ece4762011_lect9

Upload: mannat-mrjn

Post on 10-Feb-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/22/2019 ECE4762011_Lect9

    1/43

    Lecture 9

    Transformers, Per Unit

    Professor Tom Overbye

    Department of Electrical and

    Computer Engineering

    ECE 476

    POWER SYSTEM ANALYSIS

  • 7/22/2019 ECE4762011_Lect9

    2/43

    1

    Announcements

    Be reading Chapter 3

    HW 3 is 4.32, 4.41, 5.1, 5.14. Due September 22 in class.

  • 7/22/2019 ECE4762011_Lect9

    3/43

    2

    Transformer Equivalent Circuit

    Using the previous relationships, we can derive anequivalent circuit model for the real transformer

    ' 2 '2 2 1 2

    ' 2 '

    2 2 1 2

    This model is further simplified by referring all

    impedances to the primary side

    r e

    e

    a r r r r

    x a x x x x

  • 7/22/2019 ECE4762011_Lect9

    4/43

    3

    Simplified Equivalent Circuit

  • 7/22/2019 ECE4762011_Lect9

    5/43

    4

    Calculation of Model Parameters

    The parameters of the model are determined based

    upon

    nameplate data: gives the rated voltages and power

    open circuit test: rated voltage is applied to primary withsecondary open; measure the primary current and losses

    (the test may also be done applying the voltage to the

    secondary, calculating the values, then referring the

    values back to the primary side).

    short circuit test: with secondary shorted, apply voltage

    to primary to get rated current to flow; measure voltage

    and losses.

  • 7/22/2019 ECE4762011_Lect9

    6/43

    5

    Transformer Example

    Example: A single phase, 100 MVA, 200/80 kV

    transformer has the following test data:

    open circuit: 20 amps, with 10 kW losses

    short circuit: 30 kV, with 500 kW losses

    Determine the model parameters.

  • 7/22/2019 ECE4762011_Lect9

    7/43

    6

    Transformer Example, contd

    e

    2

    sc e2 2

    e

    2

    e

    100 30500 , R 60

    200 500

    P 500 kW R 2 ,

    Hence X 60 2 60

    200 410

    200R 10,000 10,000

    20

    sc e

    e sc

    c

    e m m

    MVA kVI A jX

    kV A

    R I

    kVR MkW

    kVjX jX X

    A

    From the short circuit test

    From the open circuit test

  • 7/22/2019 ECE4762011_Lect9

    8/43

    7

    Residential Distribution Transformers

    Single phase transformers are commonly used inresidential distribution systems. Most distribution

    systems are 4 wire, with a multi-grounded, common

    neutral.

  • 7/22/2019 ECE4762011_Lect9

    9/43

    8

    Per Unit Calculations

    A key problem in analyzing power systems is the

    large number of transformers.

    It would be very difficult to continually have to refer

    impedances to the different sides of the transformers

    This problem is avoided by a normalization of all

    variables.

    This normalization is known as per unit analysis.

    actual quantityquantity in per unit

    base value of quantity

  • 7/22/2019 ECE4762011_Lect9

    10/43

    9

    Per Unit Conversion Procedure, 1f1. Pick a 1fVA base for the entire system, SB

    2. Pick a voltage base for each different voltage level,

    VB. Voltage bases are related by transformer turns

    ratios. Voltages are line to neutral.3. Calculate the impedance base, ZB= (VB)

    2/SB

    4. Calculate the current base, IB= VB/ZB

    5. Convert actual values to per unit

    Note, per unit conversion on affects magnitudes, not

    the angles. Also, per unit quantities no longer have

    units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)

  • 7/22/2019 ECE4762011_Lect9

    11/43

    10

    Per Unit Solution Procedure

    1. Convert to per unit (p.u.) (many problems are

    already in per unit)

    2. Solve

    3. Convert back to actual as necessary

  • 7/22/2019 ECE4762011_Lect9

    12/43

    11

    Per Unit Example

    Solve for the current, load voltage and load powerin the circuit shown below using per unit analysis

    with an SB of 100 MVA, and voltage bases of

    8 kV, 80 kV and 16 kV.

    Original Circuit

  • 7/22/2019 ECE4762011_Lect9

    13/43

    12

    Per Unit Example, contd

    2

    2

    2

    8 0.64100

    8064

    10016

    2.56100

    LeftB

    MiddleB

    RightB

    kVZMVA

    kVZ

    MVAkV

    ZMVA

    Same circuit, with

    values expressed

    in per unit.

  • 7/22/2019 ECE4762011_Lect9

    14/43

    13

    Per Unit Example, contd

    L

    2*

    1.0 0 0.22 30.8 p.u. (not amps)3.91 2.327

    V 1.0 0 0.22 30.8

    p.u.

    0.189 p.u.

    1.0 0 0.22 30.8 30.8 p.u.

