easyair sns210...powerpoint presentation author priyanka kumar created date 3/23/2020 4:20:13 pm

11
EasyAir SNS210 Application Usecases Priyanka Kumar BG LED Q1 2020

Upload: others

Post on 09-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

EasyAir SNS210Application Usecases

Priyanka Kumar

BG LEDQ1 2020

Page 2: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

For Offices

Page 3: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Conference Room

Configuration Parameter Value

Field task level 100%

Eco on level 100%

Background light level 20%

Daylight based control Disabled

Occupancy based control Enabled

Occupancy mode Auto on/Auto off

Group Occupancy Sharing Enabled

Group Light Behaviour Eco on Level

Hold time 15 min

Grace fading 10 sec

Prolong time 15 min

Infinite Prolong time Disabled

In a meeting room area, lights are required to operate in automatic mode. It is desirable to have manual control via switches.

• Enable scene setting at group level such as presentation mode with a manual switch.

• Attendees would prefer that all lights go to maximum brightness i.e. Group Light Behaviour: Eco-on level

Page 4: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Corridor

Configuration Parameter Value

Field task level 100%

Eco on level 100%

Background light level 20%

Daylight based control Disabled

Occupancy based control Enabled

Occupancy mode Auto on/off

Group Occupancy Sharing Enabled

Group Light Behaviour Background Light Level

Hold time 60 min

Grace fading 10 sec

Prolong time 60 min

Infinite Prolong time Disabled

In a typical corridor area, lights are required to remain switched on as long as there is an occupant in any of the close-by seating areas or meeting rooms. • Increase hold time and prolong time

Page 5: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Staircase

Configuration Parameter Value

Field task level 100%

Eco on level 80%

Background light level 5%

Daylight based control Disabled

Occupancy based control Enabled

Occupancy mode Auto on/Auto off

Group Occupancy Sharing Enabled

Group Light Behaviour Background Light Level

Hold time 15 min

Grace fading 10 sec

Prolong time -

Infinite Prolong time Enabled

For staircase and elevator areas, lights are required to never switch off and operate at low dim level. • Lower light levels• Infinite Prolong time

Page 6: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Office Canteen

Configuration Parameter Value

Field task level 100%

Eco on level 100%

Background light level 20%

Daylight based control Enabled

Occupancy based control Enabled

Occupancy mode Auto on/Auto off

Group Occupancy Sharing Enabled

Group Light Behaviour Background Light Level

Hold time 15 min

Grace fading 10 sec

Prolong time 100 min

Infinite Prolong time Disabled

In a canteen or coffee area, lights are required to operate in automatic mode and remain switched on for a longer period. Manual control via switches is desired.

• Enable scene setting at group level such as celebration mode with a manual switch.

• Longer Prolong Time

Page 7: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Storage Room

Configuration Parameter Value

Field task level 100%

Eco on level 100%

Background light level 20%

Daylight based control Disabled

Occupancy based control Enabled

Occupancy mode Auto on/Auto off

Group Occupancy Sharing Enabled

Group Light Behaviour Background Light Level

Hold time 1 min

Grace fading 10 sec

Prolong time 7 min

Infinite Prolong time Disabled

In a storage area, lights are required to operate in automatic mode and switch off as soon as vacancy is detected. • Short Hold Time and Prolong Time

Page 8: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

For Schools

Page 9: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Classroom

Configuration Parameter Value

Field task level 100%

Eco on level 100%

Background light level 20%

Daylight based control Enabled

Occupancy based control Enabled

Occupancy mode Auto on/Auto off

Group Occupancy Sharing Enabled

Group Light Behaviour Eco-on Level

Hold time 15 min

Grace fading 10 sec

Prolong time 15 min

Infinite Prolong time Disabled

In a typical classroom, lights are required to operate in automatic mode and switch off when students/teacher leave the room. Manual control via switches is desired.

• Enable a switch per zone e.g. general seating area could define a zone whereas board light could define another zone.

Page 10: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Toilet Areas

Configuration Parameter Value

Field task level 100%

Eco on level 100%

Background light level 20%

Daylight based control Disabled

Occupancy based control Enabled

Occupancy mode Auto on/off

Group Occupancy Sharing Enabled

Group Light Behaviour Eco-on Level

Hold time 15 min

Grace fading 10 sec

Prolong time 15 min

Infinite Prolong time Disabled

In toilet areas, all individual lights should switch on Eco-on level. Daylight based dimming is not needed. • Group Light Behaviour should enable all the lights to go to

maximum light level

Page 11: EasyAir SNS210...PowerPoint Presentation Author Priyanka Kumar Created Date 3/23/2020 4:20:13 PM

Corridor

Configuration Parameter Value

Field task level 100%

Eco on level 100%

Background light level 20%

Daylight based control Disabled

Occupancy based control Enabled

Occupancy mode Auto on/off

Group Occupancy Sharing Enabled

Group Light Behaviour Background Light Level

Hold time 60 min

Grace fading 10 sec

Prolong time 60 min

Infinite Prolong time Disabled

In a typical corridor area, lights are required to remain switched on as long as there is an occupant in any of the close-by seating areas or meeting rooms. • Increase hold time and prolong time