ENERGY SAVER NODE FOR LIGHTING CONTROL SYSTEM. REFER TO DRAWING E8.1FOR MORE INFORMATION SENSOR MODULE FOR LIGHTING CONTROL SYSTEM. REFER TO DRAWING E8.1 FOR MORE INFORMATION ELECTRICAL GENERAL NOTES 1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING REGULATIONS, CODES, ETC. A. LOCAL CODES AND ORDINANCES B. THE EDITION OF THE NATIONAL ELECTRICAL CODE NFPA 70 (NEC) IN EFFECT. 2. PRIOR TO BEGINNING ANY WORK, SECURE NECESSARY PERMITS OR CLEARANCES FROM THE AUTHORITIES HAVING JURISDICTION. PROVIDE ALL LABOR AND MATERIALS FOR A COMPLETE INSTALLATION. WORK SHALL BE EXECUTED BY EXPERIENCED ELECTRICIANS WHO ARE LICENSED IN THE JURISDICTION WHERE THE PROJECT IS LOCATED. 3. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BE MAINTAINED. 4. THE ELECTRICAL PLANS ARE DIAGRAMMATIC ONLY. COORDINATE ELECTRICAL EQUIPMENT LOCATION AND INSTALLATION WITH EQUIPMENT BEING SERVED. PROVIDE ALL POWER AND TELECOMMUNICATION FINAL CONNECTIONS TO THE SYSTEM FURNITURE AS REQUIRED. 5. ALL EQUIPMENT SUCH AS RELAYS, SWITCHES, PANELS, AND OTHER APPURTENANCES SHALL HAVE IDENTIFICATION PLATES OF BLACK LAMINATED PLASTIC WITH 1/2" WHITE LETTERS. ALL JUNCTION BOXES IN CEILING CAN BE MARKED WITH BLACK PERMANENT MARKER ON COVER PLATES AS PANEL DESIGNATION AND CIRCUIT NUMBER FROM WHICH THEY ARE FED. 6. ALL CONDUCTORS SHALL BE IDENTIFIED. ALL WIRING DEVICES SHALL BE USED WITH TYPED LABEL ON THE COVER PLATE IDENTIFYING THE PANEL DESIGNATION AND CIRCUIT NUMBER FROM WHICH THEY ARE FED. 7. ALL EQUIPMENT SHALL BE "UL" LISTED. 8. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE. 9. ALL CONNECTIONS TO DEVICES SHALL BE TAPED WITH SCOTCH 33 ELECTRICAL TAPE. 10. ALL CONDUITS AND JUNCTION BOXES SHALL BE CONCEALED IN FINISHED AREAS. PRIOR TO CONCEALMENT OF NEW CONSTRUCTION, ALL WORK BEHIND FINISHED SURFACES SHALL BE INSPECTED BY THE OWNER'S REPRESENTATIVE. 11. CONTRACTOR SHALL INFORM THE OWNER'S REPRESENTATIVE PRIOR TO BEGINNING CONSTRUCTION AND PRIOR TO COMPLETION OF CONSTRUCTION TO ALLOW SUFFICIENT TIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTION WORK. 12. CONTROL WIRING SHALL BE TAGGED AT EACH END AND TERMINATED WHERE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURES SPECIFICATIONS. 13. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR SHALL BE LIABLE FOR ITS REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE OR IF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE MATERIAL OR EQUIPMENT DOES NOT MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. 14. THE CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST, ANY LABOR, MATERIALS, SERVICES, APPARATUS, AND DRAWINGS IN ADDITION TO CONTRACT DOCUMENTS, IN ORDER TO COMPLY WITH ALL APPLICABLE LAWS, INDICATED AND/OR SPECIFIED. PROVIDE ALL ELECTRICAL EQUIPMENT WITH ALL NECESSARY ASSOCIATED ACCESSORIES AND CONDUIT INFRASTRUCTURE AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM AT NO ADDITIONAL COST TO OWNER. 15. BEFORE SUBMITTING BIDS, THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE ALL ADJOINING EXISTING BUILDINGS, EQUIPMENT, AND SPACE CONDITIONS ON WHICH HIS WORK IS IN ANY WAY DEPENDANT FOR THE BEST WORKMANSHIP AND OPERATION ACCORDING TO THE INTENT OF THE SPECIFICATIONS AND DRAWINGS. HE SHALL REPORT TO THE ARCHITECT/ENGINEER ANY CONDITION WHICH MIGHT PREVENT HIM FROM INSTALLING HIS EQUIPMENT IN THE MANNER SPECIFIED OR AS SHOWN IN CONTRACT DOCUMENTS TEN BUSINESS DAYS PRIOR TO SUBMISSION OF BIDS. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE, NOR FOR ANY ALLEGED MISUNDERSTANDING OF MATERIALS TO BE FURNISHED OR WORK TO BE PERFORMED. THE CONTRACTOR SHALL INCLUDE IN HIS BID PRICE ALL LABOR AND MATERIAL THAT MAY EFFECT HIS WORK. 16. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF ANY DISCOVERED CONFLICTS BETWEEN EXISTING INSTALLATIONS WHICH ARE NOT SCHEDULED FOR DEMOLITION AND THE NEW WORK INDICATED WITHIN THE CONTRACT DOCUMENTS. SUCH NOTIFICATION SHALL BE ACCOMPANIED BY A DRAWING DELINEATING THE PROPOSED SOLUTION PRIOR TO STARTING ANY WORK IN THE AFFECTED AREA. 17. ALL NEW SLAB PENETRATIONS MUST BE X-RAYED OR RADAR PRIOR TO CORE DRILLING. OBTAIN APPROVAL FROM OWNER'S REPRESENTATIVE PRIOR TO ANY CORE DRILLING. 18. ALL MATERIALS AND WORK SHALL BE ACCORDING TO BASE BUILDING SPECIFICATIONS UNLESS OTHERWISE NOTED. 19. ALL CONDUCTORS SHALL BE COPPER. MINIMUM SIZE SHALL BE #12 AWG. CONDUCTOR #10 AWG AND SMALLER SHALL BE SOLID. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED. CONDUCTOR SHALL HAVE THHN/THWN INSULATION OR AS NOTED. 20. NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY. PROVIDE ALL WIRE NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER INDICATED ON PLAN OR NOT. 21. REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATION, ELEVATION, MOUNTING HEIGHTS AND DETAILS OF ALL LIGHT FIXTURES AND DEVICES. REPORT ANY DISCREPANCIES TO THE ARCHITECT IMMEDIATELY. 22. VERIFY DOOR SWINGS BEFORE INSTALLING LIGHT SWITCHES. 23. GANG ALL SWITCHES SHOWN TO BE INSTALLED AT SAME LOCATION UNDER A SINGLE COVER PLATE. PROVIDE BARRIERS SWITCH BOX AS REQUIRED TO SEPARATE 120V CIRCUITS FROM 277V CIRCUITS AND 277V CIRCUITS OF DIFFERENT PHASE. 24. PROVIDE PLASTER RING WITH PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR ALL TELEPHONE, DATA, FAX, MODEM, CATV, CARD READER, ETC. OUTLETS INSTALLED IN HOLLOW PARTITIONS. PROVIDE 3/4" EMPTY CONDUIT AND PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR THESE OUTLETS INSTALLED IN AN INSULATED PARTITION. PROVIDE 1" E.C. WITH 2 STRINGS FOR COMBINATION DATA/TEL OUTLET. 25. MAINTAIN INTEGRITY OF THE FIRE RATED CONSTRUCTION WHERE CONDUITS PASS THROUGH WALLS AND FLOORS. 26. ALL BACK BOXES INSTALLED ON OPPOSITE SIDES OF THE SAME PARTITION SHALL BE STAGGERED. DO NOT MOUNT THE BACK BOXES BACK TO BACK. 27. TYPE MC CABLE MAY BE USED IN LIEU OF EMT FOR BRANCH CIRCUITS, IN DRYWALL PARTITION AND IN CEILING PLENUM WHERE IS ALLOWED BY NEC AND THE BUILDING OWNER. (MC CABLE FOR ISOLATED CIRCUIT SHALL HAVE TWO (2) SEPARATE GROUNDING CONDUCTORS). 28. CONTRACTOR'S SCOPE OF WORK INCLUDES TRACING ALL EXISTING CIRCUITS IN THE CONSTRUCTION AREA BACK TO SOURCE. IF REMOVAL OF EXISTING ELECTRICAL EQUIPMENT AFFECTS ANY EXISTING CIRCUITS, CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS, WIRING, CONDUIT, ETC. REQUIRED TO RECONNECT EXISTING-TO-REMAIN ELECTRICAL EQUIPMENT BACK TO SOURCE. 29. PROVIDE ACCESS PANELS IN ALL INACCESSIBLE JUNCTION BOXES AS REQUIRED BY THE N.E.C. 30. CONTRACTOR SHALL PROVIDE 50% STEP-DIM BALLASTS IN ALL LIGHTING FIXTURES WHERE TWO LEVELS OF SWITCHING ARE INDICATED. 31. ALL EXISTING AND NEW PANELS IMPACTED BY THIS PROJECT SHALL BE PROVIDED WITH NEW UPDATED TYPEWRITTEN PANEL SCHEDULES INDICATING THE FINAL ROOM NUMBER AND THE EQUIPMENT OR DEVICES SERVED BY THE CIRCUIT. CONTRACTOR TO BE BALANCE THE NEW LOADS ON ALL THREE PHASES FOR EACH PANELBOARD WHERE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S SPECIFICATIONS 32. INSTALLATION OF EQUIPMENT, COMPONENTS AND WIRING FOR ELECTRICAL SYSTEMS SHALL BE IN ACCORDANCE WITH REQUIREMENTS OF EQUIPMENT MANUFACTURER. 33. DELIVER PRODUCTS TO PROJECT SITE IDENTIFIED WITH NAMES, MODEL NUMBERS, TYPES, GRADES, COMPLIANCE LABELS, AND OTHER INFORMATION NEEDED FOR DISTINCT IDENTIFICATION; ADEQUATELY PACKAGED AND PROTECTED TO PREVENT DAMAGE DURING SHIPMENT, STORAGE, AND HANDLING. PROTECT STORED EQUIPMENT AND MATERIALS FROM DAMAGE. COMPLY WITH MANUFACTURER'S RIGGING AND MOVING INSTRUCTIONS FOR UNLOADING EQUIPMENT AND MOVING INTO FINAL LOCATION. 34. CONTRACTOR TO COORDINATE ELECTRICAL WORK TO AVOID INTERFERENCE BETWEEN ALL OTHER TRADES. A. DETERMINE INTERFERENCE BEFORE WORK IS FABRICATED OR INSTALLED. THE CONTRACTOR SHALL BE THOROUGHLY FAMILIAR WITH ALL DETAILS OF WORK AND WORKING CONDITIONS AND COORDINATE WORK DURING PRELIMINARY STAGES TO ENSURE ACTUAL ERECTION WILL PROCEED WITHOUT INTERFERENCE. COORDINATION IS OF PARAMOUNT IMPORTANCE AND NO REQUESTS FOR ADDITIONAL PAYMENT WILL BE CONSIDERED WHERE REQUEST IS BASED ON INTERFERENCE. B. WHERE JOB CONDITIONS REQUIRE REASONABLE DEVIATIONS FROM CONTRACT DOCUMENTS, MAKE DEVIATIONS WITHOUT ADDITIONAL COST TO OWNER, AFTER OBTAINING APPROVAL OF ARCHITECT. C. PROVIDE MAXIMUM PRACTICAL SPACE FOR OPERATION, REPAIR, REMOVAL, AND TESTING OF ELECTRICAL EQUIPMENT. APPROVED DEVIATIONS MAY BE MADE TO PROVIDE REQUIRED ACCESSIBILITY. D. KEEP CONDUITS, WIREWAYS AND SIMILAR ITEMS AS CLOSE AS POSSIBLE TO CEILING, WALLS AND COLUMNS IN ORDER TO TAKE UP MINIMUM AMOUNT OF SPACE. E. PROVIDE OFFSETS, FITTINGS AND SIMILAR ITEMS NECESSARY TO ACCOMPLISH REQUIREMENTS OF COORDINATION WITHOUT ADDITIONAL EXPENSE TO OWNER. F. PROVIDE ACCESS TO AND CLEARANCES AROUND EQUIPMENT AS REQUIRED BY THE N.E.C. 35. LIGHTING FIXTURES SHALL BE INDIVIDUALLY SUPPORTED FROM THE STRUCTURAL FRAMING MEMBERS ABOVE. 36. CONTRACTOR SHALL PROVIDE WRITTEN CERTIFICATION THAT ALL PRODUCTS, MATERIALS AND PROCESSES INSTALLED IN THE SPACE CONTAINS NO ASBESTOS OR PCB. 37. TESTING: A. TEST AND ADJUST EQUIPMENT AND SYSTEMS INSTALLED AND DEMONSTRATE PROPER OPERATION TO OWNER'S REPRESENTATIVE. NO EQUIPMENT SHALL BE TESTED OR OPERATED FOR ANY PURPOSE UNTIL IT HAS BEEN FULLY PREPARED FOR OPERATION IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. B. SHOW, BY DEMONSTRATION IN SERVICE, THAT ALL CIRCUITS AND DEVICES ARE IN GOOD OPERATING CONDITION. EACH PIECE OF EQUIPMENT AND COMPONENT OF THE ELECTRICAL SYSTEM SHALL FUNCTION NOT LESS THAN FIVE TIMES IN COURSE OF THE ACCEPTANCE TESTS. 38. PROVIDE ALL NEW PANELS AND TRANSFORMERS WITH COPPER BUSBARS AND WINDINGS UNLESS BASE BUILDING STANDARDS DIFFER. 39. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL, PLUMBING AND OTHER TRADES TO PROVIDE ALL EQUIPMENT ASSOCIATED WITH THEIR RESPECTIVE TRADES WITH NECESSARY WIRING AND CONDUIT INFRASTRUCTURE FOR ALL SENSORS, AND CONTROL SYSTEMS AS REQUIRED. I. GENERAL: A. BEFORE SUBMITTING BID. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE SITE TO VERIFY/EXAMINE THE EXACT EXTENT OF EXISTING CONDITIONS. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE, NOR FOR ANY ALLEGED MISUNDERSTANDING OF WORK TO BE PERFORMED. THE CONTRACTOR SHALL INCLUDE IN HIS BID PRICE ALL LABOR AND MATERIAL THAT MAY EFFECT HIS WORK. B. THE GENERAL EXTENT OF EXISTING ELECTRICAL WORK TO BE DISMANTLED AND REMOVED OR RELOCATED IS INDICATED ON THE DRAWINGS. C. ALL COMPONENTS ASSOCIATED WITH SYSTEMS AND EQUIPMENT TO BE REMOVED OR RELOCATED MAY NOT BE SPECIFICALLY INDICATED. REMOVE ALL ASSOCIATED ELECTRICAL COMPONENTS, HANGERS, WIRING, CABLING, CONDUIT, BOXES, DEVICES AND ALL OTHER ITEMS RELATED TO EQUIPMENT AND MATERIALS WHICH ARE INDICATED TO BE REMOVED OR RELOCATED. REMOVE ALL WIRING/CONDUIT BACK TO THE SOURCE IN EXISTING CIRCUITS WHICH ARE BEING DEMOLISHED. UNLESS SPECIFICALLY INDICATED, NO EQUIPMENT, MATERIALS OR ASSOCIATED COMPONENTS SHALL BE ABANDONED IN PLACE. D. ABANDONED ALL CONDUITS WHICH ARE CONCEALED IN CONCRETE WALLS OR SLABS AND REMOVE ALL WIRING/CABLES FROM ABANDONED CONDUITS. II. DISPOSAL OF DEMOLITION: A. CONTRACTOR SHALL CLEAN THE PROJECT SITE AT THE END OF EACH WORKING DAY. CONTRACTOR SHALL NOTIFY BUILDING OWNER PRIOR TO DISPOSAL OF ALL DEMOLISHED MATERIALS TO ALLOW THE OWNER TO SALVAGE ANY USABLE MATERIALS. AFTER INSPECTING FROM THE OWNER'S REPRESENTATIVE ALL UNUSED MATERIALS SHALL BE REMOVED FROM THE JOB SITE WITH DISPOSAL IN ACCORDANCE WITH APPLICABLE SPECIFICATIONS AND REGULATIONS. III. PROTECTION: A. PROTECT FROM DAMAGE ALL EXISTING WORK TO REMAIN. ANY EXISTING TO REMAIN OR EXISTING TO BE RELOCATED MATERIALS AND EQUIPMENT DAMAGED DURING THE COURSE OF THE WORK SHALL BE REPLACED WITH MATERIALS AND EQUIPMENT CONFORMING TO THESE SPECIFICATIONS AT NO ADDITIONAL COST TO THE OWNER. CARE MUST TAKEN IN REMOVING ALL EXISTING MATERIALS. IV. TERMINATION AND PATCHING: A. DISCONNECT EXISTING TO BE REMOVED OR EXISTING TO BE RELOCATED CONDUIT, WIRING, CABLING, AND EQUIPMENT FROM EXISTING TO REMAIN POINT INDICATED. IF NOT INDICATED ON THE PLANS, VERIFY WITH THE DESIGN ENGINEERS OR BUILDING OWNER'S REPRESENTATIVE PRIOR TO DISCONNECTION. B. WHERE EXISTING FLOORS, WALLS AND ROOFS MUST BE CUT OR ARE DAMAGED DURING REMOVAL OR RELOCATION OF ELECTRICAL WORK, PATCH THE CUT OR DAMAGED AREAS TO MATCH ADJACENT CONSTRUCTION. C. THE CONTINUITY OF ALL EXISTING CONDUITS AND FEEDERS SERVICING AREAS TO REMAIN SHALL BE MAINTAINED. MODIFY THE EXISTING CIRCUITS IF REQUIRED IN ORDER TO MAINTAIN THE EXISTING CIRCUITRY. ELECTRICAL GENERAL DEMOLITION NOTES WIRE SIZE (AWG TYP.) LENGTH (FEET) VOLTAGE (V) 120 0-66 0-102 120 20 #12 20 #10 AMPACITY (A) 120V BRANCH CIRCUIT WIRING CONDUCTOR SIZE DEPENDING ON BRANCH CIRCUIT RUN LENGTH FROM PANELBOARD TO THE LAST DEVICE ON THE BRANCH CIRCUIT, THE CONTRACTOR SHALL INCREASE THE BRANCH CIRCUIT WIRE SIZE AS PER THE TABLE BELOW. MAXIMUM #10 WIRE SHALL BE USED FOR GENERAL RECEPTACLE CIRCUIT WIRING. REFER TO THE LIGHTING FIXTURE SCHEDULE ON DRAWINGS E6.1 FOR LIGHTING FIXTURE SPECIFICATIONS. EXIT SIGN LIGHTING FIXTURES ON EMERGENCY LIGHTING CIRCUIT TYPICAL INTERIOR LIGHTING FIXTURES TYPICAL INTERIOR LIGHTING FIXTURES ON EMERGENCY LIGHTING CIRCUIT A AMPERE AFF ABOVE FINISHED FLOOR AWG AMERICAN WIRE GAUGE BRK BREAKER C CONDUIT CB CIRCUIT BREAKER CP CONDENSATE PUMP D EXISTING TO BE DEMOLISHED DISCSW DISCONNECT SWITCH DP DISTRIBUTION PANEL DWG DRAWING E, EX EXISTING TO REMAIN EG EQUIPMENT GROUND EM DEVICE ON EMERGENCY CIRCUIT EMT ELECTRICAL METALLIC TUBING EW EMERGENCY WHITE (NIGHT) LIGHT EWH ELECTRIC WATER HEATER FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FATC FIRE ALARM TERMINAL CABINET F.L.A. FULL LOAD AMPS G, GND GROUND GFI GROUND FAULT INTERRUPTER GND GROUND HP HORSE POWER IG INTERRUPTER ISOLATED GROUND KVA KILOVOLT-AMPS KW KILOWATT MCB MAIN CIRCUIT BREAKER MD MOTORIZED DAMPER MLO MAIN LUGS ONLY MDP MAIN DISTRIBUTION PANEL N NEW NEC NATIONAL ELECTRICAL CODE NF NON FUSED N/L NIGHT LIGHT FIXTURE ON A TIMER NTS NOT TO SCALE P POLE 3+ PHASE PNL PANEL PSRH PROJECT STANDARD RECEPTACLE HEIGHT PSSH PROJECT STANDARD SWITCH HEIGHT R RELOCATED AT NEW LOCATION RR REMOVE AND RELOCATE S.N. SOLID NEUTRAL SM MOTOR THERMAL SWITCH CONTROL SWBD SWITCHBOARD TEL. TELEPHONE T, XFMR TRANSFORMER TYP TYPICAL U.H. UNIT HEATER U.O.N. UNLESS OTHERWISE NOTED V VOLTS W WATTS WP WEATHERPROOF (STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT) (ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS) ABBREVIATIONS ELECTRICAL SYMBOL LIST SINGLE POLE TOGGLE SWITCH 3 - WAY LIGHTING SWITCH WIRELESS LOW VOLTAGE KEY OPERATED SWITCH WIRELESS LOW VOLTAGE TWO BUTTON DIMMER SWITCH WITH RAISE LOWER WALL/CEILING MOUNTED OCCUPANCY SENSOR SWITCH (DUAL TECHNOLOGY SENSOR). PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNER 2 : INDICATES A BI-LEVEL SWITCH WALL/CELING/FLOOR MOUNTED JUNCTION BOX. FIELD COORDINATE EXACT LOCATION AND MOUNTING HEIGHT. FUSIBLE DISCONNECT SWITCH. TOP NUMBER INDICATES FRAME RATING. BOTTOM NUMBER INDICATES FUSE RATING. DRY TYPE TRANSFORMER, SEE FLOOR PLANS AND POWER RISER FOR SIZE 120/208V ELECTRICAL PANEL CIRCUIT HOMERUN TO DESIGNATED PANEL. NUMBER OF ARROWS INDICATE NUMBER OF CIRCUITS AND TEXT DENOTES PANELBOARD. TICK MARKS INDICATE NUMBER OF AWG WIRES CONTAINED IN CONDUIT WHEN MORE THAN TWO. TICK MARKS WITH: ( ) DENOTES SEPARATE EQUIPMENT GROUND WIRE. HOMERUN WIRING WITHOUT TICK MARKS SHALL INCLUDE 2#12+1#12G-3/4"C. EACH CIRCUIT HOMERUN SHALL BE PROVIDED WITH DEDICATED NEUTRAL UNDERGROUND OR PLATFORM WIRING/CONDUIT KEYED DRAWING NOTE SPLIT CIRCUIT 480/277V ELECTRICAL PANEL CONDUIT UP CONDUIT DOWN CONTINUOUS CIRCUIT AA 60 45 2 2 MS J J J T 3 LK L2 MS WALL/CEILING MOUNTED VACANCY SENSOR SWITCH. PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNER D : INDICATES A DIMMER SWITCH D VS VS WALL/CEILING MOUNTED WIRELESS LOW VOLTAGE VACANCY SENSOR SWITCH. PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNER D : INDICATES A DIMMER SWITCH D LV LV 2 LM LM WALL/CEILING MOUNTED WIRELESS LOW VOLTAGE OCCUPANCY SENSOR SWITCH. PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNER 2 : INDICATES A BI-LEVEL SWITCH WIRELESS LOW VOLTAGE THREE BUTTON SWITCH WITH RAISE LOWER L3 WALL-MOUNTED DUPLEX OR QUAD RECEPTACLE. 20A/125V/2P/3W (GROUNDED) NEMA 5-20R. MOUNTED @ 18" AFF, UON. E0.1 CDC VL VL SHEET LIST TABLE Drawing Sheet Title Sheet E0.1 ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS ED1.1 LIGHTING DEMOLITION PLAN ED1.2 LIGHTING DEMOLITION PLAN EL1.1 LIGHTING NEW WORK PLAN EL1.2 LIGHTING NEW WORK PLAN E5.1 POWER RISER DIAGRAM AND PANEL SCHEDULES E6.1 LIGHTING FIXTURE SCHEDULE E6.2 LIGHTING COMPLIANCE CERTIFICATE E7.1 ELECTRICAL DETAILS E8.1 LIGHTING CONTROL WIRING SCHEMATIC THE MARYLAND- NATIONAL CAPITAL PARK & PLANNING COMMISSION Maintenance and Development Prince Georges County 4200 Ritchie-Marlboro Road Upper Marlboro, MD 20772 301-780-2300 DRAWN: REVIEW: SHEET TITLE CONSULTANT DESIGN: SHEET NO. SCALE: BID NO. STAMP 01/30/2015 DATE: PHASE: 9652 Muirkirk Road Laurel, Maryland DATE: PHASE: Montpelier Arts Center Plotted By: JAMAAR BRANDON Plot Date: 6/15/2015 12:37:32 PM Saved By: JAMAAR.BRANDON File: O:\2014\SAG14023.01\SAG14023.01E\14023.01_E0.1.dwg Save Date: 06/15/2015 09:57 AM AS NOTED PROGRESS SET 06/15/2015 100% CD SUBMISSION ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