    LL L L

    G

    Ij

    VS V I

    Z

    S

  • 7/22/2019 ECE4762011_Lect9

    15/43

    14

    Per Unit Example, contd

    To convert back to actual values just multiply theper unit values by their per unit base

    L

    Actual

    ActualL

    ActualG

    MiddleB

    ActualMiddle

    0.859 30.8 16 kV 13.7 30.8 kV

    0.189 0 100 MVA 18.9 0 MVA

    0.22 30.8 100 MVA 22.0 30.8 MVA

    100 MVAI 1250 Amps

    80 kV

    I 0.22 30.8 Amps 275 30.8

    V

    S

    S

  • 7/22/2019 ECE4762011_Lect9

    16/43

    15

    Three Phase Per Unit

    1. Pick a 3fVA base for the entire system,

    2. Pick a voltage base for each different voltagelevel, VB. Voltages are line to line.

    3. Calculate the impedance base

    Procedure is very similar to 1fexcept we use a 3fVA base, and use line to line voltage bases

    3BS f

    2 2 2, , ,

    3 1 1( 3 )

    3

    B LL B LN B LNB

    B B B

    V V VZS S Sf f f

    Exactly the same impedance bases as with single phase!

  • 7/22/2019 ECE4762011_Lect9

    17/43

    16

    Three Phase Per Unit, cont'd

    4. Calculate the current base, IB

    5. Convert actual values to per unit

    3 1 13 1B B

    , , ,

    3I I

    3 3 3

    B B B

    B LL B LN B LN

    S S S

    V V V

    f f ff f

    Exactly the same current bases as with single phase!

  • 7/22/2019 ECE4762011_Lect9

    18/43

    17

    Three Phase Per Unit Example

    Solve for the current, load voltage and load power

    in the previous circuit, assuming a 3fpower base of

    300 MVA, and line to line voltage bases of 13.8 kV,

    138 kV and 27.6 kV (square root of 3 larger than the1fexample voltages). Also assume the generator is

    Y-connected so its line to line voltage is 13.8 kV.

    Convert to per unit

    as before. Note the

    system is exactly the

    same!

  • 7/22/2019 ECE4762011_Lect9

    19/43

    18

    3fPer Unit Example, cont'd

    L

    2*

    1.0 00.22 30.8 p.u. (not amps)

    3.91 2.327

    V 1.0 0 0.22 30.8

    p.u.

    0.189 p.u.

    1.0 0 0.22 30.8 30.8 p.u.

    LL L L

    G

    Ij

    VS V I

    Z

    S

    Again, analysis is exactly the same!

  • 7/22/2019 ECE4762011_Lect9

    20/43

    19

    3fPer Unit Example, cont'd

    L

    Actual

    Actual

    LActualG

    MiddleB

    ActualMiddle

    0.859 30.8 27.6 kV 23.8 30.8 kV

    0.189 0 300 MVA 56.7 0 MVA0.22 30.8 300 MVA 66.0 30.8 MVA

    300 MVAI 125 (same cur0 Amps

    3138 kVI 0.22 30.

    rent!)

    8

    V

    SS

    Amps 275 30.8

    Differences appear when we convert back to actual values

  • 7/22/2019 ECE4762011_Lect9

    21/43

    20

    3fPer Unit Example 2Assume a 3fload of 100+j50 MVA with VLL of 69 kV

    is connected to a source through the below network:

    What is the supply current and complex power?

    Answer: I=467 amps, S = 103.3 + j76.0 MVA

  • 7/22/2019 ECE4762011_Lect9

    22/43

    21

    Per Unit Change of MVA Base

    Parameters for equipment are often given using

    power rating of equipment as the MVA base

    To analyze a system all per unit data must be on a

    common power base

    2 2

    Hence Z /

    Z

    base base

    OriginalBase NewBasepu actual pu

    OriginalBase NewBase

    pu puOriginalBase NewBaseBaseBase

    NewBaseOriginalBase NewBaseBasepu puOriginalBase

    Base

    Z Z Z

    V V

    ZSS

    SZ

    S

  • 7/22/2019 ECE4762011_Lect9

    23/43

    22

    Per Unit Change of Base Example

    A 54 MVA transformer has a leakage reactance or

    3.69%. What is the reactance on a 100 MVA base?

