e shutdown and signalling - thorne and derrick uk · 2010. 5. 7. · 415 2 max 2.5 type e0301- ex d...

1
Cornwallis Road, West Bromwich, West Midlands, B70 7DX, UK Tel: +44 (0)121 500 6161 ~ Fax: +44 (0)121 500 6300 Web: www.walsall-ltd.com ~ Email: [email protected] Walsall Middle East RAK Free Trade Zone, P. O. Box 10559 Ras Al Khaimah, United Arab Emirates Tel: +971 (0) 7 2660039 Fax: +971 (0) 7 2660242 Email: [email protected] Email: [email protected] Walsall North America 11490 Westheimer, Suite 850 Houston 77077 Texas, USA Tel: +1 (713) 425 6361 Fax: +1 (713) 783 0067 Walsall Asia Pacific 10 Upper Aljunied Link,York International Industrial Building #02-05 Singapore 367904 Tel: +65 (0) 6858-5259 Fax: +65 (0) 6858-6560 Email: [email protected] Walsall South America Av Nilo Pecanha, 50.Sala 1709. Centro, Rio De Janeiro, RJ, Brazil.CEP, 20020-906. Tel: +55 (21) 2025 1059 Fax: +55 (21) 3084-1446 Emergency Shutdown and Signalling Equipment 117 113 Ø8 120 113 A B C D 117 All Dimensions in mm. Description Switch Position Resistor (s) Product Code Fire Alarm without Resistors 1N/O and 1N/C - E030110 Fire Alarm with Series Resistors 1N/O and 1N/C To be specified E030111 Fire Alarm with end of the line Resistors 1N/O and 1N/C To be specified E030112 Fire Alarm with series & end of the line Resistors 1N/O and 1N/C To be specified E030113 ORDERING INFORMATION ELECTRICAL SPECIFICATION Operating Voltage Operating Current Conductor Size Volts Max Amps mm² Max 415 2 max 2.5 Type E0301- Ex d IIC Manual Call point with Break Glass in Cast Iron Material Cast Iron to 180BSI1452:1997 Finish Zinc rich epoxy powder primer and epoxy powder top coat Colour Red (Other colours available) Weight 4.5 Kg Cover Fixing M6 allen head stainless steel screws Gasket Nitrile O ring Plastic Components Polycarbonate Operator Flamepath Brass shaft in brass housing. Nitrile O ring seal Entries 1x20mm threaded hole in face A, fitted with a nylon Ex e stopping plug. 1x20mm threaded hole in face B, fitted with a nylon Ex e cable gland. 25mm entries are available as an option. Earthing Internal and external Ex e brass clamps on base. Earth on cover ENCLOSURE SPECIFICATION HAZARDOUS AREA SPECIFICATION Marking to 94/9/EC II 2 GD Type of Protection Ex d IIC T* Gb Ex tb IIIC T**°C Db Ambient Temp.°C Gas Temperature Class (T*C) Dust Temperature Class (T**)(°C) Min Max -20* +50 T6 80 * -40°C when used with a plug and gland rated to -40°C Ingress Protection IP66 to EN60529:1992 Area Classification Zones 1,2,21,22 Certification No. SIRA03ATEX1312

Upload: others

Post on 20-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: E shutdown and signalling - Thorne and Derrick UK · 2010. 5. 7. · 415 2 max 2.5 Type E0301- Ex d IIC Manual Call point with Break Glass in Cast Iron Material Cast Iron to 180BSI1452:1997

Cornwallis Road, West Bromwich, West Midlands, B70 7DX, UKTel: +44 (0)121 500 6161 ~ Fax: +44 (0)121 500 6300Web: www.walsall-ltd.com ~ Email: [email protected]

Walsall Middle EastRAK Free Trade Zone, P. O. Box 10559 Ras Al Khaimah, United Arab EmiratesTel: +971 (0) 7 2660039Fax: +971 (0) 7 2660242Email: [email protected]: [email protected]

Walsall North America 11490 Westheimer, Suite 850Houston 77077Texas, USATel: +1 (713) 425 6361Fax: +1 (713) 783 0067

Walsall Asia Pacific10 Upper Aljunied Link,York International Industrial Building #02-05 Singapore 367904Tel: +65 (0) 6858-5259Fax: +65 (0) 6858-6560Email: [email protected]

Walsall South AmericaAv Nilo Pecanha, 50.Sala 1709. Centro, Rio De Janeiro,RJ, Brazil.CEP, 20020-906.Tel: +55 (21) 2025 1059Fax: +55 (21) 3084-1446

Emergency Shutdown and Signalling Equipment

117

113

Ø8

120

113

A

B

C D

117

All Dimensions in mm.

Description Switch Position Resistor (s) Product Code

Fire Alarm without Resistors 1N/O and 1N/C - E030110

Fire Alarm with Series Resistors 1N/O and 1N/C To be specified E030111

Fire Alarm with end of the line Resistors 1N/O and 1N/C To be specified E030112

Fire Alarm with series & end of the line Resistors 1N/O and 1N/C To be specified E030113

ORDERING INFORMATION

ELECTRICAL SPECIFICATION

Operating Voltage Operating Current Conductor Size

Volts Max Amps mm² Max

415 2 max 2.5

Type E0301- Ex d IIC Manual Call point with Break Glass in Cast Iron

Material Cast Iron to 180BSI1452:1997

Finish Zinc rich epoxy powder primer and epoxy powder top coat

Colour Red (Other colours available)

Weight 4.5 Kg

Cover Fixing M6 allen head stainless steel screws

Gasket Nitrile O ring

Plastic Components Polycarbonate

Operator Flamepath Brass shaft in brass housing. Nitrile O ring seal

Entries 1x20mm threaded hole in face A, fitted with a nylon Ex e stopping plug. 1x20mm threaded hole in face B, fitted with a nylon Ex e cable gland. 25mm entries are available as an option.

Earthing Internal and external Ex e brass clamps on base. Earth on cover

ENCLOSURE SPECIFICATION

HAZARDOUS AREA SPECIFICATION

Marking to 94/9/EC II 2 GD

Type of Protection Ex d IIC T* GbEx tb IIIC T**°C Db

Ambient Temp.°C Gas Temperature Class (T*C)

Dust Temperature Class (T**)(°C)Min Max

-20* +50 T6 80

* -40°C when used with a plug and gland rated to -40°C

Ingress Protection IP66 to EN60529:1992

Area Classification Zones 1,2,21,22

Certification No. SIRA03ATEX1312