el udriver lcu 100w 12v ip67 exc excite series - wlk 2 data sheet 02/15-lc139-0 c specific technical...
TRANSCRIPT
-
www.tridonic.com 1Subject to change without notice.Data sheet 02/15-LC139-0
LED DriverConstant voltage
EL
Product description
•ConstantvoltageLEDDriver
•Universalinputvoltagerange
•Constantoutputvoltage
•Connection:Cablewithendsleeves(lengthapprox.500mm)
•Polarityidentifiers,secondary+red/–black
•Metalcasing,encapsulated
•Nominallife-timeupto50,000h(atta50°Cwithafailurerate
max.0.2%per1,000h)
•5-yearguarantee
•SuitableforemergencyinstallationsaccordingtoEN50172
•ComplieswithCLASSCfromminimumtomaximumloadrange
accordingtoEN61000-3-2
Properties
•Smalldesign
•Highefficiency
•Lowpowerloss
•Overtemperatureprotectionwithautomaticrestart
•Overloadprotection
•Short-circuitprotectionwithautomaticrestart
•SELV
•TypeofprotectionIP67
•Metalcasing
Technical dataRatedsupplyvoltage 120–277V
Inputvoltage,AC 108–305V
Inputvoltage,DC 176–288V
Ratedcurrent12V(at230V,50Hz,fullload) 0.51A
Mainsfrequency 0/50/60Hz
Efficiency(at230V,50Hz,fullload) >90%
λ(at230V,50Hz,fullload) 0.95
Outputvoltagetolerance12V -0/+10%
Outputpower12V(ta≤60°C) 100W
Outputpower12V(ta>60°C) 80W
Outputpowerrange12V 10–100W
Turnontime(output) ≤0.5s
Turnofftime(output) ≤1s
Holdontimeatpowerfailure(Output) 10ms
Ambienttemperatureta -40...+70°C
Ambienttemperatureta(atlife-time50,000h) -40...+50°C
Storagetemperaturets -40...+85°C
DimensionsLxWxHfor12V 270x40x23mm
HolespacingD 257mm
Udriver LCU 100W 12V IP67 EXCEXCITEseries
270,0
257,0252,0
18,0
4,2
40
23
LCU100W12VIP67TOP
Ordering dataType Article number Packagingcarton Packagingpallet Weightperpc.
LCU 100W 12V IP67 TOP 28000510 10pc(s). 360pc(s). 0.56kg
-
www.tridonic.com 2Subject to change without notice.Data sheet 02/15-LC139-0
LED DriverConstant voltage
Specific technical dataType Max.casingtemperaturetc Outputvoltage Max.inputpower Outputcurrentrange Max.outputvoltage1
LCU 100W 12V IP67 TOP 95°C 12V 117W 0.83–8.33A 13.2V1 Atfailuremode(230V,50Hz).
-
www.tridonic.com 3Subject to change without notice.Data sheet 02/15-LC139-0
LED DriverConstant voltage
StandardsEN55015EN60598-1EN60598-2-22EN61000-3-2EN61000-3-3EN61347-1EN61347-2-13EN61547EN62384EN62493Acc.toEN50172:suitabelforcentralbatterysystems
Wiring diagram Connection
Primarycable
Secondarycable
L N + –
brown blue red black
Overload protectionAutomaticshutdownoftheLEDDriverifthemaximumoutputcurrentisexceeded.Automaticrestartiftheoutputcurrentisbelowthelimit.
Over temperature protectionAutomaticshutdownoftheLEDDriverifthetemperaturelimitisexceeded.Automaticrestartifthetemperaturefallsbelowthelimit.
Maximum loading of automatic circuit breakers
Automaticcircuitbreakertype C10 C13 C16 C20 B10 B13 B16 B20 Inrushcurrent
InstallationØ 1.5mm2 1.5mm2 1.5mm2 2.5mm2 1.5mm2 1.5mm2 1.5mm2 2.5mm2 Imax time
LCU 100W 12V IP67 TOP 6 7 9 12 9 12 15 19 51.5A 99µs
PRI:Ø7.7±0.2mm;2x1.04mm2(17AWG)
SEC:LCU100W12VIP67TOP:Ø8.7±0.2mm;2x2.08mm2(14AWG)
Harmonic distortion in the mains supply (at 230 V / 50 Hz and full load) in %Type THD 3 5 7 9 11
LCU 100W 12V IP67 TOP 10 3 2 2 2 1
No-load operationTheLEDDriverisnotdamagedinno-loadoperation.Themax.outputvoltage(seepage1)canbeobtainedduringno-loadoperation.
Umodule+–LCU ... IP67 TOP
L~N
+–
120–277 VACLN
838
500
Expected life-timeType Outputvoltage ta 40 °C 50 °C 60 °C
LCU 100W 12V IP67 TOP 12Vtc 60°C 70°C 80°CLife-time >100,000h >50,000h >25,000h
Installation instructionsTheswitchingofLEDsonsecondarysideisnotpermitted.AproperfunctioningoftheLCUincombinationwiththirdpartydimmingdevices(e.g.PWM)cannotbeguaranteed.
Short-circuit behaviourIncaseofashortcircuitonthesecondaryside(LED)theLEDDriverswitchesintohiccupmode.Afterremovaloftheshort-circuitfaulttheLEDDriverwillrecoverautomatically.
-
www.tridonic.com 4Subject to change without notice.Data sheet 02/15-LC139-0
LED DriverConstant voltage
THDvsload
0
8
4
16
20
55 80 85 90 9570 7560 65 100
12
Load [%]
THD
[%]
Efficiencyvsload
80
82
84
86
88
90
55 70 75 80 85 90 9560 65 100
92
Load [%]
E�ci
ency
[%]
Powerfactorvsload
Diagrams for 12 V
0,900,910,920,930,940,950,960,970,980,991,00
55 70 75 80 85 90 9560 65 100Load [%]
Pow
er fa
ctor
Additional information
Additionaltechnicalinformationatwww.tridonic.com→TechnicalData
Guaranteeconditionsatwww.tridonic.com→Services
Nowarrantyifdevicewasopened.
Isolation and electric strength testing of luminairesElectronicdevicescanbedamagedbyhighvoltage.Thishastobeconsideredduringtheroutinetestingoftheluminairesinproduction.
AccordingtoIEC60598-1AnnexQ(informativeonly!)orENEC303-AnnexA,eachluminaireshouldbesubmittedtoanisolationtestwith500VDCfor1second.Thistestvoltageshouldbeconnectedbetweentheinterconnectedphaseandneutralterminalsandtheearthterminal.Theisolationresistancemustbeatleast2MΩ.
Asanalternative,IEC60598-1AnnexQdescribesatestoftheelectricalstrengthwith1500VAC(or1.414x1500VDC).Toavoiddamagetotheelectronicdevicesthistestmustnotbeconducted.