edmt281536 fhq davma,rzqs, rzq series
TRANSCRIPT
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
1/156
EDMT281536
FHQ-DA + RZQS, RZQ series
Heat pump 50Hz
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
2/156
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
3/156
EDMT281536
Table of contents 1
Part 1 SkyAir FHQ-DA + RZQS, RZQ series ..................................5
1. External appearance...............................................................................7
2. Model name, power supply and nomenclature .......................................92.1 Model name and power supply ................................................................9
2.2 Nomenclature.........................................................................................10
3. Functions...............................................................................................11
4. Specifications........................................................................................124.1 RZQS .....................................................................................................12
4.2 RZQ-LV1 ................................................................................................13
4.3 RZQ-HAY4A...........................................................................................15
5. Dimensions and service space .............................................................175.1 Indoor unit ..............................................................................................17
5.2 Wired remote controller ..........................................................................20
5.3 Wireless remote controller......................................................................22
5.4 Outdoor unit............................................................................................23
5.5 Installation Service Space......................................................................286. Piping diagrams ....................................................................................36
6.1 Indoor unit + outdoor unit .......................................................................36
7. Wiring diagrams ....................................................................................417.1 Indoor unit ..............................................................................................41
7.2 Outdoor unit............................................................................................42
8. Field wiring ............................................................................................48
9. Electric characteristics ..........................................................................499.1 FHQ-DA + RZQS....................................................................................49
9.2 FHQ-DA + RZQ-LV1 ..............................................................................50
9.3 FHQ-DA + RZQ-HAY4A.........................................................................5110.Capacity tables......................................................................................52
10.1 RZQS .....................................................................................................52
10.2 RZQ-LV1 ................................................................................................54
10.3 RZQ-HAY4A...........................................................................................58
10.4 Capacity correction factor by the length of refrigerant piping .................61
11.Operation limits .....................................................................................62
12.Sound level ...........................................................................................6312.1 Indoor unit ..............................................................................................63
12.2 Outdoor unit............................................................................................66
13.Accessories...........................................................................................7413.1 Indoor unit ..............................................................................................74
13.2 Outdoor unit............................................................................................75
Part 2 Installation of indoor / outdoor unit.................................77
1. Centre of gravity....................................................................................78
2. Installation of indoor unit .......................................................................812.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA /
FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA..........................81
3. Installation of outdoor unit ...................................................................1013.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /
RZQ125LV1 .........................................................................................101
3.2 RZQ140LV1 .........................................................................................117
3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................133
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
4/156
EDMT281536
2 Table of contents
3.4 Equivalent piping length of joints (reference) .......................................149
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
5/156
EDMT281536 Publication list
Table of contents 3
Publication listRefrigerant
Inverter/Non Inverter
Series Book No. Type, HzModel name of
indoor / outdoor unitArea Note
Publishedin
R410A Inverter
RZQ
EDHK281002 H/P 50Hz
- Indoor unitsFCQ71/100/125/140KVEAFFQ25/35/50/60BV1BFHQ35/50/60/71/100/125BVV1BFBQ50/60BV1A
FBQ71/100/125/140DV1
- Outdoor unitsRZQ71KBV1RZQ100/125/140HY4ARXS25/35EBVMARXS50/60FVMARKS25/35EBVMARKS50/60FVMA
Hong Kong Jun. 2010
EDVN281408 H/P 50Hz
- Indoor unitsFCQ50/60LUV1VFCQ71-140LUV1FFQ25-60BV1BFHQ50/60BVV1VFHQ35/71/100/125BVV1BFHQ140CAVEAFDXS25-60CVMAFBQ50-71BV1A
FBQ50/60DV1VFBQ71-140DV1FVQ50/60CVEFVQ71-140CVEB
- Outdoor unitsRZQ50/60KBV1VRZQ50/60KBV4ARZQ71-140KCV4ARZQ100-140HAY4ARXS25/35EBVMARXS50FAVMARXS50-71FVMA
Vietnam
- New lineup of indoor units:FCQ50/60LUV1V
FHQ50/60BVV1VFBQ50/60DV1VFVQ50/60CVE
- New lineup of outdoor units:RZQ50/60KBV1V
Sep. 2014
RZQSRZQ
EDMT281426 H/P 50Hz
- Indoor unitsFCQ71/100/125/140KAVEAFHQ71/100/125BWV1A
FHQ140CAVEAFAQ71/100CVEAFBQ71/100/125/140DBVEAFVQ50/60CVEFVQ71/100/125/140CVEB
- Outdoor unitsRZQS50/60AV1RZQ71/100/125/140LV1RZQ100/125/140HAY4A
VietnamIndia
Hong Kong
- New lineup of indoor units:FHQ71/100/125BWV1AFBQ71/100/125/140DBVEA
- Model change of indoor units:
FCQ71/100/125/140KVEA
FCQ71/100/125/140KAVEA
- New lineup of outdoor units:RZQS50/60AV1RZQ71/100/125/140LV1
- Discontinued outdoor units:RZQ71KBV1RZQ50/60KBV4ARZQ71-140KCV4A
Mar. 2015
EDMT281512H/P
50/60Hz
- Indoor unitsFBQ50/60/71/100/125/140EVE
- Outdoor unitsRZQS50/60AV1RZQ71/100/125/140LV1
RZQ100/125/140HAY4ARZQ100/125/140KCTLTRZQ100/125/140LUYLT
VietnamPhilippines
India
Hong Kong
- New lineup of indoor units:FBQ50/60/71/100/125/140EVE Aug. 2015
EDMT281536 H/P 50Hz
- Indoor unitsFHQ50/60/71/100/125/140DAVMA
- Outdoor unitsRZQS50/60AV1RZQ71/100/125/140LV1RZQ100/125/140HAY4A
Hong KongVietnam
India
- New lineup of indoor units:FHQ50/60/71/100/125/140DAVMA
Dec. 2015
EDMT281536as shown by .
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
6/156
Publication list EDMT281536
4 Table of contents
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
7/156
EDMT281536
SkyAir FHQ-DA + RZQS, RZQ series 5
1art 1
SkyAir
FHQ-DA RZQS, RZQ series
Model series
1. External appearance...............................................................................7
2. Model name, power supply and nomenclature .......................................92.1 Model name and power supply ................................................................92.2 Nomenclature.........................................................................................10
3. Functions...............................................................................................114. Specifications........................................................................................12
4.1 RZQS .....................................................................................................124.2 RZQ-LV1 ................................................................................................134.3 RZQ-HAY4A...........................................................................................15
5. Dimensions and service space .............................................................175.1 Indoor unit ..............................................................................................175.2 Wired remote controller ..........................................................................205.3 Wireless remote controller......................................................................225.4 Outdoor unit............................................................................................235.5 Installation Service Space......................................................................28
6. Piping diagrams ....................................................................................366.1 Indoor unit + outdoor unit .......................................................................36
7. Wiring diagrams ....................................................................................417.1 Indoor unit ..............................................................................................417.2 Outdoor unit............................................................................................42
8. Field wiring ............................................................................................48
9. Electric characteristics ..........................................................................499.1 FHQ-DA + RZQS....................................................................................499.2 FHQ-DA + RZQ-LV1 ..............................................................................509.3 FHQ-DA + RZQ-HAY4A.........................................................................51
10.Capacity tables......................................................................................5210.1 RZQS .....................................................................................................5210.2 RZQ-LV1 ................................................................................................5410.3 RZQ-HAY4A...........................................................................................5810.4 Capacity correction factor by the length of refrigerant piping .................61
Class 50 60 71 100 125 140 Power
supply
Indoorunit
FHQ 50DA 60DA 71DA 100DA 125DA 140DA VMA
Outdoorunit
RZQS 50A 60A V1
RZQ71L 100L 125L 140L V1
100HA 125HA 140HA Y4A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
8/156
EDMT281536
6 SkyAir FHQ-DA + RZQS, RZQ series
11.Operation limits .....................................................................................62
12.Sound level ...........................................................................................6312.1 Indoor unit ..............................................................................................6312.2 Outdoor unit............................................................................................66
13.Accessories...........................................................................................7413.1 Indoor unit ..............................................................................................74
13.2 Outdoor unit............................................................................................75
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
9/156
EDMT281536 External appearance
SkyAir FHQ-DA + RZQS, RZQ series 7
11. External appearance
Indoor unit
Wired
remote controller
Wireless
remote controller
FHQ-DAVMA
BRC1E62 BRC1C61 BRC1D61
BRC7GA53 Signal receiver unit
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
10/156
External appearance EDMT281536
8 SkyAir FHQ-DA + RZQS, RZQ series
Outdoor unit
RZQS50AV1RZQS60AV1
RZQ71LV1 RZQ100LV1 RZQ125LV1 RZQ140LV1
RZQ100HAY4ARZQ125HAY4ARZQ140HAY4A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
11/156
EDMT281536 Model name, power supply and nomenclature
SkyAir FHQ-DA + RZQS, RZQ series 9
12. Model name, power supply and nomenclature
2.1 Model name and power supply
Indoor unit Outdoor unitPower supply intake
Type Model name Model name
Ceiling suspended type
FHQ50DAVMA RZQS50AV1
Outdoor unit: 1 phase, 220-240V, 50Hz
FHQ60DAVMA RZQS60AV1
FHQ71DAVMA RZQ71LV1
FHQ100DAVMA RZQ100LV1
FHQ125DAVMA RZQ125LV1
FHQ140DAVMA RZQ140LV1
FHQ100DAVMA RZQ100HAY4A
Outdoor unit: 3 phase, 415V, 50HzFHQ125DAVMA RZQ125HAY4A
FHQ140DAVMA RZQ140HAY4A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
12/156
Model name, power supply and nomenclature EDMT281536
10 SkyAir FHQ-DA + RZQS, RZQ series
2.2 Nomenclature
Indoor unit
Outdoor unit
Standard symbolA: Australia
Power supply symbolV1: 1 phase, 220-240V, 50HzVE: 1 phase, 220-240/220V, 50/60HzVM: 1 phase, 220-240/220-230V, 50/60Hz
Indicates major design category
Capacity indication
Refrigerant and typeQ: R410A, Heat pump or Cooling only
ShapeC: Ceiling mounted cassette (Round flow)H: Ceiling suspended
A: Wall mountedB(-E): Middle static pressure ceiling mounted duct
Unit categoryF: Air cooled split indoor unit
VMDAQF H A50
Standard symbolA: Australia
Power supply symbol
V1: 1 phase, 220-240V, 50HzY4: 3 phase, 415V, 50Hz
Indicates major design category
Capacity indication
Grade and refrigerant symbolS: Inverter, R410A
Refrigerant and typeQ: R410A, Heat Pump
Inverter / Non inverterZ: Inverter
Unit categoryR: Air cooled split outdoor unit
V1Q S 50Z AR
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
13/156
EDMT281536 Functions
SkyAir FHQ-DA + RZQS, RZQ series 11
13. Functions
Notes: : Functions exist.
