electrical system design for amazon
DESCRIPTION
Electrical System Design For Amazon.com. The Mid-South Annual Engineering and Sciences Conference MAESC 2006 By Phuc Linh Nguyen Liles Engineering Design Consultants March 31, 2005. Introduction. Amazon.com opens a new customer service center in Kennewick, WA. Electrical System Design - PowerPoint PPT PresentationTRANSCRIPT
Electrical System DesignElectrical System DesignForFor
Amazon.comAmazon.comThe Mid-South Annual Engineering and Sciences ConferenceThe Mid-South Annual Engineering and Sciences Conference
MAESC 2006MAESC 2006
ByBy
Phuc Linh Nguyen Phuc Linh Nguyen Liles Engineering Design ConsultantsLiles Engineering Design Consultants
March 31, 2005March 31, 2005
IntroductionIntroduction
Amazon.comAmazon.com opens a new customer opens a new customer service center in Kennewick, WA.service center in Kennewick, WA.
Electrical System DesignElectrical System Design Jim Liles at Liles Engineering Design Jim Liles at Liles Engineering Design
ConsultantsConsultants
Project ScopeProject Scope
To Provide Backup To Provide Backup Diesel GeneratorDiesel Generator
To Provide UPS SystemTo Provide UPS System To Provide load To Provide load
calculationscalculations To Perform Short-To Perform Short-
circuit calculationscircuit calculationsDiesel GeneratorUninterruptible Power Supply
Design SpecificationsDesign Specifications
Generator is rated at Generator is rated at 600 KW, 750 KVA600 KW, 750 KVA 480 V, three phase, 60Hz480 V, three phase, 60Hz
UPS is sized at 50 KVA UPS is sized at 50 KVA and 40 KW.and 40 KW. 480 VAC, 3-phase, 60Hz480 VAC, 3-phase, 60Hz
Design SpecificationsDesign Specifications
All Panels are sized All Panels are sized based on total Volt-based on total Volt-Ampere (VA) of Ampere (VA) of connected loads.connected loads.
All the loads are All the loads are summoned up summoned up throughout the entire throughout the entire systemsystem Electrical Panel
PanelsPanelsPanel ELA
Volts: 120/208V
Phase: 3
Wire: 4W
Buzzing 225 225/3 Main CB
Loads A B C BKR Ck Ck BKR A B C Loads
Receptacles 900 20/1 1 2 20/1 800 Lights
900 3 4 800 Mech VVT's
900 5 6 900 Fan F2
900 7 8 300 Liebert Rac 8
900 9 10 360
Roof Receptacles
720 11 12 300Preaction
Sprink.
720 13 14 600 Water HTR/Circ.
Total 11040 10140 8580 8000 8060 7500 Total
A: 19040
B: 18200
C: 16080
Loads A BC
BKR Ck Ck BKR A B C Loads
AV
VA159
120
19040
CurrentVoltage
ereVoltageAmp
ResultsResults
PanelCurrent (Amps)
EHA 246
EHB 327
EHC 398
EHDP 123
EMSB 1369
ELA 159
ELB 194
ELC 173
System DiagramSystem DiagramUtility Power
2000Amp, 277/4803-phase,4W
Transformer
Fault #1
1600/31600A trip breaker
Transition Transfer Switch
600KW, 750KVA277/4803- phase, 4W
Diesel Generator
Fault #2 Fault #3
Fault #4
Fault #4
1600Amps, 277/480, 3-phase, 4W
ESMB
EHA EHB
400Amps277/480
3-phase, 4w
400Amps277/480
3-phase, 4w
EHC
400Amps277/480
3-phase, 4w
Fault #5a
Fault #5b
Fault #5c
Fault #5d
400Amps277/480
3-phase, 4w
75KVA
480 – 120/208V3-phase, 4W
75KVA
480 – 120/208V3-phase, 4W
75KVA
480 – 120/208V3-phase, 4W
Fault #6a
Fault #6b
Fault #6a
400/3 400/3 400/3 400/3
125/3 125/3 125/3
Fault #7a
Fault #7b
Fault #7c
Fault #8a
Fault #8b
EHDP
UPS
Watt-stopperRelay Panel
Watt-stopperRelay Panel
Watt-stopperRelay Panel
ELA
225Amps120/208
3-phase, 4W
ELA
225Amps120/208
3-phase, 4W
ELA
225Amps120/208
3-phase, 4W
Fault #7a
Fault #7b
Fault #7c
Fault #8a
Fault #8b
225/3225/3 225/3
Rectifier/Charger
Inverter
Battery CabinetStatic
BypassSwitch
Fault #9
Fault #8bFault
#8a
CLA
225Amps120/208
3-phase, 4W
70/3 70/3
45KVA
480 – 120/208V3-phase, 4W
225Amps, 277/480, 3-phase, 4W
45KVA
480 – 120/208V3-phase, 4W
CLA
225Amps120/208
3-phase, 4W
150/3 150/3
Fault #9
Fault #10a Fault #10b
Fault #11a Fault #11b
Interrupting RatingInterrupting Rating
Available Fault
Current
Available Fault
Current
Available Fault
Current
Protective Device
LoadNormal Current Operation
Short-Circuit Operationwith Inadequate
Interrupting Rating
Short-Circuit Operationwith adequate
Interrupting Rating
Short – Circuit CalculationsShort – Circuit Calculations
LL
SCA
VnC
ILf
**
3*
fM
1
1
IFLA = Rated CurrentP = Rated Power of TransformerVL-L = Secondary Line Voltage
ISCA = Short-Circuit Current%Z = Rated Impedance of TransformerZ
II FLASCA %
f = Constant FactorL = Length of Conduitn = Number of Conduit Per PhaseC = Conductor Constant
AV
KVA902
480*3
750
AA
044,2005.0*9.0
902
0129.0480*4*28033
3*044,20*20
LL
FLV
PI
*3
MIscacsymIs *.
