Easergy MiCOM P30
IEC 60870-5-104 Protocol
Application Guide
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
CONTENTS
1 SCOPE OF APPLICATION ....................................................................................................................... 5
2 INTEGRATION OF THE IEC 60870-5-104 PROTOCOL INTO EASERGY MICOM P30 ........................ 6
2.1 ETHERNET BOARD ................................................................................................................................ 6 2.2 DEVICE SETTINGS ................................................................................................................................ 6
2.2.1 Protocol settings ........................................................................................................................ 6 2.2.2 Signal and command blocking ................................................................................................... 7 2.2.3 Time synchronization ................................................................................................................. 7 2.2.4 Virtual inputs and status information ......................................................................................... 7
2.3 DATABASES ......................................................................................................................................... 7 2.3.1 Initial state .................................................................................................................................. 7 2.3.2 Creating and loading databases ................................................................................................ 8
3 IEC 60870-5-104 SOFTWARE ARCHITECTURE .................................................................................... 9
3.1 OVERVIEW ........................................................................................................................................... 9 3.2 PROGRAM OBJECTS ............................................................................................................................. 9
3.2.1 Kernel ......................................................................................................................................... 9 3.2.2 Device interface ....................................................................................................................... 10 3.2.3 IEC 60870-5-104 telecontrol lines ........................................................................................... 10 3.2.4 IEC 60870-5-104 master station bus and client ...................................................................... 10 3.2.5 IEC 60870-5-104 server .......................................................................................................... 10 3.2.6 Logic and station interlocking .................................................................................................. 10
4 ENGINEERING ........................................................................................................................................ 11
4.1 X30 STUDIO ...................................................................................................................................... 11 4.1.1 Introduction .............................................................................................................................. 11 4.1.2 Access rights............................................................................................................................ 11
4.2 ENGINEERING STEPS OF AN IEC 60870-5-104 PROJECT ...................................................................... 11 4.2.1 Profile ....................................................................................................................................... 11 4.2.2 Typicals .................................................................................................................................... 12 4.2.3 IEDs ......................................................................................................................................... 12 4.2.4 Configuration............................................................................................................................ 12 4.2.5 Parameterization ...................................................................................................................... 13
5 DATA MODEL AND LOGIC LIBRARY .................................................................................................. 23
5.1 APPROACH ........................................................................................................................................ 23 5.2 INTEGRATION INTO PROGRAM OBJECTS ............................................................................................... 23
5.2.1 Program objects with logic library ............................................................................................ 23 5.2.2 Implementation differences ...................................................................................................... 24
5.3 FORMAT OF DATA MODEL FILES ........................................................................................................... 24 5.3.1 Basic structure of data model files ........................................................................................... 24 5.3.2 Data model file for device interface ......................................................................................... 25 5.3.3 Data model file for telecontrol lines and master station bus .................................................... 26 5.3.4 Data model file for logic / station interlocking .......................................................................... 27
5.4 PROCESSING DATA MODEL FILES ......................................................................................................... 27 5.4.1 Device interface, telecontrol lines, and master ........................................................................ 27 5.4.2 Logic / station interlocking ....................................................................................................... 28
5.5 TELEGRAM PROCESSING..................................................................................................................... 29
6 FUNCTIONS OF THE LOGIC LIBRARY ................................................................................................ 30
6.1 DATA FORMATS .................................................................................................................................. 30 6.2 IMPLICIT CONVERSION ........................................................................................................................ 31 6.3 BIT FIELD ASSIGNMENT ....................................................................................................................... 32 6.4 INPUT-RELATED FUNCTIONS ................................................................................................................ 33
6.4.1 Overview .................................................................................................................................. 33 6.4.2 Negation - 'not' ......................................................................................................................... 34 6.4.3 Arithmetic operations - 'add', 'sub', 'mult', 'div', 'sqrt' ............................................................... 35 6.4.4 Polygon scaling - 'scal' ............................................................................................................. 36 6.4.5 Comparing functions - 'ifeq', 'ifne', 'ifneq', 'ifgt', 'iflt', 'iftc', 'ifntc' ................................................ 37 6.4.6 Comparing functions - 'cmpeq', 'cmpne', 'cmpgt', 'cmpge', 'cmplt', 'cmple' ............................. 38
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.7 Comparing functions for control state messages - 'isdef', 'istra' .............................................. 39 6.4.8 Test of quality descriptors - 'isgood', 'isbad', 'isiv', 'isnt', 'isbl', 'issb', 'isov' .............................. 40 6.4.9 Switch-on delay - 'ton' .............................................................................................................. 41 6.4.10 Switch-off delay - 'toff' .............................................................................................................. 42 6.4.11 Switch-on and switch-off delay - 'tonoff' .................................................................................. 43 6.4.12 Impulse function - 'timp' ........................................................................................................... 44 6.4.13 Timer - 'timer' ........................................................................................................................... 45 6.4.14 Cycle supervision - 'cycsup' ..................................................................................................... 46 6.4.15 Input information of select function - 'sel', 'case', 'deflt' ........................................................... 46 6.4.16 Inputs of the output function D-Flip-Flop - 'set', 'res', 'dat', 'clk' ............................................... 46 6.4.17 Inputs of the output function invalid control - 'sig', 'con' ........................................................... 46 6.4.18 Inputs of the interlocking functions - 'cmd', 'req', 'enon', 'enoff', 'send', 'conf' .......................... 46
6.5 OUTPUT-RELATED FUNCTIONS ............................................................................................................ 47 6.5.1 Overview .................................................................................................................................. 47 6.5.2 Setting the output value - 'set' .................................................................................................. 48 6.5.3 Setting the cause of transmission of the output telegram - 'settc' ........................................... 48 6.5.4 Setting data and cause of transmission - 'setcmd', 'setcon', 'settrm' ....................................... 49 6.5.5 Setting the impulse duration in commands - 'pulse' ................................................................ 50 6.5.6 Setting of quality descriptors – 'setbl', 'setnt', 'setsb', 'setiv', 'setov', 'setqds', 'setca', 'setcy' .. 50 6.5.7 Logical operations - 'or', 'nor', 'and', 'nand', 'iff', 'xor' ................................................................ 51 6.5.8 Dynamic OR operation - 'dynor' ............................................................................................... 53 6.5.9 Bitstring, bitstring of 32 bits - 'bs', 'bs32' .................................................................................. 54 6.5.10 Arithmetic functions - 'sum', 'diff', 'prod', 'quot' ......................................................................... 55 6.5.11 Threshold processing (deadband) - 'db' .................................................................................. 56 6.5.12 Deadband integrated - 'dbi' ..................................................................................................... 57 6.5.13 Average value calculation - 'avg' ............................................................................................. 58 6.5.14 Selecting function (switch) - 'swi' ............................................................................................. 59 6.5.15 Flip-flop (output Q) - 'ffq' .......................................................................................................... 60 6.5.16 Interlocking functions - 'lock', 'elock' ........................................................................................ 61 6.5.17 Invalid control - 'ivcon' .............................................................................................................. 63
6.6 STATUS INFORMATION ........................................................................................................................ 64 6.6.1 Input status information ........................................................................................................... 64 6.6.2 Output status information ......................................................................................................... 65
7 SPECIAL FUNCTIONS OF PROGRAM OBJECTS ............................................................................... 66
7.1 PRIORITY-CONTROLLED DATA TRANSMISSION ...................................................................................... 66 7.1.1 Function ................................................................................................................................... 66 7.1.2 Possibilities of engineering ...................................................................................................... 66
7.2 COMMAND PROCESSING ..................................................................................................................... 67 7.2.1 Function ................................................................................................................................... 67 7.2.2 Possibilities of engineering ...................................................................................................... 68
7.3 CHECK OF CONTROL UNIQUENESS ....................................................................................................... 68 7.4 TRANSMISSION IN REVERSE DIRECTION ............................................................................................... 68 7.5 IEC 60870-5-104 REDUNDANT TRANSMISSION .................................................................................... 69 7.6 TREATMENT OF SIGNALS REPORTED IN ACTIVE STATE ONLY (TRANSIENT SIGNALS) ................................. 69 7.7 CHATTER SUPPRESSION ..................................................................................................................... 70 7.8 SIGNAL AND COMMAND BLOCKS IN THE DATA MODEL ............................................................................ 71
8 STATION INTERLOCKING ..................................................................................................................... 72
8.1 OPERATION WITH STATION INTERLOCKING ........................................................................................... 72 8.2 CONTROL PROCEDURES WITH STATION INTERLOCKING ......................................................................... 72
8.2.1 Remote control with station interlocking .................................................................................. 72 8.2.2 Local control with station interlocking ...................................................................................... 73
8.3 SYSTEM ARCHITECTURES WITH STATION INTERLOCKING ....................................................................... 74 8.3.1 Station interlocking in central substation unit .......................................................................... 74 8.3.2 Station interlocking in field unit ................................................................................................ 75
9 CHECKING AND TEST FUNCTIONS .................................................................................................... 76
9.1 PERMANENT LOGGING FUNCTIONS ...................................................................................................... 76 9.2 CONFIGURABLE LOGGING FUNCTIONS .................................................................................................. 76
10 INTERNAL TELEGRAM INTERFACE ................................................................................................ 77
10.1 TELEGRAM FORMAT AND ENCODING .................................................................................................... 77
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.1.1 Introduction .............................................................................................................................. 77 10.1.2 Data types used ....................................................................................................................... 77 10.1.3 Cause of transmission ............................................................................................................. 78 10.1.4 Data formats ............................................................................................................................ 78 10.1.5 Quality descriptors ................................................................................................................... 79 10.1.6 Device addresses of program objects ..................................................................................... 79
10.2 TELEGRAM EXCHANGE WITH THE DEVICE ............................................................................................. 79 10.2.1 Telegrams from protection part................................................................................................ 79 10.2.2 Telegrams from control part ..................................................................................................... 80 10.2.3 Signals from the communication module to the device ........................................................... 83 10.2.4 Settings from the device for the communication module ......................................................... 84
10.3 SYSTEM TELEGRAMS OF THE COMMUNICATION MODULE ....................................................................... 84 10.3.1 Introduction .............................................................................................................................. 84 10.3.2 Telegram interface of the kernel .............................................................................................. 85 10.3.3 Telegram interface of the device interface .............................................................................. 85 10.3.4 Telegram interface of the IEC 60870-5-104 telecontrol line .................................................... 85 10.3.5 Telegram interface of the IEC 60870-5-104 server ................................................................. 88 10.3.6 Telegram interface of the IEC 60870-5-104 master station bus .............................................. 89 10.3.7 Telegram interface of the IEC 60870-5-104 client ................................................................... 90 10.3.8 Telegram interface of the logic/station interlocking ................................................................. 90
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
1 Scope of application
This document applies to all device types of the Easergy MiCOM P30 series and refers to the following ver-sion of the devices' communication software:
version 4.50
The version of the communication software can be verified in the device under the following address:
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
2 Integration of the IEC 60870-5-104 protocol into Easergy MiCOM P30
2.1 Ethernet board
Depending on the setting IEC prot. variant in function group /Parameters/Config. parame-
ters/IEC, one of the following software packages is started:
• IEC 61850 Edition 2,
• IEC 61850 Edition 1,
• IEC 60870-5-104.
The IEC 60870-5-104 communication software can be used on all redundant (REB) and not-redundant (SEB) Ethernet board variants.
The firmware for IEC 60870-5-104 is the same for all Easergy MiCOM P30 device types and is adapted to the specific device type during engineering through the database.
2.2 Device settings
2.2.1 Protocol settings
The IEC 60870-5-104 protocol settings are configured in the function group Parameters/Config. pa-
rameters/IEC.
In order to configure the protocol settings, they must first be made visible by parameter IEC60870-5-
104enable. As soon as the IEC 60870-5-104 protocol has been selected, after processing by the device,
status information on the installed databases and network parameters are displayed.
General enable USER is used to enable or disable IEC 60870-5-104 communication.
Visibility of IEC 60870-5-104
Setting of IEC 60870-5-104
Status of IEC 60870-5-104
Enabling the communication
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
The settings ETH COMM Mode, Block Port A/B, Block Port C and the time zone settings have the
same effect as in the IEC 61850 Edition 1 and 2 protocols.
2.2.2 Signal and command blocking
In function group /Parameters/Function parameters/Global/IEC, command blocks and sig-
nal/measurement blocks similar to those in the IEC 60870-5-103 protocol can be set:
Blocks can also be set via binary inputs by allocating the functions Command block. EXT or Sig.meas.
block EXT.
The blocking function depends on the Ethernet board configuration. Therefore, it must be defined on the Ethernet board by engineering, which telecontrol lines are to be blocked. For further details, see section 10.2.4.2.
2.2.3 Time synchronization
The settings for the time synchronization interface are configured within function group Parameters/Con-
fig. parameters/IRIGB. If parameter General enable USER is set to Yes, synchronization will be
done via the IRIG-B interface on the communication module, otherwise via SNTP.
The SNTP protocol parameters are set at the communication module; for details, see section 4.2.5.2. For synchronization via IRIG-B, no further settings are required.
2.2.4 Virtual inputs and status information
Virtual inputs are binary signals that are transmitted from the communication module to the CPU. In function group /Parameters/Config. parameters/VINP, device functions can be mapped to those 64 signals.
Furthermore, the quality of the virtual inputs VINP Input xx faulty can be processed.
Addressing of virtual inputs from an Ethernet board perspective is described in section 10.2.3.2.
The IEC 60870-5-104 protocol software assigns status information to matrix points in the device. They can be displayed and processed in the device in the following function groups:
• Operation/Cyclic measurements/Phys. state signals/VINP,
• Operation/Cyclic measurements/Log. state signals/VINP,
• Operation/Cyclic measurements/Log. state signals/MAIN,
• Operation/Cyclic measurements/Log. state signals/IEC.
The addressing of signals on the communication module is described in section 10.2.3.
2.3 Databases
2.3.1 Initial state
The IEC 61850 approach of an active and an inactive configuration database has also been adopted to the IEC 60870-5-104 protocol.
For the IEC 60870-5-104 protocol, after loading the firmware for the active and inactive configuration, a de-fault database default.db is installed. This database contains a minimal configuration, consisting of
• system starter,
• communication kernel, and
• device interface.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Initially, the configuration does not include any IEC 60870-5-104 communication functions. Network inter-faces are initialized with the following default addresses:
• port A/B: 192.168.0.4
• port C: 192.168.1.4
The following system services are operative:
• system administration with X30 Studio, flash loader,
• communication with the setting software over network or serial interface,
• user management with the Security Administration Tool (SAT).
2.3.2 Creating and loading databases
The program X30 Studio is used to engineer Ethernet board for the IEC 60870-5-104 protocol,. The proce-dure is described in this document. The result is a database file, which can be uploaded over Ethernet or se-rial interface from X30 Studio into the device and can then be activated.
The file names of the active and inactive configuration databases and their versions are displayed in the Easergy Studio setting software in function group /Parameters/Config. parameters/IEC. In order for
the file names to be displayed correctly, they must comply with the following rules:
• total number of characters: max. 20
• file type: ".db"
• version information: “_V<Version>.<Revision>“.
Databases can be switched either in X30 Studio or in Easergy Studio with matrix point /Parameters/Con-
fig. parameters/IEC/Switch Config. Bank – execute.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
3 IEC 60870-5-104 software architecture
3.1 Overview
The above figure shows the maximum configuration of the IEC 60870-5-104 software in the communication module. Each functional block represents one program object. The program objects system starter, kernel and device interface are always started, all other objects are optionally available, depending on the configu-ration.
The central communication node of the system is the kernel. All objects are connected to and communicate with each other via the kernel.
The program objects IEC 60870-5-104 server and client are driver programs at the communication module's Ethernet interfaces. They have a special client-server interface to the application programs telecontrol line and master station bus.
The communication module is connected to the device's CPU via the program object device interface.
In order for the program objects to be managed by the kernel, each of them has a unique address.
3.2 Program objects
3.2.1 Kernel
When the system is started, the program objects register themselves and the data types of the telegrams they need to the kernel. During operation, the kernel distributes the telegrams to the program objects that have registered for the corresponding data type.
In addition, the program objects, e.g. the master station bus, register all devices they are connected with to the kernel. Thus, the kernel can send commands via the destination addresses to the addressed objects.
The program objects connected to the kernel communicate by means of telegrams in the internal telegram format as described in section 10.
Telecontrol line 1
Kernel Device
Interface
Telecontrol line 2
Master 1 station bus
Master 2 station bus
Logic
Station interlocking
IEC 60870-5-104 server
IEC 60870-5-104 client 1
Telecontrol line 3
Telecontrol line 4
Telecontrol line 5
IEC 60870-5-104 client 2
System starter
Eth
ern
et
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
3.2.2 Device interface
The device interface manages the communication with the CPU. Thereby, telegrams addressed according to IEC 60870-5-103 from the device are converted into the communication module's internal telegram format. Simultaneously, the required information is selected from the great number of telegrams offered by the de-vice.
The internal telegram format is based on the IEC 60870-5-104 format, so that already at this point, telegrams can be addressed according to the IEC 60870-5-104 customer profile.
The addresses of CPU telegrams consist of IEC 60870-5-103 function type and information number, except for measured values and commands from the protection part, whose addresses consist of matrix points.
In both cases, the address list provided for each device type can be used to identify telegrams.
Besides communication functions, the device interface also provides the following system functions:
• network interface to the Easergy Studio setting software
• interface to the Security Administration Tool (SAT)
• time synchronization via SNTP or IRIG-B
3.2.3 IEC 60870-5-104 telecontrol lines
Together with a channel of the IEC 60870-5-104 server, an IEC 60870-5-104 telecontrol line realizes an IEC 60870-5-104 server interface, that can work either at the station bus or as a SCADA line.
The telecontrol line is responsible for the application layer of the OSI model. It contains a data model for as-signing information and logic functions, in order to carry out simple data manipulations or logical operations.
Telegrams between telecontrol lines and the IEC 60870-5-104 server are exchanged in the IEC 60870-5-104 ASDU format.
3.2.4 IEC 60870-5-104 master station bus and client
These two program objects together realize one IEC 60870-5-104 master that can connect with up to 32 servers. In terms of the OSI model, the master station bus thus operates as application layer and the IEC 60870-5-104 client operates as transport and network layer.
The master station bus contains a data model for each connected server to map the information. In addition, telegrams can be processed through logic functions, e.g. for the generation of group signals.
Telegrams between the master station bus and the IEC 60870-5-104 client are exchanged in the IEC 60870-5-104 ASDU format.
3.2.5 IEC 60870-5-104 server
The IEC 60870-5-104 server operates as transport and network layer of the IEC 60870-5-104 protocol. For this purpose, it manages all TCP/IP sockets and assigns telecontrol lines to it. Thereby several telecontrol lines can work at one socket. The IEC 60870-5-104 server offers 8 channels for the connection of telecontrol lines.
3.2.6 Logic and station interlocking
The logic and station interlocking program objects can process central logic functions. In contrast to the pro-gram objects device interface, telecontrol lines and master station bus, in the logic and station interlocking, logical operations can be cascaded. This allows even complex logic functions to be processed.
For station interlocking, special interlocking functions are implemented.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
4 Engineering
4.1 X30 Studio
4.1.1 Introduction
The program X30 Studio is used to engineer the communication modules of Easergy MiCOM 30 devices for the IEC 60870-5-104 communication protocol, and also to engineer the MiCOM S30 central unit, in which also the IEC 60870-5-101/-103 and IEC 61850 protocols can be applied. X30 Studio is a comprehensive tool for the configuration of devices and systems communicating by means of above protocols.
