electric/pneumatic release model f470 - 4 and 6 inch …

12
PREACTION SYSTEM, DOUBLE INTERLOCK ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH (100 and 150 mm) m /f -7 fxjp - 2 FEET II (600mm) MINIMUM . . cr” 0 I- Model F470 External Resetting Multimatic Deluge Valve 2- Model F52O/F5201 Swing Check Valve 3- System Main Control Valve (supervised in open position) 4- System Shut-Off Valve (supervised in open position) 5 Solenoid Valve 6- Dry Pilot Actuator 7- Low Air Pressure Alam, Switch 8- Waterflow Pressure Alam Switch Q- Manual Control Station lo- Automatic Air/Nitrogen Pressure Maintenance Device 13- Manual Pull Station (as required) 14- Alarm Bell 15 Heat Detectors (or other fire detection devices) 16- Automatic Sprinklers 17- Water Supply Pressure Gauge 18- System Air Pressure Gauge lQ- Diaphragm Chamber Pressure Gauge A- Power Supply To Panel B- Audible Alarm Circuit C- Fire Detection Initiating Circuit D- Waterflow Alarm Initiating Circuit E- Supervisory Alarm Initiating Circuit F- Releasing Circuit - .- FIGURE A MODEL F470 ELECTRIC/PNEUMATIC DOUBLE INTERLOCK PREACTION SYSTEM - SCHEMATIC OF TYPICAL ARRANGEMENT- 1l- Water Motor Alarm (optional) 12- Deluge Valve Releasing Panel with Battery Back-Up G- Manual Pull Initiating Circuit The 4 and 6 inch (100 and 150 mm) Model F470 Electric/Pneumatic Dou- ble interlock Preaction Systems (Ref. Figure A) are designed for use in ap- plications, such as refrigerated areas, requiring the maximum degree of pro- tection .against inadvertent flooding of the sprinkler system piping. The F470 Electric/Pneumatic Double Interlock Preaction System utilizes a Model F470 External Resetting Multi- mati& Deluge Valve and a Model F520 or F5201 Swing Check Valve, with releasing trim consisting of both a Solenoid Valve and a Dry Pilot Actua- tor in a series configuration. The Swing Check Valve isolates the Deluge Valve from the system air pressure, which holds the Dry Pilot Actuator closed. The Solenoid Valve remains closed until it is electrically energized by a deluge valve releasing panel (auto- matic control unit) that is operated by either a fire detection device or manual pull station. In order for the Double Interlock Pre- action System to automatically actu- ate, two independent events must occur. The deluge valve releasing Printed in U.S.A. 1-96 TD1151 OBSOLETE

Upload: others

Post on 13-May-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

PREACTION SYSTEM, DOUBLE INTERLOCK ELECTRIC/PNEUMATIC RELEASE

MODEL F470 - 4 and 6 INCH (100 and 150 mm)

m /f

-7 fxjp - 2 FEET

II (600mm)

MINIMUM . .

cr” 0

I- Model F470 External Resetting Multimatic Deluge Valve

2- Model F52O/F5201 Swing Check Valve

3- System Main Control Valve (supervised in open position)

4- System Shut-Off Valve (supervised in open position)

5 Solenoid Valve 6- Dry Pilot Actuator 7- Low Air Pressure Alam, Switch 8- Waterflow Pressure Alam Switch Q- Manual Control Station lo- Automatic Air/Nitrogen Pressure

Maintenance Device

13- Manual Pull Station (as required) 14- Alarm Bell 15 Heat Detectors (or other fire

detection devices) 16- Automatic Sprinklers 17- Water Supply Pressure Gauge 18- System Air Pressure Gauge lQ- Diaphragm Chamber Pressure

Gauge A- Power Supply To Panel B- Audible Alarm Circuit C- Fire Detection Initiating Circuit D- Waterflow Alarm Initiating Circuit E- Supervisory Alarm Initiating Circuit F- Releasing Circuit - .- FIGURE A

MODEL F470 ELECTRIC/PNEUMATIC DOUBLE INTERLOCK PREACTION SYSTEM

- SCHEMATIC OF TYPICAL ARRANGEMENT-

1 l- Water Motor Alarm (optional) 12- Deluge Valve Releasing Panel

with Battery Back-Up

G- Manual Pull Initiating Circuit

The 4 and 6 inch (100 and 150 mm) Model F470 Electric/Pneumatic Dou- ble interlock Preaction Systems (Ref. Figure A) are designed for use in ap- plications, such as refrigerated areas, requiring the maximum degree of pro- tection .against inadvertent flooding of the sprinkler system piping.

The F470 Electric/Pneumatic Double Interlock Preaction System utilizes a Model F470 External Resetting Multi- mati& Deluge Valve and a Model F520 or F5201 Swing Check Valve, with releasing trim consisting of both a Solenoid Valve and a Dry Pilot Actua- tor in a series configuration. The Swing Check Valve isolates the Deluge Valve from the system air pressure, which holds the Dry Pilot Actuator closed.

The Solenoid Valve remains closed until it is electrically energized by a deluge valve releasing panel (auto- matic control unit) that is operated by either a fire detection device or manual pull station.

In order for the Double Interlock Pre- action System to automatically actu- ate, two independent events must occur. The deluge valve releasing

Printed in U.S.A. 1-96 TD1151

OBSOLETE

Page 2: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

Left Side Front

NOTES: (a.) f$gmncferance, additional 2’ (50 mm) is

(b.) Add Q”(230 mm) for optional F470 Double Interlock Accelerator Trim.

Dim A’

:

4 INCH SYSTEM Inches (mm) 23.25

;:;A; 7.00 12.00 (305)

Dim A’

:

6 INCH SYSTEM Inches (mm) 26.25 5.25 :Fz;

12.00

FIGURE B E 8.69

g; ED 8.69

14.56 I;::;

15.44 INSTALLATION CONFIGURATION F 13.89 (348) F 14.50 AND CLEARANCE DIMENSIONS

l F520 or F5201 l F520 or F5201

panel must operate and open the So- lenoid Valve upon automatic operation of the electric fire detection initiating circuit or manual operation of the elec- tric-manual pull initiating circuit, and the sprinkler system piping must lose air pressure due to operation of one or more sprinklers.

