emerson network power intellislot 485 card

25
Emerson Network Power IntelliSlot 485 Card Liebert DS 485 Network Settings Menu -------------------------- 1: Enabled Application Modbus Server 2: Control enabled 3: Server ID 8 4: Communications Rate 9600 5: Supported Data List 430 DSRNPJ 10A VENTA ANGEL RUIZ <ESC>: Cancel menu level Please select a key ?> 5 =========================================== Entry, Register(Num), Data Label, Unit, Scale, Access 1, 30017(1), Free Cooling Internal Control Mode, , x1, RO 2, 30018(1), Humidity Proportional Control Type, , x1, RO 3, 30019(1), Fan Speed Maximum Set Point, %, x1, RO 4, 30020(1), Supply Air Temperature Set Point, deg C, x10, RO

Upload: adrian-ayala-leyva

Post on 24-Oct-2014

82 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Emerson Network Power IntelliSlot 485 Card

Emerson Network Power IntelliSlot 485 Card

Liebert DS

485 Network Settings Menu

--------------------------

1: Enabled Application Modbus Server

2: Control enabled

3: Server ID 8

4: Communications Rate 9600

5: Supported Data List 430

DSRNPJ 10A VENTA ANGEL RUIZ

<ESC>: Cancel menu level

Please select a key ?> 5

===========================================

Entry, Register(Num), Data Label, Unit, Scale, Access

1, 30017(1), Free Cooling Internal Control Mode, , x1, RO

2, 30018(1), Humidity Proportional Control Type, , x1, RO

3, 30019(1), Fan Speed Maximum Set Point, %, x1, RO

4, 30020(1), Supply Air Temperature Set Point, deg C, x10, RO

5, 30021(1), Free Cooling Internal Temperature Delta, deg C, x10, RO

6, 30022(1), Minimum Chilled Water Temp Set Point, deg C, x10, RO

Page 2: Emerson Network Power IntelliSlot 485 Card

7, 30023(1), Air Temperature Set Point, deg C, x10, RO

8, 30024(1), Air Temperature Proportional Band, deg C, x10, RO

9, 30025(1), Air Temperature Dead Band, deg C, x10, RO

10, 30026(1), Air Temperature Control Integration Time, min, x1, RO

11, 30027(1), Humidity Set Point, % RH, x1, RO

12, 30028(1), Humidity Proportional Band, % RH, x1, RO

13, 30029(1), Humidity Proportional Control Integration Time, min, x1, RO

14, 30030(1), Humidity Dead Band, % RH, x10, RO

15, 30031(1), Auto Restart Delay, sec, x1, RO

16, 30033(1), Air Temperature Control Type, , x1, RO

17, 30045(1), BMS Timeout Period, min, x1, RO

18, 30050(1), Return Air Over Temp Threshold, deg C, x10, RO

19, 30051(1), Return Air Under Temp Threshold, deg C, x10, RO

20, 30052(1), Ext Air Sensor A Over Temp Threshold, deg C, x10, RO

21, 30053(1), Ext Air Sensor A Under Temp Threshold, deg C, x10, RO

22, 30054(1), High Return Humidity Threshold, % RH, x10, RO

23, 30055(1), Low Return Humidity Threshold, % RH, x10, RO

24, 30056(1), Ext Air Sensor A High Humidity Threshold, % RH, x10, RO

25, 30057(1), Ext Air Sensor A Low Humidity Threshold, % RH, x10, RO

26, 30070(1), Fan Hours Threshold, hr, x1, RO

27, 30071(1), Compressor Hours Threshold (Compressor [1]), hr, x1, RO

28, 30072(1), Compressor Hours Threshold (Compressor [2]), hr, x1, RO

29, 30073(1), Humidifier Hours Threshold, hr, x1, RO

30, 30074(1), Dehumidifier Hours Threshold, hr, x1, RO

31, 30075(1), Free Cooling Valve Hours Threshold, hr, x1, RO

32, 30076(1), Electric Reheater Hours Threshold (Electric Reheater [1]), hr,

Page 3: Emerson Network Power IntelliSlot 485 Card

x1, RO

33, 30077(1), Electric Reheater Hours Threshold (Electric Reheater [2]), hr,

x1, RO

34, 30078(1), Electric Reheater Hours Threshold (Electric Reheater [3]), hr,

x1, RO