This document does not contain a detailed description of how to use X30 Studio. Here only the principal pro-cedure and the necessary steps for configuring MiCOM 30 devices with the IEC 60870-5-104 protocol are described, without entering into the details about its use.
4.1.2 Access rights
Software programs for engineering devices and systems mostly have a very large scope of functions, which can make them rather complicated to use. In addition, there are different users who need to fulfill different tasks and who have a different level of knowledge of communication functions.
In order to meet the different user requirements, to simplify the use of the software, and to minimize applica-tion errors, a hierarchical user management has been implemented that offers each user only those func-tions they require for fulfilling their tasks.
There are 3 user levels:
• Operator - lowest access level At this level, program objects can be configured for typical application cases. To use the program, basic knowledge of the functions of program objects, of network technology and of the IEC 60870-5-104 protocol is required.
• Engineer - medium access level At this level, program objects can be adapted to special application cases. To use the program, ad-vanced knowledge of the functions of program objects, of network technology and of the IEC 60870-5-104 protocol is required.
• Expert – highest access level At this level, all parameters are visible. They permit controlling the system behavior of program ob-jects. To use the program, detailed knowledge (at software specialist level) of the functions of pro-gram objects is required. This level is required only in exceptional cases.
Program objects, in particular, are designed to be adapted to as many application cases as possible. For this reason, there is a great variety of sometimes very specific parameters. In this context, access levels are particularly important, because otherwise parameters can appear complicated and difficult to overlook.
Besides parameters, also all other functions in X30 Studio are assigned to specific access levels.
4.2 Engineering steps of an IEC 60870-5-104 project
4.2.1 Profile
Data addresses in the IEC 60870-5-104 protocol consist of the common address of ASDU and the address of the information object. For technological addressing of telegrams, typically addresses are structured into bit fields. The designations and values of those bit fields are used during engineering.
The first step when configuring a project is to define the profile in the project data folder of the project tree. The profile can be selected from the profile catalogue. If the required profile does not exist yet, it needs to be created.
A profile defines the following:
• Structure of the common address of ASDU Definition of the length and designations of the bit fields
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
• Structure of the information object address Definition of the length and designations of the bit fields
• Names of wildcards in typicals Definition of the variable fields in the typicals
• Data model typicals Definition of the device program objects for which data model templates are included in the typical
• Format of data model entry Definition of the appearance of the tables for editing of data models, i.e. configuration of the visibility of columns, the column headers, etc.
4.2.2 Typicals
The first step in engineering a device is to create a typical.
The general principle of X30 Studio projects is the handling of communication systems that have repeating data addresses, e.g. device types, field types, etc. To engineer those systems as effectively as possible, it is appropriate to use those types (hereinafter referred to as "typicals") also during engineering.
A typical in an X30 Studio project contains parts of data models and assignment information for program ob-jects that have wildcards (variables) for specific fields. By replacing those wildcards, instances of the typicals can be created.
The basis for creating a typical in X30 Studio is the device catalogue. This catalogue contains all the infor-mation about Easergy MiCOM 30 series, earlier device series and supported third-party devices, that are of-fered at the communication interfaces.
A typical in X30 Studio is created by dragging and dropping an entry from the device catalogue into the IED typicals section.
After defining the device type, the typical is edited: To this aim, the required information is selected from the total amount of data in the catalogue. In the next step the information targets, the assignment to the single telecontrol lines, the logic etc. are entered.
In all data model parts of the typical, wildcards are entered depending on project requirements.
4.2.3 IEDs
In X30 Studio, an IED is created by instantiating a typical. This is done in two steps: 1. Drag and drop the typical into the 'IED-Fields' list, and 2. drag and drop the appropriate field unit into the 'IEDs' list.
Every created IED tree structure now has branches for parameterization and function, which, however, are still empty. In order to continue working, now the device needs to be configured.
4.2.4 Configuration
When engineering a device, as a first step, it must be defined which program objects are started.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
As a result of the configuration dialogue, the parameter file for the system starter is created, which normally does not need to be further edited. Also, it has been defined which program objects must be parameterized. The program system contains the following system and driver objects:
• system starter,
• kernel,
• IEC 60870-5-104 server,
• IEC 60870-5-104 client.
Normally, those program objects need not be parameterized and their parameters can only be accessed by Engineer or higher-level accounts. Only the following user objects need to be engineered:
• device interface,
• telecontrol lines,
• master station bus,
• logic
• station interlocking.
The configuration consists of one parameter file for each program object and one or several data model files (master station bus).
4.2.5 Parameterization
4.2.5.1 User interface
In X30 Studio, parameters are entered through appropriate input masks. If necessary, help texts provide the user with support.
Only those parameters are visible that correspond to the current or to lower-level user accounts. Also, those parameters are hidden that are not relevant because they correspond to a higher-level setting: For example, in the telecontrol line, parameters 'IP Adresse Client 2 - 8' and 'Modus Redundanzbetrieb' are hidden if pa-rameter 'Protokoll' is set to 'IEC60870-5-104 SBUS'.
The following sections describe parameters for the Operator and Engineer account level.
4.2.5.2 Device interface
Setting group: Ethernet port A/B
Parameter Description
IP-Adresse (IP address)
These parameters describe the subnet at Port A/B. On the network interface a second IP address either inside or outside of the subnet can be assigned. 2. IP-Adresse
(2nd IP address)
Subnetzmaske (Subnet mask)
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Parameter Description
Gatewayadresse (Gateway address)
Address of a gateway to other networks
VLAN1 IP-Adresse (VLAN1 IP address)
IP address of virtual LAN 1
VLAN1 Anzahl Bits Subnetzmaske (VLAN1 subnet mask number of bits)
Subnet mask of virtual LAN 1, beginning at the highest bit number, e.g. 24 bits correspond to the subnet mask 255.255.255.0
VLAN1 ID Unique number to identify virtual LAN 1, 0 - 4094
VLAN1 Priorität (VLAN1 priority)
Priority of virtual LAN 1. The priority can be set from 0 to 7. Priority 7 is the highest.
VLAN1 Gatewayadresse (VLAN1 gateway address)
Address of a gateway in virtual LAN 1 to other networks
VLAN2 IP-Adresse (VLAN2 IP address)
IP address of virtual LAN 2
VLAN2 Anzahl Bits Subnetzmaske (VLAN2 subnet mask number of bits)
Subnet mask of virtual LAN 2, beginning at the highest bit number, e.g. 24 bits correspond to the subnet mask 255.255.255.0
VLAN2 ID Unique number to identify virtual LAN 2, 0 - 4094
VLAN2 Priorität (VLAN2 priority)
Priority of virtual LAN 2. The priority can be set from 0 to 7. Priority 7 is the highest.
VLAN2 Gatewayadresse (VLAN2 gateway address)
Address of a gateway in virtual LAN 2 to other networks
Setting group: Ethernet port C
Parameter Description
IP-Adresse (IP address)
These parameters describe the subnet at Port C. On the network in-terface a second IP address either inside or outside of the subnet can be assigned. 2. IP-Adresse
(2nd IP address)
Subnetzmaske (Subnet mask)
Gatewayadresse (Gateway address)
Address of a gateway to other networks at port C
Setting group: SNTP configuration
Parameter Description
Überwachungszeit Abfrage (Supervision time request)
Within this time interval the requested NTP server must send the re-ply. The supervision time is also the cycle time of the request.
Anzahl der Versuche (Number of time requests)
After the configured number of unsuccessful time requests a mes-sage 'SNTP time request disturbed' is generated
IP-Adresse Server 1 (IP address server 1)
IP address of the first NTP time server
IP-Adresse Server 2 (IP address server 2)
IP address of the alternative NTP time server
Setting group: Services
Parameter Description
Einstellprogramm (Configuration interface)
The setting program Easergy Studio uses TLS encrypted communi-cation services (Transport Layer Security) for the communication with the Ethernet board.
Benutzerverwaltung RBAC (RBAC interface)
The role-based access control (RBAC) for users of P30 devices is managed with the Security Administration Tool (SAT). An interface can be chosen for SAT access.
Zeitsynchronisierung NTP (NTP interface)
This parameter limits the visibility of the port for SNTP time re-quests.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Parameter Description
Systemadministration (System administration)
For the maintenance of the Ethernet board it is necessary to have access to the system services. Those services are used by e.g. MiCOM-Loader and the engineering program X30 Studio.
Setting group: RSTP
Parameter Description
Bridge-Prioriät (Bridge priority)
The switch with the lowest bridge priority will be the root bridge. If the bridge priority is configured equal, the MAC address is used to distinguish the priority.
Maximales Alter (Maximum age)
The maximum age is the maximum number of bridge/switch layers in the network topology. In a ring topology, it must be greater than the number of bridges/switches minus the root bridge. In a star to-pology, it must be greater than the number of hops to get from the root bridge to the furthermost switch. The rule for configuration is: 'Maximum age' > 2 x ('Hello time' + 1s). During the time ‘Maximum age’, the bridges/switches hold their network configuration.
Weiterleit-Verzögerung (Forward delay)
This is the maximum time the switch stays in the 'listening' and 'learning' states before it starts forwarding data telegrams. The rule for configuration is: 2 x ('Forward delay' - 1s) > 'Maximum age'.
Hello-Zeit (Hello time)
The hello time is the cycle time of sending the BDPU (Bridge Proto-col Data Unit).
Setting group: Device
Parameter Description
interne Geräteadresse (Internal device address)
This device address is used by the communication kernel to identify the device. It is not transmitted outside the board and it is not nor-mally necessary to change the default value.
Setting group: MVs and counters
Parameter Description
Zyklus Aktualisierung Messwerte (Cycle time update MVs)
Within this cycle time, the CPU updates the measured values on the communication module. The cycle time may be increased to re-duce the number of transmitted measurement telegrams if the filter functions on the communication module (deadband) are not appli-cable.
Zyklus Aktualisierung Zähler (Cycle time update counters)
Within this cycle time, the CPU updates the energy counter values on the communication module. If energy counters are not used, the cyclic transmission may be switched off by setting the value 65535.
Setting group: Logic
Parameter Description
Init Datenmodell mit "nicht aktuell" (Init data model with 'not topical')
By default, all data points are initialized with the quality descriptor 'invalid'. If this option is chosen, they are initialized with quality de-scriptor 'not topical'.
Berechnung Qualitätskennungen (Calculation of quality descriptor)
In logical operations (AND, OR, NAND, NOR, DYNOR), the quality descriptor can be calculated in two ways: a) OR operation of all inputs b) Special conditions are considered. If in an OR or NOR operation at least one input is logical '1' and valid, then the output will be set valid. If in an AND or NAND operation at least one input is logical '0' and valid, then the output will be set valid.
Zykluszeit AZI-Berechnung (Cycle integrated deadband calcu-lation)
In this cycle, the integrated deadband is calculated by adding the deviation (appropriately signed) from the last value transmitted.
Grenzwert Nullpunktunterdrückung (Threshold value zero suppressing)
If the absolute value to be transmitted is less than the threshold value, then 0 will be transmitted. In the data model, the output sta-tus 'z' must be set for data points to switch on zero forcing.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Parameter Description
Zustandswechsel Setzen Flatter-sperre (Transitions set chatter suppres-sion)
If more transitions than the threshold value occur within the test in-terval, then the data point will be reported with quality 'blocked'. Af-ter this, further reporting is suppressed.
Zustandswechsel Aufhebung Flat-tersperre (Transitions reset chatter suppres-sion)
If less transitions than the threshold value occur within the test inter-val, then chatter suppression will be reset for the data point. The data point will be reported with quality 'not blocked'.
Testintervall Flattersperre (Test interval chatter suppression)
Time interval during which the number of transitions is counted.
Blockierzeit Flattersperre (Blocking time chatter suppression)
After setting a chatter suppression, the data points concerned will be blocked from transmission for the configured time.
Setting group: Operating test
Parameter Description
Logdatei schreiben (Write to log file)
Telegram traffic and processing information is recorded in log files.
Dezimal (Decimal)
The number format in log files is decimal (default: hexadecimal).
Maximale Zeilenzahl je Logdatei (Number of lines in the log file)
When the maximum number of lines in the log file is reached, a new file is started with incremented index in its file name.
Maximale Anzahl Logdateien (Number of log files)
After the maximum number of indexed log files has been written, the index of the next log file restarts at 0, overwriting the oldest file.
4.2.5.3 Telecontrol line
Setting group: Main settings
Parameter Description
Protokoll (Protocol)
The setting 'IEC60870-5-104 SBUS' is used for operation at the sta-tion bus. One client can be connected to the server. The mode 'IEC60870-5-104 server' is used for SCADA lines. Up to 8 clients can be connected in 2 redundancy modes (see setting group 'IEC 60870-5-104 server').
Setting group: IEC 60870-5-104 server
Parameter Description
IP-Socketadresse (IP socket address)
Socket address at which the IEC 60870-5-104 server waits for con-nections with clients. If this address is set to 0.0.0.0, the server will wait at all TCP/IP sockets.
IP-Port (IP port)
The default port number for IEC 60870-5-104 is 2404.
IP-Adresse Client 1 (IP address of client 1)
Address of the client entitled to connect to the server. If this IP ad-dress is set to 0.0.0.0, clients with any address can connect.
IP-Adresse Client 2 (IP address of client 2)
Like IP-Adresse Client 1, available in SCADA mode only
IP-Adresse Client 3 (IP address of client 3)
Like IP-Adresse Client 1, available in SCADA mode only
IP-Adresse Client 4 (IP address of client 4)
Like IP-Adresse Client 1, available in SCADA mode only
IP-Adresse Client 5 (IP address of client 5)
Like IP-Adresse Client 1, available in SCADA mode only
IP-Adresse Client 6 (IP address of client 6)
Like IP-Adresse Client 1, available in SCADA mode only
IP-Adresse Client 7 (IP address of client 7)
Like IP-Adresse Client 1, available in SCADA mode only
IP-Adresse Client 8 (IP address of client 8)
Like IP-Adresse Client 1, available with remote operation only
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Parameter Description
Zeitfenster Empfang Quittung (t1) (Timeout receiving confirmation (t1))
The time after which a confirmation telegram on a data APDU or a test APDU should have been received.
Wartezeit Senden Quittung (t2) (Timeout transmitting confirmation (t2))
The time after which a confirmation telegram has to be transmitted in the case that no data was transmitted.
Ruhezeit Senden Testtelegramm (t3) (Idle time until test telegram (t3))
The time after which test telegrams have to be transmitted in the case of a long idle state.
Nichtquittierte APDU Senden (k) (Num. of non-ack. APDUs transmit (k))
The maximum difference between transmit sequence number and receive sequence number; if this number is reached, no further tele-grams will be transmitted.
Nichtquittierte APDU Empfang (w) (Num. of non-ack. APDUs receive (w))
The maximum difference between receive sequence number and transmit sequence number; if this number is reached, a confirma-tion telegram will be transmitted.
Verzögerungszeit Verbindungsstö-rung (Communication error delay)
After detecting a communication error, this delay gives the client time to perform retries to reconnect the link. During this delay time, FIFO data will be held.
Modus Redundanzbetrieb (Redundancy mode)
Available in SCADA mode only. In mode 'Active and standby links', acc. to IEC 60870-5-104, one link is active, i.e. data will be transmitted over this link. All other links are in passive mode. No data will be sent over those links. To control which link is active, the master station uses 'Start and stop data transmission'. Standby links are in state 'Stop data transmis-sion'. In mode 'Multiple active links', data will be sent simultaneously over all links. The master station decides from which link the data will be processed and over which link commands will be sent.
Setting group: Application layer
Parameter Description
Gemeinsame Adresse der ASDU (Common address of ASDU)
This address is used if the 'Common address of ASDU' field in the data model is empty.
Packungsverfahren Anwenderdaten (Methods for packing user data)
The following methods can be used: 1. Ausgeschaltet (Switched off) Only one information object is packed into the telegram. 2. Packung von Informationsobjekten (Sequence of infor-mation objects) Two or more information objects are packed into the telegram. 3. Packung von Informationselementen (sequenzielle Packung) (Sequence of information elements) Two or more information elements are packed into the telegram. The information objects must have consecutive addresses. The ad-dresses must be sorted in ascending order. 4. Beide Packungsverfahren (Combined method) ASDUs without time tag are packed as a sequence of information elements (e.g. response telegrams in general interrogation and cy-clic telegrams). ASDUs with time tag are packed as a sequence of information objects. For both methods, the following conditions must be fulfilled: 1. The type identification is suitable for packed messages. 2. Information objects resp. information elements must have identi-cal type identification, cause of transmission and common address of ASDU.
Maximale Länge der Anwenderda-ten (Maximum length of user data)
In monitoring direction – if possible – several information objects are packed into one telegram. The telegram buffer is filled with in-formation objects up to the maximum length of user data.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Parameter Description
ASDU 70 (Initialisierungsende) (ASDU 70 (End of initialization))
ASDU 70 is used according to standard.
Setting group: General protocol functions
Parameter Description
FIFO-Daten halten (Hold FIFO data)
If this checkbox is activated, the data will be stored in the FIFO queues if the connection is disturbed.
Setting group: Cyclic data transmission
Parameter Description
Zykluszeit (Cycle time)
When this timer expires, all data points marked for cyclic transmis-sion will be transmitted. If the cycle time is set to 0, the function is disabled.
Setting group: Station interrogation
Parameter Description
GA an Informationsquellen (GI to sources of information)
If this option is set, and if a general interrogation is received on the SCADA line, also a general interrogation is sent to the devices where the information for the SCADA line comes from.
Setting group: Clock synchronization
Parameter Description
UTC auf der Kommunikationslinie (UTC on SCADA)
UTC is used on SCADA.
Differenzzeit Zeitzone (Offset time zone)
The offset time is used to make a time zone based on UTC on SCADA. It is also possible to add a time offset to the local time. In this case, the switching of summertime is performed on SCADA.
Sommerzeit-Bit (Summer time bit)
The summer time bit is used.
Setting group: Command transmission
Parameter Description
Befehlsprozedur (Command procedure SCADA)
The configured command procedure is expected as default setting by the IEC 60870-5-104 interface. Internally, 'Direct execute' is the default setting.
Beendigung der Aktivierung (Signal control 'ACTTERM')
If this checkbox is activated, the ACTTERM confirmation will be used with commands on the telecontrol line. This means that de-vices have to transmit ACTTERM with every command they exe-cute. When the timer (see below) expires and no ACTTERM is re-ceived, the telecontrol software has to generate a negative ACT-TERM. In the case of commands for protective functions, the ACT-TERM confirmation must be defined in the telecontrol data model.
Maximales Alter von Befehlen (Maximum age of commands)
This parameter is used for commands with time tag (IEC 60870-5-104, ASDU 58...64). If a command telegram is too old, it is dis-carded without any confirmation.
Anzahl Befehlsprozeduren (Number of command procedures)
This parameter defines the number of command procedures that can be executed at the same time. If the maximum number of pro-cedures is exceeded, further commands are discarded and a nega-tive confirmation is transmitted. If a command generates two or more internal commands, a command procedure for every internal command is started.
Überwachungszeit Befehl Ausfüh-ren (Timeout execute command)
The time interval starts after receiving the select command. The peer station must send the execute command within this time.
Überwachungszeit Befehlsquit-tungen (Timeout command confirmation)
Interval between transmitting the command to the device and re-ceiving the last confirmation from the device. When this time inter-val expires, a negative confirmation is transmitted (ACTCON or ACTTERM).
