effective energy management
DESCRIPTION
Effective Energy Management. Effective Energy Management. Develop baseline Identify and quantify savings opportunities Measure and benchmark to sustain efforts. 1. Energy Use Baseline. Billing analysis How energy is priced Plant energy balance Where energy is used - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/1.jpg)
Effective Energy Management
![Page 2: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/2.jpg)
Effective Energy Management
1. Develop baseline
2. Identify and quantify savings opportunities
3. Measure and benchmark to sustain efforts
![Page 3: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/3.jpg)
1. Energy Use Baseline
–Billing analysis• How energy is priced
–Plant energy balance• Where energy is used
– Lean energy analysis (LEA)• What drives changes in energy use
![Page 4: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/4.jpg)
Utility Bill Analysis
Analyze rate schedule Verify billing amounts Check for saving
opportunities:– Primary/secondary– Power factor correction– Meter consolidation– Demand reduction
potential Benchmark costs
0
200
400
600
800
1,000
1,200
1,400
1,600
1,800
1/24/0
2
2/25/0
2
3/25/0
2
4/25/0
2
5/24/0
2
6/25/0
2
7/25/0
2
8/26/0
2
9/25/0
2
10/24
/02
11/22
/02
12/23
/02
1/24/0
3
2/24/0
3
3/25/0
3
4/24/0
3
5/23/0
3
6/24/0
3
7/25/0
3
8/26/0
3
Actu
al D
eman
d (k
W)
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
Cons
umpt
ion
(kW
h/da
y)
Actual Demand (kW) Consumption (kWh/day)
0
20
40
60
80
100
120
140
160
3/6/02
4/6/02
5/6/02
6/6/02
7/6/02
8/6/02
9/6/02
10/6/
02
11/6/
02
12/6/
021/6
/032/6
/033/6
/034/6
/035/6
/036/6
/037/6
/038/6
/03
Cons
umpt
ion
(ccf
/day
)
![Page 5: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/5.jpg)
Plant Energy Balance
Equipment Rated Power Frac Loaded Oper Hours Elec Use(hr/yr) (kWh/yr)
AC #1 50 hp 90% 5,000 187,500Lights 10 kW 100% 6,000 60,000… … … … …Other 10,000
Utility Bill Total = 257,500
Equipment Rated Input Frac Loaded Oper Hours Gas Use(Btu/hr) (hr/yr) (MBtu/yr)
Boiler 1 1,000,000 70% 5,000 3,500Make Up #1 500,000 100% 2,000 1,000… … … … …Other 500
Utility Bill Total = 5,000
1) Estimate energy use from:
• rated power• frac loaded• operating hours
2) Calibrate sum against measured total energy use
![Page 6: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/6.jpg)
Energy Use Breakdowns by Equipment
0% 12% 24% 36% 48% 60%
Vacuum PumpsProcess Blowers/Fans
LightingDust Collectors
SandersOther Process Motors
Air CompressorsProcess Heating
Other
20%
18%17%
12%12%
8%6%
5%
2%
Estimated Electrical Use Breakdown
![Page 7: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/7.jpg)
Lean Energy Analysis
Understand what drives changes in Energy
Quantify “Waste” and “Lean”
Model: Energy = a + b Production + c Weather
![Page 8: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/8.jpg)
Source Data
Date Elec (kWh/dy) Nat Gas (mcf/dy) Prod (units/dy) Toa (F)1/31/2002 76,127 590 13,065 34.72/28/2002 80,564 581 13,557 34.73/31/2002 77,362 542 12,401 39.44/30/2002 81,712 418 14,086 53.55/31/2002 80,059 348 14,181 58.66/30/2002 90,094 298 13,439 72.57/31/2002 86,361 287 10,551 77.48/31/2002 89,326 341 14,239 75.89/30/2002 95,441 348 13,830 69.710/31/2002 82,779 434 12,693 51.511/30/2002 77,639 535 12,977 39.612/31/2002 61,288 518 9,982 30.7
![Page 9: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/9.jpg)
Actual Temperature Data
http://academic.udayton.edu/kissock
![Page 10: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/10.jpg)
Plot Fuel vs Toa
![Page 11: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/11.jpg)
Model Fuel Use vs Toa: 3PH
R2 = 0.92
HS
Find
Tcp
![Page 12: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/12.jpg)
Model Fuel Use vs Production: 2P
R2 = 0.02 Prod Slope Negative
![Page 13: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/13.jpg)
Model Fuel Use vs Toa and Prod: 3PH-MVR
R2 = 0.97 Prod Slope = Positive
![Page 14: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/14.jpg)
Disaggregate Fuel Use
Weather = 28%
Production = 58%
Independent = 14%
Temperature
Fuel
![Page 15: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/15.jpg)
Model Electricity vs Toa: 3PC
R2 = 0.67
![Page 16: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/16.jpg)
Model Electricity vs Production: 2P
R2 = 0.32
![Page 17: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/17.jpg)
Model Electricity vs Toa and Prod: 3PC-MVR
R2 = 0.82
![Page 18: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/18.jpg)
Disaggregate Electricity Use
Weather = 10%
Production = 39%
Independent = 51%
Temperature
Electricity
![Page 19: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/19.jpg)
Lean Energy Analysis
Called “Lean Energy Analysis” because of synergy with “Lean Manufacturing”.
