    EDMT281536

    FHQ-DA + RZQS, RZQ series

    Heat pump 50Hz

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    2/156

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    3/156

    EDMT281536

    Table of contents 1

    Part 1 SkyAir FHQ-DA + RZQS, RZQ series ..................................5

    1. External appearance...............................................................................7

    2. Model name, power supply and nomenclature .......................................92.1 Model name and power supply ................................................................9

    2.2 Nomenclature.........................................................................................10

    3. Functions...............................................................................................11

    4. Specifications........................................................................................124.1 RZQS .....................................................................................................12

    4.2 RZQ-LV1 ................................................................................................13

    4.3 RZQ-HAY4A...........................................................................................15

    5. Dimensions and service space .............................................................175.1 Indoor unit ..............................................................................................17

    5.2 Wired remote controller ..........................................................................20

    5.3 Wireless remote controller......................................................................22

    5.4 Outdoor unit............................................................................................23

    5.5 Installation Service Space......................................................................286. Piping diagrams ....................................................................................36

    6.1 Indoor unit + outdoor unit .......................................................................36

    7. Wiring diagrams ....................................................................................417.1 Indoor unit ..............................................................................................41

    7.2 Outdoor unit............................................................................................42

    8. Field wiring ............................................................................................48

    9. Electric characteristics ..........................................................................499.1 FHQ-DA + RZQS....................................................................................49

    9.2 FHQ-DA + RZQ-LV1 ..............................................................................50

    9.3 FHQ-DA + RZQ-HAY4A.........................................................................5110.Capacity tables......................................................................................52

    10.1 RZQS .....................................................................................................52

    10.2 RZQ-LV1 ................................................................................................54

    10.3 RZQ-HAY4A...........................................................................................58

    10.4 Capacity correction factor by the length of refrigerant piping .................61

    11.Operation limits .....................................................................................62

    12.Sound level ...........................................................................................6312.1 Indoor unit ..............................................................................................63

    12.2 Outdoor unit............................................................................................66

    13.Accessories...........................................................................................7413.1 Indoor unit ..............................................................................................74

    13.2 Outdoor unit............................................................................................75

    Part 2 Installation of indoor / outdoor unit.................................77

    1. Centre of gravity....................................................................................78

    2. Installation of indoor unit .......................................................................812.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA /

    FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA..........................81

    3. Installation of outdoor unit ...................................................................1013.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /

    RZQ125LV1 .........................................................................................101

    3.2 RZQ140LV1 .........................................................................................117

    3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................133

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    4/156

    EDMT281536

    2 Table of contents

    3.4 Equivalent piping length of joints (reference) .......................................149

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    5/156

    EDMT281536 Publication list

    Table of contents 3

    Publication listRefrigerant

    Inverter/Non Inverter

    Series Book No. Type, HzModel name of

    indoor / outdoor unitArea Note

    Publishedin

    R410A Inverter

    RZQ

    EDHK281002 H/P 50Hz

    - Indoor unitsFCQ71/100/125/140KVEAFFQ25/35/50/60BV1BFHQ35/50/60/71/100/125BVV1BFBQ50/60BV1A

    FBQ71/100/125/140DV1

    - Outdoor unitsRZQ71KBV1RZQ100/125/140HY4ARXS25/35EBVMARXS50/60FVMARKS25/35EBVMARKS50/60FVMA

    Hong Kong Jun. 2010

    EDVN281408 H/P 50Hz

    - Indoor unitsFCQ50/60LUV1VFCQ71-140LUV1FFQ25-60BV1BFHQ50/60BVV1VFHQ35/71/100/125BVV1BFHQ140CAVEAFDXS25-60CVMAFBQ50-71BV1A

    FBQ50/60DV1VFBQ71-140DV1FVQ50/60CVEFVQ71-140CVEB

    - Outdoor unitsRZQ50/60KBV1VRZQ50/60KBV4ARZQ71-140KCV4ARZQ100-140HAY4ARXS25/35EBVMARXS50FAVMARXS50-71FVMA

    Vietnam

    - New lineup of indoor units:FCQ50/60LUV1V

    FHQ50/60BVV1VFBQ50/60DV1VFVQ50/60CVE

    - New lineup of outdoor units:RZQ50/60KBV1V

    Sep. 2014

    RZQSRZQ

    EDMT281426 H/P 50Hz

    - Indoor unitsFCQ71/100/125/140KAVEAFHQ71/100/125BWV1A

    FHQ140CAVEAFAQ71/100CVEAFBQ71/100/125/140DBVEAFVQ50/60CVEFVQ71/100/125/140CVEB

    - Outdoor unitsRZQS50/60AV1RZQ71/100/125/140LV1RZQ100/125/140HAY4A

    VietnamIndia

    Hong Kong

    - New lineup of indoor units:FHQ71/100/125BWV1AFBQ71/100/125/140DBVEA

    - Model change of indoor units:

    FCQ71/100/125/140KVEA

    FCQ71/100/125/140KAVEA

    - New lineup of outdoor units:RZQS50/60AV1RZQ71/100/125/140LV1

    - Discontinued outdoor units:RZQ71KBV1RZQ50/60KBV4ARZQ71-140KCV4A

    Mar. 2015

    EDMT281512H/P

    50/60Hz

    - Indoor unitsFBQ50/60/71/100/125/140EVE

    - Outdoor unitsRZQS50/60AV1RZQ71/100/125/140LV1

    RZQ100/125/140HAY4ARZQ100/125/140KCTLTRZQ100/125/140LUYLT

    VietnamPhilippines

    India

    Hong Kong

    - New lineup of indoor units:FBQ50/60/71/100/125/140EVE Aug. 2015

    EDMT281536 H/P 50Hz

    - Indoor unitsFHQ50/60/71/100/125/140DAVMA

    - Outdoor unitsRZQS50/60AV1RZQ71/100/125/140LV1RZQ100/125/140HAY4A

    Hong KongVietnam

    India

    - New lineup of indoor units:FHQ50/60/71/100/125/140DAVMA

    Dec. 2015

    EDMT281536as shown by .

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    6/156

    Publication list EDMT281536

    4 Table of contents

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    7/156

    EDMT281536

    SkyAir FHQ-DA + RZQS, RZQ series 5

    1art 1

    SkyAir

    FHQ-DA RZQS, RZQ series

    Model series

    1. External appearance...............................................................................7

    2. Model name, power supply and nomenclature .......................................92.1 Model name and power supply ................................................................92.2 Nomenclature.........................................................................................10

    3. Functions...............................................................................................114. Specifications........................................................................................12

    4.1 RZQS .....................................................................................................124.2 RZQ-LV1 ................................................................................................134.3 RZQ-HAY4A...........................................................................................15

    5. Dimensions and service space .............................................................175.1 Indoor unit ..............................................................................................175.2 Wired remote controller ..........................................................................205.3 Wireless remote controller......................................................................225.4 Outdoor unit............................................................................................235.5 Installation Service Space......................................................................28

    6. Piping diagrams ....................................................................................366.1 Indoor unit + outdoor unit .......................................................................36

    7. Wiring diagrams ....................................................................................417.1 Indoor unit ..............................................................................................417.2 Outdoor unit............................................................................................42

    8. Field wiring ............................................................................................48

    9. Electric characteristics ..........................................................................499.1 FHQ-DA + RZQS....................................................................................499.2 FHQ-DA + RZQ-LV1 ..............................................................................509.3 FHQ-DA + RZQ-HAY4A.........................................................................51

    10.Capacity tables......................................................................................5210.1 RZQS .....................................................................................................5210.2 RZQ-LV1 ................................................................................................5410.3 RZQ-HAY4A...........................................................................................5810.4 Capacity correction factor by the length of refrigerant piping .................61

    Class 50 60 71 100 125 140 Power

    supply

    Indoorunit

    FHQ 50DA 60DA 71DA 100DA 125DA 140DA VMA

    Outdoorunit

    RZQS 50A 60A V1

    RZQ71L 100L 125L 140L V1

    100HA 125HA 140HA Y4A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    8/156

    EDMT281536

    6 SkyAir FHQ-DA + RZQS, RZQ series

    11.Operation limits .....................................................................................62

    12.Sound level ...........................................................................................6312.1 Indoor unit ..............................................................................................6312.2 Outdoor unit............................................................................................66

    13.Accessories...........................................................................................7413.1 Indoor unit ..............................................................................................74

    13.2 Outdoor unit............................................................................................75

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    9/156

    EDMT281536 External appearance

    SkyAir FHQ-DA + RZQS, RZQ series 7

    11. External appearance

    Indoor unit

    Wired

    remote controller

    Wireless

    remote controller

    FHQ-DAVMA

    BRC1E62 BRC1C61 BRC1D61

    BRC7GA53 Signal receiver unit

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    10/156

    External appearance EDMT281536

    8 SkyAir FHQ-DA + RZQS, RZQ series

    Outdoor unit

    RZQS50AV1RZQS60AV1

    RZQ71LV1 RZQ100LV1 RZQ125LV1 RZQ140LV1

    RZQ100HAY4ARZQ125HAY4ARZQ140HAY4A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    11/156