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Parameter Description
Verzögerung Beendigung der Akti-vierung (Delay of Activation Termination)
This delay ensures that the confirmation ACTTERM is sent after the return info if this is not provided by the command target.
1 aus n - Kontrolle (Check control uniqueness)
If activated, it is checked whether only one command runs at a time. Further commands will not be executed and rejected with a nega-tive confirmation.
Geräteadresse Befehl läuft ext. (Device address order running ext.)
With this message, it is possible to include external signals into the check of control uniqueness.
Datenpunktdresse Befehl läuft ext. (Datapoint address order running ext.)
With this message, it is possible to include external signals into the check of control uniqueness.
Setting group: Transmission of integrated totals
Parameter Description
Betriebsart (Mode of transmission)
The following modes are available: 'Local freeze with spontaneous transfer' and 'Local freeze with counter interrogation'.
Setting group: Background scan
Parameter Description
Zykluszeit (Cycle time)
When this timer expires, one data point will be transmitted. This function is disabled if the cycle time is set to 0.
Setting group: Transmission in reverse direction
Parameter Description
Virtuelle Geräteadresse Partner-station (Virtual device address of peer sta-tion)
With this device address (virtual address), the peer station is man-aged by the kernel. The parameterized address must be unique within the system. If the device address is set to a value not equal 0, the device will be registered to the kernel so that commands can be sent over the virtual device to the peer station.
GA nach Verbindungsaufbau (General interrogation on link OK)
If this option is selected, a global general interrogation command is sent to the peer station when the link changes status from disturbed to connected.
Setting group: Data model
Parameter Description
ASDU- und Objektadresse eindeu-tig (ASDU and object adress unique)
If this checkbox is selected, the uniqueness of the combination of common address of ASDU and address of data object are checked. Otherwise using the same combination of addresses with a different type identification is tolerated.
Setting group: Logic
See the same setting group in section 4.2.5.2, Device interface.
Setting group: Operating test
See the same setting group in section 4.2.5.2, Device interface.
4.2.5.4 IEC 60870-5-104 master station bus
Setting group: Master station bus IEC104
Parameter Description
Direktmodus (Direct mode)
In direct mode, the IEC 60870-5-104 master station bus works with-out data models. In this mode, the transmission of signals in control direction is not possible because the used data types are not regis-tered to and assigned to by the kernel.
Interne Adresse 1. Gerät (Internal address of the first device)
Connected servers with consecutive addresses are allocated, start-ing at this internal device address.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Setting group: Table of connected servers
Column Description
Gerätename (Device name)
The device name is not evaluated. It can be freely allocated with a maximum length of 127 characters and it is used for documentation.
IP-Adresse (IP address)
IP address of the connected servers.
Datenmodelldatei (Data model file)
Here the name of the data model file of the connected server is en-tered without path specification. The file name is displayed only. For handling data models, X30 Studio is used.
Setting group: Master station bus IEC104
Parameter Description
Überwachungszeit Verbindungsauf-bau (t0) (Timeout connect (t0))
Within this time interval the server being contacted must reply to the connection request.
Zeitfenster Empfang Quittung (t1) (Timeout receiving confirmation (t1))
The time after which a confirmation telegram on a data APDU or a test APDU should have been received.
Wartezeit Senden Quittung (t2) (Timeout transmitting confirmation (t2))
After this time, unconfirmed receive telegrams are confirmed if no data is to be sent.
Ruhezeit Senden Testtelegramm (t3) (Idle time until test telegram (t3))
After this idle time, a test telegram is sent if no data are to be sent.
Nichtquittierte APDU Senden (k) (Num. of non-ack. APDUs transmit (k))
The maximum difference between transmit sequence number and receive sequence number; if this number is reached, no further tele-grams will be transmitted.
Nichtquittierte APDU Empfang (w) (Num. of non-ack. APDUs receive (w))
The maximum difference between receive sequence number and transmit sequence number; if this number is reached, a confirma-tion telegram will be transmitted.
Anzahl der Verbindungsversuche (Number of attempts on errors)
If this number is reached, the link is marked as disturbed.
Setting group: Operating test
See the same setting group in section 4.2.5.2, Device interface.
4.2.5.5 Logic / station interlocking
Setting group: Main settings
Parameter Description
Geräteadresse des 'Virtual Logic Device' (VLD) (Device address of Virtual Logic Device (VLD))
At this virtual device address, logic functions will be registered to and handled by the kernel. This means that all signal outputs and command inputs should be engineered with this device address.
Setting group: Station interlocking (only effective in station interlocking)
Parameter Description
Zeitüberwachung Steuerprozedur (Timeout control procedure)
The overall time of the control procedure from the select command until receiving the confirmation of activation for the execute com-mand is supervised. If the procedure 'Select and execute' is used on the telecontrol line, this timeout must be longer than the timeout for the execute command after the select.
Überwachungszeit erweiterte Ver-riegelungsfunktion (Timeout time extended locking function)
This supervision time is used by the extended locking function 'elock' to supervise the confirmation telegram after sending the query telegram.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Setting group: Data model
Parameter Description
ASDU- und Objektadresse eindeu-tig (ASDU and object adress unique)
If this checkbox is selected, the uniqueness of the combination of common address of ASDU and address of data object is checked. Otherwise using the same combination of addresses with a different type identification is tolerated.
Setting group: Logic
See the same setting group in section 4.2.5.2, Device interface.
Setting group: Command transmission
See the same setting group in section 4.2.5.3, Telecontrol line.
Setting group: Operating test
See the same setting group in section 4.2.5.2, Device interface.
4.2.5.6 IEC 60870-5-104 server
Setting group: Operating test
Parameter Description
Logdatei schreiben (Write to log file)
Telegram traffic and processing information is recorded in log files.
Dezimal (Decimal)
The number format in log files is decimal (default: hexadecimal).
Schalter Logfunktion Kanal 0 (Switch logging channel 0)
Enabling/disabling of logging channel 0
Schalter Logfunktion Kanal 1 (Switch logging channel 1)
Enabling/disabling of logging channel 1
Schalter Logfunktion Kanal 2 (Switch logging channel 2)
Enabling/disabling of logging channel 2
Schalter Logfunktion Kanal 3 (Switch logging channel 3)
Enabling/disabling of logging channel 3
Schalter Logfunktion Kanal 4 (Switch logging channel 4)
Enabling/disabling of logging channel 4
Schalter Logfunktion Kanal 5 (Switch logging channel 5)
Enabling/disabling of logging channel 5
Schalter Logfunktion Kanal 6 (Switch logging channel 6)
Enabling/disabling of logging channel 6
Schalter Logfunktion Kanal 7 (Switch logging channel 7)
Enabling/disabling of logging channel 7
Maximale Zeilenzahl je Logdatei (Number of lines in the log file)
When the maximum number of lines in the log file is reached, a new file is started with incremented index in its file name.
Maximale Anzahl Logdateien (Number of log files)
After the maximum number of indexed log files has been written, the index of the next log file restarts at 0, overwriting the oldest file.
4.2.5.7 IEC 60870-5-104 client.
Setting group: Operating test
See the same setting group in section 4.2.5.2, Device interface.
4.2.5.8 Communication kernel
Setting group: Operating test
See the same setting group in section 4.2.5.2, Device interface.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
4.2.5.9 Functions
Here the data model files of the program objects can be found, which were generated from typicals by re-placing wildcards. Data models can be opened for editing, e.g. for adding data points not provided in the typi-cals. However, post-editing of data models should remain an exception. The aim is to generate all data points from typicals.
4.2.5.10 Generating and transmitting a database
The database generating function can be found in the context-sensitive menu of the IEDs, option 'Datenüber-tragung' ('Data transmission'). After confirming with the button 'DB Erzeugen' ('Generate DB') and further confirmation with the button 'Erzeugen' ('Generate'), the user is prompted to enter the version number and a comment. After confirming the input, a new database file will be generated in the tree structure.
The user can then select this database for transmission. It is saved in the device as an inactive (standby) da-tabase. In order to activate the loaded database, databases must be switched. After restarting the Ethernet board in the device and after the connection has been reestablished, the updated database configuration is displayed.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
5 Data model and logic library
5.1 Approach
The data model and logic library was developed especially for the realization of communication functions. Although in most cases, simple logical operations are sufficient, e.g. group signals through logical OR opera-tion, sometimes also specialized functions are required in order to comply with standards.
Frequently used functions, like the assignment of telegrams, are easily possible, but so are the more com-plex logical operations, e.g. in application cases of station interlocking or logic.
Compared to classical programmable logic controllers, processing in this approach is realized in a different way. The processing of logic functions occurs event-driven, i.e. inputs and outputs of the functions are time-tagged telegrams generated at changes of state. There is no cyclic processing of logic functions with a de-fined cycle time. As a result, signal processing is typically very fast and the logic library does not cause a constantly high processor load. Moreover, it is possible to use the data model and logic library in multiple program objects or instances of program objects without overloading the system.
5.2 Integration into program objects
5.2.1 Program objects with logic library
The data model and logic library is integrated into all colored program objects of the system configuration:
This architecture allows to apply logic functions very effectively:
• A logic function in the device interface is effective on all telecontrol lines. However, the same func-tion can also be used in one telecontrol line if it is required selectively.
• By distributing to program objects, logic functions can be cascaded.
Telecontrol line 1
Kernel Device
interface
Telecontrol line 2
Master 1 station bus
Master 2 station bus
Logic
Station interlocking
IEC 60870-5-104 server
IEC 60870-5-104 client 1
Telecontrol line 3
Telecontrol line 4
Telecontrol line 5
IEC 60870-5-104 client 2
Eth
ern
et
System starter
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
5.2.2 Implementation differences
The logic library is integrated into the program objects illustrated in the above graphic. However, there are differences in the availability of the functions. The following table shows the functions and their availability depending on their implementation:
Function Logic SI Telec. Line
SBUS master
Device interface
Time functions (ton, toff, cycsup, …) x x x - x
Cyclic transmission, background scan
- - x - -
Filtering functions (deadband, chatter sup-pression, …)
x x x - x
Command procedure management, checking of control uniqueness
x x x - -
Interlocking (lock, elock) - x - - -
Chapter 6 describes, for which objects the respective function is available.
5.3 Format of data model files
5.3.1 Basic structure of data model files
A line in the data model consists of fields, separated by semicolons (Microsoft Excel® ‘.csv‘ format).
Numbers in data models are displayed in decimal format by default, hexadecimal numbers are marked by a preceding “0x“. All numbers are integers, only the parameters of input and output functions can have a frac-tional part, e.g. “3.14“, “-1.55“, etc.
Fields marked as optional may remain empty. Furthermore, after the second parameter field of the function, the line evaluation ends. Behind this, comments may be entered.
In principle, a data model line describes the allocation of an input to an output of the data model. Processing functions can be defined optionally.
Direction of transmission
The first field in the data model defines the allocation to the data model:
‘M‘ - data model entry in monitoring direction ‘C‘ - data model entry in control direction ‘I‘ - data model entry logic data model ‘P‘ - polygon definition ‘#‘ - comment line
This field also defines if, depending on the application, the line is to be processed from the right to the left or vice versa and hence defines the position of input and output information.
Data type, type identification
This field defines the type of input and output telegrams.
Address fields
Depending on the application, data model files vary in length and designation of address field designation. The structures of the address fields for input and output described here are standard format. In X30 Studio they can be overlayed by a customer-specific address profile, so that for the user, only the address fields and identifiers defined in the profile are visible.
Bit field
Here the following optional information can be given: start bit in the input telegram, length of the bit field and the target bit in the output telegram, separated by blanks. The bits are counted in the order of arithmetic sig-nificance, starting at 0 from the right.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Status, functions, and parameter
The information in these fields is optional. If the fields remain empty, the data model line is processed as per default. The positions of input and output status, functions and parameters depend on the application and direction information.
Group
Group within the general interrogation or counter group.
5.3.2 Data model file for device interface
The left-hand part of the line shows the information at device end, the right-hand part shows the internal in-formation at the communication kernel.
Field Optional Description
D no Direction of transmission 'M' = data model entry in monitoring direction 'C' = data model entry in control direction
DT no Data type (device end)
DEV no Address (device end) always to be set at 1
TYP no Function type (in certain cases also matrix point address X)
INF no Information number (in certain cases also matrix point address Y)
STAT yes Status Information (device end) Entry in monitoring direction: input status Entry in control direction: output status
FKT yes Processing function (device end) Entry in monitoring direction: input function Entry in control direction: output function
PAR yes Parameters for function (device end) Entry in monitoring direction: parameter for input function Entry in control direction: parameter for output function
ST_LN_ZI yes Bit field
DT no Internal data type
DEV yes Internal device address
DPA4 - 0 no Internal data point address
GR yes Group - not used
STAT yes Internal status information Entry in monitoring direction: output status Entry in control direction: input status
FKT yes Internal processing function Entry in monitoring direction: output function Entry in control direction: input function
PAR yes Parameters for internal function Entry in monitoring direction: parameter for output function Entry in control direction: parameter for intput function
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
5.3.3 Data model file for telecontrol lines and master station bus
The left-hand part of the line shows the internal information at the communication kernel, the right-hand part shows the information at the IEC 60870-5-104 interface.
The IEC 60870-5-104 master station bus contains a data model file for each connected server.
Field Op-tional
Description
D no Direction of transmission 'M' = data model entry in monitoring direction 'C' = data model entry in control direction
DT no Internal data type
DEV no Internal device address
DPA4 - 0 no Internal data point address
STAT yes Internal status information Telecontrol line: Entry in monitoring direction: input status
Entry in control direction: output status
Master station bus: Entry in monitoring direction: output status Entry in control direction: input status
FKT yes Internal processing function Telecontrol line: Entry in monitoring direction: input function
Entry in control direction: output function
Master station bus: Entry in monitoring direction: output function Entry in control direction: input function
PAR yes Parameters for internal function Telecontrol line: Entry in monitoring direction: parameter for input function
Entry in control direction: parameter for output function
Master station bus: Entry in monitoring direction: parameter for output function Entry in control direction: parameter for input function
ST_LN_ZI yes Bit field
TK no IEC 60870-5-104 type identification
ASDU1 - 0 yes IEC 60870-5-104 common address of asdu OBJ2 - 0 no IEC 60870-5-104 information object address
GR yes Group
STAT yes IEC 60870-5-104 status information Telecontrol line: Entry in monitoring direction: output status
Entry in control direction: input status
Master station bus: Entry in monitoring direction: input status Entry in control direction: output status
FKT yes IEC 60870-5-104 processing function Telecontrol line: Entry in monitoring direction: output function
Entry in control direction: input function
Master station bus: Entry in monitoring direction: input function Entry in control direction: output function
PAR yes IEC 60870-5-104 parameters for processing functions
Telecontrol line: Entry in monitoring direction: parameter for output function Entry in control direction: parameter for input function
Master station bus: Entry in monitoring direction: parameter for input function Entry in control direction: parameter for output function
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
5.3.4 Data model file for logic / station interlocking
The left-hand part of the line shows the information of the input data model, the right-hand part shows the information of the output data model.
Field Op-tional
Description
D no Direction of transmission ‘I‘ – Identifier for input information
DT no Data type of input telegram
DEV no Device address of input telegram
DPA4…0 no Data point address of input telegram
STAT yes Status of input processing
FKT yes Processing function for input
PAR yes Parameter for input function
ST_LN_ZI yes Bit field
DT no Data type of output telegram
DEV no device address of output telegram
DPA4..0 no Data point address of output telegram
GR yes Group (not used)
STAT yes Status of output processing
FKT yes Processing function for output
PAR yes Parameter for output function
5.4 Processing data model files
5.4.1 Device interface, telecontrol lines, and master
The following description refers to telecontrol lines. For the IEC 60870-5-104 master station bus, the monitor-ing / control direction flow is reversed.
From the data model file read at program start, two separate data models are generated. They are managed by two instances of the logic library:
• data model and processing in monitoring direction
• data model and processing in control direction
Telegrams from the kernel are processed via the data model in monitoring direction. Output telegrams are converted into the IEC 60870-5-104 format and sent via the IEC 60870-5-104 server to the network inter-face.
In control direction, first telegrams are converted into the internal telegram format. Then they are processed via the data model. The output telegrams are sent to the kernel.
Hence within the telecontrol line, cascading logical operations is not possible.
DMD and logic control direction
DMD and logic monitoring direction
Kernel Telegram conversion
IEC 104 server
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
5.4.2 Logic / station interlocking
For the application case of logic / station interlocking, there is only one data model. The following graphic shows the communication mechanisms between logic and kernel.
An input telegram is received from the kernel, it is processed, and the generated output telegrams are sent to the kernel.
The kernel distributes the telegrams to all objects having registered for the corresponding data type, also back to the logic. Hence even without special engineering, cascading logical operations is possible.
If an output in the data model is marked with status flag 'm' (“memory”), the generated output telegram is not sent to the kernel but directed internally to input processing. Thus, cascaded logical operations are pro-cessed with minimal delay.
To map the output data points of the logic and their management by the kernel, a virtual logical device is de-fined. Thus, the logic / station interlocking consists of 2 parts, each with their own unique device address:
1. the logic / Interlocking object for coupling to the kernel, and 2. the virtual logic device (VLD), the actual logic device.
Seen from the kernel, the VLD is a remote device that can be reached via the logic object – similar to a field unit coupled via the IEC 60870-5-104 master:
One logic / station interlocking object manages only one VLD.
The station interlocking is realized by a second start of the logic with other parameters. Object addresses and default addresses of the virtual logic devices are defined as follows:
Object Object address VLD address
Logic 5 56
Station interlocking 6 57
Processing via memory
Logic / station interlocking
Logic object
Virtual logic device
Kernel
Kernel
Data model and logic functions
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
5.5 Telegram processing
A line in the data model is processed as shown in the following graphic:
If a telegram is received by input processing and the address is found in the data model, an input-related en-gineerable function is called, carrying out conversions, arithmetic operations, etc.
Certain functions need further information to fulfill their tasks. This information is provided by parameters (e.g. scaling factor). Input status information can also influence processing.
If no input function is defined, by default
• telegram quality descriptors are copied into the new quality descriptors,
• telegram data are copied and converted implicitly into the new data,
• the telegram time tag is copied into the new tag.
After that, an optional output function is called to carry out special treatments like threshold processing, logic operations, etc. and to update the data model. The output function can access status information and can use one parameter (e.g. threshold value).
If no output function is defined, by default
• data model quality descriptors are compared against the new quality descriptors,
• data model data are compared against the new data,
• data model data, quality descriptors and the time tag are updated,
• if data or quality descriptors are changed, an output telegram is created.
All processing, whether via input or output functions or via implicit conversion, depends on the input and out-put data format. For commands and counters, in spontaneous transfer mode, an output telegram is gener-ated for each input telegram.
The output status ‘q‘ – quiet allows to suppress the generation of spontaneous telegrams. With status ‘f‘ – force an output telegram is always generated as a rule.
Multiple entries in the data model
1. One input can be linked to multiple outputs by inserting it multiple times into the data model.
2. Multiple inputs can be linked to one output by inserting the same output address and the same type identification / data type. In doing so, the same output function (bitstring, group signal, etc.) must be defined in all lines of the logical operation.
Output telegram
Output-related
function
Data model
Status information
Parameter
Input-related
function
Input telegram
Status information
Parameter
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6 Functions of the logic library
6.1 Data formats
Processing of data within the logic is based at defined data formats.
