electrical (e1)
DESCRIPTION
ElectricalTRANSCRIPT
1TOSHIBA MACHINE CO., LTD
DC 500 CL-T
2
PREFACE Electricity is essentially invisible. When the electricity flows in electric wires, it turns on electric lights,
drives, motor, and warms up nichrome wires. We know the great energy of electricity but have little knowledge about electricity. Unfortunately, most people are apt to give up getting to know electricity. However, change your mind about electricity, which you have believed to be difficult, and make positive maintenance management. A little knowledge about electricity enables you to maintain machines increasing the operation rate.
The following explains the fundamentals of electricity for die casting machine :
1. THEORY OF ELECTRICITY
(1) CurrentIf you connect a dry cell and a light bulb using a copper wire as shown below, electricity flows in the direction from the positive terminal (+) to the negative (-). To take water as an example for the glowing from the positive terminal (+) to the negative terminal (-), water flowing from high level to a low level is called a water flow. Similarly, electricity flows from high electric charge level to a low level. This is called a current, which expressed with the symbol A (ampere).
(2) VoltageThe potential difference between the positive (+) and negative (-) terminals before they are connected by an electric wire is called a voltage, which is expressed with the symbol V (volt).
(3) ResistanceWhile the current is flowing from the positive terminal (+) to the negative terminal (-), it encounters the light bulb which is an obstacle between them. The obstacle is called resistance, which is expressed with the symbol Ω (ohm). When a voltage of 1V is applied for flowing a current of 1A, the value of resistance is 1Ω.
(4) Ohm’s lawA ---------- Ampere V ---------- Volt R --------- OhmA = V / R ------ Formula 1 V = A X R ----- Formula 2 R = V / A ----- Formula 3The above are the fundamental electricity.Example 1: When a voltage of 100V is applied to a resistance of 20Ω, the current is obtained from formula 1 as follows:
A = 100 / 20 = 5 (A)Example 2: When a current of 2A is flowing into a resistance of 30Ω, the voltage is obtained from formula 2 as follows:
V = 30 x 2 = 60 (V)
(5) Power and quantity of powerElectricity generates heat when being used with a heater, and works as mechanical power when being used with a motor. The amount of work per unit hour is called “power”, which is expressed with the symbol W (watt). In other words, the work of 1W is the amount per unit time of work done by a current of 1A when a voltage of 1V is applied.W = VA --------- Formula 4 W = V² / R -------- Formula 5 W = A² R -------- Formula 6Example 3: If the voltage is 200V and the current is 5A, W is obtained from formula 4 as follows:
W = 200 X 5 = 1000 (W) = 1 (kW)
Dry cell1.5 V
3
If the resistance is 20Ω and the current is 5A, W is obtained from formula 6 as follows:W = 5 X 20 = 500 (W)
One hour work done by a power of 1W is counted as one unit, and the amount of work is measured in the units, which is expressed with the symbol WH (watt-hour). Horsepower (hp) can be explained just like power. The work of lifting up a weight of 1 pound by 33 000 feet for 1 minute is expressed as 1 hp. Conversion from 1hp into W is 0.746 kW. (A unit of power equal to 746 watts)
(6) Grounding ( Earth)The earth is considered as a huge conductor of which potential is zero. If we connect a charged object and the earth using an electric wire, electricity flows into the earth through the wire. This connection is called ground connection, which expressed with the symbol E or .See the grounding specifications below.A) Ground the machine through the iron base or iron core of the machine / apparatus, the control unit.B) A steel frame of the factory may be used as a grounding electrode. However never use a gas pipe or air pipe
for grounding the machine.C) The sizes of ground wires are defined depending on the main switch and the fuse capacity.Up to 50A : 3.5 mm² Up to 100A : 5.5 mm² Up to 200A : 14 mm²Up to 400A : 30 mm² Above 400A : 38 mm²
(7) Series and parallel connectionsA) Series connection of resistors
R = R1 + R2 +R3 ------ Formula 7Example 1: If R1, R2, and R3 are 10Ω, 15Ω, and 30Ω, respectively, the total resistance is obtained as follows :
R = 10 + 15 + 30 = 55 (Ω)
B) Parallel connection 1
R = ------ Formula 8
Example 1: If R1, R2, and R3 are 10Ω, 15Ω, and 30Ω, respectively, the total resistance is obtained as follows :1
R = = 5 (Ω)
(8) Frequencies of direct current and alternating currentElectricity flowing from the positive terminal (+) to the negative terminal (-) of a battery is constant free from any change. This called current, which expressed with the symbol DC.In comparison with the direct current, electricity sent to households and factory is called alternating current which expressed with the symbol AC. Positive (+) voltage and negative (-) voltage are applied alternately as shown below. This waveform is called frequency, which is expressed with the symbol Hz (hertz).
For alternating current, a voltage of up to 600V is called low voltage, a voltage of 601 to 700V is called high voltage, a voltage higher than 700V is called extra high voltage. For direct current, a voltage of up to 750V is called low voltage, and a voltage higher than 750V is called high voltage. The method of electric work is specified according to the type of voltage. However, the specification does not cover information about maintenance work for the control circuits of the machine.
1R1
1R2
1 R3+ +
110
115
130+ +
R1
R3
R2
R1 R3R2
Positive (+) potential
Negative (-) potential
1 hertz
4
2.How to read sequencer circuitsElectric control circuits are necessary for running a die casting machine.There are various electric circuits, of which main ones are relay circuits and PC (Sequencer) circuits. This chapter explain how to read the two types of electric circuits.
2.1 Comparison between Relay circuits and Sequencer circuits(1) What is a relay circuits.Below Figure is an extended connection diagram of a relay circuit (Ejector circuit). Each selector switch and the relay contact are connected through the electric wiring, and the coil of the relay or the coil of the solenoid valve is energized for getting the die casting machine to run.
6 155 7
IR
DOR
4
ET
EFR
EBR
ET
CUT
EBSOL
EFSOL
189
188
186
187
190 191
181 182 183180DOR SHFR 1CBR EFR
0BACK EJECT
EJECTOR
(1) What is a PC circuits.Below Figure is an extended connection diagram of a PC circuit. Figure 1 to 3 are hardware circuit diagrams, and figure 4 is a software circuit diagram. (Ejector circuit).The signals of the selector switches (fig. 1) and the limit switches (fig. 2) are all input into the program by the input module in order to make up the electric circuit (fig. 4). When all the conditions are satisfied, (Y04C) in the program is turned ON. When (Y04C) is turned on, the signals are output externally by the output module (Fig. 3)which energizes the solenoid valve or the like to get the die casting machine to operation.
Fig. 1 Input Module
Ejector Forward
Ejector Backward
Counter
Ejector Time
X008X100
X101
Input modulePC-0
0
1
CEF
CEB
Ejector Forward
Ejector Backward
0BACK EJECT
EJECTOR
X104
Fig. 2 Input Module
7X01A
X01B
A
B
EFL
EBL
Ejector Forward LS
Ejector Backward LS
X01
Input modulePC-0
EFLS
EBLS
4
5
Fig. 3 Output Module
Ejector Forward SOL
Ejector Backward SOL
EFSOL
EBSOL
Y04C
Y04D
Output modulePC-0
Y04 C
D
10
4
Fig. 4 Software Circuit
R012 AR
T141 DT
R038DOCB
R13ATEFX
T012EST00010T012
ESTX012 DOL
X01CSHFL
X1111CBL
R039EFY
Y04CEFS
R039EFY
X01AEFL
Y04DEBS
R010MR
X100CEF
X101CEB
Ejector Delay Time
Ejector Auxiliary
Ejector Forward SOL
2-2 How to read Basic Circuits(1) Relay Circuits Series Connection
W
PB1 PB 2 PB 1
PB 2
SL-1
SL-1
The lamp (SL-1) goes on only when you pressed the push buttons (PB1) and (PB2) concurrently. The lampGoes off when you release either one of the push button.
