e0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid...

10
B A ISSUED FOR BID 10/13/20 JK BLP ZPB JM B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM E0-1-BEL.DWG E0-1 BELLEVUE FACILITY COVER SHEET & LEGEND BLP 09/14/20 JK 09/14/20 ZPB 11/13/20 N/A THIS DRAWING WAS PREPARED BY POWER ENGINEERS, INC. FOR A SPECIFIC PROJECT, TAKING INTO CONSIDERATION THE SPECIFIC AND UNIQUE REQUIREMENTS OF THE PROJECT. REUSE OF THIS DRAWING OR ANY INFORMATION CONTAINED IN THIS DRAWING FOR ANY PURPOSE IS PROHIBITED UNLESS WRITTEN PERMISSION FROM BOTH POWER AND POWER'S CLIENT IS GRANTED. MOUNTAIN RIDES JOB NUMBER DRAWING NUMBER REVISIONS REV SCALE: DATE CKD DSGN DRN REFERENCE DRAWINGS APPD DSGN CKD DRN FOR 24x36 DWG ONLY 1 2 3 4 5 6 7 8 REV E D C B A 165994 ELECTRIC BUS CHARGING NOTES SURFACE MOUNTED PANELBOARD 1 POLE (2P, 3P, 4P, ETC.) 1P A AC ACLG ADO AF AFF AFG AFCI AHU AL ALT AMP AMPL AMPERE ABOVE COUNTER OR AIR CONDITIONER ABOVE CEILING AUTOMATIC DOOR OPENER AMP FRAME ABOVE FINISHED FLOOR ABOVE FINISHED GRADE ARC FAULT CIRCUIT INTERRUPTER AIR HANDLING UNIT ALUMINUM ALTERNATE AMPERE AMPLIFIER ANNUN APPROX AQ-STAT ARCH AS AT AMP TRIP ATS AUTO AUX AV AWG BATT BD BLDG BMS CND CAB CAT CATV CB CCTV CKT CLG COMB CMPR CONN AUTOMATIC TRANSFER SWITCH AUTOMATIC AUXILIARY AUDIO VISUAL AMERICAN WIRE GAUGE BATTERY BOARD BUILDING BUILDING MANAGEMENT SYSTEM CONDUIT CABINET CATALOG CABLE TELEVISION CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CIRCUIT CEILING COMBINATION COMPRESSOR CONNECTION CONST CONSTRUCTION CONT CONTR CONTRACTOR CONV CP CONVECTOR CRT CT CTR CU CIRCULATING PUMP CATHODE-RAY TUBE CURRENT TRANSFORMER CENTER COPPER CONTINUATION OR CONTINUOUS ARCHITECT, ARCHITECTURAL AMP SWITCH DCP DEPT DET DIA DISC DIST DN DPR DS DT DWG EC ELEC EGC EM EMS EMT EP EQUIP EWC EX EXH EXP FA FABP FACP FCU FIXT FLR FLUOR FU FUDS GA GAL GALV GC GEC GFCI GFP GND GRS DOMESTIC WATER CIRCULATING PUMP DEPARTMENT DETAIL DIAMETER DISCONNECT DISTRIBUTION DOWN DAMPER SAFETY DISCONNECT SWITCH DOUBLE THROW DRAWING ELECTRICAL CONTRACTOR ELECTRIC, ELECTRICAL EQUIPMENT GROUNDING CONDUCTOR EMERGENCY ENERGY MANAGEMENT SYSTEM ELECTRICAL METALLIC TUBING ELECTRIC PNEUMATIC EQUIPMENT ELECTRIC WATER COOLER EXISTING EXHAUST EXPLOSION PROOF FIRE ALARM FIRE ALARM BOOSTER POWER SUPPLY PANEL FIRE ALARM CONTROL PANEL FAN COIL UNIT FIXTURE FLOOR FLUORESCENT FUSE FUSED SAFETY DISCONNECT SWITCH GAUGE GALLON GALVANIZED GENERAL CONTRACTOR GROUNDING ELECTRODE CONDUCTOR GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT PROTECTOR GROUND GALVANIZED RIGID STEEL (CONDUIT) GYP BD GYPSUM BOARD HH HORIZ HP HPF HANDHOLE HORIZONTAL HORSEPOWER HIGH POWER FACTOR KV KVA KVAR KW KWH LOC LT LTG LTNG LV MAX MCB MCC MDC MDP MFR MFS MH MIC MIN MISC MLO MMS MOA MSP MSBD MT MT.C MTS MTR N.C. NEC KILOVOLT KILOVOLT-AMPERE KILOVOLT-AMPERE REACTIVE KILOWATT KILOWATT HOUR LOCATE OR LOCATION LIGHT LIGHTING LIGHTNING LOW VOLTAGE MAXIMUM MAG.S MAGNETIC STARTER M/C MC MOMENTARY CONTACT MECHANICAL CONTRACTOR MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION CENTER MAIN DISTRIBUTION PANEL MANUFACTURER MAIN FUSED DISCONNECT SWITCH MANHOLE MICROPHONE MINIMUM MISCELLANEOUS MAIN LUGS ONLY MANUAL MOTOR STARTER MULTIOUTLET ASSEMBLY MOTOR STARTER PANELBOARD MAIN SWITCHBOARD MOUNT EMPTY CONDUIT MANUAL TRANSFER SWITCH MOTOR, MOTORIZED NORMALLY CLOSED NATIONAL ELECTRICAL CODE HT HTG HTR HV HVAC HWP IC IG IMC I/W J-BOX HEIGHT HEATING HEATER HIGH VOLTAGE HEATING, VENTILATING AND AIR CONDITIONING HYDRONIC WATER PUMP INTERRUPTING CAPACITY ISOLATED GROUND INTERMEDIATE METAL CONDUIT INCAND INCANDESCENT IR INFRARED INTERLOCK WITH JUNCTION BOX PA PB PE PED PF PH PIV PNL PP PR PRI PROJ PRV PT PVC PWR QUAN RCPT REQD RM RSC RTU SC SEC SHT SIM S/N SPEC SPKR SP SR SS SSW S/S STA STD SURF SUSE PUBLIC ADDRESS PULL BOX OR PUSHBUTTON PNEUMATIC ELECTRIC PEDESTAL POWER FACTOR PHASE POST INDICATING VALVE PANEL POWER POLE PAIR PRIMARY PROJECTION POWER ROOF VENTILATOR POTENTIAL TRANSFORMER POLYVINYL CHLORIDE (CONDUIT) POWER W QUANTITY RECEPTACLE REQUIRED ROOM RIGID STEEL CONDUIT ROOF TOP UNIT SURFACE CONDUIT SECONDARY SHEET SIMILAR SOLID NEUTRAL SPECIFICATION SPEAKER SPARE SURFACE RACEWAY STAINLESS STEEL SELECTOR SWITCH STOP/START PUSHBUTTONS STATION STANDARD SURFACE MOUNTED SUITABLE FOR USE AS ANGLE @ AT DELTA ' " L FEET INCHES # NUMBER Ø PHASE C CENTER LINE PL PLATE W/ WG WH W/O WP XFMR XFR WATT WITH WIRE GUARD WATER HEATER WITHOUT WEATHERPROOF TRANSFORMER TRANSFER V VA VDT VERT VFD VOL UC UE UG UH UT UTIL UV UNDER COUNTER UNDERGROUND ELECTRICAL UNDERGROUND UNIT HEATER UNDERGROUND TELEPHONE UTILITY UNIT VENTILATOR OR ULTRAVIOLET VOLT VOLT-AMPERES VIDEO DISPLAY TERMINAL VERTICAL VARIABLE FREQUENCY DRIVE VOLUME NIC NL N.O. NPF NTS OH OL NFDS NON-FUSED SAFETY DISCONNECT SWITCH NOT IN CONTRACT NIGHT LIGHT NORMALLY OPEN NORMAL POWER FACTOR NOT TO SCALE OVERHEAD OVERLOADS SWBD SYM SYS TEL SWITCHBOARD SYMMETRICAL SYSTEM TELEPHONE TEL/DATA TELEPHONE/DATA TERM TL TR TERMINAL TWIST LOCK T-STAT TTC TV TVTC TWPR TAMPER RESISTANT THERMOSTAT TELEPHONE TERMINAL CABINET TELEVISION TELEVISION TERMINAL CABINET TWISTED PAIR ELECTRICAL SYMBOLS LEGEND ELECTRICAL ABBREVIATIONS LIST MCCB MOLDED CASE CIRCUIT BREAKER SPD SURGE PROTECTION DEVICE PM POWER METER ERMS ENERGY REDUCTION MAINTENANCE SWITCH LSI LONG TIME + SHORT TIME + INSTANTANEOUS PROTECTION LSIG LONG TIME + SHORT TIME + INSTANTANEOUS + GROUND FAULT PROTECTION NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION MCP MOTOR CIRCUIT PROTECTOR DISCONNECT SWITCH ONE-LINE SYMBOLS LEGEND LOW VOLTAGE FIXED CIRCUIT BREAKER DELTA-Y CONNECTION CONNECTION DOT DISCONNECT SWITCH LOW VOLTAGE FUSED SWITCH GROUND CONNECTION GROUNDED Y CONNECTION POWER TRANSFORMER EXISTING EQUIPMENT NEW EQUIPMENT ABOVE GRADE EXPOSED CONDUIT UNDEGROUND CONDUIT CONDUITS IN/OUT OF EQUIPMENT AQUASTAT APPROXIMATELY ANNUNCIATOR ARMS ARCHFLASH REDUCTION MAINTENANCE SYSTEM FO FIBER OPTIC KCMIL ONE THOUSAND CIRCULAR MILS SCH SCHEDULE SERVICE EQUIPMENT SW SWITCH DC DIRECT CURRENT TYP TYPICAL DC1-1 CABLE/CIRCUIT TAG DC1-1 CABLE/CIRCUIT TAG 1. THE ELECTRICAL INSTALLATION SHALL MEET THE MINIMUM REQUIREMENTS OF THE 2017 NATIONAL ELECTRIC CODE AS ADOPTED BY THE STATE OF IDAHO AND LOCAL BUILDING CODES. 2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND APPROVED AND SUITABLE FOR THE INSTALLATION. 3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW THE GENERAL INTENT OF LOCATIONS AND INSTALLATION REQUIREMENTS OF EQUIPMENT. EXACT LOCATIONS AND INSTALLATION MATERIALS REQUIRED SHALL BE VERIFIED IN FIELD WITH ACTUAL INSTALLED EQUIPMENT. 4. ALL EXISTING CONDITIONS SHALL BE VERIFIED AT THE JOB SITE PRIOR TO BID SUBMITTALS. 5. ALL WALL AND CEILING PENETRATIONS SHALL BE SEALED WITH MATERIALS APPROVED TO MAINTAIN FIRE RATINGS. 6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS NOTED OTHERWISE. 7. MULTIWIRED BRANCH CIRCUITS (SHARED NEUTRALS) SHALL NOT BE USED. 8. PROVIDE PVC40 CONDUIT WITH PVC80 FITTINGS FOR ALL UNDERGROUND CONDUIT. 9. PROVIDE EMT CONDUIT FOR ALL INDOOR AND OUTDOOR ABOVEGROUND CONDUIT PAINTED TO MATCH THE EXISTING CONDITIONS. 10. PROVIDE THWN/THHN COPPER CONDUCTORS FOR ALL POWER CONDUCTORS. ALL CONDUCTORS #10 AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AND LARGER SHALL BE STRANDED. TYPE NM CABLE IS NOT PERMITTED. 11. ALL CABLE TERMINATIONS AND FITTINGS SHALL BE RATED FOR A MINIMUM OF 75C. 12. PROVIDE BARE COPPER CONDUCTORS FOR BONDING. EQUIPMENT GROUNDING CONDUCTORS SHALL BE COPPER WITH GREEN INSULATION. 13. ALL OUTDOOR EQUIPMENT SHALL BE NEMA TYPE-3R. 14. PROVIDE CURRENT LIMITING FUSES FOR ALL FUSES IN ACCORDANCE WITH UL-4248. 15. ELECTRICAL SWITCHBOARDS SHALL HAVE A NEMA TYPE-1 RATINGS WITH COPPER BUSSING. THE CIRCUIT BREAKERS SHALL BE THE BOLT-ON TYPE. 16. GROUND RODS SHALL BE CONE POINTED COPPER, 10' IN LENGTH, WITH A 3/4" DIAMETER; SECTIONAL RODS ARE PERMITTED. 17. PROVIDE A TRANSFORMER PAD AS REQUIRED BY IDAHO POWER. 18. LOCATE EXISTING UNDERGROUND UTILITIES IN THE THE PROPOSED AREA FOR THE NEW SECONDARY CONDUITS FOR UNDERGROUND UTILITIES PRIOR TO DIGGING. 19. THIS FACILITY IS IN SEISMIC ZONE 2B, CONTRACTOR SHALL ADHERE TO THE LOCAL CODES WHEN INSTALLING AND MOUNTING EQUIPMENT AND RACEWAYS.