Upload: others

Post on 26-Dec-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

ENERGY SAVER NODE FOR LIGHTING CONTROL SYSTEM. REFER TO DRAWING E8.1FORMORE INFORMATION

SENSOR MODULE FOR LIGHTING CONTROL SYSTEM. REFER TO DRAWING E8.1 FOR MOREINFORMATION

ELECTRICAL GENERAL NOTES

1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWINGREGULATIONS, CODES, ETC.

A. LOCAL CODES AND ORDINANCES

B. THE EDITION OF THE NATIONAL ELECTRICAL CODE NFPA 70 (NEC) IN EFFECT.

2. PRIOR TO BEGINNING ANY WORK, SECURE NECESSARY PERMITS OR CLEARANCES FROMTHE AUTHORITIES HAVING JURISDICTION. PROVIDE ALL LABOR AND MATERIALS FOR ACOMPLETE INSTALLATION. WORK SHALL BE EXECUTED BY EXPERIENCED ELECTRICIANSWHO ARE LICENSED IN THE JURISDICTION WHERE THE PROJECT IS LOCATED.

3. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BE MAINTAINED.

4. THE ELECTRICAL PLANS ARE DIAGRAMMATIC ONLY. COORDINATE ELECTRICALEQUIPMENT LOCATION AND INSTALLATION WITH EQUIPMENT BEING SERVED. PROVIDEALL POWER AND TELECOMMUNICATION FINAL CONNECTIONS TO THE SYSTEMFURNITURE AS REQUIRED.

