dw-4000 - vertical installation · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside...

66
INDEX SHEET DETAIL #: DATE: XX-XX-XX-DW4V DW-4000 - VERTICAL INSTALLATION AR-PJ-01-DW4V 2" VERTICAL PANEL JOINT AR-PJ-02-DW4V 2 1/2" VERTICAL PANEL JOINT AR-PJ-03-DW4V 3" VERTICAL PANEL JOINT AR-PJ-04-DW4V 4" VERTICAL PANEL JOINT AR-PJ-05-DW4V 2" VERTICAL PANEL W/ 1 2 " REVEAL AR-PJ-06-DW4V 2 1/2" VERTICAL PANEL W/ 1 2 " REVEAL AR-PJ-07-DW4V 3" VERTICAL PANEL W/ 1 2 " REVEAL AR-PJ-08-DW4V 4" VERTICAL PANEL W/ 1 2 " REVEAL AR-PJ-09-DW4V PANEL W/ CUSTOM REVEAL AR-PJ-10-DW4V DW4000S PANEL PROFILE AR-PJ-11-DW4V PANELS OVER STRUCTURAL STEEL AR-PJ-12-DW4V PANELS OVER METAL STUDS AR-PJ-13-DW4V PANELS OVER CONCRETE AR-PJ-14-DW4V DESIGNWALL 2000 TO 4000 AR-PJ-15-DW4V DESIGNWALL 2000 TO 4000 AR-BS-01-DW4V BASE DETAIL - OVERHANG AR-BS-02-DW4V BASE DETAIL - FLUSH AR-BS-03-DW4V FLUSH BASE WITH EXTRUSION AR-BS-04-DW4V OVERHANG BASE WITH EXTRUSION AR-OC-01-DW4V 2" PANEL OUTSIDE CORNER W/ 2-PC EXTRUSION AR-OC-02-DW4V 3" PANEL OUTSIDE CORNER W/ 2 PC EXTRUSION AR-OC-03-DW4V 4" PANEL OUTSIDE CORNER W/ 2 PC EXTRUSION AR-OC-05-DW4V OUTSIDE CORNER WITH FLASHING AR-IC-01-DW4V INSIDE CORNER WITH 2-PC EXTRUSION AR-IC-02-DW4V INSIDE CORNER WITH FLASHING www.kingspanpanels.ca C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp www.kingspanpanels.us 6/25/21

Upload: others

Post on 07-Sep-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

INDEX SHEET

DETAIL #:

DATE:

XX-XX-XX-DW4V

DW-4000 - VERTICAL INSTALLATION

AR-PJ-01-DW4V 2" VERTICAL PANEL JOINT

AR-PJ-02-DW4V 2 1/2" VERTICAL PANEL JOINT

AR-PJ-03-DW4V 3" VERTICAL PANEL JOINT

AR-PJ-04-DW4V 4" VERTICAL PANEL JOINT

AR-PJ-05-DW4V 2" VERTICAL PANEL W/

1

2

" REVEAL

AR-PJ-06-DW4V 2 1/2" VERTICAL PANEL W/

1

2

" REVEAL

AR-PJ-07-DW4V 3" VERTICAL PANEL W/

1

2

" REVEAL

AR-PJ-08-DW4V 4" VERTICAL PANEL W/

1

2

" REVEAL

AR-PJ-09-DW4V PANEL W/ CUSTOM REVEAL

AR-PJ-10-DW4V DW4000S PANEL PROFILE

AR-PJ-11-DW4V PANELS OVER STRUCTURAL STEEL

AR-PJ-12-DW4V PANELS OVER METAL STUDS

AR-PJ-13-DW4V PANELS OVER CONCRETE

AR-PJ-14-DW4V DESIGNWALL 2000 TO 4000

AR-PJ-15-DW4V DESIGNWALL 2000 TO 4000

AR-BS-01-DW4V BASE DETAIL - OVERHANG

AR-BS-02-DW4V BASE DETAIL - FLUSH

AR-BS-03-DW4V FLUSH BASE WITH EXTRUSION

AR-BS-04-DW4V OVERHANG BASE WITH EXTRUSION

AR-OC-01-DW4V 2" PANEL OUTSIDE CORNER W/ 2-PC EXTRUSION

AR-OC-02-DW4V 3" PANEL OUTSIDE CORNER W/ 2 PC EXTRUSION

AR-OC-03-DW4V 4" PANEL OUTSIDE CORNER W/ 2 PC EXTRUSION

AR-OC-05-DW4V OUTSIDE CORNER WITH FLASHING

AR-IC-01-DW4V INSIDE CORNER WITH 2-PC EXTRUSION

AR-IC-02-DW4V INSIDE CORNER WITH FLASHING

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 2: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

INDEX SHEET

DETAIL #:

DATE:

XX-XX-XX-DW4V

DW-4000 - VERTICAL INSTALLATION

AR-FO-01-DW4V DOOR HEAD W/ DRIP EDGE

AR-FO-02-DW4V DOOR HEAD WITH EXTRUSION

AR-FO-03-DW4V DOOR JAMB WITH FLASHING

AR-FO-04-DW4V DOOR JAMB WITH EXTRUSION

AR-FO-05-DW4V WINDOW. HEAD WITH EXTRUSION

AR-FO-06-DW4V WINDOW HEAD WITH FLASHING

AR-FO-07-DW4V WINDOW JAMB WITH EXTRUSION

AR-FO-08-DW4V WINDOW JAMB WITH FLASHING

AR-FO-09-DW4V WINDOW SILL WITH EXTRUSION

AR-FO-10-DW4V WINDOW SILL WITH FLASHING

AR-FO-11-DW4V LOUVER W/ FIELD CUT HEAD

AR-FO-12-DW4V LOUVER WITH FIELD CUT JAMB

AR-FO-13-DW4V LOUVER SILL WITH FIELD CUT END

AR-SF-01-DW4V SOFFIT W/ EXTRUSION

AR-SF-02-DW4V SOFFIT W/ FLASHING

AR-SF-03-DW4V TRANSVERSE BENT SOFFIT

AR-SF-04-DW4V END WALL W/ EXTRUSION

AR-SF-05-DW4V END WALL W/ FLASHING

AR-SJ-01-DW4V STACK JOINT

AR-SJ-02-DW4V STACK JOINT W/ EXTRUSION

AR-PR-01-DW4V PARAPET COPING

AR-PR-02-DW4V PARAPET W/ FLUSH TRIM

AR-PR-03-DW4V PARAPET W/ PROFILED TRIM

AR-TL-01-DW4V WALL PENETRATION

AR-TL-02-DW4V PIPE PENETRATION

AR-TL-03-DW4V PENETRATION DETAIL

AR-TL-04-DW4V TRIM END LAP

AR-TL-05-DW4V TRIM END LAP WITH HEM

AR-TL-06-DW4V MENDING PLATE WITH SHINGLE LAP

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 3: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

INDEX SHEET

DETAIL #:

DATE:

XX-XX-XX-DW4V

DW-4000 - VERTICAL INSTALLATION

AR-TL-07-DW4V TRIM END LAP WITH LAP STRIP

AR-TL-08-DW4V TRIM AT FRAMED OPENING

AR-TL-09-DW4V 2" EXTRUSION

AR-TL-10-DW4V 2" EXTRUSION

AR-TL-11-DW4V 2.5" EXTRUSION

AR-TL-12-DW4V 3" EXTRUSION

AR-TL-13-DW4V 4" EXTRUSION

AR-TL-14-DW4V EXTRUSION LAP STRIPS

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 4: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

ARCHITECTURAL

DISCLAIMER

DETAIL #:

DATE:

AR-DS-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

DISCLAIMERS:

THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED

COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.

LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED

ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR

BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER).

FOR CLARITY, ALL DETAILS SHOWN WITH (1)

1

4

"-14 HEX HEAD FASTENER WITH WASHER -

CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY

REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT RECOMMENDATIONS.

ALL STRUCTURAL SUPPORTS ARE NOT BY KINGSPAN AND ARE SHOWN FOR CLARIFICATION

PURPOSES ONLY.

6/25/21

Page 5: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

DIRECTION OF INSTALLATION

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

FASTENING CLIP

1/16" NOMINAL JT.

24", 30" OR 36" MODULE STANDARD

FACE OF PANEL

HORIZONTAL SUPPORT

BY OTHERS

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

FACE SHEET WEDGE GASKET

2"

(2)1/4"-14 x 2" DP3 HWH FASTENER

PER CLIP. (USE 3" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

2" VERTICAL

PANEL JOINT

DETAIL #:

DATE:

AR-PJ-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 6: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FASTENING CLIP

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

2

1

2

"

DIRECTION OF INSTALLATION

FACE OF PANEL

S.S. FASTENING CLIP WITH PVC

FACE SHEET WEDGE GASKET

FOAM TAPE STRIP SEAL

HORIZONTAL SUPPORT

BY OTHERS

1/16" NOMINAL JT.

24", 30" OR 36" MODULE STANDARD

(2)1/4"-14 x 2 1/2" DP3 HWH FASTENER

PER CLIP. (USE 4" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

2 1/2" VERTICAL

PANEL JOINT

DETAIL #:

DATE:

AR-PJ-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 7: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

FASTENING CLIP

3"

DIRECTION OF INSTALLATION

FACE OF PANEL

S.S. FASTENING CLIP WITH PVC

FACE SHEET WEDGE GASKET

FOAM TAPE STRIP SEAL

HORIZONTAL SUPPORT

BY OTHERS

1/16" NOMINAL JT.

24", 30" OR 36" MODULE STANDARD

(2)1/4"-14 x 3" DP3 HWH FASTENER

PER CLIP. (USE 4" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

3" VERTICAL

PANEL JOINT

DETAIL #:

DATE:

AR-PJ-03-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 8: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

FASTENING CLIP

4"

DIRECTION OF INSTALLATION

FACE OF PANEL

S.S. FASTENING CLIP WITH PVC

FACE SHEET WEDGE GASKET

FOAM TAPE STRIP SEAL

HORIZONTAL SUPPORT

BY OTHERS

1/16" NOMINAL JT.

24", 30" OR 36" MODULE STANDARD

(2)1/4"-14 x 4" DP3 HWH FASTENER

PER CLIP. (USE 5" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

4" VERTICAL

PANEL JOINT

DETAIL #:

DATE:

AR-PJ-04-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 9: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

DIRECTION OF INSTALLATION

FASTENING CLIP

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

FACE OF PANEL

HORIZONTAL SUPPORT

BY OTHERS

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

FACE SHEET WEDGE GASKET

2"

1/2" REVEAL

24", 30" OR 36" MODULE STANDARD

(2)1/4"-14 x 2" DP3 HWH FASTENER

PER CLIP. (USE 3" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

2" VERTICAL PANEL

W/

1

2

" REVEAL

DETAIL #:

DATE:

AR-PJ-05-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 10: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FASTENING CLIP

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

2

1

2

"

DIRECTION OF INSTALLATION

FACE OF PANEL

FACE SHEET WEDGE GASKET

HORIZONTAL SUPPORT

BY OTHERS

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

1/2" REVEAL

24", 30" OR 36" MODULE STANDARD

(2)1/4"-14 x 2 1/2" DP3 HWH FASTENER

PER CLIP. (USE 4" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

DETAIL #:

