LAFON’s reference : 18295050 EASY CARB Terminal International Instruction Book Date : 05/2009 version E EASY CARB TERMINAL 18 29 53 00 Release (International version) Installation Instruction User’s Manual Maintenance Book Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCE Tél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121 1/47

Upload: lethu

Post on 03-May-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

  EASY CARB TERMINAL18 29 53 00 Release (International version)

Installation Instruction User’s Manual

Maintenance Book

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr1/39

Page 2: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

BEFORE ANY USE OR INTERVENTION ON ANY PART DEPENDING OF ATEX

DIRECTIVE (guideline), READ ATTENTIVLY THE SECURITY

INSTRUCTION LEAFLET.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr2/39

Page 3: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Update History Table

Version Pages Changed Nature of change Date (Day/M/Year)

A CREATION 13/04/2008

B Global Modification 09/09/2008

C 1; 8; 9; 16; 32 RFID Integration 16/01/2009

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr3/39

Page 4: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

1) CONTENTS

Summary)) Update History Table..........................................................................................................................................2

1) CONTENTS........................................................................................................................................................3

2) Generalities......................................................................................................................................................5

3) Technicals specificities......................................................................................................................................5

4) Rules and status / regulation ( ??? norme de règlementation)........................................................................6

5) Kit Content / Kit composition...........................................................................................................................6

8) Power protection..............................................................................................................................................6

10) Overview map, nomenclature (part list) and spare part................................................................................7

a) EasyC@rb Terminal..............................................................................................................................7

11) Encumbrance (or Space encumbrance)..........................................................................................................9

12) Installation.....................................................................................................................................................9

a) Mounting the fixing clamp, B-type: the small one.............................................................................10

b) Fitting the extra whistand one...........................................................................................................12

13) Maintenance procedure rules......................................................................................................................12

14) Leaflet utilization’s electronic card..............................................................................................................12

a) Power supply and Network Links: Generalities..................................................................................13

b) Rs485 Local Network cabling rules.....................................................................................................13

c) Typical Examples of wiring an rs485 network interfaced with our equipments.................................13

15) The Display...................................................................................................................................................14

16) Identification Mains.....................................................................................................................................16

17) Terminal function configuration: “Terminal Config”....................................................................................17

a) Functioning mode configuration........................................................................................................17

b) Rs485 Local Network..........................................................................................................................17

c) Default Ethernet Network configuration process..............................................................................18

d) AbiPass nozzles configuration............................................................................................................18

18) Fuel function configuration..........................................................................................................................20

a. Dispensing Mode...............................................................................................................................21

b. Counting channel...............................................................................................................................21

c. Functioning........................................................................................................................................23

d. Pulse Weight......................................................................................................................................23

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr4/39

Page 5: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

e. Gauging..............................................................................................................................................24

19) Functioning check........................................................................................................................................26

a. The power supply...............................................................................................................................26

b. Backlighting display............................................................................................................................26

c. The Keyboard / Keypad......................................................................................................................26

d. Everlasting (perpetual, perennial) totalizer(s)....................................................................................27

e. The identification (ID)........................................................................................................................27

f. The printer (option)...........................................................................................................................28

g. The fuel dispensing............................................................................................................................28

h. Error list table....................................................................................................................................29

20) Software downloading.................................................................................................................................30

a. Downloading by communication protocol.........................................................................................30

b. Downloading by EuroGestion programmer (scheduler).....................................................................30

21) “Synoptical” Cabling pattern (chart)............................................................................................................31

22) EasyCarb interfacing with CMP....................................................................................................................32

23) EasyCarb interfacing with a MicroBasic Card...............................................................................................33

24) Annexes (Attachments)................................................................................................................................34

a. Synoptical of Terminal configuration menu.......................................................................................34

b. Synoptical of Fuel configuration menu..............................................................................................35

25) Spare parts list.............................................................................................................................................36

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr5/39

Page 6: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

2) Generalities

The E@syCarb terminal is a private fleet management system connected to the EasyConnect software. It allows to access at (to) a fuel dispensing (3 product maximum) a vehicle or/and a person. It regroups in one device the site controller functions, the HMI interface (terminal) and product counting (metering). EasyC@rb is principally intented to basic architecture site (managing a single dispenser). Hence there is no rs485 local network to deploy.