35, 30079(1), Hot Water / Hot Gas Valve Hours Threshold, hr, x1, RO

36, 30100(1), System Operating State, , x1, RO

37, 30102(1), System Status, , x1, RO

38, 30103(1), Fan Speed, %, x1, RO

39, 30104(1), Compressor Utilization, %, x1, RO

40, 30105(1), Free Cooling Valve Open Position, %, x1, RO

41, 30106(1), Reheat Utilization, %, x1, RO

42, 30107(1), Humidifier Utilization, %, x1, RO

43, 30108(1), Dehumidifier Utilization, %, x1, RO

44, 30109(1), Free Cooling Status, , x1, RO

45, 30110(1), Return Air Temperature, deg C, x10, RO

46, 30112(1), Supply Air Temperature, deg C, x10, RO

47, 30113(1), Supply Air Temperature Set Point, deg C, x10, RO

48, 30115(1), Free Cooling Fluid Temperature, deg C, x10, RO

49, 30116(1), Ext Air Sensor A Temperature, deg C, x10, RO

50, 30117(1), Ext Air Sensor B Temperature, deg C, x10, RO

Continue? [Q:Quit, A:All, E:Entry #, any other key: 50 more lines]: a

51, 30118(1), Ext Air Sensor C Temperature, deg C, x10, RO

52, 30119(1), Dig Scroll Comp Discharge Temp (Compressor [1]), deg C, x1, RO

Page 4: Emerson Network Power IntelliSlot 485 Card

53, 30120(1), Dig Scroll Comp Discharge Temp (Compressor [2]), deg C, x1, RO

54, 30130(1), Return Humidity, % RH, x10, RO

55, 30132(1), Ext Air Sensor A Humidity, % RH, x10, RO

56, 30133(1), Ext Air Sensor B Humidity, % RH, x10, RO

57, 30134(1), Ext Air Sensor C Humidity, % RH, x10, RO

58, 30141(1), Fan Hours, hr, x1, RO

59, 30142(1), Compressor Hours (Compressor [1]), hr, x1, RO

60, 30143(1), Compressor Hours (Compressor [2]), hr, x1, RO

61, 30144(1), Humidifier Hours, hr, x1, RO

62, 30145(1), Dehumidifier Hours, hr, x1, RO

63, 30146(1), Free Cooling Valve Hours, hr, x1, RO

64, 30147(1), Electric Reheater Hours (Electric Reheater [1]), hr, x1, RO

65, 30148(1), Electric Reheater Hours (Electric Reheater [2]), hr, x1, RO

66, 30149(1), Electric Reheater Hours (Electric Reheater [3]), hr, x1, RO

67, 30150(1), Hot Water / Hot Gas Valve Hours, hr, x1, RO

68, 30151(1), Today's High Air Temperature, deg C, x10, RO

69, 30153(1), Today's Low Air Temperature, deg C, x10, RO

70, 30155(1), Today's High Humidity, % RH, x1, RO

71, 30157(1), Today's Low Humidity, % RH, x1, RO

72, 30257(1), Server Class, , x1, RO

73, 30258(2), Today's High Air Temperature Time, , x1, RO

74, 30260(2), Today's Low Air Temperature Time, , x1, RO

75, 30262(1), Supply Air Temperature Sensor Control, , x1, RO

76, 30263(1), Return Air Temperature Set Point, deg C, x10, RO

77, 30264(1), Return Humidity Set Point, % RH, x1, RO

78, 30265(2), Today's High Humidity Time, , x1, RO

Page 5: Emerson Network Power IntelliSlot 485 Card

79, 30267(2), Today's Low Humidity Time, , x1, RO

80, 30269(1), Compressor State (Compressor [1]), , x1, RO

81, 30270(1), Compressor State (Compressor [2]), , x1, RO

82, 30271(1), Compressor Capacity Control State (Compressor [1]), , x1, RO

83, 30272(1), Compressor Capacity Control State (Compressor [2]), , x1, RO

84, 30273(1), Infrared Humidifier Flush Rate, %, x1, RO

85, 30274(1), Fan Control Mode, , x1, RO

86, 30275(1), Analog Input Reading (Analog Inputs [1]), , x100, RO

87, 30276(1), Analog Input Reading (Analog Inputs [2]), , x100, RO

88, 30277(1), Analog Input Reading (Analog Inputs [3]), , x100, RO

89, 30278(1), Analog Input Reading (Analog Inputs [4]), , x100, RO

90, 30279(1), System Status, , x1, RO

91, 30280(1), System Control Mode, , x1, RO

92, 30281(1), System Operating State Reason, , x1, RO