During runtime of the logic, when processing a telegram, first the data formats of input and output in the data model are determined. On that basis, the logic functions can then be processed.
The following table provides an overview of the data formats supported and the related data types/type iden-tifications in the internal telegram interface and/or in the IEC 60870-5-104 standard.
Short form Data format long form DT internal
TI IEC 104
Description
SPI Single-point information 30
1 30
Single-point information Single-point information with time tag
DPI Double-point infor-mation
31
3 31
Double-point information Double-point information with time tag
VTI Value with transient state indication
32
5 32
Step position information Step position information with time tag
SCO Single command 45
45 58
Single command Single command with time tag
DCO Double command 46
46 59
Double command Double command with time tag
RCO Regulating step com-mand
47
47 60
Regulating step command Regulating step command with time tag
BS8 Bitstring of 8 bits 70 100 101
70 100 101
End of initialization General interrogation Counter read command
BS16 Bitstring of 16 bits 104 104 Test command
BS32 Bitstring of 32 bits 33
51
7 33 51 64
Bitstring of 32 bits Bitstring of 32 bits with time tag Bitstring command of 32 bits Bitstring command of 32 bits with time tag
INT16 Integer value of 16 bits 9 11 21 34 35
Measured value, normalized value Measured value, scaled value Measured value, normalized value without quality descriptor Measured value, normalized value with time tag Measured value, scaled value with time tag
INT32 Integer value of 32 bits 34 35
Measured value, normalized value Measured value, scaled value
FP32 Floating point value of 32 bits
36 36 Measured value, short floating point value with time tag
BCR32 Binary counter of 32 bits
37
15 37
Counter Counter with time tag
INT16BS8 Integer value of 16 bits with bitstring of 8 bits
48 61 49 62
Set point command, normalized value Set point command, normalized value with time tag Set point command, scaled value Set point command, scaled value with time tag
INT32BS8 Integer value of 32 bits with bitstring of 8 bits
48 49
Set point value, normalized value with time tag Set point command, scaled value with time tag
FP32BS8 Floating point value of 32 bits with bitstring of 8 bits
50
50 63
Set point command, short floating point value Set point command, short floating point value with time tag
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.2 Implicit conversion
Implicit format conversion is applied if no input function and no bit field have been specified. Please note the following particularities:
• Binary information When converting binary information (DPI) into SPI, bit 1 is assigned to bit 0. Thus, a faulty state is signaled by SPI=1 and an intermediate state is signaled by SPI=0.
• Analogue information If during conversion of the greater integer format, its value exceeds the maximum value of the smaller integer format, the overflow bit is set.
• Integer floating point During the conversion of 32 bit integer values into floating point values and vice versa, a loss of ac-curacy may occur.
The following table shows the converting possibilities between the different data formats:
Output
SP
I
DP
I
VT
I
SC
O
DC
O
RC
O
BS
8
BS
16
BS
32
INT
16
INT
32
FP
32
BC
R3
2
INT
16
BS
8
NT
32
BS
8
FP
32B
S8
Input
SPI x x x x x
DPI x x x x x
VTI x x x x
SCO x x x x x
DCO x x x x x
RCO x x x x x
BS8 x
BS16 x
BS32 x
INT16 x x x x x
INT32 x x x x x
FP32 x x x x x
BCR32 x x x
INT16BS8 x x x x x x
INT32BS8 x x x x x x
FP32BS8 x x x x x x
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 0 2 31 1 128 0 0 2 SPI->DPI
M 31 60 0 0 0 1 1 30 1 128 0 1 1 DPI->SPI
M 32 60 0 0 0 2 1 32 1 128 0 2 1 VTI->VTI
M 32 60 0 0 0 5 5 34 1 128 0 5 5 VTI->INT16
C 30 60 0 0 0 3 1 45 1 128 0 2 2 SCO->SPI
C 31 60 0 0 0 3 2 45 1 128 0 3 2 SCO->DPI
C 46 60 0 0 0 3 4 45 1 128 0 3 4 SCO->DCO
C 30 60 0 0 0 4 1 46 1 128 0 3 1 DCO->SPI
C 31 60 0 0 0 4 2 46 1 128 0 4 2 DCO->DPI
M 34 60 0 0 0 5 5 36 1 128 0 5 5 INT32->FP32
M 37 60 0 0 0 5 11 35 1 128 0 5 11 BCR32->INT16
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.3 Bit field assignment
Bit fields can be specified either with or without input and output functions. If no input function is defined, the relevant bit field is copied from the input data and inserted into the target position of the output telegram.
If an input function (e.g. 'not') is defined, the copied bit field is used as input variable for the function.
If a bit field has been specified, in contrast to implicit format conversion, the compatibility of input and output formats is not checked. Any combinations of data formats are allowed.
Unlike implicit format conversion, where, for example, qualifiers are also copied, here the bit field only is cop-ied. Its limits are checked depending on the input and output format. A data format conversion, like implicit conversion, does not take place.
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 33 60 0 0 0 248 112 8 2 0 31 1 0 60 248 128 Sig./meas.block
M 33 60 0 0 0 248 112 10 2 0 31 1 0 60 248 129 Command block
M 33 60 0 0 0 248 112 12 2 0 31 1 0 60 248 130 Blocked/faulty
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4 Input-related functions
6.4.1 Overview
Logic:
not - Bitwise negation
Arithmetic:
add - Addition of constant value sub - Subtraction of constant value mult - Multiplication with constant value div - Division by constant value sqrt - Square root scal - Polygon scaling
Comparison:
cmpeq - Result is true in case of equality cmpne - Result is true in case of inequality cmpgt - Result is true in case of greater than cmpge - Result is true in case of greater than or equal to cmplt - Result is true in case of less than cmple - Result is true in case of less than or equal to isdef - Result is true in case of defined switch position istra - Result is true in case of undefined switch position ifeq - Output telegram in case of equality ifne, ifneq - Output telegram in case of inequality ifgt - Output telegram in case of greater than ifge - Output telegram in case of greater than or equal to iflt - Output telegram in case of less than ifle - Output telegram in case of less than or equal to iftc - Output telegram in case of cause of transmission equal to ifntc - Output telegram in case of cause of transmission unequal to
Quality descriptors:
isgood - Result is true if no quality descriptor is set isbad - Result is true if quality descriptor is set isiv - Result is true if 'invalid' is set isnt - Result is true if 'not topical' is set isbl - Result is true if 'blocked' is set issb - Result is true if 'substituted' is set isov - Result is true if 'overflow' is set
Timing:
ton - Switch-on delay toff - Switch-off delay tonoff - Switch-on and switch-off delay timp - Impulse (monoflop) timer - Timer cycsup - Cycle supervision
Switch:
sel, case, deflt - Inputs of the switch function
Invalid control:
sig, con - Inputs of the invalid control function
D flip-flop
set, res, dat, clk - Inputs of the D flip-flop
Interlocking:
cmd, req, enon, enoff, send, conf
- Inputs of the interlocking function
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.2 Negation - 'not'
Function: Negation of binary data and bit fields
Availability: Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats:
Output
SP
I
DP
I
SC
O
DC
O
RC
O
BS
8
BS
16
BS
32
Input
SPI x x x x x
DPI x x x x x
SCO x x x x x
DCO x x x x x
RCO x x x x x
BS8 x
BS16 x
BS32 x
Bit field: Applicable
Description: Bitwise negation of data field or bit field
Application: Negation of binary data formats or bit fields
Particularities: The data field is negated. Qualifiers, quality descriptors, etc. are copied.
Examples (telecontrol line):
The negation function can be used for binary data formats together with default conversions.
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 160 18 not 30 1 0 134 160 18 Dev ice off-line
M 33 60 0 0 0 248 1 1 2 not 8 2 0 31 1 0 134 248 128 Bit field negation
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.3 Arithmetic operations - 'add', 'sub', 'mult', 'div', 'sqrt'
Function: Arithmetic operations with constant operand
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Operand, exception: function “sqrt“ has no parameter
Status: No particular status information
Data formats:
Output
V
TI
INT
16
INT
32
FP
32
BC
R3
2
INT
16
BS
8
INT
32
BS
8
FP
32B
S8
Input
VTI x x x x
INT16 x x x x x
INT32 x x x x x
FP32 x x x x x
BCR32 x x x
INT16BS8 x x x x x x
INT32BS8 x x x x x x
FP32BS8 x x x x x x
Bit field: Applicable
Description: Input data are arithmetically combined by the following parameters:
add - addition sub - subtraction mult - multiplication div - division sqrt - square root
Application: Scaling of measured values, curve offset
Particularities: The bit field is calculated after the arithmetic operation.
Examples (telecontrol line):
Scaling of floating point value 0 to 1 to normalized value with 240% nominal value = +/-4096
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 36 60 12 34 0 248 50 mult 1706 34 12 34 0 248 50 CurrentI1norm.
M 36 60 12 34 0 248 51 mult 1706 34 12 34 0 248 51 CurrentI2norm.
M 36 60 12 34 0 248 52 mult 1706 34 12 34 0 248 52 CurrentI3norm.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.4 Polygon scaling - 'scal'
Function: Polygon scaling of analogue values
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Polygon reference number
Status: No particular status information
Data formats:
Output
V
TI
INT
16
INT
32
FP
32
BC
R3
2
INT
16
BS
8
INT
32
BS
8
FP
32B
S8
Input
VTI x x x x
INT16 x x x x x
INT32 x x x x x
FP32 x x x x x
BCR32 x x x
INT16BS8 x x x x x x
INT32BS8 x x x x x x
FP32BS8 x x x x x x
Bit field: Not applicable
Data model: Polygon definition
1. Direction identifier = ‘P‘ 2. Polygon reference number 3. Number of pairs of interpolation points 4. Pairs of interpolation points x; y; with x values sorted in ascending order
Polygon reference
A polygon must be defined before it can be used. This reference is given by the pa-rameter of the function 'scal'.
Description: Calculation of the function value from the input value and the corresponding polygon curve. If the input value lies outside the polygon curve, the quality of the output is set to 'overflow'.
Particularities: The bit field is calculated after the arithmetic operation.
Application: Scaling of measured values
Examples:
P 1 2 0 0 32767 32767
P 2 6 -32767 -32767 -1000 -500 -500 -500 500 500 1000 500 32767 32767
P 3 7 -32767 32767 -1000 500 500 500 0 0 500 500 1000 500 32767 32767
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 34 60 0 0 0 160 1 scal 1 34 1 128 135 160 1
M 34 60 0 0 0 160 2 scal 2 34 1 128 135 160 2
M 34 60 0 0 0 160 3 scal 3 34 1 128 135 160 3
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.5 Comparing functions - 'ifeq', 'ifne', 'ifneq', 'ifgt', 'iflt', 'iftc', 'ifntc'
Function: Generation of an output telegram depending on the result of comparing operation Availability:
Logic SI Line Master Device
x x x x x
Parameter: Comparison value
Status: No particular status information
Data formats: Input: all data formats Output: command data formats
Bit field: Applicable
Description: An output telegram is created only if the following conditions are fulfilled:
ifeq - Test data for equality ifne, ifneq - Test data for inequality ifgt - Test data for greater than ifge - Test data for greater than or equal to iflt - Test data for less than ifle - Test data for less than or equal to iftc - Test cause of transmission for equality ifntc - Test cause of transmission for inequality
The state in the data model is updated in any case.
Application: With output function 'set', for instance, depending on the data content, a command can be converted into two alternative commands and assigned to two different ad-dresses. Also converting two commands into one command is possible. With output function 'settc', for instance, depending on the cause of transmission, a command confirmation can be derived from the return info. With function 'ifneq 0', the intermediate state in control state messages can be sup-pressed.
Particularities: If the input function is a comparing function, outputs with the same address can be specified several times in the data model. They are created within the data model several times and reported in general interrogations several times. For this reason, the usage of identical output addresses should be limited to commands and com-mand confirmations.
Examples (telecontrol line):
Conversion of one regulating step command into two single commands, and conversion of two single com-mands into one regulating step command
Suppressing of intermediate state in control state message
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
C 45 60 0 0 0 242 100 set 1 47 1 128 134 242 65 ifeq 1 'Low er' command
C 45 60 0 0 0 242 101 set 1 47 1 128 134 242 65 ifeq 2 'Higher' command
C 47 60 0 0 0 242 200 set 1 45 1 128 134 242 66 ifeq 1 'Low er' command
C 47 60 0 0 0 242 200 set 2 45 1 128 134 242 67 ifeq 1 'Higher' command
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 31 60 0 0 0 242 1 ifneq 0 31 1 128 60 242 1 CB status
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.6 Comparing functions - 'cmpeq', 'cmpne', 'cmpgt', 'cmpge', 'cmplt', 'cmple'
Function: Setting of an output value depending on the result of the comparing operation
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Comparison value
Status: No particular status information
Data formats: Input: all data formats Output: SPI or DPI
Bit field: Applicable
Description: The result of the comparing operation is true if the following conditions are fulfilled:
cmpeq equality cmpne inequality cmpgt greater than cmpge greater than or equal to cmplt less than cmple less than
The result is encoded as SPI or DPI, depending on the output format.
Application: When evaluating switching states in interlocking equations, for example, the compar-ing function can be used to define which states of the double-point information are to be considered as 'ON' and 'OFF'.
This function is also used for decoding bitstrings or bit fields.
Additionally, this function can be used for generating threshold messages for meas-ured values or for voltage present tests.
Particularities: -
Examples (telecontrol line):
Comparing functions for the accurate detection of control states
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 31 60 0 0 1 0 2 cmpeq 2 30 1 128 0 249 1 Q11 closed
M 31 60 0 0 1 0 6 cmpeq 1 30 1 128 0 249 2 Q15 open
M 33 60 0 0 1 0 6 cmpeq 1 0 2 0 30 1 128 0 249 3 Q16 open
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.7 Comparing functions for control state messages - 'isdef', 'istra'
Function: Setting of the output value depending on the state of double-point information
Availability: Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats: Input: DPI Output: SPI or DPI
Bit field: Applicable
Description: The result of the comparing operation is true if the following conditions are fulfilled:
isdef - defined control state (value 1 or 2) istra - transient control state (value 0 or 3)
Application: When evaluating switching states in interlocking equations, for example, the compar-ing function can be used to define which states of the double-point information are to be considered as defined or undefined.
Particularities: None
Examples (telecontrol line):
Testing of control state messages for defined or undefined state
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 31 60 0 0 1 0 2 istra 30 1 128 0 249 10 Q11 undefined
M 31 60 0 0 1 0 6 isdef 30 1 128 0 249 15 Q15 closed/open
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.8 Test of quality descriptors - 'isgood', 'isbad', 'isiv', 'isnt', 'isbl', 'issb', 'isov'
Function: Setting of the output value depending on the state of quality descriptors
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats: Input: all data formats Output: SPI or DPI
Bit field: rrelevant
Description: The result of the comparing operation is true if the following conditions are fulfilled:
isgood Result is true if no quality descriptor is set isbad Result is true if at least one quality descriptor is set isiv Result is true if 'invalid' is set isnt Result is true if 'not topical' is set isbl Result is true if 'blocked' is set issb Result is true if 'substituted' is set isov Result is true if 'overflow' is set
Application: Processing of quality information in logical operations
Particularities: None
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 32 60 0 0 0 248 86 isgood 30 1 128 0 0 250 Voltage OK
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.9 Switch-on delay - 'ton'
Function: Switch-on delay of binary signals
Availability:
Logic SI Line Master Device
x x x - x
Parameter: Time delay in seconds
Status: : ‘r‘ - re-trigger, ‘w‘ - transient signal
Data formats: Input: SPI, DPI, SCO, DCO Output: SPI, DPI, SCO, DCO
Bit field: Not applicable
Description: a) Edge-triggered
If the input signal changes from logical '0' to logical '1', the delay time is started. If the input signal is logical '1' after the delay time has expired, also the output takes on the state logical '1'.
b) State-triggered
The mode ‘state-triggered’ is used in case of command delays or if input status 'w' (transient signal) is set. If the input telegram has the state logical '1', the delay time is started. If the input signal is logical '1' after the delay time has expired, also the out-put state is set to logical '1'.
Re-trigger
If the input status is set to 'r', the delay time is re-triggered by further rising edges of the input signal or telegrams with the state logical '1'.
The (edge-triggered) function is illustrated in the following diagram:
Application: Signaling delays
Particularities: The delay time tolerance is +1 second.
If a quality descriptor has been set in the input signal, there is no delay, the mes-sage is generated immediately.
Examples (telecontrol line):
Delay in case of a communication error, bit 5 in bitstring
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 33 16 0 0 0 128 128 ton 15 5 1 0 30 1 128 0 60 10 Fault P139_128
M 33 16 0 0 0 128 129 ton 15 5 1 0 30 1 128 0 60 11 Fault P139_129
Input signal
t t t
Output without re-trigger
t t
Output with re-trigger t t t
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.10 Switch-off delay - 'toff'
Function: Switch-off delay of binary signals
Availability:
Logic SI Line Master Device
x x x - x
Parameter: Time delay in seconds
Status: Input status: ‘r‘ - re-trigger, ‘w‘ - transient signal
Data formats: Input: SPI, DPI, SCO, DCO Output: SPI, DPI, SCO, DCO
Bit field: Not applicable
Description: a) Edge-triggered
If the input signal changes from logical '1' to logical '0', the delay time is started. If the input signal is logical '0' after the delay time has expired, also the output takes on the state logical '0'.
b) State-triggered
The mode ‘state-triggered’ is used in case of command delays or input state 'w' (transient signal). If the input telegram has the state logical '0', the delay time is started. If the input signal is logical '0' after the delay time has expired, also the out-put takes on the state logical '0'.
Re-trigger
If the input status is set to 'r', the delay time is re-triggered by further falling edges of the input signal or telegrams with the state logical '0'.
The (edge-triggered) function is illustrated in the following diagram:
Application: Signaling delays
Particularities: The delay time tolerance is +1 second.
If a quality descriptor has been set in the input signal, there is no delay, the mes-sage is generated immediately.
Examples (telecontrol line):
Delay of inputs in multiple signals
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 33 16 0 0 0 128 130 toff 10 5 1 0 30 1 128 0 60 100 or Fault P139_130
M 33 16 0 0 0 128 131 toff 10 5 1 0 30 1 128 0 60 100 or Fault P139_131
M 33 16 0 0 0 128 133 5 1 0 30 1 128 0 60 100 or Fault P139_133
Input signal t t t
Output without re-trigger t t t
Output with re-trigger t
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.11 Switch-on and switch-off delay - 'tonoff'
Function: Switch-on and switch-off delay of binary signals
Availability:
Logic SI Line Master Device
x x x - x
Parameter: Time delay in seconds
Status: Input status: ‘r‘ - re-trigger, ‘w‘ - transient signal
Data formats: Input: SPI, DPI, SCO, DCO Output: SPI, DPI, SCO, DCO
Bit field: Not applicable
Description: a) Edge-triggered
If the input signal changes its state, the delay time is started. If the delay time has expired and the input signal has the same state as at the start of the delay time, also the output takes on that state.
b) State-triggered
The mode ‘state-triggered’ is used in case of command delays or input state 'w' (transient signal). At each input telegram, the delay time is started. If the delay time has expired and the input signal has the same state as at the start of the delay time, also the output takes on that state.
Re-trigger
If the input status is set to 'r', the delay time is re-triggered by further edges of the input signal and/or telegrams with the same status as at the start of the delay.
The (edge-triggered) function is illustrated in the following diagram:
Application: Signaling delays
Particularities: The delay time tolerance is +1 second.
