earthing
DESCRIPTION
Earthing and BondingTRANSCRIPT
EARTHING
Definitions:‘Connection of the exposed-conductive parts of an installation to the main earthing terminal of that
installation.’ BS 7671
Exposed-Conductive-Part: A metallic part of an Installation or Appliance
which can be touched by persons and which is not normally live but may become live due to a fault
condition.
Extraneous-conductive-part: a metallic part, structure or any metalwork within a Premises which is not part of, and is unrelated
to, the electrical Installation and which is not designed to carry current, but which may become
livedue to a fault condition.
For example:Non-insulated floors or walls, Metal framework of buildings
Metal conduits and pipework (not part of the electrical installation) for water, gas, heating,
compressed-air, etc. and metal materials associated with them
Electric Shock of persons A person subjected to an electrical voltage is electrified.
According to the gravity of the Electric Shock, this person may experience:
Discomfort * Muscular contraction * Burn * Cardiac arrest (Electrocution)
Standards and regulations distinguish two kinds of dangerous contact,
Direct contact
Indirect contact
Direct contact This is accidental contact of persons with a live conductor (phase or neutral) or a normally live
conductive element
Protection measures consist: in placing these live parts out of reach or in insulating them by means of insulators, enclosures or barriers..
Indirect contactContact of a person with accidentally energized metal frames is
known as indirect contact
Common Reasons: insulation fault
Protection measures consist: 1st level:
The earthing of all exposed-conductive-parts of electrical equipment in the installation & the constitution of an
equipotential bonding network.
2nd level: Automatic disconnection of the supply
Why Earthing is required?
The most important reason is Safety/Protection of Persons & Property;
So as to protect against electric shock by indirect contact
(Discomfort/Muscular contraction/Burn/Cardiac arrest)
&Avoid overheating & fire
Earthing of Exposed-Metallic-Parts of an Installation and of Appliances in a Premise is
required to serve the following functions of safety:
Allow the passage of fault current: in the event of a live conductor touching an Exposed-Metallic-Part;
Ensure that the magnitude of fault current is sufficient to operate Protective Devices:including Earth Leakage Protection devices,
Ensure that, the less resistance from the fault to the Earth:so as to avoid overheating or fire.
GENERAL PRINCIPLES OF EARTHING
SYSTEMS OF EARTHINGToday 3 system earthings such as defined in
IEC 60364:
TN TT ITThe purpose of these three earthings is identical as regards protection of persons and property:
They are considered to be equivalent with respect to safety of persons against indirect contacts.
Identification of the system types is thus defined by means of 2 letters:
The first one for transformer neutral connection (2 possibilities) T for "connected" to the earth I for "isolated" from the earth
The second one for the type of application frame connection (2 possibilities)
T for "directly connected" to the earth N for "connected to the neutral" at the origin of the installation
The TT system
One point at the supply source is connected directly to earth.
All exposed- and extraneous-conductive-parts are connected to a separate earth electrode at the installation.
This electrode may or may not be electrically independent of the source electrode.
Protection & Operation Technic in TT system
The residual current devices (RCDs) are used
Interruption for the first insulation fault
The source is earthed as for the TT system (above).
In the installation, all exposed and extraneous-conductive-parts are connected to the neutral conductor.
The TN system
The several versions of TN systems are shown below.
TN-CIf the N and PE neutral conductors are one and the same (PEN)
TN-SIf the N and PE neutral conductors are separate
Interruption for the first fault using overcurrent protection (circuit-breakers or fuses)
interruption for the first insulation fault
Protection & Operation in TN system
No intentional connection is made between the neutral point of the supply source and earth.
Exposed- and extraneous-conductive-parts of the installation are connected to an earth electrode.
The IT system
Indication of the first fault by an insulation monitoring device (IMD)
Interruption for the second fault using overcurrent protection (CB or fuses)
Monitoring of the first insulation faultMandatory location and clearing of the fault
Interruption for two simultaneous insulation faults
Protection & Operation in IT system
Fault Current & Automatic disconnection for different Earthing systems
Automatic disconnection & Protective Devices for different Earthing systems
CHOOSING THE EARTHING SYSTEM
Choice may be determined by normal practice in the country.
In terms of the protection of persons, the three system earthing arrangements (SEA) are equivalent if all
installation and operating rules are correctly followed.
Consequently, selection does not depend on safety criteria.
The applicable regulations which in some cases impose certain types of SEA
Secondly, the decision of the owner if supply is via a private MV/LV transformer (MV subscription) or the
owner has a private energy source (or a separate-winding transformer)
If the owner effectively has a choice, the decision on the SEA is taken following discussions with the network designer (design office,
contractor)
Fault Current & Automatic disconnection for TT system
The resistance of the earth electrode of substation neutral Rn is 10 Ω.
The resistance of the earth electrode of the installation RA is 20 Ω.
The earth-fault loop current Id = 7.7 A.
The fault voltage Uf = Id x RA = 154 V and therefore dangerous,
But IΔn = 50/20 = 2.5 A so that a standard RCD will operate without intentional time delay and will clear the fault where a fault voltage
exceeding appears on an exposed-conductive-part.
Fault Current & Automatic disconnection for TN system
The resistance of the earth electrode of substation neutral Rn is 10 Ω.
The resistance of the earth electrode of the installation RA is 20 Ω.
The earth-fault loop current Id = 7.7 A.