93, 30282(1), Maintenance Ramp, %, x1, RO

94, 30283(1), Calculated Next Maintenance Month, , x1, RO

95, 30284(1), Calculated Next Maintenance Year, , x1, RO

96, 30285(1), Hot Water / Hot Gas Valve Open Position, %, x1, RO

97, 30286(1), Maintenance Tracking State, , x1, RO

98, 30287(1), Customer Input 1 - Event Control, , x1, RO

99, 30288(1), Customer Input 1 - Event Type, , x1, RO

100, 30289(1), Customer Input 2 - Event Control, , x1, RO

101, 30290(1), Customer Input 2 - Event Type, , x1, RO

102, 30291(1), Customer Input 3 - Event Control, , x1, RO

103, 30292(1), Customer Input 3 - Event Type, , x1, RO

104, 30293(1), Customer Input 4 - Event Control, , x1, RO

Page 6: Emerson Network Power IntelliSlot 485 Card

105, 30294(1), Customer Input 4 - Event Type, , x1, RO

106, 30295(1), Ext Free Cooling Lockout - Event Control, , x1, RO

107, 30296(1), Ext Free Cooling Lockout - Event Type, , x1, RO

108, 30297(1), Ext Condenser Pump High Water - Event Control, , x1, RO

109, 30298(1), Ext Condenser Pump High Water - Event Type, , x1, RO

110, 30299(1), Ext Standby Glycol Pump On - Event Control, , x1, RO

111, 30300(1), Ext Standby Glycol Pump On - Event Type, , x1, RO

112, 30301(1), Ext Standby Unit On - Event Control, , x1, RO

113, 30302(1), Ext Standby Unit On - Event Type, , x1, RO

114, 30303(1), Ext Humidifier Lockout - Event Control, , x1, RO

115, 30304(1), Ext Humidifier Lockout - Event Type, , x1, RO

116, 30305(1), Ext Loss of Flow - Event Control, , x1, RO

117, 30306(1), Ext Loss of Flow - Event Type, , x1, RO

118, 30307(1), Ext Over Temperature - Event Control, , x1, RO

119, 30308(1), Ext Over Temperature - Event Type, , x1, RO

120, 30309(1), Ext Reheat Lockout - Event Control, , x1, RO

121, 30310(1), Ext Reheat Lockout - Event Type, , x1, RO

122, 30311(1), High Power Shutdown - Event Control, , x1, RO

123, 30312(1), High Power Shutdown - Event Type, , x1, RO

124, 30313(1), Humidifier Issue - Event Control, , x1, RO

125, 30314(1), Humidifier Issue - Event Type, , x1, RO

126, 30315(1), Master Unit Communication Lost - Event Control, , x1, RO

127, 30316(1), Master Unit Communication Lost - Event Type, , x1, RO

128, 30317(1), Service Required - Event Control, , x1, RO

129, 30318(1), Service Required - Event Type, , x1, RO

130, 30319(1), Shutdown - Loss Of Power - Event Control, , x1, RO

Page 7: Emerson Network Power IntelliSlot 485 Card

131, 30320(1), Shutdown - Loss Of Power - Event Type, , x1, RO

132, 30321(1), Smoke Detected - Event Control, , x1, RO

133, 30322(1), Smoke Detected - Event Type, , x1, RO

134, 30323(1), Water Under Floor - Event Control, , x1, RO

135, 30324(1), Water Under Floor - Event Type, , x1, RO

136, 30325(1), Ext Compressor Lockout - Event Control, , x1, RO

137, 30326(1), Ext Compressor Lockout - Event Type, , x1, RO

138, 30327(1), Clogged Air Filter - Event Control, , x1, RO

139, 30328(1), Clogged Air Filter - Event Type, , x1, RO

140, 30329(1), Ext Loss of Air Blower - Event Control, , x1, RO

141, 30330(1), Ext Loss of Air Blower - Event Type, , x1, RO

142, 30331(1), Compressor High Head Pressure - Event Control (Compressor [1]),

, x1, RO

143, 30332(1), Compressor High Head Pressure - Event Control (Compressor [2]),

, x1, RO

144, 30333(1), Compressor High Head Pressure - Event Type (Compressor [1]), ,

x1, RO

145, 30334(1), Compressor High Head Pressure - Event Type (Compressor [2]), ,

x1, RO

146, 30335(1), Compressor Low Suction Pressure - Event Control (Compressor [1]