    EDMT281536 Model name, power supply and nomenclature

    SkyAir FHQ-DA + RZQS, RZQ series 9

    12. Model name, power supply and nomenclature

    2.1 Model name and power supply

    Indoor unit Outdoor unitPower supply intake

    Type Model name Model name

    Ceiling suspended type

    FHQ50DAVMA RZQS50AV1

    Outdoor unit: 1 phase, 220-240V, 50Hz

    FHQ60DAVMA RZQS60AV1

    FHQ71DAVMA RZQ71LV1

    FHQ100DAVMA RZQ100LV1

    FHQ125DAVMA RZQ125LV1

    FHQ140DAVMA RZQ140LV1

    FHQ100DAVMA RZQ100HAY4A

    Outdoor unit: 3 phase, 415V, 50HzFHQ125DAVMA RZQ125HAY4A

    FHQ140DAVMA RZQ140HAY4A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    12/156

    Model name, power supply and nomenclature EDMT281536

    10 SkyAir FHQ-DA + RZQS, RZQ series

    2.2 Nomenclature

    Indoor unit

    Outdoor unit

    Standard symbolA: Australia

    Power supply symbolV1: 1 phase, 220-240V, 50HzVE: 1 phase, 220-240/220V, 50/60HzVM: 1 phase, 220-240/220-230V, 50/60Hz

    Indicates major design category

    Capacity indication

    Refrigerant and typeQ: R410A, Heat pump or Cooling only

    ShapeC: Ceiling mounted cassette (Round flow)H: Ceiling suspended

    A: Wall mountedB(-E): Middle static pressure ceiling mounted duct

    Unit categoryF: Air cooled split indoor unit

    VMDAQF H A50

    Standard symbolA: Australia

    Power supply symbol

    V1: 1 phase, 220-240V, 50HzY4: 3 phase, 415V, 50Hz

    Indicates major design category

    Capacity indication

    Grade and refrigerant symbolS: Inverter, R410A

    Refrigerant and typeQ: R410A, Heat Pump

    Inverter / Non inverterZ: Inverter

    Unit categoryR: Air cooled split outdoor unit

    V1Q S 50Z AR

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    13/156

    EDMT281536 Functions

    SkyAir FHQ-DA + RZQS, RZQ series 11

    13. Functions

    Notes: : Functions exist.

    : No functions

    *1: Applicable when wired remote controller is used

    *2: For the outdoor units

    *3: Applicable when BRC1D61 or BRC1E62 is used

    *4: Option

    *5: Applicable when BRC1E62 is used

    *6: Applicable when BRC1C61 is used

    *7: Installable on max. 3.5m (50-71) and 4.3m (100-140) high ceiling.

    Category Function

    Indoorunit

    FHQ50-60DAVMA FHQ71-140DAVMA

    Outdoorunit

    RZQS50-60AV1RZQ71-140LV1

    RZQ100-140HAY4A

    Inverter control

    Comfort

    Auto swing

    Swing pattern selection

    Draft prevention function (heating)

    Independent up-and-down airflow

    DC fan motor (Indoor unit)

    Switchable fan speed (3 step) (3 step)

    Auto airflow rate

    High fan speed mode

    Programme Dry

    High ceiling application (*7) (*7)

    Two selectable temperature-sensors (*1)

    Hot start

    Year-round cooling applicable

    Night quiet operation (*2)

    Remotecontroller

    Setpoint auto reset (*5)

    Setpoint range set (*5)

    Weekly schedule timer (*3)

    Off timer (programmed) (*5)

    On/Off timer (*6)

    Cleanliness

    Anti-bacterial air filter

    Mould-proof air filter

    Silver ion anti-bacterial drain pan

    Mould-proof drain pan

    Work &servicing

    Drain pump mechanism (*4)

    Pre-charged for up to 30 m (*2)

    Pre-charged for up to 10 m (*2) Long-life filter

    Filter sign

    Ceiling soiling prevention

    Low gas pressure detection (*2)

    Emergency operation

    Self-diagnosis function

    Controlfeatures

    Auto-restart

    Auto-cooling/heating change-over

    Control by 2 remote controllers

    Group control by 1 remote controller

    External command control (*4)

    Central remote control

    Interlock control with Heat Reclaim Ventilator DIII-NET communication standard

    Options

    High-efficiency filter

    Ultra long-life filter

    Fresh air intake kit

    Others Anti corrosion treated heat exchangers (*2)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    14/156

    Specifications EDMT281536

    12 SkyAir FHQ-DA + RZQS, RZQ series

    4. Specifications

    4.1 RZQS

    FHQ-DA (Ceiling suspended type)

    Notes: *1. The above data are based on the following conditions:

    *2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation

    condition, it is normally over the set value due to the environmental noise and sound reflection.

    ModelIndoor unit FHQ50DAVMA FHQ60DAVMA

    Outdoor unit RZQS50AV1 RZQS60AV1Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz

    Power supply intake Outdoor unit side Outdoor unit side

    Cooling capacity *1 *2kW 5.0 (3.2-5.6) 6.0 (3.2-6.0)

    Btu/h 17,100 (10,900-19,100) 20,500 (10,900-20,500)

    kcal/h 4,300 (2,800-4,800) 5,200 (2,800-5,200)

    Heating capacity *1 *2kW 6.0 (3.5-7.0) 6.8 (3.5-8.0)

    Btu/h 20,500 (11,900-23,900) 23,200 (11,900-27,300)

    kcal/h 5,200 (3,000-6,000) 5,900 (3,000-6,900)

    Indoor unit FHQ50DAVMA FHQ60DAVMA

    Colour Light ivory Light ivory

    Dimensions HWD mm 235960690 235960690

    Coil Type Cross fin coil Cross fin coil

    Fan

    Type Sirocco fan Sirocco fan

    Motor output W 87 87

    Airflow rate (H/M/L)

    m/min 15/12/10 15/12/10

    l/s 250/200/167 250/200/167

    cfm 530/424/353 530/424/353

    Sound pressure level (H/M/L) *3 dB(A) 37/35/32 37/35/32Air filter Resin net (with mould resistance) Resin net (with mould resistance)

    Mass kg 25 25

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)

    Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61

    Wireless BRC7GA53 BRC7GA53

    Outdoor unit RZQS50AV1 RZQS60AV1

    Colour Ivory white Ivory white

    Dimensions HWD mm 770900320 770900320

    Coil Type Cross fin coil Cross fin coil

    Comp.Type Hermetically sealed swing type Hermetically sealed swing type

    Motor output kW 1.3 1.6

    Fan

    Type Propeller fan Propeller fan

    Motor output W 70 70Airflow rate m/min 52 52

    Sound pressurelevel *3

    Cooling dB(A) 48 48

    Heating dB(A) 50 50

    Night quiet mode dB(A) 44 44

    Mass kg 64 64

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)

    Safety devices High pressure switch, Fuse. High pressure switch, Fuse.

    Capacity step % Compressor revolution speed control (Inverter system) Compressor revolut ion speed control (Inverter system)

    Refrigerant control Electronic expansion valve Electronic expansion valve

    Ref. pipingMax. length m 50 (Equivalent length 70m) 50 (Equivalent length 70m)

    Max. height difference m 30 30

    RefrigerantModel R410A R410A

    Charge (factory charge) kg 2.0 (Charged for 30m) 2.0 (Charged for 30m)

    Ref. oil

    Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.

    Charge L 0.75 0.75

    Drawing No.

    Specification C: 3D096268A C: 3D096268A

    Sound (Indoor) C: 4D079992A C: 4D079992A

    Sound (Outdoor) C: 4D090424, C: 4D090423 C: 4D090424, C: 4D090423

    Conversion formulae

    kcal/h=kW860Btu/h=kW3412

    l/s=m/min1000/60cfm=m/min35.3

    Cooling Heating Piping length

    Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB

    Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB

    7.5m(Horizontal)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    15/156

    EDMT281536 Specifications

    SkyAir FHQ-DA + RZQS, RZQ series 13

    14.2 RZQ-LV1

    FHQ-DA (Ceiling suspended type)

    Notes: *1. The above data are based on the following conditions:

    *2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation

    condition, it is normally over the set value due to the environmental noise and sound reflection.

    ModelIndoor unit FHQ71DAVMA FHQ100DAVMA

    Outdoor unit RZQ71LV1 RZQ100LV1

    Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz

    Power supply intake Outdoor unit side Outdoor unit side

    Cooling capacity *1 *2kW 7.1 (3.2-8.0) 10.0 (5.0-11.2)

    Btu/h 24,200 (10,900-27,300) 34,100 (17,100-38,200)

    kcal/h 6,100 (2,800-6,900) 8,600 (4,300-9,600)

    Heating capacity *1 *2kW 8.0 (3.5-9.0) 11.2 (5.1-12.8)

    Btu/h 27,300 (11,900-30,700) 38,200 (17,400-43,700)

    kcal/h 6,900 (3,000-7,700) 9,600 (4,400-11,000)

    Indoor unit FHQ71DAVMA FHQ100DAVMA

    Colour Light ivory Light ivory

    Dimensions HWD mm 2351,270690 2351,590690

    Coil Type Cross fin coil Cross fin coil

    Fan

    Type Sirocco fan Sirocco fan

    Motor output W 117 150

    Airflow rate (H/M/L)

    m/min 20.5/17/14 28/24/20

    l/s 342/283/233 467/400/333

    cfm 724/600/494 988/847/706

    Sound pressure level (H/M/L) *3 dB(A) 38/36/34 42/38/34Air filter Resin net (with mould resistance) Resin net (with mould resistance)

    Mass kg 32 38

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)

    Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61

    Wireless BRC7GA53 BRC7GA53

    Outdoor unit RZQ71LV1 RZQ100LV1

    Colour Ivory white Ivory white

    Dimensions HWD mm 770900320 990940320

    Coil Type Cross fin coil Cross fin coil

    Comp.Type Hermetically sealed swing type Hermetically sealed swing type

    Motor output kW 1.7 2.08

    Fan

    Type Propeller fan Propeller fan

    Motor output W 70 200

    Airflow rate m/min 52 76

    Sound pressurelevel *3

    Cooling dB(A) 49 51

    Heating dB(A) 51 53Night quiet mode dB(A) 45 47

    Mass kg 64 75

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)

    Safety devices High pressure switch, Fuse. High pressure switch, Fuse.

