B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E0-1-B
EL.D
WG
E0-1
BELLEVUE FACILITY
COVER SHEET & LEGEND
BLP 09/14/20
JK 09/14/20
ZPB 11/13/20
N/A
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
NOTES
SURFACE MOUNTED PANELBOARD
1 POLE (2P, 3P, 4P, ETC.)1P
A
AC
ACLG
ADO
AF
AFF
AFG
AFCI
AHU
AL
ALT
AMP
AMPL
AMPERE
ABOVE COUNTER OR AIR
CONDITIONER
ABOVE CEILING
AUTOMATIC DOOR OPENER
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ARC FAULT CIRCUIT
INTERRUPTER
AIR HANDLING UNIT
ALUMINUM
ALTERNATE
AMPERE
AMPLIFIER
ANNUN
APPROX
AQ-STAT
ARCH
AS
AT AMP TRIP
ATS
AUTO
AUX
AV
AWG
BATT
BD
BLDG
BMS
CND
CAB
CAT
CATV
CB
CCTV
CKT
CLG
COMB
CMPR
CONN
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AUDIO VISUAL
AMERICAN WIRE GAUGE
BATTERY
BOARD
BUILDING
BUILDING MANAGEMENT
SYSTEM
CONDUIT
CABINET
CATALOG
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
COMBINATION
COMPRESSOR
CONNECTION
CONST CONSTRUCTION
CONT
CONTR CONTRACTOR
CONV
CP
CONVECTOR
CRT
CT
CTR
CU
CIRCULATING PUMP
CATHODE-RAY TUBE
CURRENT TRANSFORMER
CENTER
COPPER
CONTINUATION OR
CONTINUOUS
ARCHITECT, ARCHITECTURAL
AMP SWITCH
DCP
DEPT
DET
DIA
DISC
DIST
DN
DPR
DS
DT
DWG
EC
ELEC
EGC
EM
EMS
EMT
EP
EQUIP
EWC
EX
EXH
EXP
FA
FABP
FACP
FCU
FIXT
FLR
FLUOR
FU
FUDS
GA
GAL
GALV
GC
GEC
GFCI
GFP
GND
GRS
DOMESTIC WATER
CIRCULATING PUMP
DEPARTMENT
DETAIL
DIAMETER
DISCONNECT
DISTRIBUTION
DOWN
DAMPER
SAFETY DISCONNECT SWITCH
DOUBLE THROW
DRAWING
ELECTRICAL CONTRACTOR
ELECTRIC, ELECTRICAL
EQUIPMENT GROUNDING CONDUCTOR
EMERGENCY
ENERGY MANAGEMENT SYSTEM
ELECTRICAL METALLIC TUBING
ELECTRIC PNEUMATIC
EQUIPMENT
ELECTRIC WATER COOLER
EXISTING
EXHAUST
EXPLOSION PROOF
FIRE ALARM
FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FIXTURE
FLOOR
FLUORESCENT
FUSE
FUSED SAFETY DISCONNECT
SWITCH
GAUGE
GALLON
GALVANIZED
GENERAL CONTRACTOR
GROUNDING ELECTRODE CONDUCTOR
GROUND FAULT CIRCUIT
INTERRUPTER
GROUND FAULT PROTECTOR
GROUND
GALVANIZED RIGID STEEL
(CONDUIT)
GYP BD GYPSUM BOARD
HH
HORIZ
HP
HPF
HANDHOLE
HORIZONTAL
HORSEPOWER
HIGH POWER FACTOR
KV
KVA
KVAR
KW
KWH
LOC
LT
LTG
LTNG
LV
MAX
MCB
MCC
MDC
MDP
MFR
MFS
MH
MIC
MIN
MISC
MLO
MMS
MOA
MSP
MSBD
MT
MT.C
MTS
MTR
N.C.
