3/4" 3.34 0.50 3/4" #12 #12 WATER SOFTENER (WS-1) 20/1 16

17

20/3 FUEL OIL PUMP (FOP-1A) #12 #12 3/4"

0.50 1.50

3/4" #12 #12 TEMPORARY WATER HEATER 20/3

18

19 0.50 1.50 20

21 0.50 1.50 22

2320/2 DUCTLESS SPLIT SYSTEM (SSOU-1) #12 #12 3/4"

0.95 0.953/4" #12 #12 DUCTLESS SPLIT SYSTEM (SSOU-2) 20/2

24

25 0.95 0.95 26

27 20/1 BOILER ROOM RECEPTACLES #12 #12 3/4" 0.50 0.50 3/4" #12 #12 CO DETECTION PANEL (CGD-1) 20/1 28

29

20/3 NATURAL GAS BOOSTER PUMP (NGBP-1) #12 #12 3/4"

0.80 0.90

3/4" #12 #12 NATURAL GAS BOOSTER PUMP (NGBP-2) 20/3

30

31 0.80 0.90 32

33 0.80 0.90 34

35 20/1 GAS METER QUAD RECEPTACLE #12 #12 3/4" 0.50 0.95 3/4" #12 #12 EXHAUST FAN (EF-1) 20/1 36

37 20/1 GAS METER QUAD RECEPTACLE #12 #12 3/4" 0.50 0.50 3/4" #12 #12 WATER SOFTENER QUAD RECEPTACLE 20/1 38

39 20/1 REFRIGERANT DETECTION PANEL #12 #12 3/4" 0.50 0.50 3/4" #12 #12 WATER SOFTENER QUAD RECEPTACLE 20/1 40

41 20/1 MOTOR OPERATED DAMPERS (MOD's) #12 #12 3/4" 0.60 0.50 3/4" #12 #12 EMERGENCY SHUTDOWN SWITCHES 20/1 42

43 20/1 PASS 'ELEVATOR PIT LIGHT/ RECEPT #12 #12 3/4" 0.50 0.50 3/4" #12 #12 FREIGHT 'ELEVATOR PIT/LIGHTING 20/1 44

45 20/1 PASS 'ELEVATOR CAB LIGHTING #12 #12 3/4" 0.50 0.50 3/4" #12 #12 ELEVATOR CAB LIGHTING 20/1 46

47 20/1 ELECTRICAL ROOM RECEPTACLES #12 #12 3/4" 0.50 0.50 3/4" #12 #12 EMR RECEPTACLES 20/1 48

49 20/1 EMR RECEPTACLES #12 #12 3/4" 1.00 0.50 3/4" #12 #12 MAIN CONTROL PANEL (MCP-1) 20/1 50

51 20/1 CLASSROOM B-21 RECEPTACLE #12 #12 3/4" 0.50 3/4" #12 #12 MUSIC ROOM B-3 RECEPTACLE 20/1 52

53 20/1 CLASSROOM B-21 RECEPTACLES #12 #12 3/4" 0.80 3/4" #12 #12 MUSIC ROOM B-3 RECEPTACLES 20/1 54

55 20/1 CLASSROOM B-21 RECEPTACLES #12 #12 3/4" 0.80 3/4" #12 #12 MUSIC ROOM B-3 RECEPTACLES 20/1 56

57 20/1 EXTERIOR RECEPTACLES #12 #12 3/4" 3/4" #12 #12 SPARE 20/1 58

59 20/1 SPARE #12 #12 3/4" 3/4" #12 #12 SPARE 20/1 60

61 20/1 SPARE #12 #12 3/4" 3/4" #12 #12 SPARE 20/1 62

63 SPACE SPACE 64

65 SPACE SPACE 66

67 SPACE SPACE 68

69 SPACE SPACE 70

71 SPACE SPACE 72

TOTAL 7.1 8.36 8.9 7.0 5.5 7.7 TOTAL

PANEL CONNECTED LOAD

ΦA 14.1 X SOLID NEUTRAL BUS

ΦB 13.9 X EQUIPMENT GROUND BUS

ΦC 16.6 X INTEGRAL SPD

44.6 KVA CONNECTED TOTAL

0.36

PANEL DESIGNATION

NEW PANEL 'PB2'

TYPE: BRANCH CIRCUIT LOCATION: BOILER ROOM

NUMBER OF POLES: 42 VOLTAGE: 208Y/120V, 3-PHASE, 4-WIRE

MAIN BUS RATING: 600A PANEL MOUNTING: SURFACE

MAIN RATING: 500A PANEL ENCLOSURE (NEMA): 1

SHORT CIRCUIT: 65kAIC

CIR. No.

CIR. BKR.

DESCRIPTION WIRE GROUND CONDUITLOAD - KVA LOAD - KVA

CONDUIT GROUND WIRE DESCRIPTIONCIR. BKR.

CIR. No.ΦA ΦB ΦC ΦA ΦB ΦC

1

20/3 SUMP PUMP (SP-1A) #12 #12 3/4"

0.90 3.00

2" #6 #1 AUTOMATIC TRANSF SWITCH 125/3

2

3 0.90 3.00 4

5 0.90 3.00 6

7

90/3DUAL TEMP WATER PUMP (DTWP-1)

#3 #8 1 1/4"

5.50 5.50

1 1/4" #8 #3DUAL TEMP WATER PUMP (DTWP-2)

90/3

8

9 5.50 5.50 10

11 5.50 5.50 12

13

90/3CONDENSATE WATER PUMP (CWP-1)

#3 #8 1 1/4"

5.50 5.50

1 1/4" #8 #3CONDENSATE WATER PUMP (CWP-2)

90/3

14

15 5.50 5.50 16

17 5.50 5.50 18

19

60/3 HEATING HOT WATER (HHWP-1) #6 #10 1"

3.70 3.70

1" #10 #6 HEATING HOT WATER (HHWP-2) 60/3

20

21 3.70 3.70 22

23 3.70 3.70 24

25

50/3DOM. COLD WATER PUMP (DWP)

#10 #10 3/4"

3.00 3.00

3/4" #10 #10DOM. COLD WATER PUMP (DCWP-1B)

50/3

26

27 3.00 3.00 28

29 3.00 3.00 30

31

40/3 EXISTING EXHAUST FAN (E-20) #8 #10 3/4"

2.00 3/4" #12 #12 SPARE 20/1 32

33 2.00 3/4" #12 #12 SPARE 20/1 34

35 2.00 3/4" #12 #12 SPARE 20/1 36

37 SPACE SPACE 38

39 SPACE SPACE 40

41 SPACE SPACE 42

TOTAL 20.6 20.6 20.6 20.7 20.7 20.7 TOTAL

PANEL CONNECTED LOAD

ΦA 41.3 X SOLID NEUTRAL BUS

ΦB 41.3 X EQUIPMENT GROUND BUS

ΦC 41.3 X INTEGRAL SPD

123.9 KVA CONNECTED TOTAL

L

CR1

N

"DOOR OPEN" TO HOUSE FAN MOTOR CONTROL CIRCUIT. (WIRE IN AS A PERMISSIVE INTERLOCK)

CR1

CONTROL RELAY (BY EC)

DATE

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,

PHILADELPHIA, PA 19121

PERMIT SET

25 MARCH 2020

ARCHITECTURAL

GANNETT FLEMING, INC.

ONE PENN PLAZA, SUITE 630

250 WEST 34TH STREET

NEW YORK, NY 10119

Phone: 212.967.9833

Fax: 212.232.5791

Email: [email protected]

Attn: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.

232 CECELIA ACRES DRIVE

IVYLAND, PA 18974

Phone: 215.354.9161

Fax: 215.354.9163

Email: [email protected]

Attn: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.

1010 ADAMS AVENUE

VALLEY FORGE, PA 19403

Phone: 610.650.8156

Fax: 610.650.8190

Email: [email protected]

Attn: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.

1801 MARKET STREET, SUITE 2600

PHILADELPHIA, PA 19103

Phone: 215.557.0106

Fax: 215.557.0337

Email: [email protected]

Attn: Mark D. DeCocinis, CEI

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)

www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

B-075c OF 2018/19

B-076c OF 2018/19B-077c OF 2018/19

B-087c OF 2018/19

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.

207 SENATE AVENUE

CAMP HILL, PA 17011

Phone: 717.763.7211

Fax: 717.763.8150

Email: [email protected]

Attn: Brian Seip, PE

SHEET OF

12" = 1'-0"

ELECTRICAL WIRE DIAGRAMSAND PANEL SCHEDULES

FJR CJG

EP-30156 58

SCALE: NTS

SCHEMATIC WIRING DIAGRAM - MOTOR OPERATED DAMPERS3

SCALE: NTS

BOILER EMERGENCY SHUT DOWN4

SCALE: NTS

NEW PANEL 'PB1'1

SCALE: NTS

NEW PANEL 'PB2'2

NOTE:REFER TO DRAWING E-104 FOR PANELBOARD FRONT STANDARD DETAIL.

SCALE: 12" = 1'-0"

SCHEMATIC WIRING DIAGRAM - MOTOR OPERATED DAMPER #55

11

1

1 4-17-2020 ADDENDUM 1 2

ADDENDUM #220 APRIL 2020

Page 25: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

EXISTPOWERPANEL

'PA'

SUBSTATION 'SA'(SEE ONE-LINE)

PB

BASEMENT

FIRST FLOOR

SA-10

EXISTLTG.

PANEL 'LA'

SA-4

EXISTPOWERPANEL

'PC'

EXISTLTG.

PANEL 'LC'

EXISTPOWERPANEL

'PZ'

SA-9

SECOND FLOOR

EXISTPOWERPANEL

'PK'

EXISTLTG.

PANEL 'LK'

SA-5

SA-11

FUTURE THIRD FLOOR

1 1/4"C

P.E. CO. METER

EXISTLTG.

PANEL 'LE'

SA-6

EXISTLTG.

PANEL 'LF'

EXISTLTG.

PANEL 'LG'

EXISTPOWERPANEL

'PG'

SA-12

EXISTPOWERPANEL

'PB'

EXISTPOWERPANEL

'PM'

SA-14

SA-13

EXISTPOWERPANEL

'PD'

EXISTLTG.

PANEL 'LD'

EXISTLTG.

PANEL 'LH'

EXISTPOWERPANEL

'PL'

EXISTLTG.

PANEL 'LL'

SA-8

SA-15

SA-12

SA-7

EXISTNORM - EM

PANEL 'EN'

SA-17(THRU TRANSFER SWITCH)

DOUBLE PANEL

(DOUBLE PANEL)

BOILER ROOM

SA-2

SA-3ELEVATOR (PASS)

25 H.P 3PH/208V

ELEVATOR (FREIGHT)25 H.P 3PH/208V

250A208/120V3PH, 4W

250A208/120V3PH, 4W

600A208/120V3PH, 4W

250A208/120V3PH, 4W

250A208/120V3PH, 4W

225A208/120V3PH, 4W

225A208/120V3PH, 4W

225A208/120V3PH, 4W

250A208/120V3PH, 4W

250A208/120V3PH, 4W

400A208/120V3PH, 4W

150A208/120V3PH, 4W

150A208/120V3PH, 4W

150A208/120V3PH, 4W

150A208/120V3PH, 4W

300A208/120V3PH, 4W

225A208/120V3PH, 4W

SA-1(SPARE 225A/3)

60/2

500A208/120V3PH, 4W

4 #1/0, 2"C

8 #3/0, 2 - 2 1/2"C

4 #1/0, 2"C

4 #4/0, 3"C

4-250MCM, 3"C

4 #1/0, 2"C

8-350MCM, 2-3 1/2"C

4-250MCM, 3"C

4 #3/0, 2 1/2"C

4-300MCM, 3"C

4 #1/0, 2"C

8 #4/0, 2-3"C

4-250MCM, 3"C

3 #4, 1 1/4"C

3 #3, 1 1/4"C

(2) 5"CSA-16

(SPARE 400A/3)

2-5"C TO MANHOLE #2(SEE ONELINE DIAGRAMON THIS SHEET) (ETR)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

15KV PULLBOX (ETR)

1

1

SUBSTATION 'SA'

15KV PULLBOX (ETR)IN ELECTRICAL ROOM

PB

13.2KV FUSED DISCONNECT

P.E.CO. METER

750/1000 KVA TRANSFORMER13.2KV - 3PH - DELTA PRIMARY120/208V - 3PH - Y SECONDARY

225/3

SP

AR

E B

KR

1

100/3

ELE

VA

TO

R (

PA

SS

)25 H

.P

3P

H/2

08V

2

100/3

ELE

VA

TO

R (

FR

EIG

HT

)25 H

.P

3P

H/2

08V

3

250/3

PN

LS

"LA

", "

LC

"3P

H -

4W

-120/2

08V

4

250/3

5

225/3

6

250/3

7

400/3

8

600/3

9

150/3

10

250/3 170/3 300/3 500/3 225/3 400/3 60/3

11 12 13 14 15 16 17

REMAINDER OF CUBICLE TO BE SPACE & BUSSING FOR FUTURE BKRS.

PN

LS

"LK

" &

FU

T.

FLO

OR

3P

H -

4W

-120/2

08V

PN

LS

"LE

, LF

", "

LG

"3P

H -

4W

-120/2

08V

PN

LS

"LD

", "

LH

"3P

H -

4W

-120/2

08V

PN

L "

LL"

& F

UT

. F

LO

OR

3P

H -

4W

-120/2

08V

PN

L "

PZ

"3P

H -

4W

-120/2

08V

PN

LS

"P

A",

"P

C"

3P

H -

4W

-120/2

08V

PN

L "

PK

" &

FU

T.

FLO

OR

3P

H -

4W

-120/2

08V

PN

LS

"P

D",

"P

G"

3P

H -

4W

-120/2

08V

PN

L "

PM

"3P

H -

4W

-120/2

08V

PN

L "

PB

"3P

H -

4W

-120/2

08V

PN

L "

PL"

& F

UT

. F

LO

OR

3P

H -

4W

-120/2

08V

SP

AR

E B

KR

TO

TR

SW

& P

NL "

EN

"

STARTER & FUSED DISCONNECT 1200A, 3PH

CONTROL PANEL

CHILLER

MECHANICAL RM. "MR-1"

MANHOLE #2 (ETR)

HANDHOLE #1(ETR)(AT 18" INSIDE PROPERTY LINE)

2-5"C

3 #1/0 (15KV) TO SUBSTATION (ETR)

CLF

TO FIRE ALARM PANEL

1

1

DATE

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,

PHILADELPHIA, PA 19121

PERMIT SET

25 MARCH 2020

ARCHITECTURAL

GANNETT FLEMING, INC.

ONE PENN PLAZA, SUITE 630

250 WEST 34TH STREET

NEW YORK, NY 10119

Phone: 212.967.9833

Fax: 212.232.5791

Email: [email protected]

Attn: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.

232 CECELIA ACRES DRIVE

IVYLAND, PA 18974

Phone: 215.354.9161

Fax: 215.354.9163

Email: [email protected]

Attn: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.

1010 ADAMS AVENUE

VALLEY FORGE, PA 19403

Phone: 610.650.8156

Fax: 610.650.8190

Email: [email protected]

Attn: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.

1801 MARKET STREET, SUITE 2600

PHILADELPHIA, PA 19103

Phone: 215.557.0106

Fax: 215.557.0337

Email: [email protected]

Attn: Mark D. DeCocinis, CEI

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)

www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

B-075c OF 2018/19

B-076c OF 2018/19B-077c OF 2018/19

B-087c OF 2018/19

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.

207 SENATE AVENUE

CAMP HILL, PA 17011

Phone: 717.763.7211

Fax: 717.763.8150

Email: [email protected]

Attn: Brian Seip, PE

SHEET OF

12" = 1'-0"

ELECTRICAL POWERSCHEMATICS AND DETAILS

Author CJG

EP-40157 58

SCALE: NTS

ELECTRICAL RISER DIAGRAM - EXISTING/DEMOLITION1

SCALE: NTS

ELECTRICAL ONE-LINE DIAGRAM - EXISTING/DEMOLITION2

1 4-17-2020 ADDENDUM 1 1 4-17-2020 ADDENDUM 1 2

ADDENDUM #220 APRIL 2020

Page 26: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

EXISTPOWERPANEL

'PA'

NEW SWITCHBOARD 3000A MCB

208/120V, 3PH, 4W

PB

BASEMENT

FIRST FLOOR

EXISTLTG.

PANEL 'LA'

EXISTPOWERPANEL

'PC'

EXISTLTG.

PANEL 'LC'

EXISTPOWERPANEL

'PZ'

SECOND FLOOR

EXISTPOWERPANEL

'PK'

EXISTLTG.

PANEL 'LK'

FUTURE THIRD FLOOR

P.E. CO. METERING

EXISTLTG.

PANEL 'LE'

EXISTLTG.

PANEL 'LF'

EXISTLTG.

PANEL 'LG'

EXISTPOWERPANEL

'PG'

NEWPANEL 'PB1'

EXISTPOWERPANEL

'PM'

EXISTPOWERPANEL

'PD'

EXISTLTG.

PANEL 'LD'

EXISTLTG.

PANEL 'LH'

EXISTPOWERPANEL

'PL'

EXISTLTG.

PANEL 'LL'

BOILER ROOM

250A208/120V3PH, 4W

250A208/120V3PH, 4W

600A208/120V3PH, 4W

250A208/120V3PH, 4W

250A208/120V3PH, 4W

225A208/120V3PH, 4W

225A208/120V3PH, 4W

225A208/120V3PH, 4W

250A208/120V3PH, 4W

250A208/120V3PH, 4W

400A208/120V3PH, 4W

150A208/120V3PH, 4W

150A208/120V3PH, 4W

150A208/120V3PH, 4W

150A208/120V3PH, 4W

430A208/120V3PH, 4W

225A208/120V3PH, 4W

225A208/120V3PH, 4W

EXISTING 2-5"C TO MANHOLE #2 (ETR)

NEWPANEL 'PB2'

500A208/120V3PH, 4W

ELEVATOR (PASS)25 HP

3PH/208V

ELEVATOR (FREIGHT)25 H.P 3PH/208V

NEW SUBSTATION 'SA'

NEW XFMR 750/1000 KVA

13.2KV PRI120/208V SEC

NEWCT

CABINET

NEW13.2KV FUSED DISC

NEW J-BOX

INTERCEPT EXISTING CONDUITS IN NEW OVERHEAD J-BOX(ES), AS REQUIRED USING CARE NOT TO DAMAGE EXISTING CONDUCTORS; EXTEND/RE-ROUTE EXISTING FEEDERS FROM NEW J-BOX(ES) TO NEW SWITCHBOARD. REFER TO SWITCHBOARD SCHEDULE FOR WIRING REQUIREMENTS FOR FEEDER EXTENSIONS.

1

1

3 7

9

11

10

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

(DOUBLE PANEL)

13TO CHILLER

NORMAL FEED TO EXISTING ATS FOR PANELS "EN"

EXISTING 15KV PULLBOX (ETR)

KEYED NEW WORK NOTES:1. NEW 200A FUSED SHUNT TRIP ELEVATOR

DISCONNECT SWITCH, WITH 110A FUSES.

#

1

1

1

1

1

1

1

1

FEEDER LEGEND:

3 #1 & #1 NEUT. + 1 #8 GRD IN 1 1/2"C.

3 #1/0 & #1/0 NEUT. + 1 #6 GRD IN 1 1/2"C.

3 #4/0 & #4/0 NEUT. + 1 #4 GRD IN 2 1/2"C.

3 #250KCMIL & #250KCMIL NEUT. + 1 #4 GRD IN 2 1/2"C.

3 #350KCMIL & #350KCMIL NEUT. + 1 #4 GRD IN 3"C.

2 SETS OF 3 #3/0 & 1 # 3/0 NEUT. + 1 #3G IN (2) 2"C.

2 SETS OF 3 #250KCMIL & 1 #250KCMIL NEUT. + 1 #2G IN (2) 2 1/2"C.

2 SETS OF 3 #350KCMIL & 1 #350KCMIL NEUT. + 1 #1G IN (2) 3"C.

2 SETS OF 3 #300KCMIL & 1 #300KCMIL NEUT. + 1 #1/0G IN (3) 3"C.

1 1/4" EMPTY CONDUIT FOR PECO METERING CONDUCTORS.

(1) 5' CONDUIT WITH 3 #1/0 (15KV); AND (1) 5" CONDUIT - SPARE.

2 #6 & #6 NEUT. + 1 #10 GRD IN 1"C.

