ece4762011_lect9
TRANSCRIPT
-
7/22/2019 ECE4762011_Lect9
1/43
Lecture 9
Transformers, Per Unit
Professor Tom Overbye
Department of Electrical and
Computer Engineering
ECE 476
POWER SYSTEM ANALYSIS
-
7/22/2019 ECE4762011_Lect9
2/43
1
Announcements
Be reading Chapter 3
HW 3 is 4.32, 4.41, 5.1, 5.14. Due September 22 in class.
-
7/22/2019 ECE4762011_Lect9
3/43
2
Transformer Equivalent Circuit
Using the previous relationships, we can derive anequivalent circuit model for the real transformer
' 2 '2 2 1 2
' 2 '
2 2 1 2
This model is further simplified by referring all
impedances to the primary side
r e
e
a r r r r
x a x x x x
-
7/22/2019 ECE4762011_Lect9
4/43
3
Simplified Equivalent Circuit
-
7/22/2019 ECE4762011_Lect9
5/43
4
Calculation of Model Parameters
The parameters of the model are determined based
upon
nameplate data: gives the rated voltages and power
open circuit test: rated voltage is applied to primary withsecondary open; measure the primary current and losses
(the test may also be done applying the voltage to the
secondary, calculating the values, then referring the
values back to the primary side).
short circuit test: with secondary shorted, apply voltage
to primary to get rated current to flow; measure voltage
and losses.
-
7/22/2019 ECE4762011_Lect9
6/43
5
Transformer Example
Example: A single phase, 100 MVA, 200/80 kV
transformer has the following test data:
open circuit: 20 amps, with 10 kW losses
short circuit: 30 kV, with 500 kW losses
Determine the model parameters.
-
7/22/2019 ECE4762011_Lect9
7/43
6
Transformer Example, contd
e
2
sc e2 2
e
2
e
100 30500 , R 60
200 500
P 500 kW R 2 ,
Hence X 60 2 60
200 410
200R 10,000 10,000
20
sc e
e sc
c
e m m
MVA kVI A jX
kV A
R I
kVR MkW
kVjX jX X
A
From the short circuit test
From the open circuit test
-
7/22/2019 ECE4762011_Lect9
8/43
7
Residential Distribution Transformers
Single phase transformers are commonly used inresidential distribution systems. Most distribution
systems are 4 wire, with a multi-grounded, common
neutral.
-
7/22/2019 ECE4762011_Lect9
9/43
8
Per Unit Calculations
A key problem in analyzing power systems is the
large number of transformers.
It would be very difficult to continually have to refer
impedances to the different sides of the transformers
This problem is avoided by a normalization of all
variables.
This normalization is known as per unit analysis.
actual quantityquantity in per unit
base value of quantity
-
7/22/2019 ECE4762011_Lect9
10/43
9
Per Unit Conversion Procedure, 1f1. Pick a 1fVA base for the entire system, SB
2. Pick a voltage base for each different voltage level,
VB. Voltage bases are related by transformer turns
ratios. Voltages are line to neutral.3. Calculate the impedance base, ZB= (VB)
2/SB
4. Calculate the current base, IB= VB/ZB
5. Convert actual values to per unit
Note, per unit conversion on affects magnitudes, not
the angles. Also, per unit quantities no longer have
units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)
-
7/22/2019 ECE4762011_Lect9
11/43
10
Per Unit Solution Procedure
1. Convert to per unit (p.u.) (many problems are
already in per unit)
2. Solve
3. Convert back to actual as necessary
-
7/22/2019 ECE4762011_Lect9
12/43
11
Per Unit Example
Solve for the current, load voltage and load powerin the circuit shown below using per unit analysis
with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV.
Original Circuit
-
7/22/2019 ECE4762011_Lect9
13/43
12
Per Unit Example, contd
2
2
2
8 0.64100
8064
10016
2.56100
LeftB
MiddleB
RightB
kVZMVA
kVZ
MVAkV
ZMVA
Same circuit, with
values expressed
in per unit.
-
7/22/2019 ECE4762011_Lect9
14/43
13
Per Unit Example, contd
L
2*
1.0 0 0.22 30.8 p.u. (not amps)3.91 2.327
V 1.0 0 0.22 30.8
p.u.
0.189 p.u.
1.0 0 0.22 30.8 30.8 p.u.