Upload: others

Post on 20-Mar-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E0-1-B

EL.D

WG

E0-1

BELLEVUE FACILITY

COVER SHEET & LEGEND

BLP 09/14/20

JK 09/14/20

ZPB 11/13/20

N/A

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

NOTES

SURFACE MOUNTED PANELBOARD

1 POLE (2P, 3P, 4P, ETC.)1P

A

AC

ACLG

ADO

AF

AFF

AFG

AFCI

AHU

AL

ALT

AMP

AMPL

AMPERE

ABOVE COUNTER OR AIR

CONDITIONER

ABOVE CEILING

AUTOMATIC DOOR OPENER

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

ARC FAULT CIRCUIT

INTERRUPTER

AIR HANDLING UNIT

ALUMINUM

ALTERNATE

AMPERE

AMPLIFIER

ANNUN

APPROX

AQ-STAT

ARCH

AS

AT AMP TRIP

ATS

AUTO

AUX

AV

AWG

BATT

BD

BLDG

BMS

CND

CAB

CAT

CATV

CB

CCTV

CKT

CLG

COMB

CMPR

CONN

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AUXILIARY

AUDIO VISUAL

AMERICAN WIRE GAUGE

BATTERY

BOARD

BUILDING

BUILDING MANAGEMENT

SYSTEM

CONDUIT

CABINET

CATALOG

CABLE TELEVISION

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CEILING

COMBINATION

COMPRESSOR

CONNECTION

CONST CONSTRUCTION

CONT

CONTR CONTRACTOR

CONV

CP

CONVECTOR

CRT

CT

CTR

CU

CIRCULATING PUMP

CATHODE-RAY TUBE

CURRENT TRANSFORMER

CENTER

COPPER

CONTINUATION OR

CONTINUOUS

ARCHITECT, ARCHITECTURAL

AMP SWITCH

DCP

DEPT

DET

DIA

DISC

DIST

DN

DPR

DS

DT

DWG

EC

ELEC

EGC

EM

EMS

EMT

EP

EQUIP

EWC

EX

EXH

EXP

FA

FABP

FACP

FCU

FIXT

FLR

FLUOR

FU

FUDS

GA

GAL

GALV

GC

GEC

GFCI

GFP

GND

GRS

DOMESTIC WATER

CIRCULATING PUMP

DEPARTMENT

DETAIL

DIAMETER

DISCONNECT

DISTRIBUTION

DOWN

DAMPER

SAFETY DISCONNECT SWITCH

DOUBLE THROW

DRAWING

ELECTRICAL CONTRACTOR

ELECTRIC, ELECTRICAL

EQUIPMENT GROUNDING CONDUCTOR

EMERGENCY

ENERGY MANAGEMENT SYSTEM

ELECTRICAL METALLIC TUBING

ELECTRIC PNEUMATIC

EQUIPMENT

ELECTRIC WATER COOLER

EXISTING

EXHAUST

EXPLOSION PROOF

FIRE ALARM

FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FIXTURE

FLOOR

FLUORESCENT

FUSE

FUSED SAFETY DISCONNECT

SWITCH

GAUGE

GALLON

GALVANIZED

GENERAL CONTRACTOR

GROUNDING ELECTRODE CONDUCTOR

GROUND FAULT CIRCUIT

INTERRUPTER

GROUND FAULT PROTECTOR

GROUND

GALVANIZED RIGID STEEL

(CONDUIT)