), , x1, RO

147, 30336(1), Compressor Low Suction Pressure - Event Control (Compressor [2]

), , x1, RO

148, 30337(1), Compressor Low Suction Pressure - Event Type (Compressor [1]),

, x1, RO

149, 30338(1), Compressor Low Suction Pressure - Event Type (Compressor [2]),

Page 8: Emerson Network Power IntelliSlot 485 Card

, x1, RO

150, 30339(1), Compressor Pump Down Issue - Event Control (Compressor [1]), ,

x1, RO

151, 30340(1), Compressor Pump Down Issue - Event Control (Compressor [2]), ,

x1, RO

152, 30341(1), Compressor Pump Down Issue - Event Type (Compressor [1]), , x1,

RO

153, 30342(1), Compressor Pump Down Issue - Event Type (Compressor [2]), , x1,

RO

154, 30343(1), Compressor Short Cycle - Event Control (Compressor [1]), , x1,

RO

155, 30344(1), Compressor Short Cycle - Event Control (Compressor [2]), , x1,

RO

156, 30345(1), Compressor Short Cycle - Event Type (Compressor [1]), , x1, RO

157, 30346(1), Compressor Short Cycle - Event Type (Compressor [2]), , x1, RO

158, 30347(1), Compressor Thermal Overload - Event Control (Compressor [1]), ,

x1, RO

159, 30348(1), Compressor Thermal Overload - Event Control (Compressor [2]), ,

x1, RO

160, 30349(1), Compressor Thermal Overload - Event Type (Compressor [1]), , x1

, RO

161, 30350(1), Compressor Thermal Overload - Event Type (Compressor [2]), , x1

, RO

162, 30351(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [1

]), , x1, RO

163, 30352(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [2

Page 9: Emerson Network Power IntelliSlot 485 Card

]), , x1, RO

164, 30353(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [1

]), , x1, RO

165, 30354(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [2

]), , x1, RO

166, 30355(1), Ext Air Sensor A High Humidity - Event Control, , x1, RO

167, 30356(1), Ext Air Sensor A High Humidity - Event Type, , x1, RO

168, 30357(1), Ext Air Sensor A Low Humidity - Event Control, , x1, RO

169, 30358(1), Ext Air Sensor A Low Humidity - Event Type, , x1, RO

170, 30359(1), Ext Air Sensor A Over Temp - Event Control, , x1, RO

171, 30360(1), Ext Air Sensor A Over Temp - Event Type, , x1, RO

172, 30361(1), Ext Air Sensor A Under Temp - Event Control, , x1, RO

173, 30362(1), Ext Air Sensor A Under Temp - Event Type, , x1, RO

174, 30363(1), High Return Humidity - Event Control, , x1, RO

175, 30364(1), High Return Humidity - Event Type, , x1, RO

176, 30365(1), Low Return Humidity - Event Control, , x1, RO

177, 30366(1), Low Return Humidity - Event Type, , x1, RO

178, 30367(1), Return Air Over Temp - Event Control, , x1, RO

179, 30368(1), Return Air Over Temp - Event Type, , x1, RO

180, 30369(1), Return Air Under Temp - Event Control, , x1, RO

181, 30370(1), Return Air Under Temp - Event Type, , x1, RO

182, 30371(1), Fan Hours Exceeded - Event Control, , x1, RO

183, 30372(1), Fan Hours Exceeded - Event Type, , x1, RO

184, 30373(1), Fan Issue - Event Control, , x1, RO

185, 30374(1), Fan Issue - Event Type, , x1, RO

186, 30375(1), Main Fan Overload - Event Control, , x1, RO

Page 10: Emerson Network Power IntelliSlot 485 Card