The Double Interlock Preaction Sys- tem will automatically actuate only when both the Dry Pilot Actuator and the Solenoid Valve are open at the same time. Accidental opening of just the Dry Pilot Actuator (for example: a lift truck accidentally dislodges a sprinkler), or just energizing the Sole- noid Valve (for example: an accidental

operation of an electric pull station), will only cause an alarm, and will not actuate the system or flood the sprink- ler system piping.

Both the 4 and 6 inch (100 and 150 mm) F470 Double Interlock Preaction Systems may be equipped, as an op- tion, with the Model F311 Accelerator. In the case of the F470 Double Inter- lock Preaction System, the F311 oper- ates as a quick opening device for the Dry Pilot Actuator and provides a re- duction in the time to open it, following the operation of one or more automatic sprinklers.

The 4 and 6 inch (100 and 150 mm) Model F470 Electric/Pneumatic Dou- ble Interlock Preaction Systems are listed by Underwriters Laboratories Inc. and Underwriters’ Laboratories of Canada as Double Interlock Type Water Control Valves, and they are approved by Factory Mutual Research Corporation as Refrigerated Area Sys- tems for use in refrigerated rooms or buildings.

WARNZNG The 4 and 6 inch Model F470 Double Interlock Preaction Systems with the

-2-

OBSOLETE

Page 3: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

associated trim described herein must be installed and maintained in com- pliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other Authorities Having Jurisdic- tion. Failure to do so may impair the integrity of the associated devices.

The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. The installing contractor or manufacturer should be contacted rel- ative to any questions.

The 4 and 6 inch (100 and 150 mm) Model F470 Electric/Pneumatic Dou- ble Interlock Preaction Systems, as well as their associated trim, are rated for use at a minimum service pressure of 20 psi (1,4 bar) and a maximum service pressure of 175 psi (12,l bar).

The following is a list of the Technical Data Sheets for the valves and de- vices which are required as part of the Double Interlock Preaction System:

Deluge Valve . . . . . . . . TD116

Swing Check Valve . . . . TD320

Dry Pilot Actuator . . . . . TDl17W

Solenoid Valve . . . . . . . TD119

Manual Control Station . . TD121

Water-flow Pressure Alarm Switch . . . . . . . . . . . TD213

Low Air Pressure Alarm Switch . . . . . . . . . . . TD232

The following is a list of the Technical Data Sheets for additional items which may be considered for use with the Double Interlock Preaction System:

Accelerator . . . . . . . . . TD109

System Pressure Maintenance De- vice (select one)

-Air Pressure Reducing Type . . . . . . . . . . . . . . TDlll

-Air Compressor Control Type . . . . . . . . . . . . . . TD112

-Nitrogen Press. Reducing Type . . . . . . . . . . . . . . TD113

Water Motor Alarm . . . . . TD250

System Design Considerations The .automatic sprinklers, as well as the deluge valve releasing panel (au-

tomatic control unit), fire detection de- vices, manual pull stations, and signal- ing devices, which are utilized with the Double Interlock Preaction System must be UL Listed, ULC Listed, C-UL Listed, or FM Approved, as applicable.

Because a double interlock preaction system requires time for a drop in sys- tem air pressure to occur (in addition to responding to a separate heat de- tection system), before it will allow water to enter the system piping, this system has characteristics similar to a dry pipe sprinkler system. Therefore, the system design considerations for a dry pipe system are normally applied to a double interlock preaction system - including a 30% increase in design area; quick opening devices for sys- tem capacities of 500 gallons (1890 litres) or more; a maximum 1 minute water delivery time for system capaci- ties of 750 gallon (2850 litres) or more; and, prohibition of gridded system pip- ing.

The deluge valve, swing check valve, and all interconnecting piping must be located in a readily visible and acces- sible location and in an area which can be maintained at a minimum tempera- ture of 4O’F/4’C.

NOTE Heat tracing is not permitted for the deluge valve, swing check valve, or any of the interconnecting piping. Heat tracing can promote the forma- tion of hardened mineral deposits which can prevent system operation. Heat tracing can also result in dam- age to the F470 Deluge Valve Dia- phragm Assembly.

In planning the installation, consider- ation must also be given to the dis- posal of the large quantities of water which may be associated with draining the system or performing a flow test.

Installation configuration and clear- ance dimensions are given in Figure B. The flanged inlet and outlet connec- tions are faced and drilled per ANSI Standard 816.1. The grooved outlet connection of the F5201 Swing Check Valve is cut in accordance with Gruvlok standard .groove specifica- tions for steel pipe, and they are suit- able for use with grooved end pipe couplings that are listed or approved for fire protection service.

In order to readily perform the System Inspection Procedure described in the Care and Maintenance section, it is recommended that a System Shut-Off Valve be installed above the Model F52O/F5201 Swing Check Valve, as shown in Figure A. The System Shut- Off Valve should be a listed or ap- proved (as appropriate) indicating valve with a supervisory switch to mon- itor the normally open position.

-3-

System Air Pressure Requirements Graph B shows the minimum Elec- tric/Pneumatic Double Interlock Pre- action System air pressure require- ment as a function of the water supply pressure. Use of an automatic air or nitrogen maintenance device is recom- mended and may be required by the Authority Having Jurisdiction.

NOTE The dew point of the air or nitrogen must be maintained below the lowest ambient temperature to which the Double Interlock Preaction System piping will be exposed, or as required by the Authority Having Jurisdiction. Accumulation of water in the connec- tion to the Dry Pilot Actuator will lower the air pressure at which the Dry Pilot Actuator will open and pos- sibly prevent proper operation. Also, introduction of moisture into the sys- tem piping that is exposed to freezing temperatures can create ice build up which could prevent proper operation of the system.

