INDEX SHEET DW-1000 - VERTICAL INSTALLATION AR-PJ-01-DW1V VERTICAL PANEL JOINT AR-PJ-02-DW1V VERTICAL PANEL W/ 1 2 " REVEAL AR-PJ-03-DW1V PANELS OVER STRUCTURAL STEEL AR-PJ-04-DW1V PANELS OVER METAL STUDS AR-PJ-05-DW1V PANELS OVER CONCRETE AR-BS-01-DW1V BASE DETAIL - OVERHANG AR-BS-02-DW1V BASE DETAIL - FLUSH AR-BS-03-DW1V FLUSH BASE WITH EXTRUSION AR-BS-04-DW1V OVERHANG BASE WITH EXTRUSION AR-OC-01-DW1V FACTORY BENT OUTSIDE CORNER AR-OC-02-DW1V 2 PIECE CORNER AR-OC-03-DW1V RADIUS BENT CORNER AR-IC-01-DW1V INSIDE CORNER WITH LONGITUDINAL BEND AR-IC-02-DW1V INSIDE CORNER WITH FIELD CUT ENDS AR-FO-01-DW1V DOOR HEAD W/ DRIP EDGE AR-FO-02-DW1V DOOR HEAD WITH EXTRUSION AR-FO-03-DW1V DOOR JAMB WITH FLASHING AR-FO-04-DW1V DOOR JAMB WITH EXTRUSION AR-FO-05-DW1V WINDOW. HEAD WITH EXTRUSION AR-FO-06-DW1V WINDOW HEAD WITH FLASHING AR-FO-07-DW1V WINDOW JAMB WITH EXTRUSION AR-FO-08-DW1V WINDOW JAMB WITH FLASHING AR-FO-09-DW1V WINDOW SILL WITH FLASHING AR-FO-10-DW1V WINDOW SILL WITH EXTRUSION AR-FO-11-DW1V LOUVER WITH FIELD CUT HEAD AR-FO-12-DW1V LOUVER WITH FIELD CUT JAMB AR-FO-13-DW1V LOUVER WITH FIELD CUT SILL AR-SF-01-DW1V SOFFIT W/ EXTRUSION AR-SF-02-DW1V SOFFIT W/ FLASHING AR-SF-03-DW1V TRANSVERSE BENT SOFFIT AR-SF-04-DW1V END WALL W/ EXTRUSION AR-SF-05-DW1V END WALL W/ FLASHING