    Capacity step % Compressor revolution speed control (Inverter system) Compressor revolut ion speed control (Inverter system)

    Refrigerant control Electronic expansion valve Electronic expansion valve

    Ref. pipingMax. length m 50 (Equivalent length 70m) 75 (Equivalent length 90m)

    Max. height difference m 30 30

    RefrigerantModel R410A R410A

    Charge (factory charge) kg 2.0 (Charged for 30m) 2.9 (Charged for 30m)

    Ref. oilModel Refer to the nameplate of compressor. Refer to the nameplate of compressor.

    Charge L 0.75 0.75

    Drawing No.

    Specification C: 3D096434B C: 3D096434B

    Sound (Indoor) C: 4D069649C C: 4D069652D

    Sound (Outdoor) C: 4D075745A, C: 4D075748A C: 4D089676, C: 4D089677A

    Conversion formulae

    kcal/h=kW860Btu/h=kW3412

    l/s=m/min1000/60cfm=m/min35.3

    Cooling Heating Piping length

    Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB

    Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB

    7.5m(Horizontal)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    16/156

    Specifications EDMT281536

    14 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ-DA (Ceiling suspended type)

    Notes: *1. The above data are based on the following conditions:

    *2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation

    condition, it is normally over the set value due to the environmental noise and sound reflection.

    ModelIndoor unit FHQ125DAVMA FHQ140DAVMA

    Outdoor unit RZQ125LV1 RZQ140LV1

    Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz

    Power supply intake Outdoor unit side Outdoor unit side

    Cooling capacity *1 *2kW 12.5 (5.7-14.0) 13.2 (6.2-15.5)

    Btu/h 42,700 (19,500-47,800) 45,000 (21,200-52,900)

    kcal/h 10,800 (4,900-12,000) 11,400 (5,300-13,300)

    Heating capacity *1 *2kW 14.0 (6.0-16.2) 16.0 (6.2-18.0)

    Btu/h 47,800 (20,500-55,300) 54,600 (21,200-61,400)

    kcal/h 12,000 (5,200-13,900) 13,800 (5,300-15,500)

    Indoor unit FHQ125DAVMA FHQ140DAVMA

    Colour Light ivory Light ivory

    Dimensions HWD mm 2351,590690 2351,590690

    Coil Type Cross fin coil Cross fin coil

    Fan

    Type Sirocco fan Sirocco fan

    Motor output W 150 150

    Airflow rate (H/M/L)

    m/min 31/27/23 34/29/24

    l/s 517/450/383 567/483/400

    cfm 1,094/953/812 1,200/1,024/847

    Sound pressure level (H/M/L) *3 dB(A) 44/41/37 46/42/38Air filter Resin net (with mould resistance) Resin net (with mould resistance)

    Mass kg 38 38

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)

    Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61

    Wireless BRC7GA53 BRC7GA53

    Outdoor unit RZQ125LV1 RZQ140LV1

    Colour Ivory white Ivory white

    Dimensions HWD mm 1,170900320 1,430940320

    Coil Type Cross fin coil Cross fin coil

    Comp.Type Hermetically sealed scroll type Hermetically sealed scroll type

    Motor output kW 2.4 3.15

    Fan

    Type Propeller fan Propeller fan

    Motor output W 70+70 200+200

    Airflow rate m/min 95 140

    Sound pressurelevel *3

    Cooling dB(A) 51 54

    Heating dB(A) 53 56

    Night quiet mode dB(A) 47 50

    Mass kg 98 108

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)

    Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)

    Safety devices High pressure switch, Fuse. High pressure switch, Fuse.

    Capacity step % Compressor revolution speed control (Inverter system) Compressor revolut ion speed control (Inverter system)

    Refrigerant control Electronic expansion valve Electronic expansion valve

    Ref. pipingMax. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)

    Max. height difference m 30 30

    RefrigerantModel R410A R410A

    Charge (factory charge) kg 3.15 (Charged for 30m) 4.2 (Charged for 30m)

    Ref. oilModel Refer to the nameplate of compressor. Refer to the nameplate of compressor.

    Charge L 1.2 1.5

    Drawing No.

    Specification C: 3D096434B C: 3D096434B

    Sound (Indoor) C: 4D069650E C: 4D069651E

    Sound (Outdoor) C: 4D075741A, C: 4D075747A C: 4D089680A, C: 4D089681A

    Conversion formulae

    kcal/h=kW860Btu/h=kW3412

    l/s=m/min1000/60cfm=m/min35.3

    Cooling Heating Piping length

    Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB

    Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB

    7.5m(Horizontal)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    17/156

    EDMT281536 Specifications

    SkyAir FHQ-DA + RZQS, RZQ series 15

    14.3 RZQ-HAY4A

    FHQ-DA (Ceiling suspended type)

    Notes: *1. The above data are based on the following conditions:

    *2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation

    condition, it is normally over the set value due to the environmental noise and sound reflection.

    ModelIndoor unit FHQ100DAVMA FHQ125DAVMA

    Outdoor unit RZQ100HAY4A RZQ125HAY4A

    Power supply 3 phase, 415V, 50Hz 3 phase, 415V, 50Hz

    Power supply intake Outdoor unit side Outdoor unit side

    Cooling capacity *1 *2kW 10.0 (5.0-11.2) 12.5 (5.7-14.0)

    Btu/h 34,100 (17,100-38,200) 42,700 (19,500-47,800)

    kcal/h 8,600 (4,300-9,600) 10,800 (4,900-12,000)

    Heating capacity *1 *2kW 11.2 (5.1-12.8) 14.0 (6.0-16.2)

    Btu/h 38,200 (17,400-43,700) 47,800 (20,500-55,300)

    kcal/h 9,600 (4,400-11,000) 12,000 (5,200-13,900)

    Indoor unit FHQ100DAVMA FHQ125DAVMA

    Colour Light ivory Light ivory

    Dimensions HWD mm 2351,590690 2351,590690

    Coil Type Cross fin coil Cross fin coil

    Fan

    Type Sirocco fan Sirocco fan

    Motor output W 150 150

    Airflow rate (H/M/L)

    m/min 28/24/20 31/27/23

    l/s 467/400/333 517/450/383

    cfm 988/847/706 1,094/953/812

    Sound pressure level (H/M/L) *3 dB(A) 42/38/34 44/41/37Air filter Resin net (with mould resistance) Resin net (with mould resistance)

    Mass kg 38 38

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)

    Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61

    Wireless BRC7GA53 BRC7GA53

    Outdoor unit RZQ100HAY4A RZQ125HAY4A

    Colour Ivory white Ivory white

    Dimensions HWD mm 1,345900320 1,345900320

    Coil Type Cross fin coil Cross fin coil

    Comp.Type Hermetically sealed scroll type Hermetically sealed scroll type

    Motor output kW 2.3 2.7

    Fan

    Type Propeller fan Propeller fan

    Motor output W 70+70 70+70

    Airflow rate m/min 100 100

    Sound pressurelevel *3

    Cooling dB(A) 49 50

    Heating dB(A) 51 52Night quiet mode dB(A) 45 45

    Mass kg 108 108

    Pipingconnections

    Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)

    Safety devices High pressure switch, Fuse. High pressure switch, Fuse.

    Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)

    Refrigerant control Electronic expansion valve Electronic expansion valve

    Ref. pipingMax. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)

    Max. height difference m 30 30

    RefrigerantModel R410A R410A

    Charge (factory charge) kg 4.3 (Charged for 30m) 4.3 (Charged for 30m)

    Ref. oilModel Refer to the nameplate of compressor. Refer to the nameplate of compressor.

    Charge L 1.2 1.2

    Drawing No.

    Specification C: 3D096435 C: 3D096435

    Sound (Indoor) C: 4D069652D C: 4D069650E

    Sound (Outdoor) C: 4D061464A, C: 4D061483A C: 4D061473A, C: 4D061484A

    Conversion formulae

    kcal/h=kW860Btu/h=kW3412

    l/s=m/min1000/60cfm=m/min35.3

    Cooling Heating Piping length

    Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB

    Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB

    7.5m(Horizontal)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    18/156

    Specifications EDMT281536

    16 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ-DA (Ceiling suspended type)

    Notes: *1. The above data are based on the following conditions:

    *2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation

    condition, it is normally over the set value due to the environmental noise and sound reflection.

