energy transfer and heat load analysis
TRANSCRIPT
![Page 1: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/1.jpg)
MECH 8250Building Systems
Winter 2015
1.Lecture: January 12th
Lab: January 13th
2015-03-31 1Mech8250 - Building Systems
![Page 2: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/2.jpg)
Energy (Heat) Transfer
• Air
• Water
• Steam
Mech8250 - Building Systems
• At standard temperature 20C (70F)• Latent Heat of Water at 0C (32F)
2015-03-31 2
![Page 3: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/3.jpg)
Thermodynamics
Mech8250 - Building Systems
• 1 psig = 2.31 ft. wg.• 7000 gr = 1.0 lbw
AIR Imperial Units SI Units
qtotal 4.5 · CFM · ∆h Btu/h 1.22 · L/s. ∆h(W) W
qsensible 1.08 · CFM· ∆t (°F) Btu/h 1.22 · L/s · ∆t(°C) W
qlatent 0.68 · CFM · W (LBSW/LBSA) Btu/h 3.0 · L/s · ∆w(gw/kgDA) W
4840 · CFM · W (LBSW/LBSA) Btu/h 2500 · L/s · W (kgW/kgdA) W
WATER Imperial Units SI Units
qtotal 500 · GPM · ∆t(°F) Btu/h 4180· (L/S) · ∆t(°C) W
= gpm x (ti‐tf) / 24 Tons Btu/h
2015-03-31 3
![Page 4: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/4.jpg)
Air Heating and Cooling Process (Sensible Heat Only)Q = 1.08 * CFM * ΔT (BTU/h)
Example A room has a heat loss of 10,000 BTU/h. This room is supplied with 95 F heated air to maintain a room temperature of 72 F. Calculate the volume flow rate of the heated air supplied to the room.
Mech8250 - Building Systems2015-03-31 4
![Page 5: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/5.jpg)
Air Heating and Cooling Process (Sensible Heat Only)Q = 1.22 * L/s * ΔT (W)
Example An electrical resistance heater is used to heat 250 L/s of supply air to a temperature of 35 C. Calculate the electrical heating capacity for the electrical resistance heater when the heated air is sufficient to maintain a room temperature of 20 C.
Mech8250 - Building Systems2015-03-31 5
![Page 6: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/6.jpg)
Water Heating and Cooling ProcessQ = 500 * GPM * ΔT
Example:Heating water supply flows at 100 gpm through a heating coil with water entering at a temperature of 200F and leaving the coil at a temperature of 180F. Determine the heating coil capacity and also the amount of outdoor air that can be heated from outside temperature at 10F to a room temperature of 70F.
Mech8250 - Building Systems2015-03-31 6
![Page 7: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/7.jpg)
Part 2: Heat Load
1. Conduction
3. Radiation
2. Convection
7Mech8250 - Building Systems2015-03-31
HEAT TRANSFER
![Page 8: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/8.jpg)
Conduction Heat transfer
• Fourier’s law of heat conduction
• Empirical statement based on experimental observations and is given by:
• K = Thermal Conductivity
Mech8250 - Building Systems2015-03-31 8
![Page 9: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/9.jpg)
Radiation Heat transfer
• Transfer does not require a medium for transmission
• Energy transfer occurs due to the propagation of electromagnetic waves
• A body due to its temperature emits electromagnetic radiation, and it is emitted at all temperatures.
• Speed of light (3 x 108 m/s) in a straight line in vacuum. Its speed decreases in a medium but it travels in a straight line in homogenous medium.
Mech8250 - Building Systems2015-03-31 9
![Page 10: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/10.jpg)
Convection Heat transfer
• Convection heat transfer takes place between a surface and a moving fluid, when they are at different temperatures
Mech8250 - Building Systems2015-03-31 10
![Page 11: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/11.jpg)
Design Conditions - OUTDOORSASHRAE
DBT 99.6%, 99%
-7C -4C18F 24F
ASHRAE
DBT / WBT 0.4%, 1%, 2%
24.4C/18.3C 23.C/17.8C 21.7C/16.7C76F/65F 74F/64F 71F/62F
ASHRAE1. Winters: In cold spells, DBT can drop below the design conditions for a week or more.2. Summers: The design conditions represent recent conditions on hot, mostly sunny days. BCBC – APPENDIX C – DIVISION B - CLIMATIC AND SEISMIC INFORMATION FOR BUILDING DESIGN IN CANADA
1. Winters: On the basis of average temperatures of January months over past 25 years. 1% =8 hours (Ordinary spaces) ; 2.5% =19 hours (Ordinary spaces) are colder than design
2. Summers: On the basis of average temperatures of July months over past 25 years. 2.5% =19 hours (Ordinary spaces) are hotter than design.
Building Code BCBC
DBT (January)
1% , 2.5%
Vancouver -9C -7C 15.8F 19.4F
Building Code BCBC
DBT / WBT (July)
2.5%
Vancouver 26C / 19C78.8F / 66.2F
Difference between Critical and Non-critical is 3C (5.6F) = 10% more conservative
Mech8250 - Building Systems2015-03-31 11
![Page 12: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/12.jpg)
Heating Load
• It is the thermal energy that must be replenished into the space in order to maintain the desired comfort conditions
• HVAC systems are used to maintain thermal conditions in comfort range
Mech8250 - Building Systems2015-03-31 12
![Page 13: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/13.jpg)
Purpose of Load Estimate
• Load profile over a day
• Peak load (basis for equipment sizing)
• Operation Energy analysis
• HVAC Construction cost
Mech
82
50
-B
uild
ing System
s
2015-03-31 13
![Page 14: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/14.jpg)
Principles of Heating Load Estimate
1. Design conditions– Outdoor & indoor
2. Envelope (Roof, Walls, Windows, Floor)– Conduction
– Convection
– Radiation
3. Infiltration Loss– Mechanical Ventilation
– Cracks and Openings (Air changes)
4. Heat Gains – Not to be accounted for (Why?)– Internal
– External or Solar
Mech8250 - Building Systems2015-03-31 14
![Page 15: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/15.jpg)
1. Enclosure Heat Transfer
1. Transmission Losses
1. Walls, Roof, Windows, Doors etc.
Q sensible = A * U * (Ti – To)
2. Floors on Slab
Q sensible = F* P * (Ti-To)
2. Infiltration LossesQ sensible = 1.08 * V * (Ti – To)
Q latent = 4840 * V * (Wi – Wo)
Mech8250 - Building Systems
A = AreaU = air to air heat transfer
coefficientTi = Indoor temperatureTo = Outdoor temperature
F = Floor Heat Loss CoefficientP = Perimeter
V = Volumetric air flow rateWi = Humidity ratio of indoor airWo= Humidity ratio of outdoor air
2015-03-31 15
![Page 16: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/16.jpg)
Heat transfer through a wall
Mech8250 - Building Systems2015-03-31 16
![Page 17: Energy transfer and heat load analysis](https://reader034.vdocument.in/reader034/viewer/2022042602/55a6c0e31a28ab3b688b4873/html5/thumbnails/17.jpg)
Difference between Winters and Summers
1. Temperatures outside conditioned spaces are generally lower than maintained space temperatures.
2. Credit for solar or internal heat gains is not included3. Thermal storage effect of building structure or content is ignored.4. Thermal bridging effects on wall and roof conduction are greater for
heating loads than for cooling loads, and greater care must be taken to account for bridging effects on U-factors used in heating load calculations.
Mech8250 - Building Systems2015-03-31 17