energi savr node qs - lutron electronics, inc. - dimmers … dali 369243c.pdf · 2012-10-31 ·...
TRANSCRIPT
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 1 05.19.10
Energi Savr Node QSThe Energi Savr Node QS unit is a DIN-rail mounted controller for DALI-compliant Digital Addressable loads. It provides DALI bus power and control for two independent DALI Buses with up to 64 ballasts each. The Energi Savr Node QS unit also provides direct connections and power for the following Lutron® devices:
•Occupancysensors•Daylightsensors•IR receivers•QS devices
Features•ProvidespowerforeitheroneortwobusesofDALI
compliant digital addressable loads (up to 250 mA per bus).
•EachDALIBuscancontrolamaximumof16zones.•Powerfailurememoryretainscontrolunitprogram-
ming in the event of a power loss.•Defaultconfigurationrequiresnocommissioning.•ProgrammingavailableviatheEnergi Savr Node QS
hand-held device.•Fouroccupancysensorinputsforautomatedcontrol
of lights in areas.
•Fourdaylightsensorinputsautomaticallyadjustlightlevels based on the amount of natural light entering through the windows.
•FourIRreceiverinputsforpersonalcontrol.•Addmoreoccupancysensors,daylightsensors,orIRreceiversbyconnectingQSSensorModules(QSMs).
•IncludesQScontrollinkforseamlessintegrationoflights,motorizedwindowtreatments,controlsta-tions,andQSSensorModules.
•Energi Savr Node QS units andQSSensorModulescan be used in a Quantum®systemtocontrolandmanage light in an entire building.
500-13431 Rev. B
N1771Z096
Energi Savr Node QS
Ballast
seeTouch® QS Wallstation
Ballast
Ballast
Ballast
Quantum Panel
LUTRON
LUTR
ON
R
QS Contact Closure Interface
GRAFIK Eye QSEnergi Savr
Node QS
LUTRON
LUTR
ON
R
Up to 64 ballasts on each loop
QS Control Link
DALIBus1
DALI Bus 2Ballast
Ballast
Energi Savr Node QS
Energi Savr Node QS
Quantum Panel
GRAFIKEyeQS
QS Contact Closure Interface
seeTouch® QS Wallstation
Ballast
Ballast
IR Receiver
DaylightSensor
OccupancySensor
220-240 V~ Upto100total QS devicesEthernet
ProgrammingLink
Onesensorgroupshown; connections
available for up to four sensor groups.
Wireless Communication QSM
RadioPowrSavrTM OccupancySensor(upto10perQSM)
Radio Powr Savr DaylightSensor (upto10perQSM)
PicoTM Wireless Controller (up to10perQSM)
Wired Daylight
Sensors*Wired Occupancy Sensors*
Wired IR Receivers*
*Upto4wiredsensorstotal(ofanytype)
Note:MultipleQSMscanbeadded to increase the number of wireless sensors and Pico wireless controllers.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 2 05.19.10
Typical Application: Requires commissioning
OccupancyS
ensorD
aylightS
ensor
Loop 2Loop 1
Versaplex Q
S
LUTRON
Wired to
sensor group 4
Open Offices Corridor Private Offices
OccupancySensor
QS Link
OccupancySensor
OccupancySensor
Energi Savr Node QS
Energi Savr Node QS
DaylightSensor
DALILoop
DALILoop
DALILoop
seeTouch® QS Wallstation
Win
dow
Win
dow
Win
dow
LUTRON OccupancySensor Daylight
Sensor
LUTRON
OccupancySensor Daylight
Sensor
LUTRON
OccupancySensor Daylight
Sensor
LUTRON
seeTouch® QS Wallstation
OccupancySensor
DaylightSensor
LUTRON
DALILoop
DALILoop
DALILoop
QS
Lin
k
QS Link
OpenOffices Corridor PrivateOffices
seeTouch® QS Wallstation
seeTouch® QS Wallstation
QSLink
QSLink
QSLink
Win
dow
Win
dow
Win
dow
DALI Bus
Daylight Sensor
Daylight Sensor
Daylight Sensor
Daylight Sensor
Daylight Sensor
Occupancy Sensor
Energi Savr Node QS
Energi Savr Node QS
Occupancy Sensor
Occupancy Sensor
Occupancy Sensor
Occupancy Sensor
Occupancy Sensor
Occupancy Sensor
DALI Bus
DALI Bus
DALI Bus
DALI Bus
DALI Bus
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 3 05.19.10
OccupancySensor
OccupancySensor
Loop 2
Wired to sensor group 2
Loop 1
Perimeter Interior
Win
dow
Win
dow
Energi Savr Node QS
Wired to sensor group 1
OccupancySensor
DaylightSensor
Loop 2Loop 1
Perimeter Interior
Win
dow
Win
dow
Energi Savr Node QS
LUTRON
Wired to sensor group 4
preconfigured mode 2two Zones with occupancy Sensors* Six fixtures shown on each bus, however,
up to 64 fixtures can be connected per bus.
