effect of inserting coiled wires on pressure drop of r-404a condensation

7
Effect of inserting coiled wires on pressure drop of R-404A condensation Mohammad Reza Salimpour*, Hesam Gholami Department of Mechanical Engineering, Isfahan University of Technology, Isfahan 84156-83111, Iran article info Article history: Received 3 June 2013 Received in revised form 12 October 2013 Accepted 27 October 2013 Available online 7 November 2013 Keywords: Pressure drop Turbulator R-404A Condensation abstract In this study, an experimental investigation was carried out to determine the increase of pressure drop during convective condensation of R-404A vapor inside coiled wire inserted tubes. Experiments were performed for a plain tube and five coiled wire inserted tubes. Data were collected for four mass velocities. For each mass velocity, six different vapor qualities were considered. From the results, it is found that the coiled wire inserts increased the pressure drop up to 1200% compared to plain tube values. An empirical correlation is also developed to predict the pressure drop of coiled wire inserted tubes during R404-A condensation with accuracy of 20%. ª 2013 Elsevier Ltd and IIR. All rights reserved. Effet de l’insertion de fils torsade ´s sur la chute de pression de condensation de R404A Mots cle ´s : Chute de pression ; Turbulateur ; R404A ; Condensation 1. Introduction Accurate prediction of two-phase flow pressure drop in evaporators, condensers and pipelines is of paramount importance for the design and optimization of refrigerant, air- conditioning and heat pump systems. The methods which are used to enhance the heat transfer will often increase the pressure drop too. One of these methods is using tube inserts like twisted tapes, brushes, and coiled wires. Due to low cost and their capability for easy installing or removing inside the tubes (for cleaning purposes), the coiled wire inserts usage is growing. The coiled wire insert causes increase in both heat transfer and pressure drop; therefore, the calculation of pressure drop in such systems is of vital importance. Some researchers have studied two-phase flow heat transfer and pressure drop during forced convective conden- sation in horizontal tubes with inserts. Kumar et al. (2005) studied heat transfer enhancement during condensation of R-22 inside a horizontal twisted tape inserted tube. Hejazi et al. (2010) studied the condensation of R-134a in horizontal tubes equipped with twisted tapes and developed a new cor- relation for prediction of pressure drop. Salimpour and * Corresponding author. Tel.: þ98 311 3915210; fax: þ98 311 3912628. E-mail address: [email protected] (M.R. Salimpour). www.iifiir.org Available online at www.sciencedirect.com ScienceDirect journal homepage: www.elsevier.com/locate/ijrefrig international journal of refrigeration 40 (2014) 24 e30 0140-7007/$ e see front matter ª 2013 Elsevier Ltd and IIR. All rights reserved. http://dx.doi.org/10.1016/j.ijrefrig.2013.10.013

Upload: hesam

Post on 30-Dec-2016

215 views

Category:

Documents


3 download

TRANSCRIPT

nline at www.sciencedirect.com

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 0 ( 2 0 1 4 ) 2 4e3 0

Available o

www. i ifi i r .org

ScienceDirect

journal homepage: www.elsevier .com/locate/ i j refr ig

Effect of inserting coiled wires on pressure dropof R-404A condensation

Mohammad Reza Salimpour*, Hesam Gholami

Department of Mechanical Engineering, Isfahan University of Technology, Isfahan 84156-83111, Iran

a r t i c l e i n f o

Article history:

Received 3 June 2013

Received in revised form

12 October 2013

Accepted 27 October 2013

Available online 7 November 2013

Keywords:

Pressure drop

Turbulator

R-404A

Condensation

* Corresponding author. Tel.: þ98 311 391521E-mail address: [email protected] (M

0140-7007/$ e see front matter ª 2013 Elsevhttp://dx.doi.org/10.1016/j.ijrefrig.2013.10.013

a b s t r a c t

In this study, an experimental investigation was carried out to determine the increase of

pressure drop during convective condensation of R-404A vapor inside coiled wire inserted

tubes. Experiments were performed for a plain tube and five coiled wire inserted tubes.