GYP BD GYPSUM BOARD

HH

HORIZ

HP

HPF

HANDHOLE

HORIZONTAL

HORSEPOWER

HIGH POWER FACTOR

KV

KVA

KVAR

KW

KWH

LOC

LT

LTG

LTNG

LV

MAX

MCB

MCC

MDC

MDP

MFR

MFS

MH

MIC

MIN

MISC

MLO

MMS

MOA

MSP

MSBD

MT

MT.C

MTS

MTR

N.C.

NEC

KILOVOLT

KILOVOLT-AMPERE

KILOVOLT-AMPERE REACTIVE

KILOWATT

KILOWATT HOUR

LOCATE OR LOCATION

LIGHT

LIGHTING

LIGHTNING

LOW VOLTAGE

MAXIMUM

MAG.S MAGNETIC STARTER

M/C

MC

MOMENTARY CONTACT

MECHANICAL CONTRACTOR

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION CENTER

MAIN DISTRIBUTION PANEL

MANUFACTURER

MAIN FUSED DISCONNECT

SWITCH

MANHOLE

MICROPHONE

MINIMUM

MISCELLANEOUS

MAIN LUGS ONLY

MANUAL MOTOR STARTER

MULTIOUTLET ASSEMBLY

MOTOR STARTER PANELBOARD

MAIN SWITCHBOARD

MOUNT

EMPTY CONDUIT

MANUAL TRANSFER SWITCH

MOTOR, MOTORIZED

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

HT

HTG

HTR

HV

HVAC

HWP

IC

IG

IMC

I/W

J-BOX

HEIGHT

HEATING

HEATER

HIGH VOLTAGE

HEATING, VENTILATING AND

AIR CONDITIONING

HYDRONIC WATER PUMP

INTERRUPTING CAPACITY

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

INTERLOCK WITH

JUNCTION BOX PA

PB

PE

PED

PF

PH

PIV

PNL

PP

PR

PRI

PROJ

PRV

PT

PVC

PWR

QUAN

RCPT

REQD

RM

RSC

RTU

SC

SEC

SHT

SIM

S/N

SPEC

SPKR

SP

SR

SS

SSW

S/S

STA

STD

SURF

SUSE

PUBLIC ADDRESS

PULL BOX OR PUSHBUTTON

PNEUMATIC ELECTRIC

PEDESTAL

POWER FACTOR

PHASE

POST INDICATING VALVE

PANEL

POWER POLE

PAIR

PRIMARY

PROJECTION

POWER ROOF VENTILATOR

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

(CONDUIT)

POWER

W

QUANTITY

RECEPTACLE

REQUIRED

ROOM

RIGID STEEL CONDUIT

ROOF TOP UNIT

SURFACE CONDUIT

SECONDARY

SHEET

SIMILAR

SOLID NEUTRAL

SPECIFICATION

SPEAKER

SPARE

SURFACE RACEWAY

STAINLESS STEEL

SELECTOR SWITCH

STOP/START PUSHBUTTONS

STATION

STANDARD

SURFACE MOUNTED

SUITABLE FOR USE AS

ANGLE

@ AT

DELTA

'

"

L

FEET

INCHES

# NUMBER

Ø PHASE

C CENTER LINE

PL PLATE

W/

WG

WH

W/O

WP

XFMR

XFR

WATT

WITH

WIRE GUARD

WATER HEATER

WITHOUT

WEATHERPROOF

TRANSFORMER

TRANSFER

V

VA

VDT

VERT

VFD

VOL

UC

UE

UG

UH

UT

UTIL

UV

UNDER COUNTER

UNDERGROUND ELECTRICAL

UNDERGROUND

UNIT HEATER

UNDERGROUND TELEPHONE

UTILITY

UNIT VENTILATOR OR

ULTRAVIOLET

VOLT

VOLT-AMPERES

VIDEO DISPLAY TERMINAL

VERTICAL

VARIABLE FREQUENCY DRIVE

VOLUME

NIC

NL

N.O.

NPF

NTS

OH

OL

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NORMAL POWER FACTOR

NOT TO SCALE

OVERHEAD

OVERLOADS

SWBD

SYM

SYS

TEL

SWITCHBOARD

SYMMETRICAL

SYSTEM

TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM

TL

TR

TERMINAL

TWIST LOCK

T-STAT

TTC

TV

TVTC

TWPR

TAMPER RESISTANT

THERMOSTAT

TELEPHONE TERMINAL CABINET

TELEVISION

TELEVISION TERMINAL CABINET

TWISTED PAIR

ELECTRICAL SYMBOLS LEGEND ELECTRICAL ABBREVIATIONS LIST

MCCB MOLDED CASE CIRCUIT

BREAKER

SPD SURGE PROTECTION DEVICE

PM POWER METER

ERMS ENERGY REDUCTION

MAINTENANCE SWITCH

LSILONG TIME + SHORT TIME +

INSTANTANEOUS PROTECTION

LSIG

LONG TIME + SHORT TIME +

INSTANTANEOUS + GROUND

FAULT PROTECTION

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

MCP MOTOR CIRCUIT PROTECTOR

DISCONNECT SWITCH

ONE-LINE SYMBOLS LEGEND

LOW VOLTAGE FIXED CIRCUIT BREAKER

DELTA-Y CONNECTION

CONNECTION DOT

DISCONNECT SWITCH

LOW VOLTAGE FUSED SWITCH

GROUND CONNECTION

GROUNDED Y CONNECTION

POWER TRANSFORMER

EXISTING EQUIPMENT

NEW EQUIPMENT

ABOVE GRADE EXPOSED CONDUIT

UNDEGROUND CONDUIT

CONDUITS IN/OUT OF EQUIPMENT

AQUASTAT

APPROXIMATELY

ANNUNCIATOR

ARMS ARCHFLASH REDUCTION

MAINTENANCE SYSTEM

FO FIBER OPTIC

KCMIL ONE THOUSAND CIRCULAR MILS

SCH SCHEDULE

SERVICE EQUIPMENT

SW SWITCH

DC DIRECT CURRENT

TYP TYPICAL

DC1-1CABLE/CIRCUIT TAG

DC1-1CABLE/CIRCUIT TAG

1. THE ELECTRICAL INSTALLATION SHALL MEET THE MINIMUM REQUIREMENTS OF THE

2017 NATIONAL ELECTRIC CODE AS ADOPTED BY THE STATE OF IDAHO AND LOCAL

BUILDING CODES.

2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND APPROVED AND SUITABLE FOR

THE INSTALLATION.

3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW THE GENERAL INTENT OF

LOCATIONS AND INSTALLATION REQUIREMENTS OF EQUIPMENT. EXACT LOCATIONS

AND INSTALLATION MATERIALS REQUIRED SHALL BE VERIFIED IN FIELD WITH ACTUAL

INSTALLED EQUIPMENT.