4 SETS OF 3 #350KCMIL & 1 #350KCMIL NEUT. + 1 #3/0G IN (4) 3"C.

1

2

3

4

5

6

7

8

9

10

11

12

13

1

MAIN SWITCHBOARDVOLTAGE: 208Y/120 V, 3-PHASE, 4-WIRE

BUS: 3000A MAIN: 3000/3 MCB (LSI)

SHORT CIRCUIT: 65 kA

ENCLOSURE: NEMA 1, FREE STANDING, FRONT ACCESS ONLY

LOADCOMMENTS

DESCRIPTION AMP/ #P

EXISTING LIGHTING PANEL 'LK' 250/3 FEEDER TYPE 4

EXISTING POWER PANEL 'PK' 250/3 FEEDER TYPE 4

EXISTING LIGHTING PANEL 'LL' 400/3 FEEDER TYPE 6

EXISTING POWER PANEL 'PM' 450/3 FEEDER TYPE 7

EXISTING POWER PANEL 'PL' 225/3 FEEDER TYPE 3

NEW WATER COOLED CHILLER 1200/3 FEEDER TYPE 13

EXISTING POWER PANEL 'PZ' 600/3 FEEDER TYPE 8

EXISTING LIGHTING PANELS 'LE', 'LF' & 'LG' 225/3 FEEDER TYPE 3

EXISTING POWER PANEL 'PG' 150/3 FEEDER TYPE 2

EXISTING ATS / PANEL "EN" (NORMAL FEED) 60/2 FEEDER TYPE 12

EXISTING LIGHTING PANELS 'LD' & 'LH' 250/3 FEEDER TYPE 4

EXISTING POWER PANEL 'PD' 150/3 FEEDER TYPE 2

EXISTING LIGHTING PANELS 'LA' & 'LC' 250/3 FEEDER TYPE 4

EXISTING POWER PANELS 'PA' & 'PC' 150/3 FEEDER TYPE 2

NEW PANEL 'PB1' 225/3 FEEDER TYPE 3

NEW PANEL 'PB2' 500/3 FEEDER TYPE 7

FREIGHT ELEVATOR 110/3 FEEDER TYPE 1

PASSENGER ELEVATOR 110/3 FEEDER TYPE 1

NOTES:

1. ALL SWITCHBOARD CIRCUIT BREAKERS LARGER THAN 100A FRAME SIZE SHALL BE PROVIDED WITH ELECTRONIC ADJUSTABLE TRIP UNITS (ADS. LSI).

2. "EXISTING" FEEDERS TO BE CAPTURED AND EXTENDED/ RECONNECTED TO NEW MAIN SWITCHBOARD. REFER TO FEEDER LEGEND FOR REFERENCED FEEDER TYPES.

1

1

1

DATE

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,

PHILADELPHIA, PA 19121

PERMIT SET

25 MARCH 2020

ARCHITECTURAL

GANNETT FLEMING, INC.

ONE PENN PLAZA, SUITE 630

250 WEST 34TH STREET

NEW YORK, NY 10119

Phone: 212.967.9833

Fax: 212.232.5791

Email: [email protected]

Attn: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.

232 CECELIA ACRES DRIVE

IVYLAND, PA 18974

Phone: 215.354.9161

Fax: 215.354.9163

Email: [email protected]

Attn: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.

1010 ADAMS AVENUE

VALLEY FORGE, PA 19403

Phone: 610.650.8156

Fax: 610.650.8190

Email: [email protected]

Attn: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.

1801 MARKET STREET, SUITE 2600

PHILADELPHIA, PA 19103

Phone: 215.557.0106

Fax: 215.557.0337

Email: [email protected]

Attn: Mark D. DeCocinis, CEI

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)

www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

B-075c OF 2018/19

B-076c OF 2018/19B-077c OF 2018/19

B-087c OF 2018/19

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.

207 SENATE AVENUE

CAMP HILL, PA 17011

Phone: 717.763.7211

Fax: 717.763.8150

Email: [email protected]

Attn: Brian Seip, PE

SHEET OF

12" = 1'-0"

ELECTRICAL POWERSCHEMATICS AND DETAILS

FJR CJG

EP-40258 58

SCALE: NTS

ELECTRICAL RISER DIAGRAM - REVISED/NEW1

SCALE: NTS

MAIN SWITCHBOARD SCHEDULE2

1 4-17-2020 ADDENDUM 11 4-17-2020 ADDENDUM 1 2

ADDENDUM #220 APRIL 2020

Page 27: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

E-001

ELECTRICALSYMBOLS AND

ABBREVIATIONS

IN FIELD.

8. EXACT LOCATION AND MOUNTING OF ALL EQUIPMENT SHALL BE VERIFIED

CLOSE AS POSSIBLE.

CIRCUIT NUMBERS MAY VARY. CONTRACTOR SHALL BALANCE PANELS AS

9. CIRCUIT NUMBERS SHOWN ARE FOR IDENTIFICATION ONLY. ACTUAL

FOR CLARIFICATION PRIOR TO STARTING ANY WORK.

SHALL REPORT DISCREPANCIES, IF ANY, TO THE ARCHITECT/ENGINEER

5. THE CONTRACTOR SHALL VERIFY ALL THE DIMENSIONS IN FIELD AND

NATIONAL ELECTRICAL CODE.

4. ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AS REQUIRED BY THE

OF THIS WORK WITH ALL TRADES.

3. THE CONTRACTOR SHALL COORDINATE THE LOCATION AND INSTALLATION

OTHER GOVERNING AGENCIES HAVING JURISDICTION.

REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, OSHA AND ALL

A MANNER AS POSSIBLE AND SHALL COMPLY WITH THE LATEST

2. ALL WORK SHALL BE NEW AND PERFORMED IN AS NEAT AND AS CLEAN

FIRE ALARM, ELECTRIC DEVICES, AND CIRCUITING SHOWN ON THE DRAWINGS.

1. PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT TO INSTALL LIGHTING,

GENERAL ELECTRICAL NOTES:

6. THE CONTRACTOR SHALL COORDINATE HIS WORK VERY CLOSELY WITH

ELECTRIC COMPANY FOR ELECTRIC SERVICE AND WITH TELEPHONE

COMPANY FOR TELEPHONE SERVICE.

7. THE CONTRACTOR, BEFORE SUBMITTING HIS BID ON THE WORK, MUST

VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL VISIBLE EXISTING

CONDITIONS. AS A RESULT OF HAVING VISITED THE PREMISES,

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE INSTALLATION OF

ON THE PART OF THE BIDDER OF HIS VISITATION TO THE SITE.

THE SUBMISSION OF A BID WILL BE CONSIDERED AN ACKNOWLEDGEMENT

THE WORK AS IT RELATES TO SUCH VISIBLE EXISTING CONDITIONS.

EQUIPMENT IDENTITY - MECHANICAL, PLUMBING OR ELECTRICAL.

THERMOSTAT.

TRANSFORMER.

METER, ELECTRIC.

PHASE.

NOTES:

1. SEE LIGHTING FIXTURE SCHEDULE FOR MANUFACTURER TYPES AND MOUNTING.

LIGHTING FIXTURE, RECESSED, SURFACE OR PENDENT MOUNTED.

CAPITAL LETTER INDICATES FIXTURE TYPE (SEE FIXTURE

EXIT LIGHT, CEILING MOUNTED. (ARROWS INDICATE DIRECTION

OF EXIT).

SWITCH, SINGLE POLE, 20A, HEAVY DUTY TOGGLE, BROWN HANDLE, 120-277 VOLT,

20 AMPERE, GROUNDING TYPE.

SWITCH, SAME AS SINGLE POLE, 20A, HEAVY DUTY TOGGLE, EXCEPT THREE POLE.

RECEPTACLE, DUPLEX, 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE,

GROUNDING TYPE. GFI=GROUND FAULT INTERRUPTER.

DOUBLE DUPLEX RECEPTACLE RECESSED WALL MOUNTED.

2P, 3W, 125 VOLT, 20 AMPERE

DATA OUTLET WITH DEVICE IN PLATE, MOUNTED IN RECESSED

RECEPTACLE, SINGLE, 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE,

GROUNDING TYPE.

WALL MOUNTED, DOUBLE DUPLEX RECEPT, 2P, 3W, 125 VOLTS,

20 AMPS, MOUNT BOTTOM OF BOX 16" A.F.F. (U.N.O.)

TELEPHONE OUTLET WITH JACK DEVICE IN PLATE, MOUNTED IN

SAFETY SWITCH, NON-FUSED, HEAVY DUTY.

SAFETY SWITCH, FUSED, HEAVY DUTY.

MOTOR STARTER, COMBINATION TYPE WITH DISCONNECT MEANS

(CIRCUIT BREAKER, FUSED SWITCH OR NON-FUSED SWITCH).

REQUIRED.

CONTACT, MAGNETIC.

MOTOR

GROUND POINT.

JUNCTION BOX, RECESSED INSTALLATION UNLESS OTHERWISE

NOTED.

CONDUIT WITH WIRE, EXPOSED TURNING DOWN

CONDUIT WITH WIRE, CONCEALED IN CEILING OR WALLS.

HOMERUN CONDUIT WITH WIRE, TO LIGHTING/POWER PANEL,

NUMERALS INDICATE BREAKER NUMBER.

CONDUIT WITH WIRE, CONCEALED BELOW FLOOR

OF POLES, FUSE SIZE OR

CIRCUIT BREAKER SIZE AS

A

S

3

S

VOLTAGE, SIZE, NUMBER

SPEAKER, CEILING MOUNTED.

SWITCH, FIRE ALARM SYSTEM, (FS) FLOW SWITCH, (PS)

SPRINKLER TAMPER SWITCH, FIRE ALARM SYSTEM.

PUBLIC ADDRESS WALL CONTROL STATION/INTERCOM

DOOR STRIKE, ELECTRIC.

PHOTO CELL.

CLOSED CIRCUIT T.V. CAMERA.

S

P

S

4

POLE, 20A, HEAVY DUTY TOGGLE, PILOT LIGHT, RED NEON, 1/25 W, 125 OR

SWITCH AND PILOT LIGHT COMBINATION, SWITCH SAME AS SINGLE

SWITCH, SAME AS SINGLE POLE, 20A, HEAVY DUTY TOGGLE, EXCEPT FOUR WAY.

277 VOLT, RECESSED WALL MOUNTED.

SWITCH, SAME AS SINGLE POLE, 20A, HEAVY DUTY TOGGLE, EXCEPT KEY OPERATED.

SK

SM

SWITCH-MANUAL MOTOR STARTER WITH THERMAL OVERLOAD.

DIMMER SWITCH, INCANDESCENT 120 VOLT, WATTAGE SIZE AS

NOTED IN SPECIFICATIONS.

ELECTRICAL PANEL.

RECESSED FLOOR BOX & WIRED TO TELEPHONE SYSTEM CABINET.

AMP

ABOVE FINISHED FLOOR

BREAKER

CONDUIT

CIRCUIT BREAKER

DRAWING

EXISTING

GROUND FAULT INTERRUPTER

GROUND

CIRCUIT

A

AFF

BRKR

C

CKT

DWG

CB

EXIST.

GND

10. ALL SPECIAL SYSTEM WIRING REQUIREMENTS SHALL BE AS SPECIFIED

BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

480v, 208v, 3 PHASE, 4 WIRES

KEYPAD - ACCESS CONTROL SYSTEM

INTERCOM STATION

PUSHBUTTON STATIONS

GFI

WP WEATHERPROOF

W

S

P

EXIT LIGHT, WALL MOUNTED. (ARROWS INDICATE DIRECTION

OF EXIT).

DRAWINGS.

ABBREVIATIONS

LEGEND

J J

T

T

Ø

SCHEDULES ON DWG. E-XX).

LIGHTING FIXTURE WIRED TO EMERGENCY PANEL OR W/EMERGENCY BALLAST

SAME AS ABOVE EXCEPT MTD. IN RECESSED FLOOR BOX.

FLOOR BOX & WIRED TO DATA SYSTEM.

SAME AS ABOVE EXCEPT WALL MOUNTED 16" AFF TO BOTTOM

P1

1

ULTRASONIC OCCUPANCY SENSOR & POWER PACK ASSEMBLY.

PASSIVE INFRARED LOW TEMPERATURE OCCUPANCY SENSOR &

POWER PACK ASSEMBLY.

CONTROL BOX FOR ELECTRONIC WATER FLUSHING SYSTEM

FURNISHED BY PLUMBING CONTRACTOR

FIRE PROTECTION WATER FLOW RELEASE CONTROL PANEL,

FURNISHED BY PLUMBING CONTRACTOR.

RECEPT

CONV CONVENIENCE

RECEPTACLE

OF BOX WITH STUB TO THE CEILING AND CAT 6 CABLE.

SAME AS ABOVE EXCEPT ISOLATED GROUND.

PRESSURE SWITCH.

SPECIAL PURPOSE OUTLET, NEMA RATING AS INDICATED ON

IG

SD

a

GFI

TV

PC

WIREMOLD RACEWAY 4000 WITH DIVIDER

TV OUTLET

EC ELECTRICAL CONTRACTOR

GENERAL CONSTRUCTION CONTRACTORGC

XFMR

MTD

PECO

NIC

UON UNLESS OTHERWISE NOTED

NOT IN CONTRACT

PHILADELPHIA ELECTRIC COMPANY

MOUNTED

TRANSFORMER

(NOT ALL SYMBOLS MAY BE USED ON DRAWINGS)

DOWNLIGHT FIXTURE

ABOVE DOOR LIGHT FIXTURE

FS

TS

SPEAKER, WALL MOUNTED.S

PA

K

I

11. ALL WIRING AND CONDUIT TO BE CONCEALED IN WALLS AND ABOVE FINISHED

CEILINGS UNLESS OTHERWISE NOTED. THE EC SHALL COORDINATE WORK

WITH THAT OF THE GENERAL CONSTRUCTION CONTRACTOR DURING WALL AND

CEILING CONSTRUCTION. ALL EXPOSED WIRING SHALL RUN IN CONDUIT.

12" ROUND, BATTERY OPERATED WIRELESS ANALOG CLOCK.

TELEPHONE OUTLET WITH JACK DEVICE IN PLATE, WALL

MOUNTED, 16" A.F.F., U.O.N., STUB TO THE CEILING AND WIRED TO

TELEPHONE SYSTEM (CAT 6 CABLE).

SAME AS ABOVE EXCEPT MOUNT 48" TO TOP OF BOX.

EXISTING(E)

NEW(N)

WALL MOUNTED RECESSED RECEPT, 2P, 3W, 125 VOLTS,

20 AMPS, MOUNT BOTTOM OF BOX 16" A.F.F.

COMBINATION TEL/DATA OUTLET WITH JACK DEVICE IN PLATE, WALL

MOUNTED, 16" A.F.F., U.O.N., STUB TO THE CEILING AND WIRED TO

TEL/DATA SYSTEM (CAT 6 CABLE).

SHEET 38 OF 61

N/A

SMOKE DETECTOR, CEILING MOUNTED.

DUCT MOUNTED SMOKE DETECTOR

HEAT DETECTOR, CEILING MOUNTED.

FIRE ALARM PULL STATION, MANUAL, WALL MOUNTED, 48" A.F.F.

FIRE ALARM COMBINATION, AUDIO/VISUAL, WALL MOUNTED

FIRE ALARM CONTROL PANEL, RECESSED WALL MOUNTED.

END OF LINE RESISTOR.

FIRE JACK AND FIRE FIGHTER'S PHONE.

SWITCH, FIRE ALARM SYSTEM, (FS) FLOW SWITCH, (PS)

SPRINKLER TAMPER SWITCH, FIRE ALARM SYSTEM.

F

SD

FACP

FAAP

EOL

FIRE ALARM ANNUNCIATOR PANEL

PRESSURE SWITCH.

DD

HD

FS

TS

FIRE ALARM STROBE, WALL MOUNTED.

FIRE ALARM MINI HORN/STROBE WALL MOUNTED

SD

FIRE ALARM SPEAKER AND STROBE

FPJ

FIRE ALARM SPEAKER

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

GENERAL NOTES

DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC AND ARE

INTENDED TO INDICATE CAPACITY, SIZE, APPROXIMATE

LOCATION AND GENERAL ARRANGEMENT. WHILE THE DRAWINGS

ARE GENERALLY TO SCALE AND ARE AS ACCURATE AS THE

SCALE WILL PERMIT, DIMENSIONS SHALL BE CONFIRMED IN THE

FIELD.

THE CONTRACTOR SHALL COMPLY WITH THE LAWS,

ORDINANCES, RULES AND REGULATIONS OF LOCAL AND

STATE GOVERNMENTAL AUTHORITIES; OF THE NATIONAL FIRE

PROTECTION ASSOCIATION AS INTERPRETED BY THE

ENFORCING AUTHORITY HAVING JURISDICTION; AND OF

PUBLIC UTILITIES HAVING CONNECTION WITH ANY OF THE

SYSTEMS HEREIN SPECIFIED.

THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS

AND INSPECTIONS REQUIRED BY ANY OF THE FOREGOING

AUTHORITIES, AND PAY FOR ALL OTHER COSTS IN CONNECTION

WITH THE WORK. CERTIFICATES SHALL BE IN DUPLICATE AND

SHALL BE DELIVERED TO THE OWNER.

THE SITE, LOCATION, AND ROUTING OF SYSTEMS INDICATED TO

HAVE NEW CONNECTIONS MADE TO THEM ARE SHOWN AS

ACCURATELY AS FIELD CONDITIONS PERMIT. CONTRACTOR

SHALL VISIT THE SITE AND THOROUGHLY EXAMINE THE

CONTRACT DRAWINGS. ALL EXISTING CONDITIONS SHALL BE

EXAMINED AND THEIR EXACT LOCATIONS VERIFIED. THE

CONTRACTOR SHALL REPORT TO THE ENGINEER ANY

CONDITIONS WHICH MIGHT MAKE INSTALLATION OF REQUIRED

EQUIPMENT A PROBLEM. NO CONSIDERATION OR ALLOWANCE

WILL BE GRANTED FOR FAILURE TO INVESTIGATE CONDITIONS OR

MISUNDERSTANDINGS OF THE CONTRACTUAL REQUIREMENTS.

THE CONTRACTOR SHALL INSTALL AND CONNECT EQUIPMENT

AND MATERIALS IN ACCORDANCE WITH THE BEST ENGINEERING

PRACTICE AND, UNLESS OTHERWISE SHOWN OR SPECIFIED,

FOLLOW THE MANUFACTURER'S PRINTED INSTALLATION

REQUIREMENTS AND RECOMMENDATIONS, AND FURNISH AND

INSTALL REQUIRED AUXILIARY ITEMS TO PROVIDE A COMPLETE

INSTALLATION.

THE CONTRACTOR SHALL REPAIR WALLS, CEILING, FLOORS,

ETC., THAT ARE REQUIRED TO BE PENETRATED, OR OTHERWISE

DISTURBED. THE REPAIRS SHALL BE WITH MATERIALS AND

FINISHES TO MATCH EXISTING. FIRE WALL PENETRATIONS

SHALL BE SEALED WITH SUITABLE MATERIALS TO PRESERVE

FIRE WALL INTEGRITY.

THE CONTRACTOR SHALL REMOVE EQUIPMENT NOT INDICATED

TO BE REUSED TO A DESIGNATED LOCATION AT THE PROJECT

SITE. AFTER THE EQUIPMENT HAS BEEN ASSEMBLED FOR THE

OWNER'S INSPECTION AND POSSIBLE RETENTION, ALL

EQUIPMENT NOT TO BE RETAINED BY THE OWNER SHALL BE

REMOVED FROM THE SITE BY THE CONTRACTOR.

BUILDING SYSTEMS SHALL REMAIN IN SERVICE UNLESS

INDICATED OTHERWISE. OUTAGES OR INTERRUPTIONS SHALL

BE KEPT TO A MINIMUM DURATION. NOTIFY THE OWNER 48

HOURS IN ADVANCE OF ANY OUTAGE OR INTERRUPTION. IF

TEMPORARY CONNECTIONS ARE NECESSARY TO ASSURE THIS

CONTINUITY OF SERVICES, THEY SHALL BE FURNISHED BY THE

CONTRACTOR WITHOUT ADDITIONAL CHARGE TO THE OWNER

AND SHALL BE REMOVED WHEN NO LONGER NEEDED.

THE CONTRACTOR SHALL ARRANGE AND EXECUTE HIS WORK

SUCH THAT ANY CONNECTIONS, BOTH TEMPORARY OR

PERMANENT, TO, OR REARRANGEMENT OF, PRESENT

EQUIPMENT, ETC., SHALL BE MADE IN SUCH A MANNER AS TO

ASSURE FULL RESUMPTION OF SERVICE AT THE TIME

DESIGNATED BY THE OWNER.

