EN 1 EN

PRODUCT INFORMATION

PURY-P***YNW-A (-BS)

PURY-EP***YNW-A (-BS)

For Europe Regulation

EN 2 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P200YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 22.40 kW

Seasonal space

cooling energy

efficiency

ηs,c 309 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC (dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given outdoor temperatures Tj

Tj = +35 ºC Pdc 22.40 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 5.05 %

Tj = + 30 ºC Pdc 16.51 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 6.11 %

Tj = + 25 ºC Pdc 10.61 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 11.11 %

Tj = + 20 ºC Pdc 10.15 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 16.21 %

Degradation co-efficient air

conditioners** Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater mode PCK 0.044 kW

Thermostat-off mode PTO 0.089 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 10200 m³/h

Sound power level,

outdoor LWA 76.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 3 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P200YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of heat pump: [select which: air]

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 25.00 kW

Seasonal space

heating energy

efficiency

ηs,h 174 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 21.09 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.50 %

Tj = + 2 ºC Pdh 13.45 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.96 %

Tj = + 7 ºC Pdh 8.65 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 7.22 %

Tj = + 12 ºC Pdh 5.64 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 10.07 %

Tj = bivalent

temperature Pdh 22.12 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.61 %

Tj = operation limit Pdh 15.13 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

1.99 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -7.0 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.089 kW Type of energy input

Crankcase heater mode PCK 0.044 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 10200 m³/h

Sound power level, indoor / outdoor

measured

LWA 78.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 4 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P250YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 28.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 316 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC (dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given outdoor temperatures Tj

Tj = +35 ºC Pdc 28.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.69 %

Tj = + 30 ºC Pdc 20.63 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 5.84 %

Tj = + 25 ºC Pdc 13.26 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 10.90 %

Tj = + 20 ºC Pdc 8.93 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 17.30 %

Degradation co-

efficient air

conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater mode PCK 0.044 kW

Thermostat-off mode PTO 0.089 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 11100 m³/h

Sound power level,

outdoor LWA 78.5 dB

if engine driven: Emissions of nitrogen

oxides

NOx -

mg/kWh fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 5 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P250YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 31.50 kW

Seasonal space

heating energy

efficiency

ηs,h 172 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 23.01 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.69 %

Tj = + 2 ºC Pdh 16.96 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.87 %

Tj = + 7 ºC Pdh 10.90 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.96 %

Tj = + 12 ºC Pdh 5.87 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 11.55 %

Tj = bivalent

temperature Pdh 25.71 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.95 %

Tj = operation limit Pdh 15.35 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.00 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -5.2 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.089 kW Type of energy input

Crankcase heater mode PCK 0.044 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 11100 m³/h

Sound power level, indoor / outdoor

measured

LWA 80.0 dB For water-/brine-to-

air heat pumps: Rated brine or water flow

rate, outdoor heat

exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 6 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P300YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×6units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 33.50 kW

Seasonal space

cooling energy

efficiency

ηs,c 297 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 33.50 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.44 %

Tj = + 30 ºC Pdc 24.68 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 5.46 %

Tj = + 25 ºC Pdc 15.87 kW Tj = + 25 ºC EERd or GUEc,bin/AEFc,bin

9.35 %

Tj = + 20 ºC Pdc 11.25 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 16.84 %

Degradation co-

efficient air

conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater mode PCK 0.043 kW

Thermostat-off mode PTO 0.090 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 12000 m³/h

Sound power level,

outdoor LWA 80.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq

(100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 7 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P300YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×6units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 37.50 kW

Seasonal space

heating energy

efficiency

ηs,h 167 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 29.42 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.58 %

Tj = + 2 ºC Pdh 20.19 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.72 %

Tj = + 7 ºC Pdh 12.98 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.89 %

Tj = + 12 ºC Pdh 7.45 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 10.68 %

Tj = bivalent

temperature Pdh 31.80 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.69 %

Tj = operation limit Pdh 19.93 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

1.87 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -6.1 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.0 kW

Thermostat-off mode PTO 0.090 kW Type of energy input

Crankcase heater mode PCK 0.043 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 14400 m³/h

Sound power level, indoor / outdoor

measured

LWA 86.5 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 8 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P350YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×2units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 40.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 298 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 40.00 kW Tj = +35 ºC EERd or GUEc,bin/AEFc,bin

3.98 %

Tj = + 30 ºC Pdc 29.47 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 5.94 %

Tj = + 25 ºC Pdc 18.95 kW Tj = + 25 ºC EERd or GUEc,bin/AEFc,bin

9.66 %

Tj = + 20 ºC Pdc 11.34 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 13.39 %