    ModelIndoor unit FHQ140DAVMA

    Outdoor unit RZQ140HAY4A

    Power supply 3 phase, 415V, 50Hz

    Power supply intake Outdoor unit side

    Cooling capacity *1 *2kW 13.2 (6.2-15.5)

    Btu/h 45,000 (21,200-52,900)

    kcal/h 11,400 (5,300-13,300)

    Heating capacity *1 *2kW 16.0 (6.2-18.0)

    Btu/h 54,600 (21,200-61,400)

    kcal/h 13,800 (5,300-15,500)

    Indoor unit FHQ140DAVMA

    Colour Light ivory

    Dimensions HWD mm 2351,590690

    Coil Type Cross fin coil

    Fan

    Type Sirocco fan

    Motor output W 150

    Airflow rate (H/M/L)

    m/min 34/29/24

    l/s 567/483/400

    cfm 1,200/1,024/847

    Sound pressure level (H/M/L) *3 dB(A) 46/42/38Air filter Resin net (with mould resistance)

    Mass kg 38

    Pipingconnections

    Liquid mm 9.5 (Flare)Gas mm 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26)

    Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61

    Wireless BRC7GA53

    Outdoor unit RZQ140HAY4A

    Colour Ivory white

    Dimensions HWD mm 1,345900320

    Coil Type Cross fin coil

    Comp.Type Hermetically sealed scroll type

    Motor output kW 2.9

    Fan

    Type Propeller fan

    Motor output W 70+70

    Airflow rate m/min 100

    Sound pressurelevel *3

    Cooling dB(A) 50

    Heating dB(A) 52

    Night quiet mode dB(A) 46

    Mass kg 108

    Pipingconnections

    Liquid mm 9.5 (Flare)

    Gas mm 15.9 (Flare)Drain mm 26 (Hole)

    Safety devices High pressure switch, Fuse.

    Capacity step % Compressor revolution speed control (Inverter system)

    Refrigerant control Electronic expansion valve

    Ref. pipingMax. length m 75 (Equivalent length 90m)

    Max. height difference m 30

    RefrigerantModel R410A

    Charge (factory charge) kg 4.3 (Charged for 30m)

    Ref. oilModel Refer to the nameplate of compressor.

    Charge L 1.2

    Drawing No.

    Specification C: 3D096435

    Sound (Indoor) C: 4D069651E

    Sound (Outdoor) C: 4D061482B, C: 4D061485B

    Conversion formulae

    kcal/h=kW860Btu/h=kW3412

    l/s=m/min1000/60cfm=m/min35.3

    Cooling Heating Piping length

    Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB

    Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB

    7.5m(Horizontal)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    19/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 17

    15. Dimensions and service space

    5.1 Indoor unit

    5.1.1 FHQ-DA

    FHQ50DAVMA / FHQ60DAVMA

    3D096238A

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    20/156

    Dimensions and service space EDMT281536

    18 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ71DAVMA

    3D096239A

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    21/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 19

    1FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA

    3D096240A

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    22/156

    Dimensions and service space EDMT281536

    20 SkyAir FHQ-DA + RZQS, RZQ series

    5.2 Wired remote controller

    BRC1E62

    BRC1C61

    3D081567

    Unit (mm)

    3D028952A

    Unit (mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    23/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 21

    1BRC1D61

    3D048117

    Unit (mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    24/156

    Dimensions and service space EDMT281536

    22 SkyAir FHQ-DA + RZQS, RZQ series

    5.3 Wireless remote controller

    BRC7GA53

    3D079916

    Unit (mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    25/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 23

    15.4 Outdoor unit

    RZQS50AV1 / RZQS60AV1 / RZQ71LV1

    3D064945G

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    26/156

    Dimensions and service space EDMT281536

    24 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ100LV1

    3D089674B

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    27/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 25

    1RZQ125LV1

    3D058488F

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    28/156

    Dimensions and service space EDMT281536

    26 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ140LV1

    3D077411C

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    29/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 27

    1RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

    3D060941B

    Unit(mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    30/156

    Dimensions and service space EDMT281536

    28 SkyAir FHQ-DA + RZQS, RZQ series

    5.5 Installation Service Space

    RZQS50AV1 / RZQS60AV1 / RZQ71LV1

    C: 3D073764B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    31/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 29

    1

    C: 3D073764B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    32/156

    Dimensions and service space EDMT281536

    30 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ100LV1

    C: 3D089675A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    33/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 31

    1

    C: 3D089675A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    34/156

    Dimensions and service space EDMT281536

    32 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ125LV1 / RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

    C: 3D073763B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    35/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 33

    1

    C: 3D073763B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    36/156

    Dimensions and service space EDMT281536

    34 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ140LV1

    C: 3D077417B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    37/156

    EDMT281536 Dimensions and service space

    SkyAir FHQ-DA + RZQS, RZQ series 35

    1

    C: 3D077417B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    38/156

    Piping diagrams EDMT281536

    36 SkyAir FHQ-DA + RZQS, RZQ series

    6. Piping diagrams

    6.1 Indoor unit + outdoor unit

    FHQ50DAVMA + RZQS50AV1

    FHQ60DAVMA + RZQS60AV1

    3D089740

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    39/156

    EDMT281536 Piping diagrams

    SkyAir FHQ-DA + RZQS, RZQ series 37

    1FHQ71DAVMA + RZQ71LV1

    3D064949F

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    40/156

    Piping diagrams EDMT281536

    38 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ100DAVMA + RZQ100LV1

    3D089678

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    41/156

    EDMT281536 Piping diagrams

    SkyAir FHQ-DA + RZQS, RZQ series 39

    1FHQ125DAVMA + RZQ125LV1FHQ140DAVMA + RZQ140LV1

    3D058486H

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    42/156

    Piping diagrams EDMT281536

    40 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ100DAVMA + RZQ100HAY4A

    FHQ125DAVMA + RZQ125HAY4A

    FHQ140DAVMA + RZQ140HAY4A

    3D060712B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    43/156

    EDMT281536 Wiring diagrams

    SkyAir FHQ-DA + RZQS, RZQ series 41

    17. Wiring diagrams

    7.1 Indoor unit

    FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA / FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA

    3D096

    206

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    44/156

    Wiring diagrams EDMT281536

    42 SkyAir FHQ-DA + RZQS, RZQ series

    7.2 Outdoor unit

    RZQS50AV1 / RZQS60AV1

    3D089620

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    45/156

    EDMT281536 Wiring diagrams

    SkyAir FHQ-DA + RZQS, RZQ series 43

    1RZQ71LV1

    3D064851L

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    46/156

    Wiring diagrams EDMT281536

    44 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ100LV1

    3D089520

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    47/156

    EDMT281536 Wiring diagrams

    SkyAir FHQ-DA + RZQS, RZQ series 45

    1RZQ125LV1

    3D056474K

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    48/156

    Wiring diagrams EDMT281536

    46 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ140LV1

    3D077448D

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    49/156

    EDMT281536 Wiring diagrams

    SkyAir FHQ-DA + RZQS, RZQ series 47

    1RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

    C:3D047451H

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    50/156

    Field wiring EDMT281536

    48 SkyAir FHQ-DA + RZQS, RZQ series

    8. Field wiring

    FHQ50DAVMA + RZQS50AV1

    FHQ60DAVMA + RZQS60AV1

    FHQ71DAVMA + RZQ71LV1

    FHQ100DAVMA + RZQ100LV1 / RZQ100HAY4A

    FHQ125DAVMA + RZQ125LV1 / RZQ125HAY4A

    FHQ140DAVMA + RZQ140LV1 / RZQ140HAY4A

    4D044483M

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    51/156

    EDMT281536 Electric characteristics

    SkyAir FHQ-DA + RZQS, RZQ series 49

    19. Electric characteristics

    9.1 FHQ-DA + RZQS

    FHQ50DAVMA + RZQS50AV1

    FHQ60DAVMA + RZQS60AV1

    4D096569A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    52/156

    Electric characteristics EDMT281536

    50 SkyAir FHQ-DA + RZQS, RZQ series

    9.2 FHQ-DA + RZQ-LV1

    FHQ71DAVMA + RZQ71LV1

    FHQ100DAVMA + RZQ100LV1

    FHQ125DAVMA + RZQ125LV1

    FHQ140DAVMA + RZQ140LV1

    4D096559A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    53/156

    EDMT281536 Electric characteristics

    SkyAir FHQ-DA + RZQS, RZQ series 51

    19.3 FHQ-DA + RZQ-HAY4A

    FHQ100DAVMA + RZQ100HAY4A

    FHQ125DAVMA + RZQ125HAY4A

    FHQ140DAVMA + RZQ140HAY4A

    4D096646

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    54/156

    Capacity tables EDMT281536

    52 SkyAir FHQ-DA + RZQS, RZQ series

    10.Capacity tables

    10.1 RZQS

    FHQ50DAVMA + RZQS50AV1

    3D0897

    37D

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    55/156

    EDMT281536 Capacity tables

    SkyAir FHQ-DA + RZQS, RZQ series 53

    1FHQ60DAVMA + RZQS60AV1

    3D089738C

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    56/156

    Capacity tables EDMT281536

    54 SkyAir FHQ-DA + RZQS, RZQ series

    10.2 RZQ-LV1

    FHQ71DAVMA + RZQ71LV1

    3D089698C

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    57/156

    EDMT281536 Capacity tables

    SkyAir FHQ-DA + RZQS, RZQ series 55

    1FHQ100DAVMA + RZQ100LV1

    3D089699E

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    58/156

    Capacity tables EDMT281536

    56 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ125DAVMA + RZQ125LV1

    3D089701A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    59/156

    EDMT281536 Capacity tables

    SkyAir FHQ-DA + RZQS, RZQ series 57

    1FHQ140DAVMA + RZQ140LV1

    3D096968

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    60/156

    Capacity tables EDMT281536

    58 SkyAir FHQ-DA + RZQS, RZQ series

    10.3 RZQ-HAY4A

    FHQ100DAVMA + RZQ100HAY4A

    3D093044A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    61/156

    EDMT281536 Capacity tables

    SkyAir FHQ-DA + RZQS, RZQ series 59

    1FHQ125DAVMA + RZQ125HAY4A

    3D093045A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    62/156

    Capacity tables EDMT281536

    60 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ140DAVMA + RZQ140HAY4A

    3D073995C

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    63/156

    EDMT281536 Capacity tables

    SkyAir FHQ-DA + RZQS, RZQ series 61

    110.4 Capacity correction factor by the length of refrigerant piping

    RZQS50AV1 / RZQS60AV1

    RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1

    RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

    3D089679

    The capacity of the unit has to be corrected in accordance with the length of refrigerant piping.