NEC
KILOVOLT
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KILOWATT HOUR
LOCATE OR LOCATION
LIGHT
LIGHTING
LIGHTNING
LOW VOLTAGE
MAXIMUM
MAG.S MAGNETIC STARTER
M/C
MC
MOMENTARY CONTACT
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION CENTER
MAIN DISTRIBUTION PANEL
MANUFACTURER
MAIN FUSED DISCONNECT
SWITCH
MANHOLE
MICROPHONE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MANUAL MOTOR STARTER
MULTIOUTLET ASSEMBLY
MOTOR STARTER PANELBOARD
MAIN SWITCHBOARD
MOUNT
EMPTY CONDUIT
MANUAL TRANSFER SWITCH
MOTOR, MOTORIZED
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
HT
HTG
HTR
HV
HVAC
HWP
IC
IG
IMC
I/W
J-BOX
HEIGHT
HEATING
HEATER
HIGH VOLTAGE
HEATING, VENTILATING AND
AIR CONDITIONING
HYDRONIC WATER PUMP
INTERRUPTING CAPACITY
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
INTERLOCK WITH
JUNCTION BOX PA
PB
PE
PED
PF
PH
PIV
PNL
PP
PR
PRI
PROJ
PRV
PT
PVC
PWR
QUAN
RCPT
REQD
RM
RSC
RTU
SC
SEC
SHT
SIM
S/N
SPEC
SPKR
SP
SR
SS
SSW
S/S
STA
STD
SURF
SUSE
PUBLIC ADDRESS
PULL BOX OR PUSHBUTTON
PNEUMATIC ELECTRIC
PEDESTAL
POWER FACTOR
PHASE
POST INDICATING VALVE
PANEL
POWER POLE
PAIR
PRIMARY
PROJECTION
POWER ROOF VENTILATOR
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
(CONDUIT)
POWER
W
QUANTITY
RECEPTACLE
REQUIRED
ROOM
RIGID STEEL CONDUIT
ROOF TOP UNIT
SURFACE CONDUIT
SECONDARY
SHEET
SIMILAR
SOLID NEUTRAL
SPECIFICATION
SPEAKER
SPARE
SURFACE RACEWAY
STAINLESS STEEL
SELECTOR SWITCH
STOP/START PUSHBUTTONS
STATION
STANDARD
SURFACE MOUNTED
SUITABLE FOR USE AS
ANGLE
@ AT
DELTA
'
"
L
FEET
INCHES
# NUMBER
Ø PHASE
C CENTER LINE
PL PLATE
W/
WG
WH
W/O
WP
XFMR
XFR
WATT
WITH
WIRE GUARD
WATER HEATER
WITHOUT
WEATHERPROOF
TRANSFORMER
TRANSFER
V
VA
VDT
VERT
VFD
VOL
UC
UE
UG
UH
UT
UTIL
UV
UNDER COUNTER
UNDERGROUND ELECTRICAL
UNDERGROUND
UNIT HEATER
UNDERGROUND TELEPHONE
UTILITY
UNIT VENTILATOR OR
ULTRAVIOLET
VOLT
VOLT-AMPERES
VIDEO DISPLAY TERMINAL
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLUME
NIC
NL
N.O.
NPF
NTS
OH
OL
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NORMAL POWER FACTOR
NOT TO SCALE
OVERHEAD
OVERLOADS
SWBD
SYM
SYS
TEL
SWITCHBOARD
SYMMETRICAL
SYSTEM
TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM
TL
TR
TERMINAL
TWIST LOCK
T-STAT
TTC
TV
TVTC
TWPR
TAMPER RESISTANT
THERMOSTAT
TELEPHONE TERMINAL CABINET
TELEVISION
TELEVISION TERMINAL CABINET
TWISTED PAIR
ELECTRICAL SYMBOLS LEGEND ELECTRICAL ABBREVIATIONS LIST
MCCB MOLDED CASE CIRCUIT
BREAKER
SPD SURGE PROTECTION DEVICE
PM POWER METER
ERMS ENERGY REDUCTION
MAINTENANCE SWITCH
LSILONG TIME + SHORT TIME +
INSTANTANEOUS PROTECTION
LSIG
LONG TIME + SHORT TIME +
INSTANTANEOUS + GROUND
FAULT PROTECTION
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
MCP MOTOR CIRCUIT PROTECTOR
DISCONNECT SWITCH
ONE-LINE SYMBOLS LEGEND
LOW VOLTAGE FIXED CIRCUIT BREAKER
DELTA-Y CONNECTION
CONNECTION DOT
DISCONNECT SWITCH
LOW VOLTAGE FUSED SWITCH
GROUND CONNECTION
GROUNDED Y CONNECTION
POWER TRANSFORMER
EXISTING EQUIPMENT
NEW EQUIPMENT
ABOVE GRADE EXPOSED CONDUIT
UNDEGROUND CONDUIT
CONDUITS IN/OUT OF EQUIPMENT
AQUASTAT
APPROXIMATELY
ANNUNCIATOR
ARMS ARCHFLASH REDUCTION
MAINTENANCE SYSTEM
FO FIBER OPTIC
KCMIL ONE THOUSAND CIRCULAR MILS
SCH SCHEDULE
SERVICE EQUIPMENT
SW SWITCH
DC DIRECT CURRENT
TYP TYPICAL
DC1-1CABLE/CIRCUIT TAG
DC1-1CABLE/CIRCUIT TAG
1. THE ELECTRICAL INSTALLATION SHALL MEET THE MINIMUM REQUIREMENTS OF THE
2017 NATIONAL ELECTRIC CODE AS ADOPTED BY THE STATE OF IDAHO AND LOCAL
BUILDING CODES.
2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND APPROVED AND SUITABLE FOR
THE INSTALLATION.
3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW THE GENERAL INTENT OF
LOCATIONS AND INSTALLATION REQUIREMENTS OF EQUIPMENT. EXACT LOCATIONS
AND INSTALLATION MATERIALS REQUIRED SHALL BE VERIFIED IN FIELD WITH ACTUAL
INSTALLED EQUIPMENT.
4. ALL EXISTING CONDITIONS SHALL BE VERIFIED AT THE JOB SITE PRIOR TO BID
SUBMITTALS.
5. ALL WALL AND CEILING PENETRATIONS SHALL BE SEALED WITH MATERIALS
APPROVED TO MAINTAIN FIRE RATINGS.
6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS
NOTED OTHERWISE.
7. MULTIWIRED BRANCH CIRCUITS (SHARED NEUTRALS) SHALL NOT BE USED.
8. PROVIDE PVC40 CONDUIT WITH PVC80 FITTINGS FOR ALL UNDERGROUND CONDUIT.
9. PROVIDE EMT CONDUIT FOR ALL INDOOR AND OUTDOOR ABOVEGROUND CONDUIT
PAINTED TO MATCH THE EXISTING CONDITIONS.