Even so, for the more important (“meaty”) site where the usage, for example, who requires the addition of terminal, calculator or the both. In consequence, the cabling in Rs485 protocol is necessary in.

The EasyCarb Terminal manages a LCD screen divided in 2 separates zone.The upper display zone is used for the refueling (volume display, product, and nozzle)The lower display zone is constituted with 4 lines, 20 digits each. It’s used for managing authorization.The EasyC@rb terminal has got a 21 Alfa numeric keyboard (cell-phone type) with 21 keys.The EasyC@rb allows to:

Identify a person with the following means:o Alfa numeric keypad (cellular phone type) of 21 keys.o Lafon badgeso Abipass Lafon antennao ISO2 Magnetic cardo RFID badges (contactless)o ISO 7816 Smart card

After identification, an authorization can be issued or denied for a refueling.

The EasyC@rb license can’t manage access or washing. For this features an add-on license is necessary.

3) Technicals specificitiesPower supply 230 VAC – 50 Hz / 60Hz3 Pulsers entries A 63 mA temporized fuse Electrical protection  1 or 2 channel. 5V power supply3 Nozzle entries Dry contact (lift closed contact)Pulse Maximal frequency 500 Hz (Hertz)3 Engine (motor) command. VAC 230 by static relay supplied.

1 A max (resistive load

Pulse weight Adjusting from 0.000001 to 0.999999 L (Liters)Perpetual Totalizer counting channel 00000000 to 99999999 L (Liters)Displayed volume From 0.01 to 999999 L (Liters)Using temperature limitation Celsius: from -10°C  to + 50°C

! Disclaimer !Every kind of non-respect of this present technical instruction disclaims any responsibility and any liability in (to) LAFON Company.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr6/39

Page 7: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

4) Rules and status / regulation ( ??? norme de règlementation)The EasyC@rb terminal is approved to the following European legislation. It respects the laws in force below.

Low Tension directive 72/*23/CEE modified by the 93/68/CEE (CE mark) The Electricals Low tension installation rules: NFC15-100 The 94/62/CE:  packaging and packaging wastage

5) Kit Content / Kit composition.The containing kit:

1 EasyC@rb terminal part number:  1 82 95 30 0 1 spare-part fuse 3 fixation devices binding The cutting template  (( cutting pattern/ layout) This notice instruction (this technical notice / this instructions note / this instruction manual)

6) Place to install each (every) parts / devices.--------------------------------------------All the items of this kit, must be assembled any outside ATEX area.

7) People Safety / Save -------------------------------------------------------------------------Do not power connection. ((or (Don’t make any connection (plugs) in tension)))

Please, be sure to follow the instructions for the safety persons.

8) Power protectionPower supply features (specificities):

Power supply tension 230V AC 50 Hz—A 230 V AC 50Hz Tension power supplied. Protection by a built-in 63 mA fuse temporized on the EasyC@rb electronic card (circuit).

The system must be protected against The shorts (circuits) The overload(s)

An upstream (en amont) protection of the Electronic (circuit) card breaker (circuit-breaker) is recommended by.The installation and protection mode must be true to the NFC 15-100.-----------------------------------------

9) People Safety(protection) ---------------------------------------------------------------Insure the people safety by connecting with the bounding strip (reference 18280620) between the terminal framework metal sheet (1829503) and the EasyC@rb device framework.Check the connections from the ground to the metallic part.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr7/39

Page 8: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Verify (keep tabs on) if the device (dispositive) is really protected by a differential “circuit breaker” with a caliber which it must be in accordance with    (doit être conforme)    the NFC- 15-100.   