    (The distance between the indoor unit and the outdoor unit)

    RZQ100-140: Heating (96.7%)

    Length of refrigerant piping (Total length)

    Capacitycorrectionfactor

    RZQ71: Heating (97.9%)7.5

    RZQ71: Cooling (95%)

    RZQ100: Cooling (84.2%)

    RZQ125: Cooling (75.2%)

    RZQ140: Cooling (70.0%)

    Notes: 1. line: Correction factor for Cooling Capacity, line: Correction factor for Heating Capacity

    2. The correction factor remains the same whether the outdoor unit is to be installed above or below

    the indoor unit.3. You cannot extend the refrigerant piping exceeding the limit shown in the above table.

    100

    95

    90

    85

    80

    75

    70

    (%)

    05 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 (m)

    RZQ50/60: Heating (98.8%)

    RZQ50/60: Cooling (97.2%)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    64/156

    Operation limits EDMT281536

    62 SkyAir FHQ-DA + RZQS, RZQ series

    11.Operation limits

    RZQS50AV1 / RZQS60AV1

    RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1

    RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

    3D046720M

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    65/156

    EDMT281536 Sound level

    SkyAir FHQ-DA + RZQS, RZQ series 63

    112.Sound level

    12.1 Indoor unit

    12.1.1 FHQ-DA

    FHQ50DAVMA / FHQ60DAVMA

    FHQ71DAVMA

    4D079992A

    4D069649C

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    66/156

    Sound level EDMT281536

    64 SkyAir FHQ-DA + RZQS, RZQ series

    FHQ100DAVMA

    FHQ125DAVMA

    4D069652D

    4D069650E

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    67/156

    EDMT281536 Sound level

    SkyAir FHQ-DA + RZQS, RZQ series 65

    1FHQ140DAVMA

    4D069651E

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    68/156

    Sound level EDMT281536

    66 SkyAir FHQ-DA + RZQS, RZQ series

    12.2 Outdoor unit

    12.2.1 RZQS

    RZQS50AV1 / RZQS60AV1 (Cooling)

    RZQS50AV1 / RZQS60AV1 (Heating)

    4D090424

    4D090423

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    69/156

    EDMT281536 Sound level

    SkyAir FHQ-DA + RZQS, RZQ series 67

    112.2.2 RZQ-L

    RZQ71LV1 (Cooling)

    RZQ71LV1 (Heating)

    4D075745A

    4D075748A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    70/156

    Sound level EDMT281536

    68 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ100LV1 (Cooling)

    RZQ100LV1 (Heating)

    4D089676

    4D089677A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    71/156

    EDMT281536 Sound level

    SkyAir FHQ-DA + RZQS, RZQ series 69

    1RZQ125LV1 (Cooling)

    RZQ125LV1 (Heating)

    4D075741A

    4D075747A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    72/156

    Sound level EDMT281536

    70 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ140LV1 (Cooling)

    RZQ140LV1 (Heating)

    4D089680A

    4D089681A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    73/156

    EDMT281536 Sound level

    SkyAir FHQ-DA + RZQS, RZQ series 71

    112.2.3 RZQ-HA

    RZQ100HAY4A (Cooling)

    RZQ100HAY4A (Heating)

    4D061464A

    4D061483A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    74/156

    Sound level EDMT281536

    72 SkyAir FHQ-DA + RZQS, RZQ series

    RZQ125HAY4A (Cooling)

    RZQ125HAY4A (Heating)

    4D061473A

    4D061484A

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    75/156

    EDMT281536 Sound level

    SkyAir FHQ-DA + RZQS, RZQ series 73

    1RZQ140HAY4A (Cooling)

    RZQ140HAY4A (Heating)

    4D061482B

    4D061485B

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    76/156

    Accessories EDMT281536

    74 SkyAir FHQ-DA + RZQS, RZQ series

    13.Accessories

    13.1 Indoor unit

    13.1.1 FHQ-DA

    Optional

    accessories

    C: 3D096220D

    Notes: 1. Wiring for wired remote controller to be procured locally.2. The interface adaptor for SkyAir series is not necessary because it is equipped to this indoor unit as standard.3. Installation box for adaptor PCB (KRP1D93A) is necessary.

    Item

    Model

    FHQ50DAVMAFHQ60DAVMA

    FHQ71DAVMAFHQ100DAVMAFHQ125DAVMAFHQ140DAVMA

    Replacement long-life filter KAFP501A56 KAFP501A80 KAFP501A160

    Fresh air intake kit KDDQ50A140

    Drain pump kit KDU50P140VE

    L-type piping kit (for upward direction) KHFP5N160

    Remote controller

    Wired type (Note 1) BRC1E62 / BRC1C61 / BRC1D61

    Wirelesstype

    HeatPump

    BRC7GA53

    Simplified remote controller(With operation mode selection button)

    Simplified remote controller(Without operation mode selection button)

    Central remote controller DCS302CA61

    Unified ON/OFF controller DCS301BA61

    Schedule timer DST301BA61

    intelligent Touch Controller (Note 2) DCS601C51

    Wiring adaptor for electrical appendices KRP1BA54

    Wiring adaptor for electrical appendices (Note 3) KRP4AA52

    Wiring adaptor for electrical appendices (Note 3)

    External adaptor for outdoor unit(installation on indoor unit)

    Installation box for adaptor printed circuit board KRP1D93A

    Adaptor box mounting plate KKSAP50A56

    Remote sensor KRCS01-4BRemote ON/OFF (Connector for forced on, forced off)

    Noise filter (for electromagnetic use only)

    Electrical box with earth terminal (3 blocks) KJB311AA

    Electrical box with earth terminal (2 blocks) KJB212AA

    Digital input adaptor (Note 3)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    77/156

    EDMT281536 Accessories

    SkyAir FHQ-DA + RZQS, RZQ series 75

    113.2 Outdoor unit

    13.2.1 RZQS

    C: 4D046721M

    13.2.2 RZQ-L / HA

    Optional

    accessories

    C: 4D046721M

    C: 4D077521E

    Name of option

    Kit name

    RZQS50AV1RZQS60AV1

    Central drain plug KKPJ5F180Wire fixture for preventingoverturning

    K-KYZP15C

    Fixture for preventingoverturning

    KPT-60B160

    Demand adaptor KRP58M51

    Name of option

    Kit name

    RZQ71LV1

    RZQ125LV1

    RZQ100LV1

    RZQ140LV1

    RZQ100HAY4ARZQ125HAY4A

    RZQ140HAY4ACentral drain plug KKPJ5F180 KKPJ5G280 KKPJ5F180

    Wire fixture for preventing overturning K-KYZP15C

    Fixture for preventing overturning KPT-60B160 KKTP5B112 KPT-60B160

    Demand adaptor KRP58M51

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    78/156

    Accessories EDMT281536

    76 SkyAir FHQ-DA + RZQS, RZQ series

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    79/156

    EDMT281536

    Installation of indoor / outdoor unit 77

    2

    Part 2

    Installation of

    indoor outdoor unit

    1. Centre of gravity....................................................................................78

    2. Installation of indoor unit .......................................................................812.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA /

    FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA..........................81

    3. Installation of outdoor unit ...................................................................1013.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /

    RZQ125LV1 .........................................................................................101

    3.2 RZQ140LV1 .........................................................................................117

    3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................133

    3.4 Equivalent piping length of joints (reference) .......................................149

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    80/156

    Centre of gravity EDMT281536

    78 Installation of indoor / outdoor unit

    1. Centre of gravity

    RZQS50AV1 / RZQS60AV1 / RZQ71LV1

    RZQ100LV1

    4D064948F

    Unit (mm)

    4D089656B

    Unit (mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    81/156

    EDMT281536 Centre of gravity

    Installation of indoor / outdoor unit 79

    2

    RZQ125LV1

    RZQ140LV1

    4D058487H

    Unit (mm)

    4D077529C

    Unit (mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    82/156

    Centre of gravity EDMT281536

    80 Installation of indoor / outdoor unit

    RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

    4D061670B

    Unit (mm)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    83/156

    EDMT281536 Installation of indoor unit

    Installation of indoor / outdoor unit 81

    2

    2. Installation of indoor unit

    2.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA / FHQ100DAVMA /

    FHQ125DAVMA / FHQ140DAVMA

    2.1.1 Names and Functions of Parts

    C: 3P400449-1E

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    84/156

    Installation of indoor unit EDMT281536

    82 Installation of indoor / outdoor unit

    2.1.2 Installation

    3P400451-1E

    1

    SPLIT SYSTEM Air Conditioners Installation manual

    CONTENTS

    1. SAFETY PRECAUTIONS ................................................1

    2. BEFORE INSTALLATION.................................................2

    3. SELECTION OF INSTALLATION LOCATION..................4

    4. PREPARATION BEFORE INSTALLATION.......................4

    5. INSTALLATION OF THE INDOOR UNIT .........................6

    6. REFRIGERANT PIPING WORK......................................6

    7. DRAIN PIPING WORK.....................................................9

    8. ELECTRIC WIRING WORK...........................................11

    9. HOW TO CONNECT WIRINGS AND

    WIRING EXAMPLE........................................................11

    10. MOUNTING SUCTION GRILLE

    DECORATION SIDE PANEL..........................................15

    11. FIELD SETTING ............................................................15

    12. TEST OPERATION ........................................................16

    After the installation is completed, test the air conditioner andcheck if the air conditioner operates properly. Give the user

    adequate instructions concerning the use and cleaning of the

    indoor unit according to the Operation Manual. Ask the user

    to keep this manual and the Operation Manual together in a

    handy place for future reference.

