eaton lv mcc communication optionspub/@electrical/documents/conte… · eaton lv mcc communication...
TRANSCRIPT
EATON LV MCC COMMUNICATION OPTIONS
Table of Contents
EATON LV MCC COMMUNICATION OPTIONS ........................................................................................ 1
Overview .......................................................................................................................................... 3
Network Selection ........................................................................................................................... 4
PLC Vendors ................................................................................................................................. 4
DCS Vendors ................................................................................................................................ 5
Smart Devices in an MCC ................................................................................................................. 6
Electro Mechanical Devices ......................................................................................................... 6
Combination Starter Overload Choices ................................................................................... 6
Starter Overload Selection Charts ........................................................................................... 8
Communication Module Selection .................................................................................................. 9
Solid State Control ......................................................................................................................... 12
S811+ Soft Starts ....................................................................................................................... 12
SVX Variable Speed Drives ......................................................................................................... 13
Network Wiring in an MCC ............................................................................................................ 14
DeviceNet Network ................................................................................................................... 14
Modbus and Profibus Networks ................................................................................................ 15
Ethernet (Modbus TCP and EtherNet/IP) .................................................................................. 16
Ethernet Topology ..................................................................................................................... 17
Home Run (standard) ............................................................................................................ 17
Daisy Chain (nonstandard) .................................................................................................... 18
Reference Drawings ...................................................................................................................... 19
C440 OLR and DeviceNet ........................................................................................................... 20
C441 OLR and DeviceNet ........................................................................................................... 21
SVX and DeviceNet .................................................................................................................... 22
C440 and Ethernet ..................................................................................................................... 23
C441 and Ethernet ..................................................................................................................... 24
SVX And Ethernet ...................................................................................................................... 25
S811+ and Ethernet ................................................................................................................... 26
Eaton LV MCC Communication Options
Version 3.0 Page 3 of 26 February 25, 20014
Overview The Eaton Freedom 2100 series MCC’s (Freedom and Freedom FlashGard) all have standard
configurations for common industrial networks which include Modbus TCP, EtherNet/IP,
DeviceNet, Profibus DP and Modbus RTU. All of Eaton’s smart MCC are tested prior to shipment
to ensure that the industrial communications is fully functional. As well, none of the Eaton
smart MCC’s utilize a gateway to bridge the motor control from a common network to the
industrial network. The Eaton MCC’s also have a scalable solution for motor protection
including control and monitoring across multiple motor control device platforms. The intent of
this document is to help select the correct type of motor protection and provide technical
information on the networks which Eaton uses in their MCC’s.
Short Discussion on Protocol
When talking control, or control and monitoring networks, it is important to understand the
different between the media (cable) and the protocol (language) and this is emphasized when
talking about our Ethernet networks. Today one will find that a specification calls for Ethernet
communication which defines the media and not the protocol. A simple way to look at the
difference between media and protocol is a home landline. The media one can see on the
telephone poles (or today probably fiber optic buried in the ground), however this doesn’t
describe the protocol going over the media. When both ends of the phone (wire) are talking
the same language (English for example) the two parties understand each other and are able to
communicate. If one end of the wire is speaking a language the other doesn’t understand
(English on one end and German on the other) then the two will not be able to communicate.
Taking this simple example to Ethernet explains why it is important to understand what the
controller (consumer) is talking so the MCC (producer) can have the correct devices installed to
communicate using the same protocol.
Eaton support Modbus TCP and EtherNet/IP over Ethernet as their protocols. Other protocols
one might hear are Ethercat and IEC61850 which at this time are not supported by Eaton motor
control.
Consumer Producer Media
English
EtherNet/IP
English
EtherNet/IP
Phone Line
Ethernet
Eaton LV MCC Communication Options
Version 3.0 Page 4 of 26 February 25, 20014
Network Selection
PLC Vendors
When selecting a network it is important to look upstream at the control to determine the
correct network for the application. In many cases the control will be a PLC (Programmable
Logic Controller) and each vendor supports a primary network for their line or product family.
Generally speaking a PLC will be used in discrete control applications even though there has
been a trend to move into the process space as these processors become more powerful. To
simplify the selection, below is a short list of PLC’s by vendor and the primary networks
supported.