5. ALL EQUIPMENT SUCH AS RELAYS, SWITCHES, PANELS, AND OTHER APPURTENANCESSHALL HAVE IDENTIFICATION PLATES OF BLACK LAMINATED PLASTIC WITH 1/2" WHITELETTERS. ALL JUNCTION BOXES IN CEILING CAN BE MARKED WITH BLACK PERMANENTMARKER ON COVER PLATES AS PANEL DESIGNATION AND CIRCUIT NUMBER FROM WHICHTHEY ARE FED.

6. ALL CONDUCTORS SHALL BE IDENTIFIED. ALL WIRING DEVICES SHALL BE USED WITHTYPED LABEL ON THE COVER PLATE IDENTIFYING THE PANEL DESIGNATION AND CIRCUITNUMBER FROM WHICH THEY ARE FED.

7. ALL EQUIPMENT SHALL BE "UL" LISTED.

8. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONALELECTRICAL CODE.

9. ALL CONNECTIONS TO DEVICES SHALL BE TAPED WITH SCOTCH 33 ELECTRICAL TAPE.

10. ALL CONDUITS AND JUNCTION BOXES SHALL BE CONCEALED IN FINISHED AREAS. PRIORTO CONCEALMENT OF NEW CONSTRUCTION, ALL WORK BEHIND FINISHED SURFACESSHALL BE INSPECTED BY THE OWNER'S REPRESENTATIVE.

11. CONTRACTOR SHALL INFORM THE OWNER'S REPRESENTATIVE PRIOR TO BEGINNINGCONSTRUCTION AND PRIOR TO COMPLETION OF CONSTRUCTION TO ALLOW SUFFICIENTTIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTIONWORK.

12. CONTROL WIRING SHALL BE TAGGED AT EACH END AND TERMINATED WHERE WORK HASBEEN PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURES SPECIFICATIONS.

13. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTORSHALL BE LIABLE FOR ITS REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE ORIF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE MATERIAL OR EQUIPMENTDOES NOT MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS.

14. THE CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST, ANY LABOR,MATERIALS, SERVICES, APPARATUS, AND DRAWINGS IN ADDITION TO CONTRACTDOCUMENTS, IN ORDER TO COMPLY WITH ALL APPLICABLE LAWS, INDICATED AND/ORSPECIFIED. PROVIDE ALL ELECTRICAL EQUIPMENT WITH ALL NECESSARY ASSOCIATEDACCESSORIES AND CONDUIT INFRASTRUCTURE AS REQUIRED TO ENSURE A COMPLETEAND OPERATIONAL SYSTEM AT NO ADDITIONAL COST TO OWNER.

15. BEFORE SUBMITTING BIDS, THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE ALLADJOINING EXISTING BUILDINGS, EQUIPMENT, AND SPACE CONDITIONS ON WHICH HISWORK IS IN ANY WAY DEPENDANT FOR THE BEST WORKMANSHIP AND OPERATIONACCORDING TO THE INTENT OF THE SPECIFICATIONS AND DRAWINGS. HE SHALL REPORTTO THE ARCHITECT/ENGINEER ANY CONDITION WHICH MIGHT PREVENT HIM FROMINSTALLING HIS EQUIPMENT IN THE MANNER SPECIFIED OR AS SHOWN IN CONTRACTDOCUMENTS TEN BUSINESS DAYS PRIOR TO SUBMISSION OF BIDS. NO CONSIDERATIONOR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE, NOR FOR ANYALLEGED MISUNDERSTANDING OF MATERIALS TO BE FURNISHED OR WORK TO BEPERFORMED. THE CONTRACTOR SHALL INCLUDE IN HIS BID PRICE ALL LABOR ANDMATERIAL THAT MAY EFFECT HIS WORK.

16. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF ANYDISCOVERED CONFLICTS BETWEEN EXISTING INSTALLATIONS WHICH ARE NOTSCHEDULED FOR DEMOLITION AND THE NEW WORK INDICATED WITHIN THE CONTRACTDOCUMENTS. SUCH NOTIFICATION SHALL BE ACCOMPANIED BY A DRAWING DELINEATINGTHE PROPOSED SOLUTION PRIOR TO STARTING ANY WORK IN THE AFFECTED AREA.

17. ALL NEW SLAB PENETRATIONS MUST BE X-RAYED OR RADAR PRIOR TO CORE DRILLING.OBTAIN APPROVAL FROM OWNER'S REPRESENTATIVE PRIOR TO ANY CORE DRILLING.

18. ALL MATERIALS AND WORK SHALL BE ACCORDING TO BASE BUILDING SPECIFICATIONSUNLESS OTHERWISE NOTED.

19. ALL CONDUCTORS SHALL BE COPPER. MINIMUM SIZE SHALL BE #12 AWG. CONDUCTOR#10 AWG AND SMALLER SHALL BE SOLID. CONDUCTORS #8 AWG AND LARGER SHALL BESTRANDED. CONDUCTOR SHALL HAVE THHN/THWN INSULATION OR AS NOTED.

20. NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERECLARIFICATION IS NECESSARY. PROVIDE ALL WIRE NECESSARY FOR THE PROPERFUNCTION OF THE SYSTEM WHETHER INDICATED ON PLAN OR NOT.

21. REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATION, ELEVATION,MOUNTING HEIGHTS AND DETAILS OF ALL LIGHT FIXTURES AND DEVICES. REPORT ANYDISCREPANCIES TO THE ARCHITECT IMMEDIATELY.

22. VERIFY DOOR SWINGS BEFORE INSTALLING LIGHT SWITCHES.

23. GANG ALL SWITCHES SHOWN TO BE INSTALLED AT SAME LOCATION UNDER A SINGLECOVER PLATE. PROVIDE BARRIERS SWITCH BOX AS REQUIRED TO SEPARATE 120VCIRCUITS FROM 277V CIRCUITS AND 277V CIRCUITS OF DIFFERENT PHASE.

24. PROVIDE PLASTER RING WITH PULL STRING TO SPACE ABOVE SUSPENDED CEILING FORALL TELEPHONE, DATA, FAX, MODEM, CATV, CARD READER, ETC. OUTLETS INSTALLED INHOLLOW PARTITIONS. PROVIDE 3/4" EMPTY CONDUIT AND PULL STRING TO SPACE ABOVESUSPENDED CEILING FOR THESE OUTLETS INSTALLED IN AN INSULATED PARTITION.PROVIDE 1" E.C. WITH 2 STRINGS FOR COMBINATION DATA/TEL OUTLET.

25. MAINTAIN INTEGRITY OF THE FIRE RATED CONSTRUCTION WHERE CONDUITS PASSTHROUGH WALLS AND FLOORS.

26. ALL BACK BOXES INSTALLED ON OPPOSITE SIDES OF THE SAME PARTITION SHALL BESTAGGERED. DO NOT MOUNT THE BACK BOXES BACK TO BACK.

27. TYPE MC CABLE MAY BE USED IN LIEU OF EMT FOR BRANCH CIRCUITS, IN DRYWALLPARTITION AND IN CEILING PLENUM WHERE IS ALLOWED BY NEC AND THE BUILDINGOWNER. (MC CABLE FOR ISOLATED CIRCUIT SHALL HAVE TWO (2) SEPARATE GROUNDINGCONDUCTORS).

28. CONTRACTOR'S SCOPE OF WORK INCLUDES TRACING ALL EXISTING CIRCUITS IN THECONSTRUCTION AREA BACK TO SOURCE. IF REMOVAL OF EXISTING ELECTRICALEQUIPMENT AFFECTS ANY EXISTING CIRCUITS, CONTRACTOR SHALL PROVIDE CIRCUITBREAKERS, WIRING, CONDUIT, ETC. REQUIRED TO RECONNECT EXISTING-TO-REMAIN

ELECTRICAL EQUIPMENT BACK TO SOURCE.

29. PROVIDE ACCESS PANELS IN ALL INACCESSIBLE JUNCTION BOXES AS REQUIRED BY THEN.E.C.

30. CONTRACTOR SHALL PROVIDE 50% STEP-DIM BALLASTS IN ALL LIGHTING FIXTURESWHERE TWO LEVELS OF SWITCHING ARE INDICATED.

31. ALL EXISTING AND NEW PANELS IMPACTED BY THIS PROJECT SHALL BE PROVIDED WITHNEW UPDATED TYPEWRITTEN PANEL SCHEDULES INDICATING THE FINAL ROOM NUMBERAND THE EQUIPMENT OR DEVICES SERVED BY THE CIRCUIT. CONTRACTOR TO BEBALANCE THE NEW LOADS ON ALL THREE PHASES FOR EACH PANELBOARD WHEREWORK HAS BEEN PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'SSPECIFICATIONS

32. INSTALLATION OF EQUIPMENT, COMPONENTS AND WIRING FOR ELECTRICAL SYSTEMSSHALL BE IN ACCORDANCE WITH REQUIREMENTS OF EQUIPMENT MANUFACTURER.

33. DELIVER PRODUCTS TO PROJECT SITE IDENTIFIED WITH NAMES, MODEL NUMBERS,TYPES, GRADES, COMPLIANCE LABELS, AND OTHER INFORMATION NEEDED FOR DISTINCTIDENTIFICATION; ADEQUATELY PACKAGED AND PROTECTED TO PREVENT DAMAGEDURING SHIPMENT, STORAGE, AND HANDLING. PROTECT STORED EQUIPMENT ANDMATERIALS FROM DAMAGE. COMPLY WITH MANUFACTURER'S RIGGING AND MOVINGINSTRUCTIONS FOR UNLOADING EQUIPMENT AND MOVING INTO FINAL LOCATION.

34. CONTRACTOR TO COORDINATE ELECTRICAL WORK TO AVOID INTERFERENCE BETWEENALL OTHER TRADES.

A. DETERMINE INTERFERENCE BEFORE WORK IS FABRICATED OR INSTALLED. THECONTRACTOR SHALL BE THOROUGHLY FAMILIAR WITH ALL DETAILS OF WORK ANDWORKING CONDITIONS AND COORDINATE WORK DURING PRELIMINARY STAGES TOENSURE ACTUAL ERECTION WILL PROCEED WITHOUT INTERFERENCE. COORDINATIONIS OF PARAMOUNT IMPORTANCE AND NO REQUESTS FOR ADDITIONAL PAYMENT WILLBE CONSIDERED WHERE REQUEST IS BASED ON INTERFERENCE.

B. WHERE JOB CONDITIONS REQUIRE REASONABLE DEVIATIONS FROM CONTRACTDOCUMENTS, MAKE DEVIATIONS WITHOUT ADDITIONAL COST TO OWNER, AFTEROBTAINING APPROVAL OF ARCHITECT.

C. PROVIDE MAXIMUM PRACTICAL SPACE FOR OPERATION, REPAIR, REMOVAL, ANDTESTING OF ELECTRICAL EQUIPMENT. APPROVED DEVIATIONS MAY BE MADE TOPROVIDE REQUIRED ACCESSIBILITY.

D. KEEP CONDUITS, WIREWAYS AND SIMILAR ITEMS AS CLOSE AS POSSIBLE TO CEILING,WALLS AND COLUMNS IN ORDER TO TAKE UP MINIMUM AMOUNT OF SPACE.

E. PROVIDE OFFSETS, FITTINGS AND SIMILAR ITEMS NECESSARY TO ACCOMPLISHREQUIREMENTS OF COORDINATION WITHOUT ADDITIONAL EXPENSE TO OWNER.

F. PROVIDE ACCESS TO AND CLEARANCES AROUND EQUIPMENT AS REQUIRED BY THEN.E.C.

35. LIGHTING FIXTURES SHALL BE INDIVIDUALLY SUPPORTED FROM THE STRUCTURALFRAMING MEMBERS ABOVE.

36. CONTRACTOR SHALL PROVIDE WRITTEN CERTIFICATION THAT ALL PRODUCTS, MATERIALSAND PROCESSES INSTALLED IN THE SPACE CONTAINS NO ASBESTOS OR PCB.

37. TESTING:

A. TEST AND ADJUST EQUIPMENT AND SYSTEMS INSTALLED AND DEMONSTRATE PROPEROPERATION TO OWNER'S REPRESENTATIVE. NO EQUIPMENT SHALL BE TESTED OROPERATED FOR ANY PURPOSE UNTIL IT HAS BEEN FULLY PREPARED FOR OPERATIONIN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

B. SHOW, BY DEMONSTRATION IN SERVICE, THAT ALL CIRCUITS AND DEVICES ARE INGOOD OPERATING CONDITION. EACH PIECE OF EQUIPMENT AND COMPONENT OF THEELECTRICAL SYSTEM SHALL FUNCTION NOT LESS THAN FIVE TIMES IN COURSE OF THEACCEPTANCE TESTS.

38. PROVIDE ALL NEW PANELS AND TRANSFORMERS WITH COPPER BUSBARS AND WINDINGSUNLESS BASE BUILDING STANDARDS DIFFER.

39. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL, PLUMBING AND OTHERTRADES TO PROVIDE ALL EQUIPMENT ASSOCIATED WITH THEIR RESPECTIVE TRADES WITHNECESSARY WIRING AND CONDUIT INFRASTRUCTURE FOR ALL SENSORS, AND CONTROLSYSTEMS AS REQUIRED.

I. GENERAL: A. BEFORE SUBMITTING BID. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

VISITING THE SITE TO VERIFY/EXAMINE THE EXACT EXTENT OF EXISTING CONDITIONS. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE, NOR FOR ANY ALLEGED MISUNDERSTANDING OF WORK TO BE PERFORMED. THE CONTRACTOR SHALL INCLUDE IN HIS BID PRICE ALL LABOR AND MATERIAL THAT MAY EFFECT HIS WORK.