Upload: others

Post on 25-Aug-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

INDEX SHEET

DW-1000 - VERTICAL INSTALLATION

AR-PJ-01-DW1V VERTICAL PANEL JOINT

AR-PJ-02-DW1V VERTICAL PANEL W/

1

2

" REVEAL

AR-PJ-03-DW1V PANELS OVER STRUCTURAL STEEL

AR-PJ-04-DW1V PANELS OVER METAL STUDS

AR-PJ-05-DW1V PANELS OVER CONCRETE

AR-BS-01-DW1V BASE DETAIL - OVERHANG

AR-BS-02-DW1V BASE DETAIL - FLUSH

AR-BS-03-DW1V FLUSH BASE WITH EXTRUSION

AR-BS-04-DW1V OVERHANG BASE WITH EXTRUSION

AR-OC-01-DW1V FACTORY BENT OUTSIDE CORNER

AR-OC-02-DW1V 2 PIECE CORNER

AR-OC-03-DW1V RADIUS BENT CORNER

AR-IC-01-DW1V INSIDE CORNER WITH LONGITUDINAL BEND

AR-IC-02-DW1V INSIDE CORNER WITH FIELD CUT ENDS

AR-FO-01-DW1V DOOR HEAD W/ DRIP EDGE

AR-FO-02-DW1V DOOR HEAD WITH EXTRUSION

AR-FO-03-DW1V DOOR JAMB WITH FLASHING

AR-FO-04-DW1V DOOR JAMB WITH EXTRUSION

AR-FO-05-DW1V WINDOW. HEAD WITH EXTRUSION

AR-FO-06-DW1V WINDOW HEAD WITH FLASHING

AR-FO-07-DW1V WINDOW JAMB WITH EXTRUSION

AR-FO-08-DW1V WINDOW JAMB WITH FLASHING

AR-FO-09-DW1V WINDOW SILL WITH FLASHING

AR-FO-10-DW1V WINDOW SILL WITH EXTRUSION

AR-FO-11-DW1V LOUVER WITH FIELD CUT HEAD

AR-FO-12-DW1V LOUVER WITH FIELD CUT JAMB

AR-FO-13-DW1V LOUVER WITH FIELD CUT SILL

AR-SF-01-DW1V SOFFIT W/ EXTRUSION

AR-SF-02-DW1V SOFFIT W/ FLASHING

AR-SF-03-DW1V TRANSVERSE BENT SOFFIT

AR-SF-04-DW1V END WALL W/ EXTRUSION

AR-SF-05-DW1V END WALL W/ FLASHING

Page 2: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

INDEX SHEET

DW-1000 - VERTICAL INSTALLATION

AR-SJ-01-DW1V STACK JOINT

AR-SJ-02-DW1V STACK JOINT W/ FLASHING

AR-PR-01-DW1V PARAPET COPING

AR-PR-02-DW1V PARAPET W/ FLUSH TRIM

AR-PR-03-DW1V PARAPET W/ EXTRUSION

AR-TL-01-DW1V COLUMN COVER

AR-TL-02-DW1V WALL PENETRATION

AR-TL-03-DW1V PIPE PENETRATION

AR-TL-04-DW1V PENETRATION DETAIL

AR-TL-05-DW1V TRIM END LAP

AR-TL-06-DW1V TRIM END LAP WITH HEM

AR-TL-07-DW1V MENDING PLATE WITH SHINGLE LAP

AR-TL-08-DW1V TRIM END LAP WITH LAP STRIP

AR-TL-09-DW1V TRIM AT FRAMED OPENING

AR-TL-10-DW1V EXTRUSION AND ACCESORIES

Page 3: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

ARCHITECTURAL

DISCLAIMER

DW-1000 - VERTICAL INSTALLATION

DISCLAIMERS:

THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED

COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.

LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED

ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR

BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER).

FOR CLARITY, ALL DETAILS SHOWN WITH (1)

1

4

"-14 HEX HEAD FASTENER WITH WASHER -

CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY

REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT RECOMMENDATIONS.

ALL STRUCTURAL SUPPORTS ARE NOT BY KINGSPAN AND ARE SHOWN FOR CLARIFICATION

PURPOSES ONLY.

Page 4: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

DIRECTION OF INSTALLATION

1/16" NOMINAL JT.

FACE OF PANEL

HORIZONTAL SUPPORT

BY OTHERS

STANDARD INTERLOCK

JOINT FINNED GASKET

1 1/8" 29 15/16"

1 1/8"

29 15/16" FACE WIDTH

1 1/8"

23 15/16" FACE WIDTH

1 1/8"

23 15/16"

24" OR 30" MODULE

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1

3

16

"

1

3

16

"

1

3

16

"

VERTICAL

PANEL JOINT

DW-1000 - VERTICAL INSTALLATION

Page 5: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

DIRECTION OF INSTALLATION

HORIZONTAL SUPPORT

BY OTHERS

1/2" REVEAL

24" OR 30" MODULE

1

3

16

"

FACE OF PANEL

STANDARD INTERLOCK

JOINT FINNED GASKET

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1 1/8" 29 15/16"

29 1/2" FACE WIDTH

1 1/8"

23 1/2" FACE WIDTH

23 15/16"

1

3

16

"

1

3

16

"

1

9

16

"

1

9

16

"

VERTICAL

PANEL JOINT

1

2

"