Data were collected for four mass velocities. For each mass velocity, six different vapor

qualities were considered. From the results, it is found that the coiled wire inserts

increased the pressure drop up to 1200% compared to plain tube values. An empirical

correlation is also developed to predict the pressure drop of coiled wire inserted tubes

during R404-A condensation with accuracy of �20%.

ª 2013 Elsevier Ltd and IIR. All rights reserved.

Effet de l’insertion de fils torsades sur la chute de pression decondensation de R404A

Mots cles : Chute de pression ; Turbulateur ; R404A ; Condensation

1. Introduction

Accurate prediction of two-phase flow pressure drop in

evaporators, condensers and pipelines is of paramount

importance for the design and optimization of refrigerant, air-

conditioning and heat pump systems. Themethods which are

used to enhance the heat transfer will often increase the

pressure drop too. One of these methods is using tube inserts

like twisted tapes, brushes, and coiled wires. Due to low cost

and their capability for easy installing or removing inside the

tubes (for cleaning purposes), the coiled wire inserts usage is

0; fax: þ98 311 3912628..R. Salimpour).ier Ltd and IIR. All rights

growing. The coiled wire insert causes increase in both heat

transfer and pressure drop; therefore, the calculation of

pressure drop in such systems is of vital importance.

Some researchers have studied two-phase flow heat

transfer and pressure drop during forced convective conden-

sation in horizontal tubes with inserts. Kumar et al. (2005)

studied heat transfer enhancement during condensation of

R-22 inside a horizontal twisted tape inserted tube. Hejazi

et al. (2010) studied the condensation of R-134a in horizontal

tubes equipped with twisted tapes and developed a new cor-

relation for prediction of pressure drop. Salimpour and

reserved.

Nomenclature

x vapor quality

d diameter, m

e wire diameter, mm

L length of test section, mm

p coil pitch, mm

f friction factor

Re Reynolds number

Y2 gas to liquid pressure gradient ratio

G mass velocity, kg(m2 s)�1

P Pressure, Pa

Greek symbol

a helix angle

ε void fraction

m dynamic viscosity, Pa s

r density, kg m�3

F2Ch Chisholm two phase multiplier

Subscripts

in inlet

G vapor

L liquid

out outlet

i n t e rn a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 0 ( 2 0 1 4 ) 2 4e3 0 25

Yarmohammadi (2012a, 2012b) reported both enhanced heat

transfer and increased pressure drop of twisted tape inserted

tubes during condensation of R-404A, experimentally. They

observed that the insertion of twisted tape inside horizontal

tubes increases the condensing pressure drop up to 239%

compared to plain tubes on a nominal area basis.

Agrawal et al. (1998) used coiled wires to augment heat

transfer coefficient in condensation of R-22 vapor. Akhavan-

Behabadi et al. (2005, 2008) performed two experimental

studies on heat transfer enhancement and pressure drop

increase of R-134a condensation inside horizontal tubes

with spring inserts. They observed that the insertion of

helically coiled wires inside horizontal tubes augments the

pressure loss from 260% to 1600% compared to the plain

tube values.

Despite the large amount of research devoted to the effect

of tube inserts on the condensation pressure drop, it is noted

that only a limited number of studies have been carried out on

R-404A condensation. Moreover, it is noteworthy that there is

no investigation on the effect of the coil inserts on the pres-

sure drop of this kind of refrigerant. R-404A is a non-

azeotropic and zero ODP refrigerant designed to serve as a

long-term alternative to R-502 and R-22 in low and medium

temperature commercial refrigeration applications. Due to

the increasing application of R-404A in different systems the

present experimental workwas conducted to assess the effect

of inserting coiled wires on the pressure drop during

condensation of R-404A in horizontal tubes.