The fault voltage Uf = Id x RA = 154 V and therefore dangerous,
But IΔn = 50/20 = 2.5 A so that a standard RCD will operate without intentional time delay and will clear the fault where a fault voltage
exceeding appears on an exposed-conductive-part.
Automatic disconnection for TN system
SYSTEMS OF EARTHINGCustomers must be provided with a supply operating
under either of the following earthing systems:
Customer Earthed System (TT): the Customer provides a Main Earth Terminal for the Installation, which is connected to a sufficient number of local Earth Electrodes to provide a maximum Earth Resistance measured at the Customer’s Main Earth Terminal of no greater than 10 Ohms (referred to in BS 7671 as a ‘TT’ system);
Distribution Company Earthed System (TN-S): the Distribution Company provides a connection to the Customer’s Main Earth Terminal, using the distribution network Earthing system, normally via the armouring or metallic sheath of the incoming supply cable (referred to in BS 7671 as a TN-S system). The Distribution Company system is earthed at the distribution transformer (11kV/400V) and separate earth and neutral conductors are used throughout the distribution network; or
Distribution Company Earthed System with additional Customer Earth (TN-S-TT):the Distribution Company provides an earth connection to the Customer’s Main Earth Terminal and a local Earth provided by the Customer is also connected to the same MET, having an Earth Resistance value of no greater than 10 Ohms.
TN-S
TT
TT-S-TN
Main Earth Terminal The Main Earth Terminal must be provided
close to or within the Main Distribution Board or other switchgear at the Supply Intake.
A means of removing the connection to Earth (such asby a detachable metal link) must be provided at the MainEarth Terminal to facilitate testing of the earthing of the
installation and the source of supply,
Main Earth TerminalIllustration shows Distribution Company Earthed System with
additional Customer Earth (TN-S-TT)
For Premises consisting of more than one building, where either a TT or TN-S-TT system is used, Earth Electrodes must be provided at each building that
is more than 30 m distance from the Supply Intake.
Earth Electrodes Earth Electrodes must be provided at Premises whichare supplied by a Customer Earthed System (TT) or aDistribution Company Earthed System with additional
Customer Earths (TN-S-TT).
Earth Electrodes will normally comprise of 9 to 15 mm diameter steel cored copper rods driven to a minimum depth of 1.2,1.5 to 3 m. The top of each Earth Electrode must be housed inside a 300 mm x 300 mm x 300 mm inspection pit which is clearly
labelled and accessible for routine testing,
Alternative types of Earth Electrodes may be used with prior approval of the Distribution Company
(e.g. plate or wire mesh type, or structural steelwork in a
building)..
Where more than one Earth Electrode is required to
achieve the required Earth Resistance value these must be separated at a distance
greater than their mutual resistance zone.
The condition of the ground in which an Earth Electrode
is placed must be taken into account to ensure its long-term performance. In
particular, potential corrosion effects and ground moisture content is of critical
importance. Proprietary chemical or salt materials may be used around the Earth
Electrode to maintain moisture content but these must be stable and sustain their
chemical properties over time.
For supplies of 500 A rating and above, at least two
independent Earth Electrodes must be provided, regardless of the Resistance Value
achieved for each Earth Electrode, and connected to the same Main Earth Terminal,
The number of Earth Electrodes required at a Premises will be determined primarily by the
value of Earth Resistance that can be achieved from each. However, the minimum
number in any case shallbe as shown below:
However, the minimum number in any case shall
be as shown below:
Main Earth Conductors (MEC): conductors connected between Distribution
Boards, Earth Electrodes and Main Earth Terminals;
Earth Conductor
Circuit Earth Conductors (CEC): connected from Final Distribution Boards and
associated with Final Circuits, including Appliance Earth Conductors such as within a
flexible cord. Outside these Regulations these may also be known as the Circuit
Protective Conductor (CPC) or Earth Continuity Conductor (ECC).
For metal sheathed or armoured cables, the sheath orarmouring may be used as the Earth Conductor where
it is rated to the equivalent of the conductor sizes shown
The metal sheath or armouring must be terminated by suitable cable glands with
appropriateconnection to an Earth Conductor,
For Main Earth Conductors between Earth Electrodes and the Main Earth Terminal of an Installation, S should be taken as the cross-
sectional area of the conductors of the incoming supply cable. For other Earth
Conductors S should be taken as the cross-sectional area of the circuit phase
conductors.
Sizing of earth conductors and equipotential bonding conductors
All Exposed-Metallic-Parts of an Installation, includingAppliances, must be connected to Earth via EarthConductors in accordance with the requirements
Exposed-metallic-partsMetallic part of an Installation
or Appliance which can be touched by persons and which is not normally live but may become live due
to a fault condition. Exposed-Metallic-Parts are required to be connected to Earth,
All connection points in an Installation must include an
Earth Conductor for future use.
The following items must be connected to the Circuit Earth Conductor, which should be
provided separately for each Final Circuit, insulated with green/yellow PVC sheath, be of
the appropriate size…
The requirement for connection of Extraneous-Metalic-
Parts to Earth Conductors depends on the type of protection system used in an Installation
All connection points in an Installation must include an
Earth Conductor for future use.
Earth Fault Loop ImpedanceThe Earth Fault Loop Impedance (Zs) is defined as the totalimpedance presented to an earth fault current, comprising
the impedance of the following parts of a system,
The requirement for connection of Extraneous-Metalic-
Parts to Earth Conductors depends on the type of protection system used in an Installation
All connection points in an Installation must include an
Earth Conductor for future use.