Parallel connection
W
PB 1
PB 2
PB 1
PB 2
SL-1
SL-1
The lamp (SL-1) goes on when you pressed either one of the push button (PB1) or (PB2)
6
Self –holding circuit.
PB1 PB 2
R 1
R 1
Self-holding contact after coil R1 ON
PB 1
R1
PB2
Interlock circuit.When the circuit of higher priority is turned ON, other circuit are opened and cannot be operated on.
R1
PB 1
R 1
R2
R 2
PB 2
R 2PB 1
R1
PB2
R2
Priority Circuit
The relay (R1) is turned on when you press the push button (PB1). In series connection, (R1) is turned off whenYou release (PB1). By connecting the push button (PB1) in parallel with contact A of (R1), (R1) remains on evenIf you release (PB1).
When you turn on a high priority circuit, the other circuit opens and is unable to work. The relay (R1) is turned onwhen you press the push button (PB1) and (PB2) remains on through the self holding feature. However when youpress the push button (PB2), the relay (R2) is turned on, and the contact B of (R2) on the circuit of (R1) opens.As a result (R1) is turn off. (R2) remains through the self holding feature. Even if you press the push button (PB1)Again, (R1) is not turned on because the contact B of (R2) id open.
R1
R 1 R 2
PB 1
R2
R 2 R 1
PB 2
PB 1
R1
PB2
R2
The latest input always has priority over the previous input. The relay (R1) is turned on when you press the pushbutton (PB1), and (R1) remains on through the self holding feature because (R2) is off. However , the relay (R2)is turned on when you press the push button (PB2) next, and the contact B of (R2) on the circuit of (R1) opens.As a result, (R1) is turned off. (R2) remains on through the self holding feature. However, (R2) is turned off whenyou press (PB1) again, and (R1) is turn on.
7
Timer circuit.
A. Delayed operation circuit.
R1
PB 1
W
T
R 1
T
PB 1
R 1
T
SL-1
Certain time operation circuit.
Actuated simultaneously when the switch is turned ON and stops when the timer set time is up.
R1
PB 1
T
R 1
T
L
PB 1
R 1
T
L
Repeated operation circuit.
Two timers are used and the circuits are repeatedly turned ON and OFF according to their set times.
SS R 1
T1
L
R1
T2
T 1T 2
R 1
T1 T2 T1 T2
SS
T 1
R 1
T 2
L
8
(2) Sequencer Circuit.Applied circuit using a basic circuit in a PC circuit.•Clamping start non-repeat circuit (safety interlock).
Common to manual and automatic operations
7 4PBS1
PBS2
X10C
X10D
Input modulePC-0
X10
C
D
PBS1
PBS2
Cycle Start
Cycle Start
1) Figure 1Clamping starts only when you press the start push button PBS1 (1)(X10C) and PBS2 (2)(X10D) concurrently or within 1 second (4)(5) (1 second set to T006 and T007 by the manufacturer
2) Figure 2Clamping does not start when you press the two push buttons separately at an interval of 1 second or more.When 1 second or more has passed after you press PBS1 (3)(X10C), the timer of start pushbutton interval 1 (4)(T006) has reached the specified time, and (6)(T006, contact B) opens. As a result, the start push button 2 cannot longer be turned on and clamping does not start.(Similarly, a non-repeat circuit is also incorporated in relay circuit.
Figure 1
Figure 2
1
2
Start Pushbutton 100206
Start Pushbutton interval 1/00207
Start Pushbutton 200208
Start Pushbutton interval 2/00205
R000HPDR
X10CPBS1
T007PBT2
R004PBR1
R000HPDR
X10DPBS2
T006PBT1
R005PBR2
T007PBT2
T006PBT1
R004PBR1
R005PBR2
3
6
4
5
00205
00206
00207
00208
9
2-3 How to read extended connection diagram of electric circuit.
(1) Relay circuitThe numbers below (1) in the below figure are addresses on the diagram. For example, the numbers above (2)indicates that the contacts of (ET) are at addresses 34 and 63.The underlined number (34) indicates contact B, and the non-underline number indicates contact A.
The number (181) indicated by (3) is the wire number (marked on the wire).
R012 AR
T141 DT
R038DOCB
R13ATEFX
T012EST00010T012
ESTX012 DOL
X01CSHFL
X1111CBL
R039EFY
Y04CEFS
R039EFY
X01AEFL
Y04DEBS
R010MR
X100CEF
X101CEB
Ejector Delay Time00719
Ejector Auxiliary00722 /0080000804
Ejector Forward SOL/00801
6 155 7
IR
DOR
4
ET
EFR
EBR
ET
CUT
EBSOL
EFSOL
189
188
186
187
190 191
181 182 183180DOR SHFR 1CBR EFR
0BACK EJECT
EJECTOR
Ejector Forward
Ejector Backward
Counter
Ejector Time34 63
3
1
1
2
2
56
58
59
60
61
62
63
00718
00719
00721
00722
Contact B
Contact B
181
Wire number(marked on the wire)
wire
(2) PC circuitAs is the case with the relay circuit, the numbers below (1) in the below figure are addresses, and the numbersabove (2) are the addresses being used.
Difference from the relay circuit is that slash (/) is prefixed to the address of contact B (/00801). The number withno slash being prefixed indicates contact A.
10
2-4 How to read extended connection diagram of relay circuit.
Example : The ejector cylinder does not move forward (Manual)(1) Using a multi-meter, check if a voltage is applied to the ejector (forward) solenoid valve.
[Measure the voltage of the wires 186 and 4 at the terminal of the ejector (forward) solenoid valve whether there is 100V. If voltage OK, then mechanical failure may cause the problem.]
(2) Conditions for turning on the ejector (forward) solenoid valve.(A) EFR (ejector forward limit switch) OFF figure 2(B) 1CBR (core 1 return limit) ON figure 2(C) SHFR (safety hook on limit) ON figure 2(D) DOR (die open limit) ON figure 2(E) Ejector selector switch “Forward” figure 2(F) Cycle selector switch “Manual” figure 1
For conditions (A) to (D) above, determined by the movement of the iron core if each relay is ON/OFF.For condition (E), check if the ejector selector switch is set to “Forward”.For condition (F), check if the cycle selector switch is set to “Manual”.Example : SHFR (safety hook on limit) is OFF due to a contact failure of the relay.
(1) Using a multi-meter, check if the voltage of wires 4 and 7 are 100V.(2) Using a multi-meter, check the voltage of each terminal on the circuit of wire 4 to find out where is shut down.(3) If a multi-meter reads that the voltages of wires 4 and 181 are 100V but the voltage of wires 4 and 182 are 0V, it
is clear that electricity is shut down at the contact A of SHFR.(4) If there is a free terminal at the contact A of SHFR, move it to another contact. If the check result is still NG,
replace the relay.