    WARNING

    Ask your local dealer or qualied personnel to carry out

    installation work.

    Improper installation may result in water leakage, electric

    shocks or a re.

    Perform installation work in accordance with this installation

    manual.

    Improper installation may result in water leakage, electric

    shocks or a re.Consult your dealer regarding what to do in case of

    refrigerant leakage.

    When the air conditioner is installed in a small room, it is

    necessary to take proper measures so that the amount of any

    leaked refrigerant does not exceed the concentration limit in

    the event of a leakage.

    Otherwise, this may lead to an accident due to oxygen deciency.

    Be sure to use only the specied parts and accessories for

    installation work.

    Failure to use the specied parts may result in the air conditioner

    falling down, water leakage, electric shocks, are, etc.

    Install the air conditioner on a foundation that can withstand

    its mass.

    Insufcient strength may result in the air conditioner falling

    down and causing injury.In addition, it may lead to vibration of indoor units and cause

    unpleasant chattering noise.

    Carry out the specied installation work in consideration of

    strong winds, typhoons, or earthquakes.

    Improper installation may result in an accident such as air

    conditioner falling.

    Make certain that all electrical work is carried out by qualied

    personnel according to the applicable legislation (note 1) and

    this installation manual, using a separate circuit.

    In addition, even if the wiring is short, make sure to use a wiring

    that has sufcient length and never connect additional

    wiring to make the length sufcient.

    Insufcient capacity of the power supply circuit or improper

    electrical construction may lead to electric shocks or a re.(note 1) applicable legislation means All international,

    national and local directives, laws, regulations and/

    or codes which are relevant and applicable for a

    certain product or domain.

    Earth the air conditioner.

    Do not connect the earth wiring to gas or water piping,

    lightning conductor or telephone earth wiring.

    Incomplete earthing may cause electric shocks or a re.

    Be sure to install an ear th leakage breaker.

    Failure to do so may cause electric shocks and a re.

    Disconnect the power supply before touching the electric

    components.

    If you touch the live part, you may get an electric shocks.

    FHQ50DAVMAFHQ60DAVMAFHQ71DAVMA

    FHQ125DAVMAFHQ100DAVMA

    FHQ140DAVMA

    1. SAFETY PRECAUTIONS

    This manual classies the precautions into WARNINGS and

    CAUTIONS.

    Be sure to follow all the precautions below: They are allimportant for ensuring safety.

    WARNING............... Indicates a potentially hazardous

    situation which, if not avoided,

    could result in death or serious

    injury.

    CAUTION.................Indicates a potentially hazardous

    situation which, if not avoided,

    may result in minor or moderate

    injury.

    It may also be used to alert

    against unsafe practices.

    Please read the these "SAFETY CONSIDERATIONS"carefully before installing air conditioning unit and be sure to

    install it correctly. After completing the installation, make surethat the unit operates properly during the start-up operation.

    Please instruct the customer on how to operate the unit andkeep it maintained.

    Also, inform customers that they should store this installationmanual along with the operation manual for future reference.

    This air conditioner comes under the term "appliances notaccessible to the general public".

    In a domestic environment this product may cause radiointerference in which case the user may be required totake adequate measures.

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    85/156

    EDMT281536 Installation of indoor unit

    Installation of indoor / outdoor unit 83

    2

    3P400451-1E

    2

    CAUTION

    Install drain piping according to this installation manual to

    ensure good drainage, and insulate the piping to prevent

    condensation.

    Improper drain piping may cause water leakage, make the

    furniture get wet.

    Install the air conditioner, power supply wiring, remote

    controller wiring and transmission wiring at least 1 meter away

    from televisions or radios to prevent image interference or noise.

    (Depending on the radio waves, a distance of 1 meter may

    not be sufcient to eliminate the noise.)

    Install the indoor unit as far as possible from orescentlamps.

    If a wireless remote controller kit is installed, the transmission

    distance may be shorter in a room where an electronic

    lighting type (inverter or rapid start type) uorescent lamp is

    installed.

    Do not install the air conditioner in places such as the

    following:

    1. Where there is mist of oil, oil spray or vapour for example

    a kitchen.

    Resin parts may deteriorate, and cause them to fall out or

    water to leak.

    2. Where corrosive gas, such as sulfurous acid gas, is

    produced.

    Corrosion of copper pipings or brazed parts may cause

    the refrigerant to leak.

    3. Where there is machinery which emits electromagnetic

    waves.

    Electromagnetic waves may disturb the control system,

    and cause malfunction of the equipment.

    4. Where ammable gases may leak, where carbon bre or

    ignitable dust is suspended in the air or where volatileammables, such as thinner or gasoline, are handled.

    If the gas should leak and remained around the air

    conditioner, it may cause ignition.

    The air conditioner is not intended for use in a potentially

    explosive atomosphere.

    2. BEFORE INSTALLATION

    SPECIAL NOTICE PRODUCT

    When unpacking and moving the indoor unit after

    unpacked, do not apply force to the piping (refrigerant and

    drain) and resin parts.

    Make sure to check in advance that the refrigerant to be used

    for installation work is R410A.

    (The air conditioner will not properly operate if a wrong

    refrigerant is used.)

    For installation of the outdoor unit, refer to the installation

    manual attached to the outdoor unit.

    Do not throw away the accessories until the installation work

    is completed.

    After the indoor unit is carried into the room, to avoid the

    indoor unit from getting damaged, take measures to protectthe indoor unit with packing materials.

    (1) Determine the route to carry the unit into the room.

    (2) Do not unpack the unit until it is carried to the installation

    location.

    Where unpacking is unavoidable, use a sling of soft

    material or protective plates together with a rope when

    lifting, to avoid damage or scratches to the indoor units.

    Have the customer actually operate the air conditioner while

    looking at the manual.

    Instruct the customer how to operate the air conditioner

    (particularly cleaning of the air lters, operation procedures,

    and temperature adjustment).

    Make sure that all wiring is secure, using the specied wiringsand ensuring that external forces do not act on the terminal

    connections or wirings.

    Incomplete connection or xing may cause an overheat or a re.

    When wiring between the indoor and outdoor units, and wiring

    the power supply, form the wirings orderly so that the controlbox lid can be securely fastened.

    If the control box lid is not in place, overheat of the terminals,

    electric shocks or a re may be caused.

    If refrigerant gas leaks during installation work, ventilate the

    area immediately.

    Toxic gas may be produced if refrigerant gas comes into

    contact with a re.

    After completing the installation work, check to make sure

    that there is no leakage of refrigerant gas.

    Toxic gas may be produced if refrigerant gas leaks into the

    room and comes into contact with a source of a re, such as

    a fan heater, stove or cooker.

    Never directly touch any accidental leaking refrigerant. This

    could result in severe wounds caused by frostbite.

    Be sure to switch off the unit before touching any electrical parts.

    Do not allow children to climb on the outdoor unit and avoidplacing objects on the unit.Injury may result if the unit becomes loose and falls.

    Make sure to provide for adequate measures in order to preventthat the outdoor unit be used as a shelter by small animals.

    Small animals making contact with electrical parts can cause keep the area around the unit clean.

    Install in a machine room that is free of moisture. The unit isdesigned for indoor use.

    Disposal requirementsDismantling of the unit, treatment of the refrigerant, of oil and ofother parts must be done in accordance with relevant local andnational legislation.

    The refrigerant R410A requires that strict precautions beobserved for keeping the system clean, dry and tightly sealed.

    Clean and dryStrict measures must be taken to keep impurities(including SUNISO oil and other mineral oils as well asmoisture) out of the system.

    Tightly sealedR410A contains no chlorine, does not destroy the ozonelayer and so does not reduce the earth's protection against

    harmful ultraviolet radiation. R410A will contribute only slightly

    to the greenhouse effect if released into the atmosphere.

    than previously. Since R410A is a mixed refrigerant, the

    required additional refrigerant must be charged in its liquid state.(If the system is charged with refrigerant in its gaseous state,due to composition change, the system will not functionnormally). The indoor unit is designed for R410A use.See the catalogue for indoor unit models that can be

    connected. (Normal operation is not possible when connectingunits that are originally designed for other refrigerants.)

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    86/156

    Installation of indoor unit EDMT281536

    84 Installation of indoor / outdoor unit

    3P400451-1E

    3

    CARRY OUT THE WORK GIVING CAUTION TO THE

    FOLLOWING ITEMS AND AFTER THE WORK IS

    COMPLETED CHECK THESE AGAIN.

