Dry Run Sensor WHITE PAPER e-SVwhite2 FEATURES The sensor is composed of a stainless steel body, a glass cap and a connecting cable. The sensor can be mounted directly on the fill plug of e-SV series pump. For the larger e-SV series sizes (33 thru 125SV) a suitable adapter is supplied with the product. Additionally the sensor has been designed to be connected directly to Hydrovar ® terminal block, X3. The sensor provides an electronic contact to be used for stopping the pump in case of lack of water in the area of the mechanical seal. The contact opens after a factory set delay. Body: AISI 316L stainless steel. Optical Cap: Glass Max pressure: 25 bar (362 psi) Liquid temperature: 0-120°C (32-248˚F) Liquids: Clean water, demineralized water Power supply: 15-25 V DC Output: NPN open collector Alarm delay:10 s Cable length = 2 meters (6.6 feet) Port: 3 8" ISO threads Adapter: 3 8" – ½" Part number: 9L127

Upload: others

Post on 20-May-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: e-SVwhite2 Dry Run Sensor · 2015-10-06 · Dry Run Sensor WHITE PAPER e-SVwhite2 FEATURES • The sensor is composed of a stainless steel body, a glass cap and a connecting cable

Dry Run Sensor

WHITE PAPERe-SVwhite2

FEATURES

• The sensor is composed of a stainless steel body, a glass cap and a connecting cable. The sensor can be mounted directly on the fill plug of e-SV series pump. For the larger e-SV series sizes (33 thru 125SV) a suitable adapter is supplied with the product. Additionally the sensor has been designed to be connected directly to Hydrovar® terminal block, X3.

• The sensor provides an electronic contact to be used for stopping the pump in case of lack of water in the area of the mechanical seal. The contact opens after a factory set delay.

• Body: AISI 316L stainless steel.

• Optical Cap: Glass

• Max pressure: 25 bar (362 psi)

• Liquid temperature: 0-120°C (32-248˚F)

• Liquids: Clean water, demineralized water

• Power supply: 15-25 VDC

• Output: NPN open collector

• Alarm delay:10 s

• Cable length = 2 meters (6.6 feet)

• Port: 3⁄8" ISO threads

• Adapter: 3⁄8" – ½"

• Part number: 9L127

Page 2: e-SVwhite2 Dry Run Sensor · 2015-10-06 · Dry Run Sensor WHITE PAPER e-SVwhite2 FEATURES • The sensor is composed of a stainless steel body, a glass cap and a connecting cable

WIRING DIAGRAM TO HYDROVAR®

3

12

4

5

6

7

8

9

10

11

24 Vdc power supply – brown

Low water protection input – black

GND – blue

TEMP – white

X3

Hyd

rova

r te

rmin

al

WIRING TO AQUAVAR® CPC

5

14

6

7

8

9

10

11

12

13

24 Vdc power supply – brown

Low water protection input – black

GND – blue

TEMP – white

CP

C t

erm

inal

WIRING TO RELAY 15 VDC

15 Vdc power supply – brown

Alarm – black

GND – blue

TEMP – white

Max 25 mA

Xylem Inc.www.xyleminc.comGoulds is a registered trademark of Goulds Pumps, Inc. and is used under license.© 2012 Xylem Inc. e-SVwhite2 February 2013

CPC WIRINGNormal Wiring with Transducer and jumpers in position.

Transducer Cable connected on terminals 1, 5 and 10.Jumpers to run:3 and 11

10 and 15

11 and 12

3 and 11

10 and 12

11 and 15

Setting up to install the dry run sensor requires the jumpers to be installed into different positions:

Installation of the Dry Run SensorPart Number 9L 127

Brown wire on # 10.

Please note: this terminal will now have three wires inside of this terminal. Please verify solid connection for all three wires.

Blue wire on Terminal 11.

Again, there are three wires inside of this terminal and verify connection is solid.

Black wire on Terminal 14.Do not use the white wire. Please tape off connector before re-installing cover.

Enable Low Water input on CPC in Menu 2405.Please change to “Fault”.