Degradation co-efficient air

conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater mode PCK 0.051 kW

Thermostat-off mode PTO 0.081 kW Standby mode PSB 0.076 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air conditioner: Nominal

air flow rate, outdoor

measured

- 15000 m³/h

Sound power level,

outdoor LWA 81.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 9 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P350YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×2units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 45.00 kW

Seasonal space

heating energy

efficiency

ηs,h 155 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 31.14 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.46 %

Tj = + 2 ºC Pdh 24.23 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.48 %

Tj = + 7 ºC Pdh 15.58 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.30 %

Tj = + 12 ºC Pdh 8.05 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 8.87 %

Tj = bivalent

temperature Pdh 35.11 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.96 %

Tj = operation limit Pdh 23.98 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.37 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -4.3 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.081 kW Type of energy input

Crankcase heater mode PCK 0.051 kW Standby mode PSB 0.076 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 15000 m³/h

Sound power level, indoor / outdoor

measured

LWA 83.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 10 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P400YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×5units , PEFY-P50VMHS2-E×1unit

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 45.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 283 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 45.00 kW Tj = +35 ºC EERd or GUEc,bin/AEFc,bin

3.88 %

Tj = + 30 ºC Pdc 33.16 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 5.34 %

Tj = + 25 ºC Pdc 21.32 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 8.47 %

Tj = + 20 ºC Pdc 12.41 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 14.79 %

Degradation co-efficient air

conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater mode PCK 0.054 kW

Thermostat-off mode PTO 0.078 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 16200 m³/h

Sound power level,

outdoor LWA 83.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 11 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P400YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×5units , PEFY-P50VMHS2-E×1unit

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 50.00 kW

Seasonal space

heating energy

efficiency

ηs,h 147 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 35.14 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.65 %

Tj = + 2 ºC Pdh 26.92 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.25 %

Tj = + 7 ºC Pdh 17.31 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 5.98 %

Tj = + 12 ºC Pdh 9.27 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 7.70 %

Tj = bivalent

temperature Pdh 38.54 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.97 %

Tj = operation limit Pdh 24.28 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.15 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -4.0 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.078 kW Type of energy input

Crankcase heater mode PCK 0.054 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 18900 m³/h

Sound power level, indoor / outdoor

measured

LWA 88.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 12 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P450YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 50.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 288 %

Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 50.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.04 %

Tj = + 30 ºC Pdc 36.84 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 5.32 %

Tj = + 25 ºC Pdc 23.68 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 8.58 %

Tj = + 20 ºC Pdc 16.33 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 15.50 %

Degradation co-

efficient air

conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater mode PCK 0.054 kW

Thermostat-off mode PTO 0.084 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal air flow rate, outdoor

measured

- 16200 m³/h

Sound power level,

outdoor LWA 83.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25. Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 13 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P450YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 56.00 kW

Seasonal space

heating energy

efficiency

ηs,h 143 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 35.68 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.67 %

Tj = + 2 ºC Pdh 30.15 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.13 %

Tj = + 7 ºC Pdh 19.38 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 5.64 %

Tj = + 12 ºC Pdh 8.63 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 6.73 %

Tj = bivalent

temperature Pdh 41.55 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 3.22 %

Tj = operation limit Pdh 24.52 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.22 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -3.3 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.084 kW Type of energy input

Crankcase heater mode PCK 0.054 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 18900 m³/h

Sound power level, indoor / outdoor

measured

LWA 89.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 14 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P500YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×8units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 56.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 277 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 56.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.40 %

Tj = + 30 ºC Pdc 41.26 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 4.42 %

Tj = + 25 ºC Pdc 26.53 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 8.29 %

Tj = + 20 ºC Pdc 17.46 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 16.32 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.047 kW

Thermostat-off mode PTO 0.091 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 17700 m³/h

Sound power level,

outdoor LWA 82.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 15 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P500YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×8units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 63.00 kW

Seasonal space

heating energy

efficiency

ηs,h 144 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 39.42 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.47 %

Tj = + 2 ºC Pdh 33.92 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.21 %

Tj = + 7 ºC Pdh 21.81 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 5.89 %

Tj = + 12 ºC Pdh 10.45 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 7.70 %

Tj = bivalent

temperature Pdh 45.62 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 3.08 %

Tj = operation limit Pdh 27.60 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.26 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -2.8 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.091 kW Type of energy input

Crankcase heater mode PCK 0.047 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 17700 m³/h

Sound power level, indoor / outdoor

measured

LWA 84.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 16 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-P550YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×8units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 63.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 265 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 63.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 3.93 %

