Page 1: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Enabling Objective 1.3

Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive

Controller

Page 2: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

IMPULSE® ControlsAdvantages

• Lowers Operating Costs and Minimizes Equipment Downtime

– AC Squirrel Cage Induction Motors for Variable Speed Control Provide Reliability

– Electronic Reversing, Multi-Speed Operation Eliminates Conventional Magnetic Contactors

– Electronic Dynamic Braking Provides Effective Braking without the Use of Mechanical Brakes

Page 3: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

IMPULSE® ControlsAdvantages

• Variable Speed Control w/Single-Speed Motor

• Minimizes High-Starting Current w/Motor

• Adjust Acceleration/Deceleration Rates

• Unique Torque Limit Function

• Creep Speed for Precise Positioning without Plugging

• Can Produce 150% Full Load Torque

Page 4: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

IMPULSE® ControlsAdvantages

• Inverter Output Frequencies >

60Hz are Possible

• Retrofit Existing AC Equipment • Motor Insulation class should be considered

Page 5: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• Brake Set Delay Timers

• Ultra Lift™

• Slip Compensation

• Stall Prevention

• Alternate Acceleration/Deceleration

• Micro-Positioning Control™

• Built-In Auto-Tuning

IMPULSE®•VG+ Series 3

Software Features

IMPULSE® Drive

Page 6: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• Motor Torque Proving at Start

• Roll Back Detection at Start

• Seized Brake Detection at Start

• Brake Proving at Stop

• Torque Limited Load Check™

• Torque Limited Accel and Decel

• Built-In Auto-Tuning

IMPULSE®•VG+ Series 3

Software Features

IMPULSE® Drive

Page 7: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• Quick Stop™

• Reverse Plug Simulation™

• Multi-Level Password

• Motor Thermal Overload Protection

• Motor Phase Loss Detection

• Ground Fault Protection

• Slack Cable Protection

Software Features

IMPULSE®•VG+ Series 3

IMPULSE® Drive

Page 8: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• Overload/Load Check Counter

• Number of Operations

• Short Circuit Protection

• Built-In Serial Communication

• Fault History and Tracing via Flash ROM

• Elapsed Run Timer

Software Features

IMPULSE®•VG+ Series 3

IMPULSE® Drive

Page 9: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• Closed Loop control via Encoder

• Speed Set Points with Torque Limit

• Determines Motor Slip

• Calculates Torque Demand

• Quick Response to Changes in Torque Demand

IMPULSE®•VG+ Series 3

Theory of Operation

IMPULSE® Drive

Page 10: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• Adjusts Torque Producing Current without Increasing Magnetizing Current

IMPULSE®•VG+ Series 3

Theory of Operation

IMPULSE® Drive

Page 11: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

In Simple Terms

• The VG+ series 3 controller is basically a 3 phase AC voltage to DC voltage to 3 phase AC voltage converter.

 

• It starts by receiving 480Vac power and utilizes a 3 phase rectifier to supply a DC bus.

Page 12: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

AC to Dc Conversion

AC INPUT

DC BUS

Page 13: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• The DC bus is then applied to an Output Transistor assembly to produce square wave pulses. These pulses are modulated and become additive to produce an output voltage at the desired frequency and amplitude. A basic bidirectional Inverter…

Page 14: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

DC to AC conversion

Gate Drive Board

DC Bus

Page 15: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

PWM Inverter

Page 16: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

PWM Inverter

Page 17: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

3-Phase PWM

Page 18: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

PWM Waveforms

Page 19: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Load Reactors

• Load Reactors (Coils) are utilized to protect the drive unit from collapsing motor fields or short circuits and they improve the efficiency by creating a more perfect sine wave.

Page 20: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

Selecting Line/Load ReactorsLoad Reactors

• Used on the Load Side of the AFD between AFD and Motor

• Protects the Drive under Motor Short Circuit Conditions

• Reactor Attempts to Recreate Perfect Sine Wave, Improves Motor Efficiency

• Use the Full Load Ampere Rating of the Motor When Selecting Load Reactors

Page 21: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• The Rectifier section of the Drive is energized when power is applied to the crane and remains so . When a drive signal is called upon to start and run a motor, a 3 phase output is developed and delivered to the motor.

IMPULSE®•VG+ Series 3

Theory of Operation

IMPULSE® Drive

Page 22: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Flux Vector “A Vector Drive uses feedback of various real world

information (encoder and CT’s) to further modify the PWM pattern to maintain more precise control of the desired operating parameter, be it current, speed or torque. Using a more powerful and faster microprocessor, it uses the feedback information to calculate the exact vector of voltage and frequency to attain the goal. In a true closed loop fashion, it goes on to constantly update that vector to maintain it. It tells the motor what to do, then checks to see if it did it, then changes its command to correct for any error.”

Page 23: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Flux Vector “A true closed Loop Vector Drive can also make an

AC motor develop continuous full torque at zero speed. This makes them suitable for crane and hoist applications where the motor must produce full torque before the brake is released or else the load begins dropping and it can't be stopped. Closed Loop is also so close to being a servo drive that some people use them as such. The shaft encoder can be used to provide precise travel feedback by counting pulses”

Page 24: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Flux Vector Control Typical

IMPULSE® Drive

Page 25: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Light Load

IMPULSE® Drive

Page 26: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Heavy Load

IMPULSE® Drive

Page 27: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Dynamic Braking

• When slowing down of stopping a motor, Dynamic Braking is utilized. Dynamic Braking occurs when the applied frequency/voltage delivered to the stator is lowered. Due to inertia, the rotor speed can now be faster than the delivered stator speed which results in the motor becoming a generator. Since Generated Voltage is proportional to Speed “N”(differential or slip) times the Magnetic Flux “O” a voltage is now delivered back through the inverter section to the DC bus. Eg = Ofield X Ndifferential

Page 28: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Dynamic Braking

• A Dynamic Braking Unit is connected across the +/- DC bus and this acts to dissipate the energy and limit the rise of DC voltage.– Without the Dynamic Braking resistor, damage

would occur to the drive unit.

Page 29: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

With Dynamic Braking

Page 30: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

V/F Ratio

Page 31: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

V/F Curve

Page 32: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

Torque & Horsepower vs. Speed

Page 33: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

Theoretical V/F Ratio w/Voltage Boost

Page 34: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

Encoder Specifications• Heavy Duty Industrial Type

• Output Resolution – 1,024 Pulses per Revolution

• 12V DC Differential Line Driver Output

• Connected to Motor Shaft to Provide Zero Backlash

• Shielded Cable

IMPULSE® Drive

Page 35: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE•VG+ Series 3 PG-T2 Board

IMPULSE® Drive

Page 36: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

PG-X2 Card Inputs/Test Points

IMPULSE® Drive

Page 37: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

• Initial Inspection

• Check Programming Parameters

• Check Encoder Connections

• Confirm Rotation of Motor

• Auto Tune Motor

Start-Up Procedure

IMPULSE®•VG+ Series 3

• Take No-Load Reading

• Load Test

• Check Brake Proving

• Save Parameters

IMPULSE® Drive

Page 38: Enabling Objective 1.3 Describe the Design of the Magnetek Impulse VG+ series 3 Variable Frequency Drive Controller

IMPULSE® Drive

Selecting Line/Load Reactors

• Acts as a Current Limiting Device

• Filters the Waveform and Attenuates Electrical Noise Associated with AFD Output

• Use Continuous Output Rating of the

Line Reactors