NOT ALL ABBREVIATIONS, LINE TYPES, OR SYMBOLS MAY APPEAR

ON THESE CONTRACT DOCUMENTS.

COORDINATE WITH OTHER TRADES TO AVOID

INTERFERENCE AMONG MECHANICAL, ELECTRICAL,

ARCHITECTURAL AND STRUCTURAL, PLUMBING, ETC.

OS WATT STOPPER DUAL TECHNOLOY OCCUPANCY SENSOR #DT200 CEILING MTD

OS

PIR

WATT STOPPER PIR OCCUPANCY SENSOR WPIR - SMALL BATHROOMS

WATT STOPPER PIR OCCUPANCY SENSOR #CI-205-1 - VESTIBULE CEILING MTD

OS

US

WATT STOPPER ULTRASONIC OCCUPANCY SENSOR #WT-1105- STALL BATHROOMS

WATT STOPPER ULTRASONIC OCCUPANCY SENSOR #WT-2255-CORRIDORS -

CEILING MOUNTED

OS

W

WATT STOPPER DUAL TECHNOLOGY OCCUPANCY SENSOR - WALL MOUNTED

WATT STOPPER DUAL TECHNOLOGY OCCUPANCY SENSOR - CEILING MTD, 360 DEG

OS

TS WATT STOPPER DIGITAL TIME SWITCH #TS-200

S WATT STOPPER, LOW VOLTAGE OVERRIDE SWITCH FOR LIGHTING CONTROLS

CONTROL MODULE

Page 28: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

UP

UP

UP

1

1

1

1

1

1

3

4

2

2

2

2

2

2

1

1

1

1 1 1

1 1 1 1

1 1 1 1

1 1 1 1

1

5 6

7

1 2

UP

UP

UP

EXISTINGPNL "LA"

2

2

2

2

2

TOP OF THE STAIR(BY THE ENTRANCE DOOR)

1

2

1

TOP OF THE STAIR(BY THE ENTRANCEDOOR)

TOP OF THE STAIR(BY THE ENTRANCEDOOR)

1

1

ABOVE LANDING

1 2

GENERAL DEMOLITION NOTES

1. ALL EXISTING INTERIOR LIGHT FIXTURES AND SWITCHES IN SUB-BASEMENT AND SOME AREAS OFTHE BASEMENT, SHALL BE REMOVED UNLESS NOTED OTHERWISE.

2. E.C. SHALL VERIFY THE PANEL DESIGNATION AND CIRCUIT NUMBER FOR EACH DEVICE TO BEREMOVED.

3. ALL SYMBOLS SHOWN LIGHTLY SOLID ARE EXISTING ELECTRICAL DEVICES/EQUIPMENT TOREMAIN.

4. ALL WIRING/CONDUIT LEFT UNUSED SHALL BE REMOVED TO ITS POINT OF ORIGIN AND CIRCUITBREAKER TO BECOME SPARE.

5. PANELBOARDS WHICH ARE AFFECTED BY THE DEMOLITION AND NEW WORK SHALL HAVE THEPANEL SCHEDULES REVISED.

6. COORDINATE ALL WORK WITH OTHER TRADES.

7. ELECTRICAL CONTRACTOR SHALL NOT DISCONNECT ANY EQUIPMENT, OR ELECTRICALCIRCUITS IN THE RENOVATED AREA WITHOUT PRIOR NOTIFICATION AND PERMISSION FROMMAINTENANCE AND ENGINEERING DEPARTMENT. EXTREME CARE SHALL BE TAKEN TOMINIMIZE DISTURBANCE TO SURROUNDING AREAS.

8. VERIFY ALL CONDITIONS AT JOB SITE.

DEMOLITION KEY NOTES

1

EXISTING LIGHT FIXTURE TO BE REMOVED. SEE GENERAL DEMOLITION NOTES.

EXISTING SWITCH TO BE REMOVED. SEE GENERAL DEMOLITION NOTES.

EXISTING GENERATOR TO BE REMOVED. SEE GENERAL DEMOLITION NOTES.

EXISTING AUTOMATIC TRANSFER SWITCH TO BE REMOVED. SEE GENERAL DEMOLITION NOTES.

EXISTING FUSED DISCONNECT SWITCH TO BE REMOVED.

EXISTING EMERGENCY SYSTEM JUNCTION/PULL BOX ABOVE ATS TO BE REMOVED.

EXISTING EMERGENCY SYSTEM CONDUIT AND CABLE - REMOVE SECTION EXPOSED TO FLOOD.

2

3

4

5

6

7

1/8" = 1'-0"

E-101

SCALE: 1/8" = 1'-0"

ELECTRICAL SUB-BASEMENT DEMOLITION PLAN - LIGHTING

1

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 1/8" = 1'-0"

ELECTRICAL BASEMENT DEMOLITION PLAN - LIGHTING

2

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ELECTRICAL SUB-BASEMENTAND BASEMENT

DEMOLITION PLANS

SHEET 39 OF 61

Page 29: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

UP

UP

UP

BOILER ROOM

SB-01

STAIRWELL

S-00

FREIGHT

ELEVATOR

MACHINE ROOM

SB-03

FREIGHT

ELEVATOR

TELECOM ROOM

SB-02

EX1

EX1

ab

EX1G

F

GF

EM/NL

EM/NL

EM/NL

DEM/NL DIM

3

4

F

EM/NLEM

EM/NL

G

EM/NL

G

A a A a

A b A a A b A a

A a A b A b

A a A b

CDIM

DIM

B

EM

b6

B b

A a

6

DIMC

DIM

DIM

2

LIGHT FIXTURE TO BE CONTROLLED BYOCCUPANCY SENSOR TO DIM 50% IF SPACE ISNOT OCCUPIED (NO AUTOMATIC SHUT-OFF).CIRC. #EM-1 (TYPICAL)

DIM

EM-1

EM-1EM-1

EM-1

EM-1

EM-1

EM-1

EM-1

LIGHT FIXTURE TO BE CONTROLLED BYOCCUPANCY SENSOR TO DIM 50% IF SPACE ISNOT OCCUPIED (NO AUTOMATIC SHUT-OFF).CIRC. #EM-1 (TYPICAL)

REFER TO ENLARGED PLAN3/102 THIS SHEETFOR ADDITIONALWORK IN THIS AREA.

UP

UP

UP

TRANSFORMER

& SWITCH

ROOM

B-16

PASSAGE

B-18

RECEIVING

AREA

B-17

CUSTOD'N

OFFICE

B-15

KITCHEN HELP

LOCKER RM.

B-14

JANITOR

SUPPLIES

B-13

HEUPS

LOCKER RM

B-12

STORAGE

B-11

B-12A

KITCHEN HELP

TOILET RM

B-14A

OFF. TOIL.

B-15B

COMPRESSOR

SPACE

B-17A

ELEV.

MACHINE

ROOM

B-10

UNEXCAVATED

CRAWL

SPACE 'C'

B-9B

UNEXCAVATED

METER ROOM

MR-5

CORRIDOR

NO.1

B-1

ELEV. NO.1

B-12B

UPPER PART

OF

MECHANICAL

EQUIPMENT

ROOM

MR-1

PIPE SPACE

CLO.

B-15C

ELEV NO.2

EXISTINGPNL "LA"

TOP OF THE STAIR(BY THE ENTRANCEDOOR)

a

5

5

GEM/NL

DIM

b

TOP OF THE STAIR(BY THE ENTRANCEDOOR)

a

5

G

EM/NL

DIM

b

LIGHT FIXTURE TO BE CONTROLLED BYOCCUPANCY SENSOR TO DIM 50% IF SPACE ISNOT OCCUPIED (NO AUTOMATIC SHUT-OFF).CIRC. #EM-1(TYPICAL)

F F

2

LIGHT FIXTURE TO BE CONTROLLED BYOCCUPANCY SENSOR TO DIM 50% IF SPACE ISNOT OCCUPIED (NO AUTOMATIC SHUT-OFF).CIRC. #EM-1(TYPICAL)

SEE EP-201 FOR ADDITIONALWORK IN THIS AREA.

REFER TO ENLARGED PLAN3/102 THIS SHEETFOR ADDITIONALWORK IN THIS AREA.

SHEET NOTES

1ELEVATOR PIT LIGHTING - PROVIDE ALL NEW CONDUIT AND WIRING.

2#12 + 1#12 GND - 3/4"C TO EXISTING PANEL "LA", 20/1 CIRCUIT BREAKER AVAILABLE AFTER DEMOLITION IS COMPLETED.FIELD VERIFY CIRCUIT NUMBER.

COORDINATE FINAL LOCATION OF LIGHTING FIXTURES WITH THE EQUIPMENT LAYOUT, PIPING, DUCTS, CONDUIT AND ETC.

LIGHT FIXTURES SHALL BE CHAIN MOUNTED AT THE HEIGHT OF 14' AFF

PROVIDE NEW 3-WAY LIGHTING SWITCH TO CONTROL NEW LIGHTS - LOCATE ON THE TOP OF THE STAIRS (AT THE ENTRANCE.

LIGHTING CIRCUIT SERVING LIGHTS MARKED AS "EM" AND SWITCHED WITH NORMAL LIGHTING SHALL BE CONTROLLED BYEMERGENCY LIGHTING CONTROL UNIT (ELCU). SEE DETAIL 2/104 FOR DETAILS.

CONNECT TO DEDICATED GFI RECEPTACLE CIRCUIT IN THE ELEVATOR PIT (LINE SIDE).

CONNECT TO DEDICATED GFI RECEPTACLE CIRCUIT IN THE ELEVATOR MACHINE ROOM (LINE SIDE).

FUSED DISCONNECT SWITCH FOR ELEVATOR CAR LIGHTS - 30/1/15A, LOCKABLE TYPE. COORDINATE LOCATION WITH ELEV.VENDOR/SHOP DRAWINGS.

PROVIDE NEW PIT LIGHT SWITCH LOCATED AT THE TOP OF PIT ACCESS LADDER.

2

3

4

5

6

7

8

9

10

7

ELEVATOR PIT(TYPICAL)

H

9

EM-5

HH

H

PB-33

EXISTING LIGHTINGTO REMAIN

10

1

1

1

1

FREIGHT

ELEVATOR

MACHINE ROOM

SB-03

FREIGHT

ELEVATOR

F

F

8

H

EM-3

9

7

PB-34

H

H

H

ELEVATOR PIT(TYPICAL)

1

1

1

1

10

PB-38

AS NOTED

E-102

SCALE: 1/8" = 1'-0"

ELECTRICAL SUB-BASEMENT NEW WORK PLAN - LIGHTING

1

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 1/8" = 1'-0"

ELECTRICAL PARTIAL BASEMENT NEW WORK PLAN - LIGHTING

2

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ELECTRICAL SUB-BASEMENTAND BASEMENT LIGHTING

PLANS

LAMP

TYPEPLAN

SYMBOL MANUFACT.TYPE CATALOGNUMBER VOLT

NO.REMARKSMOUNT.

WATT

A 120 1

EX1 EVENLITE TLX-RU - UNIV2LED120

DAY-BRITE LED 58 PENDANT

B

C

4' LINEAR, INDUSTRIAL TYPE FIXTURE; NOTE #1CHAIN MOUNTED IN HIGH CEILING AREAS, SURFACE MOUNTED ON LOW CEILINGS

120 1DAY-BRITE LED 58 PENDANT4' LINEAR, INDUSTRIAL TYPE FIXTURE; CHAIN MOUNTED IN HIGH CEILING AREAS,

SURFACE MOUNTED ON LOW CEILINGS; EMERGENCY CIRCUIT; NOTE #1

120 1DAY-BRITE LED 58 PENDANT4' LINEAR, INDUSTRIAL TYPE FIXTURE; OCCUPANCY SENSOR WITH HI-LO DIMMING (NO AUTO-SHUT OFF); CHAIN

MOUNTED IN HIGH CEILING AREAS, SURFACE MOUNTED ON LOW CEILINGS; EMERGENCY CIRCUIT; NOTE #1

FSI470L835-UNIV-DIM

FSI470L835-UNIV-DIM

FSI470L835-UNIV-DIMLSXR10ADC

D 120 1DAY-BRITE LED 58 WALL4' LINEAR, INDUSTRIAL TYPE FIXTURE; OCCUPANCY SENSOR WITH HI-LO DIMMING (NO AUTO-SHUT OFF);

EMERGENCY CIRCUIT; NOTE #1FSI470L835-UNIV-DIM

LSXR10ADC

EDGE LIT EXIT SIGN; DIRECTIONAL ARROWS AS INDICATED; SINGLE FACE

LIGHTING CONTROLS SEQUENCE OF OPERATION:

1. BOILER ROOM - MANUAL ON/OFF SWITCH FOR LOCAL CONTROL OF GENERAL LIGHTING.

2. EGRESS LIGHTING TRANSFER TO EMERGENCY/LIFE SAFETY POWER SOURCE AND FULL ON WITH LOSS OF NORMAL POWER.

4. EGRESS LIGHTING TO DIM 50% WITHIN 20 MINUTES OF OCCUPANTS LEAVING.

F 120 1DAY-BRITE LED 31 SURFACE 4' LINEAR, INDUSTRIAL TYPE FIXTURE; NOTE #1FSI440L835-UNIV-DIM

G 120 1DAY-BRITE LED 31 SURFACE4' LINEAR, INDUSTRIAL TYPE FIXTURE; OCCUPANCY SENSOR WITH HI-LO DIMMING (NO AUTO-SHUT OFF);

EMERGENCY CIRCUIT; NOTE #1FSI440L835-UNIV-DIM

LSXR10ADC

NOTES:1. PROVIDE WIREGUARD FOR FIXTURES INSTALLED IN THE BOILER ROOM.

H STONCO TW20-NW-G1-8 - WALL20LED120 ELEVATOR PIT LIGHT

SHEET 40 OF 61

SCALE: 1/4" = 1'-0"

PARTIAL SUB-BASEMENT PLAN - LIGHTING

3

SCALE: 1/4" = 1'-0"

PARTIAL BASEMENT PLAN - LIGHTING

4

Page 30: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

PNL "PB2"

UP

UP

UP

BOILER ROOM

SB-01

STAIRWELL

S-00

FREIGHT

ELEVATOR

MACHINE ROOM

SB-03

FREIGHT

ELEVATOR

TELECOM ROOM

SB-02

TERMINATE EXISTING EMERGENCYSYSTEM CONDUIT/CABLE AT THE NEWWALL MOUNTED PULL BOX. EXTENDNEW FEEDER AS REQUIRED TO THISPULL BOX.

UP TO NEW PANEL "EM"

3 4

EXISTING EMERGENCY SYSTEMCONDUIT WITH FEEDERCONDUCTORS TERMINATED ATEXISTING NORM-EM PANEL "NE"(FIRST FLOOR - CORRIDOR 101).

NEW AUTOMATICTRANSFER SWITCH

PROPOSEDLOCATIONOF NEW 30KWDIESELEMERGENCYGENERATOR

UP

UP

CREATIVE

ARTS

B-19

CORRIDOR

NO.2

B-1A

TRANSFORMER

& SWITCH

ROOM

B-16

PASSAGE

B-18

PUPIL EQUIP'T

B-19A

RECEIVING

AREA

B-17

CUSTOD'N

OFFICE

B-15

KITCHEN HELP

LOCKER RM.

B-14

JANITOR

SUPPLIES

B-13

HEUPS

LOCKER RM

B-12

STORAGE

B-11

B-12A

KITCHEN HELP

TOILET RM

B-14A

OFF. TOIL.

B-15B

COMPRESSOR

SPACE

B-17A

UNEXCAVATED

CRAWL

SPACE 'C'

B-9B

UNEXCAVATED

METER ROOM

MR-5

CORRIDOR

NO.1

B-1

UPPER PART

OF

MECHANICAL

EQUIPMENT

ROOM

MR-1

PIPE SPACE

CLO.

B-15C

TEACHERS CLOS

B-19C

ELEV NO.2

EXISTINGPNL "LA"

NEW PANEL "EM"

PROTECTIVE BOLLARDS - 5" HEAVY GAUGE,GALVANIZED STEEL PIPE FILLED WITH CONCRETE,SET IN 16" DIAMETER CONCRETE WITH MIN.HEIGHT OF 4' AFG. CONCRETE SHALL BE 5000 PSI,AIR ENTRAINED. THE BOLLARDS SHALL BE PAINTEDBRIGHT YELLOW, WITH FLUORESCENT PAINT ORMARKED WITH FLUORESCENT TAPE SUITABLE FOROUTDOOR USE.GENERAL CONTRACTOR WILL PROVIDEBOLLARDS. (TYPICAL).

PROVIDE WALL MOUNTED NEMA 4XPULL BOX WITH SEPARATECOMPARTMENT FOR LINE AND LOWVOLTAGE SYSTEMS (OR TWO SEPARATEPULL BOXES), COORDINATE IN FIELDLOCATION.

PROVIDE WALL MOUNTED PULL BOXWITH SEPARATE COMPARTMENT FORLINE AND LOW VOLTAGE SYSTEMS (ORTWO SEPARATE PULL BOXES),COORDINATE IN FIELD LOCATION.

1 2A A

3

3

42

4

4

CORE DRILL EXISTING AIRWAYCONCRETE WALL.REFER TO SHEET E-105 FOR DETAILS.

CORE DRILL EXISTING AIRWAYCONCRETE WALL.REFER TO SHEET E-105 FOR DETAILS.

4

4

EXISTINGAIRWAY

PROPOSED LOCATION OFGENERATOR REMOTE ANNUNCIATORPANEL. FINAL LOCATION TO BEAPPROVED BY SDP.

5

5

GENERATOR PAD TO BEPROVIDED BYGENERAL CONTRACTOR.

SHEET NOTES:

PROVIDE UNDERGROUND CONDUIT BANK ENCASED IN CONCRETE ENVELOPE. REFER TO DUCTBANK A-A DETAIL.

PRIOR TO START OF EXCAVATING, E.C. SHALL INVESTIGATE AND LOCATE ALL UNDERGROUNDUTILITIES, CONDUIT RUNS, PIPING AND ETC.

ALL EXPOSED CONDUIT RUNS/STUB-UPS SHALL BE GALVANIZED RIGID STEEL. TYPICAL.

REFER TO SHEET E-105 FOR ADDITIONAL EMERGENCY GENERATOR INSTALLATION DETAILS.

COORDINATE RUN OF CONDUITS WITH LOCATION OF UNDERGROUND FUEL OIL LINES/UST.

1

2

3

4

5 1/8" = 1'-0"

ELECTRICAL SUB-BASEMENTAND BASEMENT NEW WORK

PLANS - POWER

E-103

SCALE: 1/8" = 1'-0"

ELECTRICAL SUB-BASEMENT NEW WORK PLAN - POWER

2

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 1/8" = 1'-0"

ELECTRICAL BASEMENT NEW WORK PLAN - POWER

1

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

MINIMUM BURIAL DEPTHS TO TOP OF ELECTRIC DUCTS OR CABLES SHALLBE IN ACCORDANCE WITH THE NEC. MAXIMUM DEPTH TO THE TOPOF ELECTRIC DUCT BANKS SHALL BE 30 INCHES.

BURIAL DEPTHS SHALL BE PERMITTED TO BE INCREASED IN PART(S) OF THEDUCT RUN TO AVOID UNDERGROUND OBSTRUCTIONS WITHOUTDECREASING THE RATED AMPACITY OF THE CONDUCTORS. THE TOTALLENGHT OF PARTS OF THE DUCT RUN INCREASED IN DEPTH TO AVOIDOBSTRUCTION MUST BE LESS THAN 25% OF THE TOTAL RUN LENGTH ORELSE THE CAPACITY REDUCTION FACTOR OF NOTE 4 OF TABLES 310-69THROUGH 310-84 IN THE NEC SHALL BE APPLIED.

ALL DUCT BANKS SHALL BE INSTALLED PER THE NATIONAL ELECTRIC CODE.

NOT TO SCALE

NO. 4 AWG STRANDED COPPER GROUNDCONDUCTOR. CONNECT (CADWELD) TOEXISTING GROUNDING SYSTEM

NUMBER OF CONDUITS, SIZE ANDTYPE, AS INDICATED ON PLANS.

NO. 4 AWG COPPER GROUNDCONDUCTOR

CABLE

EARTH FILL

RED PLASTICMARKER TAPE

STEELREINFORCEDCONCRETE.