preconfigured mode 1perimeter Daylighting* four fixtures shown on bus 1 and eight
fixtures shown on bus 2, however, up to 64 fixtures can be connected per bus.
Occupancy Sensor Daylight SensorConnectedtosensorgroup1 ControlsBus1only ControlsBus1onlyConnected to sensor group 2 ControlsBus2only ControlsBus2onlyConnected to sensor group 3 Controls both Buses ControlsbothBuseswithequaldaylightgainConnected to sensor group 4 Controls both Buses ControlsbothBuseswithlowerdaylightgainonLoop2
Default behavior for Sensor connections
Simple Applications: Preconfigured modes require no commissioning
Troubleshooting and Maintenance Features•Maintainsredundantmemoryofballastprogrammingforeaseofsingleormultiple
ballast replacement.•Afterinstallation,"TEST"buttonverifiesDALIwiringonallfixtures•StatusLEDsverifyconnectionstocontrolstationsandsensors.•Afterinstallation,Energi Savr Node QSunitidentifiesballastcommunicationfail-
ures.
Perimeter PerimeterInterior Interior
Win
dow
Win
dow
Win
dow
Win
dow
Daylight Sensor
Wired to sensor group 4
Wired to sensor group 2
Wired to sensor group 1
Energi Savr
Node QS
Energi Savr
Node QS
Occupancy Sensor
Occupancy Sensor
Occupancy Sensor
Bus1 Bus1Bus 2
Bus 2
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 4 05.19.10
Specifications
Energi Savr Node QS
Power
•220-240V 50/60Hz,maxcurrentdraw100mA•LightningstrikeprotectionmeetsANSI/IEEEstandard62.31-1980.Canwithstandvoltagesurgesofupto 6 000 V and current surges of up to 3 000 A.
•DALIBusOutput:18V 250mAmaximumperbus.
Standards
•IEC60669-2-1•Lutron®QualitySystemsregisteredtoISO9001.2000
Environment
•AmbientTemperatureOperatingRange:0ºCto40ºC•Relativehumidity:lessthan90%non-condensing•Forindooruseonly
Terminals
•Mainswiring:1,0mm2to4,0mm2(18AWGto12AWG)•DALIBusWiring:1,0mm2to4,0mm2(18AWGto12AWG)•SensorWiring:1,0mm2to2,5mm2 (18AWGto14AWG)
Mounting
•MountstostandardDINrail•Width=9modules(161,7mm)
DALI Buses
•Upto64DALIcompliantloadsoneachbuscanbead-dressedandgroupedinto16zones
•Energi Savr Node QS unit supplies 250 mA to power each bus.
•DALIBuswiresarepolarityinsensitiveandtopology-free.
QS Link Limits
•TheQSlinkcanhaveupto100devicesand100zones.•EachEnergi Savr Node QS unit counts as one device towardthe100devicelimit.
•Eachassignedzonecountstowardthe100zonelimit.•SeeTable1(page6)fordevicedetails.
Occupancy Sensors Connected to the Energi Savr Node QS unit
•Useoccupancysensorstoautomaticallyturnthelightsoffinanareaafixedtimeafteritbecomesvacant.
•Useoccupancysensorstoautomaticallyturnthelights on in area when it becomes occupied and toautomaticallyturnthelightsoffinanareaafixedtimeafteritbecomesvacant.
•Fouroccupancysensorscanconnectdirectlytothe Energi Savr Node QS unit.
•Eacharea'soccupiedlevelandunoccupiedlevelcan be programmed.
•PowerSupplyOutputs(4) - 20-24 V 50mAmaximum. -Anauxiliarypowersupplymustbeusedifthe
devicerequiresmorethan50mA.•Occupancysensormustprovideadrycontact
closure or solid-state output.
Daylight Sensors Connected to the Energi Savr Node QS unit
•Lutrondaylightsensorsallowdaylightharvestingwith programmable gain settings in up to four gain groups per area.