10) Overview map, nomenclature (part list) and spare part.

The maintenance must be imperatively made with the manufacturer’s original equipment to respect the regulatory requirements related to the product (item). Use only genuine partLAFON S.A Company no longer has any liability if this requirement is not complied with.

a) EasyC@rb Terminal.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr8/39

Page 9: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr9/39

N° Reference  Type  Qty Descritpion Description 21 18295230 S/E 1 EasyC@rb  metal sheet2 18295000 S/E 1 EasyC@rb electronic cpu card3 00032046 14 00930073 1  4 INOX5 18295080 S/E 4 Low-cost Enhanced Display 6 18295200 17 18295220 18 18295210 1 Easy Keyboard9 00929196 10 310 00392003 5 INOX

11 00032020 4 Bounding strip

12 04709160 2

13 04709161 1

14 18295290 2 Easy Terminal Linking Sticker EASY CARB

15 18295310 1

16 18295320 1

17 01609044 1

18 01229000 1

19 18280620 1 500mm Qualys Ground 

20 18294040 1 m

21 18295050 1 mL Installer/ Maintainer Notice Easy Carb Terminal

Page 10: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

11) Encumbrance (or Space encumbrance)

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr10/39

Page 11: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

12) Installation

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr11/39

Card reader releaseOn top and underside space allowed to theDisassembly 3 cm mini.

Lafon badges reader release.Up space allowed to disassembly the companion flange.

Page 12: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

a) Mounting the fixing clamp, B-type: the small one.

Once the EasyC@rb device clipped inside the dispenser head framework. Bottom side, from the back fix and mount the terminal clamping part. 

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr12/39

Integrator clearance kit:250 mm depth allowed to the cover (wood) at 45° (degree).

Printer release: Wright space allowed to the exit of the roller printer.

Page 13: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Snap the fixing clamp on the both screw head. Apply a fitting clamping with an appropriate size screwdriver.

Don’t tighten with any clamp (or: don’t use with any clamping clamps).

b) Fitting the extra whistand one.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr13/39

Page 14: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

In the same way, after snapping the 2 clamp part onto own each screw-head, with an acceptable screwdriver size, turn and apply an appropriate clamping.

DON’ T USE WITH CLAMPING FORCEPS(traduction française: Ne pas utiliser de serrage avec une pince)

13) Maintenance procedure rulesTo prevent any damage that might result in electric shock or fire. Disconnect the Main power prior to any up keeping work. 

Any kind of intervention on the electric part must be done by an approved technician.

14) Leaflet utilization’s electronic card

a) Power supply and Network Links: GeneralitiesHigh Voltage. The EasyC@rb card is supplied with 230V AC.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr14/39

Page 15: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

If the EasyC@rb card required to be connected on the Rs485 network with a STP cable we recommend using this one:

Rs485 cable reference: BELDEN 1 Shielded Twisted-Pair (0.22 mm² section). With drain. Part Number: B9841 .

b) Rs485 Local Network cabling rulesHere below the rs485 typology. It’s also the only way to connect any devices on it and to make it properly.

EasyC@rb device is of 2 Rs485 connectors. Bus type:

Note: The EasyC@rb Terminal is equipped with a single rs485 connector. (3 wires, 3 channels from up to down:  C, B, and A)

Warning: It’s strictly forbidden to cable, to make an RS485 network wiring star:

c) Typical Examples of wiring an rs485 network interfaced with our equipments (products, “Easy” Range devices) (( or rs485 network where it’s connected our equipment using CasesRs485 Network Cases used to with our equipments.)))

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr15/39

Page 16: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

The Rs485 3 wires connection from the first to the last card respects this following links:I. A to AII. B to BIII. C to C (cable shielding)

On the Rs485 network, each (1 and 2 on the scheme) ENDPOINT’s resistors terminations must be necessary switched on. The 2 switches are activated to eliminate any kind of reflection line. (See the Establishment Map).

