Page 1: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE

Service Manual

V3.34

© TATSUNO-BENČ EUROPE a.s. Author: ing. Milan Berka Date: 21st November 2005 Document number: SP003-UK

Page 2: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 2

Performed changes from version 2.18 (2.20): Changed parameter no.4 Internal clocks setting (time/date) Changed parameter no.6 Added time and date to every saved error message Changed parameter no.7 Added time and date to every saved transaction. Reduced the number of saved transaction to 10 for every dispenser

side (A and B) Changed parameter no.44 Pulse rate is set for every pulse generator separately in range 1,00 to 250,00 pulses per liter(default value is 100,00

pulses per liter New parameter no. 46 Volume of the calibration vessel (default 20 liters) New parameter no. 47 Correction coefficient for winter season. Changed parameter no. 60 Value 4 - Calibration mode Revisions of the version 3.00: Version 3.04 20.06.2000 First tested version on station Version 3.05 30.06.2000 Removed parameter 17 - Hose locking. Removed error message E28 too

Changed parameter 18 - Now is not possible to edit time/date in parameter 18.20 and 18.21. Time/date is necessary to set by parameter 4. Added possibility to read last 10 transactions from PDE counter - new protocol command H

Version 3.07 25.07.2000 Changed default values of the parameters 83 = 84 =1 Added E20 - Abortion of the fuelling Version 3.08 25.08.2000 - completed character set for Alphanumeric LCD display. Country code for Romania (P22 = 3) - Parameter no. 67 deleted - set to value 3 - Changed default values of the parameter 11 to 0 - Restricted edition of the daily totals. For reset is possible to use only parameter 15 (or 99) Version 3.09 15.09.2000 - Changed range of the parameter 55 from 1 to 100 cl (for LPG pumps) - It is possible to use LCD displays by parameter P30=4 (6-6-4) or P30=5 (0-6-0) Version 3.10 25.09.2000 Changes for LPG dispenser: Deleted errror message 14. Instead this message use new message “OFF”. Version 3.18 12.02.2001 Version for Romania - with changes according OIML 118 (world standard ) - changed default values of parameters 73 and 74 to value 15 - inserted timeout (1000 ms) after display reset and before start of pumping

- changed default values of parameter 45 to 8 (number of failured pulses) - blocked changes of parameter 39 by calibration switch (SW1) - deleted parameters 34 ,36 and 41 and set to 1

- deleted tests 2,3,4 and 5 in parameter 90. Parameter 90 renamed to „Display test“. - new communication with displays - after display disconnection appears E5 Version 3.23 20.2.2001 Totalisators have own CRC and parameters own CRC. CRC of parameters is checked only when counter is switched

on. If the CRC is invalid then E22 appears and parameters are automatically initialized (totalisers are not resetted !). CRC of totalisers is checked before every fuelling. If the CRC is invalid then E25 appears (dispenser is locked). Toalisers are not resetted.

Version 3.23a 22.3.2001 Last tested ACR version. Version 3.23c 10.5.2001 Repaired mistake in decimal point position of the Slave LCD displays Version 3.23d 15.5.2001 Restored parameter 34 - Amount calculation (1-rounding, 0-cutting)

Version 3.24 19.6.2001 Repaired mistake of amount preselection in case of parameter 44 or 47 are set in decimal (100.40, 1.50...) Version 3.25 10.7.2001 Added parameter value 2 into parameter P49 Version 3.26 30.10.2001 All error mesages is possible to clear from display puting up the nozzle All parameters are saved in EEPROM and independent on battery status (discharge) Version 3.27 22.03.2002 Changes according OIML 117

- added display check during fuelling. Fueling is stopped max 1 second after display disconnection. Displays shows error message E5 (after interconnection) - added test of EPROM data. Every switch on and before every fueling is calculated CRC of program EPROM for validity. If the CRC is not valid appears new error message E13 on both displays - added RAM test. Before every fueling is tested some parts of RAM for read and write. If the test is not valid appears error message E12 on both displays - after counter switch on appears on displays status of SW1 and SW2 switchers (jumpers). 0 – OFF, 1 - ON

Version 3.27 rel2 24.5.2002 Because of new boards PDECPU 2.3 and PDEPWR V3.0 were made following changes: - deleted inputs for tank level sensors - deleted inputs for locking the motors (TM1,TM2...TM5) - deleted setting buttons TL1 ...TL4 from PDECPU - new error code E28 – „Switch Off Due to Overvoltage“ - deleted parameter 80, 81, 83 and 86

Version 3.28 rel1 3.10.2002 Repaired mistake from previous version (preselection)

Changed minimum preselection value. Error E21 appears only i n case when preselection value is equal to 0.

Version 3.28 rel5 11.11.2002 - new parameter P80 – Logical status of nozzle switch input (0-normally open, 1-normally closed). - - modified pulse otput for ultra high flow pump (P20=2 ). Otput sums pulses from inputs P1A and P1B

- new parameter P83 – Pulse Rest Reset (0- without reset, 1- reset)

Page 3: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 3

Version 3.29 rel1 20.11.2002 New parameters for CNG pumps: Parameter 17 – Mass/Volume coefficient and Parameter 36 – Volume displaying for CNG pumps.

Version 3.29 rel2 6.12.2002 New signal input for button TOTAL STOP (for CNG pump) and new error code E26 – „Pump locked due to

TOTAL STOP Switch“. Button TOTAL STOP is necessary to connect to the pins 3 and 15,16 of connector PEX on power supply unit (PDEPWR).

Version 3.32 rel2 27.2.2003 New version, that are valid for both PDECPU and PDEDUO boards, with following changes:

- parameter 01 and 02: deleted totalisers L0 and A0 - parameter 03: default values set to 0.00 (previously 10.00, 11.00....15.00) - parameter 05: shows program version and memmory CRC (of parameters 20-99) - previous parameters 9, 10 and 11 moved to 26, 27 and 28 - parameter 09: changed ! Now it is Maintenance history (previously 98) – last 10 yellow transmitters codes - parameter 10 ans 11 are not used - parameter 14: Actual temperature value near the processor - parameter 16: Manufacturer Check Number. Added number of days to pump lock or F (unlocked) - parameter 25: Configuration change for PDEDUO board and pump BMP514 (pulser P2 maped as P2B) - parameters 26, 27 and 28: previously 9, 10 and 11 - the same function - parameter 34: Added parameter value 2 – rounding to 5 and 0 on the last amount digit - parameter 46: Pulser Connection Check (0-current check, 1-Tatsuno check, 2 – both check) - parameter 50: deleted - parameter 60: deleted values 4 and 5 - parameter 68: Function of the relay RE5 (0-lighting, 1-heating) – default 1. Relay Re5 is switched on at 0°C

and offf at 30°C. Backlight drop of the displays PDEDIL is canceled when the temperature is below 0°C - parameter 72: Valves Delay after pump start - parameter 81: Inputs for motors lock (0-unused 1,3-NO 2,4-NC 3,4 – check during fuelling) - parameter 86: Button Total STOP (0-not used 1-NO 2-NC), standardly 0 - parameter 87: Deleted - parametr 98: moved to 09 - parameter 99: all values are locked by switch SW1

Version 3.34 rel2 3.1.2005

- Temperature correction - parameter 48 - values 1 to 9 for LPG (n-butan) and 10 to 33 for petrol - Time displaying in iddle status of LCD displays - parameter 40, value 2 - Parametrru 81 - values 5,6,7,8 for using Vapour Flow Sensors for vapour recovery system - New error message code E3 and E4 (vapour recovery pump error) - Faster display resetting in case of BMP514 pumps - Controling new signal LED on display (vapour recovery / locking) - Controling new electromechanical totalisers PDESU1 and PDESU4 - parameter 74 to 1. New error code E6.

Page 4: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 4

1. Dispenser counter parameters setting There are exists three operating modes how to read or set dispenser’s parameters:

a) Attendant mode

b) Registration mode

c) Maintenance mode

On attendant mode is allowed only to read out values of the basic parameters (from 01 to 07). Change of any parameter is not allowed. It is necessary to use white manager remote controller (button “R”).

On Registration Mode is allowed to read out and set advanced parameters (from 01 to 19). This is the mode for entering various registration data for functioning the dispensing pump. It is necessary to use white manager remote controller (button “M”). After fuelling, return nozzle to hook to be standalone position first (clear all transactions on controlling computer). Press “M” key, and then a registration password can be entered. The password can be changed freely by registration (parameter No.5), but it has been set 1111 temporarily.