10. PROVIDE THWN/THHN COPPER CONDUCTORS FOR ALL POWER CONDUCTORS. ALL
CONDUCTORS #10 AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AND LARGER
SHALL BE STRANDED. TYPE NM CABLE IS NOT PERMITTED.
11. ALL CABLE TERMINATIONS AND FITTINGS SHALL BE RATED FOR A MINIMUM OF 75C.
12. PROVIDE BARE COPPER CONDUCTORS FOR BONDING. EQUIPMENT GROUNDING
CONDUCTORS SHALL BE COPPER WITH GREEN INSULATION.
13. ALL OUTDOOR EQUIPMENT SHALL BE NEMA TYPE-3R.
14. PROVIDE CURRENT LIMITING FUSES FOR ALL FUSES IN ACCORDANCE WITH UL-4248.
15. ELECTRICAL SWITCHBOARDS SHALL HAVE A NEMA TYPE-1 RATINGS WITH COPPER
BUSSING. THE CIRCUIT BREAKERS SHALL BE THE BOLT-ON TYPE.
16. GROUND RODS SHALL BE CONE POINTED COPPER, 10' IN LENGTH, WITH A 3/4"
DIAMETER; SECTIONAL RODS ARE PERMITTED.
17. PROVIDE A TRANSFORMER PAD AS REQUIRED BY IDAHO POWER.
18. LOCATE EXISTING UNDERGROUND UTILITIES IN THE THE PROPOSED AREA FOR THE
NEW SECONDARY CONDUITS FOR UNDERGROUND UTILITIES PRIOR TO DIGGING.
19. THIS FACILITY IS IN SEISMIC ZONE 2B, CONTRACTOR SHALL ADHERE TO THE LOCAL
CODES WHEN INSTALLING AND MOUNTING EQUIPMENT AND RACEWAYS.
![Page 2: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/2.jpg)
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E1
-1
-B
EL
.D
WG
E1-1
BELLEVUE FACILITY
ONE LINE DIAGRAM
BLP 09/10/20
JK 09/10/20
ZPB 11/13/20
NONE
1. THE PROPOSED ABB EV BUS CHARGER HAVE A POWER FACTOR OF 0.95.
2. CABLE AMPACITY CALCULATIONS ARE BASED ON A 105F MAXIMUM AMBIENT
TEMPERATURE.
3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE
DISCONNECTING MEANS.
NOTES
KEYED NOTES
UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, CT, AND METER. UTILITY TO
PROVIDE PRIMARY POWER CABLES AND ASSOCIATED RACEWAY.
CONTRACTOR TO TERMINATE CUSTOMER SUPPLIED CABLES DIRECTLY TO THE
UTILITY TRANSFORMER TERMINALS.
BOND NEW GROUNDING ELECTRODE TO EXISTING GROUNDING ELECTRODE
SYSTEM PER NEC 250.
PROVIDE SPARE BREAKER FOR FUTURE EV BUS CHARGERS.
PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS
DISCONNECTED PRIOR TO SERVICING.
PROVIDE 208Y/120V PANELBOARD WITH INTERGRAL 15KVA TRANSFORMER &
ASSOCIATED CIRCUIT BREAKERS. TRANSFORMER PERCENT IMPEDANCE
ASSUMED AT 2%. REFER TO PANEL SCHEDULE DRAWING FOR CIRCUIT
BREAKER SIZES.
ONE OF THE GROUND CONDUCTORS FROM DC CHARGER WILL PASS THROUGH
DC CHARGER DISPENSER A AND CONTINUE TO DISPENSER B.
1
2
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
N G
1
3
3
4
4
2
55
5
55
6
DC1-1
DC1-4
DC1-5
DC2-1
DC2-4
DC2-5
6
P-2
P-3
P-4
P-1
P-0
4
DC1-2
DC1-3
DC2-2
DC2-3
B
7
B
7
7
B
![Page 3: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/3.jpg)
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E3-1-B
EL.D
WG
E3-1
BELLEVUE FACILITY
ELECTRICAL PANEL SCHEDULES
BLP 09/14/20
JK 09/14/20
ZPB 11/13/20
NONE
1. TWO 400A SPARE BREAKERS ON 480V SWITCHBOARD #1 IS FOR A FUTURE DC
CHARGER.
NOTES
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
KEYED NOTES
BREAKER SHALL COME EQUIPPED WITH A 30mA GFCI.1
1
1
1
1
![Page 4: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/4.jpg)
3'-0
" M
IN
1'-6
"
3" TYP
RED PLASTIC ELECTRICAL
WARNING TAPE WITH MAGNETIC
LINING THAT READS "CAUTION -
ELECTRICAL LINE BURIED BELOW"
4" SCH 40 OR SCH 80 PVC
(TYP.)
COMPACTED APPROVED BACKFILL
FINISHED GRADE
SAWCUT AND REPAIR CONCRETE AS
REQUIRED FOR NEW CONDUIT
4'-10"
1'-1
1
2
"
3'-1
0
1
8
"
2 1/2" DIA CONDUIT OPENING
2 1/2" DIA CONDUIT OPENING
1 1/2" DIA CONDUIT OPENING
5'-2
1
8
"
1
1
2
"
3"
C6X10.5
C6X10.5
C6
X1
0.5
C6
X1
0.5
4'-1
1
5
8
"
(E) CMU WALL
NOTES:
1. 19-W4 GALVANIZED STEEL BAR GRATING 1-1/2"
HEIGHT, 1/8" THICK
2. FRAME IS TO SIT ON THE CONCRETE SLAB.
LEVEL WITH GROUT AS NECESSARY.