6 155 7
IR
DOR
4
ET
EFR
EBR
ET
CUT
EBSOL
EFSOL
189
188
186
187
190 191
181 182 183180DOR SHFR 1CBR EFR
0BACK EJECT
EJECTOR
Ejector Forward
Ejector Backward
Counter
Ejector Time34 63
56
58
59
60
61
62
63
54
AutomaticAR
AR
IBRCOR
EBR7
Cycle COS1Manual Automatic
Figure 2
Figure 1
11
2-4 How to read extended connection diagram of PC circuit.
Example : The ejector cylinder does not forward. This section explains how to trouble shoot (read) the circuit when the ejector cylinder does not move forward.
There are two trouble shooting procedures:> Trouble shooting through the LED of the input and output modules.> Trouble shooting using the handy programmer to check for the software circuit.
The following explains the trouble shooting procedure through the LED of the input and output modules. (1)Check the output module LED whether Y04C (ejector forward solenoid) is ON. When the check is OK : Using
multi meter, measure the voltage at the terminal block of the ejector forward solenoid valve.If the voltage is 100V. Then mechanical failure may causes the problem.If the voltage is less than 100V. Check for the wiring from the control unit to the solenoid valve.If the check is NG. according to the software diagram, check the conditions in which Y04C is turned ON, and identify the cause the problem by the LED of the input and output modules.
(2)Conditions for turning ON Y04C. (A) X01A (ejector forward limit switch) OFF figure 2 (B) Y04D (ejector backward solenoid) OFF figure 3 (C) R039 (ejector forward auxiliary) ON figure 4
[Check the conditions for R039 according to (3) If both X01A and Y04D are OFF]
R039EFY
X01AEFL
Y04DEBS
Y04CEFS
Ejector ForwardFigure 1
7
X01A
X01B
A
B
EFL
EBL
Ejector Forward LS
Ejector Backward LS
X01
Input modulePC-0
EFLS
EBLS
4
R012 AR
T141 DT
R038DOCB
R13ATEFX
T012EST00010T012
ESTX012 DOL
X01CSHFL
X1111CBL
R039EFY
R010MR
X100CEF
X101CEB
Ejector Delay Time00719
Ejector Auxiliary00722 /0080000804
Ejector Forward SOL
Ejector Backward SOL
EFSOL
EBSOL
Y04C
Y04D
Output modulePC-0
Y04 C
D
10
4
Figure 2
Figure 3
Figure 4
•See the section explaining B200 for how to view the LED of the input and output modules.
EBLS EFLS
EjectorBackwardLimit sw
EjectorForwardLimit sw
12
R012 AR
T141 DT
R038DOCB
R13ATEFX
T012EST00010T012
ESTX012 DOL
X01CSHFL
X1111CBL
R039EFY
R010MR
X100CEF
X101CEB
Ejector Delay Time00719
Ejector Auxiliary00722 /0080000804
Figure 1
(3)Conditions for turning ON R039 (ejector forward auxiliary)The conditions for manual ejector forward auxiliary are enclosed in broken line in the circuit in figure 1.
(A) X111 (core 1 return limit) ON figure 2 (B) X01C (safety hook in limit) ON figure 3 (C) X012 (die open limit) ON figure 4 (D) X101 (ejector selector switch: ejector backward) OFF figure 5 (E) X100 (ejector selector switch: ejector forward) ON figure 5
As the case with the previous item, check the input module LED whether the conditions above are satisfied. (F) R010 (manual operation) is ON when another operation (e.g., clamping or injection) is manually performed.
If the cylinder does not move in manual mode when you attempt to perform operation such as injection, check the conditions for R010.If the check result show that any of the conditions is not satisfied, check for the hardware (e.g., LS or wiring) in the conditions.
Core 1 return limit
47
MC 1X111 X111
1CBL
X11
Input ModuleFigure 2
Safety hook in limit
47
SHFLX01C
X01C
X01
Input Module
Die open limit
47
DOLX012 X012
X01
Input Module
Figure 3
Figure 4
Ejector forward
4ManualX008
X100 X100
X10Input Module
Ejector backwardX101X101
EjectorCOS 4 0Backward ForwardFigure 5
Ejector 0
Backward Forward
Safety hook cylinder
SHFLS (a)
SHBLS (a)
Link
H
ousi
ng
DCLS (b)
DHILS (b)
SHSLS (a)
DOLS (a)
SHFLS
DOLS
13
(4)Conditions for turning ON R010 (manual operation) in figure 1. to check the manual operation conditions, set all the selector switches to neutral, turn ON X002, and then set cycle selector switch to “Manual” whether “X008” is turn ON.Conditions for turning on R010 (manual operation)
(A) X002 (selector switches neutral) ON figure 2 (B) X008 (manual) ON figure 3 (C) X009 (automatic) OFF figure 4 (D) X00A (full automatic) OFF figure 5 (E) X012 (automatic operation) OFF figure 5
(R012 is OFF when both X009 and X00A are OFF)After conforming that the conditions above are satisfied, set the ejector selector switch to “Forward” again to get the machine to runIf the cylinder does not move, probably causes are follows:
(A) A terminal of the electric wiring is loose or the wiring is about to break, and the input is unstable switching back and forth between ON and OFF.
(B) The PC is in abnormal state. (e.g., module defective)
KSM
KSA
KSFA
R010 MR
Manual operation
Selector switches neutral
Cycle manual
Selector switches neutral
X008KSM
X009KSA
X00AKSFA
X002COR
R012 AR
R010 MR
Figure 1
Figure 2
Figure 3
Figure 4
Figure 2
CORX002
Input Module
Input Module
X00
X00
X002
COR
COR
7 4
3 4
47
DIECOS2
INJECTION COS3
EJECTOR COS4
CORE 1 COS5
Open 0 Close Inject 0 Return Eject 0 Return In 0 Out20 21 22 27
CYCLE KS 2
Man Off Auto Full AutoX008
X009
X00A
Cycle auto
Cycle full auto
X008
X009
X00A
X008KSM
X009KSA
X00AKSFA
X002COR
R011 AR1
R041MRBR
R011 AR1
R010 MR
R012 AR2
R012 AR
R00CMHPR
Automatic operation auxiliary
Automatic operation
14
2-6 Lubrication pump circuit (Relay circuit). (1) Figures 1 and 2
When hydraulic pump ON is completed, the relay (MLR)(1) is turned on and the lubricant pump run (LBL)(3) is turned on through (LBX contact B)(2) at the same time. Consequently, the lubricant pump starts running.
(2) Figure 3When the lubricant pump starts running and the pressure increases to 17 kg/cm², the pressure switch (LBPS)(4) is turned ON, the lubricant pump stop (LBX)(5) is turned ON, and (LBX contact B)(2) is opens to stop. Consequently, the lubricant pump stop.
(3) Figure 3The lubricant pump stop relay (LBX)(5) remains on through the self holding feature. The timer of lubricant pump stop time (LBT)(6) starts at the same time (LBX) is turned ON.
(4) Figure 4When the timer of lubricant pump stop time (LBT) has reached the specified time, (LBT contact B)(7) opens to turns OFF the lubricant pump stop relay (LBX). Consequently, the lubricant pump starts running again.
