ee018-earthing and earth electrode resistance-th-inst.pdf

Upload: sameera

Post on 28-Feb-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    1/29

    SRI LANKA INSTITUTE of ADVANCED TECHNOLOGICAL EDUCATION

    Training Unit

    Earthing and EarthElectrode Resistance

    Theory

    No: EE 018

    INDUSTRIETECHNIKINDUSTRIETECHNIK

    ELECTRICAL and ELECTRONIC

    ENGINEERING

    Instructor Manual

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    2/29

    1

    Training Unit

    Earthing and Earth Electrode Resistance

    Theoretical Part

    No.: EE 018

    Edition: 2008Al l Rights Reserved

    Editor: MCE Industrietechnik Linz GmbH & CoEducation and Training Systems, DM-1Lunzerst rasse 64 P.O.Box 36, A 4031 Linz / Aus triaTel. (+ 43 / 732) 6987 3475Fax (+ 43 / 732) 6980 4271Website: www.mcelinz.com

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    3/29

    2

    EARTHING AND EARTH ELECTRODE RESISTANCE

    CONTENTS Page

    LEARNING OBJECTIVES...................................................................................................3

    1 EARTHING (GROUNDING) AND EARTH ELECTRODE RESISTANCE *..................4

    1.1 Earth electrode resistance ...................................................................................4

    1.1.1

    Measuring the earth electrode resistance........................................................5

    1.2

    Measuring the earthing resistance with an earth measuring bridge.....................7

    1.2.1 The functions of the earth measuring bridge....................................................7

    1.3 Earthing practice ..................................................................................................8

    2

    INSULATION RESISTANCE........................................................................................9

    2.1 Measuring the insulation resistance...................................................................11

    2.1.1

    General ..........................................................................................................11

    2.1.2 Regulations for measuring Rinsin installations with a voltage up to 1000 Volts .

    .......................................................................................................................11

    2.1.3 Measuring the insulation resistance in an installation out of Operation with a

    portable measuring instrument...................................................................................12

    2.1.4 Monitoring the insulation resistance in a live installation................................17

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    4/29

    3

    EARTHING AND EARTH ELECTRODE RESISTANCE

    LEARNING OBJECTIVES

    The student should

    explain the meaning of earth electrode (grounding) resistance explain the procedures

    followed when measuring earth electrode resistance

    explain the function of an earth-measuring bridge

    explain why insulation resistance has no fixed value

    state the regulations valid when measuring insulation resistance in a system rated up

    to 1000 Volts

    draw the principle diagram of an insulation resistance tester with an generator

    explain the function of an insulation resistance tester with battery converter

    outline the procedures to be followed when measuring the insulation resistance of a

    new installation

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    5/29

    4

    EARTHING AND EARTH ELECTRODE RESISTANCE

    1 EARTHING (GROUNDING) AND EARTH ELECTRODE RESISTANCE *

    A properly installed earthing system is of fundamental importance for safety in electrical

    installations and for lightning conductors.

    The earth (system) is sometimes used for a return path for load currents as well as for

    protection. As an example, plant and fault currents are returned through the earth.

    The purpose of earthing (grounding) system is, therefore, to hold the voltage to earth at

    any desired point in a circuit below a specified value. Should the fault current reach a

    sufficiently high value in the event of an accidental earthing (grounding) in the circuit, the

    circuit protective switch will operate and the circuit will be interrupted. An excessive fault

    current is very often caused by low resistance to earth.

    The earth electrode resistance is a very complex resistance, consisting not only of ohmic

    resistance, but of inductive and capacitive components as well. Electrolytic resistance also

    exists, which results from the organic ingredients in the earth. The earth electrode

    resistance is not always constant, but is influenced by change in the weather and

    chemical and biological factors.

    1.1 Earth electrode resistance

    The value of the earth electrode resistance (RE) must, from time to time, be re-measured,

    the circuit will only have the required safety protection when RE is below the required

    value.

    To measure the REa bridge may be used.