Tj = + 30 ºC Pdc 46.42 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 4.12 %

Tj = + 25 ºC Pdc 29.84 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 7.95 %

Tj = + 20 ºC Pdc 17.34 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 16.00 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.047 kW

Thermostat-off mode PTO 0.091 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 19500 m³/h

Sound power level,

outdoor LWA 83.5 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 17 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-P550YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×8units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 69.00 kW

Seasonal space

heating energy

efficiency

ηs,h 138 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 42.25 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.51 %

Tj = + 2 ºC Pdh 37.15 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.00 %

Tj = + 7 ºC Pdh 23.88 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 5.82 %

Tj = + 12 ºC Pdh 10.62 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 8.58 %

Tj = bivalent

temperature Pdh 48.77 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.95 %

Tj = operation limit Pdh 29.53 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.12 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -2.4 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.091 kW Type of energy input

Crankcase heater mode PCK 0.047 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 24600 m³/h

Sound power level, indoor / outdoor

measured

LWA 89.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 18 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP200YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 22.40 kW

Seasonal space

cooling energy

efficiency

ηs,c 335 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 22.40 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 5.29 %

Tj = + 30 ºC Pdc 16.51 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 7.99 %

Tj = + 25 ºC Pdc 10.61 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 12.28 %

Tj = + 20 ºC Pdc 7.40 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 13.56 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.044 kW

Thermostat-off mode PTO 0.089 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 10200 m³/h

Sound power level,

outdoor LWA 76.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 19 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP200YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of heat pump: [select which: air]

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 25.00 kW

Seasonal space

heating energy

efficiency

ηs,h 184 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 22.20 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.88 %

Tj = + 2 ºC Pdh 13.45 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 4.27 %

Tj = + 7 ºC Pdh 8.65 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 7.24 %

Tj = + 12 ºC Pdh 5.40 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 7.93 %

Tj = bivalent

temperature Pdh 23.20 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.72 %

Tj = operation limit Pdh 14.90 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

1.71 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -8.1 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.089 kW Type of energy input

Crankcase heater mode PCK 0.044 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 10200 m³/h

Sound power level, indoor / outdoor

measured

LWA 78.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 20 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP250YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 28.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 344 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 28.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.98 %

Tj = + 30 ºC Pdc 20.63 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 8.01 %

Tj = + 25 ºC Pdc 13.26 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 12.31 %

Tj = + 20 ºC Pdc 10.00 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 13.60 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.044 kW

Thermostat-off mode PTO 0.089 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 11100 m³/h

Sound power level,

outdoor LWA 78.5 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 21 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP250YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 31.50 kW

Seasonal space

heating energy

efficiency

ηs,h 177 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 22.20 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.94 %

Tj = + 2 ºC Pdh 16.96 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 4.36 %

Tj = + 7 ºC Pdh 10.90 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 7.38 %

Tj = + 12 ºC Pdh 5.40 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 8.08 %

Tj = bivalent

temperature Pdh 25.25 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.72 %

Tj = operation limit Pdh 14.90 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

1.71 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -4.8 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.089 kW Type of energy input

Crankcase heater mode PCK 0.044 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 11100 m³/h

Sound power level, indoor / outdoor

measured

LWA 80.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 22 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP300YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×6units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 33.50 kW

Seasonal space

cooling energy

efficiency

ηs,c 323 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 33.50 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.53 %

Tj = + 30 ºC Pdc 24.68 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 6.26 %

Tj = + 25 ºC Pdc 15.87 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 10.63 %

Tj = + 20 ºC Pdc 11.97 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 17.10 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.043 kW

Thermostat-off mode PTO 0.090 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 12000 m³/h

Sound power level,

outdoor LWA 80.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 23 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP300YNW-A (-BS) Indoor : PEFY-P50VMHS2-E×6units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 37.50 kW

Seasonal space

heating energy

efficiency

ηs,h 166 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 27.52 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.23 %

Tj = + 2 ºC Pdh 20.19 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.97 %

Tj = + 7 ºC Pdh 12.98 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.15 %

Tj = + 12 ºC Pdh 7.29 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 9.12 %

Tj = bivalent

temperature Pdh 31.45 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.85 %

Tj = operation limit Pdh 11.93 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

1.94 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -5.8 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.090 kW Type of energy input

Crankcase heater mode PCK 0.043 kW Standby mode PSB 0.084 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 14400 m³/h

Sound power level, indoor / outdoor

measured

LWA 86.5 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 24 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP350YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×2units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 40.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 333 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 40.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.54 %

Tj = + 30 ºC Pdc 29.47 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 6.31 %

Tj = + 25 ºC Pdc 18.95 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 11.27 %

