Service Voltage Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Electrical Service Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Ampacity Ratings by Contact Size . . . . . . . . . . . . . . . . . . . . . . . . 5Electrical Service Ratings Explained. . . . . . . . . . . . . . . . . . . . . . 6Operating Temperature Classification. . . . . . . . . . . . . . . . . . . . . 7Connector Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Insert Configuration Listing & Identification . . . . . . . . . . . . . . . . . 9Connector Grounding Systems & Horsepower Ratings. . . . . . . . 101 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-133 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-144 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-175 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-206 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-237 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-258 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-269 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2610 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-2912, 14 Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2915 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-3016, 17 Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3018 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3119 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-3220, 21 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3322, 26 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3427 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-3529 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3537 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-3638 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3639, 42, 46 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3747 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-3850, 55 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3858, 60 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3961, 64, 68, 75 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4081, 90 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41100 Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-42Table of ContentsPin-Configuration Selection Guide for HDE, HDS, & EFP3Service Voltage RatingsService Voltage Ratings: IEC & NECContact/Wire Sizes in AWG & Metric (mm)& Grounding Method Identification Grounding Contact Termination SymbolSolderWellPressure CrimpContact Symbol/Wire SizeContact SymbolsWireSize18AWG16AWG12AWG10AWG8AWG4AWG1/0AWG4/0AWG350MCM1.0 mm21.3 mm23.3 mm25.2 mm27.6 mm221 mm254 mm2109 mm2185 mm2Metric(mm)Contact SymbolsWireSize 4/0AWG262MCM313MCM373MCM444MCM500MCM535MCM646MCM109 mm2132 mm2159 mm2189 mm2227 mm2240 mm2273 mm2326 mm2Metric(mm)777MCM394 mm21111MCM562 mm2Multipin Contact SizesSingle Pole Contact Sizes SymbolDC Volts AC Volts instrumentation 10001000A 10001000 D 12501000E 17501250B 24501750C 42003000 SymbolDC Volts AC Volts instrumentation --A 250 240 D 600 600E 600 600B 600 600C 600 600NOTE: IEC Service Voltage Ratings are not for circuit-breaking applications, frequency listing at 50, 60, and 400HzIEC Ratings NEC Ratings4Alternative Classifications of Current RatingElectrical Service RatingsInsert Arrangement Service Rating - Table 1Each insert plan form has a factory designated working voltage rating. The voltage allowable through the contacts, male and female, is limited by the dielectric separation between each contact and the nearest conductor (adjacent contacts and the connector shell). Military Current Ratings According to MIL-C-39029 The maximum current carrying capability of a contact pair is determined by the basic design of the contacts and also the ability of the insulation to withstand the temperature rises caused by an increase in current. The connector is rated up to 125C (257F) for continuous operation. The actual working temperature is a function of the ambient temperature and the summation of the heat dissipated by each individual contact. The maximum current rating for continuous supply is calculated from temperature of the insert. See Column 2 in the above table. NEC (National Electrical Code) Non-Circuit Breaking Table 2, on the following page, lists ratings that are based on test results of contacts and connectors. The temperature range must fall within the range specified by Underwriters Laboratories Inc., assuming certain wire sizes.IEC Service Voltage Ratings Non-Circuit Breaking Service voltage ratings as designated by IEC are derived from IEC 60664-1 Table 3b.When ascertaining required values for creepage and clearance voltages may be increased by a factor of 1.1 to accommodate the range in common use. Table 2, on the following page, lists these ratings.A letter in Column 1 represents voltage ratings, with their associated maximum values, both AC and DC. The insert plan form listings show the ratings for each individual insert.*I = InstrumentationNEC, MS Values based on RMS using MIL-C-5015H Table, XVIII working voltage, IEC values based on 60664-1 table 3b.IEC Service Ratings circuit breaking is not permissable in IEC standards without a hot disconnet permit.Electrical Service VoltageMilitary Ratings MIL-C-5015H Specifcations Non-Circuit BreakingNEC RatingsIEC Service RatingsRequired MinimumCreepage DistanceRequired MinimumClearance orThrough Air SpacingDC (V) AC (V)Non-Circuit BreakingDC (V)Circuit BreakingAC (V)DC (V) AC (V) in mm in mmI 250 200 - - 1000 1000 1/16 2 - -A 700 500 250 240 1000 1000 1/8 3 1/16 2D 1250 900 600 600 1250 1000 3/16 5 1/8 3E 1750 1250 600 600 1750 1250 1/4 6 3/16 5B 2450 1750 600 600 2450 1750 5/16 8 1/4 6C 4200 3000 600 600 4200 3000 1 25 5/16 81 2 3 4 5 65Ampacity Ratings by Contact Size (Gauge)AWG, MCM, and mm2Table 2: The following pages, 4 and 5, apply to table below.Contact Sizes #AWG MCM ( mm )Ampacity RatingNon-Circuit BreakingNEC Ampacity Rating Non-Circuit BreakingIEC Ampacity Rating Non-Circuit BreakingContact Resistance Milliohms (mW)MS NEC Crimp Term Solder Term18 AWG (1.0 mm ) - 9 - 9 3.00 2.4716 AWG (1.3 