B. THE GENERAL EXTENT OF EXISTING ELECTRICAL WORK TO BE DISMANTLED AND REMOVED OR RELOCATED IS INDICATED ON THE DRAWINGS.

C. ALL COMPONENTS ASSOCIATED WITH SYSTEMS AND EQUIPMENT TO BE REMOVED OR RELOCATED MAY NOT BE SPECIFICALLY INDICATED. REMOVE ALL ASSOCIATED ELECTRICAL COMPONENTS, HANGERS, WIRING, CABLING, CONDUIT, BOXES, DEVICES AND ALL OTHER ITEMS RELATED TO EQUIPMENT AND MATERIALS WHICH ARE INDICATED TO BE REMOVED ORRELOCATED. REMOVE ALL WIRING/CONDUIT BACK TO THE SOURCE IN EXISTING CIRCUITS WHICH ARE BEING DEMOLISHED. UNLESS SPECIFICALLY INDICATED, NO EQUIPMENT, MATERIALS OR ASSOCIATED COMPONENTS SHALL BE ABANDONED IN PLACE.

D. ABANDONED ALL CONDUITS WHICH ARE CONCEALED IN CONCRETE WALLS OR SLABS AND REMOVE ALL WIRING/CABLES FROM ABANDONED CONDUITS.

II. DISPOSAL OF DEMOLITION: A. CONTRACTOR SHALL CLEAN THE PROJECT SITE AT THE END OF EACH WORKING DAY.

CONTRACTOR SHALL NOTIFY BUILDING OWNER PRIOR TO DISPOSAL OF ALL DEMOLISHED MATERIALS TO ALLOW THE OWNER TO SALVAGE ANY USABLE MATERIALS. AFTER INSPECTING

FROM THE OWNER'S REPRESENTATIVE ALL UNUSED MATERIALS SHALL BE REMOVED FROM THE JOB SITE WITH DISPOSAL IN ACCORDANCE WITH APPLICABLE SPECIFICATIONS AND REGULATIONS.

III. PROTECTION: A. PROTECT FROM DAMAGE ALL EXISTING WORK TO REMAIN. ANY EXISTING TO REMAIN OR

EXISTING TO BE RELOCATED MATERIALS AND EQUIPMENT DAMAGED DURING THE COURSE OF THE WORK SHALL BE REPLACED WITH MATERIALS AND EQUIPMENT CONFORMING TO THESE SPECIFICATIONS AT NO ADDITIONAL COST TO THE OWNER. CARE MUST TAKEN IN REMOVING ALL EXISTING MATERIALS.

IV. TERMINATION AND PATCHING: A. DISCONNECT EXISTING TO BE REMOVED OR EXISTING TO BE RELOCATED CONDUIT, WIRING,

CABLING, AND EQUIPMENT FROM EXISTING TO REMAIN POINT INDICATED. IF NOT INDICATED ON THE PLANS, VERIFY WITH THE DESIGN ENGINEERS OR BUILDING OWNER'S REPRESENTATIVE PRIOR TO DISCONNECTION.

B. WHERE EXISTING FLOORS, WALLS AND ROOFS MUST BE CUT OR ARE DAMAGED DURING REMOVAL OR RELOCATION OF ELECTRICAL WORK, PATCH THE CUT OR DAMAGED AREAS TOMATCH ADJACENT CONSTRUCTION.

C. THE CONTINUITY OF ALL EXISTING CONDUITS AND FEEDERS SERVICING AREAS TO REMAIN SHALL BE MAINTAINED. MODIFY THE EXISTING CIRCUITS IF REQUIRED IN ORDER TO MAINTAINTHE EXISTING CIRCUITRY.

ELECTRICAL GENERAL DEMOLITION NOTES

WIRE SIZE(AWG TYP.)LENGTH (FEET) VOLTAGE (V)

1200-660-102 120

20 #1220 #10

AMPACITY (A)

120V BRANCH CIRCUIT WIRING CONDUCTOR SIZE

DEPENDING ON BRANCH CIRCUIT RUN LENGTH FROM PANELBOARD TO THE LASTDEVICE ON THE BRANCH CIRCUIT, THE CONTRACTOR SHALL INCREASE THE BRANCHCIRCUIT WIRE SIZE AS PER THE TABLE BELOW.

MAXIMUM #10 WIRE SHALL BE USED FOR GENERAL RECEPTACLE CIRCUIT WIRING.

REFER TO THE LIGHTING FIXTURE SCHEDULE ON DRAWINGS E6.1 FOR LIGHTING FIXTURE SPECIFICATIONS.

EXIT SIGN LIGHTING FIXTURES ON EMERGENCY LIGHTING CIRCUIT

TYPICAL INTERIOR LIGHTING FIXTURES

TYPICAL INTERIOR LIGHTING FIXTURES ON EMERGENCY LIGHTING CIRCUIT

A AMPEREAFF ABOVE FINISHED FLOORAWG AMERICAN WIRE GAUGE

BRK BREAKER

C CONDUITCB CIRCUIT BREAKERCP CONDENSATE PUMP

D EXISTING TO BE DEMOLISHEDDISCSW DISCONNECT SWITCHDP DISTRIBUTION PANELDWG DRAWING

E, EX EXISTING TO REMAINEG EQUIPMENT GROUNDEM DEVICE ON EMERGENCY CIRCUITEMT ELECTRICAL METALLIC TUBINGEW EMERGENCY WHITE (NIGHT) LIGHTEWH ELECTRIC WATER HEATER

FAAP FIRE ALARM ANNUNCIATOR PANELFACP FIRE ALARM CONTROL PANELFATC FIRE ALARM TERMINAL CABINETF.L.A. FULL LOAD AMPS

G, GND GROUNDGFI GROUND FAULT INTERRUPTERGND GROUND

HP HORSE POWER

IG INTERRUPTER ISOLATED GROUND

KVA KILOVOLT-AMPSKW KILOWATT

MCB MAIN CIRCUIT BREAKERMD MOTORIZED DAMPERMLO MAIN LUGS ONLYMDP MAIN DISTRIBUTION PANEL

N NEWNEC NATIONAL ELECTRICAL CODENF NON FUSEDN/L NIGHT LIGHT FIXTURE ON A TIMERNTS NOT TO SCALE

P POLEPH, Ø PHASEPNL PANELPSRH PROJECT STANDARD RECEPTACLE HEIGHTPSSH PROJECT STANDARD SWITCH HEIGHT

R RELOCATED AT NEW LOCATIONRR REMOVE AND RELOCATE

S.N. SOLID NEUTRALSM MOTOR THERMAL SWITCH CONTROLSWBD SWITCHBOARD

TEL. TELEPHONET, XFMR TRANSFORMERTYP TYPICAL

U.H. UNIT HEATERU.O.N. UNLESS OTHERWISE NOTED

V VOLTS

W WATTSWP WEATHERPROOF

(STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT) (ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS)ABBREVIATIONSELECTRICAL SYMBOL LIST

SINGLE POLE TOGGLE SWITCH

3 - WAY LIGHTING SWITCH

WIRELESS LOW VOLTAGE KEY OPERATED SWITCH

WIRELESS LOW VOLTAGE TWO BUTTON DIMMER SWITCH WITH RAISE LOWER

WALL/CEILING MOUNTED OCCUPANCY SENSOR SWITCH (DUAL TECHNOLOGY SENSOR).PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNER2 : INDICATES A BI-LEVEL SWITCH

WALL/CELING/FLOOR MOUNTED JUNCTION BOX. FIELD COORDINATE EXACT LOCATIONAND MOUNTING HEIGHT.

FUSIBLE DISCONNECT SWITCH. TOP NUMBER INDICATES FRAME RATING. BOTTOM NUMBERINDICATES FUSE RATING.

DRY TYPE TRANSFORMER, SEE FLOOR PLANS AND POWER RISER FOR SIZE

120/208V ELECTRICAL PANEL

CIRCUIT HOMERUN TO DESIGNATED PANEL. NUMBER OF ARROWS INDICATE NUMBEROF CIRCUITS AND TEXT DENOTES PANELBOARD. TICK MARKS INDICATE NUMBER OF AWGWIRES CONTAINED IN CONDUIT WHEN MORE THAN TWO. TICK MARKS WITH: ( ) DENOTES SEPARATE EQUIPMENT GROUND WIRE.HOMERUN WIRING WITHOUT TICK MARKS SHALL INCLUDE 2#12+1#12G-3/4"C. EACH CIRCUITHOMERUN SHALL BE PROVIDED WITH DEDICATED NEUTRAL

UNDERGROUND OR PLATFORM WIRING/CONDUIT

KEYED DRAWING NOTE

SPLIT CIRCUIT

480/277V ELECTRICAL PANEL

CONDUIT UP

CONDUIT DOWN

CONTINUOUS CIRCUITAA

6045

2

2

MS

J

J

J

T

3

LK

L2

MS

WALL/CEILING MOUNTED VACANCY SENSOR SWITCH.PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNERD : INDICATES A DIMMER SWITCH

D

VS VS

WALL/CEILING MOUNTED WIRELESS LOW VOLTAGE VACANCY SENSOR SWITCH.PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNERD : INDICATES A DIMMER SWITCH

D

LV LV

2

LM LM

WALL/CEILING MOUNTED WIRELESS LOW VOLTAGE OCCUPANCY SENSOR SWITCH.PROVIDE TIME SETTING FOR 15 MINUTES OR AS DIRECTED BY ARCHITECT AND OWNER2 : INDICATES A BI-LEVEL SWITCH

WIRELESS LOW VOLTAGE THREE BUTTON SWITCH WITH RAISE LOWERL3

WALL-MOUNTED DUPLEX OR QUAD RECEPTACLE. 20A/125V/2P/3W (GROUNDED)NEMA 5-20R. MOUNTED @ 18" AFF, UON.

E0.1

CDC

VL

VL

SHEET LIST TABLEDrawing Sheet Title Sheet

E0.1 ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

ED1.1 LIGHTING DEMOLITION PLAN

ED1.2 LIGHTING DEMOLITION PLAN

EL1.1 LIGHTING NEW WORK PLAN

EL1.2 LIGHTING NEW WORK PLAN

E5.1 POWER RISER DIAGRAM AND PANEL SCHEDULES

E6.1 LIGHTING FIXTURE SCHEDULE

E6.2 LIGHTING COMPLIANCE CERTIFICATE

E7.1 ELECTRICAL DETAILS

E8.1 LIGHTING CONTROL WIRING SCHEMATIC

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:37

:32 P

MSa

ved B

y: JA

MAAR

.BRA

NDON

File

: O:\2

014\S

AG14

023.0

1\SAG

1402

3.01E

\1402

3.01_

E0.1.

dwg

Sav

e Date

: 06/1

5/201

5 09:5

7 AM

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

ELECTRICALGENERALNOTES,SYMBOLS ANDABBREVIATIONS

Page 2: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

PRINT MAKING STUDIO

ELEVATOR

IT SERVER

TEACHING AREA 1

HVAC/ ELECTRICAL

MEN

WOMEN

CERAMIC STUDIOS

STAIR 2

COPY ROOM

LOBBY

FACILITY DIRECTOR'S

STAIR 1

RECEPTION

CORR.1

CORRIDOR 2

VENDING

OFFICE

MACHINE

ELEVATOR

ADMINISTRATIVE

ASSISTANT

OFFICE

ROOM

CORRIDOR 3

CORR. 4

CLOS.

KILN AREA

ROOM

UP

UP

E

E

E

EPANEL LP1

E

PANEL GP

E E E

E

EEE

E

RESIDENT ARTIST GALLERY

STUDIO 1

CORRIDOR 4

STUDIO 3 STUDIO 2

STUDIO 4STUDIO 5STUDIO 6

STAIR 2

UP

UP

STAFF LUNCH AREA

STAFF

LUNCH

ROOM

MEN

WOMEN

ELECTRIC

CORR. 3

CORRIDOR 2

GALLERY STORAGE 1

GALLERY STORAGE 2

UP

UP

CORRIDOR 1

MAIN GALLERY

MAIN GALLERY EXTENSION

ELEVATOR

LIBRARY GALLERY

LIBRARY

STAIR 1

DN

DN

E

EE

E

E

1. REFER TO DRAWING E0.1 FOR ELECTRICAL GENERAL NOTES, GENERALDEMOLITION NOTES, LEGEND AND ABBREVIATIONS. REFER TO DRAWINGE5.1 FOR THE PARTIAL POWER RISER DIAGRAM AND PANEL SCHEDULES.

2. ALL EXISTING DEVICES TO REMAIN SHALL BE PROTECTED FROM DAMAGETHROUGHOUT THE CONSTRUCTION PROCESS.

3. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BEMAINTAINED.

4. COORDINATE WITH OWNER FOR ALL LIGHT FIXTURES, EXIT SIGNS ANDDEVICES BEING DEMOLISHED WHICH ARE TO BE RETURNED TO OWNERFOR STORAGE.

5. UNLESS OTHERWISE NOTED, REMOVE ALL ASSOCIATED ACCESSORIES,FROM EXISTING ELECTRICAL DEVICES AND FIXTURES NOTED TO BEDEMOLISHED. REMOVE ALL WIRING AND CONDUIT BACK TO SOURCE OFSUPPLY, CUT BACK CAP. ABANDON ALL CONCEALED EXISTING CONDUITSWHICH ARE LOCATED IN CONCRETE WALL OR CEILING/FLOOR SLAB.REMOVE ALL WIRING FROM ANY ABANDONED CONDUITS BACK TO THESOURCE OF SUPPLY.