15) The DisplayThe EasyC@rb Card has 2 pin connectors which can drive 2 black-lighted display panels of 128*64 dots each. 

Their displayed data are strictly the same. So, it allows making for (give, assure) the recopy feature.

Or: As the transmitted data from each connector are the same. It enables to ensure the recopy feature

On each display, 2 specific areas have been created.

Upper zone: Numerical information data. This area displays data related to Volume, summarizing (total) and error during refueling.

Lower zone: 4 lines. This area is reserved to inform the user about the site management.

It displays:  Names, wording, date/hours, identification, messages, and device configuration

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr16/39

1st

2nd

Page 17: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

“”The characters height used to display volume allows visualizing the volume data to more than a 4 meter distance at least

Or

The digit height used to display the volume allows to clearly visualizing information at a range up to 4 meter at least

                For notice needs, the 4 select keys   are associated to each line EasyC@rb terminal’s display. In consequence from up to down:

= F1 key

= F2 key

= F3 key

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr17/39

Page 18: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

= F4 key

The   and   keys allow to navigate into both mode setting terminal.

16) Identification Mains

Identification Type Device support Mark on StickerSecret code and name 

KeyboardKeyboard Keyboard dab

EASY, GLS, Connection and Stand-alone Abiself, Badge

Badge Lafon Badge reader

Abipass Abipass antenna ISO 2 or Abipass antenna

ISO 2 Magnetic card reader (ISO2 track only)

ISO 2 or Abipass antenna

Smart-card reader (ISO 7816) Smart-cardRFID Contactless Contactless badge ISO 2 or Abipass antenna

Below the card’s mapping (identification of the EasyC@rb card) with its various buttons and switches.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr18/39

Page 19: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

17) Terminal function configuration: “Terminal Config”Important pointTo enter into the terminal configuration menu, visualize the current setting, test identifications devices plugged to EasyC@rb, and change the default IP setting, just press simultaneously the 

both foll owing keyboard keys: ▲ (up arrow key) and ● (dot key). Thereafter, the user has to type the 4 digit key-code. By default it’s 0557. In this way, you can access to the Terminal Config Menu for checking and edit some features.a) Functioning mode configuration   The EasyC@rb card manages only the fuel terminal function. The others features, Access and Washing, are not available.

b) Rs485 Local Network   On the Rs485 network, the EasyC@rb card does not require any addressing network configuration for  working with every Easy range devices.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr19/39

Page 20: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

c) Default Ethernet Network configuration process   The default IP stored is: 192.168.1.87 

This feature is included into the EasyC@rb Configuration Menu. It enables to set (to map) EasyC@rb IP default connection mode into the customer local network. 

How to access it:1.    See “Important point” chapter 17.2.    Go to “Terminal Config”Default Ip ConfigEdit Config

Type all required values: Ip, Mask, Gate and / or PortType V keyA key V: yes (Save your current typing) A key A to reset the Terminal with the correct values.See Tree diagram EasyC@rb configuration Menu page xxxx.

How to use it:1. Press the ACQ button (press-stud) into the EasyC@rb card.2. Wait the L2 led lights-up. Red color3. Relate to the EasyConnect Help to download the xml file into easyc@rb.

The d) AbiPass nozzles configuration   If the ABIPASS system (Automatic identification system) fits up (equips) the site, the fueling terminal has to establish the communication bridge between the nozzle number ID (as satellite) and the “master” dispenser.

Note: This operation could be done only if the fuel terminal has been configured by the maintainer through the maintenance mode (EasyC@rb card) Maintenance mode (See on Important point§ 17) Terminal Config MenuAbipass If this feature is normally configured the user should be seeing:  

LAFON test site16/09/2009 15:52:49

Identify Driver

Note: All the following messages:

“OUT OF SERVICE: LANGAGE” or “OUT OF SERVICE: CONFIG” or “SATELLITE SLAVE ADRESS OUT of SERVICE”…,

Indicate that the Terminal is not able to receive any kind of wrights setting from the site controller.