MLR LBPS LBT
LBX
LBOL
LBX
LBT
LBL
LBPT
Lubricant pump stop
Lubricant pump stop time
Lubricant pump run
Lubricant pressure detect
MLR LBPS LBT
LBX
LBOL
LBX
LBT
LBL
LBPT
Lubricant pump stop
Lubricant pump stop time
Lubricant pump run
Lubricant pressure detect
MLR LBPS LBT
LBX
LBOL
LBX
LBT
LBL
LBPT
Lubricant pump stop
Lubricant pump stop time
Lubricant pump run
Lubricant pressure detect
R S TNFB 1 LBL LBOL
LBM
U3
V3
W3Motor for lubricant pump
Fig. 1
Fig. 3
Fig. 4
Fig. 2
1
32
5
4
6
5
7
15
2-7 Lubrication pump circuit (PC circuit). (1) Figures 1, 2 and 3
When hydraulic pump ON is completed, the relay (R000)(1) is turned on and the output relay (Y038)(2) is turned ON at the same time. Consequently, the external relay (LBL)(3) is energized through the output module, and the lubricant pump starts running. The internal timer of lubricant pump run time (T001)(4) starts at the same time.
(2) Figure 4When the timer of lubricant pump run time (T001) has reached the specified time, (T001contact B)(5) opens, and the lubricant pump run relay (Y038) is turned OFF. Consequently, the lubricant pump stop.
(3) Figure 5 and 6When the timer (T001)(6) has reached the specified time, (T001contact A)(7) is turned ON, and the timer of lubricant pump stop time (T002)(8) starts.When the timer (T002) has reached the specified time, (T002 contact B)(9) of the circuit of (Y038) opens. Consequently, (T001 contact B)(10) is reset. When the timer (T002)(8) has reached the specified time, the lubricant pump starts running.
R0 S0 T0NFB 2 LBL LBOL
LBM
U3
V3
W3Motor for lubricant pump
R000HPDR
T002LBST
T001LBMT
T001LBMT
T002LBST
Y038 LBL
R000HPDR
T001LBMT
Lubricant pump run
Lubricant pump run time
Lubricant pump stop time
Y038 LBL
LBLLBOLY03
Output module10 4
Lubricant pump onY038
Fig. 1
Fig. 3
Fig. 2
R000HPDR
T002LBST
T001LBMT
T001LBMT
Y038 LBL
Lubricant pump run
R000HPDR
T002LBST
T001LBMT
T001LBMT
Y038 LBL
Lubricant pump run
Lubricant pump run time
Lubricant pump run time
T002LBST
R000HPDR
T001LBMT
Lubricant pump stop time
1
3
Fig. 4
Fig. 6
Fig. 5
2
4
6
8
5
7
910
16
Programmable Logic ControlB200
1. Specification
Item Description
Voltage 100AC only
Regulation Between 85 and 132 VAC 50 Hz
Primary side 5V 10A 135 VAC or less
power
consumption 5V 5A 80 VAC or less
Ambient temperature used 0 to 55 ºC
Storage temperature -20º C to 65º C
Earthing Earthing in Class 3
Cooling system Natural cooling
Control system Stored program system
Program system Indicated program system
(11 rows x 11 columns + 11 output)
Word length 16 bits/word, 1 to 4 word instruction
Instruction executing time Basic input instruction : 0.42µ
Basic output instruction : 0.58µ (Y, L, SD & MC)
Basic instruction 16 types
Applied Standard FS 00 ~ FS 63 MOVE,,,,,V,BIN, & BCD
Instruction FUN instruction
User Defined User define FU 00 through FU 63 with the
FUN instruction mnemonic basic language
Program capacity 4kw, 11kw, 18kw, CMOS.RAM, EPROM
Note : The EPROM board is required to use the
EPROM
Number of points of external 2048 points between X000 to XF7F or Y000 to
input / output relay YF7F (Every 16 input/output points available)
Pow
er s
uppl
yIn
stru
ctio
n
17
Programmable Logic ControlB200
DescriptionInternal relay 1024 points, R000 to R77FTimer counter T000 to T17F 0.1 to 3276.7 sec(Totals 512 points) T200 to T37F 0.01 to 327,67T000 to T37FC000 to C37F C000 to C37F 1 to 32767Latch 128 points L000 to L07FShift register 128 points S000 to S07FEdge register 128 points E000 to E07FData register 1024 words D000 to D77F(General purpose register) Timer Set value 512 words V000 to V37F counter Preset value 512 words P000 to P37F Alarm flag A011 : To be turned ON when the battery voltage
of the CPU module is unusual.A012 : To be turned ON when the PC link transmission is unusual.A013 : To be turned ON when the user program execution times exceeds 100ms.A014 : To be turned ON when an instantaneous power failure occurs.A015 : To be turned ON when the undefined FUN instruction is executed.A016 : To be turned ON when the out put module fuse is blown out.A017 : To be turned On when the coil output instruction is used for the 16 point input in the user program.
Dead fuse alarm for A020 : To be turned ON when the output module each rack fuse of the rack No. 0 is blown out.
toA02F : To be turned ON when the output module fuse of the rack No. F is blown out.
Item
Tem
pora
ry s
tora
ge
Spe
cial
aux
iliar
y re
lay
18
Programmable Logic ControlB200
Item Description
Special PC operation Dry contact input, shorting .. PC operates,
input / input Disconnecting .. PC stops.
output Abnormal PC Contact output : 24 VDC, 250 VAC, 2A;
output contact close .. When the PC stops due to the
trouble of the PC
Indicating Power supply Power On … turned ON
function indicator (green) Power OFF … turned OFF
In operation During operation … turned ON,
indicator (green) stop … turned OFF
Alarm indicator When a controllable trouble occurs … turned ON,
(yellow) Normal … turned OFF
Trouble indicator When an uncontrollable trouble occurs … turned
(red) ON, Normal … turned OFF
Battery 25 º C 5 years or longer
life 55 º C 2 years or longer
Status holding function during The counter, latch and shift register hold the status
interruption before power failure. To hold the status of the
internal auxiliary relay, assign the storage area with
the programmer.
Battery Lithium battery brand name :
ER 6 (AA) 3.6 V 1.9 Ah
Battery replacement Within 5 minutes
Duration
19
Programmable Logic ControlB200
DescriptionTrouble Operation / Trouble of CPU :detecting monitor It is detected that the CPU is uncontrollablefunction mode
Trouble of ROM :It is detected that the system program ROMcontrolling the PC or the usersequence programEPROM is abnormal
Trouble of RAM :It is detected that the system RAM controlling thePC is abnormal
Back up data error :It is detected that the content of the user sequenceprogram CMOSRAM or the data held in serviceinterruption is changed
Instantaneous power failure detection :An intantaneous power failure of the PC powersupply for 10ms or longer is detected. (When theInstantaneous operation stop mode is set)
Trouble of the battery :It is detected that the voltage of the memory backup battery is dropped to approx. 2.8 V or lower
Dead fuse detection :It is detected that the fuse inside the output moduleis blow out
Trouble of I/O bus :Abnormal input/output data of the input/outputmodule are detected
Item
20
Programmable Logic ControlB200
DescriptionTrouble Operation / Trouble of I/O mismatch :detecting monitor It is detected that the output instruction is used forfunction mode the input module in the user program
Trouble of PC Link :The trouble of PC Link transmission is detected
Abnormal cycle time :It is detected that an undefined function instructionis processed
Function over :The memory capacity for function instruction isinsufficient
Program Circuit element errormode Memory full
MT PC playback errorPeripheral circuitsPair coil error
Searchec data errorMemory PC < MTPC = MT checking errorNumber of coil circuits errordiscompiling error
Monitored data errorMemory ROMUncompleted circuitDuplicate coil error
Item
21
Programmable Logic ControlB200
2.1. Programmable Logic ControlConnector for connecting extended Input/ Output rack
Rack number setting switch
Power module
CU module
Maximum 8 pieces of input and out moduleInput module indicates -- X Output module indicates -- Y
7 6 5 4 3 2 1 0Module slot number
Input/ Output module
1 2 3
1 indicates Rack number 2 indicates Module slot number3 indicates Terminal number
Basic base board
Connector for peripheral equipment(Programmer PGM 355)
22
Programmable Logic ControlB200
From Basic BoardMode switch
Power module
7 6 5 4 3 2 1 0Module slot number
Maximum 8 pieces of input and out moduleInput module indicates -- X Output module indicates -- Y
1 2 31 indicates Rack number 2 indicates Module slot number3 indicates Terminal number
To anotherExtension base
*Mode switch setting :1. When basic Rack number used only ‘0’ (all I/O module), the extension power module set at ‘1’2. When basic Rack number used ‘0’ & ‘1’ (all I/O module), the extension power module set at ‘2’3. When basic Rack number used ‘0’, ‘1’, ‘2’ & ‘3’ (all I/O module), the extension power module set at ‘4’
2.2. Programmable Logic Control
Extension base board
23
Programmable Logic ControlB200
3. Configuration and function of module
A. Basic Power Module – Used for the basic and remote I/O rack
Model : B200PW110A – 100 VAC
Rack Number setting switch (Set 0 at shipping)
Power lamp When 5VDC is supplied… turned ON(Green) Turned OFF if voltage is dropped to less than 5 VDC
PC operation input terminal :When the terminal is turned on, the PC executes the sequence program
PC emergency stop output terminal :When uncontrollable trouble occurs in the PC, turns off the terminal.They are normally on. Use them for emergency stop circuit, when thetrouble occurs.