187, 30376(1), Main Fan Overload - Event Type, , x1, RO

188, 30377(1), Condenser Issue - Event Control (Condenser [1]), , x1, RO

189, 30378(1), Condenser Issue - Event Control (Condenser [2]), , x1, RO

190, 30379(1), Condenser Issue - Event Type (Condenser [1]), , x1, RO

191, 30380(1), Condenser Issue - Event Type (Condenser [2]), , x1, RO

192, 39998(2), System Date and Time, , x1, RO

193, 40017(1), Free Cooling Internal Control Mode, , x1, WR

194, 40018(1), Humidity Proportional Control Type, , x1, WR

195, 40019(1), Fan Speed Maximum Set Point, %, x1, WR

196, 40020(1), Supply Air Temperature Set Point, deg C, x10, WR

197, 40021(1), Free Cooling Internal Temperature Delta, deg C, x10, WR

198, 40022(1), Minimum Chilled Water Temp Set Point, deg C, x10, WR

199, 40023(1), Air Temperature Set Point, deg C, x10, WR

200, 40024(1), Air Temperature Proportional Band, deg C, x10, WR

201, 40025(1), Air Temperature Dead Band, deg C, x10, WR

202, 40026(1), Air Temperature Control Integration Time, min, x1, WR

203, 40027(1), Humidity Set Point, % RH, x1, WR

204, 40028(1), Humidity Proportional Band, % RH, x1, WR

205, 40029(1), Humidity Proportional Control Integration Time, min, x1, WR

206, 40030(1), Humidity Dead Band, % RH, x10, WR

207, 40031(1), Auto Restart Delay, sec, x1, WR

208, 40033(1), Air Temperature Control Type, , x1, WR

209, 40045(1), BMS Timeout Period, min, x1, WR

210, 40050(1), Return Air Over Temp Threshold, deg C, x10, WR

211, 40051(1), Return Air Under Temp Threshold, deg C, x10, WR

212, 40052(1), Ext Air Sensor A Over Temp Threshold, deg C, x10, WR

Page 11: Emerson Network Power IntelliSlot 485 Card

213, 40053(1), Ext Air Sensor A Under Temp Threshold, deg C, x10, WR

214, 40054(1), High Return Humidity Threshold, % RH, x10, WR

215, 40055(1), Low Return Humidity Threshold, % RH, x10, WR

216, 40056(1), Ext Air Sensor A High Humidity Threshold, % RH, x10, WR

217, 40057(1), Ext Air Sensor A Low Humidity Threshold, % RH, x10, WR

218, 40070(1), Fan Hours Threshold, hr, x1, WR

219, 40071(1), Compressor Hours Threshold (Compressor [1]), hr, x1, WR

220, 40072(1), Compressor Hours Threshold (Compressor [2]), hr, x1, WR

221, 40073(1), Humidifier Hours Threshold, hr, x1, WR

222, 40074(1), Dehumidifier Hours Threshold, hr, x1, WR

223, 40075(1), Free Cooling Valve Hours Threshold, hr, x1, WR

224, 40076(1), Electric Reheater Hours Threshold (Electric Reheater [1]), hr,

x1, WR

225, 40077(1), Electric Reheater Hours Threshold (Electric Reheater [2]), hr,

x1, WR

226, 40078(1), Electric Reheater Hours Threshold (Electric Reheater [3]), hr,

x1, WR

227, 40079(1), Hot Water / Hot Gas Valve Hours Threshold, hr, x1, WR

228, 40262(1), Supply Air Temperature Sensor Control, , x1, WR

229, 40263(1), Return Air Temperature Set Point, deg C, x10, WR

230, 40264(1), Return Humidity Set Point, % RH, x1, WR

231, 40273(1), Infrared Humidifier Flush Rate, %, x1, WR

232, 40274(1), Fan Control Mode, , x1, WR

233, 40287(1), Customer Input 1 - Event Control, , x1, WR

234, 40288(1), Customer Input 1 - Event Type, , x1, WR