3. ALL STEEL MEMBERS TO BE PAINTED CARBON
STEEL.
BOLT CHARGERS TO
CHANNEL FRAME
AS NECESSARY
C6
X1
0.5
C6
X1
0.5
2'-5" 2'-5"
2'-3" 2'-3"
2 1/2" DIA CONDUIT OPENING
2 1/2" DIA CONDUIT OPENING
4'-10"
1'-10" 1'-10"
1 1/2" DIA CONDUIT OPENING
NOTE 1
1
1
2
"
3"
5'-2
1
8
"
TYP
FLANGES
1/8
L3X3X1/4
5/8" DIA HOLE TYP FOR
1/2" DIA THREADED ROD
W/HILTI HIT-HY270 EPOXY, MIN 5"
EMBEDMENT FULLY GROUT CMU
CELLS BEFORE INSTALLATION
DIA. GRADE
(2) 1/2" A325 BOLT TYP
C6 SEE PLAN
1
1
2
"
1"
1"
6"
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E6-1-B
EL.D
WG
E6-1
BELLEVUE FACILITY
CONDUIT SECTIONS & DETAILS
BLP 09/18/20
JK 09/18/20
ZPB 11/13/20
AS INDICATED
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
TYPICAL DUCT SECTION1
E7-1
SCALE 1" = 1'-0"
CHARGER SUPPORT FRAME2
E7-1
SCALE 1" = 1'-0"
MEMBER CONDUIT OPENINGS3
E7-1
SCALE 1" = 1'-0"
TYP 3
SIDES
CHANNEL TO MASONRY WALL CONNECTION4
E7-1
SCALE 3" = 1'-0"
1/8
TYP
MEMBER CONDUIT OPENINGS5
E7-1
SCALE 1" = 1'-0"
B
![Page 5: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/5.jpg)
DC2-4
DC2-1
DC2-2
DC2-3
DC2-5
DC1-1DC1-2
DC1-3
DC1-4
DC1-5
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E7-1-B
EL.D
WG
E7-1
BELLEVUE FACILITY
FIRST FLOOR POWER PLAN
BLP 09/14/20
JK 09/14/20
ZPB 11/13/20
1/8" = 1'-0"
1. REFER TO ONE-LINE DIAGRAM DRAWING E1-1 FOR CONDUIT & CABLE
REQUIREMENTS.
2. CONTRACTOR TO PROVIDE EQUIPMENT, CONDUITS, & TERMINATE POWER &
COMMUNICATION CABLES. REFER TO ONE LINE DIAGRAM FOR CABLE SIZING.
3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE
DISCONNECTING MEANS.
4. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO DETERMINE
THE BEST CONDUIT ROUTE IN THE FIELD.
NOTES
KEYED NOTES
UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, TRANSFORMER PAD,
PRIMARY CABLES & RACEWAYS.
CONTRACTOR SCOPE INCLUDES TERMINATION TO THE LOAD SIDE OF THE
UTILITY TRANSFORMER.
PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS
DISCONNECTED PRIOR TO SERVICING."
PROVIDE CUSTOM FABRICATED STEEL SUPPORT STAND WITH A 6" C-CHANNEL
BASE FOR ABOVEGROUND CONDUIT ENTRY TO THE BOTTOM OF THE EV
CHARGER.
PROVIDE 10" x 10" WIREWAY ON TOP OF 480V SWITCHBOARD #1 TO BE USED AS
A PULLBOX AND ENTRY POINT FOR CABLE INTO THE PANEL.
PROVIDE CONDUIT SUPPORT FOR VERTICAL CONDUITS CONTAINING DC1-1,
DC1-2, DC2-1, DC2-2 EXITING THE DC CHARGERS.