4. ALL EXISTING CONDITIONS SHALL BE VERIFIED AT THE JOB SITE PRIOR TO BID

SUBMITTALS.

5. ALL WALL AND CEILING PENETRATIONS SHALL BE SEALED WITH MATERIALS

APPROVED TO MAINTAIN FIRE RATINGS.

6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS

NOTED OTHERWISE.

7. MULTIWIRED BRANCH CIRCUITS (SHARED NEUTRALS) SHALL NOT BE USED.

8. PROVIDE PVC40 CONDUIT WITH PVC80 FITTINGS FOR ALL UNDERGROUND CONDUIT.

9. PROVIDE EMT CONDUIT FOR ALL INDOOR AND OUTDOOR ABOVEGROUND CONDUIT

PAINTED TO MATCH THE EXISTING CONDITIONS.

10. PROVIDE THWN/THHN COPPER CONDUCTORS FOR ALL POWER CONDUCTORS. ALL

CONDUCTORS #10 AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AND LARGER

SHALL BE STRANDED. TYPE NM CABLE IS NOT PERMITTED.

11. ALL CABLE TERMINATIONS AND FITTINGS SHALL BE RATED FOR A MINIMUM OF 75C.

12. PROVIDE BARE COPPER CONDUCTORS FOR BONDING. EQUIPMENT GROUNDING

CONDUCTORS SHALL BE COPPER WITH GREEN INSULATION.

13. ALL OUTDOOR EQUIPMENT SHALL BE NEMA TYPE-3R.

14. PROVIDE CURRENT LIMITING FUSES FOR ALL FUSES IN ACCORDANCE WITH UL-4248.

15. ELECTRICAL SWITCHBOARDS SHALL HAVE A NEMA TYPE-1 RATINGS WITH COPPER

BUSSING. THE CIRCUIT BREAKERS SHALL BE THE BOLT-ON TYPE.

16. GROUND RODS SHALL BE CONE POINTED COPPER, 10' IN LENGTH, WITH A 3/4"

DIAMETER; SECTIONAL RODS ARE PERMITTED.

17. PROVIDE A TRANSFORMER PAD AS REQUIRED BY IDAHO POWER.

18. LOCATE EXISTING UNDERGROUND UTILITIES IN THE THE PROPOSED AREA FOR THE

NEW SECONDARY CONDUITS FOR UNDERGROUND UTILITIES PRIOR TO DIGGING.

19. THIS FACILITY IS IN SEISMIC ZONE 2B, CONTRACTOR SHALL ADHERE TO THE LOCAL

CODES WHEN INSTALLING AND MOUNTING EQUIPMENT AND RACEWAYS.

AutoCAD SHX Text
PRELIMINARY
Page 2: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E1

-1

-B

EL

.D

WG

E1-1

BELLEVUE FACILITY

ONE LINE DIAGRAM

BLP 09/10/20

JK 09/10/20

ZPB 11/13/20

NONE

1. THE PROPOSED ABB EV BUS CHARGER HAVE A POWER FACTOR OF 0.95.

2. CABLE AMPACITY CALCULATIONS ARE BASED ON A 105F MAXIMUM AMBIENT

TEMPERATURE.

3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE

DISCONNECTING MEANS.

NOTES

KEYED NOTES

UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, CT, AND METER. UTILITY TO

PROVIDE PRIMARY POWER CABLES AND ASSOCIATED RACEWAY.

CONTRACTOR TO TERMINATE CUSTOMER SUPPLIED CABLES DIRECTLY TO THE

UTILITY TRANSFORMER TERMINALS.

BOND NEW GROUNDING ELECTRODE TO EXISTING GROUNDING ELECTRODE

SYSTEM PER NEC 250.

PROVIDE SPARE BREAKER FOR FUTURE EV BUS CHARGERS.

PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE

IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS

DISCONNECTED PRIOR TO SERVICING.

PROVIDE 208Y/120V PANELBOARD WITH INTERGRAL 15KVA TRANSFORMER &

ASSOCIATED CIRCUIT BREAKERS. TRANSFORMER PERCENT IMPEDANCE

ASSUMED AT 2%. REFER TO PANEL SCHEDULE DRAWING FOR CIRCUIT

BREAKER SIZES.

ONE OF THE GROUND CONDUCTORS FROM DC CHARGER WILL PASS THROUGH

DC CHARGER DISPENSER A AND CONTINUE TO DISPENSER B.

1

2

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

N G

1

3

3

4

4

2

55

5

55

6

DC1-1

DC1-4

DC1-5

DC2-1

DC2-4

DC2-5

6

P-2

P-3

P-4

P-1

P-0

4

DC1-2

DC1-3

DC2-2

DC2-3

B

7

B

7

7

B

AutoCAD SHX Text
1200 AMP BUS
AutoCAD SHX Text
UTILITY SOURCE
AutoCAD SHX Text
UTILITY METER
AutoCAD SHX Text
MAIN BONDING JUMPERS
AutoCAD SHX Text
(3)
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
M
AutoCAD SHX Text
POWER DISTRIBUTION PANEL '480V SWITCHBOARD #1' (1200 AMP, 480Y/277V 3 , 4W, 42K AIC, NEMA 1, SUSE)
AutoCAD SHX Text
GROUNDING ELECTRODE CONDUCTOR #3/0 CU
AutoCAD SHX Text
2-1/2" CND 3-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
DC CHARGER #1 150KW
AutoCAD SHX Text
2-1/2" CND 3-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
UTILITY XFMR 500KVA 12.47KV-480Y/277V
AutoCAD SHX Text
XFMR CABINET
AutoCAD SHX Text
1200AF 1000AT LSIG
AutoCAD SHX Text
MAIN BREAKER
AutoCAD SHX Text
NEUTRAL CONDUCTORS
AutoCAD SHX Text
DC CHARGER DISPENSER #1A
AutoCAD SHX Text
DC CHARGER DISPENSER #1B
AutoCAD SHX Text
DC CHARGER DISPENSER #2A
AutoCAD SHX Text
DC CHARGER DISPENSER #2B
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU
AutoCAD SHX Text
DC CHARGER #2 150KW
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU
AutoCAD SHX Text
35AF 35AT LSI
AutoCAD SHX Text
AC PANEL #1 208Y/120V 3PH, 4W 60A BUS 50A MAIN BKR
AutoCAD SHX Text
XFMR 480V-208Y/120V 15KVA
AutoCAD SHX Text
3/4" CND 2-1/C #12 CU 1-1/C #12 CU GND
AutoCAD SHX Text
3/4" CND 3-1/C #6 CU 1-1/C #10 CU GND
AutoCAD SHX Text
AC PANEL #1 NEMA 1 ENCLOSURE
AutoCAD SHX Text
1-1/2" CND 1-1/C #6 CU GND 3-1/C #14 CU 1-2/PR #18 TSP CU 4-OM3 FIBER OPTIC 1-CAT6 SHD
AutoCAD SHX Text
(3) 4" CND (3) 4-1/C 500KCMIL CU IN EACH CONDUIT
AutoCAD SHX Text
1-1/2" CND 1-1/C #6 CU GND 3-1/C #14 CU 1-2/PR #18 TSP CU 4-OM3 FIBER OPTIC 1-CAT6 SHD
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
1-1/2" CND 2-1/C #6 CU GND 1-2/PR #18 TSP CU 8-OM3 FIBER OPTIC
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
1-1/2" CND 2-1/C #6 CU GND 1-2/PR #18 TSP CU 8-OM3 FIBER OPTIC
AutoCAD SHX Text
PRELIMINARY
Page 3: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E3-1-B

EL.D

WG

E3-1

BELLEVUE FACILITY

ELECTRICAL PANEL SCHEDULES

BLP 09/14/20

JK 09/14/20

ZPB 11/13/20

NONE

1. TWO 400A SPARE BREAKERS ON 480V SWITCHBOARD #1 IS FOR A FUTURE DC

CHARGER.