mm ) 13 16 10 16 2.25 1.7512 AWG (3.3 mm ) 23 30 20 30 1.29 0.8610 AWG (5.2 mm ) 33 40 30 40 0.96 0.648 AWG (7.6 mm ) 46 50 40 50 0.75 0.424 AWG (21 mm ) 80 90 60 90 0.41 0.181/0 AWG (54 mm ) 150 155 100 155 0.23 0.104/0 AWG (109 mm ) 225 225 200 225 0.16 0.06262 MCM (132 mm ) - 599 - 599 0.086 NA313 MCM (159 mm ) - 636 - 636 0.090 NA350 MCM (185 mm ) - 325 - 325 0.070 NA373 MCM (189 mm ) - 674 - 674 0.070 NA500 MCM (240 mm ) - 750 - 750 0.069 NA535 MCM (273 mm ) - 898 - 898 0.032 NA646 MCM (326 mm ) - 1009 - 1009 0.026 NA777 MCM (394 mm ) - 1135 - 1135 0.020 NA1111 MCM (562 mm ) - 1303 - 1303 0.017 NA12 34 5 66Electrical Service Ratings ExplainedOn previous page, see 'Table 2' header for notations: states Assumptions and Standards:Contact sizes: assume equal wire size included as contact and wire combination. Differing wire sizes will exhibit different electrical performance results.MS Specification (MIL-C-39029D) current ratings are in accordance with MIL-C-39029DNEC Specificationsassume a wire sizeselection that is inaccordance NEC guidelines for temperature rise.NEC circuit breaking capability: connectors and contacts that have demonstrated the ability to rupture current under full rated load in accordance with UL standard 1686, 1977 and MIL-C-22992ENEC circuit breaking for hazardous locations (Class and Division system) Connectors and contacts have demonstrated the ability todisconnect under full rated load in accordance with UL standard 1977, 1919 and CSA C22.2-159-M1987IEC ampacity ratings: assume equal wire size, included as contact and wire combination. Differing wire sizes will exhibit different electrical performance results.Contact Resistance when tested in accordance with MIL-1344 method 3004.1 will not exceed the values listed in table 1 column 6

All ampacities shown are for individual contacts and must be derated to determine maximum total current to be carried by the connector. Use thetables and formulas detailed on pages: 6 and 7 Different ambient temperatures need to be taken into consideration when considering ampacity ratings, depending on application and the intended location to be used. It is particularly important to derate the connector when being used in hazardous locations.15672344.17Wire current ratings:For a more conservative standard use the hazardous location derating formulas detailed on pages 6 and 7.Hazardous locations:The following standards IEC derating per: IEC 60079-0 :2004 General requirementsIEC 60079-1 :2004 Flameproof protection 'd'IEC 60079-7 :2003 Increased Safety protection 'e'These standards require that equipment in an energized condition does not exceed the rated surface temperature in order not to ignitehazardous atmospheres. These values are listed below in 'Table 3.'The formulas detailed on pages 6 and 7 will be of assistance to determine the correct insert and allowable ampacity for the connector application and location the value is expressed as dissipated wattage. Operating Temperature Classificationsin Ambient TemperaturesNOTE:This table clarifies the differences in temperatures classification between IEC and NEC, the North American StandardTable 2 IEC vs NEC Temperature ClassificationTemp in CClassifcationIEC N. America85 T6 T6100 T5 T5120 T4 T4A135 T4 T4150 T3 T3C165 T3 T3B180 T3 T3A100 T3 T3115 T2 T2D130 T2 T2C160 T2 T2B180 T2 T2A300 T2 T2450 T1 T1Table 3 IEC Safe Equipment Operating TemperaturesSpontaneous Ignition Temp of the Gasses (T)Temperature Class of EquipmentT685CT5100CT4135CT3200CT2300CT1450C85 < T < 100100 < T < 135135 < T < 200200 < T < 300300 < T < 450450 < T Equipment Safe for UseEquipment Explosion Risk8IMPORTANTTo select the shell size of the connector, it is essential that you calculate the dissipated wattage of the arrangement. This ensures that the arrangement does not exceed the maximum permitted temperature classification with regard to the upper ambient temperature for the area of installation. In some cases it will be necessary to either derate the allowed ampacity of each contact or increase the shell size of the connector. Refer to Table 1 about the maximum allowable dissipated wattage per connector size and use the calculations below to determine safe and proper working temperature of the chosen electrical connector.NOTE: Please pay careful attention to the ambient temperature and also the temperature classification. Connectors are marked T5 unless otherwise requested.Connector Selection GuideMaximum Allowable Wattages & Contact Resistance ValuesNOTE: Contact Resistance measured in accordance with MIL-Std 1344A, Method 3004.1Contact Resistance value expressed in milliohms mW for Table 1 and Table 2.Table 1 - Maximum Allowable Dissipated WattageConnector Shell SizeUpper Ambient Temperature of +40C Upper Ambient Temperature of +50C Upper Ambient Temperature of +65CTemperature Class Temperature Class Temperature ClassT6 T5 T6 T5 T6 T512 23.8 31.7 17.0 24.3 10.7 18.716 39.6 52.8 30.2 43.2 14.6 25.620 52.1 69.4 37.2 53.1 17.1 29.824 64.3 85.1 47.0 67.1 24.1 42.128 79.5 106.1 57.3 81.8 29.8 52.2Maximum Allowable Dissipated WattageTable 2 - Contact Resistance ValuesContact SizeContact Resistance (milliohms mW)Contact Current Rating (amps)Soldered Crimped18 AWG (1.0mm) 2.47 3.00 916 AWG (1.3mm) 1.75 2.25 1612 AWG (3.3mm) 0.86 1.29 3010 AWG (5.2mm) 0.64 0.96 408 AWG (7.6mm) 0.42 0.75 504 AWG (21mm) 0.18 0.41 901/0 AWG (54mm) 0.10 0.23 1554/0 AWG (109mm) 0.06 0.16 225Contact SizeContact Resistance (milliohms mW)Contact Current Rating (amps)Soldered Crimped262 MCM (132mm) NA 0.086 599313 MCM (159mm) NA 0.075 636350 MCM (185mm) NA 0.070 725444 MCM (227mm) NA 0.062 796535 MCM (273mm) NA 0.032 898646 MCM (326mm) NA 0.026 1009777 MCM (394mm) NA 0.020 11351111 MCM (562mm) NA 0.017 13039Insert Configuration Listing & IdentificationHDE, HDS and EFP Electrical Connector Service RatingThe HDE, HDS and EFP Insert Configuration listing is used primarily to identify various contact insert arrangements. For the engineer, it provides visual selection of the insert configuration needed to satisfy his other