emergency voice communication systems evcs network 8 · assist alarm systems. these are connected...
TRANSCRIPT
The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.
Features• Fully monitored stand alone system
• Complies with BS5839 Part 9
• Fully addressable
• Duplex two way communication
• Systemflexibility
• Multiple line conversations
• Up to 8 master handsets
• Up to 256 outstations
• In addition to Type A and Type B Outstation can also
monitor Emergency Assist Alarms (using a 2 core radial)
DesignedtocomplywithBS5839Part92003theEVCSisafixed,secure, bi-directional fully-duplex voice communication system, toassistfirefighterswithinhighrisebuildingsorlargesiteswhereradiocommunicationmaynotbepossible.WherebothafiretelephoneanddisabledrefugesystemarefittedtoabuildingBS5839Part9specifiestheseshouldformasinglesystem.
The EVCS consists of three main components; the master handset (EVCS-MS), the exchanges units (EVCS-XC), and outstations (type A or type B as appropriate).
Control of EVCS is simplicity itself, the master handset has a clear, four line backlit display which shows the calling outstation name in plain text. Calls can be made to outstations by either dialling the number of the unit, or choosing the name from a text dialling directory, with conference calling possible.
Each Exchange unit connects to a data highway and is locally powered, with internal battery backup from a monitored, maintained sealed lead acid battery. Up to eight lines can be connected to each distributed exchange, and each line can have up to four phones (BS5839 Part 9 recommends one phone per line,howeverthisfacilityisrequiredinsomeretrofits).
Two types of user outstation are available as described in BS5839Part9,TypeAuseshandsets,eitherflushorsurfacemounting. Type B outstations are hands free units with echo cancellation and noise reduction. All EVCS handsets have a ‘T’ coil for hearing aid users.
InstallationMaster Handsets and exchange units are connected on a single datahighwayconsistingof2x4corefireratedcables.Upto8Master Handsets and 32 exchanges may be connected to this highway. Master Handsets may be desk or wall mounted and has a 19” rack mounting option. Exchange units are supplied in a mild steel enclosure suitable for wall mounting.
Each Exchange unit has 8 outstation lines for connection of Type A (telephone), Type B (hands free) stations or Emergancy Assist Alarm systems. These are connected to the Exchange unitwitha2corefireratedcablewithfieldwiringwhenanoutstation is connected.
Emergency Voice Communication SystemsEVCS Network 8Data Sheet
This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United KingdomPhone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888
ISO9001Design, Manufacture and
Supply to Quality Manage-mentSystemsCertifiedto
ISO9001:1994
Page 1 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsEVCS Master Handset - EVCS-MSMechanical Specification• Dimensions: Height: 268 mm Width: 275 mm Depth: 85 mm • Weight: 1.49 kg
Indication and Controls• Fault LEDs 4 off yellow (General, Panel, Supply & Exchange)• Status LEDs 4 off green (Healthy, AC, DC & Network)• LCD High contrast blue/white LCD, four line twenty-character 5x8 pixel format• Keyboard 12 key telephone style• Navigation 3 keys (Left, Accept,Right)
Network Cables• Type Fire rated (some installations will require enhanced cabling).• Cores 1 off four Pair (eg Draka 91-0245) or 2 off four core 1mm CSA Soft Skin or 4 off 1 Pair MICC Twisted• Distance 500M soft skin, 300M MICC• Monitoring Data and phantom voltage
Electrical Specification
Power Supply• Source Network Port x2• Voltage 11V to 18V DC• Current 88mA @ 12V
Processing• Clock 16MHz• Memory 4K RAM 20K EEProm 128K Flash• Monitoring Asynchronous Watchdog checksum on EEPROM & Flash
Standards Compliance• EMC EN55103-1,EN55103-2• Product Family BS5839-pt9, BS9999
EVCS Network 8 Master Handset - EVCS-MSEVCS Network 8 is a system for larger Disabled Refuge and Emergency telephone installations. Its distributed loop architecture provides a competitive system from 8 to 256 communication points as well as multiple control locations.
ControloftheEVCSissimplicityitself.TheNetwork8SystemMasterHandsetallowsswiftidentificationofoutstations via its on-board directory and clear backlit display. The master console has a clear four line backlit display which shows the calling outstation name in plain text, and calls can be made to outstations by either dialling the number of the unit, or choosing the name from a text dialling directory.
TheEVCSNetwork8systemalsoenablesNotifierEmergencyAssistAlarmsystemstobeconnecteddirectly.