In this case, please check the site controller ABIPASS setting.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr20/39

Page 21: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr21/39

Terminal DISPLAY INSTALLER ACTIONLAFON Test site16/02/2009 15:52:49

Indentify driver

To go into EasyC@rb system test configuration Menu. Push the Config installer press-stud (see the back framework sticker).

Terminal ConfigFuel Config

Press F1 key to select the Terminal function configuration

Abipass ConfigIdentificationPrinterDefault ip config

Press F1 key to select Abipass Config

Dispenser 01Dispenser 02Dispenser 03

The dispenser list or the dispenser displays on.Press F3 key to configure the dispenser N°3

Dispenser 03Nozzle GONozzle 1: 0000Nozzle 2: 0000

It can be possible (potential) to configure 2 physical ABIPASS nozzles for 1 logical nozzle (Gasoil Nozzle). I.E.: In the case of Satellite nozzle.The “ >” cursor shows the Abipass nozzle to configure. Unhook the kitted (manned) warden (custody) Abipass nozzle.Overbalance the nozzle during 3 seconds like as you put it into a tank and hang-up it to display the Number nozzle onto the EasyC@rb display.

Dispenser : 03GO nozzleNozzle 1: 0504Nozzle 2: 0000

“Nozzle 1” normally displays. If there is another one to configure, press the Up and Down arrows keys to move the cursor face to “Nozzle 2” line or just press V key to validate this choice.

Dispenser : 01Dispenser : 02Dispenser : 03

This message displays, so press A key if there is no more Abipass nozzles to set-up

At this step, Press the V key to save the Abipass setting (inside the EasyC@rb system memory.) 

Abipass Config

SavingA: No V:Yes

Page 22: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Next page: ABIPASS nozzle configuration procedure, I.E.: linked to the 3rd Dispenser.

18)  Fuel function configurationThe refueling feature can be tested irrespective of (independently from) the management connected mode function). Duly (like this, that way) the installer could configure the fuel function and makes some checking with autonomous manner.

Important Notes (Key-Point): Config Fuel MenuFirst of all, the configuration modification of the Fuel Terminal setting is carried out by pressing the “Config Installer” press-stud. However, it’s recommended to open the dispenser head door for handling and access to the EasyC@rb card.To configure this mode (Config Fuel Menu), use the arrows keys and the keypad to adjust the settings. 

ORTo modify the configuration

On the EasyCarb card lower area left side, push the “CONF” buttonTo check the configuration and change only the IP feature:

Press the arrows key and type the secret code (by default 0557)

Table ReminderConfiguration menus on the EasyCarb display Access mode Where and how to push Viewing Editing

Config Terminal Key combination 2 Arrows keys and keypad secret code  Yes IP setting only

Fuel Config “CONFIG” Press-stud

On the EasyCarb card.Left side lower area. Yes All the features

The synoptic’s configuration menu of fuel is given in annex.a. Dispensing Mode

There are 2 separate functioning modes for fuel dispensers :o Non-simultaneous Modeo Simultaneous Mode

The Non-Simultaneous mode:It’s defines with 1F 1P, 1F 2P or 1F 3P signs which signify 1 Face 1 Nozzle, 1 Face 2 Nozzles or 1 Face 3 Nozzles. When To the lifted Nozzle, the delivery (dispensing) starts. Only 1 product is distributed (delivered, fueled, dispensed) at the same time.

 The Simultaneous mode:

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr22/39

Page 23: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

It’s defines with CS 1P, CS 2P or CS 3P signs who signify Simultaneous Counting 1 Nozzle, Simultaneous Counting 2 Nozzles, or Simultaneous Counting 3 Nozzles. From each lifted nozzle a filling is initialized. The dispensed volume amount who are displayed, is a single oneThe amount volume who displays inside the upper area display totalizes all the last transactions from each lifted nozzles. It displays them to a loop slideshow every 2 seconds.OrThe amount volume who displays in the upper area display totalizes all the last transactions from each lifted nozzles. it displays them to a loop slideshow every 2 seconds.