DATE:

AR-PJ-06-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

2 1/2" VERTICAL PANEL

W/

1

2

" REVEAL 6/25/21

Page 11: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

FASTENING CLIP

3"

DIRECTION OF INSTALLATION

FACE OF PANEL

FACE SHEET WEDGE GASKET

HORIZONTAL SUPPORT

BY OTHERS

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

1/2" REVEAL

24", 30" OR 36" MODULE STANDARD

(2)1/4"-14 x 3" DP3 HWH FASTENER

PER CLIP. (USE 4" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

DETAIL #:

DATE:

AR-PJ-07-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

3" VERTICAL PANEL

W/

1

2

" REVEAL

6/25/21

Page 12: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

FASTENING CLIP

4"

DIRECTION OF INSTALLATION

FACE OF PANEL

FACE SHEET WEDGE GASKET

HORIZONTAL SUPPORT

BY OTHERS

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

1/2" REVEAL

24", 30" OR 36" MODULE STANDARD

(2)1/4"-14 x 4" DP3 HWH FASTENER

PER CLIP. (USE 5" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

DETAIL #:

DATE:

AR-PJ-08-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

4" VERTICAL PANEL

W/

1

2

" REVEAL

6/25/21

Page 13: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

CONTACT KINGSPAN TECHNICAL SERVICES

FOR SPECIFIC PROJECT FASTENING REQUIREMENTS

FASTENING CLIP

DIRECTION OF INSTALLATION

FACE OF PANEL

FACE SHEET WEDGE GASKET

(2) 1/4"-14 HWH FASTENERS PER CLIP

HORIZONTAL SUPPORT

BY OTHERS

6" MAX.

24", 30" OR 36" MODULE STANDARD

REVEAL MODIFICATION

BUILT INTO MALE EDGE

OF PANEL

11

16

"

2", 2

.5

", 3

", O

R 4

"

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

24", 30" OR 36" MODULE STANDARD

*PRE-DRILLING REQ'D*

FACTORY BUTYL CAULK INSIDE

POCKET OF LINER SHEET

PANEL W/ CUSTOM

REVEAL

DETAIL #:

DATE:

AR-PJ-09-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 14: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

24", 30", OR 36" MODULE STANDARD

3

4

" STRIATION PITCH

FACE OF PANEL

REVEAL

2", 2.5", 3", O

R 4"

STRIATED FACE SHEET

STRIATION DEPTH

.035 INCH

FACE SHEET WEDGE GASKET

FACTORY BUTYL CAULKING

DETAIL #:

DATE:

AR-PJ-10-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

DW4000S PANEL

PROFILE

6/25/21

Page 15: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

HORIZONTAL

GIRT

HORIZONTAL

ANGLE

HORIZONTAL

GIRT

VERTICAL

PANELS

ALWAYS ATTACH VERTICAL PANELS

TO HORIZONTALLY ORIENTED

SUPPORTS

PANELS OVER

STRUCTURAL STEEL

DETAIL #:

DATE:

AR-PJ-11-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 16: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

HORIZONTAL

SUBGIRT

VERTICAL

PANELS

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

VERTICAL

STUDS

SHEATHING

OPTIONAL

HORIZONTAL

SUBGIRT

ALWAYS ATTACH VERTICAL PANELS

TO HORIZONTALLY ORIENTED

SUPPORTS

PANELS OVER METAL

STUDS

DETAIL #:

DATE:

AR-PJ-12-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 17: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

HORIZONTAL

SUBGIRT

PRECAST OR

CMU WALL

ALWAYS ATTACH VERTICAL PANELS

TO HORIZONTALLY ORIENTED

SUPPORTS

VERTICAL

PANELS

*SUBGIRT DEPTH MUST BE

NO SHALLOWER THAN

SHANK PENETRATION OF

FASTENERS BEHIND LINER

SHEET

PANELS OVER

CONCRETE

DETAIL #:

DATE:

AR-PJ-13-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 18: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

DIRECTION OF INSTALLATION

DESIGNWALL 2000 PANEL

FACE SHEET WEDGE GASKET

HORIZONTAL SUPPORT

BY OTHERS

24", 30" OR 36" MODULE STANDARD

DESIGNWALL 4000 PANEL

APPLY BUTYL CAULK INSIDE

FEMALE POCKET OF LINER

SHEET OF DESIGNWALL 2000

PANEL PRIOR TO JOINT

ENGAGEMENT WITH

DESIGNWALL 4000 PANEL

DO NOT ENGAGE MALE LEG OF

DW4000 INTO EMPTY POCKET

WITH NO SEAL

(2)1/4"-14 x 3" DP3 HWH FASTENER

PER CLIP. (USE 4" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

DW2000 TO DW4000

DETAIL #:

DATE:

AR-PJ-14-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 19: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

REMOVE FINNED GASKET FROM

MALE LEG OF LINER SHEET OF

DESIGNWALL 2000 PANEL

PRIOR TO JOINT ENGAGMENT

WITH DESIGNWALL 4000 PANEL

DO NOT ENGAGE GASKET INTO

FACTORY BUTYL CAULK

DIRECTION OF INSTALLATION

DESIGNWALL 4000 PANEL

FACE SHEET WEDGE GASKET

HORIZONTAL SUPPORT

BY OTHERS

24", 30" OR 36" MODULE STANDARD

DESIGNWALL 2000 PANEL

(2)1/4"-14 x 3" DP3 HWH FASTENER

PER CLIP. (USE 4" WHEN FASTENING

THROUGH SHEATHING/DENSGLASS)

*PRE-DRILLING REQ'D*

DW2000 TO DW4000

DETAIL #:

DATE:

AR-PJ-15-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 20: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

2", 2

1

2

", 3", OR 4"

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PRE-DRILLING REQ'D*

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

TRIMLESS END

BASE FLASHING

BASE DETAIL -

OVERHANG

DETAIL #:

DATE:

AR-BS-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 21: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

TRIMLESS END

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PRE-DRILLING REQ'D*

2", 2

1

2

", 3", OR 4"

CONTINUOUS BUTYL SEALANT

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

BASE FLASHING

URETHANE SEALANT

NOT BY KINGSPAN

BASE DETAIL - FLUSH

DETAIL #:

DATE:

AR-BS-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 22: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

ALUMINUM BASE

EXTRUSION

1/4" DIA. WEEP HOLE

24" O.C. FIELD DRILLED

1"

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PRE-DRILLING REQ'D*

2", 2

1

2

", 3", OR 4"

FIELD CUT 6" SPLICE PLATE

FROM SPLICE EXTRUSION

NOTE: BREAKFORMED SPLICE FOR 2

1

2

" AND 4" PANEL EXTRUSIONS

CONTINUOUS BUTYL SEALANT

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

4" F

OR

2" &

2.5" P

AN

ELS

5" F

OR

3" &

4" P

AN

ELS

FLUSH BASE WITH

EXTRUSION

DETAIL #:

DATE:

AR-BS-03-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 23: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

ALUMINUM BASE

EXTRUSION

1/4" DIA. WEEP HOLE

24" O.C. FIELD DRILLED

4" F

OR

2" &

2.5" P

AN

ELS

1"

2", 2

1

2

", 3", OR 4"

FIELD CUT 6" SPLICE PLATE

FROM SPLICE EXTRUSION

NOTE: BREAKFORMED SPLICE FOR 2

1

2

" AND 4" PANEL EXTRUSIONS

STEEL BASE ANGLE

BY OTHERS SEAL TO SLAB

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PRE-DRILLING REQ'D*

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

5" F

OR

3" &

4" P

AN

ELS

OVERHANG BASE W/

EXTRUSION

DETAIL #:

DATE:

AR-BS-04-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 24: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

2-PC SNAP-TOGETHER OUTSIDE

CORNER EXTRUSION 3.5" x 3.5"

GIRT LINE

3

1

2

"

3

1

2

"

FIELD CUT

PANELS TO SUIT

2

"

F.I.P. INSULATION

(NOT BY KINGSPAN)

BUTYL SEALANT

" - 14 "LOW PROFILE" FASTENER

AT GIRTS

OUTSIDE CORNER

WITH 2-PC EXTRUSION

DETAIL #:

DATE:

AR-OC-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 25: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

2-PC SNAP-TOGETHER OUTSIDE

CORNER EXTRUSION 5" x 5"

GIRT LINE

FIELD CUT

PANELS TO SUIT

3

"

BUTYL SEALANT

5

"

5

"

SEALANT

1

4

" - 14 "LOW PROFILE" FASTENER

AT GIRTS

3" PANEL OUTSIDE

CORNER W/

2 PC EXTRUSION

DETAIL #:

DATE:

AR-OC-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 26: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

2-PC SNAP-TOGETHER OUTSIDE

CORNER EXTRUSION 6" x 6"

GIRT LINE

FIELD CUT

PANELS TO SUIT

4

"

BUTYL SEALANT

6

"

6

"

SEALANT

1

4

" - 14 "LOW PROFILE" FASTENER

AT GIRTS

DETAIL #:

DATE:

AR-OC-03-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

4" PANEL OUTSIDE

CORNER W/

2 PC EXTRUSION

6/25/21

Page 27: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

GIRT LINE

(2) 1/4"-14 HWH FASTENERS

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

2", 2

1

2

", 3", OR 4"

FORMED CORNER TRIM

POP RIVETS 12" O.C.

SEALANT

FIELD CUT

PANELS TO SUIT

1

4

" - 14 DP3 CONCEALOR SCREW

AT GIRTS

BUTYL SEALANT

INTERIOR MENDING PLATE

FASTEN TO LINER SHEET

PER CLIP *PRE-DRILLING REQ'D*

DETAIL #:

DATE:

AR-OC-05-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

OUTSIDE CORNER W/

FLASHING6/25/21

Page 28: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FIELD CUT

PANELS TO SUIT

CONTINUOUS BUTYL SEALANT

2

"

O

R

3

"

GIRT LINE

SEALANT

2-PC SNAP-TOGETHER INSIDE

CORNER EXTRUSION 2.5" x 2.5"

2

1

2

"

*NOTE: 2-PC INSIDE CORNER EXTRUSION AVAILABLE FOR 2" AND 3" PANELS ONLY

1

4

" - 14 "LOW PROFILE" FASTENER

AT GIRTS

INSIDE CORNER

WITH 2-PC EXTRUSION

DETAIL #:

DATE:

AR-IC-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 29: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

GIRT LINE

(2) 1/4"-14 HWH FASTENERS

S.S. FASTENING CLIP WITH PVC

FOAM TAPE STRIP SEAL

2", 2

1

2

", 3

", O

R 4

"

1

4

" - 14 "LOW PROFILE" FASTENER

AT GIRTS

FIELD CUT

PANELS TO SUIT

FORMED CORNER TRIM

SEALANT

POP RIVETS 12" O.C.