235, 40289(1), Customer Input 2 - Event Control, , x1, WR

Page 12: Emerson Network Power IntelliSlot 485 Card

236, 40290(1), Customer Input 2 - Event Type, , x1, WR

237, 40291(1), Customer Input 3 - Event Control, , x1, WR

238, 40292(1), Customer Input 3 - Event Type, , x1, WR

239, 40293(1), Customer Input 4 - Event Control, , x1, WR

240, 40294(1), Customer Input 4 - Event Type, , x1, WR

241, 40295(1), Ext Free Cooling Lockout - Event Control, , x1, WR

242, 40296(1), Ext Free Cooling Lockout - Event Type, , x1, WR

243, 40297(1), Ext Condenser Pump High Water - Event Control, , x1, WR

244, 40298(1), Ext Condenser Pump High Water - Event Type, , x1, WR

245, 40299(1), Ext Standby Glycol Pump On - Event Control, , x1, WR

246, 40300(1), Ext Standby Glycol Pump On - Event Type, , x1, WR

247, 40301(1), Ext Standby Unit On - Event Control, , x1, WR

248, 40302(1), Ext Standby Unit On - Event Type, , x1, WR

249, 40303(1), Ext Humidifier Lockout - Event Control, , x1, WR

250, 40304(1), Ext Humidifier Lockout - Event Type, , x1, WR

251, 40305(1), Ext Loss of Flow - Event Control, , x1, WR

252, 40306(1), Ext Loss of Flow - Event Type, , x1, WR

253, 40307(1), Ext Over Temperature - Event Control, , x1, WR

254, 40308(1), Ext Over Temperature - Event Type, , x1, WR

255, 40309(1), Ext Reheat Lockout - Event Control, , x1, WR

256, 40310(1), Ext Reheat Lockout - Event Type, , x1, WR

257, 40311(1), High Power Shutdown - Event Control, , x1, WR

258, 40312(1), High Power Shutdown - Event Type, , x1, WR

259, 40313(1), Humidifier Issue - Event Control, , x1, WR

260, 40314(1), Humidifier Issue - Event Type, , x1, WR

261, 40315(1), Master Unit Communication Lost - Event Control, , x1, WR

Page 13: Emerson Network Power IntelliSlot 485 Card

262, 40317(1), Service Required - Event Control, , x1, WR

263, 40318(1), Service Required - Event Type, , x1, WR

264, 40320(1), Shutdown - Loss Of Power - Event Type, , x1, WR

265, 40321(1), Smoke Detected - Event Control, , x1, WR

266, 40322(1), Smoke Detected - Event Type, , x1, WR

267, 40323(1), Water Under Floor - Event Control, , x1, WR

268, 40324(1), Water Under Floor - Event Type, , x1, WR

269, 40325(1), Ext Compressor Lockout - Event Control, , x1, WR

270, 40326(1), Ext Compressor Lockout - Event Type, , x1, WR

271, 40327(1), Clogged Air Filter - Event Control, , x1, WR

272, 40328(1), Clogged Air Filter - Event Type, , x1, WR

273, 40329(1), Ext Loss of Air Blower - Event Control, , x1, WR

274, 40330(1), Ext Loss of Air Blower - Event Type, , x1, WR

275, 40331(1), Compressor High Head Pressure - Event Control (Compressor [1]),

, x1, WR

276, 40332(1), Compressor High Head Pressure - Event Control (Compressor [2]),

, x1, WR

277, 40333(1), Compressor High Head Pressure - Event Type (Compressor [1]), ,

x1, WR

278, 40334(1), Compressor High Head Pressure - Event Type (Compressor [2]), ,

x1, WR

279, 40335(1), Compressor Low Suction Pressure - Event Control (Compressor [1]

), , x1, WR

280, 40336(1), Compressor Low Suction Pressure - Event Control (Compressor [2]