    * NOTE: Earthing may also be referred to as grounding.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    6/29

    5

    1.1.1 Measuring the earth electrode resistance

    Measurements must be made using alternating current, as electrolytic action,

    (polarization) could occur if direct current were used. Such action will cause an increase in

    REand the result in a false measurement.

    When making measurements two auxiliary earth (H1 and H2) are to be used in the

    measurement. To avoid errors in measuring (false readings) the earth and auxiliary earths

    must be minimum of 20 m apart (outside their resistance areas). The distance between H1

    and H2must be such that there is no interference between them.

    RE = Earthing resistance of the earth (ground)

    RH1 = Earthing resistance of the auxiliary earth

    RH2 = Earthing resistance of the auxiliary earth

    To determine the earthing RE the following measurements are required:

    1. Between E and H1 ... RI= RH1+ RE

    2. Between E and H2 ... RII= RH2+ RE

    3. Between H1and H2 ... RIII= RH1+ RH2

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    7/29

    6

    If the values of the first two measurements are added together and the value of the third

    measurement is subtracted from this total, then the result will be:

    In the network with the earthing as a protective measure, the earthing resistance may

    not exceed:

    RE max = 65V___________________

    operating current of the circuit breaker

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    8/29

    7

    1.2 Measuring the earthing resistance with an earth measuring bridge

    Circuit diagram

    1.2.1 The functions of the earth measuring bridge

    The connecting link between E1and E2is connected in series with the earthing resistance

    RE.

    Auxiliary earth H1 is connected at point S, auxiliary earth H2 is connected at point HE. A

    transistor power converter in the instrument produces the alternating current. After power

    has been applied to the circuit measuring current will flow through auxiliary earth RH, earth

    REand the adjustable resistor R of the compensator. The voltage drop V1which appears

    between earth and auxiliary earth H1will be opposed by the voltage drop V2 across the

    adjustable potentiometer R. When the voltages are equal, zero (0) will be indicated on the

    galvanometer. The earth resistance (indicated in Ohms) can be read on the scale of theadjustable potentiometer.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    9/29

    8

    1.3 Earthing practice

    As we have seen earthing is of fundamental importance in electrical engineering. Earthing

    is used for the following purposes:

    a) To prevent the outer casing of apparatus and conductors from reaching a

    dangerous potential and which can result in ignition of flammable vapours or the

    possibility of electric shock.

    b) To allow sufficient current to pass to earth so that protective devices will operate.

    The current path, on the occurrence of an earth fault, is from the fault to the associatedearth electrode, through the earth to the electrode of the supply transformer and back to

    the fault.

    If a low earth-loop resistance is required then a metallic earth-return path can be used.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    10/29

    9

    2 INSULATION RESISTANCE

    Insulation resistance cannot be compared with metallic conductor resistance as the

    current flow in a metallic conductor is exclusively concerned with the movement of free

    electrons.

    With insulation resistance there is a difference between the resistance within a material

    and across the surface of the material. In the interior of an insulation material there are

    practically no free electrons available and practically no current flow is possible.

    Between the insulation sheets a charging current exists which builds a space charge in

    the insulator. In the case of high voltages ionisation may also occur.

    Condensed water and the acids and salts found in the surrounding atmosphere, together

    with contamination by dust create the possibility of a current path over the surface of the

    insulating material.The insulation material, its surface condition and the temperature all affect the insulation

    resistance so, unlike metallic conductors, insulation resistance may vary.

    It is possible to make several insulation resistance measurements on the same object and

    the results may differ widely.

    Also capacitive effects can cause changing readings during the actual measurement.

    These effects can be shown more clearly with the aid of the equivalent circuit for the

    installation resistance shown overleaf.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    11/29

    10

    a) pure ohmic resistance

    b) capacitive resistance with a parallel-connected dropping resistor

    c) voltage-dependent resistance

    d) rectifier connected in series with a resistance

    e) fixed voltage source with series resistance

    Care must be taken when measuring insulation resistance that only the resistance which

    is important for the active power loss is measured. By using a DC voltage as a measuring

    voltage all of the capacitive effects may be eliminated (b).

    To arrive at values for normal operating conditions, the measuring direct voltage should

    be at least as large as the alternating voltage appearing during normal Operation.