•FourdaylightsensorscanconnectdirectlytotheEnergi Savr Node QS unit.
Infrared Receivers Connected to the Energi Savr Node QS unit
•UseLutron IR receivers for personal control of individuallightingzones.
•FourIRreceiverscanconnectdirectlytothe Energi Savr Node QS unit.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 5 05.19.10
Specifications (continued)
QSM (QS Sensor Module) - Integrating Wired and Wireless Sensors
•UsetheQSMtointegrateRadioPowrSavrTMOccupancy/Vacancysensors,Radio Powr Savr Daylightsensors,andPicoTMWirelessControllerstocontrolzonesontheEnergi Savr Node QS unit.
•Assignupto10Radio Powr SavrOccupancy/Vacancysensors per Energi Savr NodeQSunitviaQSM.
•Assignupto10Radio Powr SavrDaylightsensorsperEnergi Savr Node QSunitviaQSM.
•Assignupto10Pico Wireless Controllers per Energi Savr Node QS unit viaQSM.
•AddadditionalwiredandwirelesssensorsbyaddingQSSensorModulestotheQSlink.
• Wireandpowerupto4wiredsensors(ofanytype)total —Daylightsensors —Occupancysensors — Infrared (IR) sensors
•TheRadio Powr Savr sensors and Pico Wireless Control-lersassociatedwiththeQSMshouldbemountedwithin60ft(18m)lineofsight,or30ft(9m)throughwalls,oftheQSM.
•RefertoQSMSpecificationSubmittalformoreinforma-tion.
Accessory Controls•seeTouch®QSwallstationscanbeconfiguredto
control Energi Savr Node QSunitzones.•Selectoneof16scenesandoffinEnergi Savr Node QS
unit areas.•ControlindividuallightingzonesinEnergi Savr Node QS
unit areas.•EachEnergi Savr Node QS unit can power up to three
seeTouch QS controls.•LEDindicatordisplaysthestatusofprogrammedlights.
Communication with GRAFIK Eye® QS•Energi Savr Node QSunitzonesrespondto
GRAFIK Eye QS scene buttons in areas associ-ated with the GRAFIK Eye QS.
•Energi Savr Node QSunitzonesrespondtoscenecommandsinitiatedbytheGRAFIK Eye QSastronomictimeclockinareasassociatedwith the GRAFIK Eye QS.
•Energi Savr Node QS unit operates in afterhours mode in areas associated with a GRAFIK Eye QS that is in afterhours mode.
Communication with QSE-IO•Energi Savr Node QSunitzonesrespondtoscenecommandsinitiatedbytheQSE-IOinsceneselectionmodeoroccupancysensormode.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 6 05.19.10
QS System LimitsThetablebelowliststhedevicesavailableontheQSlink.Seebelowforeachdevice’scounttowardthelinkmaximumsforzonesanddevices.
AQSlinkcanhaveupto100zones(outputs)and100devices.Energi Savr NodeQSunitcansupply3power draw units.
Table 1: QS System Limits
QS Device Description
Zone Count
Device Count
Power Draw Units (supplied)
Power Draw Units (consumed)
Energi Savr Node QS DALI QSNE-2DAL-D up to 32 1 3 0
QSSensorModule 0 1 0 3
Lutron®OccupancySensor(connectedtoQSSensorModule)* 0 0 0 2
LutronDaylightSensor(connectedtoQSSensorModule)* 0 0 0 0.5
Lutron Infrared(IR)Receiver(connectedtoQSSensorModule)* 0 0 0 0.5
3-zoneGRAFIKEye® QS 3 1 3 0
4-zoneGRAFIK Eye QS 4 1 3 0
6-zoneGRAFIK Eye QS 6 1 3 0
6-zoneGRAFIK Eye QS with DALI 6 1 3 0
8-zoneGRAFIK Eye QS with DALI 6 1 3 0
16-zoneGRAFIK Eye QS with DALI 6 1 3 0
seeTouch® QS 0 1 0 1
QS contact closure interface up to 5 1 0 3
QSnetworkinterfaceforaudio-visualintegration 0 1 0 2
QSlinkpowersupply 0 0 8 0
*Note:PowerdrawunitsareconsumedbyOccupancySensors,DaylightSensors,andIRReceiversonlyifconnectedtotheQSSensorModule(QSM).PowerdrawcalculationsarenotneededforwirelesssensorsorsensorsconnecteddirectlytotheEnergi Savr Node QS units.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 7 05.19.10
Mechanical Dimensions
500-13431 Rev. B
N1771Z096
161.6mm(6.36 in)
60.6 mm (2.39in)
500-13431 Rev. B
N1771Z096
89.7mm(3.53 in)
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 8 05.19.10
Overview of Wiring Terminals
500-13431 Rev. B
N1771Z096
mains Wiring
Dali bus 1*
Dali bus 2*QS
linkSensorsprogramming
port
* Wire Dali according to local codes.