6. UNLESS OTHERWISE NOTED ON PLAN, IN THE SCOPE OF WORK AREA, ALLELECTRICAL DEVICES SHOWN WITH DASHED LINE AND EITHER WITHSUBSCRIPT LETTER "D" OR WITHOUT ANY SUBSCRIPT REPRESENTEQUIPMENT TO BE DEMOLISHED.

GENERAL NOTES

# KEY NOTES

1. UNLESS OTHERWISE NOTED, ALL EXISTING LIGHTING FIXTURES ANDASSOCIATED CONTROL SWITCHES IN THIS AREA ARE TO BE DEMOLISHED.ALL EXISTING LED EXIT SIGN FIXTURES TO REMAIN IN PLACE. REMOVEPHOTOLUMINESCENT EXIT SIGN FIXTURES.

2. ALL EXISTING LIGHT FIXTURES SERVING THIS ROOM ARE TO REMAIN.DEMOLISH EXISTING LIGHT SWITCH SERVING THE AREA. REFER TO NEWWORK PLAN DRAWING EL1.1 FOR MORE INFORMATION.

LIGHTING DEMOLITION PLAN - FIRST FLOOR1/8" = 1'-0"

2

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015

DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:37

:35 P

MSa

ved B

y: JA

MAAR

.BRA

NDON

File

: O:\2

014\S

AG14

023.0

1\SAG

1402

3.01E

\1402

3.01_

ED1.1

.dwg

Sav

e Date

: 06/1

5/201

5 12:3

5 PM

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

ED1.1

CDC

VL

VL

LIGHTING DEMOLITION PLAN - SECOND FLOOR1/8" = 1'-0"

1

LIGHTINGDEMOLITIONPLAN

Page 3: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

DN

DN

DN

DN

OFFICE LOFT

LITERARY LOFT

MECHANICAL ROOM

STUDIO 8 LOFT

STUDIO 7 LOFT

OPEN TO MAIN GALLERY BELOW

OPEN TO RESIDENT ARTIST GALLERY BELOW

OPEN TO STUDIOS BELOW

OPEN TO LIBRARY GALLERY BELOW

OPEN TO

LIBRARY BELOW

OPEN TO

STAIR 1 BELOW

OPEN TO

STAIR 2 BELOW

DN

E

1. REFER TO DRAWING E0.1 FOR ELECTRICAL GENERAL NOTES, GENERALDEMOLITION NOTES, LEGEND AND ABBREVIATIONS. REFER TO DRAWINGE5.1 FOR THE PARTIAL POWER RISER DIAGRAM AND PANEL SCHEDULES.

2. ALL EXISTING DEVICES TO REMAIN SHALL BE PROTECTED FROM DAMAGETHROUGHOUT THE CONSTRUCTION PROCESS.

3. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BEMAINTAINED.

4. COORDINATE WITH OWNER FOR ALL LIGHT FIXTURES, EXIT SIGNS ANDDEVICES BEING DEMOLISHED WHICH ARE TO BE RETURNED TO OWNERFOR STORAGE.

5. UNLESS OTHERWISE NOTED, REMOVE ALL ASSOCIATED ACCESSORIES,FROM EXISTING ELECTRICAL DEVICES AND FIXTURES NOTED TO BEDEMOLISHED. REMOVE ALL WIRING AND CONDUIT BACK TO SOURCE OFSUPPLY, CUT BACK CAP. ABANDON ALL CONCEALED EXISTING CONDUITSWHICH ARE LOCATED IN CONCRETE WALL OR CEILING/FLOOR SLAB.REMOVE ALL WIRING FROM ANY ABANDONED CONDUITS BACK TO THESOURCE OF SUPPLY.

6. UNLESS OTHERWISE NOTED ON PLAN, IN THE SCOPE OF WORK AREA, ALLELECTRICAL DEVICES SHOWN WITH DASHED LINE AND EITHER WITHSUBSCRIPT LETTER "D" OR WITHOUT ANY SUBSCRIPT REPRESENTEQUIPMENT TO BE DEMOLISHED.

GENERAL NOTES

# KEY NOTES

1. UNLESS OTHERWISE NOTED, ALL EXISTING LIGHTING FIXTURES ANDASSOCIATED CONTROL SWITCHES IN THIS AREA ARE TO BE DEMOLISHED.ALL EXISTING LED EXIT SIGN FIXTURES TO REMAIN IN PLACE.

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:37

:37 P

MSa

ved B

y: JA

MAAR

.BRA

NDON

File

: O:\2

014\S

AG14

023.0

1\SAG

1402

3.01E

\1402

3.01_

ED1.2

.dwg

Sav

e Date

: 06/1

5/201

5 12:3

5 PM

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

ED1.2

CDC

SME

VL

LIGHTING DEMOLITION PLAN - MEZZANINE LEVEL1/8" = 1'-0"

1

LIGHTINGDEMOLITIONPLAN

Page 4: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

PRINT MAKING STUDIO

ELEVATOR

IT SERVER

TEACHING AREA 1

HVAC/ ELECTRICAL

MEN

WOMEN

CERAMIC STUDIOS

STAIR 2

COPY ROOM

LOBBY

FACILITY DIRECTOR'S

STAIR 1

RECEPTION

CORR.1

CORRIDOR 2

VENDING

OFFICE

MACHINE

ELEVATOR

ADMINISTRATIVE

ASSISTANT

OFFICE

ROOM

CORRIDOR 3

CORR. 4

CLOS.

KILN AREA

ROOM

UP

UP

A

A

C

C

L3

D

C

C

ACCCC

L3 DC C C C

EM C C C C C C

MC

MC

I

I F1F1 F1 F1 F1 F1 F1 F1 F1 F1

F1 F1 F1 F1 F1 F1

F1

F1

MC

G G G

GGG GA

A

EMA

H

H

M

EM

I

I

I

E

C

C

D

L3

L3

L3

L3 L3

EMEM

EM

E

E

EM

C

C

C

C C

C C

EM

C

EM C

A

EMC

b

D

a

D

d

D

c

D

D

a

D

b

D

EM

EM

D

LL

EM

EM

M

a

L3

b

L3

c

L3

d

L3

e

L3

EM

L

L

L3

L3

EM

F1

EM

EM

E

d

D

c

D

EPANEL LP1

E

PANEL GP

LUTRON

LUTRON

LUTRON

LUTRON LUTRON

E E E

E

EEE

O

EM

N

LP1A-1

PANEL LP1A

LP1A-3 LP1A-5

LP1A-2

LP1A-7

LP1A-4 LP1A-6

LP1A-9,11

LP1A-8,10

LP1A-12,14

RESIDENT ARTIST GALLERY

STUDIO 1

CORRIDOR 4

STUDIO 3 STUDIO 2

STUDIO 4STUDIO 5STUDIO 6

STAIR 2

UP

UP

STAFF LUNCH AREA

STAFF

LUNCH

ROOM

MEN

WOMEN

ELECTRIC

CORR. 3

CORRIDOR 2

GALLERY STORAGE 1

GALLERY STORAGE 2

UP

UP

CORRIDOR 1

MAIN GALLERY

MAIN GALLERY EXTENSION

ELEVATOR

LIBRARY GALLERY

LIBRARY

STAIR 1

DN

DN

EE

E

E

D

A5

A5A5

A5

A5

A5

II

I I

II

A5A5A5

A5 A5A5

A5

A5

A5

A5

A5

A5

A5

A5

C

C

C

C C

C

A5

A5

A5 A5A5

A5 A5A5

C

CC

CC

C

C

C

CC

CC

C C

F2

G G

G GG

MC

L3

L3

L3

L3L3

L3

C C C

C CC

EM

L

EM

L

F2

F2

F2

F2

F2

F2F2F2

EM

EM

EM

C

C

F2 F2

IEM

E

EMC

EMC

EMC

P

P

P

P

P P

P

P

L3

L3

a

D

b

D

e

D

f

D

h

D

g

D

c

D

d

D

i

D

j

D

l

D

k

D

m

D

n

D

b

D

a

D

d

D

c

D

e

Df

D

A5

h

D

g

D

a

D

b

D

e

L3

c

D

d

D

e

D

f

D

A5

g

D

h

D

a

D

b

D

d

D

c

D

i

D

j

D

LUTRONLUTRON

LUTRON

LUTRON

LUTRON

E

LP2A-1,3

LP2A-5,7

LP2A-6,8

LP2A-2,4

LP2A-10,12LP2A-14,16

LP2A-18,20

LP2A-22,24

LP2A-26,28

LP2A-9,11

LP2A-17,19

LP2-13,15

LP2-18,20

LP2-7

LP2-5

LP2-9

LP2-11

LP2-11

LP2A-25

LP2A-13,15

LP2A-21,23

LP2-17,19

LP2-14,16

1. TWO CIRCUIT TRACK FIXTURE PROPOSED WITH TYPE A1 FIXTURE HEADS.COORDINATE WITH OWNER TO VERIFY EXACT QUANTITY AND TYPE OFFIXTURE HEAD TYPES INSTALLED TO TRACK SECTION.

2. TWO CIRCUIT TRACK FIXTURE PROPOSED WITH A COMBINATION OF TYPEA1, A3 AND A4 FIXTURE HEADS. COORDINATE WITH OWNER TO VERIFYEXACT QUANTITY AND TYPE OF FIXTURE HEAD TYPES INSTALLED TOTRACK SECTION.

3. ONE CIRCUIT TRACK FIXTURE PROVIDED WITH CORD AND PLUG OPTIONMOUNTED TO A PORTABLE HOLLOW METAL BEAM AND INSTALLED WITHTYPE A2 FIXTURE HEADS. REFER TO DETAIL ON DRAWING E7.1 FOR MOREINFORMATION IN REGARDS TO MOUNTING REQUIREMENTS.

4. UNLESS OTHERWISE NOTED, ALL TRACK INSTALLATIONS IN THIS GALLERYARE TYPE A AND MOUNTED TO THE EXISTING PIPE GRID. INSTALL TRACKWITH A COMBINATION OF TYPE A1, A3, A4, A5, A6 AND A7 FIXTURE HEADS.COORDINATE WITH OWNER TO VERIFY EXACT QUANTITY AND TYPE OFFIXTURE HEAD TYPES INSTALLED TO EACH TRACK SECTION.

5. TYPE B TRACK WITH TYPE B1 FIXTURE HEADS. COORDINATE WITH OWNERFOR CONFIGURATION AND CONFIRM LOCATION OF ASSOCIATED TYPE B2DMX CONTROL BOARD.

6. SEE DETAIL FOR "SWITCH BANK 1" ON THIS SHEET FOR SWITCHINGSCHEME TO CONTROL THE TYPE A TRACK LIGHT FIXTURES IN THERECEPTION AREA.

7. SEE DETAIL FOR "SWITCH BANK 2" ON THIS SHEET FOR SWITCHINGSCHEME TO CONTROL THE TYPE A TRACK LIGHT FIXTURES IN THECORRIDOR 1 AND 2 AREA.

8. SEE DETAIL FOR "SWITCH BANK 3" ON THIS SHEET FOR SWITCHINGSCHEME TO CONTROL LIGHT FIXTURES IN THE PRINT MAKING STUDIO.

9. CONNECT TO SPARE 120V LIGHTING CIRCUIT PREVIOUSLY SERVING THEAREA MADE AVAILABLE AFTER DEMOLITION.

10. CONNECT TO EXISTING EMERGENCY LIGHTING CIRCUIT SERVING THEAREA. CONTRACTOR TO ENSURE CIRCUIT IS CONNECTED UN-SWITCHEDTO A LOCKABLE CIRCUIT BREAKER. ENSURE TOTAL LOAD ON CIRCUITDOES NOT EXCEED 14A PER 20A CIRCUIT.

11.PROVIDE TWO CIRCUITS AS INDICATED TO SERVE THE CONNECTED TWOCIRCUIT TYPE A TRACK FIXTURES. UNLESS OTHERWISE INDICATED,CONTRACTOR TO CONNECT THE UPPER SECTION OF EACH TRACK TOONE CIRCUIT AND CONTROL SWITCH AND THE LOWER SECTION OF EACHTRACK TO THE SECOND CIRCUIT AND CONTROL SWITCH. CONNECT TOSPARE 120V LIGHTING CIRCUITS PREVIOUSLY SERVING THE AREA MADEAVAILABLE AFTER DEMOLITION.

12. SURFACE MOUNTED RECEPTACLE OUTLET MOUNTED AT 88" AFF.

13. INSTALL NEW NEW WALL MOUNTED VACANCY SENSOR DIMMER SWITCH INPLACE OF EXISTING TOGGLE SWITCH. CONNECT TO EXISTING LIGHTINGFIXTURES SERVING THE LIBRARY SPACE.

14. CONNECT AHEAD OF A LOCAL SWITCH SERVING THE ROOM.

15. SEE DETAIL FOR "SWITCH BANK 5" ON THIS SHEET FOR SWITCHINGSCHEME TO CONTROL LIGHT FIXTURES IN THE RESIDENT ARTIST GALLERY.

16. SEE DETAIL FOR "SWITCH BANK 4" ON THIS SHEET FOR SWITCHINGSCHEME TO CONTROL LIGHT FIXTURES IN THE MAIN GALLERY.

17. SEE DETAIL FOR "SWITCH BANK 6" ON THIS SHEET FOR SWITCHINGSCHEME TO CONTROL LIGHT FIXTURES IN THE MAIN GALLERY EXTENSION.