REVEAL

DW-1000 - VERTICAL INSTALLATION

Page 6: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

HORIZONTAL

GIRT

HORIZONTAL

ANGLE

HORIZONTAL

GIRT

VERTICAL

PANELS

ALWAYS ATTACH VERTICAL PANELS

TO HORIZONTALLY ORIENTED

SUPPORTS

PANELS OVER

STRUCTURAL STEEL

DW-1000 - VERTICAL INSTALLATION

Page 7: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

HORIZONTAL

SUBGIRT

VERTICAL

PANELS

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

VERTICAL

STUDS

SHEATHING

OPTIONAL

HORIZONTAL

SUBGIRT

ALWAYS ATTACH VERTICAL PANELS

TO HORIZONTALLY ORIENTED

SUPPORTS

PANELS OVER METAL

STUDS

DW-1000 - VERTICAL INSTALLATION

Page 8: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

PRECAST OR

CMU WALL

ALWAYS ATTACH VERTICAL PANELS

TO HORIZONTALLY ORIENTED

SUPPORTS

VERTICAL

PANELS

PANELS OVER

CONCRETE

DW-1000 - VERTICAL INSTALLATION

Page 9: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

TRIMLESS END

BASE FLASHING

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1

3

16

"

BASE DETAIL -

OVERHANG

DW-1000 - VERTICAL INSTALLATION

Page 10: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

TRIMLESS END

CONTINUOUS BUTYL SEALANT

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

BASE FLASHING

URETHANE SEALANT

NOT BY KINGSPAN

1

3

16

"

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

BASE DETAIL - FLUSH

DW-1000 - VERTICAL INSTALLATION

Page 11: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

ALUMINUM BASE

EXTRUSION

1/4" DIA. WEEP HOLE

24" O.C. FIELD DRILLED

1"

CONTINUOUS BUTYL SEALANT

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

1

3

16

"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

FLUSH BASE WITH

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 12: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

ALUMINUM BASE

EXTRUSION

1/4" DIA. WEEP HOLE

24" O.C. FIELD DRILLED

1"

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

1

3

16

"

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

OVERHANG BASE W/

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 13: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

GIRT LINE

FACTORY LONGITUDINAL BEND

BACK FASTEN AT GIRTS

TO PREVENT JOINT

DISENGAGEMENT

SUM OF BOTH LEGS NOT TO

EXCEED STANDARD PANEL WIDTH

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

FACTORY BENT

OUTSIDE CORNER

DW-1000 - VERTICAL INSTALLATION

Page 14: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

GIRT LINE

FORMED CORNER TRIM

POP RIVETS 12" O.C.

SEALANT

FIELD CUT

PANELS TO SUIT

BUTYL SEALANT

INTERIOR MENDING PLATE

FASTEN TO LINER SHEET

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

2 PIECE CORNER

DW-1000 - VERTICAL INSTALLATION

Page 15: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

DESIGNWALL 1000 PANEL

FACTORY CURVED "EASY WAY"

STEEL FRAMING

BY OTHERS

ORIGIN

1

8

"

M

I

N

I

M

U

M

R

A

D

I

U

S

A

R

C

L

E

N

G

T

H

T

O

S

U

I

T

C

U

R

V

E

G

E

O

M

E

T

E

R

Y

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

RADIUS BENT CORNER

DW-1000 - VERTICAL INSTALLATION

Page 16: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

GIRT LINE

FACTORY LONGITUDINAL BEND

SU

M O

F B

OT

H LE

GS

N

OT

T

O

EX

CE

ED

S

TA

ND

AR

D P

AN

EL W

ID

TH

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

LONGITUDINAL BENT

INSIDE CORNER

DW-1000 - VERTICAL INSTALLATION

Page 17: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

GIRT LINE

FIELD CUT

PANELS TO SUIT

FORMED CORNER TRIM

SEALANT

POP RIVETS 12" O.C.