PELV
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 9 05.19.10
Wiring: Line Voltage
Wiring from Distribution to Bus Supply
•Turnoffbreakeratdistributionpanel.
•Runline,neutral,andgroundwiresfroma 220-240V~50/60HzfeedtotheEnergi Savr Node QS unit.
Emergency Lighting Applications
•Usenormal(non-essential)poweronly.
•Whennormalpowerdropsout,theEnergi Savr Node QS unit will not power the DALI Buses. When thisoccurs,ballastspoweredfromemergencyfeedsgototheiremergencymode,fulllightoutputbydefault.
Mains Wiring and Low Voltage Separation
•TheEnergi Savr Node QS unit is designed to sepa-ratemainswiringfromPELVcircuits.
•Followappropriatelocalandnationalcodestoavoidviolatingrequiredseparationguidelines.
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
n
l
Distribution panel
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 10 05.19.10
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
Wiring: DALI Bus
The Energi Savr Node QSunitwillsupplypowertoanindependentDALIBus,whichsupportsamaxi-mum of 64 ballasts.
DALI Wiring
•DALIwiringisnotSELV.
•DALIwiringistreatedasmainsvoltage,andthusmayberunwithinthesamesheathing.
•Ensurethatthereisnogreaterthana2Vdropbetween the Energi Savr Node QS unit and the end of the DALI Bus.
•Consultallnationalandlocalelectricalcodesforseparationrequirements.
Wire GaugeMaximum DALI-compliant Bus Wire Length
4,0mm2(12AWG) 671m(2200ft)2,5mm2(14AWG) 427m(1400ft)1,5mm2(16AWG) 275m(900ft)1,0mm2(18AWG) 175m(570ft)
DALI1
DALI1
DALI 2
DALI 2
DALI Bus 1
DALI Bus 2
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 11 05.19.10
Wiring: QS Control Link
PELV QS System Low-Voltage Wiring
•Systemcommunicatesusinglow-voltagewiring.
•Wiringmaybedaisychainedort-tapped.
•Wiringmustberunseparatefromline/mainsvolt-age.
•Totallengthofcontrollinkmustnotexceed600m.
•Usetwo1,0mm2(18AWG)conductorsforcontrolpower(24V,COM).
•Useone,twisted-shieldedpairof1,0mm2(18AWG)fordatalink(MUX,MUX).
500-13431 Rev. B
N1771Z096
(1)(2)(3)(4)
com24 VmuXmuX
Daisy-Chain Wiring Example
EnergiSavrNode QS unit
Sivoia® QS Shade
QSM Sivoia® QS SmartPower
Panel
seeTouch® QS Wallstations
500-13431 Rev. B
N1771Z096
QSControlLink
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 12 05.19.10
Wiring: QS Control Link (continued)T-Tap Wiring Example
Sivoia® QS SmartPower
Panel
Sivoia® QS Shade
seeTouch® QS Wallstations
QSM
Energi Savr Node QS unit
QSControlLink
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 13 05.19.10
4 3
2 1 C B A
4 3
2 1 C B A
4 3
2 1 C B A
4 3
2 1 C B A4
3 2
1 C B A
4 3
2 1 C B A
4 3
2 1 C B A
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
ESN1powerswallstation1only;terminal2 terminates at wallsta-tion1
Wiring: QS Control Link (continued)Low-Voltage Wiring Example
ESN = Energi Savr Node QS unit
eSn 3
eSn 1
eSn 2
eSn 4
1 2
3
4
5
6
7
ESN4powerswallstations5,6,and7only;noterminal2connec-tion between wallstations 4 and 5
ESN3powerswallstations2,3,and4only;noterminal2connectionbetween wallstations 4 and 5
ESN2andESN3havetheirownpowersupply;noterminal2con-nection
•Connecttheterminal1,3,and4connectionstoallcontrolinterfaces.•Eachcontrolunithasitsownpowersupply.Terminatetheterminal2
connection (24 V power) so that each control unit supplies power to amaximumofthreewallstations.Donotconnectterminal2betweenan Energi Savr Node QSunitandanyotherEnergi Savr Node QS unitand/oranotherpowersupply.