18. SEE DETAIL FOR "SWITCH BANK 7" ON THIS SHEET FOR SWITCHINGSCHEME TO CONTROL LIGHT FIXTURES IN THE LIBRARY GALLERY.

19.LIGHTING CONTROL PANEL. REFER TO DETAIL ON DRAWING E7.1 FORMORE INFORMATION. INSTALL PER NEC AND CLEARANCE REQUIREMENTS.

20.CONTRACTOR TO TEST EXISTING EXTERIOR LIGHTING FIXTURE. RE-LAMPAND RE-BALLAST FIXTURE. FOR EGRESS REQUIREMENTS, PROVIDE NEWEMERGENCY BATTERY BACKUP AND AND CONNECT VIA NEW CENTRALPHOTOCELL AS REQUIRED IF EXISTING IS NOT INSTALLED.

21.NEW PENDANT MOUNTED LIGHT FIXTURE MOUNTED IN CANOPY.COORDINATE MOUNTING REQUIREMENTS AND PENDANT LENGTH WITHARCHITECT. MOUNT SUCH THAT BOTTOM OF FIXTURE IS ABOVE LOWERLIMIT OF CANOPY FRAME. CONNECT VIA CENTRAL PHOTOCELL.

22.CONNECT TO NEAREST EXISTING 120V EMERGENCY CIRCUIT SERVING THEAREA MADE AVAILABLE AFTER DEMOLITION.

23.PROVIDE TRACK WITH 2.5A CURRENT LIMITER OPTION PER CIRCUIT.

24.PROVIDE TRACK WITH 7.5A CURRENT LIMITER OPTION PER CIRCUIT.

# KEY NOTES

1. REFER TO DRAWING E0.1 FOR ELECTRICAL GENERAL NOTES, LEGENDAND ABBREVIATIONS. REFER TO DRAWING E5.1 FOR THE PARTIAL POWERRISER DIAGRAM AND PANEL SCHEDULES DRAWING E6.1 FOR THELIGHTING FIXTURE SCHEDULE.

2. GANG ALL SWITCHES, IF THERE ARE MORE THAN ONE AT THE SAMELOCATION, IN ONE BOX/COVER PLATE.

3. COORDINATE WITH ARCHITECT TO VERIFY ELEVATION AND DETAILS FOREXACT LOCATION, MOUNTING HEIGHTS AND ADDITIONAL INFORMATIONPRIOR TO ROUGH-IN WORK.

4. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BEMAINTAINED. PROVIDE NEW BRANCH CIRCUIT WIRING AS SHOWN TOACCOMMODATE FOR NEW CONSTRUCTION.

5. ALL REUSED CIRCUIT NUMBERS SHOWN ON PLAN ARE BASED ONEXISTING DOCUMENTS AND MAY NOT MATCH WITH THE ACTUAL CIRCUITFOR THAT LOCATION. EXACT CIRCUIT NUMBERS SHOULD BE VERIFIED BYCONTRACTOR DURING CONSTRUCTION.

6. AT THE COMPLETION OF CONSTRUCTION, CLEAN LENSES ANDREFLECTORS OF ALL LIGHTING FIXTURES IN CONTRACT AREAS SO AS TORENDER THEM FREE OF ANY MATERIAL, SUBSTANCE OR FILM FOREIGN TOTHE FIXTURES. BLEMISHED, DAMAGED OR UNSATISFACTORY FIXTURESSHALL BE REPLACED IN A SATISFACTORY MANNER.

7. CLEAN/RELAMP (RE BALLAST, IF REQUIRED) ALL EXISTING TO REMAIN ANDRELOCATED LIGHTING FIXTURES TO REMAIN IN THE CONTRACT AREA.CONTRACTOR SHALL ENSURE THAT ALL REUSED FIXTURES SHALL BE INGOOD WORKING CONDITION.

8. UNLESS OTHERWISE NOTED, IN THE SCOPE OF WORK AREA, ALLELECTRICAL DEVICES EITHER SHOWN WITH A SUBSCRIPT LETTER "N" ORWITHOUT ANY SUBSCRIPT ARE NEW TO BE PROVIDED.

GENERAL NOTES

SWITCH BANK 1: RECEPTION

a

D

b

D

c

D

d

D

a

D

b

D

c

D

d

D

SWITCH BANK 5:RESIDENT ARTIST GALLERY

e

D

f

D

g

D

h

D

a

D

b

D

c

D

d

D

e

D

f

D

g

D

h

D

SWITCH BANK 2: CORRIDOR

a

D

b

D

c

D

d

D

i

D

j

D

k

D

l

D

SWITCH BANK 4:MAIN GALLERY

m

D

n

D

a

D

b

D

c

D

d

D

SWITCH BANK 6:MAIN GALLERY EXTENSION

e

L3

e

D

f

D

g

D

h

D

SWITCH BANK 7: LIBRARY GALLERY

a

D

b

D

c

D

d

D

i

D

j

D

SWITCH BANK 3:PRINT MAKING STUDIO

a

L3

b

L3

c

L3

d

L3

e

L3

LIGHTING NEW WORK PLAN - FIRST FLOOR1/8" = 1'-0"

2

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:37

:41 P

MSa

ved B

y: JA

MAAR

.BRA

NDON

File

: O:\2

014\S

AG14

023.0

1\SAG

1402

3.01E

\1402

3.01_

EL1.1

.dwg

Sav

e Date

: 06/1

5/201

5 12:3

5 PM

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

EL1.1

LIGHTING NEWWORK PLAN

CDC

VL

VL

LIGHTING NEW WORK PLAN - SECOND FLOOR1/8" = 1'-0"

1

SWITCH BANK CONFIGURATIONSNTS

3

Page 5: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

DN

DN

DN

DN

OFFICE LOFT

LITERARY LOFT

MECHANICAL ROOM

STUDIO 8 LOFT

STUDIO 7 LOFT

OPEN TO MAIN GALLERY BELOW

OPEN TO RESIDENT ARTIST GALLERY BELOW

OPEN TO STUDIOS BELOW

OPEN TO LIBRARY GALLERY BELOW

OPEN TO

LIBRARY BELOW

OPEN TO

STAIR 1 BELOW

OPEN TO

STAIR 2 BELOW

DN

L3

F1

F1

F1

F1F1

F1

F1

F1

II

I

L3

L3

L3

F1

EM

F1

F1

F1

F1 F1

EM

F1

EM

F1

F1

F1

F1

F1

EM

E

IEM

LUTRON

LUTRON

LUTRON

LUTRON

PANEL LP2

E

PANEL LP2A

N

LP2-2

LP2-4

1. REPLACE ALL EXISTING FLUORESCENT UTILITY LIGHT FIXTURES IN THISROOM WITH NEW TYPE I LIGHT FIXTURES.

2. CONNECT TO SPARE 120V LIGHTING CIRCUIT PREVIOUSLY SERVING THEAREA MADE AVAILABLE AFTER DEMOLITION.

3. CONTRACTOR TO RELOCATE ANY EXISTING ACTIVE DEVICES ANDREROUTE ANY ACTIVE CONDUITS AT THAT LOCATION TO ACCOMMODATEINSTALLATION OF THE NEW PANEL. SPLICE THE ASSOCIATED EXISTINGBRANCH CIRCUIT WIRING AND CONDUITS AND EXTEND TO NEW LOCATIONFOR THE RELOCATED DEVICES AS REQUIRED.

# KEY NOTES

1. REFER TO DRAWING E0.1 FOR ELECTRICAL GENERAL NOTES, LEGENDAND ABBREVIATIONS. REFER TO DRAWING E5.1 FOR THE PARTIAL POWERRISER DIAGRAM AND PANEL SCHEDULES DRAWING E6.1 FOR THELIGHTING FIXTURE SCHEDULE.

2. GANG ALL SWITCHES, IF THERE ARE MORE THAN ONE AT THE SAMELOCATION, IN ONE BOX/COVER PLATE.

3. COORDINATE WITH ARCHITECT TO VERIFY ELEVATION AND DETAILS FOREXACT LOCATION, MOUNTING HEIGHTS AND ADDITIONAL INFORMATIONPRIOR TO ROUGH-IN WORK.

4. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BEMAINTAINED. PROVIDE NEW BRANCH CIRCUIT WIRING AS SHOWN TOACCOMMODATE FOR NEW CONSTRUCTION.

5. ALL REUSED CIRCUIT NUMBERS SHOWN ON PLAN ARE BASED ONEXISTING DOCUMENTS AND MAY NOT MATCH WITH THE ACTUAL CIRCUITFOR THAT LOCATION. EXACT CIRCUIT NUMBERS SHOULD BE VERIFIED BYCONTRACTOR DURING CONSTRUCTION.

6. AT THE COMPLETION OF CONSTRUCTION, CLEAN LENSES ANDREFLECTORS OF ALL LIGHTING FIXTURES IN CONTRACT AREAS SO AS TORENDER THEM FREE OF ANY MATERIAL, SUBSTANCE OR FILM FOREIGN TOTHE FIXTURES. BLEMISHED, DAMAGED OR UNSATISFACTORY FIXTURESSHALL BE REPLACED IN A SATISFACTORY MANNER.

7. CLEAN/RELAMP (RE BALLAST, IF REQUIRED) ALL EXISTING TO REMAIN ANDRELOCATED LIGHTING FIXTURES TO REMAIN IN THE CONTRACT AREA.CONTRACTOR SHALL ENSURE THAT ALL REUSED FIXTURES SHALL BE INGOOD WORKING CONDITION.

8. UNLESS OTHERWISE NOTED, IN THE SCOPE OF WORK AREA, ALLELECTRICAL DEVICES EITHER SHOWN WITH A SUBSCRIPT LETTER "N" ORWITHOUT ANY SUBSCRIPT ARE NEW TO BE PROVIDED.

GENERAL NOTES

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:37

:43 P

MSa

ved B

y: JA

MAAR

.BRA

NDON

File

: O:\2

014\S

AG14

023.0

1\SAG

1402

3.01E

\1402

3.01_

EL1.2

.dwg

Sav

e Date

: 06/1

5/201

5 12:3

5 PM

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

EL1.2

CDC

VL

VL

LIGHTING NEW WORK PLAN - MEZZANINE LEVEL1/8" = 1'-0"

1

LIGHTING NEWWORK PLAN

Page 6: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

(E)

PANEL"GP"

400A MCB208/120V3PH, 4W

(E)

PANEL"LP1"

225A MLO208/120V3PH, 4W

PANEL"LP2"

225A MLO208/120V3PH, 4W

(E)

FIRST FLOOR

SECOND FLOOR

MEZZANINE

(E)

(E)

SERVICESWITCH

(E)

GENERAL NOTES

1. UNLESS OTHERWISE NOTED, ALL ELECTRICAL EQUIPMENT , PANELSPANELS, FEEDERS AND ASSOCIATED CONDUITS ARE EXISTING TOREMAIN AND SHOWN FOR REFERENCE ONLY.

KEY NOTES

1. EXISTING 100A-3P CIRCUIT BREAKER.

2. CONTRACTOR TO SPLICE, INTERCEPT AND EXTEND EXISTINGBRANCH CIRCUIT LP2-38 AND LP2-40 AND ASSOCIATED WIRING, INEXISTING PANEL LP2 TO NEW CIRCUIT BREAKER LP2-16 AND LP2-18RESPECTIVELY IN ORDER TO ACCOMMODATE NEW 3 POLE CIRCUITBREAKER INSTALLATION.

3. NEW 60A-3P BREAKER TO SERVE NEW PANEL LP1A.

4. NEW 150A-3P BREAKER TO SERVE NEW PANEL LP2A.

PANEL"LP1A"

100A MLO208/120V3PH, 4W

NEW 4#4 AWG+ 1#8AWG G IN 1 1/4"C

PANEL"LP2A"

150A MCB208/120V3PH, 4W

(N)

(N)

NEW 4#1/0 AWG+1#6 AWG G IN 1 1/2"C

LOAD ANALYSIS

PROJECT SCOPE OF WORK IS LIMITED TO THE REPLACEMENT OF ONLY THEEXISTING LIGHTING FIXTURES IN THE FACILITY WITH NEW ENERGY EFFICIENTFIXTURES.ALL OTHER ELECTRICAL POWER, EQUIPMENT AND MISCELLANEOUSLOADS ARE EXISTING TO REMAIN. ALL EXISTING LIGHTING LOADS ARE FED VIAEXISTING 120/208V, 3 PHASE, 4 WIRE PANEL GP RATED FOR 400A.