On Maintenance Mode is allowed to read and set all possible parameters ( from 01 to 99). The maintenance mode is the mode for inputting various registration data for functioning the dispensing pump, same as the registration mode, and its handling requires sufficient caution because it involves parameters with the basic functions of the dispensing pump. It is necessary to use yellow maintenance remote controller (button “R). After fuelling, return nozzle to hook to be standalone position first (clear all transactions on controlling computer). Press “R key, and then a maintenance password can be entered.

Page 5: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 5

1.1. Counter setup by remote transmitter PDERT-1 In case when PDE electronic counter display is equipped with infra receiver it’s possible to use remote transmitter PDE-1 for counter setup.

PDE remote transmitter has following keyboard layout:

The keys has following functions:

• working mode:

<C> Pump side release after error or payment

<0> Pump release after error or payment (both sides).

<1> Preselection key No.3 (10 liters)

<2> Preselection key No.4 (1 liter)

<4> Preselection key No.1 (100 $)

<5> Preselection key No.2 (10 $)

<6> Preselection key No.5 - “Cancel preselection”

<7> Switch ON dispenser lighting tubes.

7 8 9

4 5 6

1 2 3

M 0 R

< > C

- + E

ON OFF

A1 CLEAR

L1 L2

A2

PDE REMOTE TRANSMITTER

Zapnutí osvětlení Switch on the lighting Включение освещения

Předvolba částky č.1 Amount preselection #1 Предзаказ суммы №1

Předvolba objemu č.1 Volume preselection #1 Предзаказ объема №1

Manažerský režim Manager mode Режим менеджера

Odblokování stojanu Unlock dispenser Отмена блокировки

Předchozí parametr Previous parameter Предыдущий параметер

Předchozí podparametr Previous subparameter Предыдущий подпарам.

Vypnutí osvětlení Switch off the lighting Выключение освещения

Zrušení předvolby Cancel preselection Отмена предзаказа

Operátorský režim Attendant mode Режим персонала

Zruš (bez uložení) Cancel (without save) Отмена (без сохранения)

Potvrzení / Změna Enter / Edit Потвержд./Изменение

Další parametr Next parameter Следующий параметер

Předvolba objemu č.2 Volume preselection #2 Предзаказ объема №2

Další podparametr Next subparameter(item) Следующий подпарам.

Předvolba částky č.2 Amount preselection #2 Предзаказ суммы №2

Zobrazení objemu CNG Volume display CNG Изображение обьёма CNG

Page 6: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 6

<8> Display volume on CNG pump (calculated from mass and coefficient in par.17)

<9> Switch OFF dispenser lighting tubes.

• setup mode start:

<R> Starts attendant mode or maintenance mode (yellow maintenance remote controller)

<M> Starts registration mode.

• parameters listing:

<4> Skip to next parameter.

<3> Skip to previous parameter.

<+> Skip to following parameter item.

<-> Skip to previous parameter item.

<E> Edit value displayed parameter value (if allowed).

<0>...<9> Jump to parameter number.

<M>,<R> Setup mode end (attendant, registration or maintenance mode).

• parameter value change and entering the password:

<0>...<9> Entering parameter value.

<+> Increase edited parameter value.

<-> Decrease edited parameter value.

<4> Skip to next edited value digit.

<3> Skip to previous edited value digit.

<E> Save parameter value changes & Quit edit.

<C> Cancel parameter value changes & Quit edit.

1.2. Displaying data in setup mode

Parameter No.: 01 Item No.: 2 Auxiliary code: L Parameter value: 327890,13

00003.2 7890.13

$

Liters

$/liter 01.L2

Auxiliary code

Parameter number

Item number

Page 7: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 7

1.3. SETUP parameters Notes: O – parameters enabled to read-out in attendant mode, M - parameters enabled to read-out and change in registered mode (possible to use white remote controller), S - parameters enabled to read-out and change in maintenance mode (necessary to use yellow remote controller), - switch SW1 will have to be ON (right position) in case of parameter change

Parameter

No. Values range Description Default values

(after total reset)

01 OMS®

0 – 40 mil. liters

Nonresetable totalisers - volume totalisers for all dispensing hoses L1, L2....L9,LH (L10) - edit and reset allowed only in maintenance mode <R> - value change is locked by switch SW1

0.00

02 OMS

0 – 40 mil. liters 0 – 400 mil. curr.units

Daily totalisers - volume totalisers for all dispensing hoses L1, L2....L9,LH (L10) - amount totalisers for all dispensing hoses A1, A2....A9,AH (A10) - reset of all totals by parameter 15

0.00

03 OMS

0000-9999 Unit price for manual mode - prices of products 1,2..5, valid in manual mode only

1-0.00, 2-0.00, 3-0.00, 4-0.00, 5-0.00

04 OMS

Date/Time - internal clock setting: hh-mm-ss-DD-MM-YY

05 OMS

Programm version and parameter memmory checksum (CRC) - checksum of the parameters from 20 to 99

CRC=22384 Version=3.32

06 OMS

Error codes history - last 10 error codes for both dispenser's sides (A and B) with date and time (after pressing <E>). 0 = no error.

0

07 OMS

Transaction history - last 10 fuelings for both dispenser's sides (A and B) with date and time (after pressing <E>). Error = empty.

0

08 MS

0000-9999 Registered mode password - 4 digits

1111

09 S

Maintenance history - last 10 service remote transmitter codes

0

10-11 Not used

12 MS

0-4

Working mode 00 Automatic

dispenser is fully controlled by Master device (PC, POS...), manual mode is not available, unit price is send from Master. Behaviour of the displays after "payment" follows setting of the parameters 40 and 69

01 Manual with autoconvert to Automatic dispenser works in manual mode with manual unit prices (par.3) till the time when is connected Master device (PC, POS..), than the working mode is converted to automatic working mode.

02 Manual with autoconvert to Automatic and locking after fueling dispenser works in manual mode with manual unit prices (par.3) till the time when is connected Master device (PC, POS..), than the working mode is converted to automatic working mode. After every fueling the dispenser is locked and it is necessary to release dispenser by special operator magnet or IR remote transmitter (button "C" or "0"). Behaviour of the displays after "release" follows setting of the parameters 40 and 64.

03 Manual dispenser works in stand alone with manual unit prices (parameter 3), communication with any Master device is restricted.

1

13 MS

Error statistics - cumulative numbers of all error codes

0

Page 8: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 8

Parameter No.

Values range Description Default values

(after total reset)

14 MS

Current temperature - temperature near the processor. Update after every minute by pressing <E>

15 MS

0,1 Daily totalisers reset - reset of all totalisers in parameter 2

0 Idle state 1 Reset

0

16 MS

Manufacturer's check number - manufacturer's check number necessary for unlocking of the locked dispenser and number of days to dispenser lock (F - lock disabled). Manufacturer's lock is possible to set by parameters 78 and 79.

000000 F

17 MS

0 až 10000 Mass/Volume coefficient for CNG dispensers - measured mass of the CNG is divided by this coefficient and displayed after fueling and pressing <8> on IR remote transmitter. Displaying of the recalculated volume is possible to set by parameter 36. Common coefficient value is 7080 ( = 0.7080)

10000 (coeff. = 1.0000)

18 MS

0,1,2 Text messages for alphanumeric LCD display - text messages on 8 characters display. Funkcion has follows 22 subparameters:

01 – product name #1 (BenzBLF) 02 – product name #2 (Benzin) 03 – product name #3 (Super) 04 – product name #4 (Diesel) 05 – product name #5 (Bio) 06 – reserved 07 – reserved 08 – reserved 09 – text for "End of fueling" (Payment) 10 – text for "Locking" (Locked) 11 – text for "Advertisement 1" (Welcome) 12 – text for "Advertisement 2" () 13 – text for "Advertisement 3" () 14 – text for "Advertisement 4" () 15 – text for "Advertisement 5" () 16 – text for "Advertisement 6" () 17 – text for "Advertisement 7" () 18 – text for "Advertisement 8" () 19 – text for "Advertisement 9" () 20 – current time 21 – current date 22 – currency unit ($) 23 – volume unit (Lt)

Current time and date are set by parameter 4 !! Is necessary to set parameter 30 to value 3 (alphanumeric LCD display)

0-not display 1-display message 2-edit message

19 MS

0,1 Display error (E1) - disabled/enabled display error message (failure of the display segment)

0 disabled E1 1 enabled E1

1

20 S

0,1,2 Dispenser configuration - dispenser configuration

0 two-sided dispenser 1 one-sided dispenser 2 one sided, ultra-high flow dispenser (linked pulsers 1A and 1B)

0

21 S

1-50 Communication address - one addres for side A, one address for side B (one-sided dispenser has A side only)

A = 1, B = 2

22 S

0,1,2,3 Country code for alphanumeric LCD display - code for character set and decimal point

0 Czech Republic 1 Slovakia 2 Russian 3 Romania

0

23 S

1,2..5 Number of products

5

Page 9: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 9

Parameter No.