Power terminal : Used to connected from power supply (external)
Common ground terminal and frame ground terminal :Used to make the ground in the shortest route.
B. Extension Power Module – Used for the extension and remote I/O rack
Model : B200PW110B – 100 VAC
Rack Number setting switch (From 0 to F)
Power lamp (Green)
Power terminal :
Common ground terminal and frame ground terminal :
Fuse (glass tube fuse 250V, 4A)
Fuse (glass tube fuse 250V, 4A)
24
Programmable Logic ControlB200
C. Cu module Model : B200 CU, B200 CURM
In operation lamp --- During normal operation .. Turned on(Green) ---During stops .. Turned off
Alarm lamp --- When a controllable trouble occurs .. Turned on(Yellow) ---During normal operation .. Turned off
Emergency --- When a controllable trouble occurs .. Turned on(Red) ---During normal operation .. Turned off
Peripheral equipment interfacing connector :To be interfaced with peripheral equipment including CRT programmer
CU Cover :Battery and memory card inside
When the front cover is removed
CU board :Used to executes / operates sequence program
Lithium battery (Model K21141G 3.6 VDC):Used for the power supply to hold the memory during serviceInterruption. For the EPROM memory, it is used to back up thedata.
Battery connector : Connect the lithium battery to the CPU board
The EPROM memory board
Battery replacement :When the alarm lamp on the PC is turned on and the message “Battery Alarm” is output to peripheral equipment or used up to 5 yrs (base on the date at the Battery replace name plate inside the CB box).Notes : Through the battery replacement can be change during the power on, replace it carefully while the PC is in operated in particular. When changing the battery at power off, replacement time within 5 min after remove the battery connector.
25
No. PC mode OFF ON4 Test mode OFF ON3 Instantaneous Operation Operation
power failure stop continuingdetection andcycle time over
2 Timer counter Unchangeable Changeableset value
1 Intial clear Unexecuted Executed
Programmable Logic ControlB200
When dismantle and view from the back
ON1
2
3
4
PC mode setting switch :Used to set the working mode of the PC and set asfollow when shipping :-
Shipping status : All OFF position
Back up area Address While data While data isis memor- memorized byized by the the EPROMCMOS Timer counterRAM set value SW
Unchan Changgeable eable
Holding area in the R000 - R37F Cleared Cleared Clearedtemporary storageduring interruptionLatch relay L000 - L07F Cleared Cleared ClearedShift relay S000 - S07F Cleared Cleared ClearedGeneral purpose D000 - D77F Cleared Cleared ClearedregisterTimer counter V000 - V37F Cleared ----- Clearedset valuePreset value of P000 - P37F Cleared ----- ClearedcounterProgram ----- Cleared ----- Cleared
Initial clear : Used to set the status on whether to clear the battery back-up area of theCMOS RAM when the power is turned on.
26
Programmable Logic ControlB200
D. 16 points Input Module Model : B200 16 AI – 100 VAC B200 16 DI -- 24 VDC
E. 16 points Output Module Model : B200 16AO – 100 VAC B200 16 DON – 24 VDC B200 16 DOP – 24 VDC
Input ON/OFF indicator lamp (red)ON – turned onOFF– turned off
Terminal block
Output ON/OFF indicator lamp (red)ON – turned onOFF– turned off
Terminal block
Built in blow-fuse indicator lamp (red)Blown out – turned onNormal – turned off
27
Programmable Logic ControlB200
F. 32 points Input Module Model : B200 32 AI – 100 VAC B200 32 DI -- 24 VDC
Input ON/OFF indicator lamp (red)ON – turned onOFF– turned off
Terminal block
G. 32 points Output Module Model : B200 32AO – 100 VAC B200 32 DON – 24 VDC B200 32 DOP – 24 VDC
Output ON/OFF indicator lamp (red)ON – turned onOFF– turned off
Terminal block
Note : The 32 points output module has no built in blow out fuseInstall the 1 common 5A fuse outside the module. Through this fusePrevent the module pattern from burning, it’s protects no internal element.
28
Programmable Logic ControlB200
3. Replace fuse on output module (B200 16AO)
Rearcover
Output board
Case Terminalblock
Fuse
Fuse
Fuseblowoutindicator
Screw 1
Screw2
Fuse : 125 V 7.5AModel : MP 7.5
Fuse : Ordinary blowout typeModel : MF-51 250V 6ASize : 5.2 X 20 mm
Note : Used recommended fuse or same ampere fuse only.
29
Programmable Logic ControlB200
4. LED display on I/O module (16 points)
01234567COM89ABCDEFCOM
AC100VOUTPUT
01234567
89ABCDEF
Fuse blownOutput moduleonly
01234567
89ABCDEF
RightSide
Y070Y071Y072Y073Y074Y075Y076Y077Y078Y709Y07AY07BY07CY07DY07EY07F
Leftside
AC100VINPUT
Note : For input, the display in the programmer will indicating ‘X’
The part (3) in figure is the close-up of the part (1) of the LED indicator.The LED indicator of a 16 point output module has a structure of 2 columns listing 8 points in vertical.The points are re-listed in a single column consisting of (a) and (b) as shown.When they are re-listed in a single column , they are easy to understand because they are in the same list as for the terminal block. Each of 2 COM indicates power supply.
(3)
(a)
(b)
(1)
30
0 1 2 30 01 12 23 34 45 56 67 7
01234567COM89ABCDEFCOM
Programmable Logic ControlB200
5. LED display on I/O module (32 points)
01234567COM89ABCDEFCOM
X000X001X002X003X004X005X006X007COMX008X009X00AX00BX00CX00DX00EX00FCOM
X100X101X102X103X104X105X106X107COMX108X109X10AX10BX10CX10DX10EX10FCOM
AC 100VINPUT
01234567
01234567
0 1 2 3
AC 100VINPUT
01234567
01234567
0 1 2 3
X000ToX007
X008ToX00F
X100ToX107
X108ToX10F
Note : For output, the display in the programmer will indicating ‘Y’
Figure 1 is the close-up of the part (1) of the LED indicator (fig. 6) of the input module. The indicator is a structure of 4 columns containing 8 points in vertical appears to be complicated, but it can be simplified by dividing as shown.