1
NORTH
0 FEET
1/8" = 1'-0"
20105
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
UTILITY
XFMR
DC CHARGER #2
DC CHARGER #1
DC CHARGER
DISPENSER 1B
DC CHARGER
DISPENSER 2A
480V
SWITCHBOARD
#1
DC CHARGER
DISPENSER 1A
DC CHARGER
DISPENSER 2B
1
2
2
3
3
3
3
3
4
4
4
1
E6-1
SCALE: 1/8" = 1'-0"
1
FIRST FLOOR POWER PLAN
P-3
P-2
P-4
P-1
P-0
AC PANEL #1
& INTEGRAL
XFMR
5
6
6
6
5
![Page 6: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/6.jpg)
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E0-1-K
ET
.D
WG
E0-1
KETCHUM FACILITY
COVER SHEET & LEGEND
BLP 09/14/20
JK 09/14/20
ZPB 11/13/20
N/A
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
SURFACE MOUNTED PANELBOARD
1 POLE (2P, 3P, 4P, ETC.)1P
A
AC
ACLG
ADO
AF
AFF
AFG
AFCI
AHU
AL
ALT
AMP
AMPL
AMPERE
ABOVE COUNTER OR AIR
CONDITIONER
ABOVE CEILING
AUTOMATIC DOOR OPENER
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ARC FAULT CIRCUIT
INTERRUPTER
AIR HANDLING UNIT
ALUMINUM
ALTERNATE
AMPERE
AMPLIFIER
ANNUN
APPROX
AQ-STAT
ARCH
AS
AT AMP TRIP
ATS
AUTO
AUX
AV
AWG
BATT
BD
BLDG
BMS
CND
CAB
CAT
CATV
CB
CCTV
CKT
CLG
COMB
CMPR
CONN
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AUDIO VISUAL
AMERICAN WIRE GAUGE
BATTERY
BOARD
BUILDING
BUILDING MANAGEMENT
SYSTEM
CONDUIT
CABINET
CATALOG
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
COMBINATION
COMPRESSOR
CONNECTION
CONST CONSTRUCTION
CONT
CONTR CONTRACTOR
CONV
CP
CONVECTOR
CRT
CT
CTR
CU
CIRCULATING PUMP
CATHODE-RAY TUBE
CURRENT TRANSFORMER
CENTER
COPPER
CONTINUATION OR
CONTINUOUS
ARCHITECT, ARCHITECTURAL
AMP SWITCH
DCP
DEPT
DET
DIA
DISC
DIST
DN
DPR
DS
DT
DWG
EC
ELEC
EGC
EM
EMS
EMT
EP
EQUIP
EWC
EX
EXH
EXP
FA
FABP
FACP
FCU
FIXT
FLR
FLUOR
FU
FUDS
GA
GAL
GALV
GC
GEC
GFCI
GFP
GND
GRS
DOMESTIC WATER
CIRCULATING PUMP
DEPARTMENT
DETAIL
DIAMETER
DISCONNECT
DISTRIBUTION
DOWN
DAMPER
SAFETY DISCONNECT SWITCH
DOUBLE THROW
DRAWING
ELECTRICAL CONTRACTOR
ELECTRIC, ELECTRICAL
EQUIPMENT GROUNDING CONDUCTOR
EMERGENCY
ENERGY MANAGEMENT SYSTEM
ELECTRICAL METALLIC TUBING
ELECTRIC PNEUMATIC
EQUIPMENT
ELECTRIC WATER COOLER
EXISTING
EXHAUST
EXPLOSION PROOF
FIRE ALARM
FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FIXTURE
FLOOR
FLUORESCENT
FUSE
FUSED SAFETY DISCONNECT
SWITCH
GAUGE
GALLON
GALVANIZED
GENERAL CONTRACTOR
GROUNDING ELECTRODE CONDUCTOR
GROUND FAULT CIRCUIT
INTERRUPTER
GROUND FAULT PROTECTOR
GROUND
GALVANIZED RIGID STEEL
(CONDUIT)
GYP BD GYPSUM BOARD
HH
HORIZ
HP
HPF
HANDHOLE
HORIZONTAL
HORSEPOWER
HIGH POWER FACTOR
KV
KVA
KVAR
KW
KWH
LOC
LT
LTG
LTNG
LV
MAX
MCB
MCC
MDC
MDP
MFR
MFS
MH
MIC
MIN
MISC
MLO
MMS
MOA
MSP
MSBD
MT
MT.C
MTS
MTR
N.C.
NEC
KILOVOLT
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KILOWATT HOUR
LOCATE OR LOCATION
LIGHT
LIGHTING
LIGHTNING
LOW VOLTAGE
MAXIMUM
MAG.S MAGNETIC STARTER
M/C
MC
MOMENTARY CONTACT
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION CENTER
MAIN DISTRIBUTION PANEL
MANUFACTURER
MAIN FUSED DISCONNECT
SWITCH
MANHOLE
MICROPHONE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MANUAL MOTOR STARTER
MULTIOUTLET ASSEMBLY
MOTOR STARTER PANELBOARD
MAIN SWITCHBOARD
MOUNT
EMPTY CONDUIT
MANUAL TRANSFER SWITCH
MOTOR, MOTORIZED
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
HT
HTG
HTR
HV
HVAC
HWP
IC
IG
IMC
I/W
J-BOX
HEIGHT
HEATING
HEATER
HIGH VOLTAGE
HEATING, VENTILATING AND
AIR CONDITIONING
HYDRONIC WATER PUMP
INTERRUPTING CAPACITY
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
INTERLOCK WITH
JUNCTION BOX PA
PB
PE
PED
PF
PH
PIV
PNL
PP
PR
PRI
PROJ
PRV
PT
PVC
PWR
QUAN
RCPT
REQD
RM
RSC
RTU
SC
SEC
SHT
SIM
S/N
SPEC
SPKR
SP
SR
SS
SSW
S/S
STA
STD
SURF
SUSE
PUBLIC ADDRESS
PULL BOX OR PUSHBUTTON
PNEUMATIC ELECTRIC
PEDESTAL
POWER FACTOR
PHASE
POST INDICATING VALVE
PANEL
POWER POLE
PAIR
PRIMARY
PROJECTION
POWER ROOF VENTILATOR
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
(CONDUIT)
POWER
W
QUANTITY
RECEPTACLE
REQUIRED
ROOM
RIGID STEEL CONDUIT
ROOF TOP UNIT
SURFACE CONDUIT
SECONDARY
SHEET
SIMILAR
SOLID NEUTRAL
SPECIFICATION
SPEAKER
SPARE
SURFACE RACEWAY
STAINLESS STEEL
SELECTOR SWITCH
STOP/START PUSHBUTTONS
STATION
STANDARD
SURFACE MOUNTED
SUITABLE FOR USE AS
ANGLE
@ AT
DELTA
'
"
L
FEET
INCHES
# NUMBER
Ø PHASE
C CENTER LINE
PL PLATE
W/
WG
WH
W/O
WP
XFMR
XFR
WATT
WITH
WIRE GUARD
WATER HEATER
WITHOUT
WEATHERPROOF
TRANSFORMER
TRANSFER
V
VA
VDT
VERT
VFD
VOL
UC
UE
UG
UH
UT
UTIL
UV
UNDER COUNTER
UNDERGROUND ELECTRICAL
UNDERGROUND
UNIT HEATER
UNDERGROUND TELEPHONE
UTILITY
UNIT VENTILATOR OR
ULTRAVIOLET
VOLT
VOLT-AMPERES
VIDEO DISPLAY TERMINAL
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLUME
NIC
NL
N.O.