requirements. For the end user, the list provides general information useful in the termination of plugs and receptacles. To aid the reader, the insert configuration are presented in numerical order, based on the number of contacts in each insert.Figure 1 - Illustration ConfigurationThe male insert illustration shown left (and those on the following pages) is shown as it appears when viewed from the front. Contacts are shown by both physical position within the configuration and by contact number. The contact number corresponds to the contact position shown on the rear face of the insert illustrated as well as to both the front and rear faces of the mating insert.The symbol used to show contact location is indicative of contact size. For example, the contact symbol in this illustration represents a #16 (1.3mm) contact. An explanation of contact symbols is presented on each page of the listing. Each drawing also provides data on normal and alternate key positions.Drawings are reduced from actual size of the insert configuration.NOTE: Alternate keying or insert polarization is intended to prevent improper intermating of plugs and receptacles of like shell sizes and like insert arrangements.01020312345678910111213141516HDS and EFP Electrical Circuit Breaking CB Series.Reversed Service Applications All contact inserts can be reversed in the field or connectors can be ordered for reverse assembly.Typically, the panel mount receptacle houses a female insert, while the cable mounted plug accommodates the male insert. In reverse service the opposite is the case. Contact Size SymbolAvailable AlternateKey PositionsContact Location NumbersStandard Shell FemaleStandard Shell MaleFigure 110Connector Shell GroundingEquipment ground conductors, when used, are always connected through a longer contact which is equipped with a spring clip for mechanically connecting the connector shell to the ground conductor. The ground Pin (male) has 1/8" (3.18mm) additional length to mate first and break last. The hard anodic coating is omitted inside shell at points of contact for the ground clip to positively bond to the connector shell. The position number of the long contact with ground clip is given on the following contact insert listing pages. No other positions are available.LoadEquipmentChasisConnector Shells GroundedCommon to grid pinCircuit GroundLine1/8(3.18mm)Horsepower Ratings: Engergized CircuitsHDS Series CB Circuit breaking connectors are capable of breaking circuits under load at their service voltage and circuit breaking ampacity rating in accordance with the new Standard UL 1686 and 1977, current rupturing requirements. They can also be used in emergencies to disconnect abnormal motor loads without danger of injurious or damaging flashover even under locked-rotor conditions. Maximum horsepower ratings at which they can safely open the circuit in emergencies are shown in the table at the right.In accordance with IEC regulations circuits may not be ruptured under load.Non-Interrupting Ampere Rating When used in series with a disconnect switch, for de-energizing the circuit before inserting or withdrawing the plug, HDS Series CB Conecctors can be used for loads up to the maximum ampere rating of the contacts. Non-interrupting ratings are shown in the table below as well as in the contact insert listings on the following pages. If emergency circuit breaking, at these higher ratings, is apt to be encountered, an automatic disconnect switch should be used in series with the connector. Information on the combination power and automatic control contact inserts for HDS Series CB Connectors can be supplied upon request.Connector Grounding Systems & Horsepower RatingsEquipment Chassis Grounding LayoutRating of Motors: Maximum HorsepowerWires, Poles & PhasesConnector Rating C Breaking AmperesClassifcation120V 240V 480V 600V3-Wire, 4-Pole Three Phase30 3 10 20 1560 10 20 30 25100 15 30 40 30200 30 50 50 303-Wire, 4-Pole Two PhaseThree Wire30 3 7.5 15 1560 7.5 15 30 25100 10 25 40 30200 25 50 50 304-Wire, 4-Pole Two PhaseFour Wire30 5 10 25 2060 10 25 40 40100 15 30 50 40200 40 50 50 4011N12 NNNNNNStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-14/0MSocket HDS-C24-14/0FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1262MSocket HDS-C24-1262FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1262MSocket HDS-C24-1262FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1373MSocket HDS-C24-1373FQuantitySize AWG/MCM (mm)Service Voltage Rating1 4/0 (109) DQuantity Size AWG/MCM(mm) Service Voltage Rating1 262MCM (132) DQuantity Size AWG/MCM (mm) Service Voltage Rating1 313MCM (159) DQuantity Size AWG/MCM (mm) Service Voltage Rating1 373MCM (189) DKeyway Positions01 - 10002 - 231One Contact12NNNNStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1444MSocket HDS-C24-1444FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1500MSocket HDS-C24-1500FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1535MSocket HDS-C24-1535FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1646MSocket HDS-C24-1646FQuantity Size AWG/MCM(mm) Service Voltage Rating1 444MCM (227) DQuantity Size AWG/MCM(mm) Service Voltage Rating1 500MCM (240) DQuantity Size AWG/MCM(mm) Service Voltage Rating1 535MCM (273) DQuantity Size AWG/MCM(mm) Service Voltage Rating1 646MCM (326) DOne Contact13NN0102030405213N1 2301NStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-1777MSocket HDS-C24-1777FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-11111MSocket HDS-C24-11111FQuantity Size AWG/MCM (mm) Service Voltage Rating1 777MCM (394) DQuantity Size AWG/MCM (mm) Service Voltage Rating1 777MCM (394) DStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-310GMSocket HDS-12-310GFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-312MSocket HDS-12-312FQuantity Size AWG/MCM (mm) Service Voltage Rating3 10 (5.2) DQuantity Size AWG/MCM (mm) Service Voltage Rating3 12 (3.3) DKeyway Positions01 - 3602 - 7203 - 10804 - 14405 - 180Keyway Positions01 - 50One ContactThree Contacts1412301020304N3210102N12301020403N3 