NOTES

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

KEYED NOTES

BREAKER SHALL COME EQUIPPED WITH A 30mA GFCI.1

1

1

1

1

AutoCAD SHX Text
PRELIMINARY
Page 4: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

3'-0

" M

IN

1'-6

"

3" TYP

RED PLASTIC ELECTRICAL

WARNING TAPE WITH MAGNETIC

LINING THAT READS "CAUTION -

ELECTRICAL LINE BURIED BELOW"

4" SCH 40 OR SCH 80 PVC

(TYP.)

COMPACTED APPROVED BACKFILL

FINISHED GRADE

SAWCUT AND REPAIR CONCRETE AS

REQUIRED FOR NEW CONDUIT

4'-10"

1'-1

1

2

"

3'-1

0

1

8

"

2 1/2" DIA CONDUIT OPENING

2 1/2" DIA CONDUIT OPENING

1 1/2" DIA CONDUIT OPENING

5'-2

1

8

"

1

1

2

"

3"

C6X10.5

C6X10.5

C6

X1

0.5

C6

X1

0.5

4'-1

1

5

8

"

(E) CMU WALL

NOTES:

1. 19-W4 GALVANIZED STEEL BAR GRATING 1-1/2"

HEIGHT, 1/8" THICK

2. FRAME IS TO SIT ON THE CONCRETE SLAB.

LEVEL WITH GROUT AS NECESSARY.

3. ALL STEEL MEMBERS TO BE PAINTED CARBON

STEEL.

BOLT CHARGERS TO

CHANNEL FRAME

AS NECESSARY

C6

X1

0.5

C6

X1

0.5

2'-5" 2'-5"

2'-3" 2'-3"

2 1/2" DIA CONDUIT OPENING

2 1/2" DIA CONDUIT OPENING

4'-10"

1'-10" 1'-10"

1 1/2" DIA CONDUIT OPENING

NOTE 1

1

1

2

"

3"

5'-2

1

8

"

TYP

FLANGES

1/8

L3X3X1/4

5/8" DIA HOLE TYP FOR

1/2" DIA THREADED ROD

W/HILTI HIT-HY270 EPOXY, MIN 5"

EMBEDMENT FULLY GROUT CMU

CELLS BEFORE INSTALLATION

DIA. GRADE

(2) 1/2" A325 BOLT TYP

C6 SEE PLAN

1

1

2

"

1"

1"

6"

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E6-1-B

EL.D

WG

E6-1

BELLEVUE FACILITY

CONDUIT SECTIONS & DETAILS

BLP 09/18/20

JK 09/18/20

ZPB 11/13/20

AS INDICATED

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

TYPICAL DUCT SECTION1

E7-1

SCALE 1" = 1'-0"

CHARGER SUPPORT FRAME2

E7-1

SCALE 1" = 1'-0"

MEMBER CONDUIT OPENINGS3

E7-1

SCALE 1" = 1'-0"

TYP 3

SIDES

CHANNEL TO MASONRY WALL CONNECTION4

E7-1

SCALE 3" = 1'-0"

1/8

TYP

MEMBER CONDUIT OPENINGS5

E7-1

SCALE 1" = 1'-0"

B

AutoCAD SHX Text
5
AutoCAD SHX Text
-
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
-
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
-
Page 5: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

DC2-4

DC2-1

DC2-2

DC2-3

DC2-5

DC1-1DC1-2

DC1-3

DC1-4

DC1-5

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E7-1-B

EL.D

WG

E7-1

BELLEVUE FACILITY

FIRST FLOOR POWER PLAN

BLP 09/14/20

JK 09/14/20

ZPB 11/13/20

1/8" = 1'-0"

1. REFER TO ONE-LINE DIAGRAM DRAWING E1-1 FOR CONDUIT & CABLE

REQUIREMENTS.

2. CONTRACTOR TO PROVIDE EQUIPMENT, CONDUITS, & TERMINATE POWER &

COMMUNICATION CABLES. REFER TO ONE LINE DIAGRAM FOR CABLE SIZING.

3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE

DISCONNECTING MEANS.

4. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO DETERMINE

THE BEST CONDUIT ROUTE IN THE FIELD.

NOTES

KEYED NOTES

UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, TRANSFORMER PAD,

PRIMARY CABLES & RACEWAYS.

CONTRACTOR SCOPE INCLUDES TERMINATION TO THE LOAD SIDE OF THE

UTILITY TRANSFORMER.

PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE

IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS

DISCONNECTED PRIOR TO SERVICING."

PROVIDE CUSTOM FABRICATED STEEL SUPPORT STAND WITH A 6" C-CHANNEL

BASE FOR ABOVEGROUND CONDUIT ENTRY TO THE BOTTOM OF THE EV

CHARGER.

PROVIDE 10" x 10" WIREWAY ON TOP OF 480V SWITCHBOARD #1 TO BE USED AS

A PULLBOX AND ENTRY POINT FOR CABLE INTO THE PANEL.

PROVIDE CONDUIT SUPPORT FOR VERTICAL CONDUITS CONTAINING DC1-1,

DC1-2, DC2-1, DC2-2 EXITING THE DC CHARGERS.

1

NORTH

0 FEET

1/8" = 1'-0"

20105

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

UTILITY

XFMR

DC CHARGER #2

DC CHARGER #1

DC CHARGER

DISPENSER 1B

DC CHARGER

DISPENSER 2A

480V

SWITCHBOARD

#1

DC CHARGER

DISPENSER 1A

DC CHARGER

DISPENSER 2B

1

2

2

3

3

3

3

3

4

4

4

1

E6-1

SCALE: 1/8" = 1'-0"

1

FIRST FLOOR POWER PLAN

P-3

P-2

P-4

P-1

P-0

AC PANEL #1

& INTEGRAL

XFMR

5

6

6

6

5

AutoCAD SHX Text
PRELIMINARY
Page 6: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E0-1-K