If a quality descriptor has been set in the input signal, there is no delay, the mes-sage is generated immediately.
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 249 1 tonoff 4 30 1 128 1 10 19 Edge-triggered
M 30 60 0 0 0 249 1 w tonoff 4 30 1 128 1 10 20 State-triggered
C 45 60 0 0 0 249 1 45 1 128 1 10 30 tonoff 5 Command delay
Input signal t t t t
Output without re-trigger t t t t
Output with re-trigger t
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.12 Impulse function - 'timp'
Function: Monoflop
Availability:
Logic SI Line Master Device
x x x - x
Parameter: Impulse duration in seconds
Status: Input status: ‘r‘ - re-trigger, ‘w‘ - transient signal
Data formats: Input: SPI, DPI, SCO, DCO Output: SPI, DPI, SCO, DCO
: Not applicable
Description: a) Edge-triggered
If the input signal changes from logical '0' to logical '1', also the output is set to logi-cal '1' and the impulse duration is started. After the impulse duration has expired, the output drops back into the state logical '0'.
b) State-triggered
The mode ‘state-triggered’ is used in case of command delays or input state 'w' (transient signal). An input signal with logical '1' sets the output to logical '1' and starts the impulse duration. After the impulse duration has expired, the output drops back into the state logical '0'.
Re-trigger
If the input status is set to 'r', the impulse duration is re-triggered by further 0-1 edges of the input signal or telegrams with the state logical '1'.
The (edge-triggered) function is illustrated in the following diagram:
Application: Impulse generation
Particularities: The tolerance is +1 second.
If a quality descriptor has been set in the input signal, there is no impulse.
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 249 10 timp 10 30 1 128 1 10 40 Edge-triggered
M 30 60 0 0 0 249 20 w timp 10 30 1 128 1 10 41 State-triggered
Input signal
t t t
Output without re-trigger
t t t t t
Output with re-trigger
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.13 Timer - 'timer'
Function: Timer
Availability:
Logic SI Line Master Device
x x x - x
Parameter: Cycle time in seconds
Status: Input status: ‘e‘ - enabling of timer
Data formats: Input: SPI, DPI, SCO, DCO Output: all
Bit field: Not applicable
Description: The elements of the data model line have the following functions:
• Input data point: enabling input
• Input function: 'timer' + cycle time parameter
• Output data point: cyclic telegram
An input telegram with status ‘1‘ enables the timer, an input telegram with status '0' disables the timer.
By default, the timer is blocked after initialization. With input status 'e', the timer works without an enabling telegram.
The timer sends cyclically an output telegram. After the configured cycle time has expired, the binary output is switched between logical '0' and logical '1' (bistable mul-tivibrator with duty cycle 1:1).
If the cycle time is set with post-decimal positions, the pre-decimal positions corre-spond to the time for logical '0' and the post-decimal positions correspond to the time for logical '1', one hundred thousandth corresponding to one second (e.g. 9.00001
9 s logical ‘0‘ and 1 s logical ‘1‘).
If the output value is set to a fixed value by the function 'set', the telegram with set data is sent cyclically.
The cause of transmission of output telegrams is 3 - 'spontaneous' for signals and 6 - 'Activation' for commands.
Application: Timer
Particularities: The tolerance is +1 second.
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 255 255 255 255 255 e timer 3 30 1 128 0 249 200 start + SPI alternating
M 30 60 0 0 0 249 1 timer 3 30 1 128 0 249 201 set 1 starttele + SPI=1
M 30 60 255 255 255 255 255 e timer 4 30 1 128 0 249 202 set 1 start + SPI=1
M 30 60 255 255 255 255 255 e timer 5 45 1 128 0 249 203 set 1 start + single command=1
M 30 60 255 255 255 255 255 e timer 600 ## 1 128 0 249 250 set 20 cy cl. general interrogation
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.4.14 Cycle supervision - 'cycsup'
Function: Supervision of cyclic signal updating
Availability:
Logic SI Line Master Device
x x x - x
Parameter: Supervision time in seconds
Status: No particular status information
Data formats: Input: all Output: all, or depending on output function
Bit field: Applicable
Description: The input signal is processed and its format is converted as per default. If within the specified time window, no input telegram is received, the input is set to 'not topical'. This state is transferred to the output data by default output processing or calling the optional output function.
Application: Supervision of cyclically updated signals
Particularities: The tolerance is +1 second.
Example (telecontrol line):
6.4.15 Input information of select function - 'sel', 'case', 'deflt'
The functions 'sel' and 'case' must only be used in connection together with the output function 'swi'; for de-tails, see section 6.5.14.
Beside its use in the switch function, the input function 'deflt' can also be used separately for initializing in-puts,
6.4.16 Inputs of the output function D-Flip-Flop - 'set', 'res', 'dat', 'clk'
The functions 'set', 'res', 'dat' and 'clk' must only be used together with the output function D flip-flop, 'ffq'; for details, see section 6.5.15.
6.4.17 Inputs of the output function invalid control - 'sig', 'con'
The functions 'sig' and 'con' must only be used together with the output function invalid control, 'ivcon'; for details, see section 6.5.17.
6.4.18 Inputs of the interlocking functions - 'cmd', 'req', 'enon', 'enoff', 'send', 'conf'
The functions 'cmd', 'req', 'enon', 'enoff', 'send' and 'conf' must only be used together with the output func-tions 'lock' or 'elock'; for details, see section 6.5.16.
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 249 50 cy csup 30 30 1 128 1 10 50 Cy cle superv ision 30s
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5 Output-related functions
6.5.1 Overview
The following output functions are implemented:
Setting functions set - Setting the output value settc - Setting the cause of transmission of the output telegram setcmd - Setting the output value and cause of transmission = 6, 'Activation' setcon - Setting the output value and cause = 7, 'Confirmation of activation' settrm - Setting the output value and cause = 10, 'Activation termination' pulse - Setting the qualifier of command
Setting of quality de-scriptors
setnt - Setting of 'not topical' setbl - Setting of 'blocked' setsb - Setting of 'substituted' setiv - Setting of 'invalid' setov - Setting of 'overflow' setqds - Setting of the quality descriptor byte setca - Setting of 'preset' (counters) setcy - Setting of 'carryover' (counters)
Logic or - OR operation of inputs nor - NOR operation of inputs and - AND operation of inputs nand - NAND operation of inputs iff - Equivalence function xor - Exclusive OR dynor - Dynamic OR bs - Bitstring synthesis bs32 - Synthesis bitstring of 32 bits
Arithmetic sum - Sum of input values diff - Difference of input values prod - Product of input values quot - Quotient of input values
Attenuation of measured values
db - Deadband function (threshold processing) dbi - Integrated deadband function avg - Average value calculation
Selecting function switch - Switch function
Flip-flop
ffq - D flip-flop
Interlocking lock - Interlocking function elock - Advanced interlocking function
Quality descriptors
ivcon - Invalid control
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.2 Setting the output value - 'set'
Function: Setting the output to a constant value
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Output value
Status: No particular status information
Data formats: Input, output: all data formats
Description: Depending on the data format, output data are set to the parameter value.
Application: Decoding functions, setting of output value in connection with comparing functions
Particularities: Not only the information bits are set, but all output data, e.g. 8 bits in case of SCO. Thus, also qualifiers can be set. In case of data formats INT32BS8 and FP32BS8, only the integer or floating point value is set.
For outputs with setting function, an output telegram is generated for each input tele-gram.
Examples (telecontrol line):
Conversion of one regulating step command into two single commands to different addresses.
6.5.3 Setting the cause of transmission of the output telegram - 'settc'
Function: Setting the cause of transmission to a constant value
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Cause of transmission
Status: No particular status information
Data formats: Input, output: all data formats
Description: The cause of transmission is set to the parameter value.
Application: Generation of command confirmations from return info telegrams
Particularities: For outputs with setting function, an output telegram is generated for each input tel-
egram.
Examples (telecontrol line):
Command confirmation ACTTERM positive for the LED reset command, derivation from return info
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
C 45 60 0 0 0 242 100 set 1 47 1 128 0 242 65 ifeq 1 'Low er' command
C 45 60 0 0 0 242 101 set 1 47 1 128 0 242 65 ifeq 2 'Higher' command
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 31 60 0 0 0 160 19 31 1 128 134 160 19 Return info of LED reset
M 31 60 0 0 0 160 19 iftc 12 45 1 128 134 160 19 settc 10 ACTTERM positiv e
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.4 Setting data and cause of transmission - 'setcmd', 'setcon', 'settrm'
Function: Setting the output and the cause of transmission
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Output value
Status: No particular status information
Data formats: Input, output: all data formats
Description: Depending on the data format, output data are set to the parameter value and cause of transmission:
setcmd - Cause of transmission = 6, 'Activation' setcon - Cause of transmission = 7, 'Activation confirmation' settrm - Cause of transmission = 10, 'Activation termination'
Through the combined setting functions the processing in the logic with 2 lines is spared.
Application: Conversion of messages into commands or command confirmations
Particularities: For outputs with setting function, an output telegram is generated for each input tel-egram.
Examples (telecontrol line):
Derivation of a regulating step command from two SPI
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 249 1 ifeq 1 47 1 128 0 248 57 setcmd 1 'Low er' command
M 30 60 0 0 0 249 2 ifeq 1 47 1 128 0 248 57 setcmd 2 'Higher' command
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.5 Setting the impulse duration in commands - 'pulse'
Function: Setting the qualifier of commands
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Value for qualifier of command
Status: No particular status information
Data formats: Output: SCO, DCO, RCO
Description: The impulse duration of commands is set as follows:
In the commands SCO, DCO, and RCO, the qualifier of command (QOC) is set with the range 0 – 3:
- QOC = 0 – no definition - QOC = 1 – short command duration - QOC = 2 – long command duration - QOC = 3 – persistent command
Application: Setting the impulse duration in commands
Particularities: None
Examples (telecontrol line):
6.5.6 Setting of quality descriptors – 'setbl', 'setnt', 'setsb', 'setiv', 'setov', 'setqds', 'setca', 'setcy'
Function: Setting of quality descriptors
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Value for the quality descriptor to be set
Status: No particular status information
Data formats: All data formats with quality descriptors
Description: setbl - Setting of 'blocked' setnt - Setting of 'not topical' setsb - Setting of 'substituted' setiv - Setting of 'invalid' setov - Setting of 'overflow' setqds - Setting of the quality descriptor byte setca - Setting of CA (preset) in counters setcy - Setting of CY (carryover) in counters
The quality descriptors are set to the defined value.
Application: Manipulation of quality descriptors
Particularities: In contrast to the setting functions for data and cause of transmission, here the old/new comparison is used to identify changes.
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
C 45 60 0 0 0 242 69 pulse 1 45 1 128 134 242 69 Short command duration
C 46 60 0 0 0 242 71 pulse 2 46 1 128 134 242 71 Long command duration
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.7 Logical operations - 'or', 'nor', 'and', 'nand', 'iff', 'xor'
Function: Logical operation of binary signals
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: Input: ‘w‘ - transient signal, output: ‘r‘ - reset telegram
Data formats: Input: SPI, DPI, SCO, DCO, RCO; optional bit field indication, length of bit field 1, 2 bits, target bit = 0 Output: SPI, DPI
Bit field: Applicable, length of bit field 1 or 2 bits, target bit = 0
Description: Logical operation:
or - OR operation nor - NOR operation and - AND operation nand - NOT AND operation iff - Equivalence xor - Exclusive OR operation
A logical operation is characterized by the same output address, type identification and logical function for all related inputs.
Processing takes place in two steps:
1. Each input is processed through implicit format conversion or an input function (e.g. 'not'), with optional indication of a bit field. The resulting output data format is a single- or double-point information (SPI or DPI).
2. Calculation of the logical operation:
When a logical operation is calculated, internal processing is always single-pole – irrespective of the output data format SPI or DPI. This means, that in double-point signals, the states '01' and '00' are interpreted as logical '0' and the states '10' and '11' as logical '1'. The DPI output of the operation cannot assume the states '00' or '11'.
Using the input comparing functions 'cmpxx', you can control which input states are processed with logical '0' or logical '1'.
In all logical operations by default the operation-dependent calculation of quality de-scriptors is used. Thereby, the output of an OR operation will be set to logical '1' and valid if at least one input is logical '1' and valid. Similarly, the output of an AND oper-ation will be set to logical '0' and valid if at least one input is logical '0' and valid.
However, input quality descriptors can also be combined by an OR operation.
Transient signals are processed in group signals just as in single signals. Addition-ally, processing is done with negated input data. The generation of a reset telegram is also possible.
Application: Generation of multiple signals
Particularities: Inputs do not need to immediately follow each other in the data model.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Examples:
Combining of starting signals to a general starting (telecontrol lines)
Cascaded logical operations (logic)
The gates are combined via memories, so that processing is done internally within the logic. If the outputs of upstream gates are needed outside the logic, status 'm' must be removed. The output gates will still remain connected via the same device and data point address. Output telegrams will return to the logic via the ker-nel.
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 160 64 30 1 128 134 160 102 or Start phase A
M 30 60 0 0 0 160 65 30 1 128 134 160 102 or Start phase B
M 30 60 0 0 0 160 66 30 1 128 134 160 102 or Start phase C
M 30 60 0 0 0 160 67 30 1 128 134 160 102 or Start phase N
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 GR STAT FKT PAR Meldung
I 30 64 0 0 0 1 1 30 56 0 0 0 1 1 m nand E1
I 30 64 0 0 0 1 2 30 56 0 0 0 1 1 m nand E2
I 30 64 0 0 0 1 3 not 30 56 0 0 0 1 1 m nand E3
I 30 65 0 0 0 1 4 30 56 0 0 0 1 2 m and E4
I 30 65 0 0 0 1 5 not 30 56 0 0 0 1 2 m and E5
I 30 66 0 0 0 1 6 30 56 0 0 0 1 3 or E6, A
I 30 56 0 0 0 1 1 30 56 0 0 0 1 3 or A
I 30 56 0 0 0 1 2 30 56 0 0 0 1 3 or A
&
& >1
A
E1
E2
E3
E4
E5
E6
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.8 Dynamic OR operation - 'dynor'
Function: OR operation with change message
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats: Input: SPI, DPI, SCO, DCO, RCO; optional bit field indication, length of bit field 1, 2 bits, target bit = 0 Output: SPI, DPI
Bit field: Applicable, length of bit field 1 or 2 bits, target bit = 0
Description: The dynamic OR is, in principle, an OR operation with the following additional func-tion:
If the output is logical '1' and another input changes from logical '0' to logical '1', the output is first signaled with a logical '0' and then with a logical '1'.
The time tag of the 1-0 edge corresponds to the time of the event. The time tag of the successive 0-1 edge corresponds to the time of the event plus the configured duration of transient signals.
Application: Generation of special multiple signals
Particularities: Inputs do not need to immediately follow each other in the data model.
In combination with the 'dynor' function, no transient reset telegrams can be gener-ated (output status 'r').
Examples:
Generation of a multiple signal for a communication error with message in case of change
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 33 10 0 0 0 128 64 5 1 0 30 1 128 10 60 100 dy nor Fault P139_64
M 33 10 0 0 0 128 65 5 1 0 30 1 128 10 60 100 dy nor Fault P139_65
M 33 10 0 0 0 128 66 5 1 0 30 1 128 10 60 100 dy nor Fault P139_66
M 33 10 0 0 0 128 67 5 1 0 30 1 128 10 60 100 dy nor Fault P139_67
M 33 10 0 0 0 128 68 5 1 0 30 1 128 10 60 100 dy nor Fault P139_68
M 33 10 0 0 0 128 69 5 1 0 30 1 128 10 60 100 dy nor Fault P139_69
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.9 Bitstring, bitstring of 32 bits - 'bs', 'bs32'
Function: Synthesis of bitstrings
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats: Input: all, the bit field must be specified at the input Output: function 'bs32': BS32,
function 'bs': all data formats
Bit field: Mandatory
Description: Assignment of bit field/bit field of 32 bits
The criteria for bitstring processing are the same output address and the same bit-string function for all related inputs.
In principle, processing itself is similar to logical operations, with the exception that bit fields are moved instead of combined.
The output quality descriptor is the result of the OR operation of the input quality de-scriptors.
Application: Compressing function
Particularities: Inputs do not need to immediately follow each other in the data model.
Examples (telecontrol line):
Starts bitstring
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 160 64 0 1 0 33 1 128 134 160 106 bs32 Start phase A
M 30 60 0 0 0 160 65 0 1 1 33 1 128 134 160 106 bs32 Start phase B
M 30 60 0 0 0 160 66 0 1 2 33 1 128 134 160 106 bs32 Start phase C
M 30 60 0 0 0 160 67 0 1 3 33 1 128 134 160 106 bs32 Start phase N
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.10 Arithmetic functions - 'sum', 'diff', 'prod', 'quot'
Function: Arithmetic operation
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats: Input: INT16, INT32, FP32, BCR32 Output: INT16, INT32, FP32, BCR32
Bit field: Not applicable
Description: Calculation of the arithmetic function:
sum - Sum of input values diff - Difference of input values prod - Product of input values quot - Quotient of input values
Calculation takes place internally in floating point format with double precision. If the number range of the output format is exceeded, the overflow bit or carryover bit (counters) is set.
The output quality descriptor is the result of the OR operation of the input quality de-scriptors.
Application: Arithmetic calculations of measurement and counter values
Particularities: Inputs do not need to immediately follow each other in the data model.
Examples:
Total power
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 36 64 0 0 0 248 89 34 1 128 134 248 200 sum Pow er 1
M 36 65 0 0 0 248 89 34 1 128 134 248 200 sum Pow er 2
M 36 66 0 0 0 248 89 34 1 128 134 248 200 sum Pow er 3
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.11 Threshold processing (deadband) - 'db'
Function: Threshold processing
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Deadband value
Status: No particular status information
Data formats: Output: INT16, INT32, FP32
Bit field: Not applicable
Description: An output telegram is generated if the amount of change – compared to the last value transmitted – is greater than the deadband value.
Application: Attenuation of measured values
Particularities: None
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 36 60 0 0 0 5 41 mult 1706 34 1 128 1 248 80 db 85 IA all MV
M 36 60 0 0 0 6 41 mult 1706 34 1 128 1 248 81 db 85 IB 240% NV = 4095
M 36 60 0 0 0 7 41 mult 1706 34 1 128 1 248 82 db 85 IC threshold 5% NV
M 36 60 0 0 0 5 43 mult 1706 34 1 128 1 248 83 db 85 VA-N
M 36 60 0 0 0 6 43 mult 1706 34 1 128 1 248 84 db 85 VB-N
M 36 60 0 0 0 7 43 mult 1706 34 1 128 1 248 85 db 85 VC-N
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.12 Deadband integrated - 'dbi'
Function: Threshold processing by integration
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Deadband value
Status: No particular status information
Data formats: Output: INT16, INT32, FP32
Bit field: Not applicable
Description: If the deviation of a received measured value from the last measured value transmit-ted exceeds the deadband value, the received measured value is transmitted imme-diately, otherwise it is only updated in the memory.
Deviations of the current measured value from the last measured transmitted value are added cyclically and appropriately signed. If the amount of total changes ex-ceeds the deadband value, the measured value is transmitted and the value of total changes is set to zero.
The cycle time of the deadband integrated processing can be configured.