BUTYL SEALANT

INTERIOR MENDING PLATE

FASTEN TO LINER SHEET

CLIP *PRE-DRILLING REQ'D*

INSIDE CORNER WITH

FLASHING

DETAIL #:

DATE:

AR-IC-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 30: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

EXTERIOR CAP TRIM

POP RIVETS

EXPOSED SEALANT

(NOT BY KINGSPAN)

FIELD CUT PANEL TO SUIT

DOOR FRAME

(NOT BY KINGSPAN)

FRAMED OPENING

(NOT BY KINGSPAN)

2", 2.5", 3", OR 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

2-PC HEAD FLASHING

NON-SKINNING BUTYL

APPLIED BETWEEN

FLASHING PIECES

DOOR HEAD W/ DRIP

EDGE

DETAIL #:

DATE:

AR-FO-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 31: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

EXPOSED SEALANT

(NOT BY KINGSPAN)

FIELD CUT PANEL TO SUIT

DOOR FRAME

(NOT BY KINGSPAN)

FRAMED OPENING

(NOT BY KINGSPAN)

2", 2.5", 3", OR 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

STANDARD SOFFIT

EXTRUSION

1"

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

DOOR HEAD WITH

EXTRUSION

DETAIL #:

DATE:

AR-FO-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 32: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FRAMED OPENING

(NOT BY KINGSPAN)

DOOR FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

POP RIVETS

JAMB TRIM

FIELD CUT PANELS TO SUIT

2", 2.5", 3", O

R 4"

1

4

" - 14 "LOW PROFILE" FASTENER

SEALANT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

NON-SKINNING BUTYL APPLIED

BETWEEN JAMB TRIM AND

JAMB MENDING PLATE

JAMB MENDING PLATE

CONTINUOUS BUTYL SEALANT

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

DOOR JAMB WITH

FLASHING

DETAIL #:

DATE:

AR-FO-03-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 33: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FRAMED OPENING

(NOT BY KINGSPAN)

DOOR FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

SEALANT

FIELD CUT PANELS TO SUIT

2", 2.5", 3", O

R 4"

CONTINUOUS BUTYL SEALANT

1

4

" - 14 "LOW PROFILE" FASTENER

TWO PIECE JAMB

EXTRUSION

FLASHING TRIM

NOT BY KINGSPAN

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

DOOR JAMB W/

EXTRUSION

DETAIL #:

DATE:

AR-FO-04-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 34: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

EXPOSED SEALANT

(NOT BY KINGSPAN)

WINDOW FRAME

(NOT BY KINGSPAN)

FIELD DRILL 1/4" Ø WEEP HOLES

(NOT BY KINGSPAN)

NOTE: 1) SEE FLUSHGLAZE 7500 DETAILS FOR INTEGRATED WINDOW DESIGNS

STANDARD SOFFIT

EXTRUSION

1"

2", 2.5", 3", OR 4"

FRAMED OPENING

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

WINDOW HEAD WITH

EXTRUSION

DETAIL #:

DATE:

AR-FO-05-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 35: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

EXPOSED SEALANT

(NOT BY KINGSPAN)

WINDOW FRAME

(NOT BY KINGSPAN)

2) SEE FLUSHGLAZE 7500 DETAILS FOR INTEGRATED WINDOW DESIGNS

2", 2.5", 3", OR 4"

TRIMLESS END

FRAMED OPENING

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

2-PC HEAD FLASHING

NON-SKINNING BUTYL

APPLIED BETWEEN

FLASHING PIECES

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

WINDOW HEAD

W/FLASHING

DETAIL #:

DATE:

AR-FO-06-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 36: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FIELD CUT PANELS TO SUIT

FRAMED OPENING

(NOT BY KINGSPAN)

WINDOW FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

TWO PIECE JAMB

EXTRUSION

NOTE: 1) SEE FLUSHGLAZE 7500 DETAILS FOR INTEGRATED WINDOW DESIGNS

2", 2.5", 3", O

R 4"

FLASHING TRIM

NOT BY KINGSPAN

CONTINUOUS BUTYL SEALANT

SEALANT

1

4

" - 14 "LOW PROFILE" FASTENER

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

WINDOW JAMB W/

EXTRUSION

DETAIL #:

DATE:

AR-FO-07-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 37: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FIELD CUT PANELS TO SUIT

WINDOW FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

2", 2

.5

", 3

", O

R 4

"

1

4

" - 14 "LOW PROFILE" FASTENER

POP RIVETS

JAMB TRIM

SEALANT

FRAMED OPENING

(NOT BY KINGSPAN)

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

NON-SKINNING BUTYL APPLIED

BETWEEN JAMB TRIM AND

JAMB MENDING PLATE

JAMB MENDING PLATE

CONTINUOUS BUTYL SEALANT

2) SEE FLUSHGLAZE 7500 DETAILS FOR INTEGRATED WINDOW DESIGNS

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

WINDOW JAMB W/

FLASHING

DETAIL #:

DATE:

AR-FO-08-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 38: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

OPTIONAL WIPER

GASKET

(FIELD INSTALLED)

NOTE: 1) SEE FLUSHGLAZE 7500 DETAILS FOR INTEGRATED WINDOW DESIGNS

2", 2.5", 3", OR 4"

SEALANT

WINDOW FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

SILL EXTRUSION

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

BREAK-FORMED 6"

SPLICE PLATE BED

SEALED IN SILICONE

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

SILL MENDING PLATE

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

NON-SKINNING BUTYL APPLIED

BETWEEN SILL EXTRUSION AND

SILL MENDING PLATE

WINDOW SILL W/

EXTRUSION

DETAIL #:

DATE:

AR-FO-09-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 39: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

2", 2.5", 3", OR 4"

SEALANT

WINDOW FRAME

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

EXTERIOR SILL TRIM

FRAMED OPENING

(NOT BY KINGSPAN)