Fig. 1 e Schematic vie

2. Experimental setup

The schematic view of the experimental setup is illustrated in

Fig. 1. Test section is a double pipe counter-flow heat

exchanger. Refrigerant flows inside inner tube while cold

water flows in counter flow through annulus. The internal

tube is made of copper with 14.1 mm ID and 0.9 mm thickness

and 1.00 m length. The outer carbon steel tube is insulated

with glass wool to minimize heat loss to surrounding. Using J-

type thermocouples with precision of 0.1 �C, outside wall

temperature of the inner tube of test section is measured at

four locations. At each location, at the top, sides and bottom of

the tube, the sensors were used in order to achieve the lon-

gitudinal and circumferential temperature distribution of the

tube wall. The average value of four circumferential readings

is taken at each longitudinal location. The cooling water

temperatures are measured at inlet and outlet of test and pre-

condensers with the same accuracy. Refrigerant absolute

pressure is measured by pressure gauge at three locations: at

the inlet of pre-condenser and at the inlet and outlet of the

test condenser with precision of 0.1 kPa. Pressure drop be-

tween the inlet and outlet of the test condenser is measured

by differential pressure transmitter which is calibrated in the

range of 0e7.4 kPa with accuracy of 3 Pa. Pre-condenser is

used to obtain the desirable range of vapor quality at the test

condenser inlet by regulating the pre-condenser coolingwater

flow rate. Refrigerant temperature ismeasured at the inlet and

w of the set-up.

Table 2 e Range of operating parameters of theexperiments.

Parameters Range

Refrigerant mass velocity 71.2e142.4 kg (m2 s)�1

Average condensing temperature 27.8e33.2 �CAverage cooling heat flux 4.33e15 kW m�2

Cooling water mass flow rate 0.036e0.122 kg s�1

Inlet temperature of cooling water 12e13.5 �CCooling water temperature increase 1.1e5.0 �CInlet vapor quality 0.2e0.82

Table 1 e Characteristic parameters of the coiled wires.

Tube set di (mm) do (mm) de (mm) L (mm) p (mm) e (mm) a (degree)

A 14.1 15.9 11.9 1000 10 0.5 73

B 14.1 15.9 10.4 1000 10 1 73

C 14.1 15.9 9.1 1000 10 1.5 73

D 14.1 15.9 8.4 1000 8 1.5 77

E 14.1 15.9 9.9 1000 13 1.5 69

F 14.1 15.9 e 1000 Plain Plain e

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 0 ( 2 0 1 4 ) 2 4e3 026

outlet of pre-condenser. Leaving the refrigerant from the test

condenser, it is cooled down to sub-cooled liquid using a

secondary condenser. The secondary condenser is actually

used to deliver completely condensed refrigerant to the rota-

meter. The pre- and secondary condensers are insulated by

glass wool to minimize heat loss to surrounding. Two appro-

priate calibrated rotameters with flow ranges of 0e15 L min�1

and accuracy of 0.1 L min�1 are used to measure the cooling

water flow rate through the pre- and test condensers. A cali-

brated rotameter with the range of 30e100 L h�1 and accuracy

of 10 L h�1 installed downstream of the secondary condenser

is used to measure the refrigerant mass flow rate. Character-

istic parameters of the used coiled wires such as thickness, e,

coil pitch, p, tube length, L, internal tube diameter, di, and

external tube diameter, do, are given in Table 1. Moreover,

geometrical parameters of the coils are illustrated in Fig. 2.

3. Data collection

In this experimental study, 150 test runs were conducted to

measure the pressure drop during the condensation of R-404A

vapor with five refrigerant mass velocities, 71.2, 89, 106.8, 124.6

and 142.4 kg(m2 s)�1 and different vapor qualities inside plain

tube and tubes with coiled wire inserts. To have a reasonable

comparison among different geometries, mass velocities are

calculated based on the plain tube case. The range of operating

conditions is given in Table 2. At first, data were collected for

condensation of R-404A vapor inside plain tube. Plain tube data

were collected in order to verify integrity of the experimental

setup and to have a reference data for contrasting the perfor-

mance of different coiled wire inserts. After that, data were

collected for condensation of R-404A vapor inside coiled wire

inserted tubes. The vapor qualitywasmeasured at the inlet and

outlet of test condenser by performing energy balance along

the pre- and test condensers, respectively. It was noted that

since the changes of vapor quality throughout the test

condenser were less than 0.2, vapor quality was assumed to be

the average of these two values.