31
Programmable Logic ControlTC200
1. Specification
Item Description
Voltage AC 100 V 50 Hz
Regulation Between 85 and 132 VAC
Primary side 5V 10A 120 VAC or less
power
consumption 5V 5A 80 VAC or less
Ambient temperature used 0 to 55 ºC
Storage temperature -20º C to 70º C
Grounding Grounding resistance of 100 ohm or less.
Cooling system Natural cooling (SEA)
Control system Stored program system
Program system Indicated program system
(11 rows x 11 columns + 11 output)
Word length 16 bits/word, 1 to 5 words instruction
Processing time Basic instruction : 0.09µ to 0.18µ
Application instruction : 0.57µ
Basic instruction 16 types
Applied Application 127 kinds (Arbitrary setting of argument and
Instruction instruction Selection of operating conditions are possible)
User defined 127 kinds
A. instruction
Program capacity Sequence area : 32 kW
User area : 12 kW
Number of points of external 2048 points between X000 to XF7F or Y000 to
input / output relay YF7F.
Pow
er s
uppl
yIn
stru
ctio
n
32
Programmable Logic ControlTC200
Item Description
Internal relay 1024 points, R000 to R77F
Extension Internal relay 1 2048 points, G000 to GF7F
Extension Internal relay 2 2048 points, H000 to HF7F
Latch relay 128 points, L000 to L07F
Shift register 128 points, S000 to S07F
Edge relay 1024 points, E000 to E77F
General-purpose register 1 2048 points, D000 to DF7F
General-purpose register 2 2048 points, B000 to BF7F
Timer / counter 1024 points, T/C000 to T/C77F
Set value 1024 points, V000 to V77F
Current value 1024 points, P000 to P77F
Alarm flag A011 - Battery fault
A012 - PC link error
A013 - Cycle time over
A014 - Instantaneous power failure
A015 - Undefined function execution
A016 - Fuse blow-out detection
A017 - Input / output module mismatch
Fuse blow-out alarm A020 - Rack No. 0 fuse blow-out
to
A02F - Rack No. F fuse blow-out
33
Programmable Logic ControlTC200
2.1. Programmable Logic Control
7 6 5 4 3 2 1
1 – Power module2 – CU module3 – Communication module ( For “J” type machine only)4 – Remote module ( For “J-S” type machine only)5 – Input module6 – Output module7 – Output module8 – Output module (For “J” type machine only)9 – Input module (For “J” type machine only)10- Input/output module (For “J” type machine only)
8
9
10
34
Programmable Logic ControlTC200
3. Configuration and function of module
A. Basic Power Module – Used for the basic and remote I/O rack
Model : TCPW 110A – AC 100V (For standard machine) TCPW 110AL – AC 100V (For Toscast machine)
I/O connector (TCPW 110AL model only)
Power indicator LED (Green)Illuminated when DC 5V power supply normal
Rack No. setting switchPower wiring terminal block :INPUT AC 100V terminalFG (frame ground) terminalSTOP relay out put terminal.
If an uncontrollable trouble occurs, turn off this terminal.Note : Contact capacity : DC 24V / AC 220 V 2A
OUTPUT DC 5V terminal. Power of 5 VDC is supplied to TCPW5B
EXT. I/O (OUT) connector :Connector for extension I/O connection. Connect it with the EXT. I/OIN connector of the next extension I/O power supply module.
B. Extension Power Module – Used for the extension I/O rackModel : TCPW 110B – AC 100V
EXT. I/O (OUT) connector :Connector for extension I/O connection. Connect it with the EXT. I/OIN connector of the next extension I/O power supply module.
Power wiring terminal block :INPUT AC 100V terminalFG (frame ground) terminalOUTPUT DC 5V terminal: Power of DC 5V is supplied to TCPW5B
Rack No. setting switch
EXT. I/O (IN) connector :Connector for extension I/O connection. Connect it with the EXT. I/O(OUT) connector of the preceding extension I/O power module.
35
Programmable Logic ControlTC200
C. Cu module Model : TCCUH (Control module with high speed sequence function)
1. RUN lamp
2. ALARM lamp
3. STOP lamp
4. Maintenance Code display
5. RUN / STOP key switch
6. Peripheral equipment interfacing connector
7. RS232 connector
8. Maintenance Code reset push button
9. Lithium battery
10.Battery connector
11. Memory card and connector
12. Memory card ejector
13. PC mode setting switch
36
Programmable Logic ControlTC200
1. RUN lamp : Illuminated during normal PC operation and goes out during stop.2. ALARM lamp : Illuminated if a controllable trouble occurs.3. STOP lamp : Illuminated if an uncontrollable trouble occurs.4. Maintenance Code display : An error message is display by the 3 digit 7 segment LED. It is also possible to display a user message. (This code cannot be cleared at trouble causing PC stop)5. RUN switch : Used to change over the PC start and stop. When this switch is set to “RUN” the PC start.6. Peripheral equipment interfacing connector : To be interfaced with peripheral equipment including the programmer. (PGM 559)7. RS232 connector : To be connector with the personal computer or equipment having an RS232 interface.8. Maintenance Code reset push button : Press this switch when clearing a maintenance code display.9. Lithium battery : RAM backup battery.10.Battery connector : Used to connect the lithium battery with the CU module.11.Memory card and connector : EEPROM type memory card storing the sequence program. The memory capacity is 128 KB. And connector for inserting the memory card.12.Memory card ejector : Eject push button for removing the memory card.13.PC mode setting switch : Used to set the PC operation mode. In all the following 8 modes are available.
ON
987654321
No. PC mode98 MC BOOT7 MC WRITE6 SEQ. PROTECT5 DATA REG. PROTECT4 I/O CHANGE3 OUT HOLD2 CONTINUE1 INITIAL
37
Programmable Logic Control TC200
No. 8. MC BOOT When set to ON from OFF, the sequence program is booted (memory card boot) from the memory card. (Also booted when the switch set to ON at power ON)No. 7. MC WRITE When set to ON from OFF, the sequence program is written (Memory card write) into the memory card. (Memory card write protect “WP” must switch to ON) See fig. below
No. 6. SEQ. PROTECT When set to ON, writing of sequence program is prohibited. (Sequence protect)No. 5. DATA REG. PROTECT Writing of data register is banned. (Data register protect)No. 4. I/O CHANGE When set to ON, the I/O module can be changed during PC (input / output change) operation. In this condition, I/O processing is not executed. After replacement, be sure to set the switch to OFF.No. 3. OUT HOLD When set to ON, output is held even if the PC stops. When (Output hold) set OFF, all number of output are turned off.No. 2. CONTINUE When set to ON, the PC operation continues even if (Resumption of operation) instantaneous power failure or cycle time over is detected.No. 1. INITIAL When set to ON from OFF, all contents of sequence program (Initial clear) and data register are cleared. (They are also cleared when the switch is set to ON at power ON)Note : All dip switches of the PC mode setting switch are set to OFF for spare parts. As for installed on the machine, usually dip switch No. 5 and 6 are set to ON.
