ECM HIGH EFFICIENCY CIRCULATORSWILO STRATOSWILO STRATOS
Stratos – Commercial high efficiency pumpg y p p
Main features & benefits
0 285 G l/ i fl• 0 - 285 Gal/min flow• 3 – 40 ft head• 8 models (1.25”, 1.5”, 2” & 3”)• EC motor (permanent magnet rotor)
A t ti ll dj t t t d d• Automatically adjusts to system demands• No external sensors required• Easy setup via red button• Water temperature from 14⁰F to 230⁰F
C t t ∆ t l d• Constant ∆‐pressure control mode• Variable ∆‐pressure control mode• Temperature control mode• BMS options: LON & Bacnet, 0-10V
I f d d i f t t l & t• Infrared device for remote control & setup• Excellent warranty 24/18 months
UNIQUE FEATURES & UP TO 80% QENERGY SAVINGS!
Stratos-D (dual-power head pump)( p p p)
2’’& 3’’ size modelsFlow up to 450 gpmp gpIF modules requiredDuty/Standby modeLead/Lag modeLead/Lag modeSpace savingAccessories saving
Sratos-Z for Domestic Hot Water
Cast S. Steel voluteEC M tEC MotorBuilt-in VFDT⁰ control with 0-10V IF0-160 GPM @ 40-3’
NSF/ANSI 61-G certified pumpNSF/ANSI 61 G certified pump
ECM Technologygy
Commutation (reverse currents)Coil 1
Coil 4 Coil 2Coil 4 Coil 2
C il 3Coil 3
Speed Control
Electronic continuous speed control (Constant Pressure)
> Automatic differential pressure controluto at c d e e t a p essu e co t o
nmax1. The „brain“ determined the actual pumping head. (actual
Ft]
H2Constant speed pump2
value)
2. The „drive“ sees the difference between the set value (point 1) and the actual
l ( i t 2)
g H
ead
H [F
13
value. (point 2)
3. Via ECM smart technology the controller reduces the speed and reduced the
i h d t t h th
H1
Pum
ping pumping head to match the
system curve. (point 3)
Flow Q [USGPM]Q2Q1
Built‐In Control Modes∆P‐C (Constant Pressure Differential) Control Mode∆P C (Constant Pressure Differential) Control Mode
On site setting via red button
Can be adjusted from 3ft to max pump head
Pump will vary the flow but keep a constant diff. pressure
Built-in control mode, does not require external sensors
Recommended in low resistance systems or in-floor heating loops zoning
In the example above, the pump is set to maintain 20 ft constant differential pressure. The flow will modulate from 0 to 230 gpm.
Built‐In Control ModesConstant Speed Control ModeConstant Speed Control Mode
On site setting via red buttonOn site setting via red button
Can be adjusted from Min to Max speed with 10 rpm increments
Max
Set
Built-in control mode, does not require external sensors
Recommended in fixed
speed2210 rpm
Recommended in fixed flow/head application
Min
In the example above, the pump is set to 2210 rpm. Minimum and Maximum speeds vary depending on pumps models.
Built‐In Control Modes∆P‐V (Variable Pressure Differential) Control Mode∆P‐V (Variable Pressure Differential) Control Mode
On site setting via red button
Can be adjusted from 3ft to max pump head
Pump will automatically vary Pump will automatically vary the flow and the head on system demand. Min head at 0 flow is half the max head set
Built-in model, does not require external sensors
Recommended in high Recommended in high resistance systems
In the example above, the pump is set to maintain 24 ft differential pressure at maximum flow As the flow decreases the head decreases proportionallyat maximum flow. As the flow decreases, the head decreases proportionally.
Built‐In Control Modes∆P‐T (Temperature Pressure Differential) Control Mode
Change in temperature at the pump changes the pressure setpoint• IR tool required to activate and set perameters
St t i t ll d t
∆P T (Temperature Pressure Differential) Control Mode
• Stratos installed on return• T Max – T Min = > or = 50 deg. F
T Max: 150 F H @ Max T: 10’T Min: 100 F H @ Max T: 30’
T Max: 190 F H @ Max T: 7’T Min: 140 F H @ Max T: 25’
30‘
Head
25‘
Head
T Min: 100 F H @ Max T: 30 T Min: 140 F H @ Max T: 25
30
10‘
25
7‘
100 F 150 F Temp 190 F 140 F Temp
Condensing Boiler Application Non-Condensing Boiler Applicationg pp(Decreases delta P on temp rise)
g pp(Increases delta P on temp rise)
Power Supplypp y
1ph‐230V G FCp
2 x 1ph‐115V
3ph‐208/230V
A bl i l 195V i / 263V
Check local electrical code
Acceptable input voltage: 195V min / 263V max
Interface Interface modules for
BMS BMS communication
External Control ModesBUILDING MANAGEMENT SYSTEMBUILDING MANAGEMENT SYSTEM
Interface modules for:
0-10V DC SignalLONBACNETDual pump operation
Inter-Face 0-10V/DP / Ext. Off
0 to 1 V: Pump Off1 to 3V: Pump On / Minimum speed
d d l i i d3 to 10V: Speed modulation, 3V=Min and 10V-MaxExt. Off Contact: if closed losed = Pump On / if open = Pump Off
Inter-Face 0-10V/DP/Ext. Min
0 to 1 V: Pump On / Minimum speed1 to 10V: Speed modulation, 1V=Min and 10V=Max
i if l d d l i / if d iExt. Min Contact: if closed = Modulation / if open = Speed Min
Inter-Face 0-10V/DP/SBM
0 to 1 V: Pump Off1 to 3V: Pump On / Minimum speed
d d l i i d3 to 10V: Speed modulation, 3V=Min and 10V-MaxSBM Status Contact: if closed = Pump is On / if open = Pump is Off
Dual Pump Operationp p
Dual pump operation
Auto changeover
Lead/Lag modeLead/Lag mode
Duty/Standby mode
Power Management
BACnet InterFace Module
MS/TP SLAVEIF RS485High Baud RatesAnalog input/outputAnalog input/outputBinary input/outputMultistate input/outputp / pDual pump operation
LON InterFace Module
FTT 10A transceiverHigh Baud RatesAnalog input/outputBinary input/outputBinary input/outputMultistate input/outputXIF files availableDual pump operation
Interface (IF) modules for Stratos
IF modules summary board
Description Article # 0‐10V Ext. Off Ext. Min Run (SBM) LON BacNet DP
IF 0‐10V/DP/Ext.Off 2030475 x x x
IF 0‐10V/DP/Ext.Min 2030485 x x x
IF 0‐10V/DP/SBM 2030495 x x x
IF SBM/Ext.Off/DP 2084867 x x x
IF LON 2030455 x x
IF BacNet 2097810 x x
Key:
x = Available
0‐10V = External 0‐10V DC input signal
Ext. Off = pump start/stop contactp p / p
Ext. Min = Default minimum speed contact
SBM = Run status contact
LON = BMS LON interface
BacNet = BMS BacNet interfaceBacNet = BMS BacNet interface
DP = Dual pump management
IR Remote Control
Infra-Red remote control:
O it i ti i On site communication via laptop
Control settinggPump monitoringData logging & saving