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

NON-SKINNING BUTYL APPLIED

BETWEEN SILL TRIM AND SILL

MENDING PLATE

SILL MENDING PLATE

2) SEE FLUSHGLAZE 7500 DETAILS FOR INTEGRATED WINDOW DESIGNS

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

WINDOW SILL W/

FLASHING

DETAIL #:

DATE:

AR-FO-10-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 40: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

EXTERIOR CAP TRIM

EXPOSED SEALANT

(NOT BY KINGSPAN)

FIELD CUT PANEL TO SUIT

FRAMED OPENING

(NOT BY KINGSPAN)

LOUVER UNIT

(NOT BY KINGSPAN)

POP RIVETS

2", 2.5", 3", OR 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

2-PC HEAD FLASHING

NON-SKINNING BUTYL

APPLIED BETWEEN

FLASHING PIECES

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

LOUVER W/ FIELD CUT

HEAD

DETAIL #:

DATE:

AR-FO-11-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 41: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

LOUVER UNIT

(NOT BY KINGSPAN)

JAMB TRIM

FRAMED OPENING

(NOT BY KINGSPAN)

EXPOSED SEALANT

(NOT BY KINGSPAN)

POP RIVETS

2", 2

.5

", 3

", O

R 4

"

1

4

" - 14 "LOW PROFILE" FASTENER

SEALANT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FIELD CUT PANELS TO SUIT

NON-SKINNING BUTYL APPLIED

BETWEEN JAMB TRIM AND

JAMB MENDING PLATE

JAMB MENDING PLATE

CONTINUOUS BUTYL SEALANT

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

LOUVER W/ FIELD CUT

JAMB

DETAIL #:

DATE:

AR-FO-12-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 42: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

EXTERIOR SILL TRIM

2", 2.5", 3", OR 4"

EXPOSED SEALANT

(NOT BY KINGSPAN)

FIELD CUT PANEL

TO SUIT

POP RIVETS

LOUVER UNIT

(NOT BY KINGSPAN)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FRAMED OPENING

(NOT BY KINGSPAN)

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

NON-SKINNING BUTYL APPLIED

BETWEEN SILL TRIM AND SILL

MENDING PLATE

SILL MENDING PLATE

NOTE: 1) SEE DETAIL AR-TL-04-DW4H, AR-TL-05-DW4H, AR-TL-06-DW4H, AR-TL-07-DW4H

AND AR-TL-08-DW4H FOR TYPICAL TRIM LAP INSTRUCTIONS

LOUVER SILL W/ FIELD

CUT END

DETAIL #:

DATE:

AR-FO-13-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 43: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

STEEL FRAMING

BY OTHERS

ALUMINUM SOFFIT

EXTRUSION

1/4" DIA. WEEP HOLE @

24" O.C. FIELD DRILLED

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

1"

1

1

2

"

2", 2

1

2

", 3", or 4"

FIELD CUT 6" SPLICE PLATE

FROM SPLICE EXTRUSION

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

SOFFIT W/ EXTRUSION

DETAIL #:

DATE:

AR-SF-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 44: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

STEEL FRAMING

BY OTHERS

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

2", 2

1

2

", 3", or 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

TRIMLESS END

POP RIVETS 12" O.C.

SEALANT

SOFFIT FLASHING

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

SOFFIT W/ FLASHING

DETAIL #:

DATE:

AR-SF-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 45: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

STEEL FRAMING

BY OTHERS

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

2", 2

1

2

", 3", or 4"

FACTORY TRANSVERSE BEND

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

SH

OR

T LE

G 6'-0 M

AX

IM

UM

, 14'-0 M

AX

IM

UM

P

AN

EL LE

NG

TH

TRANSVERSE BENT

SOFFIT

DETAIL #:

DATE:

AR-SF-03-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 46: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FIELD CUT PANEL

TO SUIT CONDITION

SEALANT

GIRT LINE

3"

ENDWALL EXTRUSION

PART "B" CAP

2", 2

1

2

", 3", O

R 4"

ENDWALL EXTRUSION

PART "A" RECEIVER

1

4

" - 14 "LOW PROFILE" FASTENER

AT GIRTS

SEALANT

BUTYL SEALANT

END WALL W/

EXTRUSION

DETAIL #:

DATE:

AR-SF-04-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 47: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FIELD CUT PANEL

TO SUIT CONDITION

SEALANT

GIRT LINE

2", 2

1

2

", 3", O

R 4"

1

4

" - 14 "LOW PROFILE" FASTENER

AT GIRTS

SEALANT

FORMED ENDWALL TRIM

POP RIVETS 12" O.C.

BUTYL SEALANT

INTERIOR MENDING PLATE

FASTEN TO LINER SHEET

END WALL W/

FLASHING

DETAIL #:

DATE:

AR-SF-05-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 48: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

SILICONE SEALANT &

BACKER ROD

ZERO PROFILE HORIZONTAL

JOINT FLASHING FOR

DRAINAGE

INSTALLER TO PLUG

TOPS OF VERTICAL

JOINTS WITH SEALANT

STEEL FRAMING

BY OTHERS

5" M

IN

. B

EA

RIN

G

DO NOT CAULK HERE

ALLOW TO DRAIN

5

8

"

2", 2

1

2

", 3", or 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

MENDING PLATE WITH BUTYL

CAULKING TO UNDERSIDE OF

HORIZONTAL JOINT FLASHING

TRIMLESS STACK

JOINT

DETAIL #:

DATE:

AR-SJ-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 49: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

STEEL FRAMING

BY OTHERS

HORIZONTAL JOINT

EXTRUSION W/ WEEP

HOLES @ 24" O.C.