Page 2 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsEVCS Master Handset - EVCS-MSWMMechanical Specification• Dimensions: Height: 300 mm Width: 300 mm Depth: 90 mm • Weight: 6.5 kg• Material Zintec, Texture Powder Coated, RAL7032
Indication and Controls• Fault LEDs 4 off yellow (General, Panel, Supply & Exchange)• Status LEDs 4 off green (Healthy, AC, DC & Network)• LCD High contrast blue/white LCD, four line twenty-character 5x8 pixel format• Keyboard 12 key telephone style• Navigation 3 keys (Left, Accept,Right)
Network Cables• Type Fire rated (some installations will require enhanced cabling).• Cores 1 off four Pair (eg Draka 91-0245) or 2 off four core 1mm CSA Soft Skin or 4 off 1 Pair MICC Twisted• Distance 500M soft skin, 300M MICC• Monitoring Data and phantom voltage
Electrical Specification
Power Supply• Source Network Port x2• Voltage 11V to 18V dc• Current 88mA @ 12V dc
Processing• Clock 16MHz• Memory 4K RAM 20K EEProm 128K Flash• Monitoring Asynchronous Watchdog checksum on EEPROM & Flash
Standards Compliance• EMC EN55103-1,EN55103-2• Product Family BS5839-pt9, BS9999
EVCS Network 8 Master Handset Wall Mounted - EVCS-MSWMEVCS Network 8 is a system for larger Disabled Refuge and Emergency telephone installations. Its distributed loop architecture provides a competitive system from 8 to 256 communication points as well as multiple control locations.
ControloftheEVCSissimplicityitself.TheNetwork8SystemMasterHandsetallowsswiftidentificationofoutstations via its on-board directory and clear backlit display. The master console has a clear four line backlit display which shows the calling outstation name in plain text, and calls can be made to outstations by either dialling the number of the unit, or choosing the name from a text dialling directory.
Thewallmountcaseismadefrompowdercoatedzintecandisfittedwith20mmcableknockoutsforallcablesneeded.
TheEVCSNetwork8systemalsoenablesNotifierEmergencyAssistAlarmsystemstobeconnecteddirectly.
300mm
300mm 90mm
Page 3 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsEVCS Network 8 Exchange Unit - EVCS-XCMechanical Specification• Dimensions: Height: 296 mm Width: 210 mm Depth: 82 mm • Weight: 1.6 kg
Indication and Controls• Fault LEDs 10 off yellow (General, PSU, 8 lines) • Status LEDs 2 off green (AC & DC)• Settings 8 way DIP switch
Outstation Cables• Grade Enhanced• Cable (per Line) 1 off 2 core (twisted for MICC)• Distance (per leg) 500M soft Skin types, 300M MICC• Monitoring DC open, short & earth
Network Cables• Type Enhanced• Cores 1 off four pair (eg Draka 91-0245) or 2 off four core 1mm CSA Soft Skin or 4 off 1 Pair MICC Twisted• Distance 500M soft Skin, 300M MICC
Electrical Specification
Power Supply• Voltage 230V AC ± 20%• Current 11mA• Battery 12V SLA 3.2AH• Charger 1A Controlled Impedance• Monitoring Open, Short & High Impedance cell
Standards Compliance• EMC EN55103-1,EN55103-2• LVD EN61000-3-2, EN61000-3-3, EN60950 • Product Family BS5839-pt9, BS9999, EN54-4
EVCS Network 8 Exchange Unit - EVCS-XCTheNetworkExchangeUnitdeliversanefficientsolutionforlargerEVCSsites.ProvidingapowersupplyforSystem Master Handsets, its distributed loop based architecture provides a competitive scalable system for up to 256 communication points. Each Exchange unit sits on a data highway and is locally powered, with internal battery backup from a monitored, maintained sealed lead acid battery. Up to eight lines can be connected to each distributed exchange, and each line is fully monitored for Open, Short or Earth faults.
The network comprises a line or ring of 8 cores (see below), each leg can be up-to 500M depending on cable type. A ring topology is recommended by 5839 pt9. Line cables consist of a single two core enhanced cable, either soft skin types or MICC and only 1mm CSA is required.
Uptothirty-twoNetwork8Exchangescanbefittedtoathesystemgivingamaximumsystemsizeof256independent lines.
Page 4 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
Page 5 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsEVCS Type A OutstationMechanical Specification - EVCS-HSP (Surface Mounting)• Dimensions: Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)
Mechanical Specification - EVCS-HFP (Flush Mounting)• Dimensions (with bezel): Height: 334 mm Width: 191 mm Depth: 85 mm • Dimensions (backbox hole): Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)
Features• Telephone type handset• Automatic dialling to Master Handset when ‘off hook’• Telecoil for hearing impaired users• Magnetic push catch door
Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault
Status LED• Flashing when ringing• Dimly lit to indicate surveillance
Standards• EMC: EN 55103-1 & EN 55103-2• LVD: EN 60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4
Surface mounting enclosure
Flush mounting enclosure
Type A Outstation - EVCS-HSP & EVCS-HFP The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.