The uncertainty of the measured refrigerant mass velocity

and saturation temperature were less than 4.5% and 0.5 �C,respectively; while, the uncertainty of the measured total

pressure drop was less than 1.5 Pa.

Fig. 2 e Dimensional parameters of the coils.

4. Results and discussion

4.1. Plain tube results

Fig. 3 shows the variation of pressure drop at different vapor

qualities for plain tube. From this figure, it is revealed that

with increasing mass flow rate and vapor quality, pressure

drop grows. The reason lies in this fact that higher mass ve-

locity augments turbulence intensity in the liquid film and

vapor core which results in the increase of shear stress. Also,

higher vapor quality enhances the vapor core volume. Hence,

vapor core velocity causes more velocity difference between

vapor core and liquid film. To validate the experimental set-

up, the plain tube pressure drop results were compared with

an existing correlation.

Fig. 3 e Frictional pressure drop variations with vapor

quality for plain tube.

i n t e rn a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 0 ( 2 0 1 4 ) 2 4e3 0 27

The experimental pressure drop is calculated as the sum of

static, momentum and frictional pressure drops as,

DPtot ¼ DPfric þ DPmom þ DPsta (1)

For horizontal tube, DPsta ¼ 0; hence,

DPtot ¼ DPfric þ DPmom (2)

Momentum pressure drop is obtained from the following

correlation (Collier and Thome, 1994).

DPmom ¼ G2total

("ð1� xÞ2rLð1� εÞ þ

x2

rGε

#out

�"ð1� xÞ2rLð1� εÞ þ

x2

rGε

#in

)(3)

where, Gtotal, x and ε are total mass velocity, vapor quality and

void fraction, respectively. Void fraction is calculated from

Steiner (1993) version of Rouhani’s (1969) correlation as

follows.

ε¼ xrG

(½1þ0:12ð1�xÞ�

�xrG

þ1�xrL

�þ1:18ð1�xÞ½gsðrL�rGÞ�0:25

Gtotalr0:5L

)�1

(4)

Frictional pressure drop is achieved from subtracting the

momentum pressure drop from the experimental data. From

the experiments it is seen that the ratio of the calculated

momentum pressure drop to the total measured pressure

drop range is 5e12%.

The results for the plain tube are then compared with the

predicted values from correlations proposed by Friedel (1979),

Lockhart and Martinelli (1979), Gronnerud (1972), Chisholm

(1973) and Muller-Steinhagen and Heck (1986); and it is

found that the present experiment is best agreed with the

proposed correlation by Chisholm (1973). As is seen from

Fig. 4, this correlation predicts the experimental pressure drop

of present study within error band of �20%. The Chisholm

correlation to calculate the frictional pressure drop is:

Fig. 4 e Comparison of the plain tube experimental

frictional pressure losses with the values predicted by

Chisholm correlation.

�dpdz

�¼

�dpdz

�F2

Ch (5)

frict L

where,F2Ch is Chisholm two-phase flow correlation factor

defined as

f2ch ¼ 1þ �

Y2 � 1�hBx

ð2�nÞ=2ð1� xÞð2�nÞ=2 þ x2�ni

(6)

In Eq. (6), n ¼ 0.25, B ¼ 4.8, and Y is calculated from liquid

and gas frictional pressure drop gradients as

Y2 ¼ ðdp=dzÞGðdp=dzÞL

(7)

where,

�dpdz

�L

¼ fL2G2

total

dirL(8)

and

�dpdz

�G

¼ fG2G2

total

dirG(9)

As coiled wires turbulate the flow, single-phase friction

factors are defined as,

fL ¼ 0:079

Re0:25L

; fG ¼ 0:079

Re0:25G

(10)

where,

ReL ¼ Gtotaldi

mL

; ReG ¼ Gtotaldi

mG

(11)

4.2. Coiled wire inserted tubes results

It is observed that by using coiled wires inside horizontal

tubes, pressure drop is increased. The amount of this increase

depends on the mass velocity, vapor quality and geometric

dimensions of coiled wire inserts. Figs. 5e7 show the varia-

tions of pressure drop versus vapor quality for tubes with

Fig. 5 e Variation of frictional pressure loss with vapor

quality for tube set ‘A’.