5" M

IN

. B

EA

RIN

G

3

1

4

"

1"

SEALANT

MENDING PLATE WITH

BUTYL CAULKING TO

UNDERSIDE OF EXTRUSION

2", 2

1

2

", 3", or 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

BREAK-FORMED 6"

SPLICE PLATES BED

SEALED IN BUTYL

STACK JOINT W/

EXTRUSION

DETAIL #:

DATE:

AR-SJ-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 50: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

4"

STAINLESS STEEL SCREW

PAINTED TO MATCH

PANEL. 12" O.C.

FABRICATED METAL

FLASHING EXTENSION

SILICONE SEALANT

PARAPET COPING EXTRUSION

2", 2

1

2

", 3", or 4"

1"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FABRICATED METAL CLEAT

WITH SCREWS 12" O.C.

POP RIVETS 12" O.C.

MEMBRANE ROOF &

PARAPET BACKER

(NOT BY KINGSPAN)

SILICONE SEALANT

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

BREAK-FORMED 6"

SPLICE PLATE BED

SEALED IN SILICONE

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

PARAPET COPING

DETAIL #:

DATE:

AR-PR-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 51: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

STAINLESS STEEL SCREW

PAINTED TO MATCH

PANEL. 12" O.C.

FABRICATED METAL

SPRING CLEAT

2", 2

1

2

", 3", or 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

FABRICATED METAL HOOK

CLEAT WITH LOW PROFILE

SCREWS 12" O.C.

MEMBRANE ROOF &

PARAPET BACKER

(NOT BY KINGSPAN)

SILICONE SEALANT

FABRICATED METAL COPING

WITH BED SEALED INSIDE

SPLICE PLATES

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

WRAP MEMBRANE (NOT BY KINGSPAN)

ADHERE TO EXTERIOR PANEL FACE

PARAPET W/ FLUSH

TRIM

DETAIL #:

DATE:

AR-PR-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 52: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

STAINLESS STEEL SCREW

PAINTED TO MATCH

PANEL. 12" O.C.

2", 2

1

2

", 3", or 4"

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

VERTICAL PANEL JOINT

MEMBRANE ROOF &

PARAPET BACKER

(NOT BY KINGSPAN)

FABRICATED METAL COPING

WITH BED SEALED INSIDE

SPLICE PLATES

POP RIVETS 12" O.C.

HORIZONTAL SUPPORTS

NOT BY KINGSPAN

FASTENING CLIP WITH

(2)

1

4

"-14 HWH FASTENERS

*PER-DRILLING REQ'D*

WRAP MEMBRANE (NOT BY KINGSPAN)

ADHERE TO EXTERIOR PANEL FACE

PARAPET W/ PROFILED

TRIM

DETAIL #:

DATE:

AR-PR-03-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 53: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

SECTION 'A-A'

PENETRATION

(NOT BY KINGSPAN)

ELEVATION

BACKER ROD AND

SEALANT

(NOT BY KINGSPAN)

POP RIVET

'A'

TRIM

FASTENER

(AS REQUIRED)

'A'

PENETRATION

(NOT BY KINGSPAN)

BACKER ROD AND

SEALANT

(NOT BY KINGSPAN)

FLASHING

SEALANT

(NOT BY KINGSPAN)

SEALANT

(NOT BY KINGSPAN)

NOTES: 1. DO NOT ALIGN PENETRATIONS AT PANEL JOINT LOCATIONS.

2. FLASHING AT PENETRATIONS TO BE FIELD FABRICATED FROM

FLATSTOCK SHEETS AS NECESSARY

WALL PENETRATION

SECTION

DETAIL #:

DATE:

AR-TL-01-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 54: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

PIPE RING WITH SEALANT

NOT BY KINGSPAN

PIPE PENETRATION

INSULATION FILL

NOT BY KINGSPAN

FIELD CUT HOLE

IN PANEL FOR PIPE

PIPE PENETRATION

DETAIL #:

DATE:

AR-TL-02-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 55: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

FASTENER AS REQUIRED

SEALANT (NOT BY KINGSPAN)

FLASHING AS REQUIRED

INSULATION FILL

(NOT BY KINGSPAN)

SEALANT (NOT BY KINGSPAN)

SEALANT (NOT BY KINGSPAN)

FLASHING AS REQUIRED

F.I.P. INSULATION

(NOT BY KINGSPAN)

FASTENER AS REQUIRED

SEALANT (NOT BY KINGSPAN)

FASTENER AS REQUIRED

FASTENER AS REQUIRED

NOTE: FLASHING AT PIPE PENETRATIONS

TO BE FIELD FABRICATED FROM FLATSTOCK

SHEETS AS NECESSARY

NOTE: DO NOT ALIGN PENETRATIONS

AT PANEL JOINT LOCATIONS.

PENETRATION DETAIL

DETAIL #:

DATE:

AR-TL-03-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 56: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

M

I

N

.

3

"

T

R

I

M

L

A

P

M

I

N

.

3

"

T

R

I

M

L

A

P

(2) BEADS

BUTYL SEALANT

TRIM END LAP

DETAIL #:

DATE:

AR-TL-04-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 57: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

M

I

N

.

3

"

T

R

I

M

L

A

P

M

I

N

.

3

"

T

R

I

M

L

A

P

(2) BEADS

BUTYL SEALANT

FIELD NOTCH HEM(S)

AS REQUIRED

(NOT BY KINGSPAN)

TRIM LAP W/ HEM

DETAIL #:

DATE:

AR-TL-05-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 58: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

(2) BEADS

BUTYL SEALANT

(2) BEADS

BUTYL SEALANT

MIN

. 3"

TR

IM

LA

P

CARRY BUTYL SEALANT

ACROSS TOP TO PREVENT

WATER SIPHONING

MENDING PLATE W/

SHINGLE LAP

DETAIL #:

DATE:

AR-TL-06-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us6/25/21

Page 59: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

(2) BEADS

BUTYL SEALANT

N

O

M

.