    1. Items to be checked after the installation work is com-

    pleted

    *Make sure to recheck the items of SAFETY PRECAUTIONS

    2. Items to be checked at delivery

    Items to be checked In case of defectiveCheck

    column

    Are the indoor and outdoor

    units rigidly xed?

    Drop vibration

    noise

    Are the installation work of the

    outdoor and indoor units complete?

    Does not operate

    burnout

    Have you carried out a leakage

    test with the test pressure

    specied in the outdoor unit

    installation manual?

    Does not cool /

    Does not heat

    Is the insulation of refrigerant

    piping and drain piping

    completely carried out?

    Water leakage

    Does the dr ow out

    smoothly?Water leakage

    Is the power supply voltage

    identical to that stated in the

    manufacturers label on the air

    conditioner?

    Does not operate

    burnout

    Are you sure that there is no

    wrong wiring or piping or no

    loose wiring?

    Does not operate

    burnout

    Is earthing completed?Danger in case of

    leakage

    Are the sizes of electric wiring

    according to the specication?

    Does not operate

    burnout

    Is any of air outlets or inlets of

    the indoor and outdoor units

    blocked with obstacles?

    (It may lead to capacity drop

    due to fan speed drop or

    malfunction of equipment.)

    Does not cool /

    Does not heat

    Have you recorded the

    refrigerant piping length and the

    refrigerant charge added?

    Refrigerant charge

    amount is not clear

    Items to be checkedCheck

    column

    Have you carried out eld setting? (if necessary)

    Are the control box lid, the air lter and the suction grille

    attached?

    Does the cool air discharge during the cooling operation and

    the warm air discharge during heating operation?Have you explained how to operate the air conditioner

    showing the operation manual to the customer?

    Have you explained the description of cooling, heating,

    program dry and automatic (cooling/heating) given in

    the operation manual to the customer?

    If you set the fan speed at thermostat OFF, did you

    explain the set fan speed to the customer?

    Have you handed the operation manual and the

    installation manual to the customer?

    For selection of installation location, use the installationpattern paper (used in common with the packing case.)as reference.

    Do not use the air conditioner where in the salty atmosphere

    such as coastal areas, vehicles, vessels or the voltage

    tuation is frequent such as factories.

    Take off static electricity from the body when carrying out

    wiring and the control box lid is removed.

    The electric parts may be damaged.

    2-1 ACCESSORIES

    Check if the following accessories are attached to the

    indoor unit.

    2-2 OPTIONAL ACCESSORIES

    For this indoor unit, the remote controller is separately

    required. There are 2 kinds of remote controller; wired type and

    wireless type.

    Install the remote controller to the place where the customer

    has given consent.

    Refer to the catalog for the applicable model.

    (Refer to the installation manual attached to the remote

    controller for how to install.)

    Name(1) Drain

    hose

    (2) Metal

    clamp

    (3) Washer

    for hanger(4) Clamp

    Quantity 1 pc. 1 pc. 8 pcs. 7 pcs.

    Shape

    Name(5) Installation

    pattern paper

    Joint insulating

    material

    Sealing

    material

    (10) Resin

    bushing

    Quantity 1 sheet 1 each 1 each 1 pc.

    Shape

    (6) For gas

    piping

    (7) For liquid

    piping

    (8) Large

    (9) Small

    Name(11) Wiring

    xture

    (12) Screw

    for wiring

    xture (Miscellaneous)

    Operation manual

    Installation manual

    Declaration of conformity

    Quantity 2 pcs. 2 pcs.

    Shape

    M4 12

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    87/156

    EDMT281536 Installation of indoor unit

    Installation of indoor / outdoor unit 85

    2

    3P400451-1E

    4

    CAUTION

    Install the indoor and outdoor units, power supply wiring,

    remote controller wiring and transmission wiring at least 1

    meter away from televisions or radios to prevent image

    interference or noise.

    (Depending on the radio waves, a distance of 1 meter may

    not be sufcient to eliminate the noise.)

    Install the indoor unit as far as possible from orescent

    lamps.

    If a wireless remote controller kit is installed, the transmissiondistance may be shorter in a room where an electronic lighting

    type (inverter or rapid start type) uorescent lamp is installed.

    (2) Use hanging bolts for installation.

    Investigate if the installation place can withstand the mass

    of the indoor unit and, if necessary, hang the indoor unit

    with bolts after it is reinforced by beams etc. (Refer to the

    installation pattern paper (5) for the mounting pitch.).

    (3) Ceiling height

    This indoor unit can be installed up to 4.3m (for 50-71model, 3.5m) of the ceiling.

    4. PREPARATION BEFORE INSTALLATION

    (1) For the locations of indoor unit hanging bolts, piping

    outlet holes, drain piping outlet hole, and electric

    wiring inlet hole. (Refer to Fig. 3)

    Model name (FHQ-) A B C D E F G H J

    Type 50 60 960 920 378 324 270 375 398 377 260

    Type 71 1270 1230 533 479 425 530 553 532 415

    Type 100 125 140 1590 1550 693 639 585 690 713 692 575

    G H

    J 5 175

    200

    View from the front

    Left back drainpiping outlet hole Wall hole for back sidepiping outlet

    (100 hole)

    Back side wiringoutlet location

    Fig. 3

    F

    690U

    nitdimension

    210

    D

    A Unit dimension

    B Hanging bolt pitch

    View from

    the ceiling260

    30

    163

    E 189

    87

    C

    Discharge

    Unit : mm

    Top panel drain piping

    connection position

    Top panel gas sidepiping connection

    position

    Top panel liquid side pipingconnection positions

    Top panel wiring outlet position

    Hanging bolt (4 pieces)

    Han

    gingboltpitch

    Points of the operation explanation

    3. SELECTION OF INSTALLATIONLOCATION

    When unpacking and moving the indoor unit after

    unpacked, do not apply force to the piping (refrigerant and

    drain) and resin parts.

    (1) Select the installation location that meets the following

    conditions and get approval of the customer. Where the cool and warm air spreads evenly in the room.

    Where there is no obstacles in the air passage.

    Where drainage can be ensured.

    Where the ceiling lower surface is not inclined.

    Where there is sufcient strength to withstand the mass

    of the indoor unit (if the strength is insufcient, the indoor

    unit may vibrate and get in contact with the ceiling and

    generate unpleasant chattering noise).

    Where a space sufcient for installation and service can

    be ensured.(Refer to Fig. 1 and Fig. 2)

    Where the piping length between the indoor and the

    outdoor units is ensured within the allowable length. (Refer

    to the installation manual attached to the outdoor unit.)

    Where there is no risk of ammable gas leak.

    NOTENOTENOTENOTE

    If there is extra space required for * part, servicing can be

    conducted more easily if 200mm or more is secured.

    In addition to the general usage, since the items in the

    operation manual with the WARNING and CAUTION

    marks are likely to result in human bodily injuries and

    property damages, it is necessary not only to explain

    these items to the customer but also to have the

    customer read them.

    It is also necessary to explain the items of NOT

    MALFUNCTION OF THE AIR CONDITIONER to the

    customer and have the customer read them carefully.

    Fig. 1

    [ Required installation space (mm) ]

    eromro03*eromro03*

    Fig. 2

    Discharge

    Obstacles

    2500 or more evel

    For highinstallation

    Floor level

    300ormore

    Suction

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    88/156

    Installation of indoor unit EDMT281536

    86 Installation of indoor / outdoor unit

    3P400451-1E

    5

    3) Remove the hanger.

    Loosen 2 bolts for installing the hanger at both sides

    (M8) (4 places at left and right) within 10mm.

    (Refer to Fig. 7 and Fig. 8)

    Remove the xture screw for hanger at the back side

    (M5), pull the hanger backward (the arrow direction) toremove. (Refer to Fig. 8)

    CAUTION

    Do not remove the tape (milky white) applied to the outside

    of the indoor unit. It may cause electric shocks or a re.

    (4) Install the hanging bolts.

    Use M8 or M10 bolts for hanging the indoor unit.

    Adjust the length of the hanging bolt from the ceiling in

    advance. (Refer to Fig. 9) Use hole-in-anchors for the existing bolts and embedded

    inserts or foundation bolts for new bolts, and x the unit

    rmly to the building so that it may withstand the mass of

    the unit.

    In addition, adjust the distance from the ceiling in

    advance.

    CAUTION

    If the hanging bolt is too long, it may damage or break the

    indoor unit or options.

    NOTE

    Parts shown Fig. 9will be all eld supply.

    Fig. 7

    Bolt (M8)

    Indoor unit

    Hanger

    Loosen within10mm

    Fig. 8

    screw (M5)

    Hanger installing bolt (M8)

    HangerLoosen

    Fig. 9 Ceiling surface

    Hanging bolt

    Foundation bolt

    Ceiling slab

    25-55m

    m

    (2) Make holes for hanging bolts, piping outlet, drain

    piping outlet, and electric wiring inlet.

    Use the installation pattern paper (5).

    Determine the locations of hanging bol ts, piping outlet,

    drain piping outlet and electric wiring inlet. And make the

    hole.(3) Remove the parts of the indoor unit.

    1) Remove the suction grille.

    Slide the suction grille xing knobs (50, 60 type: 2

    places for each, 71~140 type: 3 places for each) toward

    backward direction (as shown by an arrow) to open the

    suction grille widely. (Refer to Fig. 4)

    Keeping the suction grille opened, hold the knob at the

    back of the suction grille and at the same time, pull the

    suction grille forward to remove. (Refer to Fig. 5)

    2) Remove the decoration side panel (right, left).