BUTYL SEALANT

INTERIOR MENDING PLATE

FASTEN TO LINER SHEET

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

INSIDE CORNER W/

FIELD CUT ENDS

DW-1000 - VERTICAL INSTALLATION

Page 18: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

EXTERIOR CAP TRIM

POP RIVETS

EXPOSED SEALANT

(NOT BY KINGSPAN)

DRIP FLASHING

FIELD CUT PANEL TO SUIT

DOOR FRAME

(NOT BY KINGSPAN)

FRAMED OPENING

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

DOOR HEAD W/ DRIP

EDGE

DW-1000 - VERTICAL INSTALLATION

Page 19: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

EXPOSED SEALANT

(NOT BY KINGSPAN)

FIELD CUT PANEL TO SUIT

DOOR FRAME

(NOT BY KINGSPAN)

FRAMED OPENING

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

STANDARD BASE

EXTRUSION

1"

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

FLASHING TRIM

1/4" DIA. WEEP HOLE 24"

O.C. FIELD DRILLED

DOOR HEAD WITH

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 20: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FRAMED OPENING

(NOT BY KINGSPAN)

DOOR FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

POP RIVETS

JAMB TRIM

FIELD CUT PANELS TO SUIT

SEALANT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

DOOR JAMB WITH

FLASHING

DW-1000 - VERTICAL INSTALLATION

Page 21: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FRAMED OPENING

(NOT BY KINGSPAN)

DOOR FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

SEALANT

FIELD CUT PANELS TO SUIT

CONTINUOUS BUTYL SEALANT

TWO PIECE JAMB

EXTRUSION

FLASHING TRIM

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

DOOR JAMB W/

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 22: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

EXPOSED SEALANT

(NOT BY KINGSPAN)

WINDOW FRAME

(NOT BY KINGSPAN)

NOTE: 1) SEE FLUSHGLAZE 7500 DETAILS FOR INTEGRATED WINDOW DESIGNS

STANDARD BASE

EXTRUSION

FRAMED OPENING

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1"

FLASHING TRIM

1/4" DIA. WEEP HOLE 24"

O.C. FIELD DRILLED

WINDOW HEAD WITH

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 23: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

EXPOSED SEALANT

(NOT BY KINGSPAN)

WINDOW FRAME

(NOT BY KINGSPAN)

DRIP FLASHING

TRIMLESS END

FRAMED OPENING

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

WINDOW HEAD

W/FLASHING

DW-1000 - VERTICAL INSTALLATION

Page 24: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FRAMED OPENING

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

SEALANT

FIELD CUT PANELS TO SUIT

CONTINUOUS BUTYL SEALANT

TWO PIECE JAMB

EXTRUSION

FLASHING TRIM

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

WINDOW FRAME

(NOT BY KINGSPAN)

WINDOW JAMB W/

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 25: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FIELD CUT PANELS TO SUIT

WINDOW FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

POP RIVETS

JAMB TRIM

SEALANT

FRAMED OPENING

(NOT BY KINGSPAN)

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

WINDOW JAMB W/

FLASHING

DW-1000 - VERTICAL INSTALLATION

Page 26: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

SEALANT

WINDOW FRAME

(NOT BY KINGSPAN)EXPOSED SEALANT

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

EXTERIOR SILL TRIM

FRAMED OPENING

(NOT BY KINGSPAN)

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

POP RIVETS

WINDOW SILL W/

FLASHING

DW-1000 - VERTICAL INSTALLATION

Page 27: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

OPTIONAL WIPER

GASKET

(FIELD INSTALLED)

SEALANT

FRAMED OPENING

(NOT BY KINGSPAN)

WINDOW FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

SILL EXTRUSION

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

BREAK-FORMED 6"

SPLICE PLATE BED

SEALED IN SILICONE

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

WINDOW SILL W/

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 28: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

EXTERIOR CAP TRIM

EXPOSED SEALANT

(NOT BY KINGSPAN)