120102NStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-310MSocket HDS-12-310FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-38GMSocket HDS-12-38GFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-34GM1Socket HDS-16-34GF11 Pressure 16Pin HDS-16-34GMR1Socket HDS-16-34GFR1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-34M1Socket HDS-16-34F11 Pressure 16Pin HDS-16-34MR1Socket HDS-16-34FR1Quantity Size AWG/MCM (mm) Service Voltage Rating3 10 (5.2) DQuantity Size AWG/MCM (mm) Service Voltage Rating3 8 (7.6) AQuantity Size AWG/MCM (mm) Service Voltage Rating3 4 (21) DQuantity Size AWG/MCM (mm) Service Voltage Rating3 4 (21) DKeyway Positions01 - 3602 - 100Keyway Positions01 - 8002 - 14003 - 18004 - 220Keyway Positions01 - 4002 - 9003 - 14004 - 180Keyway Positions01 - 7002 - 110Three Contacts152134010203040506N0141230403N1234G040302N12340102NStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-416MSocket HDS-12-416FStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-48M1Socket HDS-16-48F1Quantity Size AWG/MCM (mm) Service Voltage Rating4 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 8 (7.6) DKeyway Positions01 - 3002 - 6003 - 9004 - 12005 - 15006 - 180Keyway Positions01 - 4502 - 112StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 12Pin HDS-12-410M1Socket HDS-12-410F12 Crimp 12Pin HDS-12-410MSocket HDS-12-410FStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 12Pin HDS-12-410GM1Socket HDS-12-410GF12 Crimp 12Pin HDS-12-410GMSocket HDS-12-410GFQuantity Size AWG/MCM (mm) Service Voltage Rating4 10 (5.2) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 10 (5.2) DKeyway Positions01 - 2703 - 20704 - 243Keyway Positions02 - 18003 - 20704 - 243Note: 01 key position not available in pressure terminationNote: 01 key position not available in pressure terminationFour Contacts16210134G02N34120201N1234G0102050403N123404030102NStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-44M1Socket HDS-16-44F11 Pressure 16Pin HDS-16-44MR1Socket HDS-16-44FR12 Crimp 16Pin HDS-16-44MSocket HDS-16-44FStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-44GM1Socket HDS-16-44GF11 Pressure 16Pin HDS-16-44GMR1Socket HDS-16-44GFR12 Crimp 16Pin HDS-16-44GMSocket HDS-16-44GFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder C20Pin HDS-C20-41/0GM1Socket HDS-C20-41/0GF11 Pressure C20Pin HDS-C20-41/0GMR1Socket HDS-C20-41/0GFR12 Crimp C20Pin HDS-C20-41/0GMSocket HDS-C20-41/0GFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder C20Pin HDS-C20-41/0M1Socket HDS-C20-41/0F11 Pressure C20Pin HDS-C20-41/0MR1Socket HDS-C20-41/0FR12 Crimp C20Pin HDS-C20-41/0MSocket HDS-C20-41/0FQuantity Size AWG/MCM (mm) Service Voltage Rating4 4 (21) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 4 (21) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 1/0 (54) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 1/0 (54) DKeyway Positions01 - 10502 - 13503 - 24004 - 255Keyway Positions01 - 10502 - 12003 - 31504 - 33005 - 345Keyway Positions01 - 1502 - 165Keyway Positions01 - 1502 - 225Note: 01 key position not available in pressure terminationFour Contacts17234101N014G12302N01431 2 0302N1234G 5NStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 24Pin HDS-24-44/0M1Socket HDS-24-44/0F1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-44/0CM1Socket HDS-C24-44/0CF1Quantity Size AWG/MCM (mm) Service Voltage Rating4 4/0 (109) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 4/0 (109) DKeyway Positions01 - 45Keyway Positions01 - 1502 - 22503 - 240StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-44/0GM1Socket HDS-C24-44/0GF11 Pressure C24Pin HDS-C24-44/0GMR1Socket HDS-C24-44/0GFR1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 12Pin HDS-12-512M1Socket HDS-12-512F12 Crimp 12Pin HDS-12-512MSocket HDS-12-512FQuantity Size AWG/MCM (mm) Service Voltage Rating4 4/0 (109) DQuantity Size AWG/MCM (mm) Service Voltage Rating5 12 (3.3) DKeyway Positions01 - 1502 - 165Four ContactsFive Contacts183421 5N2134G5N0112345N010212345NStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 12Pin HDS-12-512M1Socket HDS-12-512F12 Crimp 12Pin HDS-12-512MSocket HDS-12-512MFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-58M1Socket HDS-16-58F12 Crimp 16Pin HDS-16-58MSocket HDS-16-58FStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 20Pin HDS-20-54GM1Socket HDS-20-54GF11 Pressure 20Pin HDS-20-54GMR1Socket HDS-20-54GFR12 Crimp 20Pin HDS-20-54GMSocket HDS-20-54GFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-58GM1Socket HDS-16-58GF12 Crimp 16Pin HDS-16-58GMSocket HDS-16-58GFQuantity Size AWG/MCM (mm) Service Voltage Rating5 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating5 8 (7.6) DQuantity Size AWG/MCM (mm) Service Voltage Rating5 4 (21) DQuantity Size AWG/MCM (mm) Service Voltage Rating5 8 (7.6) DKeyway Positions01 - 4802 - 97.3Keyway Positions01 - 36Five ContactsNote: Contact cannot be used with short cable adapter 16191234G501N2134501N0112534GN01031234502NStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 20Pin HDS-20-54GM1Socket HDS-20-54GF11 Pressure 20Pin HDS-20-54GMRSocket HDS-20-54GFRStyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-51/0M1Socket HDS-C24-51/0F11 Pressure C24Pin HDS-C24-51/0MR1Socket HDS-C24-51/0FR1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-51/0GM1Socket HDS-C24-51/0GF11 Pressure C24Pin HDS-C24-51/0GMR1Socket HDS-C24-51/0GFR1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C28Pin HDS-C28-54/0M1Socket HDS-C28-54/0F11 Pressure C28Pin HDS-C28-54/0MR1Socket HDS-C28-54/0FR1Quantity Size AWG/MCM (mm) Service Voltage Rating5 4 (21) DQuantity Size AWG/MCM (mm) Service Voltage Rating5 1/0 (54) EQuantity Size AWG/MCM (mm) Service Voltage Rating5 1/0 (54) EQuantity Size AWG/MCM (mm) Service Voltage Rating5 1/0 (109) DKeyway Positions01 - 51Keyway Positions01 - 108Keyway Positions01 - 36Keyway Positions01 - 3602 - 12803 - 306Five Contacts20N01020312345NN03040102123 45N010203040551234N1254G3010203NStyleTerm TypeShell SizeInsert GenderPart Number1 Solder C28Pin HDS-C28-54/0CGM1Socket HDS-C28-54/0CGF11 Pressure