•Eachwallstationshouldreceivepowerfromonlyoneunit.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 14 05.19.10
500-13431 Rev. B
N1771Z096
Wiring: Class 2 SensorsElectrical Contractors and Engineers
•AllsensorwiringisPELV.Followallapplicablenationaland local codes for proper circuit separation and pro-tection.
•Class2sensorterminalsaccept1.0-2.5mm2 (18-14AWG)solidconductors.
•MainsvoltageandPELVwiringmustbekeptseparate.
Wiring Instructions:•Turnoffbreakeratdistributionpanel.
Daylight Sensor:•Connectthefourconductorstothefourterminalsas
shown.•Terminals: Red=20V Black=Common White=IR Yellow=Daylight•DaylightSensormustbeplacedwithin30mofthe
Energi Savr Node QS unit.
noteS:•Onedaylightsensorcanbewiredtoeachsensor
group.•Consultthedaylightsensorspecificationsheettoproperlylocatethesensor.
•Donotplacethesensorabovependants,fixtures,directlybelowlightingfixtures,orwithinskylightwells.
Occupancy Sensor:•Connectthreeconductorstothreeterminalsas
shown.•Oneoccupancysensorcanbewiredtoeachsensor
group.
IR Receiver:•Connectthethreeconductorstothethreeterminals
as shown.•Receivermustbeplacedwithin30moftheEnergi
Savr Node QS unit.noteS:
•OneIRReceivercanbewiredtoeachsensorgroup. *IfadaylightsensorandIRreceiverareconnected,donotconnectthedaylightsensor'sIRoutput(white wire).
NOTE: There are four sensor groups.Eachgroup wires the same and is shown above.
20 V
IR Receiver
DaylightSensor
OccupancySensor
Common
500-13431 Rev. B
N1771Z096
LUTRON
OccupancySensorDaylight/IRSensor IR Receiver*
Red
Black
Yello
w
Blu
e
Black
Red
Red
Black
Whi
te
Whi
te*
500-13431 Rev. B
N1771Z096
SensorGroup1
Sensor Group 3
Sensor Group 2
Sensor Group 4
LUTRONR
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QS QSNE-2DAL-D DALI Fixture Controller
369-243c 15 05.19.10
Installation of Programming Connection•TheEnergi Savr Node QS Hand-Held Device is used to program Energi Savr Node QS units in installations re-quiringcommissioning.
•ConnectiontothesystemismadeviaWi-Fithroughawirelessrouterasshownbelow.•Itisrecommendedthatthepersonprogrammingthesystemisabletoseeallofthelightsduringtheprogram-
ming process.
NOTE:EthernetprogrammingconnectionnotusedwhentheEnergi Savr Node QS unit is part of a Quantum®
system.
•IfEnergi Savr Node QSunitisaccessibleandlocatedsuchthatlightsarevisiblefromtheWi-Ficoveragearea,thenthewirelessroutercanbeconnecteddirectlytoEnergi Savr Node QS unit as shown below.
Recommended: Install Wall Jack for Commissioning
Alternate Approach: Router connected directly to the Energi Savr Node QS unit
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
500-13431 Rev. B
N1771Z096
Wireless Router (byothers)
QSControlLink
Wireless Router (byothers)
QSControlLink
Energi Savr Node QS unit
Energi Savr Node QS unit
Wireless router- connectedtemporarily(duringsystemcommissioning and futureadjustments)orpermanently.
All lights should be visible fromthe wireless coverage area ofthe router
Wireless router- connectedtemporarily(duringsystemcommissioning and futureadjustments)orpermanently.
All lights should be visible fromthe wireless coverage area ofthe router
DedicatedEthernetconnection* for Energi Savr Node QS units
* Note: Energi Savr Node QSunitsarenotdesignedtoexistonanopennetwork.ConnectiontoanopennetworkcouldresultinreducedperformanceandEthernetconnectivityissues.
* Note: Energi Savr Node QSunitsarenotdesignedtoexistonanopennetwork.ConnectiontoanopennetworkcouldresultinreducedperformanceandEthernetconnectivityissues.
DedicatedEthernetconnection* for Energi Savr Node QS units
EasilyaccessibleEthernetwalljackinstalledintheareacontaining the lights