(The volume's amount displayed and dispensed is a single one.)Respectively the channel A is for the first nozzle, B for the second and C for the third.Note:For a single nozzle, theses both functioning modes (1F 1P and CS 1P) are nearly the same.

b. Counting channelFor each pulse entries, it can be possible to determinate the number of counting (metering) voices.

To each pulse entry, it can be to define the number of counting channel (1 or 2). In fact … . In the case where only 1 counting (metering) channel is configured. The disconnection control system of the counting (metering) voice of the calculator is disabled.

Example: Process to define 1 single counting entry from the dispenser number 3.

Terminal DISPLAY INSTALLER ACTIONIn order to  modify the EasyC@rb’ system configuration, press the Config Installer pushbutton (See sticker)

So as to select the Wright function configuration, Press the F2 Key to configure the Config Fuel function.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr23/39

LAFON test site

20/02/2009 10:33:07

Identify driver

Terminal ConfigConfig Fuels

Page 24: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

 Press F2 Key to select the pulse channel

 The dispensers list displays on.Press the F3 key in order to customize the 3rd dispenser.

Press the C key to correct the pulse channel number.

Then, the display shows …Just press V key to validate your choice or C key to correct one.

After validation, the cursor back to the previous menu.To quit (close) this configuration menu, press A key to return (go back, into) (get back) the main menu.

Terminal DISPLAY INSTALLER ACTIONYou have to press the A key again to restart the device. The system (and the card) will reboot automatically.

Before to perform a complete reboot, this following screen proposes to the user, to save the modified setting or to reboot without any modification.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr24/39

Service ModePulse channelStatusPulse Value

Dispenser : 01Dispenser : 02Dispenser : 03

Dispenser 32 counting channelsC key = CorrectV key = Validate

Dispenser 31 counting channelC key = CorrectV key = Validate

Config Fuels

SavingA : No V : Yes

Terminal ConfigConfig Fuels

Service ModePulse channelStatusPulse Value

Page 25: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

c. FunctioningThis calculator (device) could be sets up to a Stand-Alone or a Connected Mode.Without any identification from the site controller, the Stand-Alone mode permits toInitialize (drive) a dispensing (delivery, refueling). So, the fuel feature functioning can be tested with autonomous manner. This mode is very useful just to diagnose all the features like gauging, flow rate… It must be used as (like) the first help tool.The connected mode allows that it will be managed by the software management. The fuel delivery can be available only after the first user identification.This is the standard functioning mode.

d. Pulse WeightA pulse weight is associated (linked) to each counting (metering) channel (3 channels maximum). This parameter (setting) is the average, the score between the… (This parameter is function of cyclical volume from meter and the associated pulser. (E.g.)For example:The programmed weight pulse to a 0.5 L (liter) cyclical volume meter with a 50 pulse’s 2 channel pulser is: P= 0.5/ (50*2*2) = 0.0025 L. So, it’s equal to 2500 µL.From.

e. GaugingAfter choosing the Nozzle, follow the recommended instructions has been displayed on. The system asks you to:

1- Unhook a nozzle (well, the pumping device is commanded)2- Making a gauging. 3- Re-lift the nozzle (When the gauging is done. Therefore, the engine and the pump group stop)4- Type the gauging amount onto the keyboard. Yours typed values must have 3 digits after the

decimal point. After your validation, the pulse weight has been automatically calculated and it can be consulted. 

To check it, re-entry in the same menu as describe in the previous chapter (“d)”). 

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr25/39

Page 26: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

NOTE: It’s mandatory to enter the correct decimal value that s been indicated by the gauge. You have to type it with 3 decimal digit accuracy on to the keypad terminal. E.g.(for example): 20.002

Terminal DISPLAY INSTALLER ACTIONIn order to change the EasyC@rb’ system configuration, press the Config Installer pushbutton (See sticker).