Values range Description Default values

(after total reset)

24 S

1,2..8 Product code - every fuel product has assigned product code (number from 1 to 8) – product codes will have to correspond with product codes in Master device (PC, POS...). Otherwise fueling will not start.

1-1, 2-2, 3-3, 4-4, 5-5

25 S

0, 1 PDEDUO pulser 2 configuration - parameter is valid only in case board PDEDUO.

0 Pulser 2 = P1B (BMP512) 1 Pulser 2 = P2B (BMP514)

0

26 MS

1 to 9900 Maximum pumped volume - maximum volume pumped during one transaction in litres

9900 liters

27 MS

1 až 990000

Maximum pumped amount - maximum amount pumped during one transaction in currency unit

99000.0 currency unit

28 MS

0,1,...100 Maximum pumped time - maximum pumping time in minutes (0 - not limited)

0....not limited

29

Not used

30 S

0,1,2,3 Display type 1 - FP (6-6-4) 2 - Liter FP (0-6-0) 3 - Alphanumeric LCD (8-6-6) 4 - LCD (6-6-6) 5 - Liter LCD (0-6-0)

1

31 S

1,2,3 Displays number per side 1 one display (Master) 2 two displays (Master+Slave - old version) 3 two displays (Master+Slave - new version)

A=1, B=1

32 S

0,1 Electronic totalisers 1 allowed 2 not used (parameters 01 and 02 will not be displayed)

1

33 S

0,1,2 Display amount multiplying coefficient 0 x 1 (for Rusia, Ukraine, Belorussia, Romania....) 1 x 0.1 (for Czech Republic, Slovakia...) 2 x 0.01

1

34 S

0,1,2 Amount rounding 0 amount cutting (25.87 Kč -> 25.8 Kč) 1 standard rounding (25.87 Kč -> 25.9 Kč) 2 rounding to last digit 5 and 0

(25.24 Kč -> 25.0 Kč, 25.25 Kč -> 25.5 Kč, 25.74 Kč -> 25.5 Kč, 25.75 Kč -> 25.5 Kč)

1

35 S

0,1,2,3 Decimal point position (LCD displays) - position of the decimal point on amount and unit price displays

1-2-2

36 S

0,1,2...20 Volume display for CNG dispensers - number of seconds after end of pumping for displaying calculated volume (m3) instead the measured mass (kg). To display volume immediatelly press <8> on the IR remote transmitter. The mass/volume coefficient is posible to set by parameter 17.

0

37-38

Not used

39 S®

0,1,2...20 Hose dilatation suppresion - volume in centilitres after start of pumping that will not be displayed on the displays. Data line sending to Master (PC, POS..) real pumped volume. - value change is locked by switch SW1

6

40 S

0,1 Display reset mode 0 Amount + Volume = zeroes, Unit Price = cleared 1 Amount + Volume = zeroes, Unit Price = displayed 2 Time displayed in iddle status (only in case of PDEDIL displays)

- value 0 is used for MPD dispensers, value 1 for one product dispensers.

0

Page 10: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 10

Parameter No.

Values range Description Default values

(after total reset)

41-42

Not used

43 S

1,2,...10 Display data update frequency - number of updates per second - on FP displays recommended max. 5, on LCD displays 10

5

44 S®

from 1.00 to 500.00

Pulser generator - number pulses per revolution - for every pulser generator (P1, P2...P10) - value change is locked by switch SW1

100.00 pulses/litre

45 S®

0,1,2...99 Number of the failed pulses - for every pulser generator (P1, P2...P10) - reaching the limit appears error message E31, E32...E40 (pulser P1,P2...P10) - value = 0 – failed pulses are not counted - value change is locked by switch SW1

8

46 S®

0,1,2 Pulser check mode 0 Power current check (only for PDEDUO ) 1 Tatsuno check signal (for PDECPU) 2 both (only for PDEDUO)

- after failure appears message E41, E42....E50 (pulser P1,P2...P10) - value change is locked by switch SW1

1

47 S®

0 to 50.00 Pulse generator correction - for every pulser generator (P1, P2...P10) - pulse correction is active when the SW2 switch is ON (right position). Then value of pulse correction will be subtracted from the value of the parameter 44. - value change is locked by switch SW1

0.00

48® S

0,1,2..33 Temperature pulse correction - objem je korigován počítadlem vůči objemu při 15°C. - values 1, 2, 3 and 9 are valid for liquid n-butan mixtures (propan/ butan) - values 10, 11, 12 and 33 are valid for petrol - value change is locked by switch SW1

0...no correction typical values: 7...LPG (P30/B70) 31...diesel (830-860) 23...benzin (740-750)

49 S

0 to 50.00 Calculated Preset volume rounding - the way how the preset volume will be rounded

0 rounding up 1 rounding down (cutting) 2 standard rounding (<4 down, ≥5 up)

Example: price= 18.20 Kč/lt and preselected amount =100.0 Kč, calculated preset volume (5.4945 lt) will be rounded to 5.50 if P49=0 and to 5.49 if P49=1 or 2

1

50

Not used

51 S

1,2..30000 Preselection keyboard - 4 buttons + button "Cancel". Every button is possible to set on value 1 to 30000 and define if it is amount (A) or volume (L) preselection.

1-100.0 (A) 2-10.0 (A) 3-10.00 (L) 4-1.00 (L)

52 S

0,1,2...10 Preselection rounding - how many pulses is allowed to overfill in preselection pumping. If defined limit of pulses is overfilled then appears error message E51, E52...E60 (preselection was exceeded) Example: price= 18.20 Kč/lt and preselected amount = 100.0 Kč, pumping will stop on amountě 100.0 Kč in case, P52 = 1,2..and more. In caseP52= 0, then pumping stops on amount 99,9 Kč (P49=1) or 100.1 Kč P49=0).

2

53 S

1,2...200 Keyboard preselection timeout - Number of seconds after typing preselection when the preselection value is valid. If the timeout is exceeded the preselection values are cancelled and pump will be pumping till maximum values (see parameters 26, 27 and 28)

30

54 S

1,2..40 Slow down valve control - fuel volume before preselected volume (x 0.1 liter), when the slow down valve will be open only.

12 (1.2 litru)

55 S

1,2...100 Slow down after start of pumping - fuel volume after start of pumping (x 0.01 liter) after which the slow down valve is open and dispenser starts to pump on maximum flow.

5

Page 11: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 11

Parameter No.

Values range Description Default values

(after total reset)

56 S

0,1,2...200 Slow down after interruption of the pumping (last pulse) - time in seconds after last pulse after that will be closed the slow down valve and the fuel flow will be decreased to minimum. After first pulse from pulser the slow down valve will be open according to parameter 55 .

5

57-59

Not used

60 S

1,2,3 Dispenser's mode 1 working mode

2 training mode (simulated flow 60ltrs/min, without pumping, without totalisers) 3 working mode with flow measuring (current flow is displayed on unit price display instead of price)

1

61

Not used

62 S

0,1,2 Manual release - type of manual release

0 release by operator magnet 1 release by IR remote transmitter (pressing button <C> or <0>) 2 release by IR remote transmitter and/or operator magnet

Manual release of dispenser is used when dispenser works in mode with locking after pumping (P12=2).

2

63

Not used

64 S

0,1,2...999 Display reset after manual release - time in seconds after that the display will be reset

0 display reset performed immediately after manual release 1,2..998 display reset after1,2...998 seconds after manual release 999 display reset disabled

- the mode of display reset is controlled by parameter 40

0

65

Not used

66 S

0,1,2..60 Timeout between end/start pumping - minimum time in seconds

3

67

0,1 Temperature sensor (only for PDEDUO) 0 on board PDEDUO (near processor) 1 on board PDEINP

0

68 S

0,1 Relay RE5 function 0 relay controls dispenser lighting 1 relay controls heating ( t < 0°C - ON, t >30°C – OFF)

- temperature is measured cca one times per minute

1

69 S

0,1,2...999 Display reset after Master release (automatic mode) - time in seconds after receiving command from Master device, when the display will be reset

1 display reset performed immediately after Master release 1,2..998 display reset after1,2...998 seconds after Master release 999 display reset disabled

- the mode of display reset is controlled by parameter 40

0

70

Not used

71 S

0,1,2...200 Follow-up time - how long (x 0,1 sec) will be counted pulses after nozzle down.