The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available asasurfacemountingorflushmountingunitcasedinametalwallmountingenclosure.
The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a true front face and door.
Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.
334mm
191mm 85mm
320mm
152mm 85mm
EVCS-HFPSS Flush Mount
EVCS-HSPSS Surface Mount
Page 6 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsEVCS Type A Outstation Stainless SteelMechanical Specification - EVCS-HSPSS (Surface Mounting)• Dimensions: Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)
Mechanical Specification - EVCS-HFPSS (Flush Mounting)• Dimensions (with bezel): Height: 334 mm Width: 191 mm Depth: 85 mm • Dimensions (backbox hole): Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)
Features• Telephone type handset• Automatic dialling to Master Handset when ‘off hook’• Telecoil for hearing impaired users• Magnetic push catch door
Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault
Status LED• Flashing when ringing• Dimly lit to indicate surveillance
Standards• EMC: EN 55103-1 & EN 55103-2• LVD: EN 60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4
Type A Outstation Stainless Steel - EVCS-HSPSS & EVCS-HFPSS The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.
The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available asasurfacemountingorflushmountingunitcasedinametalwallmountingenclosure.
The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a true front face and door.
Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.
334mm
191mm 85mm
320mm
152mm 85mm
EVCS-HFPSS Flush Mount
EVCS-HSPSS Surface Mount
Page 7 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsType A Outstation IP65 Lockable Surface MountMechanical Specification - EVCS-HFW• Dimensions: Height: 300 mm Width: 200 mm Depth: 120 mm • Weight: 2.5 Kg• Material Zintec, Powder coated
• Colour RAL7035 Grey
Outstation Cables• Type Enhanced• Cores 2 core 1mm or 1.5mm• Distance 500m
Features• Telephone type handset• Automatic dialling to Master Handset when ‘off hook’• Telecoil for hearing impaired users• Fittedwithastandardfiremanskeylocktopreventunauthoriseduse
Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault
Status LED• Flashing when ringing• Dimly lit to indicate surveillance
Standards• EMC EN55103-1, EN55103-2• LVD EN60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4
Mounting The UnitThe Handset should be mounted at a height of either 1200mm from the fioor,orona1400mmcentrelinetocomplywiththerequirementsofBuilding Regulations Document M (Access for the Disabled). The back box has four indented feet to allow mounting on uneven walls.If the unit is to be used as a refuge point suitable space must be allowed to the side of the unit to allow a wheelchair to be parked for using the system.
Type A Outstation IP65 Lockable Surface Mount - EVCS-HFW The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.
The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available asasurfacemountingorflushmountingunitcasedinametalwallmountingenclosure.
TheEVCS-HFWisatypeAEVCSoutstationcompatiblewiththeNotifierCompactandNetworksystems.ItissuppliedinanIP65casefittedwithastandardfiremanskeylocktopreventunauthoriseduse.
300m
m
200mm 120mm
SpecificationsType B OutstationMechanical Specification• Dimensions: Height: 133 mm Width: 133 mm Depth: 45 mm • Weight: 1.1Kg • Construction Zintec powder coated • Colour Green, Red or Stainless Steel
Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault
Outstation Cables• Cores 2 core 1mm or 1.5mm• Distance 500m
Indications & Controls• Status LEDs2offred-flasheslocation, lights solid in use• Call Press to call button• Cancel Press to cancel button
Hands Free Communications• Push button dialling to EVCS Master Handset• Echo cancellation• Noise reduction• Induction loop output for hearing impaired users• Push button cancel• Braille Signage
Standards• EMC: EN55103-1 & EN55103-2 • LVD: EN60950• Product Family: BS5839 Pt9 & BS9999
Mounting The UnitAll Type B Outstations should be mounted at a height of either 1200mm fromthefloor,orona1400mmcentrelinetocomplywiththerequirementsof Building Regulations Document M (access for the disabled).The back box has 4 indented feet to allow mounting on uneven walls.TypeBOutstationscanbeflushmountedbycuttingahole133mmx133mmand45mmdeep,andusingthestainlesssteelbezeltofinishthe surround.
Type B Outstation - EVCS-HSBG, EVCS-HSB, EVCS-HSFSSThe EVCS Type B outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.
TheTypeBoutstationisafixed,monitoredandmaintained,bi-directional,fullduplexvoicecommunicationsystemtoassisttheorderlyevacuationofdisabledormobilityimpairedpeopleandenhancefirefighterscommunication during emergencies.
Please note: When choosing the outstation type for use with an EVCS we recommend reading Section 11 of BS5839-9:2003 which deals with outstation types. Type B outstations can only be used where the background noise is below 40dBA (therefore there can be no sounder or voice alarm coverage in the area).