SUMMARY OF EXISTING LIGHTING LOAD:FLUORESCENT LIGHTING LOAD WITH T12 LAMPS = 23.5 kVA

TYPICAL TRACK FIXTURE PAR LAMP LOAD = 75 WQUANTITY OF PAR LAMP TRACK FIXTURES = 115TOTAL TRACK FIXTURE PAR LAMP LOAD = 75 x 115 = 8.63 kVA

TYPICAL TRACK FIXTURE BIAX LAMP LOAD = 85 WQUANTITY OF BIAX LAMP TRACK FIXTURES = 21TOTAL TRACK FIXTURE BIAX LAMP LOAD = 85 x 21 = 1.79 kVA

THEREFORE, TOTAL EXISTING LIGHTING LOAD = 23.5 + 8.63 + 1.79= 33.92 kVA

SUMMARY OF NEW LIGHTING DEMAND LOAD:PANEL LP1A = 17 kVAPANEL LP2 = 18 kVAPANEL LP2A = 40 kVA

THEREFORE, TOTAL NEW LIGHTING DEMAND LOAD = 75 kVA

OVERALL LOAD SUMMARY FOR PANEL GPPEAK DEMAND LOAD BY UTILITY COMPANY IN ONE YEAR PERIOD: JULY 2013 = 104 kVA

EXISTING DEMAND LOAD ON PANEL GP = 46 kVA OF 104 kVALIGHTING LOAD REMOVED FROM PANEL GP = 33.92 kVATOTAL EXISTING DEMAND LOAD ON PANEL GP = 12.08 kVATOTAL DEMAND LOAD WITH 125% FACTOR PER NEC = 12.08 x 1.25 = 15.1 kVA

THEREFORE, TOTAL DEMAND LOAD ON PANEL GP = 15.1 + 75 = 90.1 kVA= 250.3A @208V-3PH

TOTAL DEMAND LOAD OF 250.3A ON PANEL GP IS LESS THAN THE PANELCAPACITY OF 400A, AND THUS WITHIN PERMISSIBLE LIMITS FOR THE PANEL.

PANELBOARD SCHEDULE NOTES

1. TURN ALL SPARE CIRCUIT BREAKERS TO "OFF" POSITION AT COMPLETION OF WORK.

2. NEW CIRCUIT BREAKER (IF PROVIDED) MUST BE COMPATIBLE WITH EXISTING PANELBOARD (UL LISTED, MANUFACTURED BY THEPANELBOARD MANUFACTURER AND WHICH HAVE AN AIC RATING TO MATCH THE EXISTING PANEL RATING).

3. PROVIDE TYPE WRITTEN SCHEDULE FOR PANELBOARDS UTILIZED AT COMPLETION OF PROJECT INDICATING ACTUAL AS-BUILTCONDITIONS.

4. ALL SPARE CIRCUIT BREAKERS NUMBER MADE AVAILABLE AFTER DEMOLITION ARE BASED ON THE EXISTING DOCUMENTS AND MAYBE INACCURATE. THE ACTUAL CIRCUIT NUMBERS MAY BE DIFFERENT AND SHALL BE VERIFIED IN FIELD DURING CONSTRUCTION.

5. CONTRACTOR TO VERIFY QUANTITY OF ALL INACTIVE CIRCUITS BREAKERS IN ALL EXISTING PANELS ON FLOOR. TURN ALL SPARECIRCUIT BREAKERS TO OFF POSITION.

6. PROVIDE APPROPRIATE ARC FLASH WARNING LABELS FOR ALL NEW PANELBOARDS.

7. ALL THE UNGROUNDED AND GROUNDED CONDUCTORS OF EACH MULTIWIRE BRANCH CIRCUIT SHALL BE GROUPED BY WIRE TIESOR SIMILAR MEANS IN AT LEAST ONE LOCATION WITHIN THE PANELBOARD OR OTHER POINT OF ORIGINATION.

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:37

:48 P

MSa

ved B

y: VA

RUN.

LAMB

A F

ile: O

:\201

4\SAG

1402

3.01\S

AG14

023.0

1E\14

023.0

1_E5

.1.dw

g S

ave D

ate: 0

6/15/2

015 0

9:55 A

M

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

E5.1

CDC

VL

VL

PARTIAL POWER RISER DIAGRAMNTS

1

POWER RISERDIAGRAM ANDPANELSCHEDULES

Page 7: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

LIGHTING FIXTURE SCHEDULE NOTES

1. ALL LIGHTING FIXTURES SHALL BE PROVIDED COMPLETELY WITH ALLLAMPS, WIRE, CONTROLLER AND SECURELY ATTACHED TO SUPPORTS.

2. WHERE BOTH NARRATIVE AND/OR PICTORIAL FIXTURE DESCRIPTIONARE PROVIDED THE WRITTEN DESCRIPTION SHALL TAKE PRECEDENCEAND PREVAIL.

3. ALL FIXTURES AND WORKMANSHIP SHALL BE GUARANTEED FREE OFDEFECTS AND FULLY OPERATIONAL FOR A MINIMUM OF ONE YEARAFTER THE ACCEPTANCE OF THE PROJECT BY THE OWNER. FIXTURESOR WORKMANSHIP (EXCLUDING LAMPS) FOUND TO BE DEFECTIVEDURING THE WARRANTY PERIOD WILL BE EITHER FIXED OR REPLACEDBY THE CONTRACTOR AT NO COST TO THE OWNER.

4. LOCATION OF THE FIXTURES ARE SHOWN DIAGRAMMATICALLY. VERIFYEXACT LOCATION AND SPACING WITH PLANS AND THE ARCHITECTS ATTHE SITE DURING INSTALLATION IF REQUIRED. NOTIFY THE ARCHITECTABOUT FIELD CONDITIONS AT VARIANCE WITH CONTRACT DOCUMENTSBEFORE COMMENCING INSTALLATION.

5. AT THE COMPLETION OF CONSTRUCTION, CLEAN LENSES ANDREFLECTORS OF ALL LIGHTING FIXTURES IN CONTRACT AREAS SO ASTO RENDER THEM FREE OF ANY MATERIAL, SUBSTANCE OR FILMFOREIGN TO THE FIXTURES. BLEMISHED, DAMAGED, ORUNSATISFACTORY FIXTURES SHALL BE REPLACED IN A SATISFACTORYMANNER.

6. REFER TO ARCHITECTURAL PLANS, ELEVATIONS FOR EXACT FIXTURESMOUNTING REQUIREMENTS (WALL OR CEILING) PRIOR TOINSTALLATION.

CONTRACTOR TO PROVIDE A MINIMUM OF 20 TRACK FIXTURE HEADS FORFIXTURE TYPES A1, A2, A3, A4, A5, A6 AND A7.

COORDINATE WITH OWNER TO VERIFY EXACT QUANTITY OF ADDITIONALTRACK FIXTURE HEADS TO BE ORDERED FOR BUILDING STOCK.

ALSO VERIFY EXACT QUANTITY OF THE PORTABLE TRACK INSTALLATIONSWITH TYPE A2 TRACK FIXTURE HEADS AS DEPICTED IN DETAIL ON DRAWINGE7.1 REQUIRED FOR BUILDING STOCK.

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:37

:54 P

MSa

ved B

y: VA

RUN.

LAMB

A F

ile: O

:\201

4\SAG

1402

3.01\S

AG14

023.0

1E\14

023.0

1_E6

.1.dw

g S

ave D

ate: 0

6/15/2

015 1

0:41 A

M

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

E6.1

CDC

VL

VL

LIGHTINGFIXTURESCHEDULE

Page 8: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:38

:04 P

MSa

ved B

y: VA

RUN.

LAMB

A F

ile: O

:\201

4\SAG

1402

3.01\S

AG14

023.0

1E\14

023.0

1_E6

.2.dw

g S

ave D

ate: 0

6/15/2

015 0

9:55 A

M

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

CDC

VL

VL

06/15/2014Conrad  Dela Cruz, PE Sr. Electrical Engineer

E6.2

LIGHTINGCOMPLIANCECERTIFICATE

NOT APPLICABLE IN GALLERY SPACES

NOT APPLICABLE IN GALLERY SPACES

TASK TO BE PERFORMED BY CONTRACTOR

TASK TO BE PERFORMED BY CONTRACTOR

TASK TO BE PERFORMED BY CONTRACTOR

TASK TO BE PERFORMED BY CONTRACTOR

TASK TO BE PERFORMED BY CONTRACTOR

Page 9: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

1. WALL ASSEMBLY - THE FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTEDOF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL ANDPARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWINGCONSTRUCTION FEATURES:

1.1. STUDS - WALL FRAMING MAY CONSIST OF STEEL CHANNEL STUDS. STEEL STUDS TO BE MIN 3-5/8 IN.WIDE AND SPACED MAX 24 IN. OC.

1.2. GYPSUM BOARD* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS REQUIRED IN THEINDIVIDUAL WALL AND PARTITION DESIGN. MAX DIAM OF OPENING IN STEEL STUD WALLS IS 14 IN. THEHOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALLASSEMBLY IN WHICH IT IS INSTALLED.

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE FIRESTOPSYSTEM. THE SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE A MIN 0 IN.(POINT CONTACT) TO A MAX 2 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OFWALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BEUSED:

2.1. STEEL PIPE - NOM 12 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER STEEL PIPE.

2.2. IRON PIPE - NOM 12 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

2.3. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) ELECTRICAL METALLIC TUBING, NOM 6 IN. DIAM (OR SMALLER)STEEL CONDUIT OR NOM 1 IN. DIAM (OR SMALLER) FLEXIBLE STEEL CONDUIT.

2.4. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

2.5. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. FILL, VOID OR CAVITY MATERIAL* - CAULK - MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THEANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 3/8 IN. DIAM BEAD OF FILL MATERIAL APPLIED ATPOINT CONTACT LOCATION AT THE PENETRANT/GYPSUM BOARD INTERFACE ON BOTH SIDES OF WALL.MOMENTIVE PERFORMANCE MATERIALS - PENSIL 100 CAULK.

4. PENETRATIONS THROUGH STRUCTURE SHALL MAINTAIN FIRE RESISTANCE AND COMPLY WITH THEAPPLICABLE VERSION OF THE INTERNATIONAL BUILDING CODE. ALL ANNULAR SPACES BETWEEN RATEDSTRUCTURE/ENCLOSURE SHALL BE FILLED WITH APPROVED MATERIAL COMPLYING WITH REQUIREMENTS OFUL 1479.

1. WALL ASSEMBLY - MIN 6 IN. (152 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCFOR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETEBLOCKS*. MAX DIAM OF OPENING IS 25 IN. (635 MM). SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRERESISTANCE DIRECTORY FOR THE NAMES OF MANUFACTURERS.

2. THROUGH PENETRANT - ONE METALLIC PIPE, TUBING OR CONDUIT TO BE INSTALLED EITHERCONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEENPIPES, TUBING OR CONDUITS AND PERIPHERY OF OPENING IS DEPENDENT UPON THE TYPE AND MAX DIAMOF THE THROUGH PENETRANT AS TABULATED BELOW. PIPE, TUBING OR CONDUIT TO BE RIGIDLYSUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES,TUBING OR CONDUITS MAY BE USED:

2.1. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

2.2. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

2.3. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

2.4. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

2.5. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING, NOM 6 IN.(152 MM) DIAM GALV STEEL CONDUIT OR NOM 1 IN. DIAM FLEXIBLE STEEL CONDUIT.

3. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. (16 MM) THICKNESS OF FILL MATERIAL APPLIEDWITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT LOCATION BETWEENTHROUGH PENETRANT AND CONCRETE, A MIN 3/8 IN. (10 MM) DIAM BEAD OF FILL MATERIAL SHALL BEAPPLIED AT THE CONCRETE/THROUGH PENETRANT INTERFACE ON BOTH SURFACES OF WALL.

4. PENETRATIONS THROUGH STRUCTURE SHALL MAINTAIN FIRE RESISTANCE AND COMPLY WITH THEAPPLICABLE VERSION OF THE INTERNATIONAL BUILDING CODE. ALL ANNULAR SPACES BETWEEN RATEDSTRUCTURE/ENCLOSURE SHALL BE FILLED WITH APPROVED MATERIAL COMPLYING WITH REQUIREMENTSOF UL 1479.

TYPE OF THROUGH PENETRANTMAX DIAM OF THROUGH

PENETRANT, IN. (MM)MIN & MAX ANNULAR

SPACE, IN. (MM)

STEEL OR IRON PIPE 4 (102) 0, 1-1/2 (38)

STEEL TUBING OR CONDUIT 4 (102) 0, 1-1/2 (38)

STEEL CONDUIT 6 (152) 1/8 (3), 1/2 (13)

STEEL OR IRON PIPE 24 (610) 1/8 (3), 1/2 (13)

COPPER TUBING OR PIPE 6 (152) 1/8 (3), 1/2 (13)

GYPSUM WALLBOARDSYSTEM NO. W-L-1062

F RATINGS - 1 AND 2 HRT RATING - 0 HR

L RATING AT AMBIENT -LESS THAN 1 CFM/SQ FT

L RATING AT 400 F -LESS THAN 1 CFM/SQ FT

REINFORCED CONCRETESYSTEM NO. W-J-1030

F RATINGS - 2 HRT RATING - 0 HR

SECTION A-A

SECTION A-AA

A

A

A

GRADE

EXISTINGEXTERIOR WALL

DEMOUNTABLEPARTITION WALL

85"

NOTCH IN BEAM ATPARTITION WALL

198"

NEW SURFACEMOUNTED DUPLEXOUTLET AT 88" AFF

NEW FIRE RETARDANT WOODFRAMING BRACKET TO

SUPPORT BEAM, FINISH TOMATCH EXISTING WOOD TRIM

TYPE G TRACKFIXTURE WITH

CORD AND PLUG

TYPICAL, TYPE A2 TRACKFIXTURE HEAD, MINIMUM 3PER TRACK, VERIFY EXACT

QUANTITY WITH OWNER

1. CONTRACTOR TO BUILD A PORTABLE AND RIGID HOLLOW METAL BEAMTO SUPPORT THE INSTALLATION OF TYPE G TRACK FIXTURE. THE BEAM ISTO BE CONSTRUCTED OF A LIGHT WEIGHT MATERIAL SUCH AS ALUMINUMOR STRUT SO THAT IT CAN BE FULLY SUPPORTED BY THE EXISTINGDEMOUNTABLE PARTITION WALL AND NEW BRACKET.