So as to select the Wright function configuration, Press the F2 Key to configure the Config Fuel function.

Well, the following appears press the  key ( ) to unfold the menu and(then) to display so thay

Terminal DISPLAY INSTALLER ACTION

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr26/39

Service ModePulse channelStatusPulse Value

LAFON test site

20/02/2009 10:33:07

Identify driver

Terminal ConfigConfig Fuels

Dispenser : 01Dispenser : 02Dispenser : 03

Gauging

Page 27: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Terminal DISPLAY INSTALLER ACTION

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr27/39

JAUGEAGEDispenser 1

fill gauge

Service ModePulse channelStatusPulse Value

0.00Dispenser 1 lift nozzle

Dispenser : 01Dispenser : 02Dispenser : 03

JAUGEAGEDispenser 1 quantite fuelled ?

Dispenser : 010.025000 LC key = CorrectV key = Validate

Page 28: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

19)Functioning check

a. The power supplyThe E@syCarb card is powered by the sector tension 230 VAC.On the E@syCarb card, left side L6 mark, a green LED (light-emitting diode), indicates that 5V presence is required for the functional card.

b. Backlighting displayIt lights on during 1 minute:

Early as 1 keypad touch is pressed on  Or as one identification support has been detected by the system(badge, magnetic card, Abipass) Or from the nozzle lifted.

c. The Keyboard / KeypadDepends on terminal configuration is programmed in the site controller; the keypad is an alphanumeric or numeric type. The management key is the same using on the Cell phones.

d. Everlasting (perpetual, perennial) totalizer(s)

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr28/39

Terminal ConfigConfig Fuels

Fuel Config

SavingA : No V : Yes

Service ModePulse channelStatusPulse Value

Page 29: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

The nozzle pulls off and pull on under to 10 seconds allows visualizing during 3 seconds in the display area, the perennial totalizer value linked on 8 “digits”.

e. The identification (ID)It s possible to test the following identifications-Badges (LAFON): GLS, Abiself Connection, Abiself stand-alone, EASY.-Abipass-ISO2 standard Magnetic card (petroleum company card, etc…)

“”The table below indicates the procedure for checking the functioning of a badge.””

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr29/39

Page 30: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

The others acronyms 

(abbreviation, short form) are:

AA= Autonomous (Stand-Alone) Abiself and GLS for GLS terminal.

The other kind of badge acronyms are:C= Driver  I=Installer   E= Manager

f. The printer (option)

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr30/39

Terminal DISPLAY INSTALLER ACTION

To enter in the configuration menu of E@syCarb system (device), press the “Config” key onto the E@syCarb electronic card.

Press F1 key to select the Terminal function configuration

Press F2 key to select Identification.

And by pressing the Down arrow key”: Access to the Forward menu.

Backward Menu: To return, press the “Up Arrow key”.

The various menus propose 6 test options, so press F1 to select the badge test.

Insert a “Connection Abiself” Badge

AC signifies Abiself Connection0001 is the Abiself Terminal NumberV is for a VEHICLE BADGE98765 is the vehicle badge number

LAFON test site

20/02/2009 10:55:237

Identify driver

Terminal ConfigConfig Fuels

Abipass configIdentificationprinterDefault IP config

Badge TestTerminal: XXX Num: XXXX Badge Num: XX XXXX

Badge test Abipass testISO2 board testTest Tachograph Card

20.02Test Tacho KeyTest Memory Touch

Badge TestTerminal: AC Num: 0001 Badge Num: V 98765

Page 31: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

In the Maintainer/Installer mode, it’s possible to test the printer functioning:

Into the Config Terminal Menu, choose the “Printer” sub directory then, it gets 2 option choice: Ticket Demo or Ticket Config Test. 

g. The fuel dispensingThe fuel dispensing functioning could be checked. To use this feature, the E@sycarb device must be in the Maintainer mode then, go to the Fuel Config Menu, choose the functioning sub-menu and select the Stand-alone Mode. After saving and quit the maintainer mode with this new functioning setting, the fuel dispensing is initialized from the lift nozzle and the following controls can be completed:

o The nozzle entryo The pulseo The Engine command outputo The Delivered Volume LCD display (panel, screen) areao The counting (metering) accuracy with a standard gauge.

h. Error list table

If an error steps in (intervenes), the error code displays into the reserved display area signals it.