In lean manufacturing, “any activity that does not add value to the product is waste”.
Similarly, “any energy that does not add value to a
product or the facility is also waste”.
![Page 20: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/20.jpg)
Quantified “Leaness” of Fuel Use
Weather28%
Production58%
Independent14%
“Independent” is a metric of energy not added to productFuel LEA = %Production + %Weather
Fuel LEA = 86%
![Page 21: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/21.jpg)
Quantified “Leaness” of Electricity Use
Production39%
Independent51%
Weather10%
“Independent” is a metric of energy not added to productElectricity LEA = %Production + %Weather = 49%
Electricity LEA = 49%
![Page 22: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/22.jpg)
Average LEA Scores (%P+%W)(28 Manufacturing Facilities)
39%
58%
![Page 23: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/23.jpg)
Use Lean Energy Analysis To Discover Savings Opportunities
LEA Indicators of Savings Opportunities– High “Independent” indicates waste– Departure from expected shape– High scatter indicates poor control
![Page 24: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/24.jpg)
Low Electric LEA = 24%Indicates Operating Opportunities
![Page 25: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/25.jpg)
Low Fuel LEA Identifies Insulation Opportunities
![Page 26: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/26.jpg)
High Heating Slope Identifies Heating Efficiency / Insulation Opportunities
![Page 27: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/27.jpg)
High Data Scatter Identifies Control Opportunities
Heating Energy Varies by 3X at Same Temp!
![Page 28: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/28.jpg)
Departure From Expected Shape Identifies Malfunctioning Economizers
Air conditioning electricity use should flatten below 50 F Audit found malfunctioning economizers
![Page 29: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/29.jpg)
Lean Energy Analysis
Quick but accurate disaggregation of energy use: – Quantifies the energy not adding value to product or
the facility– Helps identify savings opportunities– Provides an accurate baseline for measuring the
effectiveness of energy management efforts over time.
![Page 30: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/30.jpg)
2. Identify and Quantify Saving Opportunities
Identifying energy savings– Use “Integrated Systems + Principles Approach (ISPA)– ISPA is effective and thorough
Quantifying energy savings– Requires competent engineering– May warrant energy audit– May consider energy savings performance contract (ESPC)
![Page 31: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/31.jpg)
Prioritize Saving Opportunities
Multiple filters– Financial return on investment
• Rank versus other energy saving opportunities• Rank versus other requests for capital• Risk
– Consistent with other priorities– Available and knowledgeable staff to manage project
![Page 32: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/32.jpg)
Implement Savings Opportunities
Management commitment Operator and maintenance education and buy in
![Page 33: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/33.jpg)
3. Measurement and Benchmarking
Sustaining energy efficiency efforts requires that effectiveness of past efforts be accurately evaluated. – Verify the performance of past energy-efficiency efforts– Inform the selection of future energy-efficiency initiatives– Help develop energy-efficiency targets
Measurement – Extend LEA with sliding NAC and EI to measure energy
efficiency improvement Benchmarking
– Compare NAC and EI for inter-facility benchmarking
![Page 34: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/34.jpg)
Normalized Energy Intensity
1) Characterize performance with ‘Energy signature’ model
2) Remove noise with ‘Normalized annual consumption’ NAC
3) Track performance with ‘Sliding NAC’ analysis
4) Benchmark performance with ‘Multi-site sliding NAC’ analysis
![Page 35: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/35.jpg)
Raw Energy and Production Data
![Page 36: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/36.jpg)
Normalized Energy Intensity
![Page 37: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/37.jpg)
Benchmark NEI vs. Multiple Facilities
Smallest Energy Users
Biggest Energy Decrease
Biggest Energy Increase
Biggest Energy Users
DNEI
NEI
![Page 38: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/38.jpg)
Case Study: Turn off Make-up Air Units During Non-Production Hours
Baseline Post-retrofit
Heating Slope Decreases by 50%
![Page 39: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/39.jpg)
Sliding NEI
Fuel NEI decreased by 23%
Independent of weather/production changes
![Page 40: Effective Energy Management](https://reader035.vdocument.in/reader035/viewer/2022062410/56816213550346895dd23ed2/html5/thumbnails/40.jpg)
Summary: Effective Energy Management
Develop baseline– Plant energy balance– Lean energy analysis (LEA)
Take action – Identify and quantify energy saving opportunities– Prioritize energy saving opportunities– Implement energy saving opportunities
Measure and benchmark to sustain efforts– Develop metrics for system energy efficiency– Measure energy efficiency improvement with sliding NAC and EI– Compare energy efficiency between facilities with NAC and EI