Friction Loss The nominal pressure losses versus flow rate for the 4 and 6 inch (100 and 150 mm) combinations of the Model F470 Multimatic Valve with either the Model F520 or F5201 Swing Check Valve are shown in Graphs A-l and A-2.

The approximate friction losses, based on the Hazen and Williams formula and expressed in equivalent length of Schedule 40 pipe, are given below for each size deluge and swing check valve combination. The equivalent length of pipe has been calculated on the basis of the flow rates typically used with each size system.

SIZE OF c = 100 CM20 VALVES FT. OF PIPE FT. OF PIPE

4” 18.2 25.5 6’ 26.4 36.9

Valve Trim The F470 Electric/Pneumatic Double Interlock Preaction Trim, illustrated in Figure C, is designed to be used in addition to the (Wet Pilot) Actuation Trim shown in Figure D. The combina- tion of these two trim arrangements forms the complete double interlock preaction trim arrangement. Figure C also illustrates the optional Double In- terlock Accelerator Trim complete with Model F311 Accelerator. All of the trim arrangements are designed for use with either the 4 or 6 inch (100 or 150 mm) valve arrangements.

Fire Department Connection When installing a fire department con- nection per NFPA 13 for preaction sys- tems, a tee fitting (to accomodate the supply from the fire department con- nection) will be required between the

OBSOLETE

Page 4: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

300 400 500 700 1000 2000 3000

FLOW RATE IN U.S. GALLONS PER MINUTE (GPM)

100 2000 3000 5000 7000 10000

FLOW RATE IN LITRES PER MINUTE (LPM)

GRAPH A-l

GRAPHS A-l and A-2

GRAPH A-2

NOMINAL PRESSURE LOSS VERSUS FLOW FOR THE MODEL F470 DOUBLE INTERLOCK PREACTION SYSTEM

(DELUGE VALVE AND CHECK VALVE COMBINATION)

F470 Deluge Valve and the F52OIF5201 Swing Check Valve. To facilitate the increased elevation of the F52O/F5201 Swing Check Valve, the nipple below the Solenoid Valve (9- Fig. C) may be increased in length accordingly.

NOTE Do not increase the length of the nip- ple between the Solenoid Valve and Dry Pilot Actuator or the nipple above the Dry Pilot Actuator. Increasing ei- ther of these two nipple lengths may impair operation of the system.

As indicated in the General Descrip- tion section, two independent events resulting in opening of both the Dry Pilot Actuator and the Solenoid Valve must occur to actuate the Model F470 Electric/Pneumatic Double Interlock Preaction System.

When the Double Interlock Preaction System is set for service, the dia- phragm chamber of the Model F470 Deluge Valve is pressurized through the diaphragm chamber supply con- nection (Fig. D). The Model F470 Del- uge Valve is a differential type valve which depends upon the water pres- sure in the diaphragm chamber to hold the clapper closed against the water supply pressure. The Model F470 Del- uge Valve has a nominal trip ratio of 2.5 to 1, i.e., the valve operates when pressure in the diaphragm chamber is reduced to approximately two-fifths of the water supply pressure.

The Model F470 External Resetting Deluge Valve is described in TD116.

Opening of both the Dry Pilot Actuator and the Solenoid Valve (8 & 9 - Fig. C), or operating the Manual Control Sta- tion (3 - Fig. D) will release water from the Multimatic Valve diaphragm cham- ber faster than it can be replenished through the l/8 inch (3,2 mm) diameter orifice of the Priming Supply Restric- tion (8 - Fig. D). A rapid pressure drop then results in the diaphragm chamber

-4-

and the differential between the dia- phragm chamber and waterway is eliminated. The water supply pressure then forces the waterway clapper open, permitting a flow of water to the Double Interlock Preaction System piping. Water flowing into the system also flows through the normally open Alarm Control Valve (Fig. D) to the Waterflow Pressure Alarm Switch (Fig. C), which actuates the system alarm signal.

The Double Interlock Preaction Sys- tem will automatically operate only when both the Solenoid Valve and the Dry Pilot Actuator are open at the same time. Opening of just the Dry Pilot Actuator (e.g., a lift truck acciden- tally dislodges a sprinkler) or just ener- gizing the Solenoid Valve (e.g., an ac- cidental operation of an electric pull station) will only cause an alarm, via the low air pressure alarm switch orthe deluge valve releasing panel, as appli- cable, to indicate that the system re- quires attention. The system will not actuate or flood the sprinkler system piping.

As an option, the 4 and 6 inch (100 and 150 mm) Double Interlock Preaction Systems may be equipped with a Model F311 Accelerator (Fig. C) forthe purpose of obtaining a reduction in the time for the Dry Pilot Actuator to open following the operation of one or more automatic sprinklers.

With the optional Double Interlock Ac- celerator Trim, the communication be-

OBSOLETE

Page 5: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

WATER SUPPLY PRESSURE IN PSI

GRAPH B DOUBLE INTERLOCK PREACTION SYSTEM

AIR PRESSURE REQUIREMENTS

tween the system air pressure and the Dry Pilot Actuator is made directly through the Accelerator Trim. The F311 Accelerator automatically ad- justs to small as well as slow changes in system pressure, but trips when there is a rapid and steady drop in pressure (such as will occur when a sprinkler operates). Upon tripping, the F311 Accelerator will relieve system air pressure from the Dry Pilot Actuator faster than it can be replenished through the 3/32 inch (2,4 mm) diame- ter orifice in the clapper of the l/2 inch (15 mm) Swing Check Valve (E - Fig. C), resulting in quick opening of the Dry Pilot Actuator following a sprinkler operation.

The Model F311 Accelerator is de- scribed in Technical Data Sheet TD109.

