POST-FIRE INSPECTION PROCEDURES
www.slyinc.com800-334-2957
LEARN HOW TO STAY SAFE AND PREVENT DAMAGES
![Page 2: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/2.jpg)
DAMAGE INSPECTION
• Tubesheet• Pulse pipes• Hopper• Entryways• Bolted flanges• Compressed air piping
• Housing walls• Downstream
equipment• Rupture panels
(explosion vents)• Overall inspection
![Page 3: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/3.jpg)
TUBESHEET• Check for warped
Tubesheet• Any deviation of more
than ¼” in a 24” span is considered excessive– Place a two-foot-long
straight edge at any location on the tubesheet and if the distance from “high spots” to “low spots” is over ¼”, damage is excessive.
![Page 4: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/4.jpg)
PULSE PIPES• Fire damage in pulse
pipes is rare– Abrasive wear might be
present in older collectors
• Look for damage and replace as needed
![Page 5: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/5.jpg)
HOPPER• Look for accumulation
of debris and molten metal in the bottom of the hopper
• Remove as much as possible
Pyramidal hopper
![Page 6: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/6.jpg)
ENTRYWAYS• Look at– Access doors– Ports– Roof hatches– Other external entry points
• Search for warpage preventing doors and ports from properly sealing
• Straighten or replace excessive damage
![Page 7: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/7.jpg)
BOLTED FLANGES• Check bolted flanges for damage, including brittle,
powdery, or hard textures which can cause cracks, breaks, and gaps– Pay special attention to tubesheet-housing connection
and hopper-housing connection• Methodology– Slide short, flat piece of metal between flanges to check
for gaps– Look for daylight through the flange connections when inside unit
![Page 8: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/8.jpg)
COMPRESSED AIR PIPING• Inspect– Clamps– Hoses– Tubing
• Don’t forget– Wall grommets– Morris pipe clamps– Diaphragm
valve/solenoid valve tubing
• Replace damaged parts as needed
Photo credit: http://3.imimg.com/data3/TJ/AM/MY-9263877/compressed-air-pipe-250x250.jpg
![Page 9: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/9.jpg)
HOUSING WALLS• Search for excessive distortion or permanent
deflection of the housing walls• Warpage creates contact with the installed filter
bags and causes premature wear• Distorted stiffeners lowers allowable design
pressure• Distortion generally cannot be straightened– Replacement may be required
![Page 10: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/10.jpg)
DOWNSTREAM EQIPMENT
• Look at downstream equipment– Pay close attention to
components parts (e.g. the fan)
• Damage most likely confined to debris
• Fan bearings may be affected if exposed to fire or molten debris
![Page 11: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/11.jpg)
RUPTURE PANELS• Check to ensure explosion vents are not damaged
or weakened• Repair or replace as needed
![Page 12: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/12.jpg)
OVERALL INSPECTION• Use common sense• What “doesn’t look
right” to you?• Call us with any
questions or concerns at 800-334-2957
![Page 13: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/13.jpg)
PREVENTION• Scorch damage• Ductwork• Rupture panels (explosion vents)• Witnesses
![Page 14: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/14.jpg)
SCORCH DAMAGE• Look for scorch damage, or discoloration, of
paint• Discoloration high on housing may mean a
fire on filter bags– Determine source of fire (i.e. the “spark”)– Consider grounded filters
• Discoloration low on housing may indicate a hopper fire
![Page 15: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/15.jpg)
DUCTWORK• Look for similar scorch damage, or
discoloration, on paint on the ductwork• May indicate fire started in or before the
ducting and was drawn into baghouse by fan• Isolation or suppression equipment in
ductwork may be warranted
![Page 16: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/16.jpg)
RUPTURE PANELS• If baghouse experienced a fire, but not an
explosion, rupture panels may have malfunctioned• Inspect for damage and replace as needed
Photo credit: https://en.wikipedia.org/wiki/Explosion_vent
![Page 17: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/17.jpg)
WITNESSES• Talk to employees,
maintenance personnel, etc.
• Isolate the starting point of the fire and address suppression and control at that location
![Page 18: Dust Collector Fire? Learn how to stay safe and prevent damages](https://reader035.vdocument.in/reader035/viewer/2022062503/58e682671a28ab6a5b8b5109/html5/thumbnails/18.jpg)
POST-FIRE INSPECTION PROCEDURES,REPAIR AND PREVENTION
/SlyIncorporatedStrongsville
@tweetslyinc
/company/sly-incorporated