Application: Attenuation of measured values
Particularities: None
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 36 60 0 0 0 5 41 mult 3416 34 1 128 2 248 80 dbi 171 IA all MV
M 36 60 0 0 0 6 41 mult 3416 34 1 128 2 248 81 dbi 171 IB 120 %NV = 4095
M 36 60 0 0 0 7 41 mult 3416 34 1 128 2 248 82 dbi 171 IL3 DBI 5% NV
M 36 60 0 0 0 5 43 mult 3416 34 1 128 2 248 83 dbi 171 VA-N
M 36 60 0 0 0 6 43 mult 3416 34 1 128 2 248 84 dbi 171 VB-N
M 36 60 0 0 0 7 43 mult 3416 34 1 128 2 248 85 dbi 171 VC-N
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.13 Average value calculation - 'avg'
Function: Average value calculation
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Calculation interval in seconds
Status: No particular status information
Data formats: Output: INT16, INT32, FP32
Bit field: Not applicable
Description: Processed measured values are not transmitted spontaneously. Instead, the current measured value is added every second. If the value changes several times within one second, the average value of those changes is used for addition.
At the end of the calculation interval, the average value is calculated by means of dividing the sum by the length of the interval.
If the average value has changed, a telegram is transmitted.
Application: Attenuation of measured values
Particularities: None
Examples (telecontrol line):
1/4 hour average value
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 36 60 0 0 0 7 43 36 1 128 3 248 80 av g 900 1/4 hour av erage v alue
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.14 Selecting function (switch) - 'swi'
Function: 1 out of N selection of signals via control inputs
Availability:
Logic SI Line Master Device
x x x x x
Parameter: For input functions 'sel' and 'case': input number
Status: No particular status information
Data formats: Input: sel - SPI, or bit field of 1 bit length case - all data formats
deflt - all data formats
Output: The input format of the inputs 'case' or 'deflt' must be convertible into the output format through default conversion.
Bit field: Applicable, in case of 'sel', length of bit field 1 bit, target bit = 0
Description: The selection function can have the following input functions:
sel - Selection input case - Data input deflt - Default input
The data input 'case x', for which the related selection input 'sel x' is logical '1', is connected through to the output. If several selection inputs are active, the first one becomes effective according to notation.
If no selection input is active, the default input is connected through to the output. The default input can be assigned to an input telegram via the input address, or it can be initialized with a fixed value via the parameter. If this value shall be used as the default value, the input address is set to an address not used in the system (dummy address).
Data inputs are processed via default conversion, with the selection of a bit field, if applicable.
Application: Selection of busbar voltage
Particularities: If no active selection input with good quality is found, but instead an active input with set quality descriptor is found, this latter input is used. The quality descriptor of the selection input is copied into the output value.
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 60 1 sel 1 34 1 128 1 10 12 sw i Selection V1
M 30 60 0 0 0 60 2 sel 2 34 1 128 1 10 12 sw i Selection V2
M 30 60 0 0 0 60 3 sel 3 34 1 128 1 10 12 sw i Selection V3
M 36 64 0 0 0 242 86 case 1 34 1 128 1 10 12 sw i V1
M 36 65 0 0 0 242 86 case 2 34 1 128 1 10 12 sw i V2
M 36 66 0 0 0 242 86 case 3 34 1 128 1 10 12 sw i V3
M 34 60 0 0 0 0 255 deflt 0 34 1 128 1 10 12 sw i Default = 0
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.15 Flip-flop (output Q) - 'ffq'
Function: Bistable multivibrator
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats: Inputs: SPI, DPI, SCO, DCO, RCO, length of bit field 1 bit
Output: SPI, DPI
Bit field: Applicable, length of bit field 1 bit, target bit = 0
Description: The processed information can have the following input functions:
set - Setting input res - Resetting input
dat - Data input clk - Clock input
Unnecessary inputs can be omitted.
Processing:
If the setting input = 1, the output is set to 1.
If the resetting input = 1, the output is set to 0.
If the clock input = 1, the output is set to the value of the data input.
Priority: The setting input prevails over the resetting input, and the resetting input prevails over the data input.
Quality and time tag are taken from the triggering input.
Application: Signal storage, state machines
Examples:
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 30 60 0 0 0 249 1 set 30 1 128 0 249 8 ffq Setting input
M 30 60 0 0 0 249 2 dat 30 1 128 0 249 8 ffq Clock input
M 30 60 0 0 0 249 3 clk 30 1 128 0 249 8 ffq Data input
M 30 60 0 0 0 249 4 res 30 1 128 0 249 8 ffq Resetting input
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.16 Interlocking functions - 'lock', 'elock'
Function: Locking of switchgear units
Availability:
Logic SI Line Master Device
- x - - -
Parameter: Not required
Status: No particular status information
Data formats: Inputs: cmd - DCO req - BS32 enon - SPI, DPI enoff - SPI, DPI send - SPI, DPI ('elock' only) conf - SPI, DPI ('elock' only)
Output: DCO
Bit field: Not applicable
Description: When receiving the announcement of a switching operation (select command or re-quest for SI check), the interlocking function decides on the basis of the states of the enabling signals 'enon' or 'enoff', whether a switching command is emitted or not. The telegram exchange for switching operations with station interlocking is described in section 8.
The interlocking function processes the following input information:
cmd - Switching command from the command source enon - Enable condition for the close command, enoff - Enable condition for the open command req - Request telegram for checking the station interlocking in case of local
control send - Send telegram ('elock' only) conf - Confirmation telegram ('elock' only)
The output of the interlocking function is the switching command to the device, with the output function 'lock' or 'elock'.
The conditions for the command enabling, 'enon' and 'enoff', are created by up-stream logical operations. They are updated by process messages during runtime, so that in case of a switching operation, no further calculations are required.
For the output function 'elock', after receiving the select command, additionally, first the send telegram (input 'send') is generated and the confirmation telegram (input 'conf') is received, then the actual command procedure is started with the select command. The same procedure is executed after receiving the request for checking the station interlocking in case of local control. This procedure can include further checks before the switching operation, e.g. checks of the communication with all de-vices involved in interlocking.
Application: Locking of switching devices
Particularities: None
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Examples (station interlocking):
Default interlocking function
Advanced interlocking function
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 GR STAT FKT PAR Signal
I 46 60 0 0 0 242 65 cmd 46 60 0 0 0 242 65 lock Command
I 30 57 0 0 0 0 1 enon 46 60 0 0 0 242 65 lock Enable close cmd
I 30 57 0 0 0 0 2 enoff 46 60 0 0 0 242 65 lock Enable open cmd
I 33 60 0 0 0 242 116 req 46 60 0 0 0 242 65 lock Req. SI check
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 GR STAT FKT PAR Signal
I 46 60 0 0 0 242 67 cmd 46 60 0 0 0 242 67 elock Command
I 30 57 0 0 0 0 3 enon 46 60 0 0 0 242 67 elock Enable close cmd
I 30 57 0 0 0 0 4 enoff 46 60 0 0 0 242 67 elock Enable open cmd
I 33 60 0 0 0 242 116 req 46 60 0 0 0 242 67 elock Req. SI check
I 30 57 0 0 0 0 5 send 46 60 0 0 0 242 67 elock Send telegram
I 30 57 0 0 0 0 6 conf 46 60 0 0 0 242 67 elock Confirmation tele
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.5.17 Invalid control - 'ivcon'
Function: Setting the signal quality 'invalid'
Availability:
Logic SI Line Master Device
x x x x x
Parameter: Not required
Status: No particular status information
Data formats: Input: con: SPI, bit field length 1 bit sig: all
Output: all
Bit field: Applicable, in case of 'con', length of bit field 1 bit, target bit = 0
Description : With the function 'ivcon', the quality bit 'invalid' of a signal is set, based on a control input. If the control input is active, the qualifier 'invalid' of the output signal is set. The inputs of the function are the following:
sig - Signal input con - Control input
Application: Setting of the quality 'invalid' for signals in case of a signaling voltage failure.
Particularities: None
Examples (telecontrol line):
D DT DEV DPA4 DPA3 DPA2 DPA1 DPA0 STAT FKT PAR ST_LN_ZI DT ASD1 ASD0 OBJ2 OBJ1 OBJ0 GR STAT FKT PAR TEXT
M 31 60 0 0 0 242 1 sig 31 1 128 0 242 1 iv con Signal input:DEV001
M 30 60 0 0 0 249 5 con 31 1 128 0 242 1 iv con Control input:M005
M 31 60 0 0 0 242 3 sig 31 1 128 0 242 3 iv con Signal input:DEV002
M 30 60 0 0 0 249 5 con 31 1 128 0 242 3 iv con Control input:M005
M 31 60 0 0 0 242 5 sig 31 1 128 0 242 5 iv con Signal input:DEV003
M 30 60 0 0 0 249 5 con 31 1 128 0 242 5 iv con Control input:M005
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.6 Status information
6.6.1 Input status information
Sta
tus Function and description
Lo
gic
SI
Lin
e
Ma
ste
r
Devic
e
w Signals reported in active state only (transient signal)
For signals marked with this status, the internal state is reset after the output telegram has been generated; for details, see section 7.6.
Note: In contrast to IEC 60870-5-103 and to the information given in device address lists, according to IEC 60870-5-104, all protection signals from the device are reported as coming and going.
x x x x x
b Initialization with quality descriptor 'substituted'
Data points marked with a 'b' in their input status are initialized with quality descriptor 'substituted' at startup. Additionally, the descriptor 'substituted' is set if in the case of transient signals (input status 'w') the state is reset internally; for details, see section 7.6..
x x x x x
n Setting and signaling with quality descriptor 'not topical'
Status 'n' can be used if the signal is to be sent with the quality descriptor 'not topical' in case of a coming communication error, and without 'not topical' in case of a going com-munication error. Typically, this applies to signals of connected devices not included in the general interrogation.
- - x - -
u Chatter suppression
The chatter suppression is used as described in section 7.7.
x x x - x
c Sending of command confirmation 'Activation confirmation'
After receiving the command, it is confirmed by the 'Activation confirmation'.
x x x x x
t Sending of command confirmation 'Activation termination'
After receiving the command, it is confirmed by the 'Activation termination'.
x x x x x
x Command procedure 'Direct execute'
At the input, the command procedure 'Direct execute' is expected.
x x x - -
s Command procedure 'Select and execute'
At the input, the command procedure 'Select and execute' is expected.
x x x - -
p Bypass
This double command is not included in the check of control uniqueness.
x x x - -
r Re-trigger
With the time functions 'ton', 'toff', 'tonoff', and 'timp', delays and impulse durations are re-triggered by further rising edges or by telegrams with active state, respectively.
x x x - x
e Enabling of timer
This status information has the effect that the timer starts without an enabling telegram.
x x x - x
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
6.6.2 Output status information S
tatu
s Function and description
Lo
gic
SI
Lin
e
Ma
ste
r
Devic
e
r Reset telegram for transient signals
Many network control systems cannot process transient information. Therefore, there is the possibility to transmit a telegram with reset data for transient signals.
x x x x x
c Cyclic transmission
Data points for which this status is set are reported with the configured cycle time.
- - x - -
f Force
If this status is set, for each input telegram an output telegram is generated, irrespective of whether or not there has been a change of data or quality descriptors.
x x x x x
q Quiet
If this status is set, for the data point concerned, no spontaneous output telegrams are generated.
- - x - -
m Memory
Output telegrams of a data point marked ‘m’ are returned to input processing through the internal queue. The cascading of logical operations can thus be quickly achieved.
x x - - -
b Blocked
At startup, the data point market with ‘b’ is initialized with signal/command blocking. Signals with this status are reported with the quality descriptor 'blocked'.
- - x - -
x Command procedure 'Direct execute'
At the output, the command procedure 'Direct execute' is applied; for details, see sec-
tion 7.2.2.
x x x - -
s Command procedure 'Select and execute'
At the output, the command procedure 'Select and execute' is applied; for details, see
section 7.2.2.
x x x - -
z Zero value suppression
For data points with output status 'z', output telegrams are transmitted with '0' if the value is less than the value configured at parameter 'Threshold value zero suppression'.
x x x x x
h Increasing priority
ASDUs normally transmitted via the measured value queue and marked with this status, are transmitted via the queue for binary signals instead.
- - x - -
l Decreasing priority
ASDUs normally transmitted via the queue for binary signals and marked with this sta-tus are transmitted via the measured value queue instead.
- - x - -
u Blocking of monitor direction
An output marked 'u' has the effect that in the telecontrol line concerned, the monitoring and control direction is set off-line or on-line, in analogy to IEC 60870-5-103. In case of blocking, the triggering message is the last message transmitted.
- - x - -
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
7 Special functions of program objects
7.1 Priority-controlled data transmission
7.1.1 Function
The following table shows the program objects into which priority-controlled data transmission is imple-mented:
Logic SI Line Master Device
- - x x -
At the IEC 60870-5-104 interface, input and output telegrams are written into queues, before they are pro-cessed and sent, respectively.
Depending on their IEC 60870-5-104 type identifiers, input and output telegrams are assigned queue priori-ties. Queue priorities are, in descending order:
1. Commands 2. Binary signals and measured values in floating point format (ASDUs 13,14, and 36) 3. Measured values in integer format (ASDUs 9, 10, 11, 12, 34 und 35)
When telegrams are read, the queue with the highest priority is queried first. The queue with the next priority is queried if the queue queried so far is empty.
Queues can work in two modes:
1. Normal mode All telegrams are saved in the queue in the order of arrival.
2. Overwrite mode At arrival of a new telegram in the queue, it is checked if the signaled data point already exists in the queue. If yes, that queue entry is overwritten. Thus, each data point exists only once in the queue.
By default, measured value queues work in overwrite mode. The other queues work in normal mode.
Queue overflow
If a queue in monitoring direction overflows, a buffer overflow message is generated and the oldest tele-grams are deleted until 20% of the queue is empty; for details, see section 10.3.4.
7.1.2 Possibilities of engineering
The priority in monitoring direction can be influenced by the output status in the data model.
Output status ‘h‘ - increasing priority
Telegrams with measured value priority are transmitted via the queue for binary signals. This status should be applied if in telecontrol lines, for instance the fault location has been specified as a low-priority ASDU 9, 10, 11, 12, 34, or 35. With status 'h', the telegram is transmitted with the priority of bi-nary signals, and measured values in the queue are prevented from being overwritten.
Output status ‘l‘ - decreasing priority
Telegrams with priority of binary signals are transmitted via the measured value queue. This status should be applied if measured operating values are transmitted as floating point values (ASDUs 13,14, or 36). Measured values are thus attenuated by overwriting in the queue and no longer hinder the transmission of binary signals.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
7.2 Command processing
7.2.1 Function
The following table shows the program objects into which command processing is implemented:
Logic SI Line Master Device
x x x - -
Command processing applies to all process commands (data types 45 to 51), in IEC 60870-5-104 addition-ally to type identifications with time tag (58 to 64).
The IEC 60870-5-101 and -104 standards define two different command procedures:
• 'Direct execute'
• 'Select and execute' (or SBO - select before operate)
The system-internal default command procedure is 'Direct execute'.
The default command procedure on telecontrol lines at the IEC 60870-5-104 interface is 'Direct execute', as well. However, a parameter allows for switching to 'Select and execute'. In addition, the command proce-dure can be set internally, and for the IEC 60870-5-104 interface separately for each command, via status information ‘x‘ - 'Direct execute', and 's‘ - 'Select and execute'.
In case of switchgear control with station interlocking, double commands (data type 46) are transmitted inter-nally with the 'Select and execute' procedure.
During command processing, procedures are supervised and command confirmations are assigned by means of the originator address.
Before a command is processed, it is checked if all conditions for command execution are fulfilled. If this is not the case, a negative 'Activation confirmation' is sent to the sender. The conditions for a negative confir-mation are:
• the command does not exist in the data model,
• the maximum number of running command procedures has been exceeded,
• a command with the same address is still being processed,
• with check of control uniqueness: another double command is still being processed.
In addition, a command is rejected without confirmation if it is too old.
Command processing for telecontrol line
Processing is handled in analogy to logic / station interlocking.
A command is converted into an output command via the data model in command direction. Also, input and output commands aresent to the command processing module and a command procedure is opened. In the command procedure, command confirmations ACTCON and ACTTERM (if applicable) are supervised.
Command confirmations from the device are not included into the data model in monitoring direction. In-stead, they are converted into sender command confirmations via the command processing module. If the
Command confirmation
Engineered command
confirmation
Data model Monitoring direction
Command processing
Input command
Output command(s) to device
Command confirmation from device
Return info from device
Input command
Output command
Data model
Control direction
Return info
Device
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
command confirmations from the device time out, a negative command confirmation is generated after a set supervision time period.
7.2.2 Possibilities of engineering
Command processing allows the conversion of the two command procedures.
Output status ‘s‘: 'Direct execute' 'Select and execute'
In this case, first the execute command is converted into a select command. Only after the select confirma-tion has been received from the target device will the execute command be sent.
For commands from the telecontrol line in mode 'with station interlocking', the following special feature ap-plies: If for a double command, status information 's' in mode 'with station interlocking' is defined, for the command concerned is not routed to the station interlocking. It is thus possible to bypass interlocking.
Output status ‘x‘: 'Select and execute' 'Direct execute'
In this case, the select command is confirmed on the input side and only the execute command is converted and sent to the target device.
For commands from the telecontrol line in mode 'with station interlocking', the following special feature ap-plies: If for a double command, status information 'x' in mode 'with station interlocking' is defined, the com-mand is not routed to the station interlocking. It is thus possible to bypass interlocking.
Engineering command confirmations
If the recipient of commands does not send all requested command confirmations, they can be engineered. This can be done by additionally converting the command return info into a command confirmation. Such en-gineered confirmations are also processed via the command processing module.
7.3 Check of control uniqueness
The following table shows the program objects into which the check of control uniqueness is implemented:
Logic SI Line Master Device
x x x - -
Enabling this function allows to monitor whether in the program object concerned, only one double command is being processed. All other commands are rejected and a negative confirmation is transmitted. Additionally, a message 'Violation of check of control uniqueness' is generated; for details, see section 10.3.4.
The check of control uniqueness function generates an 'order running' message that remains active as long as a command is being processed. Further conditions can be included into the check of control uniqueness using an input, e.g. 'order running' messages of other telecontrol lines or connected devices.
All double commands marked by input status 'p' (bypass) are not included into the check of control unique-ness.
If switchgear units are controlled with station interlocking, it is ensured that in the device concerned only one double command at a time is executed.
7.4 Transmission in reverse direction
The following table shows the program objects into which transmission in reverse direction is implemented:
Logic SI Line Master Device
- - x x x
All 'process information in monitoring direction' (ASDUs 1–19, 21, 30-37) can be transmitted in control direc-tion, and all 'process information in control direction' (ASDUs 45-51, 58-64) can be transmitted in monitoring direction.
For transmission in reverse direction, the same process functions (logical operations, arithmetic, etc.) are available as in normal direction.
Data are managed internally in the same way as in the logic, i.e. via a virtual logical device. The telecontrol line registers the VLD to the kernel as a device. Thereby the kernel addresses commands to the VLD and
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
thus to the peer station via the telecontrol line. All messages in control direction are given the device address of the VLD.
M* = Messages in control direction C* = Commands in monitoring direction
In the IEC 60870-5-104 master station bus, connected devices by default are registered to the kernel as far devices. The same applies to the device interface. The device is also registered to the kernel.
In the telecontrol line, a command processing module for processing of command procedures has been im-plemented for the VLD. It realizes the same functions as the one in control direction, i.e. it converts com-mand confirmations and supervises command procedures. The conversion of command procedures 'Direct execute' to 'Select and execute' and vice versa is also possible.