TYPICAL INSTALLATION OF CONCRETEENCASED UNDERGROUND CONDUITS

TYPICAL DUCTBANK DETAILSCALE: NONE

PROVIDE ANDINSTALL SPACERSAS REQUIRED.SECURE CONDUIT(S)TO SPACERS.

(4) ENCASEMENT TYPESCHEDULE 40 PVC CONDUITS

EXISTINGGRADE

NOTES:

GENERATOR DUCT BANK DETAIL A-ANOT TO SCALE

1" PVC SCH 40 JACKET HEATERBATTERY CHARGERCONVENIENCE RECEPT.

3/4" PVC SCH. 40 CONDUIT(REMOTE STARTER)

2" PVC SCH 40 CONDUITW/ POWER CONDUCTORS.

NO. 4 AWG STRANDED COPPERGROUND CONDUCTOR.CONNECT (CADWELD) TOEXISTING GROUNDING SYSTEM

3000 PSI CONCRETE ENVELOPE.

1" PVC SCH. 40 CONDUIT(REMOTE ANNUNCIATOR)

1'-0"

45°

AS REQ,D.

GENERATOR PADSCALE: 1/2" = 1'-0"

TYP.

BROOM FINISHED, 8" THICK, 3500 PSI, AT 28 DAYS,AIR ENTRAINED CONCRETE PAD WITH TURN-DOWN REINF.FOOTING ALL SIDES (PITCH 1/4 "/FT)

(2) #5 REBAR, CONTINUOUS TOP AND BOTTOM

CHAMFERED EDGE ALL AROUND

#5 REBAR @ 12" O.C. EA. WAY

COMPACTEDFREE-DRAINING MATERIAL

SHEET 41 OF 61

3

4

5

6

NOTE:1. GENERATOR PAD TO BE PROVIDED BY GENERAL CONTRACTOR.2. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH G.C.

NOTE:1. DUCT BANK CONCRETE ENCASEMENT TO BE PROVIDED BY GENERAL CONTRACTOR.2. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH G.C.3. SEE OTHER DETAILS THIS SHEET FOR ADDITIONAL INFORMATION.

NOTE:1. DUCT BANK CONCRETE ENCASEMENT TO BE PROVIDED BY GENERAL CONTRACTOR.2. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH G.C.3. SEE OTHER DETAILS THIS SHEET FOR ADDITIONAL INFORMATION.

NOTE:1. DUCT BANK CONCRETE ENCASEMENT TO BE PROVIDED BY GENERAL CONTRACTOR.2. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH G.C.3. SEE OTHER DETAILS THIS SHEET FOR ADDITIONAL INFORMATION.

Page 31: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

NONE

E-104

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

ELECTRICALDETAILS

SERVES:

LETTERING SIZE = 10 PT.

CATEGORY I NAMEPLATES

1 3/16"

"SERVES"

LOCATION:

VOLTAGE:

"SERVED BY"

CIRCUIT NO:

2 1/2"

1 3/16"

VOLTAGE:

LOCATION:SERVED BY:CIRCUIT NO:

2 1/2"

ELECTRICAL IDENTIFICATION: PANELBOARD

ARC FLASH WARNING LABEL

2" MIN.

INSIDE FACE OF WALL

FLOOR SEAL

TYPICAL CABLE (CONDUIT)

DRAWINGS

4" OR ASNOTED ON

FINISHED FLOOR

TYPICAL CABLE (CONDUIT)2" MIN.

SCALE: NONE

DUCTILE IRON PIPE SLEEVE ORGALVANIZED STEEL PIPE SLEEVEWITH WATERSTOP WELDED ALLAROUND EACH SIDE

FIRE RATED CAULKING/BARRIERAS REQUIRED TO MATCH FIRERATING OF WALL

DUCTILE IRON PIPE SLEEVE ORSCH. 40 GALVANIZED STEEL PIPEWITH WATERSTOP WELDED ALLAROUND EACH SIDE

FIRE RATED CAULKING/BARRIERAS REQUIRED TO MATCH FIRERATING OF FLOOR

INTERLOCKING SYNTHETIC RUBBERLINK TYPE SLEEVE CLOSURE.(TYPICAL)

CATEGORY I NAMEPLATE"SERVED BY"

EMERGENCY SYSTEMMARKER (IF APPLICABLE)

SCALE: NONE

SCALE: NONE

TYPICAL DETAIL FOR CABLE ORCONDUIT PASSING THROUGH FLOORSLABS OR WALL

PHENOLIC ENGRAVEDPLATE

Receptacle Outlet DetailNOT TO SCALE

+24VDC

Common

Control Output

Control Output

Common

+24VDC

Neutral

Hot

Red

Blk

Pack

Blk

Blu

Wht

Power

Any

Sensor

24VDC

Red

Ceiling/Wall

Sensor

24VDC

Any

Red

ad

oL

MULTIPLE OCCUPANCY SENSORS/SWITCH(S)LIGHTING CONTROL DETAIL

SEQUENCE OF OPERATION1. LIGHTING AUTO ON TO 100% WHEN OCCUPANCY DETECTED.2. MANUAL OFF WITH SWITCH.3. AUTO OFF ALL LIGHTING WITHIN 20 MINUTES OF OCCUPANTS LEAVING.

Local

Off

Switch

Quantity

as

shown

Quantity

as

shown

Quantity

as

shown

CORRIDOR

d

a

L

o

Single Switch

Neutral

Line

Green/Yellow

Green

Black

Ground

Ground

Red

SEQUENCE OF OPERATION1. LIGHTING IS MANUALLY CONTROLLED ON/OFF WITH OCCUPANCY SENSOR SWITCH.2. LIGHTING WILL AUTO OFF WITHIN 20 MINUTES OF OCCUPANTS LEAVING.

WALL SWITCH OCCUPANCY SENSORLIGHTING CONTROL DETAIL

Emergency Lighting

Emergency Line

Emergency Neutral

On/Off Control Device

Relay

Powerpack

Wall Switch

EmergencyPower

Normal Line

Normal Neutral

Normal Lighting

Jumper Wire or Normally Closed Input

Test Switch

Fire Alarm Input

Security Input

Other

"Sensing"

Line

"Switching"

Line

NormalPower

EMERGENCY LIGHTING CONTROL UNIT TYPICAL WIRINGNOT TO SCALE:

ELCU

2

1

5

3

7

4

8

SHEET 42 OF 61

PANELBOARD #CIRCUIT BREAKER #

Receptacle and Light inElevator Pit DetailNOT TO SCALE

9

LB FITTING

LIGHT FIXTURE

CONTINUOUS DUCTBANK

REINFORCING

STEEL CONDUITS (TYP.)

EXISTING FOUNDATION

WALL (EXTERIOR)

2" MIN.

CORE DRILLED (TYP.)

STAINLESS STEEL CONCRETE ANCHOR

SPACING AS REQUIRED

STAINLESS STEEL PIPE SPACER-LENGTH DETERMINED

BY SIZE OF FITTINGS USED AND SPACE REQUIRED FOR

SERVICING CONDUIT SEAL

SEALING LOCKNUT

(TYP.)

TERMINAL BOX

PULL BOX OR

WHERE PVC CONDUIT IS USED IN DUCTLINE, CONVERT TO

STEEL CONDUIT USING AN APPROPRIATE ADAPTER FITTING

EXPANDABLE RUBBER SEAL

LOCKNUT AND

INSULATED

BUSHING (TYP.)

SEALING

NOTE:

REINFORCING

CONTINUOUS DUCTBANK

THREADED DOWELS TO MATCH

CONCRETE ANCHOR (TYP.)

TYPE INTERNALLY THREADED

SELF-DRILLING OR DROP-IN

WITHIN 3'-0" OF WALL.

CONDUIT ENTRANCE SEAL IN EXISTING WALL

STEEL CONDUITS (TYP)

SEE NOTE BELOW

EXISTING EXTERIOR WALL

CORE DRILLED (TYP.)

STAINLESS STEEL CONCRETE

WALL INSERT & BOLT AS REQUIRED

STAINLESS STEEL PIPE SPACER-LENGTH DETERMINED

BY SIZE OF FITTINGS USED AND SPACE REQUIRED FOR

SERVICING CONDUIT SEAL

SEALING LOCKNUT

(TYPICAL)

TERMINAL BOX

PULL BOX OR

WHERE PVC CONDUIT IS USED IN DUCTLINE, CONVERT TO

STEEL CONDUIT USING AN APPROPRIATE ADAPTER FITTING

OZ GEDNEY TYPE

LOCKNUT AND

INSULATED

BUSHING (TYPICAL)

SEALING

NOTE:

WITHIN 3'-0" OF WALL.

CSM OR EQUAL

AIR GAP TO PREVENT

CONDENSATION OR

MOISTURE COLLECTION

SEAL IN EXISTING WALLCONDUIT ENTRANCE AND

TREADED COUPLING, TYPICAL

WATER PROOF SEAL - INDUSTRIAL

GRADE, PERMANENT, NON-HARDENING

SEALANT INJECTED INTO CAVITY.

EXTERIOR SIDE

(UNDERGROUND)

COATED TRANSITION

COUPLING BETWEEN RIGID

CONDUIT AND PVC

UNDERGROUND CONDUIT

RUN.

(TYPICAL).

HYDROLOCK TYPE

TREADED COLLAR (TYPICAL).

COMPRESSION BOLT (TYPICAL).

WASHER (TYPICAL).

COLLAR (TYPICAL).

CONDUIT

WATER-MOISTURE SEAL INSIDE

THE CONDUIT FOLLOWING CABLE

INSTALLATION.

WATER SEAL VACANT, SPARE

CONDUITS AS REQUIRED.

TYPICAL EXTERIOR WALL PENETRATION FOR CONDUIT

BUILDING WALL. SEE ARCHITECTURAL

DRAWINGS FOR TYPES OF WALL

CONSTRUCTION.

NEOPRENE OR SILICON

RUBBER GASKET.

10

11

12

Page 32: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

NONE

E-105

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

ELECTRICALDETAILS

GENERATOR DETAILNOT TO SCALE

NOTES:

1. THIS DETAIL IS SHOWN FOR GENERAL INFORMATION/PRICINGONLY. E.C. SHALL REFER TO GENERATOR SUBMITTAL PACKAGEFOR FINAL ELECTRICAL/CONTROLS REQUIREMENTS PRIOR TOROUGH-IN.

2. REFER TO OTHER PLANS FOR LOCATION, SIZING AND DETAILS.

3. DIFFERENT TYPE CIRCUIT BREAKERS (WITH ELECTRONIC TRIP)ARE ACCEPTABLE AS LONG AS FULL COORDINATION OF ALLPROTECTIVE DEVICES IS ASSURED TO COMPLY WITH NEC CODE.

IN-LINE CIRCUIT BREAKERFURNISHED WITH GENERATOR SET

ENGINE JACKET HEATER (NOTGFCI PROTECTED)

NEW- 6 #10,1"C. TO JACKET HEATER &CONVENIENCE OUTLET & BATTERY CHARGER

COMMERCIALSERVICE FEEDERS

GENERATOR SERVICEFEEDER

NEW GENERATOR - CONTRACTOR SHALLCOORDINATE LOCATIONS OF ALLNECESSARY MOUNTING HARDWARE ANDCONDUIT PENETRATIONS THROUGH SLABWITH MANUFACTURERS INFORMATION.

NEW- 2#14, 3/4"C. TO REMOTE ANNUNCIATOR(SEE MANUF. SUBMITTAL FOR DISTANCES/WIRESIZING)

NEW WIRING TO REMOTE ANNUNCIATOR(SEE MANUF. SUBMITTAL FOR DETAILS)

NEW GFI DUPLEX RECEPTACLELOCATED INSIDE WEATHER PROOFHOUSING (NEMA 3R)

CONCRETE PAD

ATS

ALL ADDITIONAL REMOTEEMERGENCY E-STOPS TO BEWIRED IN SERIES LOOP W/PRIMARY E-STOP ONGENERATOR CONTROLLER.

REMOTE@ ATS

2-#14, 3/4"C. FOR REMOTE START

LOAD SIDE FEEDERS

J J

3

125/3

1

ATS

125A

MAIN LINE CIRCUITBREAKER,LOCKABLE TYPE(FULLY RATED)

E.C. SHALL PROVIDE FINAL ACCEPTANCE OF THE EPSS INACCORDANCE WITH ALL APPLICABLE SECTIONS OF NFPA 1105-13.

30 KW, DIESEL ENGINE GENERATOR, 120/2080V-3Ø, 4W, WITHCRITICAL SILENCER, BATTERIES AND CHARGER, JACKET HEATER,WEATHER PROOF AND SOUND PROOF ENCLOSURE, (1) MAIN LINECIRCUIT BREAKERS.

NFPA 99 REMOTE ANNUNCIATOR. LOCATE IN MAIN OFFICE.

EMERGENCY SYSTEM POWER NOTES:

ALL UNDERGROUND CONDUIT INSTALLATION SHALL BE PVC SCH 40ENCASED IN CONCRETE ENVELOPE. PROVIDE RIGID STEEL CONDUITSFOR ALL EXPOSED INSTALLATION INCLUDING STUB-UPS. SEE OTHER PLANSFOR DETAILS.

125/4P AUTOMATIC TRANSFER SWITCH, 120/208V-3Ø, 4W WITHAUXILIARY CONTACTS, PILOT LIGHTS, TEST SWITCHES AND ADJUSTABLETIME DELAYS FOR TRANSFER, RE-TRANSFER AND COOL DOWN.

60/3

125/3

(E) PNL "EN"1ST FLOOR

CORRIDOR 101

EXISTING60A FEEDER

NEW WALL MOUNTEDPULL BOX INSUB-BASEMENTMECHANICAL ROOM

125/3

PANEL "PB2"120/208V-3PH, 4W

4#1 + 1#6 GND - 2"RSC

4#4 + 1#8 GND - 1-1/4"RSC

3#1 + 1#6 GND - 2" PVC SCH40

UNDERGROUNDENCASED IN CONCRETE

4#1 + 1#6 GND - 2"RSC

4#1 + 1#6 GND - 2"RSC

PNL "EM"ELECTRICAL RM.

NEW, NEMA 4X, WALLMOUNTED PULL BOX INEXISTING AIRWAY

PARTIAL SINGLE LINE DIAGRAM - NEW WORK

ATS

125A

(E) PNL "EN"1ST FLOOR

CORRIDOR 101TO REMAIN

EXISTING60A FEEDERTO REMAIN

EXISTING WALL MOUNTEDPULL BOX INSUB-BASEMENTBOILER ROOMTO BE REMOVED.

MAIN ELECTRICAL SWITCHBOARD120/208V-3PH, 4W

PARTIAL SINGLE LINE DIAGRAM - DEMOLITION

EXISTING 25 KVANG GENERATORIN THE BOILER ROOMSHALL BE REMOVED

EXISTING AUTOMATIC TRANSFERIN THE BOILER ROOMSHALL BE REMOVED

REMOVE

REMOVE

REMOVE

EXISTING 100A FUSEDDISCONNECT SWITCHIN THE BOILER ROOMSHALL BE REMOVED

PHASE CONDUCTORS HAVE BEEN OMITTED FOR CLARITY.

THIS DETAIL INDICATES GENERAL ARRANGEMENT OF GROUNDING REQUIREMENTS ONLY.FOR COMPLETE DISTRIBUTION REFER TO POWER RISER DIAGRAM.

NOTES:

1.

2.

N

LOAD

N GN

GROUNDING DETAILSCALE: NOTE

GND. & GROUNDROD, SIZE PER NEC

BATTERY CHARGER(NOT GFCI)

GROUNDING ELECTRODECONDUCTOR.

EMERGENCY GENERATOR.

EQUIPMENT GROUNDINGCONDUCTOR (TYPICAL).

BUILDING SERVICETRANSFORMER. MAIN SWITCHBOARD.

BUILDING SYSTEMGROUND BUS.

GROUNDINGELECTRODECONDUCTOR.

4-POLEAUTOMATICTRANSFERSWITCH.

GROUNDED CIRCUITCONDUCTOR (NEUTRAL)(TYPICAL).

BONDING JUMPER.

GROUNDING ELECTRODENEARBY.

1

2

3

4

Volts

Wire

Wire

Min. A.I.C.

Phase A

Phase C

Phase B

Total

KVA

AWire B C

Panel

Mounting

Location

25

29

27

23

21

28

30

22

24

26

19

13

17

15

11

9

18

20

16

14

10

12

Directory

Section

MAIN

Ckt

3

7

5

Bkr

1

4

8

6

ABC

2

Ckt

Directory

Bkr

KVA

A B C

Phase

/

2.5 1.5 1.5

30.0

10.9

8.9

10.2

ELECTRICAL ROOM-BASEMENT

SURFACE

EM

125A LUGS

208

4

10,000

120

3

EM LTG - SUB-BASMNT

NEW PANELBOARD

ELEV. LIGHTING

ELEV. LIGHTING

FIRE ALARM PANEL

BATTERY CHARGER

GEN JACKET HEATER

GEN. RECEPT.

SPARE

SPARE

SPACE

SPACE

EXISTING PNL "NE"

.5

.5

20/1*

20/1

#12

#12

#12

#12

INTEGRAL SPD COPPER BUS

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

20/1

20/1*

* - LOCK-ON CIRCUIT BREAKER

SPACE

SPACE

SPACE

SPACE

SPACE

.5

1.0

1.2

1.5

.2

#12

#12

#12

F/A BOOSTER PANEL

F/A BOOSTER PANEL

#12 20/1*

#12 20/1*

1.0

1.0

20/1

20/1

20/1

60

3

#4

#4

#4

7.2

7.2

7.2

8.4 8.7 7.4

SHEET 43 OF 61

CIRC. #PB2-2,4,6

TYPICAL STANDARD MOUNTING HEIGHTS DETAIL

THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED

WALL CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE

MOUNTING HEIGHTS TO CENTER OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY

TO NEAREST BLOCK OR BRICK COURSING.

OR DETAILED OTHERWISE ON THE DRAWINGS OR SPECIFICATIONS.

NOT TO SCALE:

NOTES:

2.

1.

TELEVISION OUTLET AND SERVICE RECEPTACLE - FOR7'-6"

FINISHED FLOOR

18"

4'-0"

2'-0"

4'-0"

6'-3"

4'-0"

6'-0"

6'-0"

6'-6"

OF FIXTURE

TO THE BOTTOM

6'-8"

WALL MOUNTED ELECTRICAL DEVICE LIGHTING SWITCHES,

MANUAL MOTOR STARTERS, THERMOSTATS, FIRE ALARM

ELECTRICAL RECEPTACLE WITHIN MECHANICAL SPACES,

PULL STATIONS, AND NURSE CALL DEVICES.

ELECTRICAL RECEPTACLE

TELEPHONE OUTLETS

COMPUTER OUTLETS

TELEVISION OUTLETS

WALL MOUNTED WIREMOLD.

ELECTRICAL AND ELEVATOR ROOMS.

SWITCHES, MAGNETIC STARTERS, CONTACTORS.

BED HEAD WALL LIGHTING FIXTURE - DIMENSION TO

WALL MOUNTED TELEPHONES AND PAY STATIONS (3'-6"

TOP OF FLUSH AND SURFACE MOUNTED ELECTRICAL

LIGHTING OR POWER PANELBOARDS AND TELEPHONE

TOP OF HIGHEST ELECTRICAL SAFETY DISCONNECT

TOP OF BACK-MOUNTED WALL EXIT FIXTURES (NOT

MOUNTED ABOVE DOORS)

BOTTOM OF UNIT.

AND HANDICAP LOCATIONS).

WALL SCONCES

SHELF MOUNTED T.V. IN BEDROOMS.

CABINETS.

CENTERED ABOVE

DOOR OR WINDOW

OPENING

10'-0"

FINISH CEILING

9" BELOW

WARNING AND SIGNALING FIXTURES/SIGNS.

WALL-MOUNTED CLOCKS, PROGRAM BELLS

BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED

(OR AS SHOWN ON ARCHITECTURAL DETAILS).

LIGHT HEADS (OR 1'-0" BELOW FINISHED CEILING TO

TOP OF UNIT).

96" (MAX)

80" (MIN)

WALL MOUNTED FIRE ALARM VISUAL DEVICES

5

F/A BOOSTER PANEL#12 20/1*1.0

Page 33: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

GENERAL DEMOLITION NOTES

1. EXISTING FIRE ALARM SYSTEM SHALL BE REMOVED - SEE SHEET NOTES.

2. REMOVE EXISTING FIRE ALARM SYSTEM COMPLETELY, INCLUDING FIRE ALARM CONTROLPANEL, CODED PULL STATIONS, BELLS, FIRE ALARM WIRING AND CONDUIT SYSTEM IN THEIRENTIRETY.

3. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL UNTIL THE NEW FIRE ALARMSYSTEM IS INSTALLED AND CERTIFIED.

4. DEMOLITION OF THE EXISTING FIRE ALARM SYSTEM IS NOT PERMITTED, UNTIL NEW FIRE ALARMSYSTEM IS INSTALLED.

5. VERIFY ALL CONDITIONS AT JOB SITE.

DEMOLITION KEY NOTES

1

EXISTING FIRE ALARM PULL STATION SHALL BE REMOVED.

EXISTING FIRE ALARM BELL SHALL BE REMOVED.

EXISTING FIRE ALARM CONTROL PANEL AND FUSED DISCONNECT SWITCH SHALL BEREMOVED.

EXISTING FIRE ALARM PANELS TO BE REMOVED.

2

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

MUSIC ROOM

B-3

MUSIC

EQUIPMENT

B-2

CREATIVE

ARTS

B-19

TEACHER

STORAGE

B-19B

PRACTICE

ROOM NO.1

B-4

PRACTICE

ROOM NO.2

B-5

MUSIC OFFICE

B-6

INSTRUMENTS

B-7

ENSEMBLE

PRACTICE

B-8

PA

SS

AG

E

B-7A

CORRIDOR

NO.2

B-1A

TRANSFORMER

& SWITCH

ROOM

B-16

PASSAGE

B-18

PUPIL EQUIP'T

B-19A

RECEIVING

AREA

B-17

CUSTOD'N

OFFICE

B-15

KITCHEN HELP

LOCKER RM.

B-14

JANITOR

SUPPLIES

B-13

HEUPS

LOCKER RM

B-12

STORAGE

B-11

B-12A

KITCHEN HELP

TOILET RM

B-14A

OFF. TOIL.

B-15B

COMPRESSOR

SPACE

B-17A

ELEV.

MACHINE

ROOM

B-10

UNEXCAVATED

CRAWL

SPACE 'C'

B-9B

UNEXCAVATED

METER ROOM

MR-5

UNEXCAVATED

CORRIDOR

NO.1

B-1

ELEV. NO.1

B-12B

CRAWL

SPACE 'A'

B-9

CRAWL

SPACE 'B'

B-9A

STAIR NO.3

B-22

STO.

B-20

UPPER PART

OF

MECHANICAL

EQUIPMENT

ROOM

MR-1

PIPE SPACE

CLO.

B-15C

CLOS.

B-3A

TEACHERS CLOS

B-19C

ELEV NO.2

BOILER ROOM

SB-01

STAIRWELL

S-00

FREIGHT

ELEVATOR

MACHINE ROOM

SB-03

FREIGHT

ELEVATOR

TELECOM ROOM

SB-02

3

1

3

2

1

2

UP

UP

UP

UP

UP

UP

UP

2

2 1

2

4

4

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

3/32" = 1'-0"

E-201

FIRE ALARM DEMOLITIONBASEMENT & SUB-BASEMENTFLOOR PLANS

SCALE: 3/32" = 1'-0"

FIRE ALARM DEMOLITION SUB-BASEMENT FLOOR PLAN

2

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 3/32" = 1'-0"

FIRE ALARM DEMOLITION BASEMENT FLOOR PLAN

1

SHEET 44 OF 61

Page 34: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

GENERAL DEMOLITION NOTES

1. EXISTING FIRE ALARM SYSTEM SHALL BE REMOVED - SEE SHEET NOTES.

2. REMOVE EXISTING FIRE ALARM SYSTEM COMPLETELY, INCLUDING FIRE ALARM CONTROLPANEL, CODED PULL STATIONS, BELLS, FIRE ALARM WIRING AND CONDUIT SYSTEM IN THEIRENTIRETY.

3. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL UNTIL THE NEW FIRE ALARMSYSTEM IS INSTALLED AND CERTIFIED.

4. DEMOLITION OF THE EXISTING FIRE ALARM SYSTEM IS NOT PERMITTED, UNTIL NEW FIRE ALARMSYSTEM IS INSTALLED.

5. VERIFY ALL CONDITIONS AT JOB SITE.

DEMOLITION KEY NOTES

1

EXISTING FIRE ALARM PULL STATION SHALL BE REMOVED.

EXISTING FIRE ALARM BELL SHALL BE REMOVED.2

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

UP

UPUP

GROUNDS

STORAGE

ROOM

102

KINDERGARTEN

NO.1

103

OUTDOOR

STORAGE

ROOM

104

KIND NO.1

TOILET

107

PASSAGE

NO.1

108

KIND NO.2

TOILET

112

KINDERGARTEN

NO.2

109

STORAGE

106

KIND NO.2

STORAGE

110

TUTORING

CLASSROOM

195

STAIR NO.3

198

CLOS.

103A

TEACH. CLOS.

103B

BOOK STO.

194

JAN. CL. NO.2

193

TOILET

192

DRY

STORAGE

187

ELEV NO.2

OFFICE

188

CANWASH

190

KINDERGARTEN

NO.3

113

KIND NO.3

TOIL.

117

KIND NO.3

STORAGE

114

KIND NO.1

COAT

ALCOVE

105

KIND NO.2

COAT

ALCOVE

111

TEACH. CLOS.

109A

STORAGE

195A

TEACH. CLOS.

195B

TEACH. CLOS.

113A

KIND NO.3

COAT

ALCOVE

115

BOYS TOILET

174

VEST.

172

CLOS.

173

VEST. 4

174A

JAN. CL. NO.1

176

GIRLS TOILET

166

VEST. 2

169VEST. 3

166A

PIPE SPACE

175

PIPE SPACE

173

GYMNASIUM

159

PIPE SPACE

170

PIPE SPACE

167

STORAGE

168

PL

AT

FO

RM

ST

OR

AG

E

17

9

PL

AT

FO

RM

WA

IT

IN

G

AR

EA

17

7

PASS. 6

163

LOBBY NO.1

164

LOWER PART OF

MECH EQUIP

ROOM

161

CLOS.

162

FIVE

180C

CHAIR

180D

STO.

180C

CLOS.

180B

CLOS.

180A

GYM

STORAGE

160

GYM OFFICE

157

TOILET

158

DRESSING

157A

TOILET

156

CLOS.

157B

BOYS

LOCKER RM

155

SHOWER

155B

GENERAL

STORAGE

154

GIRLS

LOCKER RM

149

TOWEL CLOS.

149F

TOWEL CLOS.

155C

BOYS TOILET

153

MEN FAC

152

PIPE SPACE

153A

PIPE SPACE

152A

SHOWER

149D

DRESS ALCOVE

149E

GIRLS

SHOWER

149A

TOIL.

150

TEAM

SUPPORTING

CL. RM.

145

CLOS.

145A

SHOWER

149C

D.R.

149B

GIRLS TOILET

147

WOMEN FAC

148

TEAM

PLANNING

NO.2

146

PIPE SPACE

147A

CLO.

146A

146B

PASSAGE

NO.5

151

COUNSELLOR

128

CONFERENCE

RM.

129

COUNSELLOR

#1

126

TOILET

131

OFFICE

125

PASSAGE NO.3

127

ASST

PRINCIPAL

121

PRINCIPALS

OFFICE

122

STAIR NO.1

196

TEAM

PLANNING #1

118

MIMEO &

SUPPLY

124

ELEV. NO.1

PASS. 2

120

T. CL.

118A

TOIL.

123

CLO.

126A

CLOS.

128A

CLOS.

122A

CLOS.

121A

CLOS.

122B

STORAGE

119

SUPPLY CLOS.

130C

HEALTH

ROOM

130

CLOS.

130B

DRESSING

130A

STAIR NO.2

197

CLASSROOM

NO.1

132

CLO.

132A

TEA. CLO.

132C

CLOS.

132B

MENS TOILET

183

WOMENS

TOILET

182

PIPE SPACE

182A

PIPE SPACE

183A

TEACHERS

DINING

184

CLOS.

184A

FREEZER

185C

FREEZER

185B

REFRIGERATOR

185A

PASSAGE 8

189

KITCHEN

185

PASSAGE

NO.7

181

AUDITORIUM -

CAFETERIA

180

PLATFORM

178

PASSAGE

186

PASS. 9

191

CLASSROOM

NO.2

133

CLASSROOM

NO.3

134

CLASSROOM

NO.5

144

CLASSROOM

NO.4

143

TEACH. CLOS.

133B

STO.

133A

TEACH. CLOS.

134B

STO.

134A

TEACH. CLOS.

143C

STO.

143A

CLOS.

143B

CLOS.

144B

TEACH. CLO.

144C

CLOS.

144D

CORRIDOR NO.1

101

CLASSROOM

NO.4

143

CLASSROOM

NO.3

134

1

2

12

2

2

2

1 2 12

1 2

2

1

1

2

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

CLASSROOM

CLASSROOM

STAIR NO.4

199

NURSERY

NO.2

141

NURSERY

NO.1

139

VESTIBULE

NO.1

138

TEACH. CLOS.

134B

STO.

134A

OU

TD

OO

R

ST

OR

AG

E

137

GE

NE

RA

L

ST

OR

AG

E

136

PASS. NO.4

135

STOR. NO.2

139B

STOR. NO.1

139A

TOIL. NO.1

139C

TOIL. NO.2

139D

TEACH. CLOS.

139F

GEN. STOR.

140

TEACH. CLOS.

141F

TOIL. NO.2

141D

TOIL. NO.1

141C

STOR. NO.2

141B

STOR. NO.1

141A

COAT ALCOVE

139E

COAT ALCOVE

141E

TEACH. CLOS.

143C

STO.

143A

CLASSROOM

NO.4

143

CLASSROOM

NO.3

134

12

3/32" = 1'-0"

E-202

FIRE ALARM DEMOLITIONFIRST FLOOR PLAN

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 3/32" = 1'-0"

FIRE ALARM DEMOLITION FIRST FLOOR PLAN

1

SHEET 45 OF 61

Page 35: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

GENERAL DEMOLITION NOTES

1. EXISTING FIRE ALARM SYSTEM SHALL BE REMOVED - SEE SHEET NOTES.

2. REMOVE EXISTING FIRE ALARM SYSTEM COMPLETELY, INCLUDING FIRE ALARM CONTROLPANEL, CODED PULL STATIONS, BELLS, FIRE ALARM WIRING AND CONDUIT SYSTEM IN THEIRENTIRETY.

3. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL UNTIL THE NEW FIRE ALARMSYSTEM IS INSTALLED AND CERTIFIED.

4. DEMOLITION OF THE EXISTING FIRE ALARM SYSTEM IS NOT PERMITTED, UNTIL NEW FIRE ALARMSYSTEM IS INSTALLED.

5. VERIFY ALL CONDITIONS AT JOB SITE.

DEMOLITION KEY NOTES

1

EXISTING FIRE ALARM PULL STATION SHALL BE REMOVED.

EXISTING FIRE ALARM BELL SHALL BE REMOVED.2

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

UPUP

CLASSROOM

NO.24

237

TOILET

237B

CLOS.

237A

TEACH. CLOS.

237D

STORAGE

243

CLOS.

202A

SPEECH

CORRECTION

202

TEACH. CLOS.

202B

CLASSROOM

NO.6

203

CLOS.

203A

TEACH. CLOS.

203B

SHOWER

237C

TEAM

SUPPORTING

NO.2

204

TEACH. CLOS.

204A

CLASSROOM

NO.7

205

TEACH. CLOS.

205A

CLASSROOM

NO.8

206

CLOS.

206A

TEACH. CLOS.

206B

CLASSROOM

NO.22

235

CLASSROOM

NO.23

236

STAIR NO.3

240

CLOS.

235A

TEACH. CLO.

235B

TEACH. CLO.

236A

CORRIDOR NO.1

201

CLASSROOM

NO.19

219

CLOS.

219B

CLOS.

219A

CLASSROOM

NO.18

218

TEACH. CLOS.

218B

CLOS.

218A

CLASSROOM

NO.15

213

TEACH. CLOS.

213B

CLO.

213A

CLASSROOM

NO.14

212

TEACH. CLO.

212A

UPPER PART

OF

AUDITORIUM-CAFETERIA

UPPER PART

OF

GYMNASIUM

MECH. EQUIP.

ROOM NO.2

228

MECH.

EQUIPMENT

ROOM NO.1

227

FAN ROOM

226

MATERIALS

PRODUCTION

ROOM

223

AUDIO-VISUAL

221

READING

ROOM

224

GIRLS TOILET

ROOM

229

224A

TEAM

SUPPORTING

NO.3

224B

CLOS.

231C

PIPE SPACE

230

PIP

E S

PA

CE

229A

JA

N. C

LO

S.

231B

PIPE SPACE

233

PASS.

231A

Room

231D

CLASSROOM

NO.21

234

234A

TEACH. CLOS.

234B

CLASSROOM

NO.9

207

TEACH. CLO.

207C

STO. CLO.

207B

STO. RM.

207A

STO. RM.

208A

STAIR NO.1

238

CLASSROOM

NO.10

208

ELEVATOR

TEACH. CLOS.

208B

CLASSROOM

NO.11

209

CLASSROOM

NO.12

210

STAIR NO.2

239

STO. RM.

210A

STO. RM.

211A

CLASSROOM

NO.13

211

STO. CLO.

211B

TEACH. CLO.

211C

TEACH. CLOS.

210B

CLOS.

210C

TEACH. CLOS.

209A

CLASSROOM

NO.18

218

CLASSROOM

NO.15

213

12

1 2 12

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

TEACH. CLOS.

218B

CLOS.

218A

STAIR NO.4

241

STORAGE

242

CLASSROOM

NO.17

217

TOILET

217A

SHOWER

217B

TEACH. CLOS.

217C

TEACHERS

WORKROOM

216

TEACH. CLOS.

216B

CLOS.

216A

CLASSROOM

NO.16

215

TOILET

215A

SHOWER

215B

TOILET

215C

TEAM

PLANNING RM

NO.3

214

214B

CLOS.

214A

CLO.

213A

CLASSROOM

NO.18

218

CLASSROOM

NO.15

213

12

3/32" = 1'-0"

E-203

FIRE ALARM DEMOLITIONSECOND FLOOR PLAN

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 3/32" = 1'-0"

FIRE ALARM DEMOLITION SECOND FLOOR PLAN

1

SHEET 46 OF 61

Page 36: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

MUSIC ROOM

B-3

MUSIC

EQUIPMENT

B-2

CREATIVE

ARTS

B-19

TEACHER

STORAGE

B-19B

PRACTICE

ROOM NO.1

B-4

PRACTICE

ROOM NO.2

B-5

MUSIC OFFICE

B-6

INSTRUMENTS

B-7

ENSEMBLE

PRACTICE

B-8

PA

SS

AG

E

B-7A

CORRIDOR

NO.2

B-1A

TRANSFORMER

& SWITCH

ROOM

B-16

PASSAGE

B-18

PUPIL EQUIP'T

B-19A

RECEIVING

AREA

B-17

BUILDING ENGINEER'S

OFFICE

B-15

KITCHEN HELP

LOCKER RM.

B-14

JANITOR

SUPPLIES

B-13

HEUPS

LOCKER RM

B-12

STORAGE

B-11

B-12A

KITCHEN HELP

TOILET RM

B-14A

OFF. TOIL.

B-15B

COMPRESSOR

SPACE

B-17A

ELEV.

MACHINE

ROOM

B-10

UNEXCAVATED

CRAWL

SPACE 'C'

B-9B

UNEXCAVATED

METER ROOM

MR-5

UNEXCAVATED

CORRIDOR

NO.1

B-1

ELEV. NO.1

B-12B

CRAWL

SPACE 'A'

B-9

CRAWL

SPACE 'B'

B-9A

STAIR NO.3

B-22

STO.

B-20

UPPER PART

OF

MECHANICAL

EQUIPMENT

ROOM

MR-1

PIPE SPACE

CLO.

B-15C

CLOS.

B-3A

TEACHERS CLOS

B-19C

ELEV NO.2

BOILER ROOM

SB-01

STAIRWELL

S-00

FREIGHT

ELEVATOR

MACHINE ROOM

SB-03

FREIGHT

ELEVATOR

TELECOM ROOM

SB-02

UP

UP

UP

UP

UP

UP

UP

HD

WP

HD

WP

HD

WP

HD

WP

HD

WP

HD

WP

HD

WP

HD

WP

HD

WP

HD

WP

SD SD SD SD SD SD

SD

SD

SD

SD

SD

SD

HD HD

HD HD

SD

SD

HD

WP

HD

WP

HD

WP

HD

SD

SD

SD

FA

CP

HD

HD

SD

SD

SD

SDSD

FIRE ALARM GENERAL NOTES:

A. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, REFER TO DRAWING E001.

D. ALL NEW FIRE ALARM DEVICES SHALL BE INSTALLED, TESTED AND ACCEPTED PRIOR TO OCCUPANCY. THE LOCAL AUTHORITY HAVING JURISDICTION SHALLPERFORM ALL FINAL ACCEPTANCES.

E. ALL FIRE ALARM POINTS MUST BE TRANSMITTED TO THE CENTRAL MONITORING STATION. EACH FIRE ALARM POINT MUST SEND THE CENTRAL MONITORINGSTATION A RESTORE CODE FOR EACH POINT.

F. ALL DEVICES CONTAINING END OF LINE RESISTORS SHALL BE LABELED 'EOL'.

G. PROVIDE SIGNAGE AT EACH MANUAL PULL STATION, SIGN MUST BE MOUNTED IMMEDIATELY ADJACENT TO THE MANUAL PULL STATION. THE SIGN SHALLREAD "INCASE OF FIRE: SOUND ALARM AND CALL THE FIRE DEPARTMENT".

H. ALL FIRE ALARM WIRING SHALL BE IN METAL CONDUIT. PROVIDE GALVANIZED RIGID STEEL CONDUIT FOR ALL RISER CONDUITS AND ALL CONDUITS INMECHANICAL, ELECTRICAL AND BOILER ROOMS. PAINT ALL JUNCTION BOXES WITH RED COLOR PAINT AND LABEL AS "FIRE ALARM".

J. ELECTRICAL CONTRACTOR SHALL USE CONDUIT SEALING FITTING WITH APPROVED SEALING COMPOUND ON ALL CONDUITS PASSING FROM INTERIOR TOEXTERIOR OF A BUILDING AND BETWEEN AREAS OF DIFFERENT TEMPERATURES. SEAL ALL CONDUIT PENETRATIONS THOUGH RATED WALLS AND FLOORS TOMAINTAIN FIRE RATING INTEGRITY.

K. WIRING TO BE RUN IN EMT CONDUIT AND COMPLY WITH NEC ARTICLE 760. CONDUIT TO RUN EXPOSED, EXCEPT ABOVE SUSPENDED CEILING (WHEREAPPLICABLE). MINIMUM CONDUIT SIZE TO BE 3/4"C. ALL WIRING TO BE COPPER. ALL RISER CONDUIT AND CONDUIT IN MECHANICAL, ELECTRICAL, ANDBOILER ROOM SHALL BE RIGID STEEL GALVANIZED CONDUIT. ALL CONDUIT AND WIRING ROUTING BETWEEN FLOORS TO BE ROUTED IN RIGID CONDUITWITH SEAL FITTING BELOW THE CEILING BEFORE PENETRATING THE FLOOR SLAB. TYPE 'MC' CABLE IS NOT ACCEPTABLE.

L. HVAC UNIT/AIR HANDILING EQUIPMENT ITEMS:1. PROVIDE ADDRESSABLE DUCT DETECTORS AND PERFORM HVAC UNIT SHUT DOWN LOCALLY.2. PROVIDE HVAC UNIT SHUTDOWN UPON FIRE ALARM SYSTEM ALARM CONDITIONS VIA CONTROL MODULES. WIRE OUTPUTS ON CONTROL MODULE TO

HVAC UNIT STARTER CIRCUIT.3. FIRE ALARM CONTROL PANEL IS TO HAVE A FIREMANS "SHUTOFF" SWITCH FOR EACH HVAC UNIT IN THE BUILDING AND A SINGLE SWITCH TO TURN OFF

ALL HVAC UNITS. SWITCHES TO BE CONNECTED TO FIRE ALARM CONTROL PANEL. CONTROL PANEL TO PERFORM HVAC UNIT SHUTDOWN VIAADDRESSABLE CONTROL MODULE OUTPUT RELAYS LOCATED AT EACH HVAC UNIT.