10

72 S

0,1,2...200 Valve delay - time delay (x 0,1 sec) at the start of pumping between start of pump motor and opening the controling valve.

0

Page 12: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 12

Parameter No.

Values range Description Default values

(after total reset)

73 S®

0,1,2...200 Display test delay - time of displaying "8"--> nothing -->0.00 on display after nozzle up (x 0,1 sec) - delay of every phase of the reset (total time is 3x longer) - value change is locked by switch SW1

15

74 S®

0,1 Electromechanical volume totalisers 0 disabled 1 enabled

- value change is locked by switch SW1

0

75 S

0,1,2...1000 Time without pumping (after last pulse) - maximum time without pumping in seconds. 0 – time is unlimited. After the time is exceeded pumping is interrupted and on display appears "OFF". Message OFF disappears after nozzle down.

60

76 S

1,2...60 Communication timeout - delay in seconds from the moment of losing communication with Master (PC, POS...). On display appears error message "E18". After communication recovery message E18 disappears.

3

77 S

0,1 Low voltage behaviour - behaviour of the dispenser after voltage drop (longer than 2 seconds) below 180 Volts

0 pumping continues – message E19 is saved into error history 1 pumping is interrupted – message E19 is displayed on display and

saved into error history

1

78 S

0,1,2 Manufacturer's lock 0 pump is not locked 1 pump is locked 2 pump will be locked after time set in parameter 79

After pump is locked appears message E27 + six digits code on amount display. Unlocking is possible to make by set P78 to 0 or enter authorization code into parameter 16.

1

79 S

0,1,2..1000 Manufacturer's lock timer - number of operation days to pump lock

20

80 S

0,1 Logical state of the nozzle input - logical state for every nozzle input (N1, N2....N10)

0 NO – normal open (nozzle up = closed) 1 NC – normal closed (nozzle up = open)

1-0, 2-0,....9-0,H-0

81 S

Auxiliary Inputs for locking the pump motors & vapour flow sensors - when the appropriate input is active then the pump motor is switched off and on displayappears message P1, P2....P5 (number of motor). After nozzle down message disappears.

2 inputs are disabled 3 not used 4 not used 5 lock the motor - contacts NO (normal open) 6 lock the motor - contacts NC (normal closed) 7 vapour flow sensor - contacts NO (normal open) without pump locking 8 vapour flow sensor - contacts NC (normal closed) without pump locking 9 vapour flow sensor - contacts NO (normal open) with pump locking 10 vapour flow sensor - contacts NC (normal closed) with pump locking

0 - default 6 - used sensor VRS1 without locking pump 8 - used sensor VRS1 with locking pump

82 S

0,1 Output pulses related to products - pulser output state for every product

0 disabled 1 enabled

1-0, 2-0, 3-0, 4-0, 5-0

83 S

0,1 Output pulse rest reset before pumping 0 disabled 1 enabled

0

84 S

0,1 Vapour recovery relays related to products - for every product is possible to set function of the vapour recovery relays RPA and RPB.

0 relays disabled 1 relays enabled

1-1, 2-1, 3-1, 4-1, 5-1

85 S

0,1,2..60 Delay of vapour recovery relays - delay after last pulse (in seconds) to switch off. if the value is equal to 0 then relays RPA and RPB will be open after nozzle down (end of pumping)

5

Page 13: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 13

Parameter No.

Values range Description Default values

(after total reset)

(end of pumping).

86

Input for TOTAL STOP button - when the input is activated then all relays are open and pumping is interrupted.On display appears message E26.

0 disabled 1 normal open (activated when closed) 2 normal closed (activated when open)

87

Not used

88 S

Maintenance mode password - 8 digits (yellow IR remote transmitter + <R>)

11111111

89

Not used

90 S

0,1 Display test - cyclic test – 0 -1-2-3-4-5-6-7-8-9-0-1..... . <C> Cancel test

0 test disabled 1 test enabled

0

91-93

Not used

94 S

0,1,2 Clear data memory 0 idle state 1 clear error data and transactions (P6,P7 a P13) 2 clear eror data only (P6 a P13) 3 clear transactions only (P7)

0

95-98

Not used

99 S®

0,1,2 Memory initialization 1111 memory initialization without totalisers 6666 totalisers reset 9999 total memory initialization including totalisers reset - values are locked by switch SW1

0

Page 14: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 14

2. Error messages Hitherto, the dispensing pump has been equipped with the self-diagnostic function, and the internal functions

have been checked in order to operate always correctly as the measuring instrument. In the case of dispenser error the pump is locked and appropriate error code is displayed. The error message on display is possible to clear by remote controller (pressing “0”) or putting nozzle down and up from nozzle boot after repair.

2.1. Error messages codes

Code Meaning Notes StoP Maximum time without pulse was exceeded.

– set in parameter 75 Take nozzle on hook. The error message disappears.

E 1 Display error – Failure of the segment of LCD or Ferranti display

Change display

E 2 Display error - Discrepancy between real number of displays and number of displays in setup (parameter 31)

Set the parameter P31

E 3 Vapour Flow Sensor A Error Check parameter 81, check vapour flow sensor VRS1 on side A, check vacuum pump on side A

E 4 Vapour Flow Sensor B Error Check parameter 81, check vapour flow sensor VRS1 on side B, check vacuum pump on side B

E 5 Display error - Display don’t answer (communication error)

Check display cables or change the display

E 6 Electromechanical totalisers error Check cables, check parameter 74 E 8 EEPROM error - Read/Write failure

Check the jumper WP on PDEDUO

E 9 Internal processor error – Power switches controlling circuits failure

Check the cable between PDECPU and PDEPWR, or change one of the board PDECPU or PDEPWR

E 10 Temperature sensor error

Check parameter 48, check board PDEINP, check temperature sensor

E 11 Controlling parameters error (after EPROM change orparameter’s initialization)

Switch OFF and switch ON the counter and check the parameters

E 12 RAM error Change PDECPU board

E 13 EPROM error Change program EPROM

E 15 Maximum time for fuelling was reached.

Check parameter 28

E 16 Communication error – Dispenser is unable to communicate with credit module PDECRE

Check display cable.

E 17 Communication error – Dispenser is unable to communicate with dispenser, line error

Check communication line setting or addresses

E 18 Communication error – Dispenser is unable to communicate with dispenser, see parameter P76

Computer is not connected or doesn’t communicate with dispenser

E 19 Power down error - Power supply voltage was lower than 180V for time longer than 2 seconds

Check dispenser power supply

E 20 Last fuelling was interrupted by power down Check the power supply

E 21

Preselection value error - Preselection is equal to 0. Set non-zero preselection volume (amount).

E 22

Fatal memory error - Invalid CRC of parameters in EEPROM and RAM - memory initialization

Switch OFF and switch ON the counter. Memory initialization will be provided.

E 23

Memory error - Invalid CRC of parameters in EEPROM memory

Switch OFF and switch ON the counter.

Page 15: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 15

Code Meaning Notes E 24

Memory error - Invalid CRC of parameters in RAM memory

Switch OFF and switch ON the counter.