NPF
NTS
OH
OL
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NORMAL POWER FACTOR
NOT TO SCALE
OVERHEAD
OVERLOADS
SWBD
SYM
SYS
TEL
SWITCHBOARD
SYMMETRICAL
SYSTEM
TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM
TL
TR
TERMINAL
TWIST LOCK
T-STAT
TTC
TV
TVTC
TWPR
TAMPER RESISTANT
THERMOSTAT
TELEPHONE TERMINAL CABINET
TELEVISION
TELEVISION TERMINAL CABINET
TWISTED PAIR
ELECTRICAL SYMBOLS LEGEND ELECTRICAL ABBREVIATIONS LIST
MCCB MOLDED CASE CIRCUIT
BREAKER
SPD SURGE PROTECTION DEVICE
PM POWER METER
ERMS ENERGY REDUCTION
MAINTENANCE SWITCH
LSILONG TIME + SHORT TIME +
INSTANTANEOUS PROTECTION
LSIG
LONG TIME + SHORT TIME +
INSTANTANEOUS + GROUND
FAULT PROTECTION
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
MCP MOTOR CIRCUIT PROTECTOR
DISCONNECT SWITCH
ONE-LINE SYMBOLS LEGEND
LOW VOLTAGE FIXED CIRCUIT BREAKER
DELTA-Y CONNECTION
CONNECTION DOT
DISCONNECT SWITCH
LOW VOLTAGE FUSED SWITCH
GROUND CONNECTION
GROUNDED Y CONNECTION
POWER TRANSFORMER
EXISTING EQUIPMENT
NEW EQUIPMENT
ABOVE GRADE EXPOSED CONDUIT
UNDEGROUND CONDUIT
CONDUITS IN/OUT OF EQUIPMENT
AQUASTAT
APPROXIMATELY
ANNUNCIATOR
ARMS ARCHFLASH REDUCTION
MAINTENANCE SYSTEM
FO FIBER OPTIC
KCMIL ONE THOUSAND CIRCULAR MILS
SCH SCHEDULE
SERVICE EQUIPMENT
SW SWITCH
DC DIRECT CURRENT
TYP TYPICAL
DC1-1CABLE/CIRCUIT TAG
DC1-1CABLE/CIRCUIT TAG
NOTES
1. THE ELECTRICAL INSTALLATION SHALL MEET THE MINIMUM REQUIREMENTS OF THE
2017 NATIONAL ELECTRIC CODE AS ADOPTED BY THE STATE OF IDAHO AND LOCAL
BUILDING CODES.
2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND APPROVED AND SUITABLE FOR
THE INSTALLATION.
3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW THE GENERAL INTENT OF
LOCATIONS AND INSTALLATION REQUIREMENTS OF EQUIPMENT. EXACT LOCATIONS
AND INSTALLATION MATERIALS REQUIRED SHALL BE VERIFIED IN FIELD WITH ACTUAL
INSTALLED EQUIPMENT.
4. ALL EXISTING CONDITIONS SHALL BE VERIFIED AT THE JOB SITE PRIOR TO BID
SUBMITTALS.
5. ALL WALL AND CEILING PENETRATIONS SHALL BE SEALED WITH MATERIALS
APPROVED TO MAINTAIN FIRE RATINGS.
6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS
NOTED OTHERWISE.
7. MULTIWIRED BRANCH CIRCUITS (SHARED NEUTRALS) SHALL NOT BE USED.
8. PROVIDE PVC40 CONDUIT WITH PVC80 FITTINGS FOR ALL UNDERGROUND CONDUIT.
9. PROVIDE EMT CONDUIT FOR ALL INDOOR AND OUTDOOR ABOVEGROUND CONDUIT
PAINTED TO MATCH THE EXISTING CONDITIONS.
10. PROVIDE THWN/THHN COPPER CONDUCTORS FOR ALL POWER CONDUCTORS. ALL
CONDUCTORS #10 AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AND LARGER
SHALL BE STRANDED. TYPE NM CABLE IS NOT PERMITTED.
11. ALL CABLE TERMINATIONS AND FITTINGS SHALL BE RATED FOR A MINIMUM OF 75C.
12. PROVIDE BARE COPPER CONDUCTORS FOR BONDING. EQUIPMENT GROUNDING
CONDUCTORS SHALL BE COPPER WITH GREEN INSULATION.