: No functions
*1: Applicable when wired remote controller is used
*2: For the outdoor units
*3: Applicable when BRC1D61 or BRC1E62 is used
*4: Option
*5: Applicable when BRC1E62 is used
*6: Applicable when BRC1C61 is used
*7: Installable on max. 3.5m (50-71) and 4.3m (100-140) high ceiling.
Category Function
Indoorunit
FHQ50-60DAVMA FHQ71-140DAVMA
Outdoorunit
RZQS50-60AV1RZQ71-140LV1
RZQ100-140HAY4A
Inverter control
Comfort
Auto swing
Swing pattern selection
Draft prevention function (heating)
Independent up-and-down airflow
DC fan motor (Indoor unit)
Switchable fan speed (3 step) (3 step)
Auto airflow rate
High fan speed mode
Programme Dry
High ceiling application (*7) (*7)
Two selectable temperature-sensors (*1)
Hot start
Year-round cooling applicable
Night quiet operation (*2)
Remotecontroller
Setpoint auto reset (*5)
Setpoint range set (*5)
Weekly schedule timer (*3)
Off timer (programmed) (*5)
On/Off timer (*6)
Cleanliness
Anti-bacterial air filter
Mould-proof air filter
Silver ion anti-bacterial drain pan
Mould-proof drain pan
Work &servicing
Drain pump mechanism (*4)
Pre-charged for up to 30 m (*2)
Pre-charged for up to 10 m (*2) Long-life filter
Filter sign
Ceiling soiling prevention
Low gas pressure detection (*2)
Emergency operation
Self-diagnosis function
Controlfeatures
Auto-restart
Auto-cooling/heating change-over
Control by 2 remote controllers
Group control by 1 remote controller
External command control (*4)
Central remote control
Interlock control with Heat Reclaim Ventilator DIII-NET communication standard
Options
High-efficiency filter
Ultra long-life filter
Fresh air intake kit
Others Anti corrosion treated heat exchangers (*2)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
14/156
Specifications EDMT281536
12 SkyAir FHQ-DA + RZQS, RZQ series
4. Specifications
4.1 RZQS
FHQ-DA (Ceiling suspended type)
Notes: *1. The above data are based on the following conditions:
*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.
ModelIndoor unit FHQ50DAVMA FHQ60DAVMA
Outdoor unit RZQS50AV1 RZQS60AV1Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
Cooling capacity *1 *2kW 5.0 (3.2-5.6) 6.0 (3.2-6.0)
Btu/h 17,100 (10,900-19,100) 20,500 (10,900-20,500)
kcal/h 4,300 (2,800-4,800) 5,200 (2,800-5,200)
Heating capacity *1 *2kW 6.0 (3.5-7.0) 6.8 (3.5-8.0)
Btu/h 20,500 (11,900-23,900) 23,200 (11,900-27,300)
kcal/h 5,200 (3,000-6,000) 5,900 (3,000-6,900)
Indoor unit FHQ50DAVMA FHQ60DAVMA
Colour Light ivory Light ivory
Dimensions HWD mm 235960690 235960690
Coil Type Cross fin coil Cross fin coil
Fan
Type Sirocco fan Sirocco fan
Motor output W 87 87
Airflow rate (H/M/L)
m/min 15/12/10 15/12/10
l/s 250/200/167 250/200/167
cfm 530/424/353 530/424/353
Sound pressure level (H/M/L) *3 dB(A) 37/35/32 37/35/32Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 25 25
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)
Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61
Wireless BRC7GA53 BRC7GA53
Outdoor unit RZQS50AV1 RZQS60AV1
Colour Ivory white Ivory white
Dimensions HWD mm 770900320 770900320
Coil Type Cross fin coil Cross fin coil
Comp.Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.3 1.6
Fan
Type Propeller fan Propeller fan
Motor output W 70 70Airflow rate m/min 52 52
Sound pressurelevel *3
Cooling dB(A) 48 48
Heating dB(A) 50 50
Night quiet mode dB(A) 44 44
Mass kg 64 64
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)
Safety devices High pressure switch, Fuse. High pressure switch, Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolut ion speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Ref. pipingMax. length m 50 (Equivalent length 70m) 50 (Equivalent length 70m)
Max. height difference m 30 30
RefrigerantModel R410A R410A
Charge (factory charge) kg 2.0 (Charged for 30m) 2.0 (Charged for 30m)
Ref. oil
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Charge L 0.75 0.75
Drawing No.
Specification C: 3D096268A C: 3D096268A
Sound (Indoor) C: 4D079992A C: 4D079992A
Sound (Outdoor) C: 4D090424, C: 4D090423 C: 4D090424, C: 4D090423
Conversion formulae
kcal/h=kW860Btu/h=kW3412
l/s=m/min1000/60cfm=m/min35.3
Cooling Heating Piping length
Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB
Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB
7.5m(Horizontal)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
15/156
EDMT281536 Specifications
SkyAir FHQ-DA + RZQS, RZQ series 13
14.2 RZQ-LV1
FHQ-DA (Ceiling suspended type)
Notes: *1. The above data are based on the following conditions:
*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.
ModelIndoor unit FHQ71DAVMA FHQ100DAVMA
Outdoor unit RZQ71LV1 RZQ100LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
Cooling capacity *1 *2kW 7.1 (3.2-8.0) 10.0 (5.0-11.2)
Btu/h 24,200 (10,900-27,300) 34,100 (17,100-38,200)
kcal/h 6,100 (2,800-6,900) 8,600 (4,300-9,600)
Heating capacity *1 *2kW 8.0 (3.5-9.0) 11.2 (5.1-12.8)
Btu/h 27,300 (11,900-30,700) 38,200 (17,400-43,700)
kcal/h 6,900 (3,000-7,700) 9,600 (4,400-11,000)
Indoor unit FHQ71DAVMA FHQ100DAVMA
Colour Light ivory Light ivory
Dimensions HWD mm 2351,270690 2351,590690
Coil Type Cross fin coil Cross fin coil
Fan
Type Sirocco fan Sirocco fan
Motor output W 117 150
Airflow rate (H/M/L)
m/min 20.5/17/14 28/24/20
l/s 342/283/233 467/400/333
cfm 724/600/494 988/847/706
Sound pressure level (H/M/L) *3 dB(A) 38/36/34 42/38/34Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 32 38
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)
Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61
Wireless BRC7GA53 BRC7GA53
Outdoor unit RZQ71LV1 RZQ100LV1
Colour Ivory white Ivory white
Dimensions HWD mm 770900320 990940320
Coil Type Cross fin coil Cross fin coil
Comp.Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.7 2.08
Fan
Type Propeller fan Propeller fan
Motor output W 70 200
Airflow rate m/min 52 76
Sound pressurelevel *3
Cooling dB(A) 49 51
Heating dB(A) 51 53Night quiet mode dB(A) 45 47
Mass kg 64 75
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)
Safety devices High pressure switch, Fuse. High pressure switch, Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolut ion speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Ref. pipingMax. length m 50 (Equivalent length 70m) 75 (Equivalent length 90m)
Max. height difference m 30 30
RefrigerantModel R410A R410A
Charge (factory charge) kg 2.0 (Charged for 30m) 2.9 (Charged for 30m)
Ref. oilModel Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Charge L 0.75 0.75
Drawing No.