C28Pin HDS-C28-54/0CGMR1Socket HDS-C28-54/0CGFR1StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-316CMSocket HDS-12-316CFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-34/0CM1Socket HDS-C24-34/0CF1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 20Pin HDS-20-312CM1Socket HDS-20-312CF12 Crimp 20Pin HDS-20-312CMSocket HDS-20-312CFQuantity Size AWG/MCM (mm) Service Voltage Rating5 4/0 (109) DQuantity Size AWG/MCM (mm) Service Voltage Rating2 8 (7.6) A3 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating3 4/0 (109) D2 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating2 1/0 (54) E3 12 (3.3) EKeyway Positions01 - 9002 - 12603 - 180Keyway Positions01 - 4502 - 9003 - 11504 - 18005 - 270Keyway Positions01 - 4502 - 15703 - 292Keyway Positions01 - 8002 - 11003 - 25004 - 280Five Contacts21Six Contacts01020304050607123456N010203040514G5236N01 040302123456N0102 0304123456NStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-412CMSocket HDS-20-412CFStyleTerm TypeShell SizeInsert GenderPart Number1 Pressure 20Pin HDS-20-44CGMR1Socket HDS-20-44CGFR1Quantity Size AWG/MCM (mm) Service Voltage Rating2 8 (7.6) E4 12 (3.3) EQuantity Size AWG/MCM (mm) Service Voltage Rating4 4 (21) D2 10 (5.2) DKeyway Positions01 - 2302 - 4503 - 6804 - 9005 - 11206 - 13507 - 157Keyway Positions01 - 3002 - 12003 - 18004 - 24005 - 270StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 20Pin HDS-20-21/0CM1Socket HDS-20-21/0CF12 Crimp 20Pin HDS-20-21/0CMSocket HDS-20-21/0CFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 20Pin HDS-20-31/0CM1Socket HDS-20-31/0CF12 Crimp 20Pin HDS-20-31/0CMSocket HDS-20-31/0CFQuantity Size AWG/MCM (mm) Service Voltage Rating2 1/0 (54) A4 4 (21) AQuantity Size AWG/MCM (mm) Service Voltage Rating3 1/0 (54) D3 12 (3.3) DKeyway Positions01 - 2602 - 24403 - 27004 - 334Keyway Positions01 - 7002 - 14503 - 21504 - 29022010203561234N134650102030405N04612354030201N010214G52630403NStyleTerm TypeShell SizeInsert GenderPart Number1 Pressure C24Pin HDS-C24-31/0CGMR1Socket HDS-C24-31/0CGFR1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-34/0CM1Socket HDS-C24-34/0CF1StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C28Pin HDS-C28-61/0MSocket HDS-C28-61/0FStyleTerm TypeShell SizeInsert GenderPart Number1 Solder C28Pin HDS-C28-44/0CM1Socket HDS-C28-44/0CF1Quantity Size AWG/MCM (mm) Service Voltage Rating3 1/0 (54) D2 10 Relay (5.2) D1 4 (21) DQuantity Size AWG/MCM (mm) Service Voltage Rating3 4/0 (109) D3 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating6 1/0 (54) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 4/0 (109) D2 12 Relay (3.3) AKeyway Positions01 - 3002 - 12003 - 18004 - 240Keyway Positions01 - 7002 - 14503 - 21504 - 290Keyway Positions01 - 3002 - 6003 - 9004 - 12005 - 230Keyway Positions01 - 9002 - 12603 - 252Six Contacts23StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C28Pin HDS-C28-44/0CGM1Socket HDS-C28-44/0CGF1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C28Pin HDS-C28-4350CM1Socket HDS-C28-4350CF1StyleTerm TypeShell SizeInsert GenderPart Number1 Crimp 12Pin HDS-12-716MSocket HDS-12-716FQuantity Size AWG/MCM (mm) Service Voltage Rating4 4/0 (109) D2 12 Relay (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating4 350MCM (185) D2 12 Relay (3.3) EQuantity Size AWG/MCM (mm) Service Voltage Rating7 350MCM (185) DKeyway Positions01 - 9002 - 126Keyway Positions01 - 6002 - 12003 - 195Keyway Positions01 - 30 07 - 21002 - 60 08 - 24003 - 90 09 - 27004 - 120 10 - 30005 - 150 11 - 33006 - 1800102561234GN010203126345N010203123654GN01675432102030405 0708091011NKeyway Positions01 - 9002 - 12603 - 180Six ContactsSeven ContactsStyleTerm TypeShell SizeInsert GenderPart Number1 Pressure C28Pin HDS-C28-44/0CGMR1Socket HDS-C28-44/0CGFR11 Solder C28Pin HDS-C28-44/0CGM1Socket HDS-C28-44/0CGF1Quantity Size AWG/MCM (mm) Service Voltage Rating4 4/0 (109) D2 10 Relay (5.2)240102030405060708091236745N0102031234567040506070809N34567 12N1234567NStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-712GMSocket HDS-12-712GFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-712MSocket HDS-12-712FQuantity Size AWG/MCM (mm) Service Voltage Rating7 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating7 12 (3.3) AStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-78MSocket HDS-20-78FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-74MSocket HDS-24-74FQuantity Size AWG/MCM (mm) Service Voltage Rating7 8 (7.6) EQuantity Size AWG/MCM (mm) Service Voltage Rating7 8 (7.6) EKeyway Positions01 - 36 06 - 21602 - 72 07 - 25203 - 108 08 - 28804 - 144 09 - 32405 - 180Keyway Positions01 - 36 06 - 21602 - 72 07 - 25203 - 108 08 - 28804 - 144 09 - 32405 - 180Seven Contacts250102030405060708091674523N132876540102030405N0102030412345678N127N483601NKeyway Positions01 - 36 06 - 21602 - 72 07 - 25203 - 108 08 - 28804 - 144 09 - 32405 - 180StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-71/0M1Socket HDS-C24-71/0F12 Crimp C24Pin HDS-C24-71/0MSocket HDS-C24-71/0MQuantity Size AWG/MCM (mm) Service Voltage Rating7 1/0 (54) DKeyway Positions01 - 2202 - 5703 - 10504 - 14705 - 200Keyway Positions01 - 3002 - 7103 - 10804 - 222Keyway Positions01 - 60StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 24Pin HDS-24-41/0CM1Socket HDS-24-41/0CF12 Crimp 24Pin HDS-24-41/0CMSocket HDS-24-41/0CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-41/0CMSocket HDS-C24-41/0CFStyleTerm TypeShell SizeInsert GenderPart Number2 Solder C28Pin HDS-C28-4350CM1Socket HDS-C28-4350CF1Quantity Size AWG/MCM (mm) Service Voltage Rating4 1/0 (54) D4 4 (21) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 1/0 (54) B4 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating4 350MCM (185) D4 12 (3.3) ESeven ContactsEight Contacts260167891054321N01020304195324 67805N0102030405123456789N0126364G517NKeyway Positions01 - 75Keyway Positions01 - 6002 - 12003 - 18004 - 24005 - 300Keyway Positions01 - 3002 - 6003 - 9004 - 12005 - 230Keyway Positions01 - 75StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C28Pin HDS-C28-4350CGM1Socket