ET

.D

WG

E0-1

KETCHUM FACILITY

COVER SHEET & LEGEND

BLP 09/14/20

JK 09/14/20

ZPB 11/13/20

N/A

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

SURFACE MOUNTED PANELBOARD

1 POLE (2P, 3P, 4P, ETC.)1P

A

AC

ACLG

ADO

AF

AFF

AFG

AFCI

AHU

AL

ALT

AMP

AMPL

AMPERE

ABOVE COUNTER OR AIR

CONDITIONER

ABOVE CEILING

AUTOMATIC DOOR OPENER

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

ARC FAULT CIRCUIT

INTERRUPTER

AIR HANDLING UNIT

ALUMINUM

ALTERNATE

AMPERE

AMPLIFIER

ANNUN

APPROX

AQ-STAT

ARCH

AS

AT AMP TRIP

ATS

AUTO

AUX

AV

AWG

BATT

BD

BLDG

BMS

CND

CAB

CAT

CATV

CB

CCTV

CKT

CLG

COMB

CMPR

CONN

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AUXILIARY

AUDIO VISUAL

AMERICAN WIRE GAUGE

BATTERY

BOARD

BUILDING

BUILDING MANAGEMENT

SYSTEM

CONDUIT

CABINET

CATALOG

CABLE TELEVISION

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CEILING

COMBINATION

COMPRESSOR

CONNECTION

CONST CONSTRUCTION

CONT

CONTR CONTRACTOR

CONV

CP

CONVECTOR

CRT

CT

CTR

CU

CIRCULATING PUMP

CATHODE-RAY TUBE

CURRENT TRANSFORMER

CENTER

COPPER

CONTINUATION OR

CONTINUOUS

ARCHITECT, ARCHITECTURAL

AMP SWITCH

DCP

DEPT

DET

DIA

DISC

DIST

DN

DPR

DS

DT

DWG

EC

ELEC

EGC

EM

EMS

EMT

EP

EQUIP

EWC

EX

EXH

EXP

FA

FABP

FACP

FCU

FIXT

FLR

FLUOR

FU

FUDS

GA

GAL

GALV

GC

GEC

GFCI

GFP

GND

GRS

DOMESTIC WATER

CIRCULATING PUMP

DEPARTMENT

DETAIL

DIAMETER

DISCONNECT

DISTRIBUTION

DOWN

DAMPER

SAFETY DISCONNECT SWITCH

DOUBLE THROW

DRAWING

ELECTRICAL CONTRACTOR

ELECTRIC, ELECTRICAL

EQUIPMENT GROUNDING CONDUCTOR

EMERGENCY

ENERGY MANAGEMENT SYSTEM

ELECTRICAL METALLIC TUBING

ELECTRIC PNEUMATIC

EQUIPMENT

ELECTRIC WATER COOLER

EXISTING

EXHAUST

EXPLOSION PROOF

FIRE ALARM

FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FIXTURE

FLOOR

FLUORESCENT

FUSE

FUSED SAFETY DISCONNECT

SWITCH

GAUGE

GALLON

GALVANIZED

GENERAL CONTRACTOR

GROUNDING ELECTRODE CONDUCTOR

GROUND FAULT CIRCUIT

INTERRUPTER

GROUND FAULT PROTECTOR

GROUND

GALVANIZED RIGID STEEL

(CONDUIT)

GYP BD GYPSUM BOARD

HH

HORIZ

HP

HPF

HANDHOLE

HORIZONTAL

HORSEPOWER

HIGH POWER FACTOR

KV

KVA

KVAR

KW

KWH

LOC

LT

LTG

LTNG

LV

MAX

MCB

MCC

MDC

MDP

MFR

MFS

MH

MIC

MIN

MISC

MLO

MMS

MOA

MSP

MSBD

MT

MT.C

MTS

MTR

N.C.

NEC

KILOVOLT

KILOVOLT-AMPERE

KILOVOLT-AMPERE REACTIVE

KILOWATT

KILOWATT HOUR

LOCATE OR LOCATION

LIGHT

LIGHTING

LIGHTNING

LOW VOLTAGE

MAXIMUM

MAG.S MAGNETIC STARTER

M/C

MC

MOMENTARY CONTACT

MECHANICAL CONTRACTOR

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION CENTER

MAIN DISTRIBUTION PANEL

MANUFACTURER

MAIN FUSED DISCONNECT

SWITCH

MANHOLE

MICROPHONE

MINIMUM

MISCELLANEOUS

MAIN LUGS ONLY

MANUAL MOTOR STARTER

MULTIOUTLET ASSEMBLY

MOTOR STARTER PANELBOARD

MAIN SWITCHBOARD

MOUNT

EMPTY CONDUIT

MANUAL TRANSFER SWITCH

MOTOR, MOTORIZED

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

HT

HTG

HTR

HV

HVAC

HWP

IC

IG

IMC

I/W

J-BOX

HEIGHT

HEATING

HEATER

HIGH VOLTAGE

HEATING, VENTILATING AND

AIR CONDITIONING

HYDRONIC WATER PUMP

INTERRUPTING CAPACITY

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

INTERLOCK WITH

JUNCTION BOX PA

PB

PE

PED

PF

PH

PIV

PNL

PP

PR

PRI

PROJ

PRV

PT

PVC

PWR

QUAN

RCPT

REQD

RM

RSC

RTU

SC

SEC

SHT

SIM

S/N

SPEC

SPKR

SP

SR

SS

SSW

S/S

STA

STD

SURF

SUSE

PUBLIC ADDRESS

PULL BOX OR PUSHBUTTON

PNEUMATIC ELECTRIC

PEDESTAL

POWER FACTOR

PHASE

POST INDICATING VALVE

PANEL

POWER POLE

PAIR

PRIMARY

PROJECTION

POWER ROOF VENTILATOR

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

(CONDUIT)

POWER

W

QUANTITY

RECEPTACLE

REQUIRED

ROOM

RIGID STEEL CONDUIT

ROOF TOP UNIT

SURFACE CONDUIT

SECONDARY

SHEET

SIMILAR

SOLID NEUTRAL

SPECIFICATION

SPEAKER

SPARE

SURFACE RACEWAY

STAINLESS STEEL

SELECTOR SWITCH

STOP/START PUSHBUTTONS

STATION

STANDARD

SURFACE MOUNTED

SUITABLE FOR USE AS

ANGLE

@ AT

DELTA

'

"

L

FEET

INCHES

# NUMBER

Ø PHASE

C CENTER LINE

PL PLATE

W/

WG

WH

W/O

WP

XFMR

XFR

WATT

WITH

WIRE GUARD

WATER HEATER

WITHOUT

WEATHERPROOF

TRANSFORMER

TRANSFER

V

VA

VDT

VERT

VFD

VOL

UC

UE

UG

UH

UT

UTIL

UV

UNDER COUNTER

UNDERGROUND ELECTRICAL

UNDERGROUND

UNIT HEATER

UNDERGROUND TELEPHONE

UTILITY

UNIT VENTILATOR OR

ULTRAVIOLET

VOLT

VOLT-AMPERES

VIDEO DISPLAY TERMINAL

VERTICAL

VARIABLE FREQUENCY DRIVE

VOLUME

NIC

NL

N.O.

NPF

NTS

OH

OL

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NORMAL POWER FACTOR

NOT TO SCALE

OVERHEAD

OVERLOADS

SWBD

SYM

SYS

TEL

SWITCHBOARD

SYMMETRICAL

SYSTEM

TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM

TL

TR

TERMINAL

TWIST LOCK

T-STAT

TTC

TV

TVTC

TWPR

TAMPER RESISTANT

THERMOSTAT

TELEPHONE TERMINAL CABINET

TELEVISION

TELEVISION TERMINAL CABINET

TWISTED PAIR

ELECTRICAL SYMBOLS LEGEND ELECTRICAL ABBREVIATIONS LIST

MCCB MOLDED CASE CIRCUIT

BREAKER

SPD SURGE PROTECTION DEVICE

PM POWER METER

ERMS ENERGY REDUCTION

MAINTENANCE SWITCH

LSILONG TIME + SHORT TIME +

INSTANTANEOUS PROTECTION

LSIG

LONG TIME + SHORT TIME +

INSTANTANEOUS + GROUND

FAULT PROTECTION

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

MCP MOTOR CIRCUIT PROTECTOR

DISCONNECT SWITCH

ONE-LINE SYMBOLS LEGEND

LOW VOLTAGE FIXED CIRCUIT BREAKER

DELTA-Y CONNECTION

CONNECTION DOT

DISCONNECT SWITCH

LOW VOLTAGE FUSED SWITCH

GROUND CONNECTION

GROUNDED Y CONNECTION

POWER TRANSFORMER

EXISTING EQUIPMENT

NEW EQUIPMENT

ABOVE GRADE EXPOSED CONDUIT

UNDEGROUND CONDUIT

CONDUITS IN/OUT OF EQUIPMENT

AQUASTAT

APPROXIMATELY

ANNUNCIATOR

ARMS ARCHFLASH REDUCTION

MAINTENANCE SYSTEM

FO FIBER OPTIC

KCMIL ONE THOUSAND CIRCULAR MILS

SCH SCHEDULE

SERVICE EQUIPMENT

SW SWITCH

DC DIRECT CURRENT

TYP TYPICAL

DC1-1CABLE/CIRCUIT TAG

DC1-1CABLE/CIRCUIT TAG

NOTES

1. THE ELECTRICAL INSTALLATION SHALL MEET THE MINIMUM REQUIREMENTS OF THE

2017 NATIONAL ELECTRIC CODE AS ADOPTED BY THE STATE OF IDAHO AND LOCAL

BUILDING CODES.