2. HOLLOW METAL BEAM IS TO RUN ACROSS LENGTH OF TYPICAL STUDIOSPACE AND REST UPON EXISTING DEMOUNTABLE PARTITION WALL ANDNEW BRACKET AS INDICATED. VERIFY FINISH WITH ARCHITECT ANDCONTRACTING OFFICERS REPRESENTATIVE AND CONSTRUCT WITHFACTORY APPLIED.

3. CONTRACTOR TO VERIFY ALL NOTED DIMENSIONS IN FIELD AND PROVIDESHOP DRAWINGS FOR REVIEW PRIOR TO INSTALLATION. VERIFY EXACTQUANTITY OF THIS PORTABLE TRACK INSTALLATION REQUIRED FORBUILDING STOCK WITH ARCHITECT AND OWNER.

# KEY NOTES

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:38

:11 P

MSa

ved B

y: VA

RUN.

LAMB

A F

ile: O

:\201

4\SAG

1402

3.01\S

AG14

023.0

1E\14

023.0

1_E7

.1.dw

g S

ave D

ate: 0

6/12/2

015 0

3:30 P

M

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

E7.1

CDC

SME

VL

THROUGH-PENETRATION FIRESTOP DETAILNTS

1

FIXTURE TYPE G INSTALLATION IN TYPICAL STUDIONTS

2

ELECTRICALDETAILS

TYPICAL PANEL BOARD NAMEPLATE DETAILNTS

4

Page 10: E0 electrical general notes 1.installation of all work shall be in accordance with the following regulations, codes, etc. a. local codes and ordinances b. the edition of the national

QS WIRING AS REQUIRED BY CONTROL LINK LENGTH:

CONTROL LINKLENGTH

WIRE GAUGEAVAILABLE FROM

LUTRON IN ONE CABLE:

LESS THAN500FT (153M)

POWER (TERMINALS 1&2):1 PAIR 18 AWG (1.0MM²) GRX-CBL-346S

ORGRX-PCBL-346S

DATA (TERMINALS 3&4):1 PAIR 22 AWG (0.5MM²),

TWISTED AND SHIELDED*

500FT (153M) TO2000FT (610M)**

POWER (TERMINALS 1&2):1 PAIR 12 AWG (1.0MM²)

GRX-CBL-46LOR

GRX-PCBL-46LDATA (TERMINALS 3&4):1 PAIR 22 AWG (0.5MM²),

TWISTED AND SHIELDED*

*ALTERNATE DATA-ONLY CABLE: USE APPROVED DATA LINK CABLE (22 AWG[0.5MM²] TWISTED/SHIELDED) FROM BELDEN (MODEL # 9461).**TOTAL LENGTH OF THE QS LINK MUST NOT EXCEED 2000FT (610M).***QS LINK CAN HAVE A MAXIMUM OF 99 DEVICES, 100 ZONES, AND 512SWITCH LEGS.

INPUT POWER

2 #12AWG

3 #12AWG

ECOSYSTEM BUS:LUTRON CABLE C-CBL-216-GR-1 (2 #16 CONDUCTOR NON-PLENUM) ORC-PCBL-216-CL-1 (2 #16 CONDUCTOR PLENUM RATED). OTHERWISE USE2 #16 AWG.

CAT5E OR BETTER CABLE FOR DEDICATED LUTRON NETWORKTERMINATED WITH RJ45 CONNECTORS. 328 FEET (100M) MAXIMUM RUN.

E

QS CONTROL LINK (*SEE BELOW)

QS CONTROL LINK (*SEE BELOW)(CONNECT WIRES 1, 3 AND 4. DO NOT CONNECT WIRE # 2)

ORUSE:

\

\

CONTRACTOR TO COORDINATE WITH ARCHITECT AND OWNER TOVERIFY EXACT LOCATIONS AND QUANTITY OF ALL WALL MOUNTEDLIGHTING CONTROL STATIONS, LIGHT SCENE SELECTION SETTINGSAND TO CLARIFY LIGHTING ZONING INTENT. COORDINATE WITHEQUIPMENT VENDOR AND PROVIDE ALL NECESSARY ACCESSORIESAND VERIFY ALL DEVICE QUANTITIES, SPECIFICATION NUMBERS ANDWIRING REQUIREMENTS TO ENSURE A COMPLETE OPERATIONALSYSTEM PRIOR TO ORDERING AND INSTALLATION.

SEQUENCE OF OPERATIONS TO BE COORDINATED WITH ARCHITECT,OWNER AND EQUIPMENT VENDOR.

ORUSE:

QS CONTROL LINKTHE QS CONTROL LINK HAS A FREE WIRING TOPOLOGY (DAISY CHAIN, T-TAP, ETC.)FOR ILLUSTRATION PURPOSES THE QS CONTROL LINK IS SHOWN WIRED IN THE DAISYCHAIN FASHION. ADDITIONALLY, CONTROLS HAVE BEEN LAID OUT TO ENSUREAPPROPRIATE POWER TO EACH DEVICE. CHECK POWER REQUIREMENTS BEFOREMODIFYING DEVICE WIRING ORDER. USE LUTRON CABLE GRX-CBL-346S (4CONDUCTOR NON-PLENUM) OR GRX-PCBL-346S (4 CONDUCTOR PLENUM).OTHERWISE USE 2 #18 AWG (1.0 MM SQ) AND 1 BELDEN #9461. USE GRX-CBL-46L ORGRX-PCBL-46L (4 CONDUCTOR PLENUM) FOR LINKS RUNNING LONGER THAN 500 FT.

ECOSYSTEM BUSTHE ECOSYSTEM BUS HAS A FREE WIRING TOPOLOGY (DAISY, CHAIN, T-TAP,HOME-RUN ETC.) FOR ILLUSTRATION PURPOSES THE ECOSYSTEM BUS IS SHOWNWIRED IN DAISY CHAIN FASHION. ECOSYSTEM BUS REQUIRES LUTRON CABLEC-CBL-216-GR-1 (2 #16 CONDUCTOR NON-PLENUM) OR C-PCBL-216-CL-1 (2 #16CONDUCTOR PLENUM RATED). OTHERWISE USE 2 #16 AWG BY OTHERS. ECOSYSTEMBUS (E1 AND E2) ARE POLARITY INSENSITIVE.

BUS LENGTH IS LIMITED BY THE WIRE GAUGE USED FOR E1 AND E2 AS FOLLOWS:

WIRE GAUGE MAX LOOP LENGTH#18 AWG (1.02MM) 550' (167M)#16 AWG (1.29MM) 900' (274M)#14 AWG (1.63MM) 1,400' (426M)#12 AWG (2.05MM) 2,200' (670M)

WIRING NOTES:

QS-A-CMP-S/RQUANTUM LIGHTING MANAGEMENT SYSTEM DEDICATED

SERVER. TOWER CASE OR RACK MOUNT CAN BE PROVIDED.INSTALLATION TO MEET SPECIFICATIONS AND

REQUIREMENTS IN QS-A-CMP-R-0 SPEC SHEET.PROVIDE WITH INTEGRAL BACNET GATEWAY.

COORDINATE WITH OWNER TO VERIFY EXISTING PC LOCATION.COORDINATE WITH LIGHTING MANAGEMENT SYSTEM VENDOR FORALL NECESSARY CONNECTION REQUIREMENTS AND PROVIDE AS

REQUIRED. INSTALL Q-ADMIN SOFTWARE ON SYSTEM AS REQUIRED.

2 #12 AWG LUTRON

\ \

BASIS OF DESIGN: LUTRON QUANTUM.LIGHTING CONTROL WIRING SCHEMATIC DIAGRAM SHOWN FORREFERENCE AND LIGHTING CONTROL DESIGN INTENT ONLY.APPROVED EQUIVALENT SOLUTION FROM ALTERNATEMANUFACTURER IS ACCEPTABLE.

20A-1P, 120V DEDICATED CIRCUIT

QP3-1PL-100-240QUANTUM LIGHT MANAGEMENT HUB

CONTAINING (1) QUANTUM PROCESSORWITH 2 CONFIGURABLE LINKS

PROVIDE WITH INTEGRATED SOFTWARE ANDNETWORK SWITCH

ADDRESS: MONTPELIER ARTS CENTERLOCATION: FIRST FLOOR ELECTRICAL ROOM

(TYPICAL)QSN-2ECO-S

DEVICE: FIRST FLOOR ELECTRICAL ROOMENERGI SAVR NODE QS (ESN)

(2) ECOSYSTEM DIGITAL LINKSAND (1) QS COMMUNICATION LINK

PROVIDE ONE PER 128 BALLASTS

\

120VINPUT FEED

2 #12 AWG

(TYPICAL)QSM2-4W-C

QUANTUM SENSOR MODULE (QSM)434MHZ WIRELESS SENSOR MODULE

30' RADIUS COVERAGE AREA MAXLOCATE WITHIN 30' OF LUTRON

WIRELESS LIGHTING CONTROL DEVICE.MAXIMUM 10 OF EACH WIRELESS

DEVICE TYPE PER QSM.

QSPS-P1-1-50QS LINK POWER SUPPLY

PROVIDE AS NEEDEDBETWEEN QSM MODULES

PROVIDE 120V DUPLEX RECEPTACLE.COORDINATE EXACT LOCATION OF OUTLET

IN FIELD WITH EQUIPMENT VENDOR

\

LUTRON

\

TO ADDITIONAL QSN-2ECO-S DEVICE INSTALLED IN THESECOND FLOOR ELECTRICAL CLOSET TO SERVE THE LIGHTFIXTURES ON THE SECOND FLOOR AND MEZZANINE LEVELS

LUTRON

Off

Adjust

Light

On

(TYPICAL)MRF2-3BRL-L-WG

434 MHZ PICO WIRELESS3 BUTTON CONTROLWITH RAISE/LOWER

SHOWN WITH CW-1-WHCLARO WALLPLATE

LOCATE WITHIN 30' OFQSM DEVICE

(TYPICAL)LRF2-OCRB-P-WH434MHZ WIRELESS

OCCUPANCY SENSOR

LOCATE WITHIN 30' OF QSM DEVICE

(TYPICAL)LRF2-OWLB-P-WH434MHZ WIRELESS

WALL MOUNTEDOCCUPANCY/VACANCY

SENSOR

LOCATE WITHIN 30' OFQSM DEVICE

(TYPICAL)MASTER CONTROL WALL

STATIONQSWS2-2BN-WH

SeeTouch DEVICEFUNCTION: 2-BUTTON

SCENE 1 AND OFF(1 GANG US BACKBOX BY

CONTRACTOR)

\

TYPICAL DEVICES ON LIGHTING CONTROL SYSTEM. REFER TOFLOOR PLAN DRAWING FOR PROPOSED LOCATION AND QUANTITIES.

TO QS DEVICES(UP TO 30 PDUS)

ECOSYSTEM DIGITAL LOOP #2

Hi-Lume LED®

HI-LUME A SERIESLUTRON LED DRIVER

120V/277V 277V INPUT FEED FROMDISTRIBUTION PANEL

TYPICAL DRIVER FOR ALL INTERIOR LED FIXTURES.REFER TO FLOOR PLANS AND LIGHTING FIXTURES

SCHEDULE FOR QUANTITY AND FIXTURE SPECIFICATION.INTERFACE MODULE FOR FIXTURES NOT DIRECTLY COMPATIBLE WITH

THE LIGHTING CONTROL SYSTEM. TYPICAL ONE PER FIXTURE.

TVI-LMF-2ALUTRON TRANSFER CARD INTERFACE

INTEGRATED WITH LED FIXTURE

INPUT FEED

TO ECOSYSTEMBALLASTS/MODULES

(64 MAXIMUM PER LINK)

TO ECOSYSTEMBALLASTS/MODULES

(64 MAXIMUM PER LINK)

ECOSYSTEM DIGITAL LOOP #1

TO 120V DUPLEXRECEPTACLE

NETWORK SWITCHTERMINAL BOX BY LUTRON

DEDICATED ETHERNET ENVIRONMENT

TO LOCAL AREANETWORK (LAN)

UPSUNINTERRUPTIBLE

POWER SUPPLYBY LUTRON

CONTRACTOR TO PROVIDE ANDCONNECT TO 120V DEDICATED

DUPLEX RECEPTACLE

WIRING LEGEND:

THE MARYLAND-

NATIONAL CAPITAL

PARK & PLANNING

COMMISSION

Maintenance and

Development

Prince Georges County

4200 Ritchie-Marlboro Road

Upper Marlboro, MD 20772

301-780-2300

DRAWN:

REVIEW:

SHEET TITLE

CONSULTANT

DESIGN:

SHEET NO.

SCALE:

BID NO.

STAMP

01/30/2015DATE:

PHASE:

9652 Muirkirk Road

Laurel, Maryland

DATE:

PHASE:

Montpelier Arts Center

Plott

ed B

y: JA

MAAR

BRA

NDON

Plot

Date

: 6/15

/2015

12:38

:14 P

MSa

ved B

y: VA

RUN.

LAMB

A F

ile: O

:\201

4\SAG

1402

3.01\S

AG14

023.0

1E\14

023.0

1_E8

.1.dw

g S

ave D

ate: 0

6/12/2

015 0

1:48 P

M

AS NOTED

PROGRESS SET

06/15/2015

100% CD SUBMISSION

E8.1

CDC

VL

VL

LIGHTING CONTROL WIRING SCHEMATICNTS

1

LIGHTINGCONTROLWIRINGSCHEMATIC