    Remove the xture screw of the decoration side panel(one for each), pull forward (arrow direction) to remove.

    (Refer to Fig. 6)

    Take out accessories. (Refer to Fig. 6)

    Open the knock hole at the wiring inlet side at the rear

    surface or top surface, and install the attached resin

    bushing (10).

    Fig. 4

    Fig. 5

    Fixing knobSuction grille

    Rear knob

    Resin bushing (10)

    (accessory)

    Removable part(for leading in from the upward-facing)

    Resin bushing (10)

    (accessory)

    Removable part

    (for leading in from the rear-facing)

    Fig. 6

    Fixing screw for decoration side Panel

    (M4)

    Decoration side panel

    Accessories

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    89/156

    EDMT281536 Installation of indoor unit

    Installation of indoor / outdoor unit 87

    2

    3P400451-1E

    6

    A. When the drain piping is tilted to the right, or to the right

    and back.

    Place it level, or tilt it slightly to the right or the back.(Within 1)

    B. When the drain piping is tilted to the left, or to the leftand back.

    Place it level, or tilt it slightly to the left or the back.(Within 1)

    WARNING

    The indoor unit must be securely installed on a place

    that can withstand the mass.

    If the strength is insufcient, the indoor unit may fall down

    and cause injuries.

    6. REFRIGERANT PIPING WORK

    For the outdoor unit refrigerant piping, refer to the installation

    manual attached to the outdoor unit.

    Carry out insulation of both gas and liquid refrigerant piping

    securely. If not insulated, it may cause water leakage. For

    gas piping, use insulation material of which heat resistant

    temperature is not less than 120C. For use under high

    humidity, strengthen the insulation material for refrigerant

    piping. If not strengthened, the surface of insulation material

    may sweat.

    Before installation work, make sure that the refrigerant is

    R410A. (Unless the refrigerant is R410A, the normal

    operation cannot be expected.)

    CAUTION

    This air conditioner is a dedicated model for new refrigerant

    R410A. Make sure to meet the requirements shown right

    and carry out installation work.

    Use dedicated piping cutters and aring tools for R410A.

    When making a are connection, coat the d inner

    surface only with ether oil or ester oil.

    Use only the are nuts attached to the air conditioner. If

    other nuts are used, it may cause refrigerant leakage.

    To prevent contamination or moisture from getting into the

    piping, take measures such as pinching or taping the

    pipings.

    Do not mix substance other than the specied refrigerant

    such as air into the refrigeration circuit.

    If the refrigerant leaks during the work, ventilate the room.

    A

    A.B

    B

    Fig. 12

    5. INSTALLATION OF THE INDOOR UNIT

    It is easy to attach the optional parts before installing the

    indoor unit. Refer to also the installation manual attached

    to the optional parts.

    For installation, use the attached installation parts and

    parts.

    (1) Fix the hanger to the hanging bolt. (Refer to Fig. 10)

    CAUTION

    For safety, make sure to use a washer for hanger (3)

    (accessory) and x by double nuts rmly.

    (2) Lift up the indoor unit, slide from the front and put the

    hanger installing bolt (M8) into the securely for temporary

    hanging.(Refer to Fig. 11)

    (3) Tighten the hanger xing screws (M5) at 2 places, which

    were removed, as they were before.

    (Refer to Fig. 11)

    It is necessary to prevent misalignment of the indoor unit.

    (4) Tighten the hanger installing bolts (M8) at 4 places

    securely.(Refer to Fig. 11)

    (5) When hanging the indoor unit, make sure to use the level to

    have better drainage and install it horizontally. Also, if it is

    possible at the installation site, install so that the drain

    piping side is slightly lower.(Refer to Fig. 12)

    CAUTION

    Setting the indoor unit at an angle opposite to the drain

    piping might cause a water leakage.

    Do not insert materials other than that into

    the clearance between the hanger and the washer for

    hanger (3).

    Unless the washers are properly attached, the hanging

    bolts may come off from the hanger.

    Hanger

    Hanging bolt

    Washer for hanger (3) (accessory)

    Double nuts

    Fig. 10

    Hanger

    ew

    (M5)

    Attachment partHanger

    Reinforcing plate (left/right)

    When carrying the indoor unit,

    do not hold the reinforcing plates.

    Hanger installing

    bolt (M8)

    Fig. 11

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    90/156

    Installation of indoor unit EDMT281536

    88 Installation of indoor / outdoor unit

    3P400451-1E

    7

    CAUTION

    Insulation of eld piping must be carried out up to the

    connection inside the casing. If the piping is exposed to the

    atmosphere, it may cause sweating or burn due to touching

    the piping, electric shocks or a re due to the wiring touchingthe piping.

    After leak test, referring to Fig. 15, insulate both the gas and

    liquid piping connection with the attached joint insulating

    material (6) and (7) to prevent the piping from getting

    exposed. Then, tighten the both ends of insulating material

    with the clamp (4).

    Wrap the sealing material (Small) (9) around the joint insulating

    material (6) nut section), only the gas piping side.

    Make sure to bring the seam of joint insulating material (6)

    and (7) to the top.

    Remove the stay for packing and delivering (reinforcing

    plate) before refrigerant piping work.

    (Refer to Fig. 18)

    The refrigerant is pre-charged in the outdoor unit.

    When connecting the pipings to the air conditioner, make sure

    to use a spanner and a torque wrench as shown in Fig.13.For the dimension of ared part, refer to the Table 1.

    When making a are connection, coat the ared inner surface

    only with ether oil or ester oil. (Refer to Fig. 14)Then, turn theare nut 3 to 4 times with your hand and screw in the nut.

    For the tightening torque, refer to the Table 1.

    Table 1

    CAUTION

    Do not have oil adhere to the screw ng part of resin

    parts.

    If oil adheres, it may weaken the strength of screwed part.

    Do not tighten e nuts too tight.

    If a nut cracks, the refrigerant may leak.

    If there is no torque wrench, use Table 2 as a rule of thumb.

    When tightening a nut with a spanner harder andharder, there is a point where the tightening torque suddenly

    increases. From that position, tighten the nut additionally the

    angle shown in Table 2. After the work is nished, check

    securely that there is no gas leak. If the nut is not tightened

    as instructed, it may cause slow refrigerant leak and result in

    malfunction (such as does not cool or heat).

    Table 2

    Piping size

    (mm)

    Tightening

    torque (Nm)

    Dimension

    for processing

    e A (mm)

    Flare shape

    6.4 15.7 1.5 8.9 0.2

    9.5 36.3 3.6 13.0 0.2

    12.7 54.9 5.4 16.4 0.2

    15.9 68.6 6.8 19.5 0.2

    Piping size

    (mm)Tightening angle

    Recommended arm length

    of tool used

    6.4 60 90 Approximately 150mm

    9.5 60 90 Approximately 200mm

    12.7 30 60 Approximately 250mm

    15.9 30 60 Approximately 300mm

    Torque wrench

    Spanner

    Flare nut

    Union joint Fig. 13

    face

    only with ether oil or ester oil.

    Fig. 14

    R0.4-0.8

    902

    A

    45

    2

  • 7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series

    91/156

    EDMT281536 Installation of indoor unit

    Installation of indoor / outdoor unit 89

    2

    3P400451-1E

    8

    (1) For rear side piping

    Remove the rear piping penetration cover, and connect

    the piping. (Refer to Fig. 16 and Fig. 18)

    (2) For upward piping

    For upward piping, L-shaped connection piping kit

    (optional accessory) will be required. Remove the top panel penetration cover, and use the L-

    shaped connection piping kit (optional accessory) to con-

    duct piping. (Refer to Fig. 16 and Fig. 17)

    (3) For right side piping

    Remove the stay for packing and delivering (reinforcing

    plate) at the right side, and put back the screw to the orig-

    inal position of the indoor unit. (Refer to Fig. 18)

    Open the knockout hole at the decoration side panel

    (right), and connect piping. (Refer to Fig. 18)

    Top panel penetration cover

    Cut at the position avoidingthe knob part of the

    penetration cover

    Rear piping penetration cover

    View fromair inlet side

    Cutoff

    Cutoff

    Top panel

    Fig. 16

    Upward refrigerant piping

    L-shaped branch piping kit(Optional accessory)

    Fig. 17

    Screw(put back to the indoor unit)

    Decoration side panel (right)Separating parts

    Cut only this part when laying onlythe drain piping on the right side.

    Stay for packing and delivering(reinforcing plate)

    Right side refrigerant piping

    Rear side drain piping

    Rear side refrigerant piping

    Right side drain piping

    Fig. 18

    Joint insulating material (6) (accessory)

    Gas side piping insulating method

    Piping insulating material (unit side)Do not leaveclearance

    Wrap from theroot of the unit

    Sealing material (Small) (9)(accessory)

    Bring the seamto the top

    Flare nutconnection

    Piping insulating material

    For prevention of sweating,do not expose the piping

    Clamp (4) (accessory) Tighten the pipinginsulating material

    Liquid side piping insulating method

    Joint insulating material (7)(accessory)

    Flare nutconnection

    Piping insulatingmater

    For prevention of sweating,do not expose the piping

    Fig. 15

    Gas piping

    Liquid piping

    Indoor unit

    Bring the seamto the top

    Piping insulating material(unit side)

    Do not leave clearance

    Clamp (4)(access