Date: 6-5-2019 Test Reference Number: M060519-01-TAB Place: Waalwijk Model (name/type): CR60-100 MFUS Result: Class C Air temperature (ºC) 21 Atmospheric pressure (Pa) 101980 Pressure �me 120 sec. (standard) Correcon factor 1,002 Surface Area: 0,11 m 2 Case width (m) 0,100 Measuring Equipment: Case Height (m) 0,100 Air leakage tester type: Airow HVLT MK4 M (230V) Duct Length (m) 1 Serial No: 125286 Tielenstraat 17, 5145 RC Waalwijk Other Date cer�ficaon: 12-09-2018 [email protected], www.inatherm.nl Calibraon cert.nr. 21700548 Stac Leakage EN 1751 EN 1751 EN 1751 Reading Pressure Leakage Rig Leakage Duct Surface Corrected Class A Class B Class C (Pa) (N l/s) (l/s) (l/s/m 2 ) (l/s/m 2 ) (l/s/m 2 ) (l/s/m 2 ) 1 400 1,04 1,02 0,102 0,102 1,326 0,442 - 2 1000 1,69 1,67 0,231 0,232 - 0,802 0,267 3 2000 2,43 2,39 0,361 0,362 - - 0,420 From DW/144 Duct Pressure Class Stac pressure limit Posi�ve Nega�ve 1 2 3 4 Pa Pa m/s Low - Class A 500 500 10 Medium - Class B 1000 750 20 High - Class C 2000 750 40 @ Pa: Approved and cer�fied by Cer�ficate nr. : P-97/52-24 x 5 l/s/m2 0.027 x p 0.65 0.009 x p 0.65 0.003 x p 0.65 0,089 0,140 Maximum Air Velocity Air leakage limits litres per second per square metre of duct surface area Visual deformaon? No - EN 1751 Test Report Casing Air Leakage Rate Tested by: Tom Absil Witness by: Yori van Spijk MR/vs010315 Approximate EN 1751 Class D (l/s/m 2 ) 100 1000 0,05 0,50 5,00 OVERPRESSURE Pa LEAKAGE l/s/m 2 EN 1751 Figure C.2 - Classicaon of Case Leakage A B C D

Upload: others

Post on 24-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EN 1751 Test Report Casing Air Leakage RateJun 05, 2019  · EN 1751 Test Report Casing Air Leakage Rate Tested by: Tom Absil Witness by: Yori van Spijk MR/vs010315 Approximate EN

Date: 6-5-2019 Test Reference Number: M060519-01-TABPlace: Waalwijk

Model (name/type): CR60-100 MFUS Result: Class C

Air temperature (ºC) 21Atmospheric pressure (Pa) 101980 Pressure �me 120 sec. (standard)

Correc�on factor 1,002 Surface Area: 0,11 m2

Case width (m) 0,100 Measuring Equipment:Case Height (m) 0,100 Air leakage tester type: Airflow HVLT MK4 M (230V)Duct Length (m) 1 Serial No: 125286 Tielenstraat 17, 5145 RC WaalwijkOther Date cer�fica�on: 12-09-2018 [email protected], www.inatherm.nl

Calibra�on cert.nr. 21700548

Sta�c Leakage EN 1751 EN 1751 EN 1751Reading Pressure Leakage Rig Leakage Duct Surface Corrected Class A Class B Class C

(Pa) (N l/s) (l/s) (l/s/m2) (l/s/m2) (l/s/m2) (l/s/m2)

1 400 1,04 1,02 0,102 0,102 1,326 0,442 -2 1000 1,69 1,67 0,231 0,232 - 0,802 0,2673 2000 2,43 2,39 0,361 0,362 - - 0,420

From DW/144Duct Pressure Class Sta�c pressure limit

Posi�ve Nega�ve1 2 3 4

Pa Pa m/s

Low - Class A 500 500 10Medium - Class B 1000 750 20High - Class C 2000 750 40

@ Pa:

Approved and cer�fied by Cer�ficate nr. : P-97/52-24

x

5l/s/m2

0.027 x p 0.65

0.009 x p 0.65

0.003 x p 0.65

0,0890,140

Maximum Air Velocity

Air leakage limits litres per second per square metre of duct surface area

Visual deforma�on? No

-

EN 1751 Test Report Casing Air Leakage Rate

Tested by: Tom Absil Witness by: Yori van Spijk MR/vs010315

ApproximateEN 1751Class D(l/s/m2)

100

1000

0,05 0,50 5,00

OVE

RPRE

SSU

RE P

a

LEAKAGE l/s/m2

EN 1751 Figure C.2 - Classifica�on of Case Leakage

AB

CD