13. ALL OUTDOOR EQUIPMENT SHALL BE NEMA TYPE-3R.
14. PROVIDE CURRENT LIMITING FUSES FOR ALL FUSES IN ACCORDANCE WITH UL-4248.
15. ELECTRICAL SWITCHBOARDS SHALL HAVE A NEMA TYPE-1 RATINGS WITH COPPER
BUSSING. THE CIRCUIT BREAKERS SHALL BE THE BOLT-ON TYPE.
16. GROUND RODS SHALL BE CONE POINTED COPPER, 10' IN LENGTH, WITH A 3/4"
DIAMETER; SECTIONAL RODS ARE PERMITTED.
17. PROVIDE A TRANSFORMER PAD AS REQUIRED BY IDAHO POWER.
18. LOCATE EXISTING UNDERGROUND UTILITIES IN THE THE PROPOSED AREA FOR THE
NEW SECONDARY CONDUITS FOR UNDERGROUND UTILITIES PRIOR TO DIGGING.
19. THIS FACILITY IS IN SEISMIC ZONE 2B, CONTRACTOR SHALL ADHERE TO THE LOCAL
CODES WHEN INSTALLING AND MOUNTING EQUIPMENT AND RACEWAYS.
![Page 7: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/7.jpg)
E1
-1
-K
ET
.D
WG
E1-1
KETCHUM FACILITY
ONE LINE DIAGRAM
BLP 09/10/20
JK 09/10/20
ZPB 11/13/20
NONE
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
N G
1
2
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
4 4 4 4
1. THE PROPOSED ABB EV BUS CHARGER HAVE A POWER FACTOR OF 0.95.
2. CABLE AMPACITY CALCULATIONS ARE BASED ON A 105F MAXIMUM AMBIENT
TEMPERATURE.
3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE
DISCONNECTING MEANS.
NOTES
KEYED NOTES
UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, CT, AND METER. UTILITY TO
PROVIDE PRIMARY POWER CABLES AND ASSOCIATED RACEWAY.
CONTRACTOR TO TERMINATE CUSTOMER SUPPLIED CABLES DIRECTLY TO THE
UTILITY TRANSFORMER TERMINALS.
BOND NEW GROUNDING ELECTRODE TO EXISTING GROUNDING ELECTRODE
SYSTEM PER NEC 250.
PROVIDE SPARE BREAKER FOR FUTURE EV BUS CHARGERS.
PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS
DISCONNECTED PRIOR TO SERVICING.
PROVIDE 208Y/120V PANELBOARD WITH INTERGRAL 15KVA TRANSFORMER &
ASSOCIATED CIRCUIT BREAKERS. TRANSFORMER PERCENT IMPEDANCE
ASSUMED AT 2%. REFER TO PANEL SCHEDULE DRAWING FOR CIRCUIT
BREAKER SIZES.
ONE OF THE GROUND CONDUCTORS FROM DC CHARGER WILL PASS THROUGH
DC CHARGER DISPENSER A AND CONTINUE TO DISPENSER B.
1
2
3
4
5
55 55
DC1-1
DC1-2
DC1-5
DC2-1
DC2-4
DC2-5
DC1-4
6
6
P-2
P-3
P-4
P-1
3
P-0
DC1-3
DC2-2
DC2-3
7
B
B
7
B
7
![Page 8: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/8.jpg)
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E3-1-K
ET
.D
WG
E3-1
KETCHUM FACILITY
ELECTRICAL PANEL SCHEDULES
BLP 09/14/20
JK 09/14/20
ZPB 11/13/20
NONE
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
1. TWO 400A & 150A SPARE BREAKERS ON 480V SWITCHBOARD #1 ARE FOR FUTURE DC
CHARGERS.
NOTES
KEYED NOTES
BREAKER SHALL COME EQUIPPED WITH A 30mA GFCI.1
1
1
1
1
![Page 9: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/9.jpg)
3'-0
" M
IN
1'-6
"
3" TYP
RED PLASTIC ELECTRICAL
WARNING TAPE WITH MAGNETIC
LINING THAT READS "CAUTION -
ELECTRICAL LINE BURIED BELOW"
COMPACTED APPROVED BACKFILL
FINISHED GRADE
SAWCUT AND REPAIR CONCRETE AS
REQUIRED FOR NEW CONDUIT
SHOP FLOOR
FINISHED GRADE
UTILITY XFMR PAD
UTILITY
XFMR
24
"
LB
CONDULET
WATERPROOF SEAL AT
WALL PENETRATION
480V SWITCHBOARD #1
EXTERIOR
WALL
WALL PENETRATION MINIMUM
OF 24" ABOVE TOP OF
TRANSFORMER PAD
4" SCH 40 OR SCH 80 PVC
(TYP. UNDERGROUND)
4" RGC CONDUIT
(TYP. ABOVE
GROUND)
3'-1
0
1
8
"
2'-6"
2 1/2" DIA CONDUIT OPENING
2 1/2" DIA CONDUIT OPENING
1 1/2" DIA CONDUIT OPENING
2'-1
7
8
"
4
1
4
" 2
7
8
"4
1
2
"
C6X10.5
C6X10.5
C6
X1
0.5
C6
X1
0.5
2'-1
7
8
"
2"
1"
5/8" DIA HOLE (BOTTOM FLANGE ONLY)
FOR 1/2" DIA KWIK BOLT TZ-CS MIN 3"
EMBEDMENT TYPICAL (1) EACH CORNER
USE BEVELED WASHER.