1

4

"

G

A

P

8" LONG LAP STRIP

TRIM END LAP WITH

LAP STRIP

DETAIL #:

DATE:

AR-TL-07-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 60: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

USE DUPONT

FLEXWRAP NF 6" x 6"

PATCH

JAMB MENDING PLATE

OR FLASHING LEG

BEHIND PANEL

SILL MENDING PLATE

BEHIND PANEL

4" LAP BED SEALED IN

BUTYL CAULK

1" TAB UP BED SEALED IN

BUTYL CAULK

4" LAP BED SEALED IN

BUTYL CAULK

1" TAB DOWN BED SEALED

IN BUTYL CAULK

HEAD FLASHING

PEFORM THIS WORK PRIOR

TO INSTALLING PANELS

USE DUPONT

FLEXWRAP NF 6" x 6"

PATCH

CARRY NON-SKINNING BUTYL

REAR SEAL CAULK OVER THE

FLEXWRAP NF TAPE

HEAD FLASHING LEG

BEHIND PANEL

TRIM AT FRAMED

OPENINGS

DETAIL #:

DATE:

AR-TL-08-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 61: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

2" PANEL ENDWALL

EXTRUSION RECEIVER

DIE #11487

ENDWALL EXTRUSION CAP

6" SPLICE PLATE DIE

#13262

2" PANEL BASE

EXTRUSION DIE #11372

CAP DIE #11488

2" PANEL SOFFIT

EXTRUSION DIE #11423

2" PANEL HORIZONTAL

JOINT EXTRUSION DIE

#11298

PARAPET EXTRUSION

DIE # 13938

SILL EXTRUSION

DIE #13937

OUTSIDE CORNER

EXTRUSION

RECEIVER DIE

#13264

2" OUTSIDE CORNER

EXTRUSION CAP DIE

#13263

2" EXTRUSION

DETAIL #:

DATE:

AR-TL-09-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 62: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

INSIDE CORNER

EXTRUSION

RECEIVER DIE

#14298

2" INSIDE CORNER

EXTRUSION CAP

DIE #15693

2" EXTRUSION

DETAIL #:

DATE:

AR-TL-10-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 63: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

PARAPET EXTRUSION

SILL EXTRUSION

DIE #13937

DIE # 13938

2.5" TWO PIECE

ENDWALL/JAMB

EXTRUSION RECEIVER

DIE #16010

TWO PIECE

ENDWALL/JAMB

EXTRUSION CAP

DIE #11488

2.5" OUTSIDE CORNER

EXTRUSION RECEIVER

DIE #16006

BASE EXTRUSION

DIE # 16009

2.5" STANDARD SOFFIT

EXTRUSION DIE #16004

6" SPLICE PLATE DIE

#16003

2.5" PANEL HORIZONTAL

JOINT EXTRUSION DIE

#16005

2.5" EXTRUSION

DETAIL #:

DATE:

AR-TL-11-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 64: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

ENDWALL EXTRUSION CAP

3" PANEL BASE

EXTRUSION DIE #11366

3" PANEL ENDWALL

EXTRUSION RECEIVER

DIE #12714

CAP DIE #11488

3" PANEL HORIZONTAL

JOINT EXTRUSION DIE

#12861

3" STANDARD SOFFIT EXTRUSION

DIE #13789

PARAPET EXTRUSION

DIE # 13938

SILL EXTRUSION

DIE #13937

INSIDE CORNER

EXTRUSION

RECEIVER DIE

#14298

3" INSIDE CORNER

EXTRUSION CAP

DIE #14299

3" OUTSIDE CORNER

EXTRUSION

RECEIVER DIE #16017

3" OUTSIDE CORNER

EXTRUSION CAP DIE

#14108

6" SPLICE PLATE DIE

#13862

3" EXTRUSION

DETAIL #:

DATE:

AR-TL-12-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 65: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

4" OUTSIDE CORNER

EXTRUSION CAP

DIE #14109

PARAPET EXTRUSION

4" OUTSIDE CORNER

EXTRUSION RECEIVER

DIE #16016

SILL EXTRUSION

DIE #13937

DIE # 13938

TWO PIECE

ENDWALL/JAMB

EXTRUSION CAP

DIE #11488

4" TWO PIECE

ENDWALL/JAMB

EXTRUSION RECEIVER

DIE #16014

4" STANDARD BASE

EXTRUSION DIE #16011

4" STANDARD SOFFIT

EXTRUSION DIE #16012

6" SPLICE PLATE DIE

#16013

4" PANEL HORIZONTAL

JOINT EXTRUSION DIE

#16015

4" EXTRUSION

DETAIL #:

DATE:

AR-TL-13-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21

Page 66: DW-4000 - VERTICAL INSTALLATION · 2021. 6. 30. · designwall 4000 panel apply butyl caulk inside female pocket of liner sheet of designwall 2000 panel prior to joint engagement

LAP STRIPS FOR OUTSIDE CORNER

LAP STRIP FOR PARAPET EXTRUSION

LAP STRIP FOR BASE EXTRUSION

LAP STRIPS FOR INSIDE CORNER

EXTRUSIONEXTRUSION

JAMB EXTRUSION

LAP STRIP FOR TWO PIECE

LAP STRIP FOR SOFFIT EXTRUSION

EXTRUSION LAP

STRIPS

DETAIL #:

DATE:

AR-TL-14-DW4V

DW-4000 - VERTICAL INSTALLATION

www.kingspanpanels.ca

C:\Users\adam.rinder\Documents\BENCHMARK\Kingspan Benchmark Logo_RGB.bmp

www.kingspanpanels.us

6/25/21