The deluge valve, swing check valve, and all interconnecting piping must be installed in a readily visible and acces- sible location and in an area which can be maintained at a minimum tempera- ture of 4O’F/4’C.

NOTE Heat tracing is not permitted for the deluge valve, swing check valve, or any of the interconnecting piping. Heat tracing will promote the forma- tion of hardened mineral deposits which can prevent valve operation. Heat tracing can also result in dam- age to the F470 Deluge Valve Dia- phragm Assembly.

The 4 and 6 inch (100 and 150 mm) Electric/Pneumatic Double Interlock Preaction Systems must be installed in accordance with the following instruc-

tions. Proper operation of the Double Interlock Preaction System depends upon it being installed in accordance with the instructions given below. Fail- ure to follow these instructions may prevent the devices from functioning properly as well as void listings, ap- provals, and the manufacturer’s war- ranties.

1. All pipe thread connections must be free of scale and burrs before installation. Use pipe thread seal- ant sparingly on male pipe threads only.

2. The F470 Deluge Valve must be installed vertically as shown in Fig- ure B and C.

3. To attach the lower flange of the F520 or F5201 Check Valve to the upper flange of the F470 Deluge Valve, as shown in Figure B, at least four out of the eight required flange fasteners must be stud bolts and nuts. The stud bolts must be 5/8”-11 UNC x 3-l/4” long for4 inch (100 mm) valves and 3/4”-10UNC ;a;;3f” long for 6 inch (150 mm)

4. Install the (Wet Pilot) Actuation Trim as specifie.d by TDl16 and then the Double Interlock Preac- tion Trim as shown in Figure C.

Care must be taken to make sure that check valves, globe valves, etc. are installed with the flow ar- rows in the proper direction.

Drain tubing to the Drip Funnel must be installed with smooth bends that will not restrict flow.

5. Attach the Model F470 Double In- terlock Label (11 - Fig. C) to the 2 inch high x 4 inch (50 x 200 mm) wide nameplate mounting pad on

-5-

the Handhole Cover of the F52OIF5201 Swing Check Valve. Place the Label over the man- ufacturer’s logo nameplate, if one is located on the pad.

6. The Diaphragm Chamber Supply Connection (Fig. C) must be con- nected to the water supply side of the System Main Control Valve to facilitate setting of the F470 Del- uge Valve.

7. Connect the Air Supply Connec- tion to an air or nitrogen supply. Use of an automatic air or nitrogen maintenance device is recom- mended and may be required by the Authority Having Jurisdiction. Refer to Graph B for Double Inter- lock Preaction System air pressure requirements.

An air dryer, when specified, is to be installed as required by the Au- thority Having Jurisdiction.

8. Install, as applicable, the optional Double Interlock Accelerator Trim as shown in Figure C.

The drain tubing must be installed with smooth bends that will not re- strict flow.

The connection to the system pip- ing must be located on the supply side of the System Shut-off Valve (Fig. A) and at least two feet above the F52OIF5201 Check Valve, so that drain back/condensate will not flow into the Accelerator piping.

Connections to a feed or cross main must be made either to the side or top of the main.

After installing the F311 Accelera- tor, close the Accelerator Control Valve.

NOTES Failure to follow the above in- structions can result in accidental tripping of the Accelerator.

The Accelerator Control Valve must be closed during hydrostatic testing of the system to prevent internal damage to the F311 Ac- celerator.

9. The Low Air Pressure Alarm Switch (Fig. C) is to be adjusted to operate on falling pressure at ap- proximately 6 psi (0,4 bar) below the minimum Double Interlock Dry System air pressure requirement shown on Graph B.

10. The Pressure Relief Valve (5 - Fig. C) is factory set to relieve at a pressure of approximately 45 psi (3,l bar), which can typically be used for a maximum system pres-

OBSOLETE

Page 6: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

ACCELERATOR CONNECTION TO SYSTEM REFER TO INSTALLATION STEP 8

E

/

ACCELERATOR CONTROL

P VALVE (NORMALLY OPEN)

A- Model F311 Ii- l/4’ Tube, 36’ Accelerator long (2 req’d)

B- 250 lb. Air J- l/2’ Plug Pressure Gauge K- 112’ x l/4’

c- 112’ Y-Strainer Reducing Elbow Q- l/2’ Globe Vatve L- l/2” x l/2’ x l/4’ E- 112’ Swing Check Tee

Valve WI 3l32’ M- I/2’ Tee Orifice N- l/4’ x I’ Nipple

F- I/4’ Angle Valve P- 112’ x l-1/2’ G- l/4’ Tubing Nipple (5 req’d)

Connector Q- 112’ x 3’ Nipple (2 req’d)

Optional Accelerator Trim - Bill of Materiaie-

I- 250 lb. Air Pressure Gauge

2- l/4’ Gauge Test Valve

3- Model PSIO-2A Pressure Alarm Switch

4- Model PS40-1A Pressure Alan Switch

5 l/4’ Pressure Relief Valve

6- l/2’ Globe Valve 7- l/2” Swing Check Valve 9 Model B-l Dry Pilot

Actuator 9- 24 VDC Solenoid Valve IO- T Angle Valve ll- Label 12- l/2” Tubing Connector 13- l/2’ Tube, 36’ long

14- l/2’ Union 15 I/2’ 45’ Elbow 16- l/2’ 90’ Elbow (4 req’d) 17- l/2’ Tee (2 req’d) 19 l/2’ x l/2’ x l/4’ Tee 19- l/4’ Plug 20- l/C X 4’ Nipple 21- l/2” x close Nipple 22- l/2’ x l-1/2’ Nioole

(10 req’d) ” 23- l/2’ x 2’ Nipple 24- l/2’ x 5’ Nipple

for 4’ valves, l/2’ x 5-l/2’ Nipple for 6’ valves

25- l/2’ x 4-W’ Niwle ’ ’ 26- 2’ x 2-112’

