electrical machines

31
Electrical Machines LSEGG216A 9080V

Upload: wyome

Post on 13-Feb-2016

107 views

Category:

Documents


1 download

DESCRIPTION

Electrical Machines. LSEGG216A 9080V. Parallel Operation & Auxiliary equipment. Introduction. Identify. Parallel Operation. Why not get a bigger one?. Can carry many of the same size so maintenance is easier & cheaper If one fails can still supply some load - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Electrical Machines

Electrical Machines

LSEGG216A9080V

Page 2: Electrical Machines

Parallel OperationParallel Operation&&

Auxiliary equipmentAuxiliary equipment

Page 3: Electrical Machines

IntroductionIntroduction• Identify

Page 4: Electrical Machines

Parallel Parallel OperationOperationWhy not get a bigger one?

• Can carry many of the same size so maintenance is easier & cheaper

• If one fails can still supply some load• Can turn one off if load reduces

Page 5: Electrical Machines

Parallel Parallel OperationOperationBoth transformers must have:

• Same voltage• Frequency• Roughly the same VA rating• Same polarity

Page 6: Electrical Machines

Parallel Parallel OperationOperationSingle Phase

Incorrect Polarity

High circulation currents will flow

Page 7: Electrical Machines

Parallel Parallel OperationOperationSingle Phase Correct Polarity

Page 8: Electrical Machines

Parallel Parallel OperationOperationTesting for Polarity

Place a voltmeter across the transformer terminal

and the supply line

Correct polarity =Incorrect polarity =

0 VoltsTransformer voltage or higher

Page 9: Electrical Machines

3 Phase 3 Phase TransformersTransformers

TypesStar

PRIMARY SECONDARY

No Phase Shift

Star

Reference

Page 10: Electrical Machines

3 Phase 3 Phase TransformersTransformers

TypesDelta

PRIMARY SECONDARY

No Phase Shift

Delta

Reference

Page 11: Electrical Machines

3 Phase 3 Phase TransformersTransformers

TypesDelta

PRIMARY SECONDARY

V2 Leads V1 by 30

Star

30Reference

Page 12: Electrical Machines

3 Phase 3 Phase TransformersTransformers

TypesDelta

PRIMARY SECONDARY

V2 Lags V1 by 30

Star

30

Reference

Page 13: Electrical Machines

Paralleling 3 Phase Paralleling 3 Phase TransformersTransformers

Must be from the same vector groupMust have the same effect on voltage:

-Δ paralleled with -Δ

Δ- paralleled with Δ-

Δ- paralleled with -Δ Provided that the line voltages are equal

Page 14: Electrical Machines

Paralleling 3 Phase Paralleling 3 Phase TransformersTransformers

Must be from the same vector groupMust have the same effect on voltage:

-Δ paralleled with -Δ

Δ- paralleled with Δ-

Δ- paralleled with -Δ

Δ- -30 & -Δ +30

The voltage phase difference would be 60

Page 15: Electrical Machines

Auxiliary Auxiliary EquipmentEquipment• Protection

• Voltage adjustment

• Over temperature• Over pressure• Low oil level• Oil quality• Reduction of water

• Tap changers

Page 16: Electrical Machines

Transformer Transformer ConstructionConstruction

• Most large transformers are oil filled

• The oil level must be high enough to cover the transformer

• Oil must be kept dry and clean

Page 17: Electrical Machines

Transformer Transformer ConstructionConstruction

Sealed Tank

Conserver Tank

Tank always stays full

Page 18: Electrical Machines

Transformer Transformer ConstructionConstruction

Pressure relief valve allows over pressure oil to escape

Over temperature thermostat trips circuit breaker if

transformer gets too hot

Buchholz relay monitors oil between transformer and

conserver tank

Page 19: Electrical Machines

Buchholz Buchholz relayrelay

• Presence of air bubbles due to faulty initial filling or faulty seal of gaskets

• Formation of gas due to burning of oil or solid insulation

• Lowering of oil level due to leak of the tank

• Oil flow from tank to conservator due to explosion or short circuit

Monitors

Page 20: Electrical Machines

Buchholz Buchholz relayrelay

On a slow accumulation of gas, due to slight overload accumulates in the top of the relay and forces the oil level down. A float operated switch in the relay is used to initiate an alarm signal

Page 21: Electrical Machines

Buchholz Buchholz relayrelay rapid gas accumulation, flow of oil

operates a switch attached to a vane

Test port to allow the accumulated gas to be withdrawn for testing

Page 22: Electrical Machines

Buchholz Buchholz relayrelay

Oil & Gass from Tx Oil to conserver

Oil for testing

Gas testingDry air test

Page 23: Electrical Machines
Page 24: Electrical Machines

Tap ChangersTap ChangersTwo types:• Off Load• On Load

Can be located on the primary or secondary of the transformer

Page 25: Electrical Machines

Off LoadOff Load• Basically a multi-position switch

• Open circuits output between positions

• Contacts not rated to open circuit under load

Page 26: Electrical Machines
Page 27: Electrical Machines

Transformer Open circuited

Page 28: Electrical Machines
Page 29: Electrical Machines

On LoadOn Load• Manual• Automatic

Transformer windings

Common terminal

Sliding switch

Page 30: Electrical Machines

On LoadOn LoadInductors carry

current when contact is between taps

Page 31: Electrical Machines

On LoadOn LoadContact moves to new tap