2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND APPROVED AND SUITABLE FOR

THE INSTALLATION.

3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW THE GENERAL INTENT OF

LOCATIONS AND INSTALLATION REQUIREMENTS OF EQUIPMENT. EXACT LOCATIONS

AND INSTALLATION MATERIALS REQUIRED SHALL BE VERIFIED IN FIELD WITH ACTUAL

INSTALLED EQUIPMENT.

4. ALL EXISTING CONDITIONS SHALL BE VERIFIED AT THE JOB SITE PRIOR TO BID

SUBMITTALS.

5. ALL WALL AND CEILING PENETRATIONS SHALL BE SEALED WITH MATERIALS

APPROVED TO MAINTAIN FIRE RATINGS.

6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS

NOTED OTHERWISE.

7. MULTIWIRED BRANCH CIRCUITS (SHARED NEUTRALS) SHALL NOT BE USED.

8. PROVIDE PVC40 CONDUIT WITH PVC80 FITTINGS FOR ALL UNDERGROUND CONDUIT.

9. PROVIDE EMT CONDUIT FOR ALL INDOOR AND OUTDOOR ABOVEGROUND CONDUIT

PAINTED TO MATCH THE EXISTING CONDITIONS.

10. PROVIDE THWN/THHN COPPER CONDUCTORS FOR ALL POWER CONDUCTORS. ALL

CONDUCTORS #10 AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AND LARGER

SHALL BE STRANDED. TYPE NM CABLE IS NOT PERMITTED.

11. ALL CABLE TERMINATIONS AND FITTINGS SHALL BE RATED FOR A MINIMUM OF 75C.

12. PROVIDE BARE COPPER CONDUCTORS FOR BONDING. EQUIPMENT GROUNDING

CONDUCTORS SHALL BE COPPER WITH GREEN INSULATION.

13. ALL OUTDOOR EQUIPMENT SHALL BE NEMA TYPE-3R.

14. PROVIDE CURRENT LIMITING FUSES FOR ALL FUSES IN ACCORDANCE WITH UL-4248.

15. ELECTRICAL SWITCHBOARDS SHALL HAVE A NEMA TYPE-1 RATINGS WITH COPPER

BUSSING. THE CIRCUIT BREAKERS SHALL BE THE BOLT-ON TYPE.

16. GROUND RODS SHALL BE CONE POINTED COPPER, 10' IN LENGTH, WITH A 3/4"

DIAMETER; SECTIONAL RODS ARE PERMITTED.

17. PROVIDE A TRANSFORMER PAD AS REQUIRED BY IDAHO POWER.

18. LOCATE EXISTING UNDERGROUND UTILITIES IN THE THE PROPOSED AREA FOR THE

NEW SECONDARY CONDUITS FOR UNDERGROUND UTILITIES PRIOR TO DIGGING.

19. THIS FACILITY IS IN SEISMIC ZONE 2B, CONTRACTOR SHALL ADHERE TO THE LOCAL

CODES WHEN INSTALLING AND MOUNTING EQUIPMENT AND RACEWAYS.

AutoCAD SHX Text
PRELIMINARY
Page 7: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

E1

-1

-K

ET

.D

WG

E1-1

KETCHUM FACILITY

ONE LINE DIAGRAM

BLP 09/10/20

JK 09/10/20

ZPB 11/13/20

NONE

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

N G

1

2

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

4 4 4 4

1. THE PROPOSED ABB EV BUS CHARGER HAVE A POWER FACTOR OF 0.95.

2. CABLE AMPACITY CALCULATIONS ARE BASED ON A 105F MAXIMUM AMBIENT

TEMPERATURE.

3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE

DISCONNECTING MEANS.

NOTES

KEYED NOTES

UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, CT, AND METER. UTILITY TO

PROVIDE PRIMARY POWER CABLES AND ASSOCIATED RACEWAY.

CONTRACTOR TO TERMINATE CUSTOMER SUPPLIED CABLES DIRECTLY TO THE

UTILITY TRANSFORMER TERMINALS.

BOND NEW GROUNDING ELECTRODE TO EXISTING GROUNDING ELECTRODE

SYSTEM PER NEC 250.

PROVIDE SPARE BREAKER FOR FUTURE EV BUS CHARGERS.

PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE

IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS

DISCONNECTED PRIOR TO SERVICING.

PROVIDE 208Y/120V PANELBOARD WITH INTERGRAL 15KVA TRANSFORMER &

ASSOCIATED CIRCUIT BREAKERS. TRANSFORMER PERCENT IMPEDANCE

ASSUMED AT 2%. REFER TO PANEL SCHEDULE DRAWING FOR CIRCUIT

BREAKER SIZES.

ONE OF THE GROUND CONDUCTORS FROM DC CHARGER WILL PASS THROUGH

DC CHARGER DISPENSER A AND CONTINUE TO DISPENSER B.

1

2

3

4

5

55 55

DC1-1

DC1-2

DC1-5

DC2-1

DC2-4

DC2-5

DC1-4

6

6

P-2

P-3

P-4

P-1

3

P-0

DC1-3

DC2-2

DC2-3

7

B

B

7

B

7

AutoCAD SHX Text
1200 AMP BUS
AutoCAD SHX Text
MAIN BONDING JUMPERS
AutoCAD SHX Text
POWER DISTRIBUTION PANEL '480V SWITCHBOARD #1' (1200 AMP, 480Y/277V 3 , 4W, 42K AIC, NEMA 1, SUSE)
AutoCAD SHX Text
GROUNDING ELECTRODE CONDUCTOR #3/0 CU
AutoCAD SHX Text
1200AF 1200AT LSIG ARMS
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
MAIN BREAKER
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
150AF 125AT LSI
AutoCAD SHX Text
150AF 125AT LSI
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
400AF 300AT LSI
AutoCAD SHX Text
UTILITY SOURCE
AutoCAD SHX Text
UTILITY METER
AutoCAD SHX Text
(3)
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
M
AutoCAD SHX Text
UTILITY XFMR 750KVA 12.47KV-480Y/277V
AutoCAD SHX Text
XFMR CABINET
AutoCAD SHX Text
35AF 35AT LSI
AutoCAD SHX Text
NEUTRAL CONDUCTORS
AutoCAD SHX Text
AC PANEL #1 208Y/120V 3PH, 4W 60A BUS 50A MAIN BKR
AutoCAD SHX Text
XFMR 480V-208Y/120V 15KVA
AutoCAD SHX Text
(4) 4" CND 4" CND (4) 4-1/C 500KCMIL CU IN EACH CONDUIT4-1/C 500KCMIL CU IN EACH CONDUIT
AutoCAD SHX Text
3/4" CND 2-1/C #12 CU 1-1/C #12 CU GND
AutoCAD SHX Text
DC CHARGER #1 150KW
AutoCAD SHX Text
DC CHARGER DISPENSER #1A
AutoCAD SHX Text
DC CHARGER DISPENSER #1B
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
DC CHARGER DISPENSER #2A
AutoCAD SHX Text
DC CHARGER DISPENSER #2B
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU
AutoCAD SHX Text
DC CHARGER #2 150KW
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU
AutoCAD SHX Text
3/4" CND 3-1/C #6 CU 1-1/C #10 CU GND
AutoCAD SHX Text
AC PANEL #1 NEMA 1 ENCLOSURE
AutoCAD SHX Text
1-1/2" CND 2-1/C #6 CU GND 1-2/PR #18 TSP CU 8-OM3 FIBER OPTIC
AutoCAD SHX Text
1-1/2" CND 1-1/C #6 CU GND 3-1/C #14 CU 1-2/PR #18 TSP CU 4-OM3 FIBER OPTIC 1-CAT6 SHD
AutoCAD SHX Text
1-1/2" CND 1-1/C #6 CU GND 3-1/C #14 CU 1-2/PR #18 TSP CU 4-OM3 FIBER OPTIC 1-CAT6 SHD
AutoCAD SHX Text
2-1/2" CND 3-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
2-1/2" CND 3-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
2-1/2" CND 2-1/C 350KCMIL CU 1-1/C #4 CU GND
AutoCAD SHX Text
1-1/2" CND 2-1/C #6 CU GND 1-2/PR #18 TSP CU 8-OM3 FIBER OPTIC
AutoCAD SHX Text
PRELIMINARY
Page 8: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E3-1-K

ET

.D

WG

E3-1

KETCHUM FACILITY

ELECTRICAL PANEL SCHEDULES

BLP 09/14/20

JK 09/14/20

ZPB 11/13/20

NONE

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

1. TWO 400A & 150A SPARE BREAKERS ON 480V SWITCHBOARD #1 ARE FOR FUTURE DC

CHARGERS.