    Through this, the influence (c) is eliminated, while the electrolytic voltage (e) and theblocking voltage are only very small and, therefore, need not be taken into consideration.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    12/29

    11

    2.1 Measuring the insulation resistance

    2.1.1 General

    Before putting an installation into operation the soundness of the insulation must be

    tested. It is not possible to insulate an installation completely.

    For this reason, leakage currents will appear from time to time. However, with a good

    insulation not more than 1 mA of current should occur in practice. The insulation

    resistance (Rins) will be measured, restricts leakage current.

    The following regulations are to be followed when measuring Rins in installations with a

    voltage up to 1000 Volts.

    2.1.2 Regulations for measuring Rinsin installations with a voltage up to 1000 Volts

    a) When possible, the measurement should be made at the rated insulation voltage, and

    not less than 500 Volts.

    b) When measuring the insulation resistance of a conductor to earth, the negative pole of

    the voltage source should be connected, where possible to the conductor being

    measured.c) When not only the insulation resistance of the conductor to earth, but also the

    insulation resistance between two conductors are to be tested, all light bulbs, motors

    and other power users should be disconnected from the supply; all light sockets will be

    connected, all fuses, circuit breakers and switches will be switched on.

    d) Each final circuit (circuit directly connected from a fuse to a current consuming device)

    must have Rinsof not less than 1000 Ohms per volt of the supply voltage.

    Example: 100 V network Rins100 k

    380 V network Rins380 k

    500 V network Rins500 k

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    13/29

    12

    2.1.3 Measuring the insulation resistance in an installation out of Operation with a

    portable measuring instrument

    The device most frequently used is the insulation resistance meter with hand generator.

    a) Insulation resistance tester with hand generator and crossed coil instrument

    The measured value is not dependent on the voltage (speed of turning hand

    generator).

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    14/29

    13

    b) Insulation resistance tester with hand generator and moving coil Instrument

    To produce the proper measuring voltage so that the correct Mscale reading is obtained

    the hand generator must be turned at a given rpm.

    For the actual measurement of the insulation resistance, button S1 is pressed and the

    hand generator is turned faster and faster until the indicator of the moving coil meter

    movement indicates zero on the Mscale. When the button S1 is released the insulation

    resistance is indicated. (When S1 is pressed the R is bypassed).

    c) Insulation resistance tester with battery converter

    Function

    A DC voltage delivered from a flash light battery is chopped (mechanically or

    electronically) and so transformed into a square alternating voltage.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    15/29

    14

    This AC is stepped up across a transformer to the desired test voltage and then rectified

    by a rectifying circuit, producing a DC voltage. This DC voltage is in turn filtered by a

    capacitor. With this high DC voltage the insulation measurement is accomplished.

    As an indicating device, a crossed-coil measuring instrument is used.

    A direct indicating resistance-measuring instrument may also be used. This is

    accomplished by measuring the current with known applied voltage across a resistance.

    As an indicator, a normal moving coil instrument is used. The indicator is not dependent

    on the condition of the battery. The battery voltage is held constant through the use of a

    transistor-regulating circuit.

    Measuring the insulation resistance of an installation not in operation

    a) Insulation resistance to earth

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    16/29

    15

    b) Insulation resistance between lines

    c) Separate circuits - between lines

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    17/29

    16

    d) Separate circuits - conductor to earth

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    18/29

    17

    2.1.4 Monitoring the insulation resistance in a live installation

    For this purpose an earth leakage indicator is used. The simplest method is to measure

    the three conductor voltage in the power network to earth. This method is only suitable

    when the neutral point is not earthed.

    Circuit for three-conductor network (mains)

    Circuit for two-conductor network

    In a system without error the three voltage meters will indicate the same voltage V0/ 3.

    Should accidental earthing occur, then the voltage indicated on the voltmeter connected

    on the defective conductor will become less, while the voltage on the other two voltmeters

    will increase.

    Only for networks which are not earthed (grounded)!