Tj = + 20 ºC Pdc 13.82 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 15.91 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.051 kW

Thermostat-off mode PTO 0.081 kW Standby mode PSB 0.076 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 15000 m³/h

Sound power level,

outdoor LWA 81.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 25 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP350YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×2units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 45.00 kW

Seasonal space

heating energy

efficiency

ηs,h 161 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 32.24 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.46 %

Tj = + 2 ºC Pdh 24.23 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.49 %

Tj = + 7 ºC Pdh 15.58 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.50 %

Tj = + 12 ºC Pdh 8.34 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 10.28 %

Tj = bivalent

temperature Pdh 35.96 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 3.12 %

Tj = operation limit Pdh 23.10 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.24 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -4.8 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.081 kW Type of energy input

Crankcase heater mode PCK 0.051 kW Standby mode PSB 0.076 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 15000 m³/h

Sound power level, indoor / outdoor

measured

LWA 83.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 26 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP400YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×5units , PEFY-P50VMHS2-E×1unit

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 45.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 311 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 45.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 3.97 %

Tj = + 30 ºC Pdc 33.16 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 6.12 %

Tj = + 25 ºC Pdc 21.32 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 9.23 %

Tj = + 20 ºC Pdc 15.47 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 17.67 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.054 kW

Thermostat-off mode PTO 0.078 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 16200 m³/h

Sound power level,

outdoor LWA 83.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 27 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP400YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×5units , PEFY-P50VMHS2-E×1unit

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 50.00 kW

Seasonal space

heating energy

efficiency

ηs,h 159 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 37.26 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.82 %

Tj = + 2 ºC Pdh 26.92 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.60 %

Tj = + 7 ºC Pdh 17.31 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 5.94 %

Tj = + 12 ºC Pdh 8.27 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 7.10 %

Tj = bivalent

temperature Pdh 40.71 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 3.11 %

Tj = operation limit Pdh 24.87 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.21 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -5.2 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.078 kW Type of energy input

Crankcase heater mode PCK 0.054 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 18900 m³/h

Sound power level, indoor / outdoor

measured

LWA 88.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 28 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP450YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 50.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 307 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 50.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.66 %

Tj = + 30 ºC Pdc 36.84 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 5.76 %

Tj = + 25 ºC Pdc 23.68 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 9.00 %

Tj = + 20 ºC Pdc 15.81 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 16.07 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.054 kW

Thermostat-off mode PTO 0.084 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 16200 m³/h

Sound power level,

outdoor LWA 83.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 29 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP450YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×4units , PEFY-P50VMHS2-E×4units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 56.00 kW

Seasonal space

heating energy

efficiency

ηs,h 151 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 37.35 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.96 %

Tj = + 2 ºC Pdh 30.15 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.52 %

Tj = + 7 ºC Pdh 19.38 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.12 %

Tj = + 12 ºC Pdh 8.63 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 7.31 %

Tj = bivalent

temperature Pdh 41.12 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.95 %

Tj = operation limit Pdh 24.28 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.08 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -3.1 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.084 kW Type of energy input

Crankcase heater mode PCK 0.054 kW Standby mode PSB 0.073 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 18900 m³/h

Sound power level, indoor / outdoor

measured

LWA 89.0 dB For water-/brine-to-

air heat pumps: Rated brine or water

flow rate, outdoor

heat exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 30 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP500YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×8units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 56.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 301 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 56.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 4.41 %

Tj = + 30 ºC Pdc 41.26 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 5.12 %

Tj = + 25 ºC Pdc 26.53 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 9.02 %

Tj = + 20 ºC Pdc 18.30 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 17.52 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.047 kW

Thermostat-off mode PTO 0.091 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 17700 m³/h

Sound power level,

outdoor LWA 82.0 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 31 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP500YNW-A (-BS) Indoor : PEFY-P63VMHS2-E×8units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 63.00 kW

Seasonal space

heating energy

efficiency

ηs,h 148 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 39.57 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.47 %

Tj = + 2 ºC Pdh 33.92 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.23 %

Tj = + 7 ºC Pdh 21.81 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.11 %

Tj = + 12 ºC Pdh 10.93 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 10.04 %

Tj = bivalent

temperature Pdh 45.88 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 3.12 %

Tj = operation limit Pdh 27.00 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.25 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -2.9 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.091 kW Type of energy input

Crankcase heater mode PCK 0.047 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 17700 m³/h

Sound power level, indoor / outdoor

measured

LWA 84.0 dB For water-/brine-to-

air heat pumps: Rated brine or water flow

rate, outdoor heat

exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 32 EN

PRODUCT INFORMATION(1)