System commands (general interrogation, counter read, read command, and test command) from the kernel to the VLD are also supported.
All signaling information from the VLD is transmitted to the kernel with quality descriptor 'not topical' if the link to the peer station is disturbed. When the link is re-established, a general interrogation is sent to the peer station and thus the current status (without 'not topical') is restored.
For transmission in reverse direction, a group has been implemented in the parameter subset. This allows to set the VLD address and to define whether a general interrogation is sent at re-establishing of the link.
7.5 IEC 60870-5-104 redundant transmission
IEC 60870-5-104 telecontrol lines can be set for two different application cases:
1. Operation at the station bus In this mode, a telecontrol line can communicate with one client only. Redundant transmission is not used.
2. Remote operation In this mode, redundant transmission to up to 8 clients in one redundancy group is supported. Re-dundant transmission is possible in two ways:
a) According to IEC 60870-5-104 Ed. 2 Only one link is active with data transmission enabled, all other links are passive and supervised by test telegrams. Connected clients define with 'Start data transmission', which link is active.
b) Operation of parallel links All links are simultaneously fed with data and commands are received from all links. Clients de-fine which client is active, i.e. which client is allowed to process signals and send commands.
7.6 Treatment of signals reported in active state only (transient signals)
In specific protocols, e.g. IEC 60870-5-103, some binary and analogue signals are only reported in active state. Those signals are called transient signals.
In contrast to the information given in device address lists, according to IEC 60870-5-104, all protection sig-nals from the device are reported as coming and going. However, there are signals from the system or from external devices that are reported as coming only.
Telecontrol Line
Kernel
Commands
Messages
M*
C* C*
M* Virtual logical device
Data model
control direction
Data model monitoring direction
Telecontrol
Line
object
IEC 60870-5-104 server
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Issues at processing
● In case of default processing, signals about processing issues are signaled only once and do not change their state thereafter.
● Some IEC 60870-5-103 protection signals are not included into the general interrogation of devices, so that they remain 'invalid' in the data model after startup.
Input status ‘w‘ – transient signal:
● With this status, the signal is internally reset after the coming message and initialized with 'valid' quality at startup.
Issues at a telecontrol line
● There is no going message at the control center. ● Transient signals are not reported with quality descriptor 'not topical' if the connection to the device is
disturbed.
Output status ‘r‘ – reset telegram
● With this status, a going message is sent after the coming message. The time difference between the messages is configurable, default setting is 0.
Input status ‘n‘ – signaling with 'not topical'
● If the connection to the device is disturbed, signals marked are reported with quality descriptor 'not topical'.
Special treatment with input status ‘b‘ - initialization with 'substituted'
● Signals marked are initialized with quality descriptor 'substituted' and the reset telegram is also re-ported with 'substituted'.
7.7 Chatter suppression
The following table shows the program objects into which chatter suppression is implemented:
Logic SI Line Master Device
x x x - x
The following figure illustrates the function:
In the data model the input status 'u' must be set for data points to activate chatter suppression.
If the number of transitions within the test interval exceeds the threshold value, then chatter suppression will be applied to the data point and the data point will be reported with quality 'blocked'. After that, no further
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
transitions are reported within the blocking time. When the blocking time has elapsed, transitions are counted again during the test interval.
If the number of transitions within the test interval is less than or equal to the threshold value, then chatter suppression will be reset for the data point. The data point will be reported with quality 'not blocked'. If the number of transitions exceeds the threshold value, the blocking time restarts.
The chatter suppression status is reported device-related by a single-point signal. This information is set when the first chatter suppression is applied in the device, and it is reset when the chattering of the last sig-nal ends.
7.8 Signal and command blocks in the data model
The following table shows the program objects into which signal and command blocks are implemented:
Logic SI Line Master Device
- - x - --
Blocks in the data model are set/reset through bitstring commands. These commands are confirmed with ACTCON. However, there are no data points, which could be acknowledged or queried, reflecting the status of the blocks.
The blocking command allows to select the data model (monitoring/control direction), the type of block (sig-nal/command block) and the addressing mode (individual/group block).
Thus, blocks in the data model can be set selectively for
• individual data points,
• groups of data points,
• device or ASDU addresses.
Blocks are always set in the output data model and encoded according to internal or IEC 60870-5-104 ad-dressing.
When a signal block is set, blocked data points are reported via the telecontrol line with quality descriptor 'blocked'. After that, for blocked data points, no spontaneous messages are sent anymore. However, even with a set signal block the data model is updated.
In general interrogations, the current status is reported with quality descriptor 'blocked'.
When the signal block is removed, data points are reported via the telecontrol line with the status 'not blocked'
Commands to data points with a set signal block are rejected with an ACTCON negative command confirma-tion.
Telegrams for setting and resetting blocks are described in section 10.3.4.2.
Input data model
monitoring direction
(Dev, DPAddr)
Output data model
control direction
(Dev, DPAddr)
Output data model
monitoring direction
Input data model
control direction
(ASDU, ObjAddr)
Signal blocks
Command blocks
Internal addressing Addressing acc. to IEC 60870-5-104
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
8 Station interlocking
8.1 Operation with station interlocking
In the device setting file, operation with station interlocking is enabled by the following parameter:
Parameters/Function parameters/Control/MAIN/SI active USER: Yes
This parameter sets the command procedure for switching devices (double command) in the device to 'Se-lect and execute' and also enables the station interlocking function on the communication module.
On the communication module, the operation mode with station interlocking can be set by starting the station interlocking program object when configuring the device in X30 Studio. In this operation mode, double com-mands are treated at the communication module as follows:
• The command procedure from the telecontrol lines to the device is set to 'Select and execute'.
• The commands are addressed on the communication module directly to the device. However, in or-der to check interlocking conditions, they are transmitted to the device via station interlocking.
8.2 Control procedures with station interlocking
8.2.1 Remote control with station interlocking
8.2.1.1 Enabling by station interlocking
Telecontrol line Station interlocking Device (CPU)
Select command, DT=46 Station interlocking check
Select command, DT=46 Bay interlocking check
ACTCON+ Select, DT=46
ACTCON+ Select, DT=46
Req. SI check, DT=33
Execute command, DT=46 Station interlocking check
Execute command, DT=46 Bay interlocking check
ACTCON+ Exec., DT=46 ACTCON+ Exec., DT=46
Return of control state, DT=31
ACTTERM+ Sel., DT=46 ACTTERM+ Sel., DT=46
8.2.1.2 Blocking by bay interlocking 1st or 2nd check
Telecontrol line Station interlocking Device (CPU)
Select/Exec. comm., DT=46 Station interlocking check
Select/Exec. command, DT=46 Bay interlocking check
ACTCON- Sel./Exec., DT=46
ACTCON- Sel./Exec., DT=46
Blocking signal BI, DT=33
8.2.1.3 Blocking by station interlocking 1st check
Telecontrol line Station interlocking Device (CPU)
Select command, DT=46
Station interlocking check
ACTCON- Select, DT=46
Blocking signal SI, DT=30
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
8.2.1.4 Blocking by station interlocking 2nd check
Telecontrol line Station interlocking Device (CPU)
Select command, DT=46 Station interlocking check
Select command, DT=46 Bay interlocking check
ACTCON+ Select, DT=46
ACTCON+ Select, DT=46
Req. SI check, DT=33
Execute command, DT=46
Station interlocking check
ACTCON- Execute, DT=46
Blocking signal SI, DT=30
Cancel command, DT=46
ACTCON+ Cancel, DT=46
8.2.2 Local control with station interlocking
8.2.2.1 Enabling by station interlocking
Telecontrol line Station interlocking Device (CPU)
Local command
Bay interlocking check
Station interlocking check Req. SI check, DT=33
Execute command, DT=46
Bay interlocking check
ACTCON+ Exec., DT=46
Return info of control state, DT=31
ACTTERM+ Sel., DT=46
8.2.2.2 Blocking by station interlocking
Telecontrol line Station interlocking Device (CPU)
Local command
Bay interlocking check
Station interlocking check Req. SI check, DT=33
Cancel command, DT=46
ACTCON+ Cancel, DT=46
Blocking signal SI, DT=30
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
8.3 System architectures with station interlocking
8.3.1 Station interlocking in central substation unit
The central substation unit can be a MiCOM S30 or an Easergy MiCOM P30 relay. In this configuration, all central functions are managed by this unit. The HMI and the telecontrol center use this unit to communicate with the devices.
The central unit also contains the interlocking logic and an interlocking function 'lock' or 'elock' for each switching device to be switched with interlocking. The interlocking logic receives the states of all switching devices and calculates the enabling signals 'enable on' ('enon') and 'enable off' ('enoff') for the interlocking functions.
A switching command sent from the HMI or the telecontrol center reaches the interlocking function and is ex-ecuted or rejected depending on the enabling signals.
In case of local control, the field unit sends a request for a station interlocking check to the corresponding interlocking function. If the operation is allowed, the station interlocking issues the switching enable by means of a switching command.
In this configuration, the command procedure 'Select and execute' must be used at the station bus for con-trolling the switchgear units with interlocking.
Gateway/central unit
HMI
Field unit 2 Field unit 1 Field unit n
Telecontrol center
lock lock lock
Interlocking logic
enon, enoff
Control state
Control state Control state
lock lock
Station bus
…
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
8.3.2 Station interlocking in field unit
The field units contain an interlocking function ('lock' or 'elock') for each switching device to be switched with interlocking. One field unit at the station bus contains the central station interlocking function. As an IEC 60870-5-104 client, it receives the states of all relevant switching devices. The interlocking logic calcu-lates the enabling signals 'enable on' ('enon') and 'enable off' ('enoff') and sends them to the interlocking functions in the field units.
A switching command from the HMI or the control center is sent directly to the addressed field unit, where the enable signal is checked by the respective interlocking function and the command is either rejected or executed.
In case of local control, in the field unit the request for station interlocking check is processed by the respec-tive interlocking function. If the operation is allowed, the station interlocking internally issues the switching enable by means of a switching command.
The command procedure at the station bus for controlling switchgear units with station interlocking can be set at the telecontrol lines. The command procedure required for interlocking, 'Select and execute', is only used within the field units.
Field unit with central function
HMI
Field unit 2 Field unit 1
Gateway
Telecontrol center
lock
lock
lock
Interlocking logic
enon, enoff
enon, enoff
Control state
Control state
lock
lock lock
Station bus
…
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
9 Checking and test functions
9.1 Permanent logging functions
Information about serious errors affecting the functionality of the software system is stored on the Ethernet board for subsequent evaluation. Those errors can lead to a system failure, which is assigned on the CPU to matrix point Operation/Cyclic measurements/Log. state signals/IEC/Comm. link faulty.
Additionally, an alarm is triggered at the CPU.
The program objects of the Ethernet board log the following information:
• Central error file The startup of the Ethernet board is documented in a central log file. Fatal errors that could lead to a program termination are also recorded into this central log file by all program objects.
• Data model log files Every program object reading a data model file writes its own log file that informs about errors oc-curred in the data model. Based on those log files, engineering errors can be identified and elimi-nated.
In addition, the following log files are written, facilitating error search in case of problems:
• Log file for control with interlocking In this log file, the station interlocking program object logs all control procedures with interlocking. Based on those log files, it is possible to determine whether the control procedure was error-free and why switching operations were rejected by the interlocking.
The following log files can be useful for error clarification by experts:
• Log file for startups of device interface In this log file, software startups of the communication module – in interaction with the CPU – are stored.
• Log file for startups of cyber security module
• Log files for telegram traffic with CPU The telegram traffic is stored in hexadecimal format in a ring memory consisting of 2 files with max. 0.5 MB capacity each.
Logging is done on the RAM disk of the Ethernet board. Please note that with each restart of the device, logs are lost.
9.2 Configurable logging functions
The program objects of the Ethernet board can log important information about their processes, so that pro-cesses can be analyzed afterwards. To this aim, program objects write a configurable number of files of con-figurable size. The file names are indexed. If the maximum number of files is reached, the index is set to 0 and the oldest file is overwritten, so that a ring memory is created.
The log files are stored at the RAM disk of the communication module. For example, for long-term record-ings, the number and size settings of the log files allow to control how much storage space is available for each program, and to avoid that information is lost if the RAM disk is full.
The log functions have only little influence on the performance of the program objects, so that they can be used in continuous operation without any problems.
For each program object, logging can be enabled or disabled via parameters of the ‘Operating test’ setting group. The following information is logged:
• Telegram traffic All telegram traffic to and from the kernel or, if applicable, via the interface to a communication server or at the communication interface to the outside (e.g. IEC 60870-5-104) is logged.
• Processing functions All information about processing functions, e.g. logic functions or command procedures, is logged.
Additionally, it is possible to set whether logging shall take place in decimal or in hexadecimal format.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10 Internal telegram interface
10.1 Telegram format and encoding
10.1.1 Introduction
Depending on the configuration, the system architecture can be very simple with only one telecontrol line, or very complex with maximum configuration. To engineer extensive communication functions, relevant ele-ments of the program objects' internal telegram interfaces are described here.
The internal telegram structure and the encodings used for type identification and cause of transmission are based on IEC 60870-5-104. Telegram elements are allocated as follows:
IEC 60870-5-104 Length Internal telegram Length
Type identification 1 Data type 2
Variable structure qualifier 1 Number of information ob-jects
1
Cause of transmission 1 Cause of transmission 1
Originator address 1 Originator address 2
Common address of ASDU 2 Device address 2
Information object address 3 Data point address 8
Time tag 7 Time tag 8
Notes:
• Internally, only single telegrams are used, i.e. the number of information objects is always 1.
• Of the 8 bytes of the data point address, 5 bytes are used.
10.1.2 Data types used
Coding Designation Data format
30 Single-point information with time tag SPI
31 Double-point information with time tag DPI
32 Step position information with time tag VTI
33 Bitstring of 32 bits with time tag BS32
34 Measured value, normalized value with time tag INT32
35 Measured value, scaled value with time tag INT32
36 Measured value, floating point value with time tag FP32
37 Integrated totals with time tag BCR32
38 Event of protection equipment with time tag DPI
70 End of initialization BS8
45 Single command with time tag SCO
46 Double command with time tag DCO
47 Regulating step command with time tag RCO
48 Set point command, normalized value with time tag
INT32BS8
49 Set point command, scaled value with time tag INT32BS8
50 Set point command, floating point value with time tag
FP32BS8
51 Bitstring of 32 bits, command with time tag BS32
100 General interrogation command with time tag BS8
101 Counter interrogation command with time tag BS8
102 Read command with time tag -
103 Synchronization command -
104 Test command with time tag BS16
Notes:
• All internal telegram types have a time tag.
• 16 bit measured values and set point values acc. to IEC 60870-5-104 are used internally with 32 bit.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.1.3 Cause of transmission
The following table shows the causes of transmission used:
Coding Designation
1 Cyclic
2 Background scan
3 Spontaneous
4 Initialized
5 Requested
6 Activation
7 Positive activation confirmation
8 Deactivation
9 Positive deactivation confirmation
10 Positive activation termination
11 Return info caused by a remote command
12 Return info caused by a local command
20 General interrogation
38 Counter read
Notes:
• The positive/negative bit (P/N) is used according to standard.
• The test bit (T) is used according to standard.
10.1.4 Data formats
Principally, the data formats used are identical to those described in standard IEC 60870-5-101, section 7.2.6 “Information elements”. Differences are described in the following table:
Data format Designation IEC 60870-5-101
SPI Single-point information 7.2.6.1
DPI Double-point information 7.2.6.2
VTI Value with transient state indication 7.2.6.5
SCO Single command 7.2.6.15
DCO Double command 7.2.6.16
RCO Regulating step command 7.2.6.17
BS8 Bitstring of 8 bits (1)
BS16 Bitstring of 16 bits (2)
BS32 Bitstring of 32 bits 7.2.6.13
INT32 Signed integer value of 32 bits (3)
FP32 Floating point value of 32 bits 7.2.6.8
BCR32 Binary counter reading of 32 bits 7.2.6.9
INT32BS8 Integer value of 32 bits with bit field of 8 bits
BS8: 7.2.6.39
FP32BS8 Floating point value of 32 bits with bit field of 8 bits
7.2.6.8 + 7.2.6.39
Notes:
(1) - BS8 := 8BS1[1..8]<0..1> (IEC 60870-5-4 type 6) (2) - BS16 := 16BS1[1..16]<0..1> (IEC 60870-5-4 type 6) (3) - INT32 := I32[1..32]<-231..+231-1> (IEC 60870-5-4 type 2.1) (4) - In the internal telegram format, a separate byte is used for quality descriptors.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.1.5 Quality descriptors
Quality descriptors for all data types are encoded according to IEC 60870-5-101, section 7.2.6.3:
B7 B6 B5 B4 B3 B2 B1 B0
IV NT SB BL 0 0 0 OV
IV - valid/invalid NT - topical/not topical SB - not substituted/substituted BL - not blocked/blocked OV - no overflow/overflow
10.1.6 Device addresses of program objects
The following table shows the addressing of the internal program objects:
Program object Device address
Kernel 1
Logic 5
Station interlocking 6
Device interface 15
Master station bus 1 16
Master station bus 2 17
IEC 60870-5-104 client 1 24
IEC 60870-5-104 client 2 25
Telecontrol line 1 32
Telecontrol line 2 33
Telecontrol line 3 34
Telecontrol line 4 35
Telecontrol line 5 36
IEC 60870-5-104 server 40
10.2 Telegram exchange with the device
10.2.1 Telegrams from protection part
10.2.1.1 Status
The scope of information depends on the type of protection and can be found in the address list provided for each device type. In general, all information that can be transmitted via the IEC 60870-5-103 interface is available.
During engineering with X30 Studio, all relevant status messages are offered for selection.
The internal data type used is 30 – single-point information with time tag.
10.2.1.2 Commands
In the protection part, all commands known from IEC 60870-5-103 are available. However, they are not ad-dressed via IEC 60870-5-103 function type and information number, but via the matrix point address.
Command Type Inf Data
Auto-recloser ON/OFF 015 064 Binary data: 1 – ON, 0 - OFF
Teleprotection ON/OFF 015 008
Device on-line/off-line 003 030
Reset of indications 021 010
Parameter subset 003 062 Parameter subset number 1...4
During engineering with X30 Studio, all relevant commands are offered for selection.
The internal data type used is 48 – set point command of 32 bit, normalized value with time tag
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Apart from that, all matrix points marked as writable in the address list ('Type ID Write' unequal to 00) can be written with the same data type.
10.2.1.3 Measured values
The scope of available measured values depends on the device type and can be found in the address list provided for each device type. They are addressed via the matrix point address, too.
During engineering with X30 Studio, all relevant measured values are offered for selection.
The data type used is 36 – measured value, short floating point value
10.2.1.4 Energy counters
The following counters from the address list are available:
Counters Type Inf Data
MAIN: Act.energy outp.prim 005 061 Signed counter value of 31 bits
MAIN: Act.energy inp. prim 005 062
MAIN: React.en. outp. prim 005 063
MAIN: React. en. inp. prim 005 064
The data type used is 35 – measured value of 32 bits, scaled value
10.2.2 Telegrams from control part
10.2.2.1 Switchgear units
The control state of switchgear units is signaled with data type 31 – double-point information with time tag. Devices are controlled by telegrams of type 46 – double command. The following table shows the ad-dressing of switchgear units:
External device
Type Inf Message
Inf Command
DEV01 242 01 65
DEV02 242 03 67
DEV03 242 05 69
DEV04 242 07 71
DEV05 242 09 73
DEV06 242 11 75
DEV07 242 13 77
DEV08 242 15 79
DEV09 242 17 81
DEV10 242 19 83
Depending on the device type and the bay type selected, there can be less switchgear units present.