), , x1, WR

281, 40337(1), Compressor Low Suction Pressure - Event Type (Compressor [1]),

Page 14: Emerson Network Power IntelliSlot 485 Card

, x1, WR

282, 40338(1), Compressor Low Suction Pressure - Event Type (Compressor [2]),

, x1, WR

283, 40339(1), Compressor Pump Down Issue - Event Control (Compressor [1]), ,

x1, WR

284, 40340(1), Compressor Pump Down Issue - Event Control (Compressor [2]), ,

x1, WR

285, 40341(1), Compressor Pump Down Issue - Event Type (Compressor [1]), , x1,

WR

286, 40342(1), Compressor Pump Down Issue - Event Type (Compressor [2]), , x1,

WR

287, 40343(1), Compressor Short Cycle - Event Control (Compressor [1]), , x1,

WR

288, 40344(1), Compressor Short Cycle - Event Control (Compressor [2]), , x1,

WR

289, 40345(1), Compressor Short Cycle - Event Type (Compressor [1]), , x1, WR

290, 40346(1), Compressor Short Cycle - Event Type (Compressor [2]), , x1, WR

291, 40347(1), Compressor Thermal Overload - Event Control (Compressor [1]), ,

x1, WR

292, 40348(1), Compressor Thermal Overload - Event Control (Compressor [2]), ,

x1, WR

293, 40349(1), Compressor Thermal Overload - Event Type (Compressor [1]), , x1

, WR

294, 40350(1), Compressor Thermal Overload - Event Type (Compressor [2]), , x1

, WR

295, 40351(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [1

Page 15: Emerson Network Power IntelliSlot 485 Card

]), , x1, WR

296, 40352(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [2

]), , x1, WR

297, 40353(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [1

]), , x1, WR

298, 40354(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [2

]), , x1, WR

299, 40355(1), Ext Air Sensor A High Humidity - Event Control, , x1, WR

300, 40357(1), Ext Air Sensor A Low Humidity - Event Control, , x1, WR

301, 40359(1), Ext Air Sensor A Over Temp - Event Control, , x1, WR

302, 40361(1), Ext Air Sensor A Under Temp - Event Control, , x1, WR

303, 40363(1), High Return Humidity - Event Control, , x1, WR

304, 40365(1), Low Return Humidity - Event Control, , x1, WR

305, 40367(1), Return Air Over Temp - Event Control, , x1, WR

306, 40369(1), Return Air Under Temp - Event Control, , x1, WR

307, 40371(1), Fan Hours Exceeded - Event Control, , x1, WR

308, 40373(1), Fan Issue - Event Control, , x1, WR

309, 40374(1), Fan Issue - Event Type, , x1, WR

310, 40375(1), Main Fan Overload - Event Control, , x1, WR

311, 40376(1), Main Fan Overload - Event Type, , x1, WR

312, 40377(1), Condenser Issue - Event Control (Condenser [1]), , x1, WR

313, 40378(1), Condenser Issue - Event Control (Condenser [2]), , x1, WR

314, 40379(1), Condenser Issue - Event Type (Condenser [1]), , x1, WR

315, 40380(1), Condenser Issue - Event Type (Condenser [2]), , x1, WR

316, 40381(1), System Event Acknowledge/Reset, , x1, WR

317, 49998(2), System Date and Time, , x1, WR

Page 16: Emerson Network Power IntelliSlot 485 Card

318, 10009(1), Ext Reheat Lockout

319, 10010(1), Ext Humidifier Lockout

320, 10013(1), Minimum Chilled Water Temp Set Point Enable

321, 10019(1), Return Air Sensor Event Control

322, 10020(1), Ext Air Sensor A Event Control

323, 10021(1), Ext Compressor Lockout

324, 10025(1), Fan State

325, 10026(1), Cooling State

326, 10027(1), Free Cooling State

327, 10028(1), Hot Water / Hot Gas State

328, 10029(1), Electric Reheat State

329, 10030(1), Humidifier State

330, 10031(1), Dehumidifier State

331, 10034(1), Main Fan Overload

332, 10035(1), Loss of Air Flow

333, 10036(1), Ext Loss of Flow

334, 10037(1), Compressor High Head Pressure (Compressor [1])

335, 10038(1), Compressor Low Suction Pressure (Compressor [1])

336, 10039(1), Compressor Thermal Overload (Compressor [1])

337, 10040(1), Compressor Pump Down Issue (Compressor [1])

338, 10041(1), Compressor High Head Pressure (Compressor [2])

339, 10042(1), Compressor Low Suction Pressure (Compressor [2])

340, 10043(1), Compressor Thermal Overload (Compressor [2])

341, 10044(1), Compressor Pump Down Issue (Compressor [2])

342, 10045(1), Dig Scroll Comp Over Temp (Compressor [1])

343, 10046(1), Dig Scroll Comp Over Temp (Compressor [2])