FIELD CUT PANEL TO SUIT

FRAMED OPENING

(NOT BY KINGSPAN)

LOUVER UNIT

(NOT BY KINGSPAN)

POP RIVETS

DRIP FLASHING

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

LOUVER W/ FIELD CUT

HEAD

DW-1000 - VERTICAL INSTALLATION

Page 29: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FIELD CUT PANELS TO SUIT

LOUVER UNIT

(NOT BY KINGSPAN)

JAMB TRIM

FRAMED OPENING

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

POP RIVETS

SEALANT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

LOUVER JAMB W/ FIELD

CUT END

DW-1000 - VERTICAL INSTALLATION

Page 30: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

EXTERIOR SILL TRIM

EXPOSED SEALANT

(NOT BY KINGSPAN)

FIELD CUT PANEL

TO SUIT

POP RIVETS

LOUVER UNIT

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FRAMED OPENING

(NOT BY KINGSPAN)

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

NOTE: 1) SEE DETAIL AR-TL-05-DW1V, AR-TL-06-DW1V, AR-TL-07-DW1V, AR-TL-08-DW1V

AND AR-TL-09-DW1V FOR TYPICAL TRIM LAP INSTRUCTIONS

LOUVER SILL W/ FIELD

CUT END

DW-1000 - VERTICAL INSTALLATION

Page 31: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

STEEL FRAMING

BY OTHERS

ALUMINUM BASE

EXTRUSION

1/4" DIA. WEEP HOLE @

24" O.C. FIELD DRILLED

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

1"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

POP RIVETS 12" O.C.

SEALANT

FORMED TRIM WITH SEALANT

SOFFIT W/ EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 32: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

STEEL FRAMING

BY OTHERS

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

TRIMLESS END

POP RIVETS 12" O.C.

SEALANT

SOFFIT FLASHING

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

SOFFIT W/ FLASHING

DW-1000 - VERTICAL INSTALLATION

Page 33: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

STEEL FRAMING

BY OTHERS

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FACTORY TRANSVERSE BEND

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

TRANSVERSE BENT

SOFFIT

DW-1000 - VERTICAL INSTALLATION

Page 34: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FIELD CUT PANEL

TO SUIT

SEALANT

GIRT LINE

3"

ENDWALL EXTRUSION

PART "B" CAP

ENDWALL EXTRUSION

PART "A" RECEIVER

SEALANT

BUTYL SEALANT

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

END WALL W/

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 35: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FIELD CUT PANEL

TO SUIT CONDITION

SEALANT

GIRT LINE

SEALANT

FORMED ENDWALL TRIM

POP RIVETS 12" O.C.

BUTYL SEALANT

INTERIOR MENDING PLATE

FASTEN TO LINER SHEET

#14 "LOW PROFILE"

THRU FASTENER

(NOT BY KINGSPAN)

END WALL W/

FLASHING

DW-1000 - VERTICAL INSTALLATION

Page 36: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

SILICONE SEALANT

ZERO PROFILE HORIZONTAL

JOINT FLASHING FOR

DRAINAGE

STEEL FRAMING

BY OTHERS

5" M

IN

. B

EA

RIN

G

DO NOT CAULK HERE

ALLOW TO DRAIN

5

8

"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

CONTINUOUS

MENDING PLATE

TRIMLESS END

TRIMLESS END

TRIMLESS STACK

JOINT

DW-1000 - VERTICAL INSTALLATION

Page 37: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

HORIZONTAL JOINT STACK

FLASHING WITH SEALANT

STEEL FRAMING

BY OTHERS

5" M

IN

. B

EA

RIN

G

DO NOT CAULK HERE

ALLOW TO DRAIN

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

CONTINUOUS

MENDING PLATE

POP RIVETS 12" O.C.

TRIMLESS END

STACK JOINT W/

FLASHING

DW-1000 - VERTICAL INSTALLATION

Page 38: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

STAINLESS STEEL SCREW

PAINTED TO MATCH

PANEL. 12" O.C.