PLC Section Chart
PLC Vendor Leading Platform Primary Network
Siemens S7 Profibus DP
Schneider Electric Modicon Quantum Modbus TCP
Modicon Momentum Modbus TCP
Rockwell ControlLogix EtherNet/IP
DeviceNet
CompactLogix EtherNet/IP
DeviceNet
Eaton LV MCC Communication Options
Version 3.0 Page 5 of 26 February 25, 20014
DCS Vendors
There are also other control systems which include SCADA (Supervisory Control and Data
Acquisition) and DCS (Distributed Control System) which are more process driven and less
discrete control and will be used in applications such as power plants, pulp and paper machines,
refining and many more continuous process applications. These vendors are consolidating and
support a wide range of control networks and a short list of the major DSC manufactures and
platforms is listed below. Most SCADA applications will communicate to any network as most of
these are PC based where a network card of choice can be added.
DCS Selection Chart
DCS Vendor Leading Platform Primary Network
Emerson Process Management Delta V Profibus DP
DeviceNet
Modbus TCP
EtherNet/IP
Ovation Profibus DP
DeviceNet
Honeywell Process Solutions Experion Profibus DP
Modbus TCP
DeviceNet through Rockwell
EtherNet/IP through Rockwell
Note: Rockwell relationships is
waning
Schneider Electric PlantStruxure Pillar Modbus TCP
EtherNet/IP
Profibus DP
Siemens Energy & Automation SPPA-T300 Modbus TCP
EtherNet/IP
Profibus DP
ABB 800xA Profibus DP
DeviceNet
Modbus TCP
Foxboro Invensys Profibus DP
DeviceNet
Eaton LV MCC Communication Options
Version 3.0 Page 6 of 26 February 25, 20014
Smart Devices in an MCC There are many types of smart devices in an MCC, they range from across the line starters to
solid state control and include meters and breaker measurement. Generally speaking the motor
control devices will support all the communication protocols natively while the meters and
breaker monitoring will only provide Modbus TCP connectivity requiring a linking adapter to
bridge to the other networks.
Electro Mechanical Devices
Electro Mechanical devices refer to across the line combination starters where there is a
contactor which mechanically switches the power and then in combination an overload with
protects the load. For this paper the contactor is not important, however the overload relay
(OLR) is very important as options and capabilities change between the families.
Combination Starter Overload Choices
There are 4 selections of OLR in Bid Manager in the Starter Wiring tab. To choose the type of
overload, from the Starter / Wiring tab go to the bottom left and you will see Overload Type.
The selections for Overload Type are:
• Bi-metallic – C306 Overload
• Solid State Standard – C440 Self Powered Overload
• Solid State Standard with Ground Fault – C440 Self Powered Overload with integral
machine level ground fault
• Solid State Advanced with Ground Fault – C441 Motor Insight
• Solid State Advanced with HRG – C441 Motor Insight with low ground fault pick up settable
to less than 3A which is suitable for High Resistance Grounded system. For motors larger
than size 4, a D64RPB is used in conjunction with the C441 (already in the Bid Man logic) to
achieve sensing less than 3A. For Size 1 to 3 the C441 will detect to 3A residual Ground
Fault Current. For Sizes 4-6 must use a D64RPB to detect the ground fault since the C441
cant detect the 3 amp ground fault. The D64RPB is then wired into the communication
module so that the network can detect the ground fault.
Eaton LV MCC Communication Options
Version 3.0 Page 7 of 26 February 25, 20014
OLR Communication Choices
All the OLR’s can be connected directly to an industrial network for control and monitoring with
the networks including:
DeviceNet / Modbus RTU / Profibus DP / EtherNet/IP / Modbus TCP
Pictures of the ORL’s in combination (except for the C441 Motor Insight)
Device Picture Competitor OLR’s
C441 Motor Insight
(link) C441 SSOL
• AB E3, E3+ and E300
• Siemens Simocode
• SQD TeSys T
• GE MM200/MM300
• Symcom 777
C440 Self Powered OLR
(link) C440 SSOL
• AB E1
• Siemens ESP2000
• SQD Motor Logic
C306 Bi Metallic OLR
• Many
Eaton LV MCC Communication Options
Version 3.0 Page 8 of 26 February 25, 20014
Starter Overload Selection Charts
These charts are to be used to compare and contrast features of the different types of overloads
which are able to be installed in the Freedom MCC.