BOLT CHARGERS TO
CHANNEL FRAME AS
NECESSARY
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E6-1-K
ET
.D
WG
E6-1
KETCHUM FACILITY
CONDUIT SECTIONS & DETAILS
BLP 09/18/20
JK 09/18/20
ZPB 11/13/20
AS INDICATED
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
TYPICAL DUCT SECTION1
E7-1
SCALE 1" = 1'-0"
WALL PENETRATION DETAIL
TYPICAL DUCT SECTION2
E7-1
NTS
KEYED NOTES
CONDUITS MUST PENETRATE EXTERIOR WALL 24" MINIMUM ABOVE TOP OF UTILITY XFMRPAD AND HAVE A WATERPROOF SEAL BETWEEN LB CONDULETS AND WALL PENETRATION.WATER PROOF SEAL TO BE FOAM APPROVED FOR CABLE INSULATION AND DUCT SEALCOMPOUND.
1
1
CHARGER SUPPORT FRAMES3
E7-1
SCALE 1"=1'-0"
MEMBER CONDUIT OPENINGS4
E7-1
SCALE 1"=1'-0"
TYP 3
SIDES1/8
NOTES:
ALL MATERIAL TO BE PAINTED CARBON STEEL.
CHARGER SUPPORT FRAME IS TO SIT ON THE
CONCRETE SLAB. GROUT UNDERNEATH AS NECESSARY
TO LEVEL THE FRAME.
B
![Page 10: E0-1 · 2020. 12. 7. · a issued for bid 10/13/20 jk blp zpb jm e0-1-bel.dwg b re-issued for bid 11/13/20 jk blp zpb jm ... mcc mdc mdp mfr mfs mh mic min misc mlo mms moa msp msbd](https://reader036.vdocument.in/reader036/viewer/2022090810/611b8a4ef348fe7e1f2815c0/html5/thumbnails/10.jpg)
B
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM
B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM
E7-1-K
ET
.D
WG
E7-1
KETCHUM FACILITY
FIRST FLOOR POWER PLAN
BLP 09/14/20
JK 09/14/20
ZPB 11/13/20
3/32"=1'-0"
NORTH
TRUE
NORTH
PLAN
FEET
3/32" = 1'-0"
201050
THIS DRAWING WAS PREPARED BY POWER
ENGINEERS, INC. FOR A SPECIFIC PROJECT,
TAKING INTO CONSIDERATION THE SPECIFIC
AND UNIQUE REQUIREMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS
WRITTEN PERMISSION FROM BOTH POWER
AND POWER'S CLIENT IS GRANTED.
MOUNTAIN RIDES
JOB NUMBER
DRAWING NUMBER
REVISIONSREV
SCALE:
DATE CKDDSGNDRN REFERENCE DRAWINGSAPPD
DSGN
CKD
DRN
FOR 24x36 DWG ONLY
1 2 3 4 5 6 7 8
REV
E
D
C
B
A
165994
ELECTRIC BUS CHARGING
1. REFER TO ONE-LINE DIAGRAM DRAWING E1-1 FOR CONDUIT & CABLE
REQUIREMENTS.
2. CONTRACTOR TO PROVIDE EQUIPMENT, CONDUITS, & TERMINATE POWER &
COMMUNICATION CABLES. REFER TO ONE LINE DIAGRAM FOR CABLE SIZING.
3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE
DISCONNECTING MEANS.
4. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO DETERMINE
THE BEST CONDUIT ROUTE IN THE FIELD.
NOTES
KEYED NOTES
UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, TRANSFORMER PAD,
PRIMARY CABLES & RACEWAYS.
CONTRACTOR SCOPE INCLUDES TERMINATION TO THE LOAD SIDE OF THE
UTILITY TRANSFORMER.
PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS
DISCONNECTED PRIOR TO SERVICING."
PROVIDE CUSTOM FABRICATED STEEL SUPPORT STAND WITH A 6" C-CHANNEL
BASE FOR ABOVEGROUND CONDUIT ENTRY TO THE BOTTOM OF THE EV
CHARGER.
CONDUITS MUST PENETRATE WALL 24" MINIMUM ABOVE TOP OF THE UTILITY
TRANSFORMER PAD AND HAVE WATER PROOF SEAL AT WALL PENETRATION.
REFER TO SHEET E6-1 FOR DETAIL.
1
2
3
4
UTILITY
XFMR
DC2-4
DC1-1
DC2-2
DC2-3
DC2-5
DC2-1
DC1-2
DC1-3
DC1-4
DC1-5
DC CHARGER #2
DC CHARGER #1
DC CHARGER
DISPENSER 1B
DC CHARGER
DISPENSER 2A
480V SWITCHBOARD #1
DC CHARGER
DISPENSER 1A
DC CHARGER
DISPENSER 2B
4
4
AC PANEL #1
& INTEGRAL
XFMR
3
3
3
3
1 2
5
1
E6-1
P-1
P-2P-0
P-4
P-3
SCALE: 3/32" = 1'-0"
1
FIRST FLOOR POWER PLAN
2
E6-1
5
EXISTING PANEL
EXISTING STARTER
EXISTING PANEL
B