Nipple

Double interlock Preaction Trim - Bill of Materiaie-

FIGURE C 4 AND 6 INCH DOUBLE INTERLOCK PREACTION TRIM & OPTIONAL ACCELERATOR TRIM

-6

OBSOLETE

Page 7: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

I- 300 lb. Water Pressure Gauge (2 req’d)

2- 114’ Gauge Test Valve

3- Model Fli30 Manual Control Station

4- 2’ Angle Vaive 5- l/2’ Ball Valve

(2 req’d) 6- l/2’ Swing Check

Valve 7- l/2’ Spring Loaded

Check Valve 6 Priming Supply

Restriction 9- I/2’ Y-Strainer lo- Model F793

Automatic Drain Valve

II- Drip Funnel supporl Plug

12- Drip Funnel Support

13- Drip Funnel 14- 3132’ Vent

Fitting 15- I/2’ Angle

Valve 16- I/4’ Tube,

30’ long 17- ll2’Tube

Connector 19 l/2’ Tube,

24’ long 19- l/4’ Plug 20- l/2’ Plug 21- 314” Plug 22- l/2’ Union

(5 w’d) 23- l/2’ 90’ Elbow

(3 req’d) 24- l/2’ Tee (6 req’d) 25- l/2’ x l/4’ x I/2” Tee

(3 req’d) 26- I/2’ x I/2’ x 3l4’ Tee 27- 2’ 90’ Elbow 29 l/2’ x1-112”

Nipple (17 req’d)

29- l/2’ x 3’ Nipple

30- l/2” x 4” Nipple 31- I/2” x 5’ Nipple

(2 req’d) 32- l/2’ x7-112

Nipple 33- II2 x 10-l/2”

Nipple for 4” valve, l/2’ x 12’ Nipple for 6’ valve

34- l/4’ x 1 -l/2 Nipple

35- 2 x 3 Nipple (2 req’d)

13

21 ‘CTION \

26

ALARM CONTROL VALVE * (NORMALLY OPEN) 26

25

ALARM TEST 16

LLY CLOSED)

‘DIAPHRAGM CHAMBER PRESSURE GAUGE

TO DRIP FUNNE MANUAL CONTROL STATION

TO DRIP FUNNEL

DIAPHRAGM CHAMBER SUPPLY CONTROL VALVE (NORMALLY OPEN)

26

23

ul ‘DIAPHRAGM CHAMBER SUPPLY CONNECTION

FIGURE D (Reference from TD116)

(WET PILOT) ACTUATION TRIM FOR MODEL F470 DELUGE VALVE

NOTES:

1. The nipples utilized in the trim arrangements shown in Figures C and D are Schedule 40 steel per ASTM A53 or Al35 and they are threaded per ANSI B1.20.1 The fittings are either malleable iron per ANSI 816.3 or cast iron per ANSI 816.4.

2. The trim arrangement shown in Figure D is factory assembled as shown in TD116.

3. “Standard order” trim is provided with black nipples and fittings: however, galvanized nipples and fittings are available on “special order”.

-7-

OBSOLETE

Page 8: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

11

12

A. Immediately verify whether or not a fire situation is present. If a fire condition does exist, notify the local fire service and follow the plan prescribed by the Authority Having Jurisdiction.

B. If a fire condition does not exist:

1. Close the Diaphragm Chamber Supply Control Valve (Fig. D).

2. Close the system’s Main Control Valve (Fig. A).

3. Open the Main Drain Valve (Fig. D) at the rear of the F470 Deluge Valve.

4. If the system has been flooded, open the System Main Drain Valve at the side of the F52O/F5201 Check Valve (Fig. C), Inspector’s Test Connection, and all auxiliary drains in the sys- tem piping. Check to see that the drainage water will not cause damage or result in dangerous conditions.

5. Notify the alarm monitoring sta- tions (if applicable) as well as the Authority Having Jurisdiction that there is an impairment to the fire protection system.

6. Determine if the false alarm was caused by the electric fire detec- tion system or a low air pressure condition and then promptly cor- rect the impairment and return the fire protection system to service, as soon as possible.

sure of 40 psi (2,8 bar). The Pres- sure Relief Valve may be reset; however, it must be be reset to relieve at a pressure which is in accordance with the requirements of the Authority Havng Jurisdiction.

To reset the Pressure Relief Valve, first loosen the jam nut and then adjust the cap accordingly - clockwise for a higher pressure setting or counterclockwise for a lower pressure setting. After verify- ing the desired pressure setting, tighten the jam nut.

Suitable provision must be made for disposal of drain water. Drain- age water must be directed such that it will not cause damage or result in dangerous conditions.

All conduit and electrical connec- tions are to be made in accordance with the requirements of the Au- thority Having Jurisdiction and/or the National Electrical Code.

The Double Interlock Preaction Sys- tem will not automatically reset after an operation. It must be manually reset and it should be restored to service as soon as possible.

NOTES It is recommended that the individual responsible for placing the Double Zn- terlock Preaction System in service de- velop a working understanding of the system in general, prior to placing it in operation. These instructions, as well as individual instructions for the deluge valve, swing check valve, dry pilot actuator, solenoid valve, manual control station, switches, accelerator (if applicable), and pressure mainte- nance device should be reviewed.

After placing a fire protection system in service, notify the proper authori- ties and advise those responsible for monitoring proprietary and /or cen- tral station alarms.

The procedure is as follows:

1. Close the Diaphragm Chamber Supply Control Valve (Fig. D).

2. Operate (open) the Manual Control Station (Fig. D) to assure that the F470 Deluge Valve Diaphragm Chamber is vented.

3. Close the Double Interlock System Main Control Valve (Fig. A), Air Supply Control Valve (Fig. C), and, if applicable, the Accelerator Con- trol Valve (Fig. C).

4. Open the System Main Drain Valve (Fig. C), Main Drain Valve at the rear of the F470 (Fig. D), Inspector’s Test Connection, and all auxiliary drains in the system piping. Check to see that the drain- age water will not cause damage or result in dangerous conditions.