Specification C: 3D096434B C: 3D096434B
Sound (Indoor) C: 4D069649C C: 4D069652D
Sound (Outdoor) C: 4D075745A, C: 4D075748A C: 4D089676, C: 4D089677A
Conversion formulae
kcal/h=kW860Btu/h=kW3412
l/s=m/min1000/60cfm=m/min35.3
Cooling Heating Piping length
Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB
Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB
7.5m(Horizontal)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
16/156
Specifications EDMT281536
14 SkyAir FHQ-DA + RZQS, RZQ series
FHQ-DA (Ceiling suspended type)
Notes: *1. The above data are based on the following conditions:
*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.
ModelIndoor unit FHQ125DAVMA FHQ140DAVMA
Outdoor unit RZQ125LV1 RZQ140LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
Cooling capacity *1 *2kW 12.5 (5.7-14.0) 13.2 (6.2-15.5)
Btu/h 42,700 (19,500-47,800) 45,000 (21,200-52,900)
kcal/h 10,800 (4,900-12,000) 11,400 (5,300-13,300)
Heating capacity *1 *2kW 14.0 (6.0-16.2) 16.0 (6.2-18.0)
Btu/h 47,800 (20,500-55,300) 54,600 (21,200-61,400)
kcal/h 12,000 (5,200-13,900) 13,800 (5,300-15,500)
Indoor unit FHQ125DAVMA FHQ140DAVMA
Colour Light ivory Light ivory
Dimensions HWD mm 2351,590690 2351,590690
Coil Type Cross fin coil Cross fin coil
Fan
Type Sirocco fan Sirocco fan
Motor output W 150 150
Airflow rate (H/M/L)
m/min 31/27/23 34/29/24
l/s 517/450/383 567/483/400
cfm 1,094/953/812 1,200/1,024/847
Sound pressure level (H/M/L) *3 dB(A) 44/41/37 46/42/38Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 38 38
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)
Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61
Wireless BRC7GA53 BRC7GA53
Outdoor unit RZQ125LV1 RZQ140LV1
Colour Ivory white Ivory white
Dimensions HWD mm 1,170900320 1,430940320
Coil Type Cross fin coil Cross fin coil
Comp.Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 2.4 3.15
Fan
Type Propeller fan Propeller fan
Motor output W 70+70 200+200
Airflow rate m/min 95 140
Sound pressurelevel *3
Cooling dB(A) 51 54
Heating dB(A) 53 56
Night quiet mode dB(A) 47 50
Mass kg 98 108
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)
Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)
Safety devices High pressure switch, Fuse. High pressure switch, Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolut ion speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Ref. pipingMax. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Max. height difference m 30 30
RefrigerantModel R410A R410A
Charge (factory charge) kg 3.15 (Charged for 30m) 4.2 (Charged for 30m)
Ref. oilModel Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Charge L 1.2 1.5
Drawing No.
Specification C: 3D096434B C: 3D096434B
Sound (Indoor) C: 4D069650E C: 4D069651E
Sound (Outdoor) C: 4D075741A, C: 4D075747A C: 4D089680A, C: 4D089681A
Conversion formulae
kcal/h=kW860Btu/h=kW3412
l/s=m/min1000/60cfm=m/min35.3
Cooling Heating Piping length
Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB
Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB
7.5m(Horizontal)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
17/156
EDMT281536 Specifications
SkyAir FHQ-DA + RZQS, RZQ series 15
14.3 RZQ-HAY4A
FHQ-DA (Ceiling suspended type)
Notes: *1. The above data are based on the following conditions:
*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.
ModelIndoor unit FHQ100DAVMA FHQ125DAVMA
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Power supply 3 phase, 415V, 50Hz 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
Cooling capacity *1 *2kW 10.0 (5.0-11.2) 12.5 (5.7-14.0)
Btu/h 34,100 (17,100-38,200) 42,700 (19,500-47,800)
kcal/h 8,600 (4,300-9,600) 10,800 (4,900-12,000)
Heating capacity *1 *2kW 11.2 (5.1-12.8) 14.0 (6.0-16.2)
Btu/h 38,200 (17,400-43,700) 47,800 (20,500-55,300)
kcal/h 9,600 (4,400-11,000) 12,000 (5,200-13,900)
Indoor unit FHQ100DAVMA FHQ125DAVMA
Colour Light ivory Light ivory
Dimensions HWD mm 2351,590690 2351,590690
Coil Type Cross fin coil Cross fin coil
Fan
Type Sirocco fan Sirocco fan
Motor output W 150 150
Airflow rate (H/M/L)
m/min 28/24/20 31/27/23
l/s 467/400/333 517/450/383
cfm 988/847/706 1,094/953/812
Sound pressure level (H/M/L) *3 dB(A) 42/38/34 44/41/37Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 38 38
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26) VP20 (I.D.20O.D.26)
Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61 BRC1E62 / BRC1C61 / BRC1D61
Wireless BRC7GA53 BRC7GA53
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Colour Ivory white Ivory white
Dimensions HWD mm 1,345900320 1,345900320
Coil Type Cross fin coil Cross fin coil
Comp.Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 2.3 2.7
Fan
Type Propeller fan Propeller fan
Motor output W 70+70 70+70
Airflow rate m/min 100 100
Sound pressurelevel *3
Cooling dB(A) 49 50
Heating dB(A) 51 52Night quiet mode dB(A) 45 45
Mass kg 108 108
Pipingconnections
Liquid mm 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare)Drain mm 26 (Hole) 26 (Hole)
Safety devices High pressure switch, Fuse. High pressure switch, Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Ref. pipingMax. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Max. height difference m 30 30
RefrigerantModel R410A R410A
Charge (factory charge) kg 4.3 (Charged for 30m) 4.3 (Charged for 30m)
Ref. oilModel Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Charge L 1.2 1.2
Drawing No.
Specification C: 3D096435 C: 3D096435
Sound (Indoor) C: 4D069652D C: 4D069650E
Sound (Outdoor) C: 4D061464A, C: 4D061483A C: 4D061473A, C: 4D061484A
Conversion formulae
kcal/h=kW860Btu/h=kW3412
l/s=m/min1000/60cfm=m/min35.3
Cooling Heating Piping length
Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB
Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB
7.5m(Horizontal)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
18/156
Specifications EDMT281536
16 SkyAir FHQ-DA + RZQS, RZQ series
FHQ-DA (Ceiling suspended type)
Notes: *1. The above data are based on the following conditions:
*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.
ModelIndoor unit FHQ140DAVMA
Outdoor unit RZQ140HAY4A
Power supply 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side
Cooling capacity *1 *2kW 13.2 (6.2-15.5)
Btu/h 45,000 (21,200-52,900)
kcal/h 11,400 (5,300-13,300)
Heating capacity *1 *2kW 16.0 (6.2-18.0)
Btu/h 54,600 (21,200-61,400)
kcal/h 13,800 (5,300-15,500)
Indoor unit FHQ140DAVMA
Colour Light ivory
Dimensions HWD mm 2351,590690
Coil Type Cross fin coil
Fan
Type Sirocco fan
Motor output W 150
Airflow rate (H/M/L)
m/min 34/29/24
l/s 567/483/400
cfm 1,200/1,024/847
Sound pressure level (H/M/L) *3 dB(A) 46/42/38Air filter Resin net (with mould resistance)
Mass kg 38
Pipingconnections
Liquid mm 9.5 (Flare)Gas mm 15.9 (Flare)Drain mm VP20 (I.D.20O.D.26)
Remote controller (option)Wired BRC1E62 / BRC1C61 / BRC1D61
Wireless BRC7GA53
Outdoor unit RZQ140HAY4A
Colour Ivory white
Dimensions HWD mm 1,345900320
Coil Type Cross fin coil
Comp.Type Hermetically sealed scroll type
Motor output kW 2.9
Fan
Type Propeller fan
Motor output W 70+70
Airflow rate m/min 100
Sound pressurelevel *3
Cooling dB(A) 50
Heating dB(A) 52
Night quiet mode dB(A) 46
Mass kg 108
Pipingconnections
Liquid mm 9.5 (Flare)
Gas mm 15.9 (Flare)Drain mm 26 (Hole)
Safety devices High pressure switch, Fuse.