NOTES

KEYED NOTES

BREAKER SHALL COME EQUIPPED WITH A 30mA GFCI.1

1

1

1

1

AutoCAD SHX Text
PRELIMINARY
Page 9: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

3'-0

" M

IN

1'-6

"

3" TYP

RED PLASTIC ELECTRICAL

WARNING TAPE WITH MAGNETIC

LINING THAT READS "CAUTION -

ELECTRICAL LINE BURIED BELOW"

COMPACTED APPROVED BACKFILL

FINISHED GRADE

SAWCUT AND REPAIR CONCRETE AS

REQUIRED FOR NEW CONDUIT

SHOP FLOOR

FINISHED GRADE

UTILITY XFMR PAD

UTILITY

XFMR

24

"

LB

CONDULET

WATERPROOF SEAL AT

WALL PENETRATION

480V SWITCHBOARD #1

EXTERIOR

WALL

WALL PENETRATION MINIMUM

OF 24" ABOVE TOP OF

TRANSFORMER PAD

4" SCH 40 OR SCH 80 PVC

(TYP. UNDERGROUND)

4" RGC CONDUIT

(TYP. ABOVE

GROUND)

3'-1

0

1

8

"

2'-6"

2 1/2" DIA CONDUIT OPENING

2 1/2" DIA CONDUIT OPENING

1 1/2" DIA CONDUIT OPENING

2'-1

7

8

"

4

1

4

" 2

7

8

"4

1

2

"

C6X10.5

C6X10.5

C6

X1

0.5

C6

X1

0.5

2'-1

7

8

"

2"

1"

5/8" DIA HOLE (BOTTOM FLANGE ONLY)

FOR 1/2" DIA KWIK BOLT TZ-CS MIN 3"

EMBEDMENT TYPICAL (1) EACH CORNER

USE BEVELED WASHER.

BOLT CHARGERS TO

CHANNEL FRAME AS

NECESSARY

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E6-1-K

ET

.D

WG

E6-1

KETCHUM FACILITY

CONDUIT SECTIONS & DETAILS

BLP 09/18/20

JK 09/18/20

ZPB 11/13/20

AS INDICATED

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

TYPICAL DUCT SECTION1

E7-1

SCALE 1" = 1'-0"

WALL PENETRATION DETAIL

TYPICAL DUCT SECTION2

E7-1

NTS

KEYED NOTES

CONDUITS MUST PENETRATE EXTERIOR WALL 24" MINIMUM ABOVE TOP OF UTILITY XFMRPAD AND HAVE A WATERPROOF SEAL BETWEEN LB CONDULETS AND WALL PENETRATION.WATER PROOF SEAL TO BE FOAM APPROVED FOR CABLE INSULATION AND DUCT SEALCOMPOUND.

1

1

CHARGER SUPPORT FRAMES3

E7-1

SCALE 1"=1'-0"

MEMBER CONDUIT OPENINGS4

E7-1

SCALE 1"=1'-0"

TYP 3

SIDES1/8

NOTES:

ALL MATERIAL TO BE PAINTED CARBON STEEL.

CHARGER SUPPORT FRAME IS TO SIT ON THE

CONCRETE SLAB. GROUT UNDERNEATH AS NECESSARY

TO LEVEL THE FRAME.

B

AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
4
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
4
Page 10: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd

B

A ISSUED FOR BID 10/13/20 JK BLP ZPB JM

B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM

E7-1-K

ET

.D

WG

E7-1

KETCHUM FACILITY

FIRST FLOOR POWER PLAN

BLP 09/14/20

JK 09/14/20

ZPB 11/13/20

3/32"=1'-0"

NORTH

TRUE

NORTH

PLAN

FEET

3/32" = 1'-0"

201050

THIS DRAWING WAS PREPARED BY POWER

ENGINEERS, INC. FOR A SPECIFIC PROJECT,

TAKING INTO CONSIDERATION THE SPECIFIC

AND UNIQUE REQUIREMENTS OF THE

PROJECT. REUSE OF THIS DRAWING OR ANY

INFORMATION CONTAINED IN THIS DRAWING

FOR ANY PURPOSE IS PROHIBITED UNLESS

WRITTEN PERMISSION FROM BOTH POWER

AND POWER'S CLIENT IS GRANTED.

MOUNTAIN RIDES

JOB NUMBER

DRAWING NUMBER

REVISIONSREV

SCALE:

DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD

DSGN

CKD

DRN

FOR 24x36 DWG ONLY

1 2 3 4 5 6 7 8

REV

E

D

C

B

A

165994

ELECTRIC BUS CHARGING

1. REFER TO ONE-LINE DIAGRAM DRAWING E1-1 FOR CONDUIT & CABLE

REQUIREMENTS.

2. CONTRACTOR TO PROVIDE EQUIPMENT, CONDUITS, & TERMINATE POWER &

COMMUNICATION CABLES. REFER TO ONE LINE DIAGRAM FOR CABLE SIZING.

3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE

DISCONNECTING MEANS.

4. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO DETERMINE

THE BEST CONDUIT ROUTE IN THE FIELD.

NOTES

KEYED NOTES

UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, TRANSFORMER PAD,

PRIMARY CABLES & RACEWAYS.

CONTRACTOR SCOPE INCLUDES TERMINATION TO THE LOAD SIDE OF THE

UTILITY TRANSFORMER.

PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE

IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS

DISCONNECTED PRIOR TO SERVICING."

PROVIDE CUSTOM FABRICATED STEEL SUPPORT STAND WITH A 6" C-CHANNEL

BASE FOR ABOVEGROUND CONDUIT ENTRY TO THE BOTTOM OF THE EV

CHARGER.

CONDUITS MUST PENETRATE WALL 24" MINIMUM ABOVE TOP OF THE UTILITY

TRANSFORMER PAD AND HAVE WATER PROOF SEAL AT WALL PENETRATION.

REFER TO SHEET E6-1 FOR DETAIL.

1

2

3

4

UTILITY

XFMR

DC2-4

DC1-1

DC2-2

DC2-3

DC2-5

DC2-1

DC1-2

DC1-3

DC1-4

DC1-5

DC CHARGER #2

DC CHARGER #1

DC CHARGER

DISPENSER 1B

DC CHARGER

DISPENSER 2A

480V SWITCHBOARD #1

DC CHARGER

DISPENSER 1A

DC CHARGER

DISPENSER 2B

4

4

AC PANEL #1

& INTEGRAL

XFMR

3

3

3

3

1 2

5

1

E6-1

P-1

P-2P-0

P-4

P-3

SCALE: 3/32" = 1'-0"

1

FIRST FLOOR POWER PLAN

2

E6-1

5

EXISTING PANEL

EXISTING STARTER

EXISTING PANEL

B

AutoCAD SHX Text
PRELIMINARY