10.2.2.2 Single-point information and single commands
The following table shows the addressing of single-point information of function group SIG_1. Single-point
information is signaled with data type 30 – single-point information with time tag.
Signal Type Inf
S001 249 01
S002 249 02
S003 249 03
… … …
S040 249 40
Device types P132, P433, P435, P631, P632, P633 have max. 12 single-point signals. Device types P139, P439, and P532 have max. 64 single-point signals.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
The following table shows the addressing of single commands of function group CMD_1. Single commands
are sent with data type 45 – single command.
Command Type Inf
C001 249 129
C002 249 130
C003 249 131
… … …
C026 249 154
Device types P132, P433, P435, P631, P632, P633 have max. 12 single commands. Device types P139, P439, and P532 have max. 26 single commands.
10.2.2.3 Pulse counter values
The following table shows the addressing of pulse counter values of function group Count. Counter values
are sent with data type 37 – counter value with time tag.
Counters Type Inf
Counter 1 248 1
Counter 2 248 2
Counter 3 248 3
Counter 4 248 4
10.2.2.4 Multiple signaling
Single-point information is signaled with data type 30 – single-point information with time tag. Confirma-tions of group signals are sent with data type 45 – single command.
Signal Type Inf
Group signal 1 248 65
Storing of group signal 1 248 66
Confirmation of group signal 1 248 67
Group signal 2 248 68
Storing of group signal 3 248 69
Confirmation of group signal 4 248 70
10.2.2.5 Circuit breaker trip signal
Circuit breaker trip signals are sent with data type 30 – single-point information with time tag.
Signal Type Inf
CB tripped 248 71
10.2.2.6 System information
The following table shows the addressing of system information, data type 33 – bitstring.
Signal name Type
Inf Data
Bay status 248 112 0 BS1 BS2 BS3
Type of Bay 248 113 Bay type number
Interlock violation 248 115 DCX 00 242 CMD
Request of station interlocking check 248 116 DCO 00 242 CMD
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Bay status BS1
7 6 5 4 3 2 1 0
| | | | | | | | 0 1 x x x x 0 1 Signal/measured value release 0 1 x x x x 1 0 Signal/measured value block 0 1 x x 0 1 x x Command enable 0 1 x x 1 0 x x Command block 0 1 0 1 x x x x Device not blocked/faulty 0 1 1 0 x x x x Device blocked/faulty 0 1 x x x x x x Physical addressing
Bay status BS2
7 6 5 4 3 2 1 0
| | | | | | | | x x x x x x 0 1 Operation with bay interlocking x x x x x x 1 0 Operation without bay interlocking x x x x 0 1 x x Operation with station interlocking x x x x 1 0 x x Operation without station interlocking x x 0 1 x x x x Enabling of remote control x x 1 0 x x x x Blocking of remote control 0 1 x x x x x x Enabling of local control 1 0 x x x x x x Blocking of local control
Bay status BS3
7 6 5 4 3 2 1 0
| | | | | | | | 1 0 x x x x x x Command blocking because of monitoring number of
CB operations
Interlock violation, request of station interlocking check
CMD: Command information number
DCO: Double command, consisting of
S/E QU DCS
S/E: QU: DCS:
0 = execution, 1 = selection 0 = termination of switching command after position status signal 1 = short time (1s), 2 = long time (20s) 3 = persistent command 01 = OFF, 10 = ON, 00,11 = inadmissible
DCX: Like DCO, most significant bit set for indicating an interlock vi-olation
Example: DCO=02H becomes DCX=42H
The following table shows the addressing of system information, data type 30 – double-point information.
Signal name Type Inf Data
Command execution in progress 248 117 1 - command in pro-gress, 0 - command not in progress
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.2.3 Signals from the communication module to the device
10.2.3.1 Permanently assigned signals from the communication module to the device
Besides commands, also message telegrams can be sent to the device. They are assigned to matrix points in the device and are available for processing.
The following table shows the permanently assigned signals on the communication module:
Signal in device Description
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Comm.link faulty
Internal malfunction of the commu-nication module, e.g. because of engineering or parameterization er-rors.
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Port A faulty
Fault of port A network connection
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Port B faulty
Fault of port B network connection
10.2.3.2 Assignable signals from the communication module to the device
The following table shows the addressing of assignable signals on the communication module:
Signal in device Type Inf
Operation/Cyclic measurements/Log. state signals/MAIN/Communication
error (1)
128 00
Operation/Cyclic measurements/Log. state signals/MAIN/SI commu.
disturbed 248 212
Operation/Cyclic measurements/Phys. state signals/VINP/Input 1
state (3) 0 1
Operation/Cyclic measurements/Phys. state signals/VINP/Input 2
state 0 2
… … … Operation/Cyclic measurements/Phys. state signals/VINP/Input 64
state 0 64
Operation/Cyclic measurements/Log. state signals/VINP/Input 1
faulty (4) 0 1
Operation/Cyclic measurements/Log. state signals/VINP/Input 2
faulty 0 2
… … … Operation/Cyclic measurements/Log. state signals/VINP/Input 64
faulty 0 64
(1) Communication error
To this matrix point, depending on the configuration, all information about the communication status should be assigned via a logical operation, e.g. an OR operation of communication errors of the engineered telecon-trol lines. See also section 10.3.3.
(2) SI communication error
To this matrix point, the communication error message of the line to the device where the station interlocking is running should be assigned. Setting 'SI communication error' has the effect that in the device, control is performed without SI and that the interlocking logic is switched to operation without SI.
(3) Virtual inputs
Via matrix points Operation/Cyclic measurements/Log. state signals/VINP/Input xx
state, any binary signals available at the communication module can be assigned for processing in the de-
vice.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
(4) Virtual inputs faulty
The matrix points Operation/Cyclic measurements/Log. state signals/VINP/Input xx
faulty are not specifically assigned. They are set if in the appropriate state messages, the quality is 'not
topical' or 'invalid'.
10.2.4 Settings from the device for the communication module
10.2.4.1 Permanently assigned settings from the device for the communication module
The following table shows the permanently assigned signals from the device to the communication module:
Signal in device Description
Parameters/Config. parameters/IEC/General enable USER If 'No' is set, IEC 60870-5-104 communication is blocked by disabling the IEC 60870-5-104 server and all clients; for de-
tails, see sections 10.3.5 and
10.3.7. Operation/Cyclic measurements/Log. state sig-
nals/MAIN/Subst. interl. act.
Depending on the state, a command for station interlock-ing status ON/OFF is gener-ated; for details, see section
10.3.8.
10.2.4.2 Assignable settings from the device for the communication module
The following table shows the addressing of single-point signals with system information:
Signal name Type Inf Data
Command execution in progress 248 117 1 - command in pro-gress, 0 - command not in progress
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Control blocking
248 177 1 – blocking 0 – no blocking
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Command blocking
248 208 1 – blocking 0 – no blocking
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Sig./meas.val.block
248 209 1 – blocking 0 – no blocking
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Command block. EXT
248 210 1 – blocking 0 – no blocking
Operation/Cyclic measurements/Log. state sig-
nals/IEC/Sig./meas.block EXT
248 211 1 – blocking 0 – no blocking
Blocking and activation of telecontrol lines can be engineered user-specifically. The required telegrams are described in section 10.3.
10.3 System telegrams of the communication module
10.3.1 Introduction
Program objects send and receive system telegrams for controlling and monitoring communication functions. Some of these system telegrams may be of interest to the user, since they contain important information about the state of the system and the program objects' communication interfaces. System telegrams are transmitted after a general interrogation to the respective program object and spontaneously at a change of state.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.3.2 Telegram interface of the kernel
Signal in device DT Dev Data point address Data
Sum fault of internal program objects 30 1 17 1 - faulty, 0 - not faulty
A sum fault is set if at least 1 program object is faulty. A program object is faulty if it terminates itself e.g. be-cause of data model or parameterization errors.
The sum fault status of internal program objects is permanently assigned to matrix point Operation/Cy-
clic measurements/Log. state signals/IEC/Comm.link faulty; for details, see section
10.2.3.1.
10.3.3 Telegram interface of the device interface
Signal in device DT Dev Data point address Data
SNTP/IRIG-B time synchronization faulty 30 15 FF01H 1 - faulty, 0 - not faulty
If parameter Parameters/Config. parameters/IRIGB/IRIGB/General enable USER is set to
'No', the state of the SNTP reception is signaled, otherwise the state of the IRIG-B reception is signaled.
10.3.4 Telegram interface of the IEC 60870-5-104 telecontrol line
10.3.4.1 Status signals and commands
Signal in device DT Dev Data point address Data
Processing status message 33 32-36 5 See (1)
Processing status command 51 32-36 6 See (2)
Telecontrol line status message 33 32-36 8000H See (3)
Telecontrol line status command 51 32-36 8800H See (4)
Double command procedure in progress 30 32-36 11 1 - yes 0 - no
Violation of control uniqueness check 30 32-36 12 1 - yes
Telegram buffer overflow message 30 32-36 16 1 – overflow (5)
Chatter suppression signal 30 32-36 10000H + device address
1 - ON 0 - OFF
(1) Processing status message
7 6 5 4 3 2 1 0
Data byte 1 0 0 START CMD SIG
Data byte 2 - 4 0 0 0 0 0 0 0 0
SIG: Status of monitoring direction 01 = Monitoring direction off-line
10 = Monitoring direction on-line
CMD: Status of control direction 01 = Control direction off-line 10 = Control direction on-line
START: Status of startup 01 = Startup terminated 10 = Startup in progress
(2) Processing status command:
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 CMD SIG
Data byte 2 - 4 0 0 0 0 0 0 0 0
SIG: Status command for monitoring direction 00 = No change
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
01 = Setting monitoring direction off-line 10 = Setting monitoring direction on-line
CMD: Status command for control direction 00 = No change
01 = Setting control direction off-line 10 = Setting control direction on-line
(3) Telecontrol line status message:
7 6 5 4 3 2 1 0
Data byte 1 0 0 STO ONL PRO
Data byte 2 0 0 0 B 0 0 S K
Data byte 3 - 4 0 0 0 0 0 0 0 0
PRO: Status projected/not projected 01 = Channel not projected 10 = Channel projected
ONL: Status on-line/off-line 01 = Channel off-line 10 = Channel on-line
STO: Status faulty/not faulty 01 = Not faulty 10 = Faulty
Faulty state of IEC 60870-5-104 telecontrol line
If a station is operated with only one IEC 60870-5-104 link, the status of the line corresponds to the status of this link. If the telecontrol system is operated redundantly, up to 8 clients per line can be connected. In that case, the status of the line is faulty if all links are faulty, and the status of the line is not faulty if at least one IEC 60870-5-104 link is operational. For details, see section 10.3.5.
Failure reason:
K = 1 - Communication server link faulty S = 1 - Static communication fault B = 1 - Fault caused by remote station permanently unready to take over
(4) Telecontrol line status command
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 ONL PRO
Data byte 2 - 4 0 0 0 0 0 0 0 0
PRO: Setting of projected/not projected 00 = No change 01 = Setting of not projected (not used) 10 = Setting of projected (not used)
ONL: Setting of on-line/off-line 00 = No change 01 = Setting of off-line 10 = Setting of on-line
(5) Telegram buffer overflow
A telegram buffer overflow occurs if a telegram to be sent cannot be queued before sending because the queue is full. In that case, older telegrams at the head of the queue are deleted until 20% of storage is avail-able again, and the triggering message is buffered at the end of the queue.
If the message 'telegram buffer overflow' is signaled via the telecontrol line (engineering), it is buffered at the head of the queue, at the position where the telegrams were deleted. A telegram buffer overflow is only sig-naled as coming.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.3.4.2 Commands for setting data model blocks
Commands for setting blocks in the data model are sent with data type 51 – bitstring command of 32 bits. The data point address is structured as follows:
7 6 5 4 3 2 1 0
Byte 0 (low) ASDU/device address low
Byte 1 ASDU/device address high
Byte 2 KE DM TY AD 0 0 DCO
0 Byte 3 (high) 00H
Data point address byte 2: mode
KE Identifying bit for data model blocks 0 - Not used here 1 - Data model blocking command
DM Data model identifier 0 - Data model in monitoring direction 1 - Data model in control direction
TY Type of block 0 - Signal block 1 - Command block
AD Addressing identifier of block 0 - Individual block 1 - Group block
DCO Blocking command 01 - Resetting of block 10 - Setting of block
Data are set depending on the addressing identifier (AD):
Data with addressing identifier AD = 0 - individual blocks
7 6 5 4 3 2 1 0
Data byte 0 (low) Data point/object address byte 0 (low)
Data byte 1 Data point/object address byte 1
Data byte 2 Data point/object address byte 2
Data byte 3 (high) Data point/object address byte 3 (high)
If data bytes 0 to 3 are equal to 0, the block for all data points of the addressed device / the common address of ASDU is set, respectively reset.
Data with addressing identifier AD = 1 - group blocks
7 6 5 4 3 2 1 0
Data byte 1 (low) Group low
Data byte 2 Group high
Data byte 3 Number of bits group (1 … 16)
Data byte 4 (high) Start bit group (0 … 31)
In case of group blocks, filtering occurs by a group identifier (e.g. bay number) that is encoded in a bit field in the data point or information object address.
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.3.5 Telegram interface of the IEC 60870-5-104 server
Signal in device DT Dev Data point address Data
Global status signal of server 33 40 5 See (1)
Global status command to server 51 40 6 See (2)
Channel 0 status IEC104 link 0 33 40 8000H See (3)
Channel 0 status IEC104 link 1 33 40 8001H See (3)
… … … …
Channel 0 status IEC104 link 7 33 40 8007H See (3)
Channel 1 status IEC104 link 0 33 40 8100H See (3)
Channel 1 status IEC104 link 1 33 40 8101H See (3)
… … … …
Channel 1 status IEC104 link 7 33 40 8107H See (3)
… … … …
Channel 7 status IEC104 link 0 33 40 8700H See (3)
Channel 7 status IEC104 link 1 33 40 8701H See (3)
… … … …
Channel 7 status IEC104 link 7 33 40 8707H See (3)
(1) Global status signal of IEC 60870-5-104 server
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 0 0 ONL
Data byte 2 - 4 0 0 0 0 0 0 0 0
ONL: Status on-line/off-line 01 = Server off-line 10 = Server on-line In case of off-line status, IEC 60870-5-104 communication is disabled at the network interfaces, i.e. no
links are accepted by the clients.
(2) Global status command to IEC 60870-5-104 server
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 0 0 ONL
Data byte 2 - 4 0 0 0 0 0 0 0 0
ONL: Status on-line/off-line 01 = Setting the server off-line 10 = Setting the server on-line
(3) Status signal of IEC 60870-5-104 link
7 6 5 4 3 2 1 0
Data byte 1 0 0 STO ONL PRO
Data byte 2 - 4 0 0 0 0 0 0 0 0
PRO: Status projected/not projected 01 = Channel not projected 10 = Channel projected
ONL: Status on-line/off-line 01 = Channel off-line 10 = Channel on-line
STO: Status faulty/not faulty 01 = Not faulty 10 = Faulty
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
10.3.6 Telegram interface of the IEC 60870-5-104 master station bus
Signal in device DT Dev Data point address Data
Processing status message 33 10/11 5 See (1)
Processing status command 51 10/11 6 See (2)
Status signal of server link 33 10/11 8000H + server address (3)
See (4)
(1) - Data of processing status message
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 CMD SIG
Data byte 2 - 4 0 0 0 0 0 0 0 0
SIG: Status of monitoring direction 01 = Monitoring direction off-line
10 = Monitoring direction on-line
CMD: Status of control direction 01 = Control direction off-line 10 = Control direction on-line
(2) Data of processing status command:
7 6 5 4 3 2 1 0
Data byte 1 (low) 0 0 0 0 CMD SIG
Data byte 2 - 4 (high) 0 0 0 0 0 0 0 0
SIG: Status command for monitoring direction 00 = No change
01 = Setting monitoring direction off-line 10 = Setting monitoring direction on-line
CMD: Status command for control direction 00 = No change
01 = Setting control direction off-line 10 = Setting control direction on-line
(3) Server address
The server address corresponds to the internal device address under which the server is listed by the com-munication kernel.
1. IEC 60870-5-104 master (address 16): server addresses 64 to 95 (40H-5FH) 2. IEC 60870-5-104 master (address 17): server addresses 96 to 127 (50H-6FH)
(3) Data of status signal of IEC 60870-5-104 link
7 6 5 4 3 2 1 0
Data byte 1 0 0 STO ONL ANG
Data byte 2 - 4 0 0 0 0 0 0 0 0
ANG: Status registered/not registered 01 = Not registered 10 = registered ONL: Status on-line/off-line 01 = Server off-line 10 = Server on-line STO: Status faulty/not faulty
01 = Not faulty 10 = Faulty
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
Failure reason:
K = 1 - Communication server link faulty S = 1 - Static communication fault B = 1 - Server permanently unready to take over
10.3.7 Telegram interface of the IEC 60870-5-104 client
Signal in device DT Dev Data point address Data
Global status signal of server 33 24/25 5 See (1)
Global status command to server 51 24/25 6 See (2)
(1) Global status signal of IEC 60870-5-104 server
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 0 0 ONL
Data byte 2 - 4 0 0 0 0 0 0 0 0
ONL: Status on-line/off-line 01 = Server off-line 10 = Server on-line In case the status is off-line, IEC 60870-5-104 communication is disabled at the network interfaces,
i.e. no links are established to servers.
(2) Global status command to IEC 60870-5-104 server
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 0 0 ONL
Data byte 2 - 4 0 0 0 0 0 0 0 0
ONL: Status on-line/off-line 01 = Setting the server off-line 10 = Setting the server on-line
10.3.8 Telegram interface of the logic/station interlocking
Signal in device DT DEV Data point address Data
Status signal of station interlocking 33 6 5 See (1)
Status command to station interlocking 51 6 6 See (2)
Double command procedure in progress 30 5/6 11 1 - yes 0 - no
Violation of control uniqueness check 30 5/6 12 1 - yes
Blocking signal of station interlocking 30 6 100H + device address command
1 - ON
Signal of SI blocking cause Station interlocking
30 6 80H + blocking cause Cause of interlock violation (3)
1 – ON
Chatter suppression signal 30 5/6 10000H + device address 1 - ON 0 - OFF
(1) Status of station interlocking
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 0 0 STA
Data byte 2...4 0 0 0 0 0 0 0 0
STA: Status of station interlocking 01 = Interlocking OFF
10 = Interlocking ON
[Communication] IEC 60870-5-104 Protocol
Schneider Electric
(2) Status command to station interlocking
7 6 5 4 3 2 1 0
Data byte 1 0 0 0 0 0 0 STB
Data byte 2...4 0 0 0 0 0 0 0 0
STB: Status command to station interlocking 01 = Enabling of interlocking
10 = Enabling of interlocking
(3) Relative addresses for cause of interlock violation
0 - Switching operation not allowed 1 - Enabling signal invalid 2 - No select command before execution 3 - Command procedure still in progress 4 - Negative confirmation of selection 5 - Negative confirmation of execution 6 - Negative confirmation of cancelling 7 - Invalid command telegram 8 - Invalid command confirmation 9 - Timeout of procedure 10 - Engineering error 11 - Enabling (positive)
A cause of interlock violation is only signaled as coming.