Capacity step % Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve
Ref. pipingMax. length m 75 (Equivalent length 90m)
Max. height difference m 30
RefrigerantModel R410A
Charge (factory charge) kg 4.3 (Charged for 30m)
Ref. oilModel Refer to the nameplate of compressor.
Charge L 1.2
Drawing No.
Specification C: 3D096435
Sound (Indoor) C: 4D069651E
Sound (Outdoor) C: 4D061482B, C: 4D061485B
Conversion formulae
kcal/h=kW860Btu/h=kW3412
l/s=m/min1000/60cfm=m/min35.3
Cooling Heating Piping length
Indoor: 27CDB, 19CWBOutdoor: 35CDB, 24CWB
Indoor: 20CDB, 15CWBOutdoor: 7CDB, 6CWB
7.5m(Horizontal)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
19/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 17
15. Dimensions and service space
5.1 Indoor unit
5.1.1 FHQ-DA
FHQ50DAVMA / FHQ60DAVMA
3D096238A
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
20/156
Dimensions and service space EDMT281536
18 SkyAir FHQ-DA + RZQS, RZQ series
FHQ71DAVMA
3D096239A
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
21/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 19
1FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA
3D096240A
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
22/156
Dimensions and service space EDMT281536
20 SkyAir FHQ-DA + RZQS, RZQ series
5.2 Wired remote controller
BRC1E62
BRC1C61
3D081567
Unit (mm)
3D028952A
Unit (mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
23/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 21
1BRC1D61
3D048117
Unit (mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
24/156
Dimensions and service space EDMT281536
22 SkyAir FHQ-DA + RZQS, RZQ series
5.3 Wireless remote controller
BRC7GA53
3D079916
Unit (mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
25/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 23
15.4 Outdoor unit
RZQS50AV1 / RZQS60AV1 / RZQ71LV1
3D064945G
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
26/156
Dimensions and service space EDMT281536
24 SkyAir FHQ-DA + RZQS, RZQ series
RZQ100LV1
3D089674B
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
27/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 25
1RZQ125LV1
3D058488F
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
28/156
Dimensions and service space EDMT281536
26 SkyAir FHQ-DA + RZQS, RZQ series
RZQ140LV1
3D077411C
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
29/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 27
1RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A
3D060941B
Unit(mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
30/156
Dimensions and service space EDMT281536
28 SkyAir FHQ-DA + RZQS, RZQ series
5.5 Installation Service Space
RZQS50AV1 / RZQS60AV1 / RZQ71LV1
C: 3D073764B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
31/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 29
1
C: 3D073764B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
32/156
Dimensions and service space EDMT281536
30 SkyAir FHQ-DA + RZQS, RZQ series
RZQ100LV1
C: 3D089675A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
33/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 31
1
C: 3D089675A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
34/156
Dimensions and service space EDMT281536
32 SkyAir FHQ-DA + RZQS, RZQ series
RZQ125LV1 / RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A
C: 3D073763B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
35/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 33
1
C: 3D073763B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
36/156
Dimensions and service space EDMT281536
34 SkyAir FHQ-DA + RZQS, RZQ series
RZQ140LV1
C: 3D077417B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
37/156
EDMT281536 Dimensions and service space
SkyAir FHQ-DA + RZQS, RZQ series 35
1
C: 3D077417B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
38/156
Piping diagrams EDMT281536
36 SkyAir FHQ-DA + RZQS, RZQ series
6. Piping diagrams
6.1 Indoor unit + outdoor unit
FHQ50DAVMA + RZQS50AV1
FHQ60DAVMA + RZQS60AV1
3D089740
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
39/156
EDMT281536 Piping diagrams
SkyAir FHQ-DA + RZQS, RZQ series 37
1FHQ71DAVMA + RZQ71LV1
3D064949F
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
40/156
Piping diagrams EDMT281536
38 SkyAir FHQ-DA + RZQS, RZQ series
FHQ100DAVMA + RZQ100LV1
3D089678
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
41/156
EDMT281536 Piping diagrams
SkyAir FHQ-DA + RZQS, RZQ series 39
1FHQ125DAVMA + RZQ125LV1FHQ140DAVMA + RZQ140LV1
3D058486H
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
42/156
Piping diagrams EDMT281536
40 SkyAir FHQ-DA + RZQS, RZQ series
FHQ100DAVMA + RZQ100HAY4A
FHQ125DAVMA + RZQ125HAY4A
FHQ140DAVMA + RZQ140HAY4A
3D060712B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
43/156
EDMT281536 Wiring diagrams
SkyAir FHQ-DA + RZQS, RZQ series 41
17. Wiring diagrams
7.1 Indoor unit
FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA / FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA
3D096
206
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
44/156
Wiring diagrams EDMT281536
42 SkyAir FHQ-DA + RZQS, RZQ series
7.2 Outdoor unit
RZQS50AV1 / RZQS60AV1
3D089620
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
45/156
EDMT281536 Wiring diagrams
SkyAir FHQ-DA + RZQS, RZQ series 43
1RZQ71LV1
3D064851L
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
46/156
Wiring diagrams EDMT281536
44 SkyAir FHQ-DA + RZQS, RZQ series
RZQ100LV1
3D089520
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
47/156
EDMT281536 Wiring diagrams
SkyAir FHQ-DA + RZQS, RZQ series 45
1RZQ125LV1
3D056474K
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
48/156
Wiring diagrams EDMT281536
46 SkyAir FHQ-DA + RZQS, RZQ series
RZQ140LV1
3D077448D
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
49/156
EDMT281536 Wiring diagrams
SkyAir FHQ-DA + RZQS, RZQ series 47
1RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A
C:3D047451H
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
50/156
Field wiring EDMT281536
48 SkyAir FHQ-DA + RZQS, RZQ series
8. Field wiring
FHQ50DAVMA + RZQS50AV1
FHQ60DAVMA + RZQS60AV1
FHQ71DAVMA + RZQ71LV1
FHQ100DAVMA + RZQ100LV1 / RZQ100HAY4A
FHQ125DAVMA + RZQ125LV1 / RZQ125HAY4A
FHQ140DAVMA + RZQ140LV1 / RZQ140HAY4A
4D044483M
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
51/156
EDMT281536 Electric characteristics
SkyAir FHQ-DA + RZQS, RZQ series 49
19. Electric characteristics
9.1 FHQ-DA + RZQS
FHQ50DAVMA + RZQS50AV1
FHQ60DAVMA + RZQS60AV1
4D096569A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
52/156
Electric characteristics EDMT281536
50 SkyAir FHQ-DA + RZQS, RZQ series
9.2 FHQ-DA + RZQ-LV1
FHQ71DAVMA + RZQ71LV1
FHQ100DAVMA + RZQ100LV1
FHQ125DAVMA + RZQ125LV1
FHQ140DAVMA + RZQ140LV1
4D096559A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
53/156
EDMT281536 Electric characteristics
SkyAir FHQ-DA + RZQS, RZQ series 51
19.3 FHQ-DA + RZQ-HAY4A
FHQ100DAVMA + RZQ100HAY4A
FHQ125DAVMA + RZQ125HAY4A
FHQ140DAVMA + RZQ140HAY4A
4D096646
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
54/156
Capacity tables EDMT281536
52 SkyAir FHQ-DA + RZQS, RZQ series
10.Capacity tables
10.1 RZQS
FHQ50DAVMA + RZQS50AV1
3D0897
37D
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
55/156
EDMT281536 Capacity tables
SkyAir FHQ-DA + RZQS, RZQ series 53
1FHQ60DAVMA + RZQS60AV1
3D089738C
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
56/156
Capacity tables EDMT281536
54 SkyAir FHQ-DA + RZQS, RZQ series
10.2 RZQ-LV1
FHQ71DAVMA + RZQ71LV1
3D089698C
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
57/156
EDMT281536 Capacity tables
SkyAir FHQ-DA + RZQS, RZQ series 55
1FHQ100DAVMA + RZQ100LV1
3D089699E
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
58/156
Capacity tables EDMT281536
56 SkyAir FHQ-DA + RZQS, RZQ series
FHQ125DAVMA + RZQ125LV1
3D089701A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
59/156
EDMT281536 Capacity tables
SkyAir FHQ-DA + RZQS, RZQ series 57
1FHQ140DAVMA + RZQ140LV1
3D096968
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
60/156
Capacity tables EDMT281536
58 SkyAir FHQ-DA + RZQS, RZQ series
10.3 RZQ-HAY4A
FHQ100DAVMA + RZQ100HAY4A
3D093044A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
61/156
EDMT281536 Capacity tables
SkyAir FHQ-DA + RZQS, RZQ series 59
1FHQ125DAVMA + RZQ125HAY4A
3D093045A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
62/156
Capacity tables EDMT281536
60 SkyAir FHQ-DA + RZQS, RZQ series
FHQ140DAVMA + RZQ140HAY4A
3D073995C
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
63/156
EDMT281536 Capacity tables
SkyAir FHQ-DA + RZQS, RZQ series 61
110.4 Capacity correction factor by the length of refrigerant piping
RZQS50AV1 / RZQS60AV1
RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1
RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A
3D089679
The capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)
RZQ100-140: Heating (96.7%)
Length of refrigerant piping (Total length)
Capacitycorrectionfactor
RZQ71: Heating (97.9%)7.5
RZQ71: Cooling (95%)
RZQ100: Cooling (84.2%)
RZQ125: Cooling (75.2%)
RZQ140: Cooling (70.0%)
Notes: 1. line: Correction factor for Cooling Capacity, line: Correction factor for Heating Capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below
the indoor unit.3. You cannot extend the refrigerant piping exceeding the limit shown in the above table.