Protective Comparison
Protective Features C441 C440 C306
Thermal Overload X X X
Phase Loss/Imbalance X X X
Selectable Trip Class X X
Ground Fault X X
Current Unbalance X X
Voltage Unbalance X
Phase Reversal X
Stall/Jam X
Under/Over kW Trip X
Under/Over V Trip X
Under/Over I Trip X
Communications Comparison
Communications C441 C440 C306
DeviceNet X X *
Modbus X X *
Modbus TCP X X *
EtherNet/IP X X *
Profibus X X *
PowerXpert Software X X
* Connected to IO module for control and
trip monitoring only
Monitoring Comparison
Monitoring Features C441 C440 C306
Thermal Capacity X X
Phase Currents X X
Current Unbalance X X
Ground Fault Current X X
Voltage Unbalance X
Phase Voltages X
kW X
Power Factor X
Frequency X
Run Hours X
Motor Starts X
Time to Restart X
Control Comparison
Control Features C441 C440 C306
Hard Wire Control X X X
Local Reset X X X
Network Reset X X
Programmable Alarm
Contacts X
Network Control X X X
Eaton LV MCC Communication Options
Version 3.0 Page 9 of 26 February 25, 20014
Communication Module Selection
Protocol Picture Part Number(s) Features
EtherNet/IP
Modbus TCP
C441R
C441T
C441U
C441V
4 AC or DC Inputs
2 B300 Relay Outs
Built in 2 port switch
DeviceNet
C441K
C441L
4 AC or DC Inputs
2 B300 Relay Outs
Profibus
C441S
C441Q
4 AC or DC Inputs
2 B300 Relay Outs
Modbus RTU Slave port for
secondary communication
Modbus RTU
C441M
C441N
C441P
4 AC or DC Inputs
2 B300 Relay Outs
Eaton LV MCC Communication Options
Version 3.0 Page 10 of 26 February 25, 20014
Selection of the input voltage
By default, all inputs for starter configuration are 120V due to the control power being 120V.
The only time this is broken is if the customer specifically asks for 24V inputs or when used in
conjunction with feeder breakers. When monitoring a feeder, typically a CPT is not needed due
to the 24V inputs being self-powered by the IO card. When extra IO is needed with a S811+ or a
SVX then by default the 120V input version is selected.
For S811+ the control is usually 120V to the field and internal connections, therefore use the
120V input modules.
Kit Information
When combining the communication modules with the OLR or standalone they will generally
require accessory parts to make the connections and these are generally assembled into kits
which can be purchased. When a kit is available, it will be in the matrix for the specific OLR.
Description C441 Motor
Insight
C440 Feeder
(molded case)
S811+*
DeviceNet
DeviceNet module with
120V inputs C441K C440-DN-120
DeviceNet module with
24vdc inputs C441L C440-DN-24
C441L + C440-
COM-ADP
Modbus RTU
Modbus module without
IO C441M
Modbus module with 120V
inputs C441N C440-MOD-120
Modbus module with
24vdc inputs C441P C440-MOD-24
C441P + C440-
COM-ADP
Profibus DP
Profibus module with 120V
inputs C441S C440-DP-120
Profibus module with
24vdc inputs C441Q C440-DP-24
C441Q + C440-
COM-ADP
EtherNet/IP and Modbus TCP
Ethernet module with
120V inputs C441R
Ethernet module with
24vdc inputs C441T
Ethernet Standalone
module with 120V inputs C440-ET-120 C441U **
Ethernet Standalone
module with 24vdc inputs C440-ET-24 C441V C441V **
* S811+ Communicated via HMS Any Bus Linking Adapter to Profibus and DeviceNet
** Switch S2 configures the remote communication port for Modbus (ON) or QCPort (OFF) upon 24 Vdc
power up of the unit.
Eaton LV MCC Communication Options
Version 3.0 Page 11 of 26 February 25, 20014
2 Speed with 1 or 2 Windings
• Each unit requires 2 OLR’s (Bid Man picks this automatically), one for the fast and one
for the slow speed.
• Each OLR requires a communication module (fast and slow) for control and monitoring.
• If needed a shorting contactor will be placed and then wired to the Fast IO card for
monitoring of the M contact.
Typical Monitoring and Control IO Points for Motor Control Devices
Typical inputs include
(1) Run contact from the contactor
(2) Run contact from reversing contactor
(3) Hand Feedback
(4) Auto Feedback
Typical outputs include
(1) Forward control when in auto
(2) Reverse control when in auto
MMX AFD
• The MMX AFD has provisions to communicate directly to Profibus DP using the following
option card XMX-NET-PD-A.
• The MMX AFD has provisions to communicate directly to DeviceNet using the following
option card XMX-NET-DN-A.
• If Modbus TCP or EtherNet/IP communications is required for the MMX upgrade to the
SVX AFD which has these option cards.
Eaton LV MCC Communication Options
Version 3.0 Page 12 of 26 February 25, 20014
Solid State Control
S811+ Soft Starts
The S811+ soft start has native Modbus RTU onboard for a connection to the Ethernet modules
and to the HMS Any Bus linking adapters for DeviceNet and Profibus. The S811+ is the smallest
reduced voltage starter in the industry which includes a fully rated run bypass contactor rated
from 5 HP to 700 HP. All of the S811+ frames are mounted standard in the MCC with frames up
to 200mm able to be pluggable / removable units.
