emergency light fittings for fluorescent lamps series exlux 6008
TRANSCRIPT
-
8/16/2019 Emergency Light Fittings for Fluorescent Lamps Series EXLUX 6008
1/2
R. STAHL Schaltgeräte GmbH Page 1 / 2Data Sheet 27.08.2012
R. STAHL Schaltgeräte GmbH 169732P.O. Box 40 - D-74636 Waldenburg - Tel. 07942 943-0 - Fax 07942 943-4333
e-mail: [email protected] - Internet: http://www.stahl.de
Page / Data SheetIdent-No.169732
Ident-No. 169732
Order number 6008/542-9011-7147
Emergency Light Fittings for Fluorescent Lamps Series EXLUX 6008
Luminous Characteristics
Lamps 2 x 36 W W
Battery 7 Ah
Lighting hours 1.5 / 3 h (emergency light)
Explosion protection
Global (IECEx)
IECEx IECEx PTB 07.0053
Gas explosion pro-
tection
Ex d e mb IIC T4
Dust explosion pro-
tection
Ex tD A21 IP66 T80°C
Europe (ATEX)
Gas explosion pro-
tection
PTB 97 ATEX 2032
Gas explosion pro-
tection
II 2 G Ex d e mb IIC T4
Dust explosion pro-
tection
PTB 97 ATEX 2032
Dust explosion pro-
tection
II 2 D Ex tD A21 IP6. T80°C
Certificates and appro-
vals
Certificates IECEx, ATEX, Brazil (UL do Brasil), India (PESO), Canada (CSA), Kazakhstan (GOST-K), Rus-
sia (GOST-R), Ukraine (GOST-U), USA (FM), Belarus (GOST-B), Serbia (IZP), Corea KGS),
China (CQST)
Other approvals ship approval (GL)
Further parameters
Marking (CE)
0158
Electrical data
Rated voltage 220 ... 254 V, 50 / 60 Hz
110 ... 127 V, 50 / 60 Hz available on request
Disconnection of the light When opening the light
Switch with safety lock; when opening the central lock, all poles of the voltage supply to the
ballast are disconnected; contacts of the switching element are NC contacts, they can only
switched on again when the lamp cover and the central locking system are closed.
In case of a lamp fault, the electronic ballast disconnects the defective lamp from the power
supply.
Emergency light electronics
Operating modes Continuous operation, continuous operation with emergency light blocking and stand-by
switching
Battery charge Intelligent battery management, controlled microprocessor (charging time max. 14 h) total dischargeprotection to avoid a pole reversal
-
8/16/2019 Emergency Light Fittings for Fluorescent Lamps Series EXLUX 6008
2/2
R. STAHL Schaltgeräte GmbH Page 2 / 2Data Sheet 27.08.2012
R. STAHL Schaltgeräte GmbH 169732P.O. Box 40 - D-74636 Waldenburg - Tel. 07942 943-0 - Fax 07942 943-4333
e-mail: [email protected] - Internet: http://www.stahl.de
Switchover voltage from mains to battery operation for U < 0.74 x UNfrom battery to mains operation for U > 0.80 x UN
Test functions
Functional test The emergency light function is checked once a week
First test takes place 1 hour after putting into operation
For the first test, both lamps are switched on for 1 minute and the battery is charged with the
rated current.
Battery errors and lamp faults are detected and indicated via the LED.
Light duration test of the
emergency lighting
Test of the battery capacity in time intervals of 12 months; operation of the device in the
emergency light mode during 2/3 of rated operation time. If the light is switched off by the
discharge protection before the time has elapsed, the battery cannot be used for the emer-
gency mode.
The red LED indicates the error.
Battery set
Version Gas-tight NiCd battery
Operating voltage 6 V
Capacity 7 Ah
Replacing the battery set When the battery enclosure is opened, the battery set is de-energised;
the battery set can be removed from the enclosure after disconnection of the plug-in
contacts
Mechanical data
Ambient conditions
Ambient temperature Standard operation: - 20 ... + 50 °C
Battery operation: - 5 ... + 50 °C charging, - 20 ... + 50 °C discharging
Material
Enclosure material Polyester, glass fibre reinforced, colour: white, similar to RAL 9010
Lamp cover Polycarbonate
Gasket Polyurethane foam gasket in the lamp cover
Lamp locking Central locking which can be opened/closed using a socket key M8 / wrench size 13, hinged
lamp cover
Connection Polyamide terminal block with cover
Marking: L1, N, PE, L’ (L’ = charging phase)
Connection range: max. 2 x 6 mm2 (solid), 2 x 4 mm2 (flexible)
Weight 10.400 kg
Cable entry Connection side: 1 cable gland M 25 x 1.5 and 1 stopping plug M 25 x 1.5
Opposite side: 1 stopping plug M 25 x 1.5
Connection Polyamide terminal block with cover
Marking: L1, N, PE, L’ (L’ = charging phase)
Connection range: max. 2 x 6 mm2 (solid), 2 x 4 mm2 (flexible)
Through wiring without