E E 7 0Error code

Significance (Senses) Resources (Patch, Fix)

01 Power default Check the card power supply. If the tension is 230 V: OK. Change ther E@syCarb card.

02 Memory default  EEPROM 12C problem. In case of repeated apparition. Change the E@syCarb card. Also, This message could appear during a download (an upgrade) by the EuroGestion programmer. In this case, it s not an error. 

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr31/39

Page 32: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

04 Configuration default This message appears when the Easy calculator configuration is blank or is faulty. So, enter to the configuration menu especially to save the current setting.Press V key when the “SAVE” message is displayed. If frequently displayed, replace the EasyC@rb card. 

10 Pulse 1 problem Disconnection pulse 1 channel A11 Pulse 1 problem Disconnection pulse 1 channel B15 Pulse 2 problem Disconnection pulse 2 channel A16 Pulse 2 problem Disconnection pulse 2 channel B20 Pulse 3 problem Disconnection pulse 3 channel A21 Pulse 3 problem Disconnection pulse 3 channel B30 Power cut (line cut) Line cut during a delivery (dispensing, refueling).60 Maximum time w/o an 

impulse.The maximal time dispensing without any fuel delivered is over the limit.

61 Maximum time dispensing. The maximal time allowed to a delivery, is over the limit.

62 Maximum volume (dispensed quantity) over-limit volume.

The Maximal Volume refueled is reached

65 Gauging timeout The Time allowed to the gauging is pealed out (over).Remake a gauging process.

70 Faulty Totalizer The totalizer memorization is faulty or any transaction has been recorded again. This error will disappear at the first refueling. In case of repeated apparition, you have to change the terminal card.

20)Software downloading

a. Downloading by communication protocolThe EasyC@rb card can download it-self and upgrade every part available on the Rs485 network.

b. Downloading by EuroGestion programmer (scheduler)This downloading mode is only used if the O.S. (Operating Software)’s software compatibility doesn’t allow to download it by the communication protocol.

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr32/39

Page 33: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr33/39

Page 34: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

21)“Synoptical” Cabling pattern (chart)

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr34/39

Page 35: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

22) EasyCarb interfacing with CMP 

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr35/39

Page 36: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

23) EasyCarb interfacing with a MicroBasic Card

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr36/39

Page 37: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

24)Annexes (Attachments)a. Synoptical of Terminal configuration menu

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr37/39

Page 38: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

b. Synoptical of Fuel configuration menu

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr38/39

Page 39: EasyCarb Book - Freefpxcel.free.fr/.../STPWorks/EasyCarb_DocEng_TekBeta.docx · Web viewRs485 Local Network cabling rules Here below the rs485 typology. It’s also the only way to

LAFON’s reference : 18295050 EASY CARB Terminal

International Instruction Book

Date : 05/2009version E

25)Spare parts list

18295210PR   EASYCARB FRONTSIDE KEYBOARD.18295000PR   EASYCARB Cpu board18295110PR   EASYCARB Ground Cable18295120PR   EASYCARB Terminal fixing part 

18295200PR   Hub Cap18295080PR   Display LCD panel18294040PR   Display cable (display dab)

Head Quarter : Avenue Lucien Victor Meunier – 33530 BASSENS – FRANCETél. : (+00 33) 557.808.080 -- Fax : (+00 33) 556.316.121

http://www.lafon.fr39/39