Page 17: Emerson Network Power IntelliSlot 485 Card

344, 10047(1), Smoke Detected

345, 10048(1), Water Under Floor

346, 10049(1), Humidifier Issue

347, 10050(1), Ext Standby Glycol Pump On

348, 10051(1), Ext Standby Unit On

349, 10052(1), Ext Condenser Pump High Water

350, 10053(1), Return Air Sensor Issue

351, 10055(1), Ext Loss of Air Blower

352, 10058(1), Humidifier Low Water

353, 10059(1), Humidifier Over Current

354, 10060(1), Ext Over Temperature

355, 10061(1), Shutdown - Loss Of Power

356, 10065(1), Supply Chilled Water Over Temp

357, 10067(1), Return Air Over Temperature

358, 10068(1), Return Air Under Temperature

359, 10069(1), High Return Humidity

360, 10070(1), Low Return Humidity

361, 10071(1), Ext Air Sensor A Over Temperature

362, 10072(1), Ext Air Sensor A Under Temperature

363, 10073(1), Ext Air Sensor A High Humidity

364, 10074(1), Ext Air Sensor A Low Humidity

365, 10075(1), Supply Chilled Water Loss of Flow

366, 10076(1), Clogged Air Filter

367, 10077(1), Supply Air Sensor Issue

368, 10078(1), Free Cooling Temp Sensor Issue

369, 10079(1), Ext Air Sensor A Issue

Page 18: Emerson Network Power IntelliSlot 485 Card

370, 10080(1), Fan Hours Exceeded

371, 10081(1), Compressor Hours Exceeded (Compressor [1])

372, 10082(1), Compressor Hours Exceeded (Compressor [2])

373, 10083(1), Free Cooling Valve Hours Exceeded

374, 10084(1), Electric Reheater Hours Exceeded (Electric Reheater [1])

375, 10085(1), Electric Reheater Hours Exceeded (Electric Reheater [2])

376, 10086(1), Electric Reheater Hours Exceeded (Electric Reheater [3])

377, 10087(1), Hot Water / Hot Gas Valve Hours Exceeded

378, 10088(1), Humidifier Hours Exceeded

379, 10089(1), Dehumidifier Hours Exceeded

380, 10091(1), Unit Communication Lost

381, 10092(1), Master Unit Communication Lost

382, 10094(1), Unit Code Missing

383, 10098(1), Service Required

384, 10099(1), Humidifier Control Board Not Detected

385, 10104(1), Customer Input 1

386, 10105(1), Customer Input 2

387, 10106(1), Customer Input 3

388, 10107(1), Customer Input 4

389, 10108(1), Dig Scroll Comp Discharge Temp Sensor Issue (Compressor [1])

390, 10109(1), Dig Scroll Comp Discharge Temp Sensor Issue (Compressor [2])

391, 10209(1), Supply Air Over Temperature

392, 10210(1), Supply Air Under Temperature

393, 10211(1), Ambient Air Sensor Issue

394, 10212(1), Compressor Short Cycle (Compressor [1])

395, 10213(1), Compressor Short Cycle (Compressor [2])

Page 19: Emerson Network Power IntelliSlot 485 Card

396, 10214(1), Ext Free Cooling Lockout

397, 10215(1), Reheater Over Temperature

398, 10216(1), Humidifier Cylinder Worn

399, 10217(1), Humidifier Under Current

400, 10218(1), Fan Issue

401, 10219(1), Condenser TVSS Issue

402, 10220(1), Condenser VFD Issue

403, 10221(1), Condenser Issue (Condenser [1])

404, 10222(1), Condenser Issue (Condenser [2])

405, 10223(1), BMS Communications Timeout

406, 10224(1), Digital Output Board Not Detected (iCOM DO Board [1])

407, 10225(1), Digital Output Board Not Detected (iCOM DO Board [2])

408, 10226(1), Digital Output Board Not Detected (iCOM DO Board [3])

409, 10227(1), RAM Battery Issue

410, 10228(1), Water Leakage Detector Sensor Issue

411, 10229(1), External Fire Detected

412, 10230(1), Chilled Water Control Valve Position (Chilled Water Valve [1])

413, 10231(1), Chilled Water Control Valve Position (Chilled Water Valve [2])

414, 10232(1), Unit Off

415, 10233(1), Unit On

416, 10234(1), Unit Partial Shutdown

417, 10235(1), Unit Shutdown

418, 10236(1), High Power Shutdown

419, 10237(1), Unit Standby

420, 10238(1), Maintenance Due

421, 10239(1), Maintenance Completed

Page 20: Emerson Network Power IntelliSlot 485 Card

422, 10240(1), Compressor Low Pressure Transducer Issue (Compressor [1])

423, 10241(1), Compressor Low Pressure Transducer Issue (Compressor [2])

424, 10242(1), Compressor High Pressure Transducer Issue (Compressor [1])

425, 10243(1), Compressor High Pressure Transducer Issue (Compressor [2])

426, 10244(1), Compressor Capacity Reduced

427, 13(1), Minimum Chilled Water Temp Set Point Enable

428, 19(1), Return Air Sensor Event Control

429, 20(1), Ext Air Sensor A Event Control

430, 25(1), System On/Off Control

===========================================