987.00129.01
1
AA 783,19987.0*044,20 IS.CSYM = Short Circuit at a fault
ResultsResults Number and Short-Circuit Length
Type of Number of Size of wire and conduit Current of Wires
Fault # Conduit Parallel Runs (AWG or kcmil) (Amps) (feet)
1 Non-Magnetic 4 4 - 600MCM, 4"C 19,783 20
2 Steel 4 4 - 600MCM, 4"C 19,625 10
3 Steel 4 4 - 600MCM, 1 - #4/0(G), 4"C 19,331 20
4 Steel 4 4 - 600MCM, 1 - #4/0(G), 4"C 18,906 30
5a Steel 2 4 - #3/0, 1 - #1/0(G), 2 1/2"C 17,507 30
5b Steel 2 4 - 250MCM, 1 - #2(G), 2 1/2"C 10,669 373
5c Steel 2 4 - 350MCM, 1 - #1(G), 3"C 13,536 229
5d Steel 1 3 - 350MCM, 1 - #4(G), 3"C 15,701 59
6a Steel 1 3 - 3, 1 - #6(G), 1 1/4"C 14,706 22
6b Steel 1 3 - 3, 1 - #6(G), 1 1/4"C 9,559 22
6c Steel 1 3 - 3, 1 - #6(G), 1 1/4"C 11,803 22
7a Steel 1 4 - #4/0, #2(G), 2 1/2"C 3,563 25
7b Steel 1 4 - #4/0, #2(G), 2 1/2"C 3,397 25
7c Steel 1 4 - #4/0, #2(G), 2 1/2"C 3,486 25
8a Steel 1 3 - #3, 1 - #6(G), 1 1/4"C 11,996 26
8b Steel 1 3 - #3, 1 - #6(G), 1 1/4"C 11,996 26
9 Steel 1 3 - #3, 1 - #6(G), 1 1/4"C 6,705 26
10a Steel 1 3 - #4, 1 - #8(G), 1"C 6,909 44
10b Steel 1 3 - #4, 1 - #8(G), 1"C 7,094 40
11a Steel 1 4 - #1/0, 1 - #4(G), 1 - #4(IG), 2 1/2"C 1,929 16
11b Steel 1 4 - #1/0, 1 - #4(G), 1 - #4(IG), 2 1/2"C 1,932 16
ResultsResults
Ampere
Interrupting
Capacity (AIC)
1600A trip breaker 50,000
Transition switch 50,000
Panel EHA 35,000
Panel EHB 35,000
Panel EHC 35,000
Panel EHDP 35,000
Panel EMSB 50,000
Panel ELA 10,000
Panel ELB 10,000
Panel ELC 10,000
Panel CHDP 25,000
Panel CLA 10,000
Panel CLB 10,000
Electrical CostElectrical CostElectric System Material Quotes Labor EQ&Tool Total
Labor Hr
Service & Distribution $24,540 $38,165 $27,795 $1,500 $92,000 546
Lighting and Control $7,795 $286,444 $45,390 $4,000 $343,629 890
Devices $3,115 0 $12,240 $2,500 $17,855 240
Branch Lighting $15,100 0 $48,093 $2,800 $65,993 943
Branch Power $25,755 0 $68,697 $1,500 $95,952 1347
Feeders $38,150 0 $23,868 $1,500 $63,518 468
Basic Materials/Misc $5,212 0 $31,875 $1,000 $38,087 625
Fire Alarm 5145% $22,296 $37,587 $1,000 $66,028 737
Emergency Generation $10,225 $129,700 $8,568 $2,500 $150,993 168
Lighting protection $120 $13,880 $1,224 $1,500 $16,724 24
Reuse Existing CDT/Wire - $12000 $0 - $10,200 - $22,200 -200
Temp Pwr/LTG $55,000 $0 $7,650 $13,150 150
Mob/Demob/Permits $3,500 $2,272 $1,224 $6,996 24
Meggar Testing/start up $3,825 $3,825 75
Second Shift Premium $20,400 $20,400
Overtime Premium $5,100 $5,100
Sub Total Prices $132,157 $492,757 $333,336 $19,800 $978,050 6036
Mark Up At 15% $19,823.55 $73,913.55 $50,000 $2,970 $146,707.50
Totals $151,981 $566,671 $383,336 $22,770 $1,124,758 6036
ConclusionConclusion
Provides power distributionProvides power distribution Provides back up power supply Provides back up power supply Provides uninterruptible power to Provides uninterruptible power to
server roomserver room Provides adequate interrupting rating Provides adequate interrupting rating
for protective devicesfor protective devices
Questions?Questions?