WP
D. Replacement of battery
1. Replace the memory backup and clock battery within the term of validity. The battery can be replace while the PRIVISOR power is on or off. When the power off, replace the battery within 5 minutes.2. Model : ER3V-C
Battery connector
38
Programmable Logic Control TC200
D. Input module Model : TC 32DI – DC 24V TC 32AI – AC 100V
E. Output module Model : TC 32DON – DC 24V COM - NEGATIVE TC 32 DOP – DC 24V COM - POSITIVE TC 32AO – AC 100V
Input signal indicator lampWhen the input signal is ON, LED light in red
Terminal block
Input signal indicator lampWhen the input signal is ON, LED light in red
Terminal block
Fuse blow out indicator lampIlluminated in red if the output wiring protection has blown out
39
Programmable Logic ControlTC200
4. Fuse replacement on Output module
Only the fuse of the output module is changeable by customer. If the fuse has blown out,identify and remove the case, then replace it with a new fuse.Through the fuse is also in the Power Module, it is blown out even by an abnormal generatedIn the internal circuit and must not be replaced by customer.
PCB Case
Terminal block
Rearcover
Sparefuse
Fuse
Note : Used recommended fuse or same ampere fuse only.
Note :Type of fuse used : Normal blow out fuse 5.2 X 20 mm TC 32 DON : MF – 51, 250V 8A TC 32 DOP : MF – 51, 250V 8A TC 32 AO : MF – 51, 250V 6A
Before replacing the fuse, be sure to turn off the PROVISOR and I/O power supply.
40
Programmable Logic Control TC200
5. 32 points input module LED display and terminal connection
0 1 2 30 01 12 23 34 45 56 67 7
13578ACEC213578ACEC4
0246C19BDF0246C39BDF
X001X003X005X007X008X00AX00CX00ECOMX101X103X105X107X108X10AX10CX10ECOM
X000X002X004X006COMX009X00BX00DX00FX100X102X104X106COMX109X10BX10DX00F
TC 32DI
01234567
01234567
0 1 2 3
TC 32DI
01234567
01234567
0 1 2 3
X000ToX007
X008ToX00F
X100ToX107
X108ToX10F
TC 32AI
TC 32AI
41
Programmable Logic Control TC200
6. 32 points Output module LED display and terminal connection
0 1 2 30 01 12 23 34 45 56 67 7
13579BDF-13579BDF-
02468ACEC102468ACEC2
Y001Y003Y005Y007Y009Y00BY00DX00E NY101Y103Y105Y107Y109Y10BY10DY10F N
Y000Y002Y004Y006Y008Y00AY00CY00ECOMY100Y102Y104Y106Y108Y10AY10CY10ECOM
TC 32DON
01234567
01234567
0 1 2 3
TC 32DON
01234567
01234567
0 1 2 3
Y000ToY007
Y008ToY00F
Y100ToY107
Y108ToY10F
FUSEFuse blown out indicator
42
Programmable Logic Control TC200
7. 16/4 points input module. Model : TR 16DIC, TR 16DIE, TR 04DI
Mode switch
Input LED display
LINEEND
01
1 2
CH NO
Terminal connector
Operation monitor LED display
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16
Main I/O Unit supply DC24V DC24V X**0 COM X**1 X**2 COM1 X**3 X**4 COM2 X**5 X**6 COM3 X**7
X**8 COM4 X**9 X**A COM5 X**B X**C COM6 X**D X**E COM7 X**FFGA+ B- FG
43
Programmable Logic Control TC200
8. 16/4 points output module. Model : TR 16AOECE, TR 16AOE, TR 04AO
Terminal connector
A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16
B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16
I/O supply AC100V Y**0 COM Y**1 Y**2 COM1 Y**3 Y**4 COM2 Y**5 Y**6 COM3 Y**7
Y**8 COM4 Y**9 Y**A COM5 Y**B Y**C COM6 Y**D Y**E COM7 Y**FFG
Input LED display
Fuse250 VAC 3A5.2 X 20mm
44
Programmable Logic Control TC200
9. Input / output module. Model : TR 80DIDOPT (64 points input & 16 points output)
TB1 TB2
12345678910111213141516171819202122232425262728293031323334353637383940
X+0 X+201234567C189ABCDEFC2
01234567C389ABCDEFC4
OVOV24V24V
01234567C589ABCDEFC6
01234567C789ABCDEFC8
OVOV24V24V
Power LEDRun LEDError LED
DC 24V Input
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Fuse for outputY**0 to Y**7
Fuse for outputY**8 to Y**F
TB3
O OSW2 SW3
SW1
2 1
Channel I/O LED indicator
F1F2
F32 – Line End1 – Channel change
Power Supply Control
I/O LEDdisplayLed 1 - 16
Y**
0Y
**1
Y**
2Y
**3
Y**
4Y
**5
Y**
6Y
**7
C9
Y**
8Y
**9
Y**
AY
**B
Y**
CY
**D
Y**
EY
**F
C10
(-)
24V
0V FG A(+
)B
(-)
SG
FG
Fuse type: for F1 and F2 normal blown out fuse 250V / 1A 5.2 X 20mm for F3 normal blown out fuse 250v / 3A 5.2 X 20mm
45
Programmable Logic Control TC200
9-1. Terminal connector TB 1 and TB 2 (DC24V input) Common connector C1 to C8 (0V) for 8 points input C1at TB 1-1-9 pinExample : Input contact X000, X00F and X020 X000 to connect at TB 1-1 pin X00F to connect at TB 1-9 pin X020 to connect at TB 2-1 pin Power supply : OV to connect at TB 1-37, TB 1-38, TB 2-37 & TB 2-38. DC 24V to connect at TB 1-39, TB 1-40, TB 2-39 & TB 2-40.
9-2. Terminal connector TB3 (Included output, communication and control power supply ports)Example : Output contact Y000 and Y00f Y000 to connect at TB 3-1 pin Y00F to connect at TB 3-18 pin Common connector C9 and C10 (24V) for 8 points output C9 at TB 3-9 and TB 3-19. RS485 I/F connection (A+ and B-) Split I/O communication A+ to connect at TB 3-24 and B- to connect at TB 3-25 For shield FG to connect at TB 3-27 Power supply connection (0V, 24V and FG) 0V to connect at TB 3-21 24V to connect at TB 3-22 FG to connect at TB 3-23
9-3. LED 1-16 (I/O display LED) / SW3 (indicator I/O)
FEDCBA9876543210
LED 16LED 15LED 14LED 13LED 12LED 11LED 10LED 9LED 8LED 7LED 6LED 5LED 4LED 3LED 2LED 1
0
12 3
4
56
789
SW30 OFF1 LED display for input signal TB 1-1 to 8 & 10 to 17 connection ports2 LED display for input signal TB 1-19 t0 26 & 28 to35 connection ports3 LED display for input signal TB 2-1 to 8 & 10 to17 connection ports4 LED display for input signal TB 2-19 to 26 & 28 to35 connection ports5 LED display for output signal TB 3-1 to 8 & 11 to 18 connection ports6~8 Unused9 LED test mode
46
Programmable Logic Control TC200
10. Communication module. Model : TCRMT
TCRMT
RUNALARMSTOP
RS485
A
B
FG
RS485
A
B
FG
Operation LED displayRun : ON when CU module switch to runAlarm : On when RS485 wire troubleStop : Module trouble
Terminal connectorConnect the blocks according. These 2 terminal blocksare connected internally by connecting the same signals.