100
95
90
85
80
75
70
(%)
05 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 (m)
RZQ50/60: Heating (98.8%)
RZQ50/60: Cooling (97.2%)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
64/156
Operation limits EDMT281536
62 SkyAir FHQ-DA + RZQS, RZQ series
11.Operation limits
RZQS50AV1 / RZQS60AV1
RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1
RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A
3D046720M
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
65/156
EDMT281536 Sound level
SkyAir FHQ-DA + RZQS, RZQ series 63
112.Sound level
12.1 Indoor unit
12.1.1 FHQ-DA
FHQ50DAVMA / FHQ60DAVMA
FHQ71DAVMA
4D079992A
4D069649C
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
66/156
Sound level EDMT281536
64 SkyAir FHQ-DA + RZQS, RZQ series
FHQ100DAVMA
FHQ125DAVMA
4D069652D
4D069650E
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
67/156
EDMT281536 Sound level
SkyAir FHQ-DA + RZQS, RZQ series 65
1FHQ140DAVMA
4D069651E
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
68/156
Sound level EDMT281536
66 SkyAir FHQ-DA + RZQS, RZQ series
12.2 Outdoor unit
12.2.1 RZQS
RZQS50AV1 / RZQS60AV1 (Cooling)
RZQS50AV1 / RZQS60AV1 (Heating)
4D090424
4D090423
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
69/156
EDMT281536 Sound level
SkyAir FHQ-DA + RZQS, RZQ series 67
112.2.2 RZQ-L
RZQ71LV1 (Cooling)
RZQ71LV1 (Heating)
4D075745A
4D075748A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
70/156
Sound level EDMT281536
68 SkyAir FHQ-DA + RZQS, RZQ series
RZQ100LV1 (Cooling)
RZQ100LV1 (Heating)
4D089676
4D089677A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
71/156
EDMT281536 Sound level
SkyAir FHQ-DA + RZQS, RZQ series 69
1RZQ125LV1 (Cooling)
RZQ125LV1 (Heating)
4D075741A
4D075747A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
72/156
Sound level EDMT281536
70 SkyAir FHQ-DA + RZQS, RZQ series
RZQ140LV1 (Cooling)
RZQ140LV1 (Heating)
4D089680A
4D089681A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
73/156
EDMT281536 Sound level
SkyAir FHQ-DA + RZQS, RZQ series 71
112.2.3 RZQ-HA
RZQ100HAY4A (Cooling)
RZQ100HAY4A (Heating)
4D061464A
4D061483A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
74/156
Sound level EDMT281536
72 SkyAir FHQ-DA + RZQS, RZQ series
RZQ125HAY4A (Cooling)
RZQ125HAY4A (Heating)
4D061473A
4D061484A
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
75/156
EDMT281536 Sound level
SkyAir FHQ-DA + RZQS, RZQ series 73
1RZQ140HAY4A (Cooling)
RZQ140HAY4A (Heating)
4D061482B
4D061485B
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
76/156
Accessories EDMT281536
74 SkyAir FHQ-DA + RZQS, RZQ series
13.Accessories
13.1 Indoor unit
13.1.1 FHQ-DA
Optional
accessories
C: 3D096220D
Notes: 1. Wiring for wired remote controller to be procured locally.2. The interface adaptor for SkyAir series is not necessary because it is equipped to this indoor unit as standard.3. Installation box for adaptor PCB (KRP1D93A) is necessary.
Item
Model
FHQ50DAVMAFHQ60DAVMA
FHQ71DAVMAFHQ100DAVMAFHQ125DAVMAFHQ140DAVMA
Replacement long-life filter KAFP501A56 KAFP501A80 KAFP501A160
Fresh air intake kit KDDQ50A140
Drain pump kit KDU50P140VE
L-type piping kit (for upward direction) KHFP5N160
Remote controller
Wired type (Note 1) BRC1E62 / BRC1C61 / BRC1D61
Wirelesstype
HeatPump
BRC7GA53
Simplified remote controller(With operation mode selection button)
Simplified remote controller(Without operation mode selection button)
Central remote controller DCS302CA61
Unified ON/OFF controller DCS301BA61
Schedule timer DST301BA61
intelligent Touch Controller (Note 2) DCS601C51
Wiring adaptor for electrical appendices KRP1BA54
Wiring adaptor for electrical appendices (Note 3) KRP4AA52
Wiring adaptor for electrical appendices (Note 3)
External adaptor for outdoor unit(installation on indoor unit)
Installation box for adaptor printed circuit board KRP1D93A
Adaptor box mounting plate KKSAP50A56
Remote sensor KRCS01-4BRemote ON/OFF (Connector for forced on, forced off)
Noise filter (for electromagnetic use only)
Electrical box with earth terminal (3 blocks) KJB311AA
Electrical box with earth terminal (2 blocks) KJB212AA
Digital input adaptor (Note 3)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
77/156
EDMT281536 Accessories
SkyAir FHQ-DA + RZQS, RZQ series 75
113.2 Outdoor unit
13.2.1 RZQS
C: 4D046721M
13.2.2 RZQ-L / HA
Optional
accessories
C: 4D046721M
C: 4D077521E
Name of option
Kit name
RZQS50AV1RZQS60AV1
Central drain plug KKPJ5F180Wire fixture for preventingoverturning
K-KYZP15C
Fixture for preventingoverturning
KPT-60B160
Demand adaptor KRP58M51
Name of option
Kit name
RZQ71LV1
RZQ125LV1
RZQ100LV1
RZQ140LV1
RZQ100HAY4ARZQ125HAY4A
RZQ140HAY4ACentral drain plug KKPJ5F180 KKPJ5G280 KKPJ5F180
Wire fixture for preventing overturning K-KYZP15C
Fixture for preventing overturning KPT-60B160 KKTP5B112 KPT-60B160
Demand adaptor KRP58M51
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
78/156
Accessories EDMT281536
76 SkyAir FHQ-DA + RZQS, RZQ series
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
79/156
EDMT281536
Installation of indoor / outdoor unit 77
2
Part 2
Installation of
indoor outdoor unit
1. Centre of gravity....................................................................................78
2. Installation of indoor unit .......................................................................812.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA /
FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA..........................81
3. Installation of outdoor unit ...................................................................1013.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /
RZQ125LV1 .........................................................................................101
3.2 RZQ140LV1 .........................................................................................117
3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................133
3.4 Equivalent piping length of joints (reference) .......................................149
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
80/156
Centre of gravity EDMT281536
78 Installation of indoor / outdoor unit
1. Centre of gravity
RZQS50AV1 / RZQS60AV1 / RZQ71LV1
RZQ100LV1
4D064948F
Unit (mm)
4D089656B
Unit (mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
81/156
EDMT281536 Centre of gravity
Installation of indoor / outdoor unit 79
2
RZQ125LV1
RZQ140LV1
4D058487H
Unit (mm)
4D077529C
Unit (mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
82/156
Centre of gravity EDMT281536
80 Installation of indoor / outdoor unit
RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A
4D061670B
Unit (mm)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
83/156
EDMT281536 Installation of indoor unit
Installation of indoor / outdoor unit 81
2
2. Installation of indoor unit
2.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA / FHQ100DAVMA /
FHQ125DAVMA / FHQ140DAVMA
2.1.1 Names and Functions of Parts
C: 3P400449-1E
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
84/156
Installation of indoor unit EDMT281536
82 Installation of indoor / outdoor unit
2.1.2 Installation
3P400451-1E
1
SPLIT SYSTEM Air Conditioners Installation manual
CONTENTS
1. SAFETY PRECAUTIONS ................................................1
2. BEFORE INSTALLATION.................................................2
3. SELECTION OF INSTALLATION LOCATION..................4
4. PREPARATION BEFORE INSTALLATION.......................4
5. INSTALLATION OF THE INDOOR UNIT .........................6
6. REFRIGERANT PIPING WORK......................................6
7. DRAIN PIPING WORK.....................................................9
8. ELECTRIC WIRING WORK...........................................11
9. HOW TO CONNECT WIRINGS AND
WIRING EXAMPLE........................................................11
10. MOUNTING SUCTION GRILLE
DECORATION SIDE PANEL..........................................15
11. FIELD SETTING ............................................................15
12. TEST OPERATION ........................................................16
After the installation is completed, test the air conditioner andcheck if the air conditioner operates properly. Give the user
adequate instructions concerning the use and cleaning of the
indoor unit according to the Operation Manual. Ask the user
to keep this manual and the Operation Manual together in a
handy place for future reference.