Fig. 6 e Variation of frictional pressure loss with vapor

quality for tube set ‘B’.

Fig. 8 e Variation of frictional pressure loss with vapor

quality for tube set ‘D’.

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 0 ( 2 0 1 4 ) 2 4e3 028

coiledwire inserts of 10mmpitch and 0.5, 1.0 and 1.5mmwire

diameter, respectively. Considering these figures, it is

concluded that the increase of pressure drop is due to the

increase of coiled wire diameter. For example, tube set C

which holds the thickest coiled wire has the highest pressure

drop compared to other tube sets. Akhavan-Behabadi et al.

(2008) referred this trend to the fact that the rise in wire

thickness increases the frictional surface which results in

more frictional pressure loss. Also, thicker coils promote tur-

bulence of the vapor core and liquid film which causes

increased frictional pressure loss. For these coils, momentum

pressure loss is also increased because of the increased ve-

locity resulted from reduced flow cross-section area. Figs. 7e9

present the variations of condensation pressure drop with

Fig. 7 e Variation of frictional pressure loss with vapor

quality for tube set ‘C’.

vapor quality for tubes with coiled wire inserts of 1.5 mmwire

diameter and 10, 8 and 13 mm coil pitches, respectively. From

these figures, it is seen that with reducing the coil pitch,

pressure drop increases. This trend can be explained as for

smaller coil pitches, frictional surface per length is increased

which results in higher frictional pressure drop.

Fig. 10 shows the variations of the ratio of coiled wire

inserted tube to plain tube pressure drops for different mass

velocities. From this figure, it is obvious that the ratio usually

increases with mass velocity. From this figure, it is also seen

that maximum value of pressure drop increase is occurred in

tube set D which has the thickest wire diameter and the

smallest coil pitch. The pressure drop of this tube set is

increased by about 1300% in comparison with plain tube

Fig. 9 e Variation of frictional pressure loss with vapor

quality for tube set ‘E’.

Fig. 11 e Comparison of the present experimental frictional

pressure drops with the values predicted by Eq. (15).

i n t e rn a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 0 ( 2 0 1 4 ) 2 4e3 0 29

values at mass velocity 142.4 kg (m2 s)�1. Tube set A which

exhibits the minimum increase, augments the pressure drop

by 131% in comparison to the plain tube at mass velocity 89 kg

(m2 s)�1.

5. Development of a correlation

Literature review on forced condensation of refrigerant

revealed the need for a suitable correlation to predict the

condensation pressure drop of R-404A vapor in tubes with

coiled wire inserts. To develop a new correlation, the Chis-

holm’s correlation that predicted plain tube results within the

Fig. 10 e Ratio of coiled wire inserted tube to plain tube

frictional pressure losses for different mass velocities.

error band of �20%, was used as the basic correlation to

consider the effects of coiled wire inserts. The combination of

two parameters (p/d) and (e/d) in the form of (e2/pde) was used

in the proposed relation. For this purpose, the following form

of functional relationship which was previously proposed by

Akhavan-Behabadi et al. (2008) is used,

DPc=DPs ¼�c1 þ c2

e2

pde

�c3

(12)

where DPs and DPc are total pressure drops in plain tube and

coiled wire inserted tube, respectively and de is equivalent

diameter calculated as follows,

de ¼�d2 � ge

��ðdþ gÞ (13)

where,

g ¼ peðd� eÞ=ðp sinaÞ (14)

In Eq. (14), a is coil helix angle. The following correlation is

derived by using least square regression analysis to predict

the present experimental data of coiled wire inserted tubes:

DPc=DPs ¼�2þ 450

e2

pde

�0:81

(15)

Fig. 11 contains a comparison between the data predicted

by our proposed correlation and experimental data of pres-

sure drop. From this figure, it is observed that this correlation

predicts the experimental data within an error band of �20%.