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

MEMBRANE ROOF &

PARAPET BACKER

(NOT BY KINGSPAN)

FABRICATED METAL COPING

WITH BED SEALED INSIDE

SPLICE PLATES

POP RIVETS 12" O.C.

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

PARAPET COPING

DW-1000 - VERTICAL INSTALLATION

Page 39: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

STAINLESS STEEL SCREW

PAINTED TO MATCH

PANEL. 12" O.C.

FABRICATED METAL

SPRING CLEAT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FABRICATED METAL HOOK

CLEAT WITH LOW PROFILE

SCREWS 12" O.C.

MEMBRANE ROOF &

PARAPET BACKER

(NOT BY KINGSPAN)

SILICONE SEALANT

FABRICATED METAL COPING

WITH BED SEALED INSIDE

SPLICE PLATES

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

PARAPET W/ FLUSH

TRIM

DW-1000 - VERTICAL INSTALLATION

Page 40: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

4"

STAINLESS STEEL SCREW

PAINTED TO MATCH

PANEL. 12" O.C.

FABRICATED METAL

FLASHING EXTENSION

SILICONE SEALANT

PARAPET COPING EXTRUSION

1"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FABRICATED METAL CLEAT

WITH SCREWS 12" O.C.

POP RIVETS 12" O.C.

MEMBRANE ROOF &

PARAPET BACKER

(NOT BY KINGSPAN)

SILICONE SEALANT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

BREAK-FORMED 6"

SPLICE PLATE BED

SEALED IN SILICONE

1

4

" - 14 HEX HEAD

FASTENERS WITH WASHER

(NOT BY KINGSPAN)

PARAPET W/

EXTRUSION

DW-1000 - VERTICAL INSTALLATION

Page 41: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

VJ-2 VERTICAL JOINT

GASKET SELECT BLACK

OR GRAY

ALIGN FRAMING

WITH JOINTS

CUSTOM PANEL

MODIFIED EDGE

#12 PHILLIPS HEAD

SCREWS

1

3

16

"

COLUMN COVER

DW-1000 - VERTICAL INSTALLATION

Page 42: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

SECTION 'A-A'

PENETRATION

(NOT BY KINGSPAN)

ELEVATION

BACKER ROD AND

SEALANT

(NOT BY KINGSPAN)

POP RIVET

'A'

TRIM

FASTENER

(AS REQUIRED)

'A'

PENETRATION

(NOT BY KINGSPAN)

BACKER ROD AND

SEALANT

(NOT BY KINGSPAN)

FLASHING

SEALANT

(NOT BY KINGSPAN)

SEALANT

(NOT BY KINGSPAN)

NOTES: 1. DO NOT ALIGN PENETRATIONS AT PANEL JOINT LOCATIONS.

2. FLASHING AT PENETRATIONS TO BE FIELD FABRICATED FROM

FLATSTOCK SHEETS AS NECESSARY

1

3

16

"

WALL PENETRATION

SECTION

DW-1000 - VERTICAL INSTALLATION

Page 43: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

PIPE RING WITH SEALANT

NOT BY KINGSPAN

PIPE PENETRATION

INSULATION FILL

NOT BY KINGSPAN

FIELD CUT HOLE

IN PANEL FOR PIPE

1

3

16

"

PIPE PENETRATION

DW-1000 - VERTICAL INSTALLATION

Page 44: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

FASTENER AS REQUIRED

SEALANT (NOT BY KINGSPAN)

FLASHING AS REQUIRED

INSULATION FILL

(NOT BY KINGSPAN)

SEALANT (NOT BY KINGSPAN)

SEALANT (NOT BY KINGSPAN)

FLASHING AS REQUIRED

F.I.P. INSULATION

(NOT BY KINGSPAN)

FASTENER AS REQUIRED

SEALANT (NOT BY KINGSPAN)

FASTENER AS REQUIRED

FASTENER AS REQUIRED

NOTE: FLASHING AT PIPE PENETRATIONS

TO BE FIELD FABRICATED FROM FLATSTOCK

SHEETS AS NECESSARY

NOTE: DO NOT ALIGN PENETRATIONS

AT PANEL JOINT LOCATIONS.