LL L L
G
Ij
VS V I
Z
S
-
7/22/2019 ECE4762011_Lect9
15/43
14
Per Unit Example, contd
To convert back to actual values just multiply theper unit values by their per unit base
L
Actual
ActualL
ActualG
MiddleB
ActualMiddle
0.859 30.8 16 kV 13.7 30.8 kV
0.189 0 100 MVA 18.9 0 MVA
0.22 30.8 100 MVA 22.0 30.8 MVA
100 MVAI 1250 Amps
80 kV
I 0.22 30.8 Amps 275 30.8
V
S
S
-
7/22/2019 ECE4762011_Lect9
16/43
15
Three Phase Per Unit
1. Pick a 3fVA base for the entire system,
2. Pick a voltage base for each different voltagelevel, VB. Voltages are line to line.
3. Calculate the impedance base
Procedure is very similar to 1fexcept we use a 3fVA base, and use line to line voltage bases
3BS f
2 2 2, , ,
3 1 1( 3 )
3
B LL B LN B LNB
B B B
V V VZS S Sf f f
Exactly the same impedance bases as with single phase!
-
7/22/2019 ECE4762011_Lect9
17/43
16
Three Phase Per Unit, cont'd
4. Calculate the current base, IB
5. Convert actual values to per unit
3 1 13 1B B
, , ,
3I I
3 3 3
B B B
B LL B LN B LN
S S S
V V V
f f ff f
Exactly the same current bases as with single phase!
-
7/22/2019 ECE4762011_Lect9
18/43
17
Three Phase Per Unit Example
Solve for the current, load voltage and load power
in the previous circuit, assuming a 3fpower base of
300 MVA, and line to line voltage bases of 13.8 kV,
138 kV and 27.6 kV (square root of 3 larger than the1fexample voltages). Also assume the generator is
Y-connected so its line to line voltage is 13.8 kV.
Convert to per unit
as before. Note the
system is exactly the
same!
-
7/22/2019 ECE4762011_Lect9
19/43
18
3fPer Unit Example, cont'd
L
2*
1.0 00.22 30.8 p.u. (not amps)
3.91 2.327
V 1.0 0 0.22 30.8
p.u.
0.189 p.u.
1.0 0 0.22 30.8 30.8 p.u.
LL L L
G
Ij
VS V I
Z
S
Again, analysis is exactly the same!
-
7/22/2019 ECE4762011_Lect9
20/43
19
3fPer Unit Example, cont'd
L
Actual
Actual
LActualG
MiddleB
ActualMiddle
0.859 30.8 27.6 kV 23.8 30.8 kV
0.189 0 300 MVA 56.7 0 MVA0.22 30.8 300 MVA 66.0 30.8 MVA
300 MVAI 125 (same cur0 Amps
3138 kVI 0.22 30.
rent!)
8
V
SS
Amps 275 30.8
Differences appear when we convert back to actual values
-
7/22/2019 ECE4762011_Lect9
21/43
20
3fPer Unit Example 2Assume a 3fload of 100+j50 MVA with VLL of 69 kV
is connected to a source through the below network:
What is the supply current and complex power?
Answer: I=467 amps, S = 103.3 + j76.0 MVA
-
7/22/2019 ECE4762011_Lect9
22/43
21
Per Unit Change of MVA Base
Parameters for equipment are often given using
power rating of equipment as the MVA base
To analyze a system all per unit data must be on a
common power base
2 2
Hence Z /
Z
base base
OriginalBase NewBasepu actual pu
OriginalBase NewBase
pu puOriginalBase NewBaseBaseBase
NewBaseOriginalBase NewBaseBasepu puOriginalBase
Base
Z Z Z
V V
ZSS
SZ
S
-
7/22/2019 ECE4762011_Lect9
23/43
22
Per Unit Change of Base Example
A 54 MVA transformer has a leakage reactance or
3.69%. What is the reactance on a 100 MVA base?
100
0.0369 0.0683 p.u.54eX
-
7/22/2019 ECE4762011_Lect9
24/43
23
Transformer Reactance
Transformer reactance is often specified as a
percentage, say 10%. This is a per unit value
(divide by 100) on the power base of the
transformer. Example: A 350 MVA, 230/20 kV transformer has
leakage reactance of 10%. What is p.u. value on
100 MVA base? What is value in ohms (230 kV)?
2
1000.10 0.0286 p.u.350
2300.0286 15.1
100
eX
-
7/22/2019 ECE4762011_Lect9
25/43
24
Three Phase Transformers
There are 4 different ways to connect 3ftransformersY-Y -
Usually 3ftransformers are constructed so all windings
share a common core
-
7/22/2019 ECE4762011_Lect9
26/43
25
3fTransformer Interconnections-Y Y-
-
7/22/2019 ECE4762011_Lect9
27/43
26
Y-Y Connection
Magnetic coupling with An/an, Bn/bn & Cn/cn
1, ,An AB A
an ab a
V V Ia a
V V I a
-
7/22/2019 ECE4762011_Lect9
28/43
27
Y-Y Connection: 3fDetailed Model
-
7/22/2019 ECE4762011_Lect9
29/43
28
Y-Y Connection: Per Phase Model
Per phase analysis of Y-Y connections is exactly the
same as analysis of a single phase transformer.