WARNING
Ask your local dealer or qualied personnel to carry out
installation work.
Improper installation may result in water leakage, electric
shocks or a re.
Perform installation work in accordance with this installation
manual.
Improper installation may result in water leakage, electric
shocks or a re.Consult your dealer regarding what to do in case of
refrigerant leakage.
When the air conditioner is installed in a small room, it is
necessary to take proper measures so that the amount of any
leaked refrigerant does not exceed the concentration limit in
the event of a leakage.
Otherwise, this may lead to an accident due to oxygen deciency.
Be sure to use only the specied parts and accessories for
installation work.
Failure to use the specied parts may result in the air conditioner
falling down, water leakage, electric shocks, are, etc.
Install the air conditioner on a foundation that can withstand
its mass.
Insufcient strength may result in the air conditioner falling
down and causing injury.In addition, it may lead to vibration of indoor units and cause
unpleasant chattering noise.
Carry out the specied installation work in consideration of
strong winds, typhoons, or earthquakes.
Improper installation may result in an accident such as air
conditioner falling.
Make certain that all electrical work is carried out by qualied
personnel according to the applicable legislation (note 1) and
this installation manual, using a separate circuit.
In addition, even if the wiring is short, make sure to use a wiring
that has sufcient length and never connect additional
wiring to make the length sufcient.
Insufcient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or a re.(note 1) applicable legislation means All international,
national and local directives, laws, regulations and/
or codes which are relevant and applicable for a
certain product or domain.
Earth the air conditioner.
Do not connect the earth wiring to gas or water piping,
lightning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a re.
Be sure to install an ear th leakage breaker.
Failure to do so may cause electric shocks and a re.
Disconnect the power supply before touching the electric
components.
If you touch the live part, you may get an electric shocks.
FHQ50DAVMAFHQ60DAVMAFHQ71DAVMA
FHQ125DAVMAFHQ100DAVMA
FHQ140DAVMA
1. SAFETY PRECAUTIONS
This manual classies the precautions into WARNINGS and
CAUTIONS.
Be sure to follow all the precautions below: They are allimportant for ensuring safety.
WARNING............... Indicates a potentially hazardous
situation which, if not avoided,
could result in death or serious
injury.
CAUTION.................Indicates a potentially hazardous
situation which, if not avoided,
may result in minor or moderate
injury.
It may also be used to alert
against unsafe practices.
Please read the these "SAFETY CONSIDERATIONS"carefully before installing air conditioning unit and be sure to
install it correctly. After completing the installation, make surethat the unit operates properly during the start-up operation.
Please instruct the customer on how to operate the unit andkeep it maintained.
Also, inform customers that they should store this installationmanual along with the operation manual for future reference.
This air conditioner comes under the term "appliances notaccessible to the general public".
In a domestic environment this product may cause radiointerference in which case the user may be required totake adequate measures.
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
85/156
EDMT281536 Installation of indoor unit
Installation of indoor / outdoor unit 83
2
3P400451-1E
2
CAUTION
Install drain piping according to this installation manual to
ensure good drainage, and insulate the piping to prevent
condensation.
Improper drain piping may cause water leakage, make the
furniture get wet.
Install the air conditioner, power supply wiring, remote
controller wiring and transmission wiring at least 1 meter away
from televisions or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufcient to eliminate the noise.)
Install the indoor unit as far as possible from orescentlamps.
If a wireless remote controller kit is installed, the transmission
distance may be shorter in a room where an electronic
lighting type (inverter or rapid start type) uorescent lamp is
installed.
Do not install the air conditioner in places such as the
following:
1. Where there is mist of oil, oil spray or vapour for example
a kitchen.
Resin parts may deteriorate, and cause them to fall out or
water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is
produced.
Corrosion of copper pipings or brazed parts may cause
the refrigerant to leak.
3. Where there is machinery which emits electromagnetic
waves.
Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
4. Where ammable gases may leak, where carbon bre or
ignitable dust is suspended in the air or where volatileammables, such as thinner or gasoline, are handled.
If the gas should leak and remained around the air
conditioner, it may cause ignition.
The air conditioner is not intended for use in a potentially
explosive atomosphere.
2. BEFORE INSTALLATION
SPECIAL NOTICE PRODUCT
When unpacking and moving the indoor unit after
unpacked, do not apply force to the piping (refrigerant and
drain) and resin parts.
Make sure to check in advance that the refrigerant to be used
for installation work is R410A.
(The air conditioner will not properly operate if a wrong
refrigerant is used.)
For installation of the outdoor unit, refer to the installation
manual attached to the outdoor unit.
Do not throw away the accessories until the installation work
is completed.
After the indoor unit is carried into the room, to avoid the
indoor unit from getting damaged, take measures to protectthe indoor unit with packing materials.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the installation
location.
Where unpacking is unavoidable, use a sling of soft
material or protective plates together with a rope when
lifting, to avoid damage or scratches to the indoor units.
Have the customer actually operate the air conditioner while
looking at the manual.
Instruct the customer how to operate the air conditioner
(particularly cleaning of the air lters, operation procedures,
and temperature adjustment).
Make sure that all wiring is secure, using the specied wiringsand ensuring that external forces do not act on the terminal
connections or wirings.
Incomplete connection or xing may cause an overheat or a re.
When wiring between the indoor and outdoor units, and wiring
the power supply, form the wirings orderly so that the controlbox lid can be securely fastened.
If the control box lid is not in place, overheat of the terminals,
electric shocks or a re may be caused.
If refrigerant gas leaks during installation work, ventilate the
area immediately.
Toxic gas may be produced if refrigerant gas comes into
contact with a re.
After completing the installation work, check to make sure
that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the
room and comes into contact with a source of a re, such as
a fan heater, stove or cooker.
Never directly touch any accidental leaking refrigerant. This
could result in severe wounds caused by frostbite.
Be sure to switch off the unit before touching any electrical parts.
Do not allow children to climb on the outdoor unit and avoidplacing objects on the unit.Injury may result if the unit becomes loose and falls.
Make sure to provide for adequate measures in order to preventthat the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause keep the area around the unit clean.
Install in a machine room that is free of moisture. The unit isdesigned for indoor use.
Disposal requirementsDismantling of the unit, treatment of the refrigerant, of oil and ofother parts must be done in accordance with relevant local andnational legislation.
The refrigerant R410A requires that strict precautions beobserved for keeping the system clean, dry and tightly sealed.
Clean and dryStrict measures must be taken to keep impurities(including SUNISO oil and other mineral oils as well asmoisture) out of the system.
Tightly sealedR410A contains no chlorine, does not destroy the ozonelayer and so does not reduce the earth's protection against
harmful ultraviolet radiation. R410A will contribute only slightly
to the greenhouse effect if released into the atmosphere.
than previously. Since R410A is a mixed refrigerant, the
required additional refrigerant must be charged in its liquid state.(If the system is charged with refrigerant in its gaseous state,due to composition change, the system will not functionnormally). The indoor unit is designed for R410A use.See the catalogue for indoor unit models that can be
connected. (Normal operation is not possible when connectingunits that are originally designed for other refrigerants.)
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
86/156
Installation of indoor unit EDMT281536
84 Installation of indoor / outdoor unit
3P400451-1E
3
CARRY OUT THE WORK GIVING CAUTION TO THE
FOLLOWING ITEMS AND AFTER THE WORK IS
COMPLETED CHECK THESE AGAIN.