M. THE QUANTITY OF FIRE ALARM BOOSTER PANELS SHOWN ON THESE DRAWINGS AND THE RISER DIAGRAM ARE FOR SCHEMATIC PURPOSES ONLY. THECONTRACTOR AND FIRE ALARM VENDOR SHALL DETERMINE THE EXACT QUANTITY OF BOOSTER PANELS REQUIRED BASED ON THE MANUFACTURER'SPANEL FUNCTION AND SPECIFICATIONS. THE CONTRACTOR SHALL PROVIDE THE QUANTITY OF BOOSTER PANELS REQUIRED TO SUPPORT THE ENTIRE FIREALARM SYSTEM BASED ON THE QUANTITY OF DEVICES SHOWN ON PLAN, TOTAL POWER NEEDED TO SUPPORT THE DEVICES, VOLTAGE DROPCALCULATIONS FOR EACH CIRCUIT, BATTERY CALCULATIONS, SIZE OF BUILDING, ETC. THE CONTRACTOR SHALL PROVIDE 120V, 20AMP CIRCUITS FOR ALLBOOSTER PANELS THAT ARE INSTALLED BASED ON THE FIRE ALARM VENDOR'S CALCULATIONS AT NO ADDITIONAL COST TO SDP.

1 PROVIDE KEYED RESET PULL STATION WITH BATTERY OPERATED LOCAL ALARM BY STI (ORAPPROVED EQUAL) AND IMPACT RESISTANCE PROTECTIVE COVER

PROVIDE A DUCT MOUNTED SMOKE DETECTOR IN RETURN DUCT AND SUPPLY DUCT OF HVAC UNIT (OVER 2000CFM). EACH DUCT MOUNTED SMOKE DETECTOR SHALL HAVE REMOTE TEST SWITCH AND LED ALARMINDICATORS. WHERE THE CEILING HEIGHT IS HIGHER THAN 10', THE REMOTE TEST SWITCH AND LED ALARMINDICATORS SHALL BE WALL MOUNTED AT 48" A.F.F. ADJACENT HVAC UNIT. PROVIDE AND CONNECT ACONTROL MODULE AT EACH HVAC UNIT EXISTING MOTOR STARTER TO SHUTDOWN HVAC UNIT, FIELD VERIFYEXACT LOCATION. DEVICES TO BE LOCATED WHERE ACCESSIBLE BY QUALIFIED PERSONNEL ONLY. PROVIDE (1)REMOTE TEST STATIONS FOR EACH DUCT MOUNTED SMOKE DETECTORS.

FIELD COORDINATE EXACT LOCATIONS OF HEAT DETECTORS. DEVICES TO BE MOUNTED BELOW ALL DUCTWORK,PIPING, AND CONDUIT. DEVICES SHALL BE CLEAR OF ANY OBSTRUCTIONS. DEVICES SHALL BE MOUNTED TOUNISTRUT FRAMING SECURELY FASTENED TO CEILING.

PROVIDE WEATHER PROOF CONVENTIONAL TYPE FIRE ALARM DEVICES WITHIN BOILER ROOM ANDMECHANICAL SPACES. PROVIDE A REMOTE RELAY MODULE FOR ALL CONVENTIONAL TYPE DEVICES WITHINTHE BOILER ROOM AND MECHANICAL SPACES.

NEW FIRE ALARM CONTROL PANEL. PROVIDE 120V, 20AMP EMERGENCY CIRCUIT FROM PANELBOARD "EM" -2#12 + 1#12 GND IN 3/4" CONDUIT.

EXISTING MAIN TELEPHONE DEMARCATION. INTERCONNECT NEW (2) TELEPHONE LINES OR CAT6 CABLESFOR FIRE ALARM SYSTEM.

PROVIDE (5) CONTROL MODULES IN ELEVATOR MACHINE ROOM FOR ELEVATOR RECALL

PROVIDE A SMOKE DETECTOR AT BOTTOM OF ELEVATOR SHAFT.

SMOKE DETECTOR TO INITIATE ELEVATOR PRIMARY AND ALTERNATE RECALL.

PROVIDE FACP WITH DIGITAL ALARM COMMUNICATOR TRANSMITTER (DACT) FOR OFF-PREMISES MONITORINGOF THE FACP ALARM POINTS. PROVIDE (2) CAT 6 OR (2) COPPER LAND LINE CABLES FROM THE FACP TO THETELEPHONE DEMARCATION STATION (MAIN TELEPHONE SERVICE BOX).

PROVIDE A NEW 120V, 20AMP EMERGENCY POWER CIRCUIT FROM PANELBOARD "EM" IDENTIFIED FOR FACPSYSTEM PRINTER RECEPTACLE. PROVIDE CIRCUIT EM-7 WITH 2#12 +1#12 GND IN 3/4" CONDUIT.

DD

DD

110cd

110cd

110cd

FIRE ALARM SHEET NOTES

1

1

1

WP

WP

WP

WP

2

2

3

4

3 4 3 4

3 4 3 4

1

3 4

WP

5

10

6

6

7

7

ELEV.CONTROLPANEL

C

3 4

3 4 3 4

3 4

3 4

3 4

3 4

3 4 3 4 3 4

7

ELEV.CONTROLPANEL

C

SD

8

8

SD

8

9

9

9

10

5

11

11

PANEL"EM"

8

FAAP

1

15cd

15cd

15cd 15cd 15cd

15cd

15cd

15cd15cd

15cd 15cd 15cd 15cd

15cd

15cd

15cd 15cd

15cd

15cd

15cd

15cd

15cd

75cd

75cd 75cd

15cd

F/A BOOSTERPANELCIRC. #EM-13

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

HD

WP

HD

WP

3 4

3 4

3/32" = 1'-0"

E-204

FIRE ALARM NEW WORKBASEMENT & SUB-BASEMENTFLOOR PLANS

SCALE: 3/32" = 1'-0"

FIRE ALARM NEW WORK SUB-BASEMENT FLOOR PLAN

2

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 3/32" = 1'-0"

FIRE ALARM NEW WORK BASEMENT FLOOR PLAN

1

SHEET 47 OF 61

Page 37: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

UP

UPUP

GROUNDS

STORAGE

ROOM

102

KINDERGARTEN

NO.1

103

OUTDOOR

STORAGE

ROOM

104

KIND NO.1

TOILET

107

PASSAGE

NO.1

108

KIND NO.2

TOILET

112

KINDERGARTEN

NO.2

109

STORAGE

106

KIND NO.2

STORAGE

110

TUTORING

CLASSROOM

195

STAIR NO.3

198

CLOS.

103A

TEACH. CLOS.

103B

BOOK STO.

194

JAN. CL. NO.2

193

TOILET

192

DRY

STORAGE

187

ELEV NO.2

OFFICE

188

CANWASH

190

KINDERGARTEN

NO.3

113

KIND NO.3

TOIL.

117

KIND NO.3

STORAGE

114

KIND NO.1

COAT

ALCOVE

105

KIND NO.2

COAT

ALCOVE

111

TEACH. CLOS.

109A

STORAGE

195A

TEACH. CLOS.

195B

TEACH. CLOS.

113A

KIND NO.3

COAT

ALCOVE

115

BOYS TOILET

174

VEST.

172

CLOS.

173

VEST. 4

174A

JAN. CL. NO.1

176

GIRLS TOILET

166

VEST. 2

169VEST. 3

166A

PIPE SPACE

175

PIPE SPACE

173

GYMNASIUM

159

PIPE SPACE

170

PIPE SPACE

167

STORAGE

168

PL

AT

FO

RM

ST

OR

AG

E

17

9

PL

AT

FO

RM

WA

IT

IN

G

AR

EA

17

7

PASS. 6

163

LOBBY NO.1

164

LOWER PART OF

MECH EQUIP

ROOM

161

CLOS.

162

FIVE

180C

CHAIR

180D

STO.

180C

CLOS.

180B

CLOS.

180A

GYM

STORAGE

160

GYM OFFICE

157

TOILET

158

DRESSING

157A

TOILET

156

CLOS.

157B

BOYS

LOCKER RM

155

SHOWER

155B

GENERAL

STORAGE

154

GIRLS

LOCKER RM

149

TOWEL CLOS.

149F

TOWEL CLOS.

155C

BOYS TOILET

153

MEN FAC

152

PIPE SPACE

153A

PIPE SPACE

152A

SHOWER

149D

DRESS ALCOVE

149E

GIRLS

SHOWER

149A

TOIL.

150

TEAM

SUPPORTING

CL. RM.

145

CLOS.

145A

SHOWER

149C

D.R.

149B

GIRLS TOILET

147

WOMEN FAC

148

TEAM

PLANNING

NO.2

146

PIPE SPACE

147A

CLO.

146A

146B

PASSAGE

NO.5

151

COUNSELLOR

128

CONFERENCE

RM.

129

COUNSELLOR

#1

126

TOILET

131

OFFICE

125

PASSAGE NO.3

127

ASST

PRINCIPAL

121

PRINCIPALS

OFFICE

122

STAIR NO.1

196

TEAM

PLANNING #1

118

MIMEO &

SUPPLY

124

ELEV. NO.1

PASS. 2

120

T. CL.

118A

TOIL.

123

CLO.

126A

CLOS.

128A

CLOS.

122A

CLOS.

121A

CLOS.

122B

STORAGE

119

SUPPLY CLOS.

130C

HEALTH

ROOM

130

CLOS.

130B

DRESSING

130A

STAIR NO.2

197

CLASSROOM

NO.1

132

CLO.

132A

TEA. CLO.

132C

CLOS.

132B

MENS TOILET

183

WOMENS

TOILET

182

PIPE SPACE

182A

PIPE SPACE

183A

TEACHERS

DINING

184

CLOS.

184A

FREEZER

185C

FREEZER

185B

REFRIGERATOR

185A

PASSAGE 8

189

KITCHEN

185

PASSAGE

NO.7

181

AUDITORIUM -

CAFETERIA

180

PLATFORM

178

PASSAGE

186

PASS. 9

191

CLASSROOM

NO.2

133

CLASSROOM

NO.3

134

CLASSROOM

NO.5

144

CLASSROOM

NO.4

143

TEACH. CLOS.

133B

STO.

133A

TEACH. CLOS.

134B

STO.

134A

TEACH. CLOS.

143C

STO.

143A

CLOS.

143B

CLOS.

144B

TEACH. CLO.

144C

CLOS.

144D

CORRIDOR NO.1

101

CLASSROOM

NO.4

143

CLASSROOM

NO.3

134

SD SD SD SD SD SD SD SD SD SD

SD

SD

SD

SD

HD

HD

HD

SD

SD

SD

SD

SD

F

SD

F

FAAP

FAAPF

HD

FIRE ALARM GENERAL NOTES:

A. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, REFER TO DRAWING E001.

D. ALL NEW FIRE ALARM DEVICES SHALL BE INSTALLED, TESTED AND ACCEPTED PRIOR TO OCCUPANCY. THE LOCAL AUTHORITY HAVING JURISDICTION SHALLPERFORM ALL FINAL ACCEPTANCES.

E. ALL FIRE ALARM POINTS MUST BE TRANSMITTED TO THE CENTRAL MONITORING STATION. EACH FIRE ALARM POINT MUST SEND THE CENTRAL MONITORINGSTATION A RESTORE CODE FOR EACH POINT.

F. ALL DEVICES CONTAINING END OF LINE RESISTORS SHALL BE LABELED 'EOL'.

G. PROVIDE SIGNAGE AT EACH MANUAL PULL STATION, SIGN MUST BE MOUNTED IMMEDIATELY ADJACENT TO THE MANUAL PULL STATION. THE SIGN SHALLREAD "INCASE OF FIRE: SOUND ALARM AND CALL THE FIRE DEPARTMENT".

H. ALL FIRE ALARM WIRING SHALL BE IN METAL CONDUIT. PROVIDE GALVANIZED RIGID STEEL CONDUIT FOR ALL RISER CONDUITS AND ALL CONDUITS INMECHANICAL, ELECTRICAL AND BOILER ROOMS. PAINT ALL JUNCTION BOXES WITH RED COLOR PAINT AND LABEL AS "FIRE ALARM".

J. ELECTRICAL CONTRACTOR SHALL USE CONDUIT SEALING FITTING WITH APPROVED SEALING COMPOUND ON ALL CONDUITS PASSING FROM INTERIOR TOEXTERIOR OF A BUILDING AND BETWEEN AREAS OF DIFFERENT TEMPERATURES. SEAL ALL CONDUIT PENETRATIONS THOUGH RATED WALLS AND FLOORS TOMAINTAIN FIRE RATING INTEGRITY.

K. WIRING TO BE RUN IN EMT CONDUIT AND COMPLY WITH NEC ARTICLE 760. CONDUIT TO RUN EXPOSED, EXCEPT ABOVE SUSPENDED CEILING (WHEREAPPLICABLE). MINIMUM CONDUIT SIZE TO BE 3/4"C. ALL WIRING TO BE COPPER. ALL RISER CONDUIT AND CONDUIT IN MECHANICAL, ELECTRICAL, ANDBOILER ROOM SHALL BE RIGID STEEL GALVANIZED CONDUIT. ALL CONDUIT AND WIRING ROUTING BETWEEN FLOORS TO BE ROUTED IN RIGID CONDUITWITH SEAL FITTING BELOW THE CEILING BEFORE PENETRATING THE FLOOR SLAB. TYPE 'MC' CABLE IS NOT ACCEPTABLE.

L. HVAC UNIT/AIR HANDILING EQUIPMENT ITEMS:1. PROVIDE ADDRESSABLE DUCT DETECTORS AND PERFORM HVAC UNIT SHUT DOWN LOCALLY.2. PROVIDE HVAC UNIT SHUTDOWN UPON FIRE ALARM SYSTEM ALARM CONDITIONS VIA CONTROL MODULES. WIRE OUTPUTS ON CONTROL MODULE TO

HVAC UNIT STARTER CIRCUIT.3. FIRE ALARM CONTROL PANEL IS TO HAVE A FIREMANS "SHUTOFF" SWITCH FOR EACH HVAC UNIT IN THE BUILDING AND A SINGLE SWITCH TO TURN OFF

ALL HVAC UNITS. SWITCHES TO BE CONNECTED TO FIRE ALARM CONTROL PANEL. CONTROL PANEL TO PERFORM HVAC UNIT SHUTDOWN VIAADDRESSABLE CONTROL MODULE OUTPUT RELAYS LOCATED AT EACH HVAC UNIT.

M. THE QUANTITY OF FIRE ALARM BOOSTER PANELS SHOWN ON THESE DRAWINGS AND THE RISER DIAGRAM ARE FOR SCHEMATIC PURPOSES ONLY. THECONTRACTOR AND FIRE ALARM VENDOR SHALL DETERMINE THE EXACT QUANTITY OF BOOSTER PANELS REQUIRED BASED ON THE MANUFACTURER'SPANEL FUNCTION AND SPECIFICATIONS. THE CONTRACTOR SHALL PROVIDE THE QUANTITY OF BOOSTER PANELS REQUIRED TO SUPPORT THE ENTIRE FIREALARM SYSTEM BASED ON THE QUANTITY OF DEVICES SHOWN ON PLAN, TOTAL POWER NEEDED TO SUPPORT THE DEVICES, VOLTAGE DROPCALCULATIONS FOR EACH CIRCUIT, BATTERY CALCULATIONS, SIZE OF BUILDING, ETC. THE CONTRACTOR SHALL PROVIDE 120V, 20AMP CIRCUITS FOR ALLBOOSTER PANELS THAT ARE INSTALLED BASED ON THE FIRE ALARM VENDOR'S CALCULATIONS AT NO ADDITIONAL COST TO SDP.

1 PROVIDE KEYED RESET PULL STATION WITH BATTERY OPERATED LOCAL ALARM BY STI (ORAPPROVED EQUAL) AND IMPACT RESISTANCE PROTECTIVE COVER

SMOKE DETECTOR TO INITIATE ELEVATOR PRIMARY AND ALTERNATE RECALL.

FIRE ALARM SHEET NOTES

2

3

1

1

1

3

3

PROVIDE PROTECTIVE WIREGUARD FOR ALL FIRE ALARM DEVICES WITHIN GYM.

WG

110cd 110cd

WG

110cd

WG

110cd

WG2

2

2

2

2

2

2

SD

F/ABOOSTERPANEL#EM-9

NEW FIRE ALARM REMOTE BOOSTER POWER SUPPLY. PROVIDE 120V, 20AMP EMERGENCY POWER CIRCUITFROM PANELBOARD "EM" IDENTIFIED FOR FIRE ALARM REMOTE BOOSTER POWER SUPPLIES -CIRCUIT #EM-9.4

4

5NOT USED

SD

PROVIDE A SMOKE DETECTOR ON THE TOP OF ELEVATOR SHAFT.6

6

DD

3

DD

PROVIDE A DUCT MOUNTED SMOKE DETECTOR IN RETURN DUCT AND SUPPLY DUCT OF HVAC UNIT (OVER 2000CFM). EACH DUCT MOUNTED SMOKE DETECTOR SHALL HAVE REMOTE TEST SWITCH AND LED ALARMINDICATORS. WHERE THE CEILING HEIGHT IS HIGHER THAN 10', THE REMOTE TEST SWITCH AND LED ALARMINDICATORS SHALL BE WALL MOUNTED AT 48" A.F.F. ADJACENT HVAC UNIT. PROVIDE AND CONNECT ACONTROL MODULE AT EACH HVAC UNIT EXISTING MOTOR STARTER TO SHUTDOWN HVAC UNIT, FIELD VERIFYEXACT LOCATION. DEVICES TO BE LOCATED WHERE ACCESSIBLE BY QUALIFIED PERSONNEL ONLY. PROVIDE (1)REMOTE TEST STATIONS FOR EACH DUCT MOUNTED SMOKE DETECTORS.

7

7

15cd

15cd

15cd

15cd 15cd

15cd

15cd

15cd

15cd 15cd 15cd

15cd

15cd

15cd

15cd 15cd

15cd

15cd

15cd

15cd15cd

15cd

15cd

15cd

15cd

15cd

15cd 15cd

15cd

15cd15cd

15cd

15cd

15cd

75cd75cd75cd75cd75cd

15cd15cd

15cd

15cd

15cd

15cd

15cd

15cd

75cd

75cd

75cd

15cd

15cd

110cd

110cd

110cd

15cd

75cd75cd

15cd

75cd75cd

75cd

75cd

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

STAIR NO.4

199

NURSERY

NO.2

141

NURSERY

NO.1

139

VESTIBULE

NO.1

138

STO.

134A

OU

TD

OO

R

ST

OR

AG

E

137

GE

NE

RA

L

ST

OR

AG

E

136

PASS. NO.4

135

STOR. NO.2

139B

STOR. NO.1

139A

TOIL. NO.1

139C

TOIL. NO.2

139D

TEACH. CLOS.

139F

GEN. STOR.

140

TEACH. CLOS.

141F

TOIL. NO.2

141D

TOIL. NO.1

141C

STOR. NO.2

141B

STOR. NO.1

141A

COAT ALCOVE

139E

COAT ALCOVE

141E

TEACH. CLOS.

143C

STO.

143A

CLASSROOM

NO.4

143

CLASSROOM

NO.3

134

SD

SD

15cd

15cd

15cd

15cd

15cd

15cd

75cd

75cd

75cd

3/32" = 1'-0"

E-205

FIRE ALARM DEMOLITIONFIRST FLOOR PLAN

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 3/32" = 1'-0"

FIRE ALARM NEW WORK FIRST FLOOR PLAN

1

SHEET 48 OF 61

Page 38: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

UPUP

CLASSROOM

NO.24

237

TOILET

237B

CLOS.

237A

TEACH. CLOS.

237D

STORAGE

243

CLOS.

202A

SPEECH

CORRECTION

202

TEACH. CLOS.

202B

CLASSROOM

NO.6

203

CLOS.

203A

TEACH. CLOS.

203B

SHOWER

237C

TEAM

SUPPORTING

NO.2

204

TEACH. CLOS.

204A

CLASSROOM

NO.7

205

TEACH. CLOS.

205A

CLASSROOM

NO.8

206

CLOS.

206A

TEACH. CLOS.

206B

CLASSROOM

NO.22

235

CLASSROOM

NO.23

236

STAIR NO.3

240

CLOS.

235A

TEACH. CLO.

235B

TEACH. CLO.

236A

CORRIDOR NO.1

201

CLASSROOM

NO.19

219

CLOS.

219B

CLOS.

219A

CLASSROOM

NO.18

218

CLASSROOM

NO.15

213

TEACH. CLOS.

213B

CLASSROOM

NO.14

212

TEACH. CLO.

212A

UPPER PART

OF

AUDITORIUM-CAFETERIA

UPPER PART

OF

GYMNASIUM

MECH. EQUIP.