NOTE Do not open the Inspector’s Test Connection and auxiliary drains if resetting after a system test; oth- erwise, system airpressure will be relieved unnecessarily.

Inspect for and clear all ice plugs, where system piping has been ex- posed to freezing conditions and when there has been a flow of water into the system.

Close the System Main Drain Valve. Insoector’s Test Connec- tion, and ail auxiliary drains in the system piping. Leave the Main Drain Valve at the rear of the F470 open.

Depress the plunger of the Auto-

-8-

matic Drain Valve (Fig. D), to verify that it is open and that the F470 Deluge Valve has been completely drained.

8. Clean out the Strainer (Fig. D) in the connection to the F470 Deluge Valve Diaphragm Chamber.

9. Push the F470 Reset Knob inward to allow the Clapper to reseat.

Under normal circumstances, the reseating of the Clapper can be heard. However, after the system inspection procedure, for example, due to minimal flow through a par- tially opened main control valve, the Clapper may not have latched fully open. In this case, the reseat- ing sound of the Clapper will not be heard.

10. Close the Manual Control Station (Fig. D) by pushing the operating lever up. Do not close the hinged cover at this time.

Il. Open the Alarm Control Valve (Fig. D), if it was closed to silence local alarms.

It is recommended that the Alarm Control Valve be wire sealed in the open position with a No. 16 twisted wire, the ends of which are se- cured by a lead seal. The wire seal should be looped through the hole in the handle and tightly twisted around the pipe nipple adjacent to the handle.

12. Replace all damaged or operated sprinklers. Replacement sprinklers must be of the same type and tem- ;;;;rtre rating as those which op-

NOTE In order to prevent the possibility of a subsequent operation of an overheated solder type sprinkler, any solder type sprinklers which were possibly exposed to a temper- aturegreater than their maximum rated ambient must also be re- placed.

13. Service the air dryer, if applicable, in accordance with the man- ufacturer’s instructions.

14. Open (energize) the Solenoid Valve by manually operating the deluge valve releasing panel.

15. Open the Diaphragm Chamber Supply Control Valve (Fig. D) and allow water to discharge from the Dry Pilot Actuator. Close the Dia- phragm Chamber Supply Control Valve when air is no longer present in the discharge from the Dry Pilot Actuator.

OBSOLETE

Page 9: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

16. If resetting after a test, fully open the System Shut-Off Valve (Fig. A), if applicable.

17. Open the Air Supply Control Valve (Fig. C) and pressurize the sprink- ler system in accordance with Graph B.

18. Return the Solenoid Valve to its normally closed position by reset- ting the automatic control unit.

19. Fully open the Diaphragm Cham- ber Supply Valve (Fig. D) and allow time for full pressure to build up in the Diaphragm Chamber of the Multimatic Valve.

20. Operate (open) the Manual Control Station (Fig. D). SLOWLY close the operating lever, by pushing it up, after air is no longer present in the discharge from the drain tub- ing. Close the hinged cover and insert a new break rod (PSN 92- 289-1-008) in the small hole through the top of the enclosing box.

21. Inspect the drain connections from the Dry Pilot Actuator and Manual Control Station for leaks. Leaks, if any, must be corrected before the system is restored to service.

22. Reset the F311 Accelerator (Fig. C) as follows, if the system is so equipped; otherwise, proceed to Step 23.

a. Close the Accelerator Control Valve.

b. Slowly remove the plug from the Strainer at the Accelerator inlet to relieve any inlet pressure. This procedure will trip the Accelerator if it is not already tripped.

c. Clean out the Strainer at the Ac- celerator inlet.

NOTE A clogged strainer can prevent the Accelerator from properly tripping the system.

d. Open the Accelerator Bleed-off Valve (Fig. C) and blow any resid- ual water in the connection to the system piping out through the tube to the Drip Funnel. Close the Bleed-off Valve after water ceases to drain.

e. Open the Accelerator Control Valve one-quarter turn and blow any residual water in the connec- tion to the system piping out through the Strainer.

f. Close the Accelerator Control Valve and replace the Strainer Plug.

g. Slowly remove the Vent Plug lo- cated in the front of the Accelera- tor Cover and bleed off any resid- ual pressure in the Accelerator Differential Chamber.

h. Unscrew (counter-clockwise rota- tion) the knurled Reset Knob at the front of the Accelerator until it resists further turning. A click, which is the sound of the Lever snapping back into the set posi- tion, should be heard. Screw the Reset Knob back in until it is finger tight.

i.

i.

Replace the Vent Plug.

Verify that the system pressure has returned to normal.

k. Using a watch, note the time for the pressure in the Differential Chamber of the Accelerator to in- crease to 10 psi, after the Accel- erator Control Valve is opened. The time should be within the range of values indicated below, for optimum performance of the Accelerator.

System Air Pressure,

PSI 20 25 30 40 50 60

Time to 10 psi, sec. Min. Max.

40 160 29 116 23 92 15 60 12 48 9 36

NOTE Zf the time to pressurize the Dif- ferential Chamber of the F311 Accelerator is not within the range of values given in the above table or any other resetting problem is encountered, the Ac- celerator Control Valve should be closed and corrective action taken (refer to TD109).

I. When the air pressure in the Dif- ferential Chamber of the Acceler- ator is equal to that in the system, the Accelerator is set and ready for service.

23. Slowly open the Main Control Valve (Fig. A). Close the Main Drain Valve at the rear of the F470 as soon as water discharges from the drain connection. Observe the Automatic Drain Valve for leaks. If there are leaks, either the Clapper is not properly seated and the Dou- ble Interlock Preaction System must be reset, or there is internal leakage past the Clapper Facing or Diaphragm. Determine/correct the cause of the leakage problem. If there are no leaks, fully open the Main Control Valve (Fig. A).

24. Verify that the deluge valve releas-

-9-

ing panel is returned to a normal standby condition.