1. Items to be checked after the installation work is com-
pleted
*Make sure to recheck the items of SAFETY PRECAUTIONS
2. Items to be checked at delivery
Items to be checked In case of defectiveCheck
column
Are the indoor and outdoor
units rigidly xed?
Drop vibration
noise
Are the installation work of the
outdoor and indoor units complete?
Does not operate
burnout
Have you carried out a leakage
test with the test pressure
specied in the outdoor unit
installation manual?
Does not cool /
Does not heat
Is the insulation of refrigerant
piping and drain piping
completely carried out?
Water leakage
Does the dr ow out
smoothly?Water leakage
Is the power supply voltage
identical to that stated in the
manufacturers label on the air
conditioner?
Does not operate
burnout
Are you sure that there is no
wrong wiring or piping or no
loose wiring?
Does not operate
burnout
Is earthing completed?Danger in case of
leakage
Are the sizes of electric wiring
according to the specication?
Does not operate
burnout
Is any of air outlets or inlets of
the indoor and outdoor units
blocked with obstacles?
(It may lead to capacity drop
due to fan speed drop or
malfunction of equipment.)
Does not cool /
Does not heat
Have you recorded the
refrigerant piping length and the
refrigerant charge added?
Refrigerant charge
amount is not clear
Items to be checkedCheck
column
Have you carried out eld setting? (if necessary)
Are the control box lid, the air lter and the suction grille
attached?
Does the cool air discharge during the cooling operation and
the warm air discharge during heating operation?Have you explained how to operate the air conditioner
showing the operation manual to the customer?
Have you explained the description of cooling, heating,
program dry and automatic (cooling/heating) given in
the operation manual to the customer?
If you set the fan speed at thermostat OFF, did you
explain the set fan speed to the customer?
Have you handed the operation manual and the
installation manual to the customer?
For selection of installation location, use the installationpattern paper (used in common with the packing case.)as reference.
Do not use the air conditioner where in the salty atmosphere
such as coastal areas, vehicles, vessels or the voltage
tuation is frequent such as factories.
Take off static electricity from the body when carrying out
wiring and the control box lid is removed.
The electric parts may be damaged.
2-1 ACCESSORIES
Check if the following accessories are attached to the
indoor unit.
2-2 OPTIONAL ACCESSORIES
For this indoor unit, the remote controller is separately
required. There are 2 kinds of remote controller; wired type and
wireless type.
Install the remote controller to the place where the customer
has given consent.
Refer to the catalog for the applicable model.
(Refer to the installation manual attached to the remote
controller for how to install.)
Name(1) Drain
hose
(2) Metal
clamp
(3) Washer
for hanger(4) Clamp
Quantity 1 pc. 1 pc. 8 pcs. 7 pcs.
Shape
Name(5) Installation
pattern paper
Joint insulating
material
Sealing
material
(10) Resin
bushing
Quantity 1 sheet 1 each 1 each 1 pc.
Shape
(6) For gas
piping
(7) For liquid
piping
(8) Large
(9) Small
Name(11) Wiring
xture
(12) Screw
for wiring
xture (Miscellaneous)
Operation manual
Installation manual
Declaration of conformity
Quantity 2 pcs. 2 pcs.
Shape
M4 12
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
87/156
EDMT281536 Installation of indoor unit
Installation of indoor / outdoor unit 85
2
3P400451-1E
4
CAUTION
Install the indoor and outdoor units, power supply wiring,
remote controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image
interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufcient to eliminate the noise.)
Install the indoor unit as far as possible from orescent
lamps.
If a wireless remote controller kit is installed, the transmissiondistance may be shorter in a room where an electronic lighting
type (inverter or rapid start type) uorescent lamp is installed.
(2) Use hanging bolts for installation.
Investigate if the installation place can withstand the mass
of the indoor unit and, if necessary, hang the indoor unit
with bolts after it is reinforced by beams etc. (Refer to the
installation pattern paper (5) for the mounting pitch.).
(3) Ceiling height
This indoor unit can be installed up to 4.3m (for 50-71model, 3.5m) of the ceiling.
4. PREPARATION BEFORE INSTALLATION
(1) For the locations of indoor unit hanging bolts, piping
outlet holes, drain piping outlet hole, and electric
wiring inlet hole. (Refer to Fig. 3)
Model name (FHQ-) A B C D E F G H J
Type 50 60 960 920 378 324 270 375 398 377 260
Type 71 1270 1230 533 479 425 530 553 532 415
Type 100 125 140 1590 1550 693 639 585 690 713 692 575
G H
J 5 175
200
View from the front
Left back drainpiping outlet hole Wall hole for back sidepiping outlet
(100 hole)
Back side wiringoutlet location
Fig. 3
F
690U
nitdimension
210
D
A Unit dimension
B Hanging bolt pitch
View from
the ceiling260
30
163
E 189
87
C
Discharge
Unit : mm
Top panel drain piping
connection position
Top panel gas sidepiping connection
position
Top panel liquid side pipingconnection positions
Top panel wiring outlet position
Hanging bolt (4 pieces)
Han
gingboltpitch
Points of the operation explanation
3. SELECTION OF INSTALLATIONLOCATION
When unpacking and moving the indoor unit after
unpacked, do not apply force to the piping (refrigerant and
drain) and resin parts.
(1) Select the installation location that meets the following
conditions and get approval of the customer. Where the cool and warm air spreads evenly in the room.
Where there is no obstacles in the air passage.
Where drainage can be ensured.
Where the ceiling lower surface is not inclined.
Where there is sufcient strength to withstand the mass
of the indoor unit (if the strength is insufcient, the indoor
unit may vibrate and get in contact with the ceiling and
generate unpleasant chattering noise).
Where a space sufcient for installation and service can
be ensured.(Refer to Fig. 1 and Fig. 2)
Where the piping length between the indoor and the
outdoor units is ensured within the allowable length. (Refer
to the installation manual attached to the outdoor unit.)
Where there is no risk of ammable gas leak.
NOTENOTENOTENOTE
If there is extra space required for * part, servicing can be
conducted more easily if 200mm or more is secured.
In addition to the general usage, since the items in the
operation manual with the WARNING and CAUTION
marks are likely to result in human bodily injuries and
property damages, it is necessary not only to explain
these items to the customer but also to have the
customer read them.
It is also necessary to explain the items of NOT
MALFUNCTION OF THE AIR CONDITIONER to the
customer and have the customer read them carefully.
Fig. 1
[ Required installation space (mm) ]
eromro03*eromro03*
Fig. 2
Discharge
Obstacles
2500 or more evel
For highinstallation
Floor level
300ormore
Suction
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
88/156
Installation of indoor unit EDMT281536
86 Installation of indoor / outdoor unit
3P400451-1E
5
3) Remove the hanger.
Loosen 2 bolts for installing the hanger at both sides
(M8) (4 places at left and right) within 10mm.
(Refer to Fig. 7 and Fig. 8)
Remove the xture screw for hanger at the back side
(M5), pull the hanger backward (the arrow direction) toremove. (Refer to Fig. 8)
CAUTION
Do not remove the tape (milky white) applied to the outside
of the indoor unit. It may cause electric shocks or a re.
(4) Install the hanging bolts.
Use M8 or M10 bolts for hanging the indoor unit.
Adjust the length of the hanging bolt from the ceiling in
advance. (Refer to Fig. 9) Use hole-in-anchors for the existing bolts and embedded
inserts or foundation bolts for new bolts, and x the unit
rmly to the building so that it may withstand the mass of
the unit.
In addition, adjust the distance from the ceiling in
advance.
CAUTION
If the hanging bolt is too long, it may damage or break the
indoor unit or options.
NOTE
Parts shown Fig. 9will be all eld supply.
Fig. 7
Bolt (M8)
Indoor unit
Hanger
Loosen within10mm
Fig. 8
screw (M5)
Hanger installing bolt (M8)
HangerLoosen
Fig. 9 Ceiling surface
Hanging bolt
Foundation bolt
Ceiling slab
25-55m
m
(2) Make holes for hanging bolts, piping outlet, drain
piping outlet, and electric wiring inlet.
Use the installation pattern paper (5).
Determine the locations of hanging bol ts, piping outlet,
drain piping outlet and electric wiring inlet. And make the
hole.(3) Remove the parts of the indoor unit.
1) Remove the suction grille.
Slide the suction grille xing knobs (50, 60 type: 2
places for each, 71~140 type: 3 places for each) toward
backward direction (as shown by an arrow) to open the
suction grille widely. (Refer to Fig. 4)
Keeping the suction grille opened, hold the knob at the
back of the suction grille and at the same time, pull the
suction grille forward to remove. (Refer to Fig. 5)
2) Remove the decoration side panel (right, left).
Remove the xture screw of the decoration side panel(one for each), pull forward (arrow direction) to remove.