HDS-C28-4350CGF1StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-816CMSocket HDS-16-816CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-612CMSocket HDS-16-612CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-1016MSocket HDS-12-1016FQuantity Size AWG/MCM (mm) Service Voltage Rating4 350MCM (185) D4 12 (3.3) EQuantity Size AWG/MCM (mm) Service Voltage Rating1 4 (21) D8 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating6 12 (3.3) A3 8 (7.6) AQuantity Size AWG/MCM (mm) Service Voltage Rating10 16 (1.3) AEight ContactsNine ContactsTen Contacts2702031234 5678910N139287654100102N139287654G1001N0102030412346957 108NKeyway Positions02 - 7003 - 145Keyway Positions01 - 3002 - 45Keyway Positions01 - 35Keyway Positions01 - 3002 - 6003 - 9004 - 120StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-1016GMSocket HDS-12-1016GFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-612CMSocket HDS-16-612CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-612CGMSocket HDS-16-612CGFStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 20Pin HDS-20-812CM1Socket HDS-20-812CF1Quantity Size AWG/MCM (mm) Service Voltage Rating10 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating4 10 (5.2) D6 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 10 (5.2) D6 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating2 1/0 (54) D8 12 (3.3) DTen Contacts28N0167859102 134GNN139287654100102NN010203040506070813928 7654108N139287654100102NKeyway Positions01 - 3002 - 45Keyway Positions01 - 3002 - 45Keyway Positions01 - 35StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-612CMSocket HDS-20-612CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-612CMSocket HDS-C24-612CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C24Pin HDS-C24-612CGMSocket HDS-C24-612CGFQuantity Size AWG/MCM (mm) Service Voltage Rating4 4 (21) D6 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 1/0 (54) D6 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating4 1/0 (54) D6 12 (3.3) DStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-88CMSocket HDS-24-88CFQuantity Size AWG/MCM (mm) Service Voltage Rating2 4 (21) D8 8 (7.6)Ten Contacts29010203040506123456789101112N01020304050619 213 10384712145611N0102123456789101112131415NN01 12345678910111213 1415NKeyway Positions01 - 2702 - 6703 - 10704 - 13305 - 17306 - 214Keyway Positions01 - 3002 - 6003 - 9004 - 11205 - 13506 - 157Keyway Positions01 - 3602 - 126Keyway Positions01 - 36StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-1210MSocket HDS-20-1210FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-1216MSocket HDS-16-1216FStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 24Pin HDS-24-1016CM1Socket HDS-24-1016CF1StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 24Pin HDS-24-1012CM1Socket HDS-24-1012CF1Quantity Size AWG/MCM (mm) Service Voltage Rating12 10 (5.2) DQuantity Size AWG/MCM (mm) Service Voltage Rating2 4 (21) D12 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating5 1/0 (54) D10 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating5 1/0 (54) D10 12 (13.3) ATwelve ContactsFourteen ContactsFifteen Contacts3001020304050607081234567891011121314151617N01020312345678910111213141516NN0102031119876 5432101316141512N123456789 101112131415NFifteen ContactsSixteen ContactsSeventeen ContactsKeyway Positions01 - 9002 - 18003 - 243Keyway Positions01 - 3602 - 5703 - 90StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-1210CGM1Socket HDS-C24-1210CGF1StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-1616MSocket HDS-16-1616FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-168MSocket HDS-20-168FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 12Pin HDS-12-1718MSocket HDS-12-1818FQuantity Size AWG/MCM (mm) Service Voltage Rating5 1/0 (54) D10 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating16 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating16 8 (7.6) AQuantity Size AWG/MCM (mm) Service Voltage Rating17 18 (1.0) AKeyway Positions01 - 36 05 - 19802 - 72 06 - 23403 - 108 07 - 27004 - 144 08 - 3063125678910111234151 6 171813 141910203N019 101234567811121314 151617 1819N010203 040605123456789101112131415161 718NEighteen ContactsNineteen ContactsKeyway Positions01 - 6002 - 9003 - 15004 - 21105 - 25506 - 300Keyway Positions01 - 24Keyway Positions02 - 4803 - 144StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-1616CMSocket HDS-16-1616CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-1912MSocket HDS-16-1912FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-1912GMSocket HDS-16-1912GFQuantity Size AWG/MCM (mm) Service Voltage Rating2 10 (5.2) D16 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating19 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating19 12 (3.3) A32010203040506070809123456 78910111213141516171819N1183179161514131112287654 1910N11 83179161514131 11 22876541910NNineteen ContactsStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-1916MSocket HDS-16-1916FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-1912MSocket HDS-20-1912FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-1912GMSocket HDS-20-1912GFQuantity Size AWG/MCM (mm) Service Voltage Rating19 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating19 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating19 12 (3.3) DKeyway Positions01 - 36 06 - 21602 - 72 07 - 25203 - 108 08 - 28804 - 144 09 - 32405 - 18033011 234678171820199 101112131415165N01678918543211719201011121 31 41 516NN010503021234567891 01 1121314151617181 920N0102030512345678910111213141516171 8192021NTwenty ContactsTwenty-One ContactsKeyway Positions01 - 43Keyway Positions01 - 56Keyway Positions01 - 6002 - 12003 - 18005 - 300Keyway Positions01 - 3002 - 9003 - 15004 - 222StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-2012MSocket HDS-20-2012FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-2012GMSocket HDS-20-2012GFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-1616CMSocket HDS-20-1616CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-1116CMSocket HDS-16-1116CFQuantity Size AWG/MCM (mm) Service Voltage Rating20 12 (3.3) B Center / A OuterQuantity Size AWG/MCM (mm) Service Voltage Rating20 12 (3.3) B Center / A OuterQuantity Size AWG/MCM (mm) Service Voltage Rating4 8 (7.6) D16 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating10 12 (3.3) A11 16 (1.3) A341392876541018171 51 4 G1311121 6192021222324 2526270102N0102123456789 1 01 1121314151617182021 2 2232425271926N010203040506070809 1234567891 01 1121314151617182223 1924262 52021N0102031172 0234567891011121314151622211819NStyleTerm TypeShell SizeInsert GenderPart Number1 Solder 16Pin HDS-16-818CM1Socket HDS-16-818CF1Quantity Size AWG/MCM (mm) Service Voltage Rating4 12 (3.3) A4 16 (1.3) A18 18 (1.0) AKeyway Positions01 - 36 06 - 21602 - 72 07 - 25203 - 108 08 - 28804 - 144 09 - 32405 - 180Keyway Positions01 - 4502 - 9003 - 191Keyway Positions01 - 3302 - 90Keyway Positions01 - 5402 - 90StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-2016CMSocket HDS-20-2016CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-2416CMSocket HDS-16-2416CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-2416CGMSocket HDS-16-2416CGFQuantity Size AWG/MCM (mm) Service Voltage Rating2 8 (7.6) E20 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating3 12 (3.3) A24 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating24 16 (1.3) A3 12 (3.3) ATwenty-Two ContactsTwenty-Six ContactsTwenty-Seven Contacts350102060504031234567891 01 11213141516171822192021 23262527 24N010203040512345678910111 2 1 31 4211 51617181920222324252 7282629N0102030405 06070809123456789 1 0 1 1121314151617 18192021222324 2 526272829303132333 43 53637N11831791615141311122876541 92 0282726252423212229303 73635343331 3 210NKeyway Positions01 - 32 06 - 19502 - 65 07 - 22703 - 97 08 - 26004 - 130 09 - 29205 - 162Keyway Positions01 - 3002 - 4503 - 9004 - 12005 - 15006 - 225Keyway Positions01 - 4502 - 6603 - 9004 - 13505 - 155StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-2512CMSocket HDS-20-2512CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C28Pin HDS-C28-2312CMSocket HDS-C28-2312CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-3712MSocket HDS-20-3712FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-3716MSocket HDS-16-3716F3 Crimp 16Pin HDS-16-3716MCSocket HDS-16-3716FC1 Solder 16Pin HDS-16-3716M1Socket HDS-16-3716F1Quantity Size AWG/MCM (mm) Service Voltage Rating2 4 (21) D25 12 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating4 1/0 (54) D2 8 (7.6) D23 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating37 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating37 16 (1.3) ATwenty-Seven ContactsTwenty-Nine ContactsThirty-Seven Contacts36N1183179161514131 11 228765419202827262 52423212229303736353 43331321 002N010203118317916151413111228765419202827262 52 4232122293037363 5343331 321 0NN01020305041 1831791615141311122876541920 2827262 52 42321222930373635343 331321 0N010208070605030411831791615141 31 11 22876541920282 72 62524232122293038373 635343331321 0NKeyway Positions02 - 100Keyway Positions01 - 1502 - 4503 - 90Keyway Positions01 - 2502 - 7603 - 12704 - 17805 - 254StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-3712GMSocket HDS-20-3712GFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-3716MSocket HDS-24-3716FStyleTerm TypeShell SizeInsert GenderPart Number1 Solder C24Pin HDS-C24-3516CM1Socket HDS-C24-3516CF1StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-3516CMSocket HDS-20-3516CFQuantity Size AWG/MCM (mm) Service Voltage Rating37 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating37 16 (1.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating2 1/0 (52) D35 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating3 10 (5.2) A35 16 (1.3) AKeyway Positions01 - 27 05 - 22502 - 60 06 - 25503 - 90 07 - 28304 - 117 08 - 315Thirty-Seven ContactsThirty-Eight Contacts37N05010403021183179161514131 1122876541920282 72 625242321222930373 635343331 321 0383 9NN06050403010211831791615141 31 11 228765419202 8272625242321 222 9303 8373635343331323 94041421 0N118317916151413111228765419202827262524232122293038373635343331 32394041421043444546N0106050403021183179161 51 41 3111 22876541920282726 252423212229303837363 53 43331323940464 5444341421047NKeyway Positions01 - 4002 - 8003 - 14004 - 21005 - 280Keyway Positions01 - 3002 - 6003 - 9004 - 12005 - 15006 - 180Keyway Positions01 - 3002 - 6003 - 9004 - 12005 - 15006 - 180StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp C28Pin HDS-C28-3112CMSocket HDS-C28-3112CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 28Pin HDS-28-4212MSocket HDS-28-4212FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-4516CMSocket HDS-20-4516CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-4516CMSocket HDS-16-4516CFQuantity Size AWG/MCM (mm) Service Voltage Rating1 8 (7.6) D2 1/0 (54) D5 10 (5.2) S31 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating42 12 (3.3) DQuantity Size AWG/MCM (mm) Service Voltage Rating2 8 (7.6) D45 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating45 18 (1.0) A1 8 (7.6) AThirty-Nine Contacts, Fourty-Two ContactsFourty-Six Contacts, Fourty-Seven Contacts38N118317916151413111228765419202827 2625242321222930383736353433313239404847464544434142 4950105153525554010204NN11831791615141 31 11 228765419202827262524232122293 03837363534333 13239404847464 54 443414249501 0515352555401020304050607090810N1183179161514131112287654192028272625242321222930383736353433313239404847464544434142495010010203040506N NN02031370123456789382829303139111012 13141516171819202122232425413635343233404647 4245444326270405NKeyway Positions01 - 6002 - 12003 - 18004 - 24005 - 300Keyway Positions01 - 3002 - 6003 - 12004 - 15005 - 22506 - 315Keyway Positions01 - 3002 - 9004 - 180StyleTerm TypeShell SizeInsert GenderPart Number1 Solder C28Pin HDS-C28-4312CM1Socket HDS-C28-4312CF1StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-4616CMSocket HDS-20-4616CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 28Pin HDS-28-4116CMSocket HDS-28-4116CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-5518MSocket