25. It is recommended that the Main Control Valve and the System Shut-Off Valve (if applicable) be locked in the full open position if they are not monitored by supervi- sory switches.

NOTE After placing a fire protection sys- tem in service, notify the proper authorities and advise those re- sponsible for monitoring propri- etary and/or central station alarms.

The Double Interlock Preaction Sys- tem is now set for service.

The Double Interlock Preaction Sys- tem requires regularly scheduled care and maintenance of its principle com- ponents, as described in their individ- ual technical data sheets. In addition, it is recommended that the proper op- eration and condition of the system be periodically verified in accordance with the following described inspection pro- cedure.

Any impairment to the system must be promptly corrected in order to maintain the integrity of the system.

It is recommended that the System Inspection Procedure be performed at least semi-annually by a qualified In- spection Service. The Double Interlock Preaction System Inspection Proce- dure may be followed in lieu of per- forming any of the operational tests recommended in the Technical Data Sheets for the Model F470 Deluge Valve, Model F52OIF5201 Swing Check Valve, Model B-1 Dry Pilot Ac- tuator, 24 VDC Solenoid Valve, Mod- els PSlO-2A and PS40-1A Pressure Switches, and Model F180 Manual Control Station.

NOTES 1. It is recommended that individu-

als responsible for care and main- tenance of the Double Interlock Preaction System develop a work- ing understanding of the system, in general, prior to performing in- spection andlor maintenance procedures. These instructions, as well as individual instructions for the deluge valve, swing check valve, dry pilot actuator, solenoid valve, manual control station, switches, accelerator (if applica- ble), and pressure maintenance device should be reviewed.

2. The following procedures pertain to the automatic control valve

OBSOLETE

Page 10: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

portion of the Double Interlock Preaction System. Refer to the manufacturer’s instructions and NFPA 25 for care and mainte- nance procedures for all other de- vices (e.g., electric detection, main control and system shut-off valves, supervisory devices, sprinklers, etc.).

3. Before performing the System Zn- spection Procedure, which will re- sult in operation of alarms, notify theproperauthorities and allper- sonnel who may be affected.

4. Before closing a fire protection system main control valve for maintenance work on the firepro- tection system which it controls, permission to shut down the af- fected fire protection system must be obtained from the proper au- thorities and all personnel who may be affected by this action must be notified.

System inspection Procedure 1. Close the Main Control Valve (Fig.

A) and then open the Main Drain Valve at the rear of the F470 (Fig. W

2. Open (energize) the Solenoid Valve by manually operating the automatic control unit. Verify that there is no leakage out the Dry Pilot Actuator drain. Also, verify full operation of the deluge valve re- leasing panel and its associated alarms.

NOTES During this procedure, the Sole- noid Valve is opened; however, the Dry Pilot Actuator should remain closed and the F470 Deluge Valve Diaphragm Chamber should re- main pressurized.

This procedure is used to verify that the F470 Deluge Valve will remain set if the ele:tric detection system operates but the sprinkler system remains in its normally pressurized condition.

3. Open the Inspector’s Test Connec- tion but be prepared to close it, as well as the Accelerator Control Valve (Fig. C), if applicable, im- mediately after verifying the follow- ing:

a. If the system is equipped with an Accelerator, verify that the time to Accelerator trip is essentially the same as in previous tests, and verify that the Diaphragm Cham- ber Pressure Gauge (Fig. D) de- creases to a pressure below 25% of the water supply pressure.

b. Verify that the Low Pressure

Alarm Switch (Fig. C) and its as- sociated alarms operate properly. The Low Pressure Alarm Switch should operate at the previously established pressure (refer to In- stallation section, Step 10).

Close the Inspector’s Test Con- nection, and, if applicable, close the Accelerator Control Valve.

4. Close the Diaphragm Chamber Supply Control Valve (Fig. D).

5. Close the System Shut-off Valve (Fig. A) after the system air pres- sure has been restored to normal.

6. Manually restore the electric fire detection system to a normal con- dition in accordance with the manufacturer’s instructions. The Solenoid Valve will then be de-en- ergized and returned to its nor- mally closed position.

7. Open the Diaphragm Chamber Supply Control Valve.

8. Open the Main Control Valve (Fig. A) one turn beyond the position at which water just begins to flow from the Main Drain Valve at the rear of the F470.

9. Close the Main Drain Valve at the rear of the F470 (Fig. D).

10. Close the Air Supply Control Valve (Fig. C).

11. Open the Dry Pilot Actuator by par- tially opening the System Main Drain Valve (Fig. C) to relieve air pressure at the inlet to the Actua- tor. Verify that there is no leakage out the Dry Pilot Actuator.

NOTES During this procedure, the Dry Pilot Actuator is opened; however, the Solenoid Valve should remain closed and the F470 Deluge Valve Diaphragm Chamber should re- main pressurized.

This procedure is used to verify that the F470 Deluge Valve will remain set if the Dry Pilot Actua- tor operates due to loss of system air pressure and the electric detec- tion system remains in a normal condition.

12. Open (energize) the Solenoid Valve by operating the deluge valve releasing panel, and verify the following:

a. Verify that the F470 Deluge Valve operates, as is indicated by a dis- charge of water from the System Main Drain Valve and the Auto- matic Drain Valve. The Automatic Drain Valve may or may not close

depending on the amount of flow past the partially open Main Con- trol Valve.

b. Verify that the Water-flow Pres- sure Alarm Switch (Fig. C) and its associated alarms properly oper- ate.

c. Verify that the Water Motor Alarm, if applicable, properly operates.

NOTE This procedure simulates opening of both the Dry Pilot Actuator (loss of system air pressure) and Sole- noid Valve (operation of the auto- matic control unit) to verify auto- matic system operation.

13. Reset the Double Interlock Dry System in accordance with the Re- setting Procedure section.

Seller warrants for a period of one year from the date of shipment (warranty period) that the products furnished hereunder will be free from defects in material and workmanship.