Open the cover on the module front lower side, and you can see switches SW1 and SW2 there.The function of each switch is as follows. Set these switches accordingto the intended use. SW1 TERMINATING RESISTANCE Used to turn on and off the 100 Ω terminator. Only when the module is located on the final end of the transmission line, set this switch ON. SW2 MASTER/SLAVE MODE SWITCH Used to select the master station or slave station for the module. When the module is used as the master station, set the switch to “MASTER”. When its serve as the slave station, set it to “SLAVE”. In the same remote system, only 1 master station is available. NEVER set 2 or more modules for the master station.
Power Peripheral Alarm contentsupply equipment & referencemodule error message for remedyPower RUN ALARM STOP MAINTENA-
NCE CODE
O
O O O C.7.0 F Table error The undefined function instruction is used.
C.7.1 I/O mismatch The output instruction is used for the input module.
C.7.2 Link table error The link table data isabnormal.
C.6.0 Cycle time over The processing time of one cycle exceeds thepredetermined time.
C.4.0 Battery fail The battery voltage dropsto 2.8 V or less.
C.4.1 EEPROM Data writing to or readingfrom the memory card isabnormal.
F.0.0 to Fuse down The fuse of the outputF.0.7 module has blown out.
L.0.0 to PC link error Abnormal data L.3.F transmission by PC link.
O O C.0.0 PC CPU error The main PC CPU hasmalfunction.
C.0.1 PC RAM error The operating system RAM is abnormal.
C.0.2 PC ROM error The operating system ROM is abnormal.
P.0.0 EXT. power fail The DC 5V power voltageabnormal.
C.3.0 Back up data The sequence memory error data is abnormal.
L6.0 Link master Two or more link mastermaster are preset.
C.6.1 INT. Prog. over The interruptive programhas not been processed within the predetermined time.
Normal condition
Abnormal condition, operation continues.
Abnormal condition, operation stop.
LED ON / OFF State of Power supply and CU moduleO : LED ON, : LED OFF
LED indication
CU module
Programmable Logic Control TC200
48
Programmable Logic Control TC200
Notes :If the cycle time over or instantaneous power failure is detected, the PC operating condition and LED status change with the internal setting of the CU module.
Maintenance code display content
. . .
Signifies the related module.C : CU ModuleP : Power ModuleU : I/O ModuleE : Intelligent Module
Signifies the alarm breakdown.0 ~ 2 : Replacement of module is needed3 ~ 5 : If the same alarm is repeated, replacement module, etc. is needed.6 ~ 8 : Illegal programming or setting.
. . .
F : Fuse downH : Remote I/O errorU : I/O error
0 ~ F : Rack number 0 ~ 7 : Card number (If the remote I/O isgenerated, the card number is “0”)
L. . .
L : PC link error 0 ~ 3 : PC number (Upper)
0 ~ F : PC number (Lower)
Maintenance code display
SYMBOL (1)
ELECTRICAL SYMBOL
Name Symbol Symbol Name Description
FUSEEE
MOTOR
M
OVERLOAD RELAY MOL
MOL
MOL
LMAGNETIC SWITCH
DFFORWARD /REVERSESWITCH
DB
DF
CUTSHOT COUNTER
DB
Fuse
3-phaseinductionmotor
Melts down to protect the circuit whenelectric current larger than the flows.Therefore, do not use fuse greater than the rated capacity.
Bimetal
Contact
This is a 3-phase motor and a symbol forthe location it is used is entered in this part.The supply voltage must be ±10% of theRated voltage.
Generates heat when a current larger thanthe rated current flows, becoming warpedto break the contact. This action turns offcurrent in the magnet switch coil to protectthe motor.
Coil
Contact
When current flows in the coil, its activatesthe motor that has contacts connected.Normally open contacts operated by above.
Coil to move dieheight unitforward andbackward.
Contacts of DFand DB.
When current flows in the coil, it connectscontact DF or DB.
Contacts connected by DF or DB.
Shot counterWhen current flows in the power section, itrotates the gear a ½ turn and when current stops, it simultaneously rotates the gear ½ turn further to change the indicator number.
A BC DE FG H
SYMBOL (2)
ELECTRICAL SYMBOL
COS & KS 1 0 2
SELECTOR SWITCH &KEY SWITCH
PRS
PRS
PRESSURE SWITCH
a
d
b
c
e
SELECT SWITCHPS
FSFOOT SWITCH
SOLENOID COIL
Standard CloseSHORTING WIRE
SSSNAP SWITCH
EGROUND(EARTH)
Tr
180 200 220
100
TRANSFORMER
SLINDICATOR LAMP
Name Symbol Symbol Name Description Vertical line =a switch position,the horizontalline = combination, &the • mark =connection.
Locations where broken line intersect asmarked by • are connected from left to right.When switch to 0 connection is from C to DAnd G to H.When switch to 1 connection is from A to BWhen switch to 2 connection is from E to F
Contact A(normally opencontact)Contact B(normally closecontact)
Connected when pressure rises above theset pressure. Disconnected when pressure is below the set pressure.Disconnected when pressure rises aboveshe set pressure. Connected whenpressure is below the set pressure.
a → b Contact Ba → c Contact Ad → e Contact A
Contact A
When switched over, a to c and d to e areconnected, a to b are disconnected.If is not switch over, the connection as shown in the diagram.
Connection when the pedal is stepped on.
Solenoid coilWhen the current flows, it is energized toSwitch over the valve.
Shorted forStandard Machine.
Discounted in the terminal block sectionwhen using automatic device or safety equipment.
Contact A Connected when switch lever push to ON position. And disconnected when push toOFF position.
Earth One side of the transformer secondarycircuit is grounded to earth with green wire.(wire directly connected to the coil)
Primary side
Secondary side
Voltage varies in proportion to the numberOf coil windings. The voltage on the secondary side varies as the tap on theprimary side is changed.
W
Indicator lamp Also called signal lamp.Symbol W is white, G is green, R is red &Y is yellow.
SYMBOL (3)
ELECTRICAL SYMBOL
PBPUSH BUTTON SWITCH
LIMIT SWITCH
RAUXILIARY RELAY
T
T
T
Off OnKS
TIMER(TIMER LAGRELAY)
KEY SWITCH
METAL CONSENT MC
a b
W
PUSH BUTTON WITHLAMP
BZBUZZER
Name Symbol Symbol Name Description
Contact A
Contact B(mushroom type)Contact B
Connected when pushed & disconnectedwhen release.Disconnected when pushed & connectedwhen release.(use at emergency stop)
Contact A
Contact B
Connected when lever was pressed anddisconnected when release.
Disconnected when lever was pressed andconnected when release.
Coil
Contact A
Contact B
When current flows, it is energized toswitch over the contact.
Connected when coil energized.Disconnected when coil is not energized.Disconnected when coil is energized.Connected when coil is not energized.
Coil
Contact A
Contact B
When current flows, it time lag operationstart.Connected when the set time elapses afterflows in the coil. Disconnected when current stops.Disconnected when the set time elapsesAfter current flows in the coil. Connectedwhen current stops.
Key switchThis switch cannot be operated unless thekey was inserted. When the key inserted &turn to ON position, a and b are connected.
a b
Metal connector Core in/out limit switch is connected when using a core. And a & b are connectedthrough the limit switch.
Contact A
Lamp
The lamp lights when the push button ispressed.W is white.R is red.
BuzzerWhen current flows in the coil, it’s createsa sound.