S811+ Monitoring Parameters
Thermal Capacity
Phase Currents
Power Pole Temperatures
Start Count
Fault Status
Motor Status
Power (kW)
Communications
DeviceNet (AB7001 Anybus Linking Adapter)
Modbus RTU (Native)
Modbus TCP (C441V)
EtherNet/IP (C441V)
Profibus (AB7000 Anybus Linking Adapter)
PowerXpert Software
Control Features
Hard Wire Control
Local Reset
Network Reset
Network Control
Eaton LV MCC Communication Options
Version 3.0 Page 13 of 26 February 25, 20014
SVX Variable Speed Drives
The SVX VFD is comes with network interfaces to DeviceNet, Modbus, Modbus TCP, EtherNet/IP
and Profibus including many of the building automation networks. All of the SVX frames are
mounted standard in the MCC up though 500 HP including constant torque, variable torque and
18 pulse clean power. Eaton provides a 3% line reactor standard in each unit except for the FR9
(150 HP to 250 HP CT) frame where if the reactor is needed an additional section has to be
added for the reactor.
SVX Monitoring Parameters (short list)
Motor Current
Motor Torque
Motor Power
Motor RPM
Output Frequency
DC Bus Voltage
Fault Codes
Motor Status
Input Board Discrete Status
Communications
DeviceNet (OPTC7)
Modbus RTU (OPTC2)
Modbus TCP (OPTCK)
EtherNet/IP (OPTCQ)
Profibus (OPTC5)
PowerXpert Software (OPTC2)
Control Features
Hard Wire Control
Local Reset
Network Reset
Network Control
Eaton LV MCC Communication Options
Version 3.0 Page 14 of 26 February 25, 20014
Network Wiring in an MCC
DeviceNet Network
DeviceNet is a trunk drop type network with the trunk (thick) being installed in the upper wire
way and then drops(thin) going down each vertical wire way where there is a DeviceNet tee and
then again dropping into the specific unit. DeviceNet allows for 64 devices to be connected to
one network. DeviceNet also uses a 600V rated cable with power and communication on one
cable and screwed IP20 type micro connectors at each junction.
Even though it isn’t required, many times a DeviceNet power supply is provided in the MCC to
power the DeviceNet network and devices (by default). Each of the communication devices
need to be powered from 24Vdc which is provided via the DeviceNet cable. At the time of
manufacture, the MCC is fully functional and is tested for communications prior to leaving the
factory floor.
DeviceNet requires terminating resistors on each physical end of the network; Eaton provides
these resistors for each Item. When connecting to the user controller, it is important to
understand this since many times one of the resistors will need to be removed and then placed
at the controller. When the MCC is shipped, at splits the trunk is unscrewed from the T and the
user must reattach this connection when bolting the MCC back together.
Below is an example of a network physical layout using DeviceNet showing the trunk and the
drops. This type of drawing is not provided as part of the standard drawing package as this is
only representative of a DeviceNet layout.
Eaton LV MCC Communication Options
Version 3.0 Page 15 of 26 February 25, 20014
Modbus and Profibus Networks
Both Modbus and Profibus are daisy chain type of networks where one cable is daisy chained
from device to device. Connecting more than 30 devices together at a time is not possible
without the use of network repeater. Modbus uses a RS485 shielded twisted pair cable while
Profibus uses a specific Profibus cable, both these cables are 600V rated.
With both Modbus and Profibus, a network power supply is required to power the
communication devices since these networks don’t combine power and communications on the
same cable. This power supply is usually located in the center of the MCC and will then fed both
left and right to the communication modules in each unit. At the time of manufacture, the MCC
is fully functional and is tested for communications prior to leaving the factory floor.
Modbus and Profibus requires terminating resistors on each physical end of the network; Eaton
provides these resistors for each lineup. When connecting to the user controller, it is important
to understand this since many times one of the resistors will need to be removed and then
placed at the controller. When the MCC is shipped, each of the daisy chain connectors are
pulled back and rolled up to one section. The user must then unspool the cable / connectors, re-
rout them in the horizontal and vertical wire ways and connect the connectors back to the
communication module in the unit when reassembling the MCC.
Below is an example of a network physical layout using Profibus (Modbus looks the same). This
type of drawing is not provided as part of the standard drawing package as this is only
representative of a Profibus or Modbus RTU layout.