Page 8 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsJack Plate Mechanical Specification• Dimensions: Height: 86 mm Width: 86 mm Depth: 25 mm • Weight: 140g • Construction Brushed stainless steel
Outstation Cables• Cores 2 core 1mm or 1.5mm • Distance 500m• End of Line 10K 1/4 W
Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault
Roaming Handset Mechanical Specification• Dimensions: Height: 210 mm Width: 66 mm Depth: 45 mm • Weight: 700g • Construction ABS UL90V1• Connection 1/4” mono neutrik heavy duty jack
Standards Compliance• EMC EN55103-1,EN55103-2• LVD EN60950
Controls
• Call Automatic off hook dialing
Roaming Handset and Jack PlateThe Roaming Handset and Jack plate are designed to provide a cost effective solution for Fire Telephones in highrisebuildings.Notifier’srangeofEVCSsystemscoverawiderangeofbuildingsizesprovidinghighqualityfull duplex Emergency Voice Communication.
The Roaming Handset is used along with the Jack Plate for Emergency Voice Communication System installationsincountrieswhosefirecodesallowforRoamingHandsets*.Whenusedtogether,theRoamingHandset and Jack Plate form a Type A Outstation which is compatible with all EVCS systems.
Low noise high quality telephone jack with Telecoil for hearing impaired users.
Stainlesssteeljackplatecanbesurfaceorflushmounted
*TheseunitsarenotsuitableforinstallationintheUKtoBS5839Pt9
Page 9 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
SpecificationsEmergency Assist Alarm Kit EVCS-TA
Features• Monitored to BS 5839-9
• Remote powered from EVCS exchange
• Dual loop pull cord
• High contrast labels
• Braille on cancel plate
• Blue indication
Benefits• No PSU is required remote powered by
EVCS system
• All calls from disabled toilets and refuge points monitored from one location
• Tactile braille signage to assist partially sighted people
Page 10 of 11 - 990-130_0213 www.notifierfiresystems.co.uk
Over door indicator
Dimensions: Width:Height:Depth:
87 mm87 mm31.5 mm
ElectricalSpecification: Operating voltage: 12V dc (nominal)
Physical: Construction: PC
Cancel button
Dimensions: Width:Height:Depth:
87 mm87 mm25 mm
ElectricalSpecification: Operating voltage: 12V dc (nominal)
Physical: Construction: PC
Pull cord unit
Dimensions: Width:Height:Depth:
87 mm87 mm30.5 mm
ElectricalSpecification: Operating voltage: 12V dc (nominal)
Physical: Construction: PC
Wiring Guide Using 2 Core Cable
+-
+-
Power Supply
12V +-
+-
+-+
-
Over DoorIndicator
CancelUnit
Pull Cord Unit
IN
IN
OUT
OUT
OUT INEVCS Exchange Over Door IndicatorOver Door Indicator Cancel UnitCancel Unit Pull Cord Unit
Emergency Assist Alarm Kit - EVCS-TATheEmergencyassistalarmkithasbeenspecificallydesignedtointegratedisabledcallfunctionsintotheEVCSNetworkorEVCSCompact ranges providing the perfect solution for conformity with the Building regulations Document M and Equality Act 2010.
The Emergency Assist Alarm Kit solution is fully monitored and battery backed by the EVCS system, saving local power supplies and givingconfidenceinthesystemintegrity.
The Emergency Assist Alarm Kit shows up as a call on the EVCS system, but has no speech path so a conversation cannot be had with the occupant, use of the Type B Outstations would allow this.
www.notifierfiresystems.co.uk
Product Range at a Glance
Part Number
EVCS Master Handset Desk/Wall Mount EVCS-MS
Network 8 Master Handset Wall Mounted EVCS-MSWM
8 Way Exchange Unit/Charger. EVCS-XC
Flush Outstation Push Door. Type A EVCS-HFP
Flush Outstation Type A, Push Door, Stainless Steel EVCS-HFPSS
Surface Outstation. Push Door. Type A EVCS-HSP
Surface Outstation Type A, Push Door, Stainless Steel EVCS-HSPSS
Weatherproof Type A Outstation EVCS-HFW
Surface Outstation, Type B, Green EVCS-HSBG
Surface Outstation, Type B, Red EVCS-HSB
Surface Outstation, Type B Stainless Steel EVCS-HSFSS
Wall Jack Outlet Point EVCS-WJP
Loose Handset with Jack Lead EVCS-HLJ
Emergency Assist Alarm Kit (without PSU) EVCS-TA
EVCS-HSBStainlessSteelflushmountingbezel EVCS-VCFHB
EVCS-MS Rackmount Kit 6U. EVCS-RM
Charles AvenueBurgess HillW. SussexRH15 9UF
T: +44 (0) 116 246 2255F: +44 (0) 116 246 2210E: [email protected]