Model(s): Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP550YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×8units

Outdoor heat exchanger of air conditioner: [default: air]

Indoor heat exchanger of air conditioner: [default: air]

Type: compressor driven vapour compression or sorption process

if applicable: driver of compressor: [electric motor or internal combustion]

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity Prated,c 63.00 kW

Seasonal space

cooling energy

efficiency

ηs,c 289 %

Declared cooling capacity for part load at given

outdoor temperatures Tj and indoor 27º/19ºC

(dry/wet bulb)

Declared energy efficiency ratio or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = +35 ºC Pdc 63.00 kW Tj = +35 ºC EERd or

GUEc,bin/AEFc,bin 3.94 %

Tj = + 30 ºC Pdc 46.42 kW Tj = + 30 ºC EERd or

GUEc,bin/AEFc,bin 4.82 %

Tj = + 25 ºC Pdc 29.84 kW Tj = + 25 ºC EERd or

GUEc,bin/AEFc,bin 8.87 %

Tj = + 20 ºC Pdc 19.31 kW Tj = + 20 ºC EERd or

GUEc,bin/AEFc,bin 16.28 %

Degradation co-

efficient air conditioners**

Cd 0.25 -

Power consumption in modes other than 'active

mode'

Off mode POFF 0.000 kW Crankcase heater

mode PCK 0.047 kW

Thermostat-off mode PTO 0.091 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air air

conditioner: Nominal

air flow rate, outdoor

measured

- 19500 m³/h

Sound power level,

outdoor LWA 83.5 dB

if engine driven:

Emissions of nitrogen

oxides

NOx -

mg/kWh

fuel input

GCV

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on

the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 33 EN

PRODUCT INFORMATION(1)

Information to identify the model(s) to which the information relates :

Outdoor : PURY-EP550YNW-A (-BS) Indoor : PEFY-P71VMHS2-E×8units

Outdoor heat exchanger of heat pump: [select which: air

Indoor heat exchanger of heat pump: [select which: air]

Indication if the heater is equipped with a supplementary heater: no

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons

are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 69.00 kW

Seasonal space

heating energy

efficiency

ηs,h 141 %

Declared heating capacity for part load at indoor

temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or gas utilization

efficiency / auxiliary energy factor for part load at given

outdoor temperatures Tj

Tj = - 7 ºC Pdh 41.19 kW Tj = - 7 ºC COPd or

GUEh,bin/AEFh,bin 2.51 %

Tj = + 2 ºC Pdh 37.15 kW Tj = + 2 ºC COPd or

GUEh,bin/AEFh,bin 3.03 %

Tj = + 7 ºC Pdh 23.88 kW Tj = + 7 ºC COPd or

GUEh,bin/AEFh,bin 6.24 %

Tj = + 12 ºC Pdh 11.00 kW Tj = + 12 ºC COPd or

GUEh,bin/AEFh,bin 11.14 %

Tj = bivalent

temperature Pdh 47.78 kW

Tj = bivalent

temperature

COPd or

GUEh,bin/AEFh,bin 2.95 %

Tj = operation limit Pdh 27.92 kW Tj = operation limit COPd or GUEh,bin/AEFh,bin

2.06 %

For air-to-water heat

pumps: Tj = - 15 ºC (if

TOL < - 20 ºC)

Pdh - kW

For water-to-air heat

pumps: Tj = - 15 ºC

(if TOL < -20 ºC)

COPd or

GUEh,bin/AEFh,bin - %

Bivalent temperature Tbiv -2.0 ºC

For water-to-air heat

pumps: Operation

limit temperature

Tol - ºC

Degradation co-

efficient heat pumps** Cdh 0.25 -

Power consumption in modes other than 'active

mode' Supplementary heater

Off mode POFF 0.000 kW Electric back-up

heating capacity * elbu 0.000 kW

Thermostat-off mode PTO 0.091 kW Type of energy input

Crankcase heater mode PCK 0.047 kW Standby mode PSB 0.080 kW

Other items

Capacity control fixed/staged/variable

For air-to-air heat

pumps: Nominal air

flow rate, outdoor

measured

- 24600 m³/h

Sound power level, indoor / outdoor

measured

LWA 89.0 dB For water-/brine-to-

air heat pumps: Rated brine or water flow

rate, outdoor heat

exchanger

- - m³/h

Emissions of nitrogen

oxides (if applicable) NOx - mg/kWh

GWP of the refrigerant 2088 kg CO2 eq (100 years)

Contact details Name and address of the manufacturer or of its authorised representative.

** If Cd is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25.

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the

manufacturer or importer.

(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 34 EN