1

3

16

"

PENETRATION DETAIL

DW-1000 - VERTICAL INSTALLATION

Page 45: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

M

I

N

.

3

"

T

R

I

M

L

A

P

M

I

N

.

3

"

T

R

I

M

L

A

P

(2) BEADS

BUTYL SEALANT

TRIM END LAP

DW-1000 - VERTICAL INSTALLATION

Page 46: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

M

I

N

.

3

"

T

R

I

M

L

A

P

M

I

N

.

3

"

T

R

I

M

L

A

P

(2) BEADS

BUTYL SEALANT

FIELD NOTCH HEM(S)

AS REQUIRED

(NOT BY KINGSPAN)

TRIM LAP W/ HEM

DW-1000 - VERTICAL INSTALLATION

Page 47: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

(2) BEADS

BUTYL SEALANT

(2) BEADS

BUTYL SEALANT

MIN

. 3"

TR

IM

LA

P

MENDING PLATE W/

SHINGLE LAP

DW-1000 - VERTICAL INSTALLATION

Page 48: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

(2) BEADS

BUTYL SEALANT

N

O

M

.

1

4

"

G

A

P

8" LONG LAP STRIP

TRIM END LAP WITH

LAP STRIP

DW-1000 - VERTICAL INSTALLATION

Page 49: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

TAB UP TOP METAL OF HEAD

TRIM AS SHOWN AND SEAL

AGAINST BACK LEG TO FORM

END DAM

E

X

T

E

R

I

O

R

S

I

L

L

T

R

I

M

E

X

T

E

R

I

O

R

H

E

A

D

T

R

I

M

EXPOSED SEALANT

(NOT BY KINGSPAN)

EX

TE

RIO

R JA

MB

T

RIM

3

5

SEALANT END DAM

(NOT BY KINGSPAN)

TRIM INSTALLATION SEQUENCE:

1 EXTERIOR JAMB TRIM

2 EXTERIOR HEAD TRIM

3 EXTERIOR HEAD TRIM TAB UP

4 EXTERIOR HEAD TRIM TAB DOWN

5 EXTERIOR SILL TRIM

6 EXTERIOR SILL TRIM TAB UP

2

6

TAB DOWN BOTTOM METAL OF

HEAD TRIM AS SHOWN OVER

TOP OF JAMB TRIM SEAL AS

NECESSARY

TAB UP SILL TRIM IN FIELD AS

SHOWN AND SEAL AGAINST

JAMB TRIM

1

FIELD EXTEND HEAD TRIM TO

OUTER EXREMITY OF JAMB TRIM

SEAL AS NECESSARY

4

FIELD MITER AND OVERLAP

TRIMS, POP RIVET AND SEAL AS

NECESSARY

TRIM AT FRAMED

OPENINGS

DW-1000 - VERTICAL INSTALLATION

Page 50: DW-1000 - VERTICAL INSTALLATION · 2020. 7. 17. · architectural disclaimer dw-1000 - vertical installation disclaimers: these details are provided as a guideline for proper panel

LAP STRIP FOR BASE EXTRUSION

JAMB EXTRUSION

LAP STRIP FOR TWO PIECE

BASE EXTRUSION

DIE # 10309

ENDWALL EXTRUSION CAP

DIE # 11488

ENDWALL EXTRUSION

RECEIVER

DIE # 11958

VJ-2

VERTICAL JOINT GASKET

PARAPET EXTRUSION

SILL EXTRUSION

DIE #13937

DIE # 13938

EXTRUSION AND

ACCESORIES

DW-1000 - VERTICAL INSTALLATION