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    19/29

    18

    EE 018Earthing and Earth Electrode

    Resistance

    Theoretical Test

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    20/29

    19

    EE 018

    EARTHING AND EARTH ELECTRODE RESISTANCE

    TEST 1

    QUESTIONS:

    1. What is the purpose of an earthing system?

    2. What influences the value of the earth electrode resistance?

    3. Draw a diagram and write the appropriate equations used to measure earthing

    resistance.

    4. What type of current is used for measuring the earthing resistance?

    5. What is the maximum earthing resistance in a network with earthing as a protective

    device?

    6. State the current path in a earth measuring bridge when measuring the earthing

    resistance.

    7. Draw a schematic diagram to be used for measuring the earthing resistance with earth

    measuring bridge.

    8. Why has the insulation resistance no fixed value?

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    21/29

    20

    Test 1 - questions continued

    9. Using the equivalent circuit diagram for the insulation resistance given below, explain

    how (b) and (c) can be eliminated.

    10. State how the insulation resistance may be monitored in a live installation.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    22/29

    21

    EE 018

    EARTHING AND EARTH ELECTRODE RESISTANCE

    TEST 2

    QUESTIONS:

    1. State the value of Rins per volt of the supply between two lines in order for the

    insulation resistance to be considered satisfactory and calculate Rinsfor:

    a) 120 V network

    b) 340 V network

    c) 460 V network

    2. Draw the circuit used to measure the insulation resistance to earth in an installation

    not connected to the supply.

    3. Draw a diagram in order to measure the Rinsusing an insulation resistance tester with

    hand generator and moving coil instrument.

    4. Draw a diagram in order to measure the insulation resistance between conductor and

    conductor of an installation not in operation.

    5. Draw a diagram to measure the Rinsusing an insulation meter with a hand generator

    and cross-coil instrument.

    6. Why is an earth leakage indicator built into an installation?

    7. Draw a diagram for monitoring the insulation resistance in an installation in operation

    with a two conductor (single phase) network.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    23/29

    22

    Test 2 - questions continued

    8. In the diagram shown below, state what is the voltage indication of each meter for

    a) Fault free condition

    b) Accidental earthing of one line

    9. Draw a diagram to be used for monitoring the insulation resistance in an installation in

    operation with a three-conductor network.

    10. State for what type of network the earth leakage indicator shown below is valid.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    24/29

    23

    EE 018

    EARTHING AND EARTH ELECTRODE RESISTANCE

    TEST 1

    SOLUTION:

    1. To hold the voltage at any desired point in a circuit below a specified value to earth.

    2. It is influenced by chemical, biological and weather changes.

    3.

    4. Alternating current (AC).

    5. REmax. = 65 V __

    operating current of the circuit breaker

    6. Through auxiliary earth resistance (RH) and earth resistance (RE) and the adjustable

    resistor of the compensator (R).

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    25/29

    24

    Test 1 - answers continued

    7.

    8. Because of contamination of the surface by dust and condensed water and also

    because of the acids and salts in the surrounding atmosphere.

    9. Through the use of DC voltage as a measuring voltage all of the capacitive influence

    (b) can be eliminated. If the measuring voltage is at least as large as the alternating

    voltage during normal operation, then (c) is eliminated.

    10. An earth leakage indicator is built in.The simplest system is to measure the three conductor voltages to earth in the circuit.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    26/29

    25

    EE 018

    EARTHING AND EARTH ELECTRODE RESISTANCE

    TEST 2

    SOLUTION:

    1. Rins= 1000 ohms per installation Volt.

    2.

    3.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    27/29

    26

    Test 2 - answers continued

    4.

    5.

    6. To monitor the insulation resistance in a live installation.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    28/29

    27

    Test 2 - answers continued ...

    7.

    8. a) Same voltage on each meter.

    b) The voltage indicated on the voltmeter connected to the defective conductor will

    become less, while the other two readings will increase.

    9.

    10. For networks which are not earthed.

  • 7/25/2019 EE018-Earthing and Earth Electrode Resistance-Th-Inst.pdf

    29/29

    KEY TO EVALUATION

    PER CENT MARK

    88 100 1

    75 87 2

    62 74 3

    50 61 4

    0 49 5