(Refer to Fig. 6)
Take out accessories. (Refer to Fig. 6)
Open the knock hole at the wiring inlet side at the rear
surface or top surface, and install the attached resin
bushing (10).
Fig. 4
Fig. 5
Fixing knobSuction grille
Rear knob
Resin bushing (10)
(accessory)
Removable part(for leading in from the upward-facing)
Resin bushing (10)
(accessory)
Removable part
(for leading in from the rear-facing)
Fig. 6
Fixing screw for decoration side Panel
(M4)
Decoration side panel
Accessories
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
89/156
EDMT281536 Installation of indoor unit
Installation of indoor / outdoor unit 87
2
3P400451-1E
6
A. When the drain piping is tilted to the right, or to the right
and back.
Place it level, or tilt it slightly to the right or the back.(Within 1)
B. When the drain piping is tilted to the left, or to the leftand back.
Place it level, or tilt it slightly to the left or the back.(Within 1)
WARNING
The indoor unit must be securely installed on a place
that can withstand the mass.
If the strength is insufcient, the indoor unit may fall down
and cause injuries.
6. REFRIGERANT PIPING WORK
For the outdoor unit refrigerant piping, refer to the installation
manual attached to the outdoor unit.
Carry out insulation of both gas and liquid refrigerant piping
securely. If not insulated, it may cause water leakage. For
gas piping, use insulation material of which heat resistant
temperature is not less than 120C. For use under high
humidity, strengthen the insulation material for refrigerant
piping. If not strengthened, the surface of insulation material
may sweat.
Before installation work, make sure that the refrigerant is
R410A. (Unless the refrigerant is R410A, the normal
operation cannot be expected.)
CAUTION
This air conditioner is a dedicated model for new refrigerant
R410A. Make sure to meet the requirements shown right
and carry out installation work.
Use dedicated piping cutters and aring tools for R410A.
When making a are connection, coat the d inner
surface only with ether oil or ester oil.
Use only the are nuts attached to the air conditioner. If
other nuts are used, it may cause refrigerant leakage.
To prevent contamination or moisture from getting into the
piping, take measures such as pinching or taping the
pipings.
Do not mix substance other than the specied refrigerant
such as air into the refrigeration circuit.
If the refrigerant leaks during the work, ventilate the room.
A
A.B
B
Fig. 12
5. INSTALLATION OF THE INDOOR UNIT
It is easy to attach the optional parts before installing the
indoor unit. Refer to also the installation manual attached
to the optional parts.
For installation, use the attached installation parts and
parts.
(1) Fix the hanger to the hanging bolt. (Refer to Fig. 10)
CAUTION
For safety, make sure to use a washer for hanger (3)
(accessory) and x by double nuts rmly.
(2) Lift up the indoor unit, slide from the front and put the
hanger installing bolt (M8) into the securely for temporary
hanging.(Refer to Fig. 11)
(3) Tighten the hanger xing screws (M5) at 2 places, which
were removed, as they were before.
(Refer to Fig. 11)
It is necessary to prevent misalignment of the indoor unit.
(4) Tighten the hanger installing bolts (M8) at 4 places
securely.(Refer to Fig. 11)
(5) When hanging the indoor unit, make sure to use the level to
have better drainage and install it horizontally. Also, if it is
possible at the installation site, install so that the drain
piping side is slightly lower.(Refer to Fig. 12)
CAUTION
Setting the indoor unit at an angle opposite to the drain
piping might cause a water leakage.
Do not insert materials other than that into
the clearance between the hanger and the washer for
hanger (3).
Unless the washers are properly attached, the hanging
bolts may come off from the hanger.
Hanger
Hanging bolt
Washer for hanger (3) (accessory)
Double nuts
Fig. 10
Hanger
ew
(M5)
Attachment partHanger
Reinforcing plate (left/right)
When carrying the indoor unit,
do not hold the reinforcing plates.
Hanger installing
bolt (M8)
Fig. 11
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
90/156
Installation of indoor unit EDMT281536
88 Installation of indoor / outdoor unit
3P400451-1E
7
CAUTION
Insulation of eld piping must be carried out up to the
connection inside the casing. If the piping is exposed to the
atmosphere, it may cause sweating or burn due to touching
the piping, electric shocks or a re due to the wiring touchingthe piping.
After leak test, referring to Fig. 15, insulate both the gas and
liquid piping connection with the attached joint insulating
material (6) and (7) to prevent the piping from getting
exposed. Then, tighten the both ends of insulating material
with the clamp (4).
Wrap the sealing material (Small) (9) around the joint insulating
material (6) nut section), only the gas piping side.
Make sure to bring the seam of joint insulating material (6)
and (7) to the top.
Remove the stay for packing and delivering (reinforcing
plate) before refrigerant piping work.
(Refer to Fig. 18)
The refrigerant is pre-charged in the outdoor unit.
When connecting the pipings to the air conditioner, make sure
to use a spanner and a torque wrench as shown in Fig.13.For the dimension of ared part, refer to the Table 1.
When making a are connection, coat the ared inner surface
only with ether oil or ester oil. (Refer to Fig. 14)Then, turn theare nut 3 to 4 times with your hand and screw in the nut.
For the tightening torque, refer to the Table 1.
Table 1
CAUTION
Do not have oil adhere to the screw ng part of resin
parts.
If oil adheres, it may weaken the strength of screwed part.
Do not tighten e nuts too tight.
If a nut cracks, the refrigerant may leak.
If there is no torque wrench, use Table 2 as a rule of thumb.
When tightening a nut with a spanner harder andharder, there is a point where the tightening torque suddenly
increases. From that position, tighten the nut additionally the
angle shown in Table 2. After the work is nished, check
securely that there is no gas leak. If the nut is not tightened
as instructed, it may cause slow refrigerant leak and result in
malfunction (such as does not cool or heat).
Table 2
Piping size
(mm)
Tightening
torque (Nm)
Dimension
for processing
e A (mm)
Flare shape
6.4 15.7 1.5 8.9 0.2
9.5 36.3 3.6 13.0 0.2
12.7 54.9 5.4 16.4 0.2
15.9 68.6 6.8 19.5 0.2
Piping size
(mm)Tightening angle
Recommended arm length
of tool used
6.4 60 90 Approximately 150mm
9.5 60 90 Approximately 200mm
12.7 30 60 Approximately 250mm
15.9 30 60 Approximately 300mm
Torque wrench
Spanner
Flare nut
Union joint Fig. 13
face
only with ether oil or ester oil.
Fig. 14
R0.4-0.8
902
A
45
2
-
7/26/2019 Edmt281536 Fhq Davma,Rzqs, Rzq Series
91/156
EDMT281536 Installation of indoor unit
Installation of indoor / outdoor unit 89
2
3P400451-1E
8
(1) For rear side piping
Remove the rear piping penetration cover, and connect
the piping. (Refer to Fig. 16 and Fig. 18)
(2) For upward piping
For upward piping, L-shaped connection piping kit
(optional accessory) will be required. Remove the top panel penetration cover, and use the L-
shaped connection piping kit (optional accessory) to con-
duct piping. (Refer to Fig. 16 and Fig. 17)
(3) For right side piping
Remove the stay for packing and delivering (reinforcing
plate) at the right side, and put back the screw to the orig-
inal position of the indoor unit. (Refer to Fig. 18)
Open the knockout hole at the decoration side panel
(right), and connect piping. (Refer to Fig. 18)
Top panel penetration cover
Cut at the position avoidingthe knob part of the
penetration cover
Rear piping penetration cover
View fromair inlet side
Cutoff
Cutoff
Top panel
Fig. 16
Upward refrigerant piping
L-shaped branch piping kit(Optional accessory)
Fig. 17
Screw(put back to the indoor unit)
Decoration side panel (right)Separating parts
Cut only this part when laying onlythe drain piping on the right side.
Stay for packing and delivering(reinforcing plate)
Right side refrigerant piping
Rear side drain piping
Rear side refrigerant piping
Right side drain piping
Fig. 18
Joint insulating material (6) (accessory)
Gas side piping insulating method
Piping insulating material (unit side)Do not leaveclearance
Wrap from theroot of the unit
Sealing material (Small) (9)(accessory)
Bring the seamto the top
Flare nutconnection
Piping insulating material
For prevention of sweating,do not expose the piping
Clamp (4) (accessory) Tighten the pipinginsulating material
Liquid side piping insulating method
Joint insulating material (7)(accessory)
Flare nutconnection
Piping insulatingmater
For prevention of sweating,do not expose the piping
Fig. 15
Gas piping
Liquid piping
Indoor unit
Bring the seamto the top
Piping insulating material(unit side)
Do not leave clearance
Clamp (4)(access