ROOM NO.2

228

MECH.

EQUIPMENT

ROOM NO.1

227

FAN ROOM

226

MATERIALS

PRODUCTION

ROOM

223

AUDIO-VISUAL

221

READING

ROOM

224

GIRLS TOILET

ROOM

229

224A

TEAM

SUPPORTING

NO.3

224B

CLOS.

231C

PIPE SPACE

230

PIP

E S

PA

CE

229A

JA

N. C

LO

S.

231B

PIPE SPACE

233

PASS.

231A

Room

231D

CLASSROOM

NO.21

234

234A

TEACH. CLOS.

234B

CLASSROOM

NO.9

207

TEACH. CLO.

207C

STO. CLO.

207B

STO. RM.

207A

STO. RM.

208A

STAIR NO.1

238

CLASSROOM

NO.10

208

ELEVATOR

TEACH. CLOS.

208B

CLASSROOM

NO.11

209

CLASSROOM

NO.12

210

STAIR NO.2

239

STO. RM.

210A

STO. RM.

211A

CLASSROOM

NO.13

211

STO. CLO.

211B

TEACH. CLO.

211C

TEACH. CLOS.

210B

CLOS.

210C

TEACH. CLOS.

209A

CLASSROOM

CLASSROOM

SD SD SD SD SD SDSD

SD SD SD

SD

SD

HD

SD

HD

HD

HD

FIRE ALARM GENERAL NOTES:

A. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, REFER TO DRAWING E001.

D. ALL NEW FIRE ALARM DEVICES SHALL BE INSTALLED, TESTED AND ACCEPTED PRIOR TO OCCUPANCY. THE LOCAL AUTHORITY HAVING JURISDICTION SHALLPERFORM ALL FINAL ACCEPTANCES.

E. ALL FIRE ALARM POINTS MUST BE TRANSMITTED TO THE CENTRAL MONITORING STATION. EACH FIRE ALARM POINT MUST SEND THE CENTRAL MONITORINGSTATION A RESTORE CODE FOR EACH POINT.

F. ALL DEVICES CONTAINING END OF LINE RESISTORS SHALL BE LABELED 'EOL'.

G. PROVIDE SIGNAGE AT EACH MANUAL PULL STATION, SIGN MUST BE MOUNTED IMMEDIATELY ADJACENT TO THE MANUAL PULL STATION. THE SIGN SHALLREAD "INCASE OF FIRE: SOUND ALARM AND CALL THE FIRE DEPARTMENT".

H. ALL FIRE ALARM WIRING SHALL BE IN METAL CONDUIT. PROVIDE GALVANIZED RIGID STEEL CONDUIT FOR ALL RISER CONDUITS AND ALL CONDUITS INMECHANICAL, ELECTRICAL AND BOILER ROOMS. PAINT ALL JUNCTION BOXES WITH RED COLOR PAINT AND LABEL AS "FIRE ALARM".

J. ELECTRICAL CONTRACTOR SHALL USE CONDUIT SEALING FITTING WITH APPROVED SEALING COMPOUND ON ALL CONDUITS PASSING FROM INTERIOR TOEXTERIOR OF A BUILDING AND BETWEEN AREAS OF DIFFERENT TEMPERATURES. SEAL ALL CONDUIT PENETRATIONS THOUGH RATED WALLS AND FLOORS TOMAINTAIN FIRE RATING INTEGRITY.

K. WIRING TO BE RUN IN EMT CONDUIT AND COMPLY WITH NEC ARTICLE 760. CONDUIT TO RUN EXPOSED, EXCEPT ABOVE SUSPENDED CEILING (WHEREAPPLICABLE). MINIMUM CONDUIT SIZE TO BE 3/4"C. ALL WIRING TO BE COPPER. ALL RISER CONDUIT AND CONDUIT IN MECHANICAL, ELECTRICAL, ANDBOILER ROOM SHALL BE RIGID STEEL GALVANIZED CONDUIT. ALL CONDUIT AND WIRING ROUTING BETWEEN FLOORS TO BE ROUTED IN RIGID CONDUITWITH SEAL FITTING BELOW THE CEILING BEFORE PENETRATING THE FLOOR SLAB. TYPE 'MC' CABLE IS NOT ACCEPTABLE.

L. HVAC UNIT/AIR HANDILING EQUIPMENT ITEMS:1. PROVIDE ADDRESSABLE DUCT DETECTORS AND PERFORM HVAC UNIT SHUT DOWN LOCALLY.2. PROVIDE HVAC UNIT SHUTDOWN UPON FIRE ALARM SYSTEM ALARM CONDITIONS VIA CONTROL MODULES. WIRE OUTPUTS ON CONTROL MODULE TO

HVAC UNIT STARTER CIRCUIT.3. FIRE ALARM CONTROL PANEL IS TO HAVE A FIREMANS "SHUTOFF" SWITCH FOR EACH HVAC UNIT IN THE BUILDING AND A SINGLE SWITCH TO TURN OFF

ALL HVAC UNITS. SWITCHES TO BE CONNECTED TO FIRE ALARM CONTROL PANEL. CONTROL PANEL TO PERFORM HVAC UNIT SHUTDOWN VIAADDRESSABLE CONTROL MODULE OUTPUT RELAYS LOCATED AT EACH HVAC UNIT.

M. THE QUANTITY OF FIRE ALARM BOOSTER PANELS SHOWN ON THESE DRAWINGS AND THE RISER DIAGRAM ARE FOR SCHEMATIC PURPOSES ONLY. THECONTRACTOR AND FIRE ALARM VENDOR SHALL DETERMINE THE EXACT QUANTITY OF BOOSTER PANELS REQUIRED BASED ON THE MANUFACTURER'SPANEL FUNCTION AND SPECIFICATIONS. THE CONTRACTOR SHALL PROVIDE THE QUANTITY OF BOOSTER PANELS REQUIRED TO SUPPORT THE ENTIRE FIREALARM SYSTEM BASED ON THE QUANTITY OF DEVICES SHOWN ON PLAN, TOTAL POWER NEEDED TO SUPPORT THE DEVICES, VOLTAGE DROPCALCULATIONS FOR EACH CIRCUIT, BATTERY CALCULATIONS, SIZE OF BUILDING, ETC. THE CONTRACTOR SHALL PROVIDE 120V, 20AMP CIRCUITS FOR ALLBOOSTER PANELS THAT ARE INSTALLED BASED ON THE FIRE ALARM VENDOR'S CALCULATIONS AT NO ADDITIONAL COST TO SDP.

1 SMOKE DETECTOR TO INITIATE ELEVATOR PRIMARY AND ALTERNATE RECALL.

FIRE ALARM SHEET NOTES

2

3

NEW FIRE ALARM REMOTE BOOSTER POWER SUPPLY. PROVIDE 120V, 20AMP EMERGENCY POWER CIRCUITFROM PANELBOARD "EM" IDENTIFIED FOR FIRE ALARM REMOTE BOOSTER POWER SUPPLIES -CIRCUIT #EM-11.

1

PROVIDE A DUCT MOUNTED SMOKE DETECTOR IN RETURN DUCT AND SUPPLY DUCT OF HVAC UNIT (OVER 2000CFM). EACH DUCT MOUNTED SMOKE DETECTOR SHALL HAVE REMOTE TEST SWITCH AND LED ALARMINDICATORS. WHERE THE CEILING HEIGHT IS HIGHER THAN 10', THE REMOTE TEST SWITCH AND LED ALARMINDICATORS SHALL BE WALL MOUNTED AT 48" A.F.F. ADJACENT HVAC UNIT. PROVIDE AND CONNECT ACONTROL MODULE AT EACH HVAC UNIT EXISTING MOTOR STARTER TO SHUTDOWN HVAC UNIT, FIELD VERIFYEXACT LOCATION. DEVICES TO BE LOCATED WHERE ACCESSIBLE BY QUALIFIED PERSONNEL ONLY. PROVIDE (1)REMOTE TEST STATIONS FOR EACH DUCT MOUNTED SMOKE DETECTORS.

4

F/ABOOSTERPANEL#EM-11

2

DD

DD

DD

DD

DD

DD

DD

DD

3 3 3

3

PROVIDE A SMOKE DETECTOR ON THE TOP OF ELEVATOR SHAFT.

4

SD

DD

DD

3

SD

15cd 15cd 15cd

15cd

15cd

15cd

110cd

15cd

110cd

110cd

15cd

15cd

75cd75cd75cd75cd75cd75cd75cd75cd

75cd

75cd

75cd

75cd

15cd75cd

75cd

75cd

75cd

75cd75cd

75cd

15cd

75cd 75cd

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

SE

E P

AR

TIA

L P

LA

N T

HIS

SH

EE

T F

OR

C

ON

TIN

UA

TIO

N

UP

TEACH. CLOS.

218B

CLOS.

218A

STAIR NO.4

241

STORAGE

242

CLASSROOM

NO.17

217

TOILET

217A

SHOWER

217B

TEACH. CLOS.

217C

TEACHERS

WORKROOM

216

TEACH. CLOS.

216B

CLOS.

216A

CLASSROOM

NO.16

215

TOILET

215A

SHOWER

215B

TOILET

215C

TEAM

PLANNING RM

NO.3

214

214B

CLOS.

214A

CLO.

213A

CLASSROOM

NO.18

218

CLASSROOM

NO.15

213

SD

SD

15cd

15cd

15cd

75cd

30cd

75cd

15cd

15cd

75cd

75cd

3/32" = 1'-0"

E-206

FIRE ALARM NEW WORKSECOND FLOOR PLAN

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

DIAMOND ST.N. 1

6TH

ST.

N. 1

5TH

ST.

N

KEYPLAN

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: 3/32" = 1'-0"

FIRE ALARM NEW WORK SECOND FLOOR PLAN

1

SHEET 49 OF 61

Page 39: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

NONE

E-207

FIRE ALARMRISER DIAGRAM

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

SCALE: NONEADDRESSABLE VOICE FIRE RISER DIAGRAM

1

FIRE ALARM SYSTEM RISER NOTES:

1. THIS RISER DIAGRAM IS BASED ON SIEMENS BUILDING TECHNOLOGIES DESIGO VOICE FIRE ALARM CONTROL PANEL. THIS DIAGRAM IS SCHEMATIC ONLY AND DOES NOT REPRESENT ACTUAL DEVICE QUANTITIESUNLESS OTHERWISE NOTED. IT IS A REPRESENTATION OF THE INTENDED SYSTEM FOR THIS PROJECT. SEE THE FLOOR PLANS FOR EXACT QUANTITIES AND LOCATIONS OF FIELD EQUIPMENT. SEE THE PROJECTSPECIFICATIONS FOR PERFORMANCE AND COMPLIANCE REQUIREMENTS. QUANTITY AND SIZE OF CONDUCTORS TO BE DETERMINED BY SIEMENS.

2. THE SYSTEM SHALL BE UL LISTED FOR FIRE [UL864] AND MASS NOTIFICATION [UL2572] IN ONE (1) FIRE ALARM CONTROL PANEL (FACP). IT SHALL ALSO SUPPORT GAS ALARM EVENTS FOR CO DETECTION, PER NFPA 72.

3. THE SYSTEM SHALL HAVE THE CAPACITY TO NETWORK UP TO 32 FIRE AND VOICE PANELS UTILIZING VOICE-OVER-IP (VOIP) TECHNOLOGY. ALL FIRE AND VOICE SIGNALS SENT OVER THE SAME CONDUCTORS.PEER-TO-PEER NETWORKED PANELS SHALL HAVE THE CAPABILITY OF DISPLAYING LOCAL OR GLOBAL EVENTS. THE NETWORK SHALL ALSO SUPPORT THE ABILITY TO INTERFACE WITH A UL LISTED DESKTOPWORKSTATION.

4. PROVIDE AUXILIARY FIRE ALARM SIGNAL PANEL(S) AND VOICE AMPLIFIERS W/ BATTERY BACKUP AS REQUIRED TO SUPPORT NOTIFICATION APPLIANCE LOADS. THE SYSTEM SHALL HAVE THE CAPABILITY TO SUPPORT ATHREE-CHANNEL MESSAGE PLAYER WITH UPTO 300 MESSAGES.

5. PROVIDE A MANUAL VOICE PAGING SWITCHES FOR 'ALL CALL' FOR SIMULTANEOUSLY PAGING THE ENTIRE FACILITY AND SELECTIVE PAGING FOR EACH FLOOR AND FIRE AREA.

6. ALL WIRING REQUIREMENTS SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS, BUT NOT LESS THAN INDICATED ON THIS DRAWING.

7. PROVIDE END OF LINE RESISTERS AS NECESSARY.

8. ALL ADDRESSABLE SLC'S SHALL BE NFPA 72 CLASS B, STYLE 4.

9. ALL NOTIFICATION NAC'S SHALL BE NFPA 72 CLASS B, STYLE Y.

10. STROBE CANDELAS MUST BE SIZED PER NFPA 72 REQUIREMENTS BY THE FIRE ALARM VENDOR AND SHOWN ON THE SHOP DRAWINGS.

11. ALL PANEL BATTERY BACKUP (STANDBY & ALARM) SHALL BE SIZED PER NFPA 72 REQUIREMENTS.

12. A COMPLETE SET FOR FIRE ALARM PRODUCT CUT SHEETS, FIRE ALARM SHOP DRAWINGS, AND BATTERY/ VOLTAGE/ LOAD CALCULATIONS MUST BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION.

13. PRIMARY FACP POWER FED VIA BRANCH CIRCUIT(S) DEDICATED FOR THE FIRE ALARM SYSTEM. PROVIDE NORMAL/EMERGENCY POWER CIRCUITS TO THE FIRE ALARM CONTROL PANEL AND ALL REMOTE NAC PANELS(NOT APPLICABLE TO BUILDINGS WHICH DO NOT HAVE EMERGENCY GENERATORS). PROVIDE A 120 VOLT DUPLEX RECEPTACLE AT FIRE ALARM PANEL FOR MAINTENANCE AND PRINTER USE.

14. ALL EARTH GROUND PANEL CONNECTIONS REQUIRED BY THE MANUFACTURER SHALL BE CONNECTED TO THE BUILDING'S GROUND. PANEL NEUTRAL OR GROUNDING TO CONDUIT/ BUILDING STEEL NOTACCEPTABLE.

EARTHGROUND

CONNECT TO 20A/1P CIRCUITBREAKER IN NEAREST 120V PANEL.RUN (2) #12 IN 3 4" CONDUIT.

COORDINATE EXACT LOCATION WITHFIRE MARSHAL PRIOR TO ROUGH-IN.

OFF-SITEIP &

CELLULARNETWORKABLE FIRE

AND VOICE SYSTEMSOVER CAT5 OR

FIBER-OPTIC CABLES

SIZE OF CONDUCTORS, QUANTITY OF NAC'S ANDBOOSTER PANELS TO BE DETERMINED BY SIEMENS.ACTIVE ALARM CAPACITY MUST NOT EXCEED80%. ALL STROBES SHALL HAVE ADA COMPLIANTSYNCHRONIZED FLASHING. VOICE SPEAKERCIRCUITS SIZED PER THE BUILDING'S FIRE ZONES.

REMOTE ANNUNCIATORPOWER & DATA

EARTH GROUND

PROVIDE ADDRESSABLE MONITORING MODULES OR CONTROL MODULES AT THELOCATIONS SHOWN ON THE FLOORPLANS, PER THE FUNCTIONS LISTED BELOW:

SUPPRESSION KITCHEN SUPPRESSION HOOD MONITORINGELEVATOR SIGNAL THE CONTROLLER TO INITIATE PRIMARY, SECONDARY, AND FIRE HAT

FUNCTIONS SIGNAL THE SHUNT TRIP BREAKER TO INITIATE POWER SHUTDOWNSMOKE MANAGEMENT SIGNAL HVAC FAN SHUTDOWN

SIGNAL RELEASE OF MAGNETIC SMOKE DOOR HOLDER SIGNAL SMOKE DAMPER CLOSURESECURITY SIGNAL THE EGRESS DOOR LOCKS TO UNLOCK

STROBE BOOSTER PANELACTIVATION CIRCUIT

ADDRESSABLE SIGNAL LINE CIRCUIT (SLC)

GENERAL FIRE ALARM SYSTEM NOTES

1. THIS SYSTEM HAS BEEN ENGINEERED BASED ON THE PERFORMANCE AND CAPABILITIES OF SIEMENS DESIGO ADDRESSABLE VOICE FIRE ALARM CONTROL PANEL (FACP) WITH DOOR-MOUNTED DISPLAY/CONTROLS, AND INTERNAL BATTERY BACKUP. MANUFACTURES AND MODEL NUMBERS NOTED ON THE CONSTRUCTION DOCUMENTS ARE FOR REFERENCE ONLY AND TO ESTABLISH A BASIS OF DESIGN.PRODUCTS PROVIDED BY ALTERNATIVE MANUFACTURERS SHALL BE ACCEPTABLE PROVIDING THEY MEET THE QUALITY STANDARDS REFERENCED HEREIN. APPROVED ADDITIONAL FIRE ALARM SYSTEMMANUFACTURERS ARE: EDWARDS, NOTIFIER AND GAMEWELL (FCI).

2. THE SELECTED SYSTEM IS MODULAR IN DESIGN. ALL SPECIFIED COMPONENTS MUST HAVE A MINIMUM 20% SPARE EXPANSION CAPACITY TO ACCOMMODATE CONSTRUCTION CHANGES AND FUTURERENOVATIONS. THIS SPARE CAPACITY INCLUDES CABINET EXPANSION SPACE, CAPACITIES ON POWER SUPPLIES/ PANEL CARDS AND NETWORKING CAPABILITY.

3. IT IS THE INTENT THAT THE DRAWINGS AND SPECIFICATIONS SHALL PROVIDE A WORKING INSTALLATION. THE OMISSION OF EXPRESSED REFERENCE IN THE DRAWINGS OR SPECIFICATION TO ANY LABOR ORMATERIAL NECESSARY FOR THE PROPER EXECUTION OF THE WORK IN ACCORDANCE WITH PRESENT GOOD PRACTICE OF THE TRADE SHALL NOT RELIEVE THIS CONTRACTOR FROM PROVIDING, AT NO COST,SUCH ADDITIONAL LABOR AND MATERIAL UNDER THIS CONTRACT.

4. ALL WIRING SHALL COMPLY WITH PROJECT SPECIFICATIONS, NFPA 72, NEC ARTICLE 760, AND THE REQUIREMENTS OF THE AHJ. NO FIRE ALARM POWER-LIMITED WIRING SHALL BE PERMITTED IN THE SAMERACEWAY AS NO POWER-LIMITED UNLESS SEPARATED BY AN APPROVED BARRIER.

5. FOR CONDUIT APPLICATIONS, USE ELECTRICAL METALLIC TUBING (EMT), 3/4" MINIMUM.

6. ALL CONDUITS, CONDUCTORS, RACEWAYS, EQUIPMENT, ETC., SHALL BE SUPPORTED IN AN APPROVED MANNER BY THE BUILDING STRUCTURE, INCLUDING HANGERS AND RESTRAINTS, IN ACCORDANCE WITHALL APPLICABLE CODES AND SEISMIC RESTRAINT REQUIREMENTS.

7. ALL FIRE RATED PENETRATIONS SHALL BE MADE WITH A UL APPROVED FIRE STOP MATERIAL OR METHOD.

8. SEAL ALL PENETRATIONS THROUGH EXTERIOR WALLS, FLOORS, AND ROOFS WITH WATERTIGHT MATERIAL.

9. FURNISH AND INSTALL ACCESS PANELS WHERE REQUIRED FOR ACCESS TO CONCEALED EQUIPMENT WHERE NO OTHER MEANS IS PROVIDED.

10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING PATCHING AND PAINTING REQUIRED FOR COMPLETE FIRE ALARM SYSTEM INSTALLATION.

11. MOUNTING FOR ALL DEVICES AND APPLIANCES SHALL COMPLY WITH STATE, LOCAL, AND ADAAG.

12. CONTRACTOR SHALL REPAIR/PATCH AND/OR REPAINT TO MATCH ADJACENT AREAS, ANY AREAS DAMAGED (OR WHERE ITEMS WERE REMOVED/ DEMOLISHED) BY WORK OF THIS CONTRACT.

13. THE FIRE ALARM VENDOR MUST CALCULATE THE NOTIFICATION APPLIANCES CANDELA RATINGS AND DESIGNATE THEM ON THE SHOP DRAWINGS. ALL STROBE SETTING MUST COMPLY WITH NFPA 72REQUIREMENTS.