E 25

Totalisers error - Invalid CRC of totalisers in memory, totalisers were cleared

Switch OFF and switch ON the counter. Check the totalisers

E 26

TOTAL STOP button Put nozzle down and up from nozzle boot

E 27 Dispenser is locked by manufacturer Set parameter P78 to value 0 or enter secret code

E 28 Switch Off Due to Overvoltage U>265V E 29 Invalid password Enter valid password E 30 Product unit price is zero Set nonzero unit price E 31 Pulse generator error - Pulse channel error or double

pulse check error Pulse generator 1 (1A)

E 32 Pulse generator 2 (2A) E 33 Pulse generator 3 (3A) E 34 Pulse generator 4 (4A) E 35 Pulse generator 5 (5A) E 36 Pulse generator 6 (1B) E 37 Pulse generator 7 (2B) E 38 Pulse generator 8 (3B) E 39 Pulse generator 9 (4B) E 40 Pulse generator 10 (5B)

Check the pulse generator channel connection and parameter P45 Tatsuno pulse generator: 2-green (ch A), 3-white (ch B) Hectronic Kienzle pulse generator: 2-green (ch A), 3-white (ch B) Eltomatic pulse generator: 2-white (ch A), 3-yellow (ch B)

E 41 Pulse generator error – Pulse generator power supply error or pulse generator is not connected Pulse generator 1 (1A)

E 42 Pulse generator 2 (2A) E 43 Pulse generator 3 (3A) E 44 Pulse generator 4 (4A) E 45 Pulse generator 5 (5A) E 46 Pulse generator 6 (1B) E 47 Pulse generator 7 (2B) E 48 Pulse generator 8 (3B) E 49 Pulse generator 9 (4B) E 50 Pulse generator 10 (5B)

Check the pulse generator: connection Tatsuno pulse generator: 1-red (5V), 2-green (ch A), 3-white (ch B), 4-yellow (CHCK), 5-black (0V)

Hectronic Kienzle pulse generator: 1-yellow (5V), 2-green (ch A), 3-white (ch B), 4-brown (0V), 5-brown (0V)

Eltomatic pulse generator: 1-green (5V), 2-white (ch A), 3-yellow (ch B), 4-brown (0V) 5-brown (0V)

E 51 Controlling valve error – Preselection value was exceeded Hose 1 (1A)

E 52 Hose 2 (2A) E 53 Hose 3 (3A) E 54 Hose 4 (4A) E 55 Hose 5 (5A) E 56 Hose 6 (1B) E 57 Hose 7 (2B) E 58 Hose 8 (3B) E 59 Hose 9 (4B) E 60 Hose 10 (5B)

Check valves and setting of the parameter P52 (min. 1 liter - low flow, 1.2 liter – high flow)

Page 16: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 16

3. Appendixies

3.1. Preselection on the dispensers Electronic counter PDE offers four variants how to use preselection on the dispensers:

Var. Parameters setting #49 & #52

Preset amount [Euro]

Preset price

[Euro/liter]

Preset volume

(calculated)

Preset volume

(displayed)

Fuelled volume [liters]

Fuelled amount [Rub]

Variance

[Rub] A Parameter 49 = 0

Parameter 52 = 0

10,00

01,82

5,4945055

5,50

5,50

10,01

0

B Parameter 49 = 0 Parameter 52 = 1,2…

10,00

01,82

5,4945055

5,50

5,50

10,00

+ 0,0100

C Parameter 49 = 1 Parameter 52 = 0

10,00

01,82

5,4945055

5,49

5,49

9,99

0

D Parameter 49 = 1 Parameter 52 = 1,2…

10,00

01,82

5,4945055

5,49

5,49

10,00

- 0,0082

E Parameter 49 = 2 Parameter 52 = 0

10,00

01,82

5,4945055

5,49

5,49

9,99

0

F Parameter 49 = 1 Parameter 52 = 1,2…

10,00

01,82

5,4945055

5,49

5,49

10,00

- 0,0082

Variant A – Fuelled amount is not rounded. Fuelled amount corresponds with fuelled volume. In some cases fuelled amount is not equal to preset amount – fuelled amount is equal or higher than preset amount. Result: Dispenser sometimes overfill the preset amount. Calculation „Price“ x „Volume“ is every time OK. Variant B – Fuelled amount is every time rounded to preset amount. Fuelled amount in some cases doesn‘t correspond with fuelled volume. Fuelled rounded amount is every time lower or equal to real (calculated) amount (service station owner somtimes losing money). Preset amount is every time equal to the fuelled amount. Result: Dispenser every time fuels exactly the preset amount. Calculation „Price“ x „Volume“ is in some cases higher than fuelled amount. Variant C – Fuelled amount is not rounded. Fuelled amount corresponds with fuelled volume. In some cases fuelled amount is not equal to preset amount – fuelled amount is equal or lower than preset amount. Result: Dispenser sometimes doesn‘t reach the preset amount. Calculation „Price“ x „Volume“ is every time OK. Variant D – Fuelled amount is every time rounded to preset amount. Fuelled amount in some cases doesn‘t correspond with fuelled volume. Fuelled rounded amount is every time higher or equal to real (calculated) amount (customer sometimes losing money). Preset amount is every time equal to the fuelled amount. Result: Dispenser every time fuels exactly the preset amount. Calculation „Price“ x „Volume“ is in some cases lower than fuelled amount. Variant E – Fuelled amount is not rounded. Fuelled amount corresponds with fuelled volume. In some cases fuelled amount is not equal to preset amount – fuelled amount is equal or lower than preset amount. Result: Dispenser sometimes doesn‘t reach or overfill the preset amount. Calculation „Price“ x „Volume“ is every time OK. Variant F – Fuelled amount is every time rounded to preset amount. Fuelled amount in some cases doesn‘t correspond with fuelled volume. Fuelled rounded amount is every time higher, lower or equal to real (calculated) amount (customer or service station owner sometimes losing money). Preset amount is every time equal to the fuelled amount. Result: Dispenser every time fuels exactly the preset amount. Calculation „Price“ x „Volume“ is in some cases lower or higher than fuelled amount.

Page 17: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 17

Examples of fuelling on preset (P52>2)

Preset and fuelled volume [x10-3ltr] Preset and fuelled

amount Fuel Price

Calculated volume

[x10-3ltr] P49=0 P49=1 P49=2 131.31 7.37 17.8168250 17.82 17.81 17.82189.73 7.37 25.7435550 25.75 25.74 25.74

51.00 7.37 6.9199457 6.92 6.91 6.9258.00 7.37 7.8697422 7.87 7.86 7.8732.48 7.37 4.4070556 4.41 4.40 4.4144.44 7.37 6.0298507 6.03 6.02 6.03

127.26 7.37 17.2672999 17.27 17.26 17.27102.00 7.37 13.8398915 13.84 13.83 13.84131.31 10.00 13.1310000 13.14 13.13 13.13189.73 10.00 18.9730000 18.98 18.97 18.97

51.00 10.00 5.1000000 5.10 5.10 5.1058.00 10.00 5.8000000 5.80 5.80 5.8032.48 10.00 3.2480000 3.25 3.24 3.2544.44 10.00 4.4440000 4.45 4.44 4.44

127.26 10.00 12.7260000 12.73 12.72 12.73102.00 10.00 10.2000000 10.20 10.20 10.20

50.00 10.00 5.0000000 5.00 5.00 5.0050.05 10.00 5.0050000 5.01 5.00 5.0149.99 10.00 4.9990000 5.00 4.99 5.0010.00 3.00 3.3333333 3.34 3.33 3.3310.01 3.00 3.3366667 3.34 3.33 3.3420.00 3.00 6.6666667 6.67 6.66 6.6729.99 3.00 9.9966667 10.00 9.99 10.0030.00 3.00 10.0000000 10.00 10.00 10.0033.33 3.00 11.1100000 11.11 11.11 11.1133.32 3.00 11.1066667 11.11 11.10 11.1133.35 3.00 11.1166667 11.12 11.11 11.12

100.00 18.20 5.4945055 5.50 5.49 5.49

Page 18: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 18

3.2. Electronic calibration of the pump flow meters

Electronic calibration enables to calibrate mechanical flow meters by change of parameter 44 (pulse rate) of the appropriate flow meter.

Calibration routine:

Switch the SW1 of the PDECPU into position ON (right)

Take maintenance remote controller. Go into maintenance mode and set parameter 12 to value 3 (stand alone mode) and set parameter 44 to value 100.00 for tested flow meter.

Go out from the maintenance mode (press <M> or <R>)

Take nozzle that you need to calibrate and fill fuel into calibration vessel (2, 5, 10, 20, 50 or 100 litres).

After filling exactly vessel volume return nozzle to nozzle hook. See filled volume on display and find corresponding value of the pulse rate in calibration table.

For example: value 19.98 (vessel 20 litres) corresponds with pulse rate value 99,90 in calibration table D.

Go into maintenance mode and set the parameter 44 to new pulse rate value

Go out from the maintenance mode (press <M> or <R>)

Take nozzle and make testing filling into calibration vessel (2, 5, 10, 20, 50 or 100 litres).

Take the maintenance remote controller and go into maintenance mode and set parameter 12 back to 1 or 0.