Eaton LV MCC Communication Options
Version 3.0 Page 16 of 26 February 25, 20014
Ethernet (Modbus TCP and EtherNet/IP)
Ethernet networks by default use a home run topology where each device has a home run to a
switch which is local to a grouping of starters. There will be a switch located at each shipping
split so that Ethernet cables do t have to be pulled back from each unit when the MCC is
packaged for shipment. The user will be required to connect the jumper between the switches
to complete the communication between switches during install. The Ethernet cables are all
shielded and 600V rated. Switch configuration of 8, 16 and 24 port are available as are both
Level 1 unmanaged and Level 2 managed switches.
The switch is located in dedicated low voltage unit in the MCC so that a user can access that unit
without any voltages present with are greater than 24V. Some vendors place this switch in the
wire way and it is the view of Eaton that this is unsafe since to gain access one has to open a
space which has the possibility 600V present.
For Modbus TCP the default switch is the Hirschmann Spider II TX which is an 8 port unmanaged
switch. When more than 8 ports are needed in a shipping split then more switches are stacked
in that switch unit.
Form EtherNet/IP the default switch is the Hirschman RS20 which is a Level 2 switch with 8-24
ports and comes standard with the Professional software load. This switch has many features
and is EtherNet/IP conformance tested and integrates into the Logix platform of processors.
With Ethernet, a network power supply is required to power the communication devices since
these networks do not combine power and communications on the same cable. This power
supply is usually located in the center of the MCC and will then fed both left and right to the
communication modules in each unit. At the time of manufacture, the MCC is fully functional
and is tested for communications prior to leaving the factory floor.
When the MCC is shipped, only the 24V feed and the Ethernet jumper cables are rolled back to
one section. The user must then unspool the cable / connectors, re-rout them in the horizontal
wire ways connect in the switch unit when reassembling the MCC.
Eaton LV MCC Communication Options
Version 3.0 Page 17 of 26 February 25, 20014
Ethernet Topology
There are two ways in which the Ethernet devices can be connected, they are either a home run
or a daisy chain. The standard configuration method is to home run each device back to a
switch and is also the most robust. With a home run a single device failure will not affect any of
the other connected devices.
Home Run (standard)
Below is an example of a home run configuration. In this configuration the devices will be
connected to a dedicated port on the switch and the switches will be daisy chained together to
form the network.
In each shipping split the switch or grouping of switches required for the devices in that split will
be connected so that switches daisy chained across the MCC. In this configuration the user will
connect their control system to one open port on any of the switches.
Split 1 Split 2 Split 3 Split 4 Split 5
Home Run Type Topology (Star)
To Devices To Devices To Devices To Devices To Devices
Eaton LV MCC Communication Options
Version 3.0 Page 18 of 26 February 25, 20014
A non-standard configuration uses a master switch and then all the shipping split switches are
home run to that switch. The master switch is then the switch the customer connects to for
communications to the MCC. This method is used to eliminate a failure caused by a switch
losing power or breaking the chain.
Split 1 Split 2 Split 3 Split 4 Split 5
When a managed switch design is employed technologies such as spanning tree or ring
technologies can be used to create a robust self-healing network.
Daisy Chain (nonstandard)
An extremely rare network topology which can be used is the Daisy Chain. In this the devices
are all daisy chained to one another and then brought to a switch or a ring master with DLR
(Device Level Ring). In a daisy chain topology if one device breaks the chain communications will
stop after that device. With the addition of a ring master (DLR) the ring will heal, however only
once deice can be out a time in this configuration.
Master Switch
Ring Master
Switch
Optional Ethernet
for ring
Ring type topology
Eaton LV MCC Communication Options
Version 3.0 Page 19 of 26 February 25, 20014
Reference Drawings
Eaton LV MCC Communication Options
Version 3.0 Page 20 of 26 February 25, 20014
C440 OLR and DeviceNet
Eaton LV MCC Communication Options
Version 3.0 Page 21 of 26 February 25, 20014
C441 OLR and DeviceNet
Eaton LV MCC Communication Options
Version 3.0 Page 22 of 26 February 25, 20014
SVX and DeviceNet
Eaton LV MCC Communication Options
Version 3.0 Page 23 of 26 February 25, 20014
C440 and Ethernet
Eaton LV MCC Communication Options
Version 3.0 Page 24 of 26 February 25, 20014
C441 and Ethernet
Eaton LV MCC Communication Options
Version 3.0 Page 25 of 26 February 25, 20014
SVX And Ethernet
Eaton LV MCC Communication Options
Version 3.0 Page 26 of 26 February 25, 20014
S811+ and Ethernet