    100

    0.0369 0.0683 p.u.54eX

  • 7/22/2019 ECE4762011_Lect9

    24/43

    23

    Transformer Reactance

    Transformer reactance is often specified as a

    percentage, say 10%. This is a per unit value

    (divide by 100) on the power base of the

    transformer. Example: A 350 MVA, 230/20 kV transformer has

    leakage reactance of 10%. What is p.u. value on

    100 MVA base? What is value in ohms (230 kV)?

    2

    1000.10 0.0286 p.u.350

    2300.0286 15.1

    100

    eX

  • 7/22/2019 ECE4762011_Lect9

    25/43

    24

    Three Phase Transformers

    There are 4 different ways to connect 3ftransformersY-Y -

    Usually 3ftransformers are constructed so all windings

    share a common core

  • 7/22/2019 ECE4762011_Lect9

    26/43

    25

    3fTransformer Interconnections-Y Y-

  • 7/22/2019 ECE4762011_Lect9

    27/43

    26

    Y-Y Connection

    Magnetic coupling with An/an, Bn/bn & Cn/cn

    1, ,An AB A

    an ab a

    V V Ia a

    V V I a

  • 7/22/2019 ECE4762011_Lect9

    28/43

    27

    Y-Y Connection: 3fDetailed Model

  • 7/22/2019 ECE4762011_Lect9

    29/43

    28

    Y-Y Connection: Per Phase Model

    Per phase analysis of Y-Y connections is exactly the

    same as analysis of a single phase transformer.

    Y-Y connections are common in transmission systems.

    Key advantages are the ability to ground each side

    and there is no phase shift is introduced.

  • 7/22/2019 ECE4762011_Lect9

    30/43

    29

    - Connection

    Magnetic coupling with AB/ab, BC/bb & CA/ca

    1 1, ,AB AB A

    ab ab a

    V I Ia

    V I a I a

  • 7/22/2019 ECE4762011_Lect9

    31/43

    30

    - Connection: 3fDetailed Model

    To use the per phase equivalent we need to use

    the delta-wye load transformation

  • 7/22/2019 ECE4762011_Lect9

    32/43

    31

    - Connection: Per Phase Model

    Per phase analysis similar to Y-Y except impedances

    are decreased by a factor of 3.

    Key disadvantage is D-Dconnections can not be

    grounded; not commonly used.

  • 7/22/2019 ECE4762011_Lect9

    33/43

    32

    -Y Connection

    Magnetic coupling with AB/an, BC/bn & CA/cn

  • 7/22/2019 ECE4762011_Lect9

    34/43

    33

    -Y Connection V/I Relationships

    , 3 30

    30 30Hence 3 and 3

    For current we get

    1

    13 30 303

    130

    3

    AB AB an ab anan

    AB Anab an

    ABa AB

    ab

    A AB AB A

    a A

    V Va V V V V a

    V VV V

    a a

    II a I

    I a

    I I I I

    a I

  • 7/22/2019 ECE4762011_Lect9

    35/43

    34

    -Y Connection: Per Phase Model

    Note: Connection introduces a 30 degree phase shift!

    Common for transmission/distribution step-down sincethere is a neutral on the low voltage side.

    Even if a = 1 there is a sqrt(3) step-up ratio

  • 7/22/2019 ECE4762011_Lect9

    36/43

    35

    Y- Connection: Per Phase Model

    Exact opposite of the D-Y connection, now with a

    phase shift of -30 degrees.

  • 7/22/2019 ECE4762011_Lect9

    37/43

    36

    Load Tap Changing Transformers

    LTC transformers have tap ratios that can be varied

    to regulate bus voltages

    The typical range of variation is 10% from the

    nominal values, usually in 33 discrete steps(0.0625% per step).

    Because tap changing is a mechanical process, LTC

    transformers usually have a 30 second deadband to

    avoid repeated changes.

    Unbalanced tap positions can cause "circulating

    vars"

  • 7/22/2019 ECE4762011_Lect9

    38/43

    37

    LTCs and Circulating Vars

    slack

    1 1.00 pu

    2 3

    40.2 MW

    40.0 MW

    1.7 Mvar

    -0.0 Mvar

    1.000 tap 1.056 tap

    24.1 MW

    12.8 Mvar

    24.0 MW-12.0 Mvar

    A

    MVA

    1.05 pu0.98 pu

    24 MW

    12 Mvar

    64 MW

    14 Mvar

    40 MW

    0 Mvar

    0.0 Mvar

    80%A

    MVA

  • 7/22/2019 ECE4762011_Lect9

    39/43

  • 7/22/2019 ECE4762011_Lect9

    40/43

    39

    Phase Shifter Example 3.13

    slack

    Phase Shifting Transformer

    345.00 kV 341.87 kV

    0.0 deg

    216.3 MW 216.3 MW

    283.9 MW 283.9 MW

    1.05000 tap

    39.0 Mvar 6.2 Mvar

    93.8 Mvar125.0 Mvar

    500 MW

    164 Mvar 500 MW100 Mvar

  • 7/22/2019 ECE4762011_Lect9

    41/43

    40

    ComED Control Center

  • 7/22/2019 ECE4762011_Lect9

    42/43

    41

    ComED Phase Shifter Display

  • 7/22/2019 ECE4762011_Lect9

    43/43

    Autotransformers

    Autotransformers are transformers in which the

    primary and secondary windings are coupled

    magnetically and electrically.

    This results in lower cost, and smaller size andweight.

    The key disadvantage is loss of electrical isolation

    between the voltage levels. Hence auto-

    transformers are not used when a is large. Forexample in stepping down 7160/240 V we do not

    everwant 7160 on the low side!