Go out from the maintenance mode

Switch the SW1 into position OFF (left)

Page 19: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 19

3.3. Twice flow meter setting in Russian countries

In Russian countries is necessary to use two different flow meter setting (pulse rate), one for summer period and other one for winter period. In PDE electronic counter with version 3.00 values is this solved by switch SW2. When the switch SW2 is on OFF position (left) then counter works with summer period pulse rate setting and when the switch SW2 is on ON position (right) then counter works with winter period pulse rate setting.

In summer period SW2=0FF) is taken for pulse rate value of the parameter 44.

In winter period (SW2=ON) is taken for pulse rate subtraction of values of the parameter 44 and 47 (44-47)

In winter period must be the pulse rate lowe than in summer period because the same amount of the fuel have lower volume in winter. How to set summer/winter pulse rate? Follow next steps:

In summer period

Switch SW2 into left position (OFF) and perform pulse rate calibration of the parameter 44 according above-mentioned calibration methods.

In winter period

Take maintenance remote controller. Go into maintenance mode and set parameter 12 to value 3 (stand alone mode).

Perform testing filling into calibration vessel and find the volume different (in winter you must fill lower volume of the petrol into calibration vessel than in summer time). For example: in winter you fill 0.05 litres less into 20 litres calibration vessel than in summer (summer = 20.00 litres / winter 19.95 litres).

The volume summer/winter difference strongly depends on type of the fuel and measuring temperature.

In table A, B, C, D, E or F find corresponding pulse rate correction value and set this value into parameter no.47. For example: for temperature difference value 0.05 litres is pulse rate correction 0.25 pulse per litre (for calibration vessel 20 litres)

Go into maintenance mode and set the parameter 47 to new correction value

Go out from the maintenance mode (press <M> or <R>)

Switch SW2 into right position (ON), take nozzle and make testing filling into calibration vessel (you must fill accurate volume)

Take the maintenance remote controller and go into maintenance mode and set parameter 12 back to 1 or 0.

Go out from the maintenance mode

Switch the SW1 into position OFF (left)

Page 20: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 20

3.4. Calibration tables

Calibration table A

(Vessel = 2 litres)

Fuelled volume

[litres]

Fuelled volume

deviation [litres]

Accuracy

[%]

Corrected pulse rate

(P44) [pulse/litre]

Volume

difference winter/summer

[litres]

Pulse rate correction

(P47) [pulse/litre]

1.90 -0.10 -5.00 95.00 0.00 0.00 1.91 -0.09 -4.50 95.50 -0.01 0.50 1.92 -0.08 -4.00 96.00 -0.02 1.00 1.93 -0.07 -3.50 96.50 -0.03 1.50 1.94 -0.06 -3.00 97.00 -0.04 2.00 1.95 -0.05 -2.50 97.50 -0.05 2.50 1.96 -0.04 -2.00 98.00 -0.06 3.00 1.97 -0.03 -1.50 98.50 -0.07 3.50 1.98 -0.02 -1.00 99.00 -0.08 4.00 1.99 -0.01 -0.50 99.50 -0.09 4.50 2.00 0.00 0.00 100.00 -0.10 5.00 2.01 +0.01 +0.50 100.50 -0.11 5.50 2.02 +0.02 +1.00 101.00 -0.12 6.00 2.03 +0.03 +1.50 101.50 -0.13 6.50 2.04 +0.04 +2.00 102.00 -0.14 7.00 2.05 +0.05 +2.50 102.50 -0.15 7.50 2.06 +0.06 +3.00 103.00 -0.16 8.00 2.07 +0.07 +3.50 103.50 -0.17 8.50 2.08 +0.08 +4.00 104.00 -0.18 9.00 2.09 +0.09 +4.50 104.50 -0.19 9.50 2.10 +0.10 +5.00 105.00 -0.20 10.00

Page 21: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 21

Calibration table B

(Vessel = 5 litres)

Fuelled volume

[litres]

Fuelled volume

deviation [litres]

Accuracy

[%]

Corrected pulse rate

(P44) [pulse/litre]

Volume

difference winter/summer

[litres]

Pulse rate correction

(P47) [pulse/litre]

4.75 -0.25 -5.00 95.00 0.00 0.00 4.76 -0.24 -4.80 95.20 -0.01 0.20 4.77 -0.23 -4.60 95.40 -0.02 0.40 4.78 -0.22 -4.40 95.60 -0.03 0.60 4.79 -0.21 -4.20 95.80 -0.04 0.80 4.80 -0.20 -4.00 96.00 -0.05 1.00 4.81 -0.19 -3.80 96.20 -0.06 1.20 4.82 -0.18 -3.60 96.40 -0.07 1.40 4.83 -0.17 -3.40 96.60 -0.08 1.60 4.84 -0.16 -3.20 96.80 -0.09 1.80 4.85 -0.15 -3.00 97.00 -0.10 2.00 4.86 -0.14 -2.80 97.20 -0.11 2.20 4.87 -0.13 -2.60 97.40 -0.12 2.40 4.88 -0.12 -2.40 97.60 -0.13 2.60 4.89 -0.11 -2.20 97.80 -0.14 2.80 4.90 -0.10 -2.00 98.00 -0.15 3.00 4.91 -0.09 -1.80 98.20 -0.16 3.20 4.92 -0.08 -1.60 98.40 -0.17 3.40 4.93 -0.07 -1.40 98.60 -0.18 3.60 4.94 -0.06 -1.20 98.80 -0.19 3.80 4.95 -0.05 -1.00 99.00 -0.20 4.00 4.96 -0.04 -0.80 99.20 -0.21 4.20 4.97 -0.03 -0.60 99.40 -0.22 4.40 4.98 -0.02 -0.40 99.60 -0.23 4.60 4.99 -0.01 -0.20 99.80 -0.24 4.80 5.00 0.00 0.00 100.00 -0.25 5.00 5.01 +0.01 +0.20 100.20 -0.26 5.20 5.02 +0.02 +0.40 100.40 -0.27 5.40 5.03 +0.03 +0.60 100.60 -0.28 5.60 5.04 +0.04 +0.80 100.80 -0.29 5.80 5.05 +0.05 +1.00 101.00 -0.30 6.00 5.06 +0.06 +1.20 101.20 -0.31 6.20 5.07 +0.07 +1.40 101.40 -0.32 6.40 5.08 +0.08 +1.60 101.60 -0.33 6.60 5.09 +0.09 +1.80 101.80 -0.34 6.80 5.10 +0.10 +2.00 102.00 -0.35 7.00 5.11 +0.11 +2.20 102.20 -0.36 7.20 5.12 +0.12 +2.40 102.40 -0.37 7.40 5.13 +0.13 +2.60 102.60 -0.38 7.60 5.14 +0.14 +2.80 102.80 -0.39 7.80 5.15 +0.15 +3.00 103.00 -0.40 8.00 5.16 +0.16 +3.20 103.20 -0.41 8.20 5.17 +0.17 +3.40 103.40 -0.42 8.40 5.18 +0.18 +3.60 103.60 -0.43 8.60 5.19 +0.19 +3.80 103.80 -0.44 8.80 5.20 +0.20 +4.00 104.00 -0.45 9.00 5.21 +0.21 +4.20 104.20 -0.46 9.20 5.22 +0.22 +4.40 104.40 -0.47 9.40 5.23 +0.23 +4.60 104.60 -0.48 9.60 5.24 +0.24 +4.80 104.80 -0.49 9.80 5.25 +0.25 +5.00 105.00 -0.50 10.00

Page 22: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 22

Calibration table C

(Vessel = 10 litres)

Fuelled volume

[litres]

Fuelled volume

deviation [litres]

Accuracy

[%]

Corrected pulse rate

(P44) [pulse/litre]

Volume

difference winter/summer

[litres]

Pulse rate correction

(P47) [pulse/litre]