14. EACH AIR HANDLING SYSTEM 2000 CFM OR GREATER SHALL BE EQUIPPED WITH A SUPPLY AND RETURN DUCT DETECTOR.

15. ALL WORK AND SHUTDOWNS ASSOCIATED WITH FIRE ALARM SYSTEM INTERFACES SHALL BE COORDINATED THROUGH THE RESPECTIVE CONTRACTOR, INCLUDING BUT NOT LIMITED TO: SPECIAL HAZARDSUPPRESSION SYSTEM(S), AUTOMATIC SPRINKLER SYSTEM(S), HVAC SYSTEM(S), ELEVATOR SYSTEM(S), AND SECURITY/ ACCESS CONTROL SYSTEM(S).

16. SYSTEM MANUFACTURER SHALL COORDINATE FINAL QUANTITIES AND LOCATIONS OF ALL SYSTEM MONITORS AND CONTROL MODULES WITH THE RESPECTIVE CONTRACTORS FOR INTERFACE. FINAL LOCATIONSTO BE SHOWN ON SHOP DRAWINGS. CHECK AND VERIFY ALL CONDITIONS AT THE SITE WITHIN THE CONTRACT LIMITS. THE INSTALLATION CONTRACTOR IS RESPONSIBLE FOR ALL FIELD MEASUREMENTS ANDVERIFICATION OF FIELD CONDITIONS PRIOR TO COMMENCING WORK. ANY CHANGES IN WORK NECESSITATED BY FAILURE OF THIS CONTRACTOR TO COMPLY WITH THIS PROCEDURE SHALL BE UNDERTAKEN BYTHIS CONTRACTOR AT HIS/ HER OWN EXPENSE.

17. THE INSTALLATION CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE FIRE ALARM SHOP DRAWING SUBMITTAL FOR COMPLETE COMPLIANCE WITH THE FULL SET OF BID DOCUMENTS PRIOR TO SUBMITTING TOTHE ENGINEER FOR APPROVAL.

18. ACCEPTANCE TESTING MUST BE PERFORMED IN ACCORDANCE WITH NFPA 72 AND AHJ REQUIREMENTS.

19. UPON COMPLETION OF FINAL TESTING AND APPROVAL OF THE AHJ, THE SYSTEM VENDOR SHALL SUBMIT RECORD DRAWINGS TO THE OWNER DETAILING AS-BUILT CIRCUITING AS SHOWN ON THE INSTALLER'SRED-LINE MARKUPS. THEY SHALL INCORPORATE ALL FIELD AND DESIGN DIRECTIVES GIVEN THROUGH OUT THE PROJECT.

FIRE CONTROL PANELVOICE

CONNECT TO 20A/1P CIRCUIT BREAKER (PANEL "EM") WITH(2) #12 IN 3 4" CONDUIT. UTILIZE EMERGENCY POWERCIRCUIT AND SIZE THE FACP STANDBY BATTERIES PER NFPA72 REQUIREMENTS.

REMOTE ANNUNCIATOR WITHDISPLAY & CONTROL

FUNCTIONS

4 X 40 BACK LIT LCD SCREENPOWERTROUBLESUPPRE

ALARMALARMSILENCEDALARM

ACKNOWLEDGEALARM SILENCE SYSTEM RESET

MAIN

DESIGO

FACP

CONNECT TO 20A/1P CIRCUITBREAKER IN NEAREST 120V PANEL.RUN (2) #12 IN 3 4" CONDUIT.

EARTH GROUND

STROBE BOOSTER PANELACTIVATION CIRCUIT

A/V NOTE:SPEAKER AND STROBES MAY BE SUPPORTED BY ACOMBINATION OF THE MAIN FIRE ALARM PANELAND/OR BY BOOSTER PANELS. ALL BOOSTER PANELSSHALL BE SUPERVISED BY THE MAIN FACP. PROVIDE ADEDICATED SMOKE DETECTOR FOR THE BOOSTERPANELS IF AREA SMOKE COVERAGE NOT SUPPLIED INTHE BASE DESIGN. PROVIDE A LISTED WIRE GUARD FORAPPLIANCES IN GYMNASIUMS AND LOCKER ROOMS.

PROVIDE FIRE ALARMANNUNCIATORS AT THE MAINFIRE DEPARTMENT ENTRANCE,BUILDING ENGINEER'S OFFICEAND MAIN OFFICE.

PROVIDE A SIGN TO EACHMANUAL PULL STATION. THESIGN SHALL BE MOUNTEDIMMEDIATELY ADJACENT TOTHE MANUAL PULL STATION.THE SIGN SHALL READ “INCASE OF FIRE: SOUNDALARM AND CALL THE FIREDEPARTMENT”.

AUXILIARYSPEAKERBOOSTERPANEL W/BATTERYBACKUP

CONTROLLED& MONITORED

BY FACP

AUXILIARYSTROBE

BOOSTERPANEL W/BATTERYBACKUP

CONTROLLED& MONITORED

BY FACP

MANUAL PULLSTATION WITH

PROTECTIVE COVER

ADDRESSABLEMULTICRITERIA

SMOKEDETECTOR

ADDRESSABLESMOKE

DETECTORW/ RELAY

BASE

ADDRESSABLESMOKE

DETECTOR W/CO

DETECTION

ADDRESSABLEHEAT HEATDETECTOR

ADDRESSABLESMOKE DUCT

DETECTOR

ADDRESSABLEMODULE

SPEAKERAPPLIANCE

STROBEAPPLIANCE

SPEAKER/STROBEAPPLIANCE

PROVIDE OUTSIDEWEATHERPROOF STROBE NEARENTRANCE TO FIRE COMMAND,ACTIVATE ON ANY ALARM

STROBEAPPLIANCE

DIAGRAM IS SCHEMATIC ONLY AND DOES NOT REPRESENTACTUAL DEVICE QUANTITIES UNLESS OTHERWISE NOTED.EVERY DEVICE INDICATED MAY NOT BE UTILIZED FOR THISPROJECT. REFER TO DRAWINGS, AND ALLOWANCES FOREQUIPMENT QUANTITIES. REFER TO SPEC. FOR FURTHERPERFORMANCE INFORMATION.

#EM-7

#EM-9

#EM-11

SHEET 50 OF 61

PROVIDE SEPARATEADDRESSABLE CIRCUITHOMERUNS FOR EACH LEVELAND FOR EACH SEPARATE FIREAREA

PROVIDE WIRING TO STARTERS FORFAN SHUTDOWN OF MECH. AIRHANDING UNITS WITH DUCT SMOKEDETECTORS. USE A SEPARATEADDRESSABLE RELAY MODULE FORFAN SHUTDOWN IF THE STARTER ISREMOTE FROM THE UNIT.

HVAC UNIT

MOTOR

MOTOR STARTER

RETURN OR SUPPLY AIR DUCTWORK

NC

DUCT MOUNTEDSMOKE DETECTOR WITHSHUTDOWN RELAY

REMOTE TEST STATION(WALL MOUNTED)

FA SIGNAL CIRCUIT TO FACPPANEL

NOT TO SCALETYPICAL AHU SHUTDOWN DETAILS

L

NOTE:PROVIDE WIRING TO STARTERS FOR FANSHUTDOWN OF MECHANICAL AIR HANDLINGUNITS WITH DUCT SMOKE DETECTORS. USE ASEPARATE ADDRESSABLE RELAY MODULE FORFAN SHUTDOWN IF THE STARTER IS REMOTEFROM THE UNIT.

FANSHUTDOWN

PROVIDE NAMEPLATEINDICATING AHU NUMBER.

WIRING IN CONDUIT

NAMEPLATEINDICATINGAHU NUMBER

INDICATORLIGHT

REMOTE TESTSWITCH

DUCTDETECTOR

OTHER INDICATORS FOR MULTIPLEDETECTOR LOCATIONS.

RTS/I NOT TO SCALETYPICAL SPEAKER/STROBE WIRING DETAIL

1 PAIR #14 AWG (MIN)

UNSHIELDED

STROBE POWER 24VDC

NOTES:1. ALL WIRING IN CONDUIT.

STROBE SPEAKER/STROBE

STROBESPEAKER

2

3

1 1 PAIR #14 AWG (MIN) UNSHIELDED STROBE POWER 24VDC

2 1 PAIR #16 AWG (MIN) SHIELDED SPEAKER POWER 24VDC

3 1 PAIR #14 AWG SHIELDED ADDRESSABLE DATA LOOP

4 1 PAIR #14 AWG UNSHIELDED 24V POWER

5 (2) CAT 6 DATA CABLES WITH RJ-45 TERMINATION

6 (1) RS-232 PRINTER DATA COMMUNICATIONS CABLE

FIRE ALARM RISER WIRING LEGEND:

PROVIDE STANDALONE DIGITAL ALARM COMMUNICATORTRANSMITTER (DACT) FOR OFF-PREMISES MONITORING OFTHE FACP ALARM POINTS. PROVIDE (2) CAT 6 CABLESFROM THE FACP TO THE TELEPHONE DEMARCATIONSTATION (MAIN TELEPHONE SERVICE BOX).FACP TO COMMUNICATOR CONNECTIONS PERMANUFACTURER, DACT POWERED BY FACP.

1 PAIR #16 AWG (MIN) SHIELDED

SPEAKER POWER 24VDC

34PRINTER

PROVIDE SUPERVISED RELAYING FORELEVATOR RECALL, LOCATE IN ELEVATORMACHINE ROOM, PROVIDE RELAY ANDSUITABLE ENCLOSURE, ALLINTERCONNECTIONS TO ELEVATORCONTROLLER SHALL BE BY ELEVATORCONTRACTOR.

PROVIDE SUPERVISED RELAYING FORELEVATOR ALTERNATE RECALL,LOCATE IN ELEVATOR MACHINEROOM, PROVIDE RELAY AND SUITABLEENCLOSURE, ALL INTERCONNECTIONSTO ELEVATOR CONTROLLER SHALL BEBY ELEVATOR CONTRACTOR.

Page 40: Due to restrictions in place for COVID -19 by Governor ......3. REVISED ELECTRICAL BID PROPOSAL FORM: Bidders for Electrical Construction must use the attached Revised Bid Proposal

3/32" = 1'-0"

E-208

FIRE ALARMDETAILS

N/A4460

FLOOD REMEDIATIONPROJECT

DR. TANNER G. DUCKREYELEMENTARY SCHOOL

1501 DIAMOND STREET,PHILADELPHIA, PA 19121

SEAL:

OFFICE OF CAPITAL PROGRAMS

440 NORTH BROAD STREETPHILADELPHIA, PA 19130 - 4015

(215) 400 - 4730 | (215) 400 - 4731 (fax)www.philasd.org

DRAWING NO.

DRAWN BY CHECKED BY

FILE NO.LOCATION NO.

DRAWING TITLE

PROJECT TITLE

NO. DATE REVISION

87654321

A

B

C

D

E

F

DRAWING SCALE

DATEGRAZYNA S. PLICHTAPA PE045538E 09/30/2019

GSPDGW

ARCHITECTURAL

GANNETT FLEMING, INC.ONE PENN PLAZA, SUITE 630250 WEST 34TH STREETNEW YORK, NY 10119Phone: 212.967.9833Fax: 212.232.5791Email: [email protected]: Kayoko Karatsu, AIA

ELECTRICAL LIGHTING AND FIRE ALARM

DGW ELECTRICAL ENGINEERING, INC.232 CECELIA ACRES DRIVEIVYLAND, PA 18974Phone: 215.354.9161Fax: 215.354.9163Email: [email protected]: Grazyna Plichta, PE

MECHANICAL

GANNETT FLEMING, INC.1010 ADAMS AVENUEVALLEY FORGE, PA 19403Phone: 610.650.8156Fax: 610.650.8190Email: [email protected]: Brian M. Weisser, PE

VERTICAL TRANSPORTATION

GANNETT FLEMING, INC.1801 MARKET STREET, SUITE 2600PHILADELPHIA, PA 19103Phone: 215.557.0106Fax: 215.557.0337Email: [email protected]: Mark D. DeCocinis, CEI

ELECTRICAL POWER AND TELECOMMUNICATIONS

GANNETT FLEMING, INC.207 SENATE AVENUECAMP HILL, PA 17011Phone: 717.763.7211Fax: 717.763.8150Email: [email protected]: Brian Seip, PE

B-075c OF 2018/19B-076c OF 2018/19B-077c OF 2018/19B-078c OF 2018/19

PERMIT SET25 MARCH 2020

NOTE: THIS FIGURE IS BASED ON THE THE ACCESSIBILITY GUIDELINESFOR BUILDINGS AND FACILITIES (ADAAG)

REMOTEANNUNCIATOR

SUPE

RVISI

NG ST

ATIO

N

NOTIF

ICAT

ION

SIGNA

LS

OFF

SITE

SIG

NAL S

ENT T

O

ACTIV

ATE

EVAC

UATIO

N

ANNU

NCIA

TE @

FAC

P

TRO

UBLE

SIG

NAL

SYST

EM A

LARM

AREA DETECTOR (SMOKE, HEAT, OR BEAM)

MANUAL PULL STATION

FACP/PB PRIMARY POWER FAILURE

ANNU

NCIA

TE @

RA

SUPE

RVISO

RY SI

GNA

L

FAN

SHUT

DOW

N O

F

ASSO

CIA

TED

HVAC

UNI

T

FACP/PB LOW BATTERY

SLC/NAC OPEN-CIRCUIT

SLC/NAC GROUND-FAULT

SLC/NAC SHORT-CIRCUIT

DUCT SMOKE DETECTOR

FIRE PUMP RUNNING

RELE

ASE

SMO

KE

DOO

R HO

LDER

S

RELE

ASE

EGRE

SS

DOO

R LO

CKS ALARM

TROUBLE

A SIGNAL WHICH INDICATES AN EMERGENCY SITUATION REQUIRING IMMEDIATE

ACTION

A SIGNAL WHICH INDICATES A

FAULT WITH AN APPLIANCE, DEVICE, OR

SYSTEM COMPONENT

SUPERVISORYA SIGNAL WHICH

INDICATES A NON-

EMERGENCY SITUATION REQUIRING IMMEDIATE

ACTION

FIRE ALARM SYSTEM OPERATION NOTES:

1. THIS NFPA 72 OPERATIONAL MATRIX IS BASED ON A SIEMENS DESIGO FIRE ALARM SYSTEM.2. ALL SYSTEM STATUS CONDITIONS SHALL BE MIRRORED AT REMOTE ANNUCIATORS.3. IN ORDER TO INSURE CONTINUED SAFE AND RELIABLE OPERATION OF THE FIRE ALARM SYSTEM, PERIODIC INSPECTION AND TESTING SHOULD BE PERFORMED IN ACCORDANCE

WITH APPLICABLE NFPA 72 STANDARDS.FOR ANY REQUIRED SERVICE, REFER TO THE SYSTEM MANUAL OR CONTACT A FACTORY AUTHORIZED REPRESENTATIVE.4. IN NORMAL STANDBY OPERATION, THE GREEN AC POWER ON LED SHOULD BE ILLUMINATED AND NO OTHER INDICATOR OPERATING. THE DISPLAY WILL SHOW THE SYSTEM NAME,

"SYSTEM NORMAL" ANNOUNCEMENT AND THE CURRENT DATE, DAY, AND TIME.5. THIS SYSTEM IS CAPABLE OF EVERY INITIATION DEVICE AND NOTIFICATION APPLIANCE ACTIVATING SIMULTANEOUSLY.6. SYSTEM OPERATING INSTRUCTIONS ARE PRINTED ON THE INSIDE DOOR OF THE FACP.7. ALL SIEMENS FIRE ALARM CABINET DOORS WITH KEYED LOCKS UTILIZE A T-45 KEY.

TYPICAL FIRE ALARM EQUIPMENT MOUNTING NOTES:

THESE MOUNTING DIMENSIONS COMPLY WITH THE FOLLOWING: NFPA 72 CHAPTER 5 & 7 CABO/ANSI A117.1 IBC 2018, CHAPTER 9 ADA PARAGRAPH 4.2.5 & 4.2.6 THE ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS & FACILITIES (ADAAG)

FOR LOW CEILINGS WHERE THE PRESCRIBED MOUNTING HEIGHTS FOR THE SIGNALINGAPPLIANCES CAN NOT BE MET, INSTALL THE APPLIANCE 6" FROM THE CEILING.

ALL DEVICE & APPLIANCE HEIGHTS SHOULD BE CONSISTENT FOR THE ENTIRE PROJECT.

FOR COMBINATION AUDIO/ VISUAL APPLIANCES, THE STROBE PLACEMENT TAKESPRECEDENCE.

SHEET 51 OF 61

ACCEPTABLEMOUNTING AREA FORMANUAL PULLSTATIONS. MEASUREDFROM THE CENTER OFTHE HANDLE.

5' MAX

MIN. 3 FTCLEARANCE INFRONT OF THEFACP

EXITDOOR6'

MAX

DUCT SMOKEDETECTOR

REMOTE TESTSTATION

TYPICALLY48"

6" MIN.

MIN. 3 FTCLEARANCEIN FRONTOF THE RA

ACCEPTABLE MOUNTING AREA FOR,STROBES, OR AUDIBLE/STROBECOMBINATION APPLIANCES(NONSLEEPING ROOMS ANDCORRIDORS). DISTANCES AREMEASURED SO THAT THE ENTIRE LENSMUST BE WITHIN THE AREA SHOWN.

ACCEPTABLEMOUNTING AREA FORAUDIBLE DEVICEDISTANCES AREMEASURED FROM THETOP OF THEAPPLIANCE.

MIN. 90" MIN. 80"

FIRE ALARM EQUIPMENT MOUNTING HEIGHTS DIMENSIONS

TS

MIN. 42"

5' MAX

SMOKE DETECTORS SPECIFIC LOCATION REQUIREMENTS:

1. NO CLOSER THAN 4" FROM ADJOINING WALL SURFACE.2. NO CLOSER THAN 36" FROM THE BATHROOM DOOR.3. AT LEAST 36" AWAY FROM THE SUPPLY REGISTERS OF THE FORCED AIR HEATING OR COOLING, AND OUTSIDE OF THE DIRECT AIRFLOW FROM THESE REGISTERS.4. AT LEAST 36" AWAY FROM THE TIP OF THE BLADE OF THE CEILING FAN.

NOT TO SCALEFLUSH MOUNTED AUTOMATIC DETECTOR DETAIL

3

ROOF OR FLOORSTRUCTURE

J-BOX

STRUCTUREOR BEAM

BEAM CLAMP OR SUPPORTFOR RACEWAY PER NEC.(TYPICAL)

EMT CONDUIT

FLEX CONDUIT TODETECTOR

EMT CONDUITSUPPORT PERNEC. (TYPICAL)

J-BOXSMOKE OR HEATDETECTORS

PROVIDE J-BOXSUPPORT PER NEC.

SMOKE OR HEATDETECTOR (TYP)

NOTES:BOX TO BE ACCESSIBLE VIA CEILING TILE. BOXTO BE PAINTED RED AND HAVE A COVERLABELED "FIRE ALARM"

3/4" FLEXIBLE CONDUIT TO JCT. BOX

LAY-IN CEILING

PROVIDE T&B CONNECTOR

4" DEEP OCTAGON BOXSUPPORT WITH HANGER

SUSPENDED T-BAR

LAY-IN CEILING

NOT TO SCALEDETECTOR DETAIL4

SURFACE MOUNTED J-BOXSAME SIZE AS DETECTOR BASE

SMOKE OR HEATDETECTOR.(TYPICAL)

STRAP PER NEC.

EMT CONDUIT

EXISTINGWALL

FLOOR

SURFACE MOUNTED AUTOMATIC

NOT TO SCALESTATION DETAIL5

SURFACE MOUNTED PULL

NOT TO SCALEDEVICE DETAIL6

SURFACE NOTIFICATION

DECK OR CONCRETESTRUCTURE

EMT CONDUIT STRAPPER NEC.

EMTCONDUIT

EMT CONDUIT STRAPPER NEC.

SURFACE METALRACEWAY J-BOX

SURFACE MOUNTED PULLSTATION

MOUNTING HEIGHT TOOPERATING HANDLE

42" AFF. (MIN.)48" AFF. (MAX.)

FLOOR

DECK OR CONCRETESTRUCTURE

EMT CONDUIT STRAPPER NEC.

EMTCONDUIT

EMT CONDUIT STRAP PER NEC.

SURFACE METALRACEWAY J-BOX

SURFACE MOUNTEDNOTIFICATIONAPPLIANCE

80" AFF.

FLOOR

EXISTINGWALL

EXISTINGWALL

1

2