For further details on Warranty, see Price List.

All orders must include the description and Product Symbol Number (PSN).

NOTES Heat detection equipment and signal- ling devices must be separately or- dered.

To attach the lower flange of the F520 or F5201 Check Valve to the upper flange of the F470 Deluge Valve, as shown in Figure B, at least four out of the eight required flange fasteners must be stud bolts and nuts. The stud bolts, which are to be separately or- dered, must be 5/8”-1lUNC x 3-l/4” long for 4 inch (100 mm) valves and 3/4”-IOUNC x 3-314” long for 6 inch (150 mm) valves.

Use of an automatic pressure mainte- nance device is recommended. Refer to Table A.

When ordering the 4 or 6 inch (100 or 150 mm) Double Interlock Preaction System, ‘the following items selected

-lO-

OBSOLETE

Page 11: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

DELUGE VALVE

Specify: (specify size), Model F470 External Resetting Deluge Valve , PSN (specify).

4 Inch (100 mm) . . . . . . . . . . . . PSN 52-470-l-013 77 Ibs. (34,Q kg)

6 Inch (150 mm) . . . . . . . . . . . PSN 52-470-l-015 111 Ibs. (%I,3 kg)

Specify: (specify size), (specify model) Check Valve, PSN (specify).

SWING CHECK VALVE

4 Inch (100 mm), Model F520 Flange x Flange PSN 52-520-l-013 62 tbs. (26,l kg) 6 Inch (150 mm), Model F520 Flange x Flange PSN 52-520-l-015 93 Ibs. (42,2 kg)

4 Inch (100 mm), Model F5201 Flange x Groove . . PSN 52-520-l-413 51 Ibs. (23,l kg) 6 Inch (150 mm), Model F5201 Flange x Groove . . PSN 52-520-I-615 76 Ibs. (35,4 kg)

ELECJPNEUMATIC DOUBLE

INTERLOCK PREACTION TRIM

Specify: (specify Black or Galvanized) 4 and 6 inch (100 and 150 mm) Electric/Pneumatic Double Interlock Preaction Trim, PSN (specify).

‘Standard Order’ Black . PSN 52-470-l-100 26 Ibs. (11,6 kg) “Special Order” Galvanized . . . PSN 52-470-2-l 00 26 Ibs. (ii,6 kg)

ACTUATION TRIM

Specify: Factory assembled* (specify black or galvanized), Wet Pilot Actuation Trim for use with the Model F470 External Resetting Deluge Valve, PSN (specify)

“Standard Order” Black . . . . PSN 52-470-l-101 28 Ibs. (12,7 kg)

‘Special Order” Galvanized . . . . PSN 52-470-2-101 28 Ibs. (12,7 kg)

* The actuation trim is factory assembled as shown in TDI 16. Unassembled trim can be provided on “special order”.

AUTOMATIC PRESSURE

MAINTENANCE DEVICE

(recommended)

Select one of the following three options and specify: (product name), PSN (specify).

Model F324 Air Maintenance Device (Pressure Reducing Type) . . PSN 52-324-I-002 6.5 Ibs. (2,Q kg) Model F326 Air Maintenance Device (Compressor Control Type) . PSN 52-326-l-001 8.5 Ibs. (3,8 kg) Model F328 Nitrogen Maintenance Device . . . PSN 52-328-l-001 3.7 Ibs. (1,5 kg)

ACCELERATOR (as applicable)

Specify: Double Interlock Accelerator Trim complete with F311 Accelerator, PSN 52-470-I -200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TABLE A

14 Ibs. (6,4 kg)

INDIVIDUAL COMPONENT ORDERING LIST FOR 4 and 6 INCH (100 and 150 mm) ELECTRIC /PNEUMATIC DOUBLE INTERLOCK PREACTION SYSTEMS

from Table A should be ordered:

l Deluge Valve

l Swing Check Valve

l Electric/Pneumatic Double Interlock Preaction Trim

l (Wet Pilot) Actuation Trim

l Automatic Pressure Maintenance Device (recommended)

l Accelerator (as applicable)

Replacement Trim Parts: Specify: (description) for use with Dou- ble Interlock Preaction System, PSN (specify).

Figure C - Double Interlock Preaction Trim

l-250 lb. Air Pressure Gauge . . . . PSN 92-343-l-012

2-114’ Gauge Test Valve . . . . . . . . . . PSN 46-005-l-002

3-Model PSlO-PA Waterflow Pressure Alarm Switch . . PSN 54-281-l-002

4-Model PS40-1A Low Air Pressure Alarm Switch PSN 54-281-l -003

5-114’ Pressure Relief Valve . . . PSN 92-343-l -020

6-l/2’ Globe Valve . PSN 46-047-l -004 7-112’ Swing Type

Check Valve . PSN 46-049-l -004 8-Model B-1 Dry

Pilot Actuator . . PSN 52-280-l -001 9-24 VDC Solenoid

Valve . . . . . . . . PSN 52-287-l -024 10-2’ Angle Valve . . . . . . . . . PSN 46-048-l-009

Figure C - Double Interlock Accelerator Trim

A-Model F311 Accelerator . .PSN 52-31 l-l-001

B-250 lb. Air Pressure Gauge .PSN 92-343-l-012

C-1/2” Y-Strainer. .PSN 52-353-l-005 D-112’ Globe Valve . .PSN 46-047-l-004 E-1/2’ Swing Check

Valve with 3/32” orifice .PSN 52-403-I-004

F-1/4’ Angle Valve .PSN 46-048-l -002

-ll-

OBSOLETE

Page 12: ELECTRIC/PNEUMATIC RELEASE MODEL F470 - 4 and 6 INCH …

@ Reg. trademark of GRINNELL CORPORATION, 3 TYCO PARK, EXETER, NH 03833 A tL/CO INTERNATIONAL LTD. COMPANY

OBSOLETE