9.80 -0.20 -2.00 98.00 0.00 0.00 9.81 -0.19 -1.90 98.10 -0.01 0.10 9.82 -0.18 -1.80 98.20 -0.02 0.20 9.83 -0.17 -1.70 98.30 -0.03 0.30 9.84 -0.16 -1.60 98.40 -0.04 0.40 9.85 -0.15 -1.50 98.50 -0.05 0.50 9.86 -0.14 -1.40 98.60 -0.06 0.60 9.87 -0.13 -1.30 98.70 -0.07 0.70 9.88 -0.12 -1.20 98.80 -0.08 0.80 9.89 -0.11 -1.10 98.90 -0.09 0.90 9.90 -0.10 -1.00 99.00 -0.10 1.00 9.91 -0.09 -0.90 99.10 -0.11 1.10 9.92 -0.08 -0.80 99.20 -0.12 1.20 9.93 -0.07 -0.70 99.30 -0.13 1.30 9.94 -0.06 -0.60 99.40 -0.14 1.40 9.95 -0.05 -0.50 99.50 -0.15 1.50 9.96 -0.04 -0.40 99.60 -0.16 1.60 9.97 -0.03 -0.30 99.70 -0.17 1.70 9.98 -0.02 -0.20 99.80 -0.18 1.80 9.99 -0.01 -0.10 99.90 -0.19 1.90 10.00 0.00 0.00 100.00 -0.20 2.00 10.01 +0.01 +0.10 100.10 -0.21 2.10 10.02 +0.02 +0.20 100.20 -0.22 2.20 10.03 +0.03 +0.30 100.30 -0.23 2.30 10.04 +0.04 +0.40 100.40 -0.24 2.40 10.05 +0.05 +0.50 100.50 -0.25 2.50 10.06 +0.06 +0.60 100.60 -0.26 2.60 10.07 +0.07 +0.70 100.70 -0.27 2.70 10.08 +0.08 +0.80 100.80 -0.28 2.80 10.09 +0.09 +0.90 100.90 -0.29 2.90 10.10 +0.10 +1.00 101.00 -0.30 3.00 10.11 +0.11 +1.10 101.10 -0.31 3.10 10.12 +0.12 +1.20 101.20 -0.32 3.20 10.13 +0.13 +1.30 101.30 -0.33 3.30 10.14 +0.14 +1.40 101.40 -0.34 3.40 10.15 +0.15 +1.50 101.50 -0.35 3.50 10.16 +0.16 +1.60 101.60 -0.36 3.60 10.17 +0.17 +1.70 101.70 -0.37 3.70 10.18 +0.18 +1.80 101.80 -0.38 3.80 10.19 +0.19 +1.90 101.90 -0.39 3.90 10.20 +0.20 +2.00 102.00 -0.40 3.00

Page 23: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 23

Calibration table D

(Vessel = 20 litres)

Fuelled volume

[litres]

Fuelled volume

deviation [litres]

Accuracy

[%]

Corrected pulse rate

(P44) [pulse/litre]

Volume

difference winter/summer

[litres]

Pulse rate correction

(P47) [pulse/litre]

19.75 -0.25 -1.25 98.75 0.00 0.00 19.76 -0.24 -1.20 98.80 -0.01 0.05 19.77 -0.23 -1.15 98.85 -0.02 0.10 19.78 -0.22 -1.10 98.90 -0.03 0.15 19.79 -0.21 -1.05 98.95 -0.04 0.20 19.80 -0.20 -1.00 99.00 -0.05 0.25 19.81 -0.19 -0.95 99.05 -0.06 0.30 19.82 -0.18 -0.90 99.10 -0.07 0.35 19.83 -0.17 -0.85 99.15 -0.08 0.40 19.84 -0.16 -0.80 99.20 -0.09 0.45 19.85 -0.15 -0.75 99.25 -0.10 0.50 19.86 -0.14 -0.70 99.30 -0.11 0.55 19.87 -0.13 -0.65 99.35 -0.12 0.60 19.88 -0.12 -0.60 99.40 -0.13 0.65 19.89 -0.11 -0.55 99.45 -0.14 0.70 19.90 -0.10 -0.50 99.50 -0.15 0.75 19.91 -0.09 -0.45 99.55 -0.16 0.80 19.92 -0.08 -0.40 99.60 -0.17 0.85 19.93 -0.07 -0.35 99.65 -0.18 0.90 19.94 -0.06 -0.30 99.70 -0.19 0.95 19.95 -0.05 -0.25 99.75 -0.20 1.00 19.96 -0.04 -0.20 99.80 -0.21 1.05 19.97 -0.03 -0.15 99.85 -0.22 1.10 19.98 -0.02 -0.10 99.90 -0.23 1.15 19.99 -0.01 -0.05 99.95 -0.24 1.20 20.00 0.00 0.00 100.00 -0.25 1.25 20.01 +0.01 +0.05 100.05 -0.26 1.30 20.02 +0.02 +0.10 100.10 -0.27 1.35 20.03 +0.03 +0.15 100.15 -0.28 1.40 20.04 +0.04 +0.20 100.20 -0.29 1.45 20.05 +0.05 +0.25 100.25 -0.30 1.50 20.06 +0.06 +0.30 100.30 -0.31 1.55 20.07 +0.07 +0.35 100.35 -0.32 1.60 20.08 +0.08 +0.40 100.40 -0.33 1.65 20.09 +0.09 +0.45 100.45 -0.34 1.70 20.10 +0.10 +0.50 100.50 -0.35 1.75 20.11 +0.11 +0.55 100.55 -0.36 1.80 20.12 +0.12 +0.60 100.60 -0.37 1.85 20.13 +0.13 +0.65 100.65 -0.38 1.90 20.14 +0.14 +0.70 100.70 -0.39 1.95 20.15 +0.15 +0.75 100.75 -0.40 2.00 20.16 +0.16 +0.80 100.80 -0.41 2.05 20.17 +0.17 +0.85 100.85 -0.42 2.10 20.18 +0.18 +0.90 100.90 -0.43 2.15 20.19 +0.19 +0.95 100.95 -0.44 2.20 20.20 +0.20 +1.00 101.00 -0.45 2.25 20.21 +0.21 +1.05 101.05 -0.46 2.30 20.22 +0.22 +1.10 101.10 -0.47 2.35 20.23 +0.23 +1.15 101.15 -0.48 2.40 20.24 +0.24 +1.20 101.20 -0.49 2.45 20.25 +0.25 +1.25 101.25 -0.50 2.50

Page 24: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 24

Calibration table E - Part 1

(Vessel = 50 litres)

Fuelled volume

[litres]

Fuelled volume

deviation [litres]

Accuracy

[%]

Correctedpulse rate

(P44) [pulse/litre]

Volume

difference winter/summer

[litres]

Pulse rate correction

(P47) [pulse/litre]

49.50 -0.50 -1.00 99.00 0.00 0.00 49.51 -0.49 -0.98 99.02 -0.01 0.02 49.52 -0.48 -0.94 99.04 -0.02 0.04 49.53 -0.47 -0.96 99.06 -0.03 0.06 49.54 -0.46 -0.92 99.08 -0.04 0.08 49.55 -0.45 -0.90 99.10 -0.05 0.10 49.56 -0.44 -0.88 99.12 -0.06 0.12 49.57 -0.43 -0.86 99.14 -0.07 0.14 49.58 -0.42 -0.84 99.16 -0.08 0.16 49.59 -0.41 -0.82 99.18 -0.09 0.18 49.60 -0.40 -0.80 99.20 -0.10 0.20 49.61 -0.39 -0.78 99.22 -0.11 0.22 49.62 -0.38 -0.76 99.24 -0.12 0.24 49.63 -0.37 -0.74 99.26 -0.13 0.26 49.64 -0.36 -0.72 99.28 -0.14 0.28 49.65 -0.35 -0.70 99.30 -0.15 0.30 49.66 -0.34 -0.68 99.32 -0.16 0.32 49.67 -0.33 -0.66 99.34 -0.17 0.34 49.68 -0.32 -0.64 99.36 -0.18 0.36 49.69 -0.31 -0.62 99.38 -0.19 0.38 49.70 -0.30 -0.60 99.40 -0.20 0.40 49.71 -0.29 -0.58 99.42 -0.21 0.42 49.72 -0.28 -0.56 99.44 -0.22 0.44 49.73 -0.27 -0.54 99.46 -0.23 0.46 49.74 -0.26 -0.52 99.48 -0.24 0.48 49.75 -0.25 -0.50 99.50 -0.25 0.50 49.76 -0.24 -0.48 99.52 -0.26 0.52 49.77 -0.23 -0.46 99.54 -0.27 0.54 49.78 -0.22 -0.44 99.56 -0.28 0.56 49.79 -0.21 -0.42 99.58 -0.29 0.58 49.80 -0.20 -0.40 99.60 -0.30 0.60 49.81 -0.19 -0.38 99.62 -0.31 0.62 49.82 -0.18 -0.36 99.64 -0.32 0.64 49.83 -0.17 -0.34 99.66 -0.33 0.66 49.84 -0.16 -0.32 99.68 -0.34 0.68 49.85 -0.15 -0.30 99.70 -0.35 0.70 49.86 -0.14 -0.28 99.72 -0.36 0.72 49.87 -0.13 -0.26 99.74 -0.37 0.74 49.88 -0.12 -0.24 99.76 -0.38 0.76 49.89 -0.11 -0.22 99.78 -0.39 0.78 49.90 -0.10 -0.20 99.80 -0.40 0.80 49.91 -0.09 -0.18 99.82 -0.41 0.82 49.92 -0.08 -0.16 99.84 -0.42 0.84 49.93 -0.07 -0.14 99.86 -0.43 0.86 49.94 -0.06 -0.12 99.88 -0.44 0.88 49.95 -0.05 -0.10 99.90 -0.45 0.90 49.96 -0.04 -0.08 99.92 -0.46 0.92 49.97 -0.03 -0.06 99.94 -0.47 0.94 49.98 -0.02 -0.04 99.96 -0.48 0.96 49.99 -0.01 -0.02 99.98 -0.49 0.98 50.00 0.00 0.00 100.00 -0.50 1.00