6. Conclusions

From the present investigation, the following conclusions can

be drawn.

1. The insertion of coiled wire inside horizontal tubes causes

increase of condensing pressure drop up to 1300%

compared to plain tube values.

2. Pressure drop is increased with the increase of coiled wire

diameter.

3. It is also seen that with reducing the coil pitch, pressure

drops more.

4. A new correlation is proposed to predict the forced

convective condensation pressure drop of R-404A inside

horizontal coiled wire inserted tubes.

Acknowledgment

The authors wish to acknowledge Isfahan University of

Technology for its financial support for the setup construction

and implementing this research.

r e f e r e n c e s

Agrawal, K.N., Kumar, A., Akavan-Behabadi, M.A., Varma, H.K.,1998. Heat transfer augmentation by coiled wire inserts during

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 0 ( 2 0 1 4 ) 2 4e3 030

forced convection condensation of R-22 inside horizontaltubes. Int. J. Multiphase Flow 24, 635e650.

Akhavan-Behabadi, M.A., Salimpoor, M.R., Kumar, R.,Agrawal, K.N., 2005. Augmentation of forced convectioncondensation heat transfer inside a horizontal tube usingspiral spring inserts. J. Enhanc. Heat Transfer 12, 373e384.

Akhavan-Behabadi, M.A., Salimpour, M.R., Pazouki, V.A., 2008.Pressure drop increase of forced convective condensationinside coiled wire inserted tube. Int. Commun. Heat MassTransfer 35, 1220e1226.

Chisholm, D., 1973. Pressure gradients due to friction during theflow of evaporating two-phase mixtures in smooth tubes andchannels. Int. J. Heat Mass Transfer 16, 347e358.

Collier, J.G., Thome, J.R., 1994. Convective Boiling andCondensation, third ed. Oxford University Press.

Friedel, L., 1979. Improved friction pressure drop correlation forhorizontal and vertical two-phase pipe flow. In: EuropeanTwo-phase Flow Group Meeting, Ispra, Italy. Paper E2.

Gronnerud, R., 1972. Investigation in Liquid Holdup, FlowResistance and Heat Transfer in Circular Type Evaporators,Part IV: Two-phase Resistance in Boiling Refrigerants. Bulletinde l’Hnst. Du Froid, Annexe.

Hejazi, V., Akhavan-Behabadi, M.A., Afshari, A., 2010.Experimental investigation of twisted tape inserts

performance on condensation heat transfer enhancementand pressure drop. Int. Commun. Heat Mass Transfer 37,1376e1387.

Kumar, R., Agrawal, K.N., Lal, S.N., Varma, H.K., 2005. Anexperimental study on condensation enhancement of R-22 bythe turbulence promoter. ASHRAE Trans. 111, 18e25.

Lockhart, R.W., Martinelli, R.C., 1979. Proposed correlation datafor isothermal two-phase two-component flow in pipes.Chem. Eng. Prog. 45, 39e45.

Muller-Steinhagen, H., Heck, K., 1986. A simple friction pressuredrop correlation for two-phase flow in pipes. Chem. Eng.Process. 20, 297e308.

Rouhani, Z., 1969. Subcooled Void Fraction, AB AtomenergiSweeden. Internal Rept. AE-RTV841.

Salimpour, M.R., Yarmohammadi, S., 2012a. Effect of twisted tapeinserts on pressure drop during R-404A condensation. Int. J.Refrigeration 35, 263e269.

Salimpour, M.R., Yarmohammadi, S., 2012b. Heat transferenhancement during R-404A vapor condensation in swirlingflow. Int. J. Refrigeration 35, 2014e2021.

Steiner, D., 1993. VDI-Warmeatlas (VDI Heat Atlas). VereinDeutscher Ingenieure, VDI Gesellschaft Verfahrenstechnikund Chemieingenieurwesen (GVC), Dusseldorf. Chapter Hbb.