HDS-16-5518FQuantity Size AWG/MCM (mm) Service Voltage Rating1 1/0 (54) D3 4 (21) D43 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating4 8 (7.6) D46 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating3 8 (7.6) D6 4 (21) D5 12 (3.3) A41 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating55 18 (1.0) Inst.Keyway Positions01 - 32 06 - 18002 - 60 07 - 22003 - 90 08 - 25504 - 117 09 - 28505 - 150 10 - 345Fourty-Seven ContactsFifty ContactsFifty-Five Contacts3911831791 61 51 41 311122876541920282726252423212229303837363 53 433313239404 84 7464544434142495010515359525857565554600103060405N1183179161 51 41 3111 2287654192028272625242321222930383736353 43 3313 239404 84 746454443414249501051535952585 7565554600102 0503 04N1691882476542317232221201910113938373 61 51 4121 34041313029282726 4225323 34443 525150493 43 5454614 75 64 8585554535701N118317916151413111228765419202827262 52 42 3212 22930383736353433 3132394 04847 464544434 14 24950105 15 35 25 85756555401NKeyway Positions01 - 165Keyway Positions01 - 45Keyway Positions01 - 3002 - 9003 - 15004 - 21005 - 270Keyway Positions01 - 3002 - 9003 - 15004 - 21005 - 270StyleTerm TypeShell SizeInsert GenderPart Number1 Solder 24Pin HDS-24-5812M1Socket HDS-24-5812F12 Crimp 24Pin HDS-24-5812MSocket HDS-24-5812FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-5812GMSocket HDS-24-5812GFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-6016MSocket HDS-20-6016FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-5316CMSocket HDS-24-5316CFQuantity Size AWG/MCM (mm) Service Voltage Rating58 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating58 12 (3.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating60 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating7 12 (3.3) A53 16 (1.3) AFifty-Eight ContactsSixty Contacts40118317916151 41 3111 228765419202827262524232122293038373 63 53 43 3313239404847464544 4341424 9 5 010515359 525 85756555461 6001020403N11831791 61 51 41 3111 2287654192028 2726252423212229303 83 73 635343331323 9404847464544434142495010515 359525857565 55 4616 3626460010203N11831791 61 51 41 3111 22876541920282726252423212229303 83 73 635343331323 9404847464544434142495010515 3595 25857565 55 4616362 686766656 46002050403N11 831 791 61 51 41311122876541 920282726252423212229303837363534333132394048474 64 54 44 3414 2495010515359525857565554616 3696 2686766656 460717 372757470010203040506070809NKeyway Positions01 - 7502 - 10503 - 15004 - 232StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 16Pin HDS-16-6118MSocket HDS-16-6118F3 Crimp 16Pin HDS-16-6118M3Socket HDS-16-6118F3Quantity Size AWG/MCM (mm) Service Voltage Rating61 18 (1.0) Inst.Keyway Positions01 - 9002 - 13503 - 202Keyway Positions02 - 4503 - 15704 - 22805 - 292StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-6216CMSocket HDS-20-6216CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-6116CMSocket HDS-24-6116CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-6816MSocket HDS-20-6816FQuantity Size AWG/MCM (mm) Service Voltage Rating2 10 (5.2) A62 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating3 8 (7.6) A11 12 (3.3) A61 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating68 16 (1.3) AKeyway Positions01 - 30 06 - 18002 - 60 07 - 20703 - 90 08 - 27004 - 127 09 - 31105 - 160Sixty-One Contacts, Sixty-Four ContactsSixty-Eight Contacts, Seventy-Five Contacts411183179161514131 11 22876541920282726252423212229303837363 53 43 331323940484746454443414249501 05153595258575 65 55 461636 9626867666564607 1737 97278777675747 0818001020304050607NN11 831 791 61 5141311122876541 92028272625242321222930383736353433313239404847464 54 44 34 1 4 24950105153595258575655 54616 36962686766656 460717379727 87 77675747081838982888 78685848090010203040506N11 831 791 61 5141311122876541 92 028272625242321222930383736353433313239404 84 74 64 54 443414249501051535952585756555461636 9626 867666564607 173797278777675747 08183898288878 68 58480 91939992989 79 69594 90100NKeyway Positions01 - 4502 - 9003 - 13504 - 18005 - 22506 - 27007 - 300Keyway Positions01 - 5402 - 9003 - 13004 - 18005 - 22506 - 270StyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-7018CMSocket HDS-20-7018CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 20Pin HDS-20-9018MSocket HDS-20-9018FStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-10016MSocket HDS-24-10016FQuantity Size AWG/MCM (mm) Service Voltage Rating11 12 (3.3) A70 18 (1.0) AQuantity Size AWG/MCM (mm) Service Voltage Rating90 18 (1.0) AQuantity Size AWG/MCM (mm) Service Voltage Rating100 16 (1.3) AEighty-One ContactsNinety ContactsOne-Hundred ContactsN11 831 791 615141311122876541 9 2 02827262 52 42 32 12 2293038373635343331323940484746454443414249501051535 9525 85 75 65 55 46163696268676665646 07173797278777675747081838 9828 88 78 68 584809193999298979695949001101118103 1171 0 91161151141131 1 11 1 21021 0 8107106105104119 1201 2 81 2 71 2 61251241231211221 2 91301381371361351341331311321 3 91 4 01431411421 1 0100N01123465879101112131415 161718192021222324252627282930313233353440393837364150494847464544 4342595857 56555453525160706968676665646362617978777675747372718081898887868584838290 959998979694939291100N92 6112 5172 42 3222119201016151413122 72 8432132312930564544434241407846475 55 45 35 25 150484956571858346433393837363566687 4677 372717069657 678837763626160597 58587798692919 08 98884 81959482939 99 89796 80100NStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 24Pin HDS-24-10016GMSocket HDS-24-10016GFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 28Pin HDS-28-8316CMSocket HDS-28-8316CFStyleTerm TypeShell SizeInsert GenderPart Number2 Crimp 28Pin HDS-28-14316MSocket HDS-28-14316FQuantity Size AWG/MCM (mm) Service Voltage Rating100 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating17 12 (3.3) A83 16 (1.3) AQuantity Size AWG/MCM (mm) Service Voltage Rating143 16 (1.3) AKeyway Positions01 - 60Keyway Positions01 - 46One-Hundred ContactsOne-Hundred Fourty-Three Contacts42Electrical Equipment Corp.4050 North Rockwell StreetChicago, Illinois 60618, USA