Page 25: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

Electronic Counter for Fuel Dispensers PDE - Service Manual

Page 25

Calibration table E - Part 2

(Vessel = 50 litres)

Fuelled volume

[litres]

Fuelled volume

deviation [litres]

Accuracy

[%]

Correctedpulse rate

(P44) [pulse/litre]

Volume

difference winter/summer

[litres]

Pulse rate correction

(P47) [pulse/litre]

50.00 0.00 0.00 100.00 -0.51 1.02 50.01 +0.01 +0.02 100.02 -0.52 1.04 50.02 +0.02 +0.04 100.04 -0.53 1.06 50.03 +0.03 +0.06 100.06 -0.54 1.08 50.04 +0.04 +0.08 100.08 -0.55 1.10 50.05 +0.05 +0.10 100.10 -0.56 1.12 50.06 +0.06 +0.12 100.12 -0.57 1.14 50.07 +0.07 +0.14 100.14 -0.58 1.16 50.08 +0.08 +0.16 100.16 -0.59 1.18 50.09 +0.09 +0.18 100.18 -0.60 1.20 50.10 +0.10 +0.20 100.20 -0.61 1.22 50.11 +0.11 +0.22 100.22 -0.62 1.24 50.12 +0.12 +0.24 100.24 -0.63 1.26 50.13 +0.13 +0.26 100.26 -0.64 1.28 50.14 +0.14 +0.28 100.28 -0.65 1.30 50.15 +0.15 +0.30 100.30 -0.66 1.32 50.16 +0.16 +0.32 100.32 -0.67 1.34 50.17 +0.17 +0.34 100.34 -0.68 1.36 50.18 +0.18 +0.36 100.36 -0.69 1.38 50.19 +0.19 +0.38 100.38 -0.70 1.40 50.20 +0.20 +0.40 100.40 -0.71 1.42 50.21 +0.21 +0.42 100.42 -0.72 1.44 50.22 +0.22 +0.44 100.44 -0.73 1.46 50.23 +0.23 +0.46 100.46 -0.74 1.48 50.24 +0.24 +0.48 100.48 -0.75 1.50 50.25 +0.25 +0.50 100.50 -0.76 1.52 50.26 +0.26 +0.52 100.52 -0.77 1.54 50.27 +0.27 +0.54 100.54 -0.78 1.56 50.28 +0.28 +0.56 100.56 -0.79 1.58 50.29 +0.29 +0.58 100.58 -0.80 1.60 50.30 +0.30 +0.60 100.60 -0.81 1.62 50.31 +0.31 +0.62 100.62 -0.82 1.64 50.32 +0.32 +0.64 100.64 -0.83 1.66 50.33 +0.33 +0.66 100.66 -0.84 1.68 50.34 +0.34 +0.68 100.68 -0.85 1.70 50.35 +0.35 +0.70 100.70 -0.86 1.72 50.36 +0.36 +0.72 100.72 -0.87 1.74 50.37 +0.37 +0.74 100.74 -0.88 1.76 50.38 +0.38 +0.76 100.76 -0.89 1.78 50.39 +0.39 +0.78 100.78 -0.90 1.80 50.40 +0.40 +0.80 100.80 -0.91 1.82 50.41 +0.41 +0.82 100.82 -0.92 1.84 50.42 +0.42 +0.84 100.84 -0.93 1.86 50.43 +0.43 +0.86 100.86 -0.94 1.88 50.44 +0.44 +0.88 100.88 -0.95 1.90 50.45 +0.45 +0.90 100.90 -0.96 1.92 50.46 +0.46 +0.92 100.92 -0.97 1.94 50.47 +0.47 +0.94 100.94 -0.98 1.96 50.48 +0.48 +0.96 100.96 -0.99 1.98 50.49 +0.49 +0.98 100.98 -1.00 1.00 50.50 +0.50 +1.00 101.00

Page 26: Electronic Counter for Fuel Dispensers PDE - elpm.se2010-8-29 · Electronic Counter for Fuel Dispensers PDE - Service Manual S 34 )

TATSUNO-BENČ EUROPE a.s., Pražská 68, P.O.BOX 49, 678 01 Blansko, tel.+420 516 428 411, fax. +420 516 428410, email:[email protected]

Page 26

Calibration table F

(Vessel = 100 litres)

Fuelled volume

[litres]

Fuelled volume

deviation [litres]

Accuracy

[%]

Correctedpulse rate

(P44) [pulse/litre]

Volume

difference winter/summer

[litres]

Pulse rate correction

(P47) [pulse/litre]

99.00 -1.00 -1.00 99.00 0.00 0.00 99.05 -0.95 -0.95 99.05 -0.05 0.05 99.10 -0.90 -0.90 99.10 -0.10 0.10 99.15 -0.85 -0.85 99.15 -0.15 0.15 99.20 -0.80 -0.80 99.20 -0.20 0.20 99.25 -0.75 -0.75 99.25 -0.25 0.25 99.30 -0.70 -0.70 99.30 -0.30 0.30 99.35 -0.65 -0.65 99.35 -0.35 0.35 99.40 -0.60 -0.60 99.40 -0.40 0.40 99.45 -0.55 -0.55 99.45 -0.45 0.45 99.50 -0.50 -0.50 99.50 -0.50 0.50 99.55 -0.45 -0.45 99.55 -0.55 0.55 99.60 -0.40 -0.40 99.60 -0.60 0.60 99.65 -0.35 -0.35 99.65 -0.65 0.65 99.70 -0.30 -0.30 99.70 -0.70 0.70 99.75 -0.25 -0.25 99.75 -0.75 0.75 99.80 -0.20 -0.20 99.80 -0.80 0.80 99.85 -0.15 -0.15 99.85 -0.85 0.85 99.90 -0.10 -0.10 99.90 -0.90 0.90 99.95 -0.05 -0.05 99.95 -0.95 0.95 100.00 0.00 0.00 100.00 -1.00 1.00 100.05 +0.05 +0.05 100.05 -1.05 1.05 100.10 +0.10 +0.10 100.10 -1.10 1.10 100.15 +0.15 +0.15 100.15 -1.15 1.15 100.20 +0.20 +0.20 100.20 -1.20 1.20 100.25 +0.25 +0.25 100.25 -1.25 1.25 100.30 +0.30 +0.30 100.30 -1.30 1.30 100.35 +0.35 +0.35 100.35 -1.35 1.35 100.40 +0.40 +0.40 100.40 -1.40 1.40 100.45 +0.45 +0.45 100.45 -1.45 1.45 100.50 +0.50 +0.50 100.50 -1.50 1.50 100.55 +0.55 +0.55 100.55 -1.55 1.55 100.60 +0.60 +0.60 100.60 -1.60 1.60 100.65 +0.65 +0.65 100.65 -1.65 1.65 100.70 +0.70 +0.70 100.70 -1.70 1.70 100.75 +0.75 +0.75 100.75 -1.75 1.75 100.80 +0.80 +0.80 100.80 -1.80 1.80 100.85 +0.85 +0.85 100.85 -1.85 1.85 100.90 +0.90 +0.90 100.90 -1.90 1.90 100.95 +0.95 +0.95 100.95 -1.95 1.95 101.00 +1.00 +1.00 101.00 -2.00 2.00