Y-Y connections are common in transmission systems.
Key advantages are the ability to ground each side
and there is no phase shift is introduced.
-
7/22/2019 ECE4762011_Lect9
30/43
29
- Connection
Magnetic coupling with AB/ab, BC/bb & CA/ca
1 1, ,AB AB A
ab ab a
V I Ia
V I a I a
-
7/22/2019 ECE4762011_Lect9
31/43
30
- Connection: 3fDetailed Model
To use the per phase equivalent we need to use
the delta-wye load transformation
-
7/22/2019 ECE4762011_Lect9
32/43
31
- Connection: Per Phase Model
Per phase analysis similar to Y-Y except impedances
are decreased by a factor of 3.
Key disadvantage is D-Dconnections can not be
grounded; not commonly used.
-
7/22/2019 ECE4762011_Lect9
33/43
32
-Y Connection
Magnetic coupling with AB/an, BC/bn & CA/cn
-
7/22/2019 ECE4762011_Lect9
34/43
33
-Y Connection V/I Relationships
, 3 30
30 30Hence 3 and 3
For current we get
1
13 30 303
130
3
AB AB an ab anan
AB Anab an
ABa AB
ab
A AB AB A
a A
V Va V V V V a
V VV V
a a
II a I
I a
I I I I
a I
-
7/22/2019 ECE4762011_Lect9
35/43
34
-Y Connection: Per Phase Model
Note: Connection introduces a 30 degree phase shift!
Common for transmission/distribution step-down sincethere is a neutral on the low voltage side.
Even if a = 1 there is a sqrt(3) step-up ratio
-
7/22/2019 ECE4762011_Lect9
36/43
35
Y- Connection: Per Phase Model
Exact opposite of the D-Y connection, now with a
phase shift of -30 degrees.
-
7/22/2019 ECE4762011_Lect9
37/43
36
Load Tap Changing Transformers
LTC transformers have tap ratios that can be varied
to regulate bus voltages
The typical range of variation is 10% from the
nominal values, usually in 33 discrete steps(0.0625% per step).
Because tap changing is a mechanical process, LTC
transformers usually have a 30 second deadband to
avoid repeated changes.
Unbalanced tap positions can cause "circulating
vars"
-
7/22/2019 ECE4762011_Lect9
38/43
37
LTCs and Circulating Vars
slack
1 1.00 pu
2 3
40.2 MW
40.0 MW
1.7 Mvar
-0.0 Mvar
1.000 tap 1.056 tap
24.1 MW
12.8 Mvar
24.0 MW-12.0 Mvar
A
MVA
1.05 pu0.98 pu
24 MW
12 Mvar
64 MW
14 Mvar
40 MW
0 Mvar
0.0 Mvar
80%A
MVA
-
7/22/2019 ECE4762011_Lect9
39/43
-
7/22/2019 ECE4762011_Lect9
40/43
39
Phase Shifter Example 3.13
slack
Phase Shifting Transformer
345.00 kV 341.87 kV
0.0 deg
216.3 MW 216.3 MW
283.9 MW 283.9 MW
1.05000 tap
39.0 Mvar 6.2 Mvar
93.8 Mvar125.0 Mvar
500 MW
164 Mvar 500 MW100 Mvar
-
7/22/2019 ECE4762011_Lect9
41/43
40
ComED Control Center
-
7/22/2019 ECE4762011_Lect9
42/43
41
ComED Phase Shifter Display
-
7/22/2019 ECE4762011_Lect9
43/43
Autotransformers
Autotransformers are transformers in which the
primary and secondary windings are coupled
magnetically and electrically.
This results in lower cost, and smaller size andweight.
The key disadvantage is loss of electrical isolation
between the voltage levels. Hence auto-
transformers are not used when a is large. Forexample in stepping down 7160/240 V we do not
everwant 7160 on the low side!