3903005 03.22 Installation & Operating Manual
ENERVEXADM & ADF AUTOMATED DAMPER
ENERVEX Inc.1685 Bluegrass Lakes Parkway Alpharetta, GA 30004USA
P: 770.587.3238 F: 770.587.4731 T: 800.255.2923 [email protected] www.enervex.com
READ AND SAVE THESE INSTRUCTIONS!
UL File E467733
2
3903005 03.22
This symbol shows that the ENERVEX ADM/ADF Automatic Dampers are listed in the US and certified for Canada under Underwriters Laboratories Inc. file no. E467733.
IMPORTANT: READ THESE INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION.
• EXAMINE ALL COMPONENTS FOR POSSIBLE SHIPPING DAMAGE PRIOR TO INSTALLATION.
• PROPER JOINT ASSEMBLY IS ESSENTIAL FOR A SAFE INSTALLATION. FOLLOW THESE INSTRUCTIONS EXACTLY AS WRITTEN. CHECK SECURENESS OF JOINTS UPON COMPLETION OF ASSEMBLY.
WARNINGFailure to follow these installation instructions could cause FIRE, CARBON MONOXIDE
POISONING, and/or DEATH. If you are unsure of installation requirements, contact ENERVEX.
UL File E467733
Symbol LegendThe following terms are used throughout this manual to bring attention to the presence of potential hazards, or to important information concerning the product.
DANGER: Indicates an imminent hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING: Indicates an imminent hazardous situation which, if not avoided, may result in personal injury or property damage.
How to use this manual This installation manual does not contain any system design documentation. System design documentation is available from any authorized ENERVEX representative. Accessories, fans, and variable frequency drives are not covered by this manual. Please refer to these component’s individual manuals.
TO REDUCE THE RISK OF FIRE, ELECTRI-CAL SHOCK OR INJURY TO PERSONS, OB-SERVE THE FOLLOWING:
1. Use this unit in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed on the front of the manual.
2. Before servicing or cleaning the unit, switch off at service panel and lock service panel to prevent power from being switched on accidentally.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with applicable codes and standards.
4. Follow the appliance manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers ASHRAE), and the local code authorities.
5. This unit must be grounded.
3
3903005 03.22
Content1. PRODUCT INFORMATION 1.1 Function ............................................................3 1.2 Shipping ...........................................................3 1.3 Warranty ...........................................................3
2. SPECIFICATIONS AND DIMENSIONS 2.1 Dimensions and Capacities ...............................4
3. MECHANICAL INSTALLATION 3.1 General .............................................................5
4. ELECTRICAL INSTALLATION 4.1 Wiring ...............................................................6
5. MAINTENANCE 5.1 General .............................................................7
1. PRODUCT INFORMATION
1.1 FUNCTIONThe ENERVEX ADM/ADF Automatic Damper is a single blade, two position damper powered by an actuator. The ADM/ADF is available in standard stack diameters ranging from 4 to 36 inches. The actuator interlocks with a boiler or gas fireplace to open the damper when the appliance is in use, and close it when the appliance is not in use.
The ADM/ADF is powered by a 120 VAC or 24 VAC/VDC actuator. The actuator is equipped with a fail safe system to open the damper in the event of an electrical or mechanical failure. It has an adjustable NO/NC endswitch to provide damper position open/closed.
The ADM damper is manufactured to connect to chimneys w/o flange connections. The ADF damper is manufactured to connect to chimneys with a standard 1/2" flanged connection. The ADM/ADF is rated for temperatures up to 1400oF (760oC).
The ADM/ADF should be installed with sufficient clearance above the boiler outlet to allow for damper protrusion into the stack when fully open. ADM/ADF nameplates located as shown on diagram below. It is for installation with gas-fired or oil-fired equipment only.1.2 SHIPPING• Standard Packing List
• ADM/ADF is shipped completely assembled
1.3 WARRANTY2-Year Factory Warranty. Complete warranty conditions are available from ENERVEX, Inc.
4
3903005 03.22
Model Stack ID (in)
Dia. A in / mm
Dim. B in / mm
Dim. C in / mm
Dim. D in / mm
ADM 6 6 5.85 / 146 8.0 / 203 7.85 / 199 10.85 / 276
ADM 8 8 7.85 / 197 8.0 / 203 9.85 / 250 12.85 / 326
ADM 10 10 9.85 / 248 10.0 / 254 11.85 / 301 14.85 / 377
ADM 12 12 11.85 / 298 10.0 / 254 13.85 / 352 16.85 / 428
ADM 14 14 13.85 / 349 10.0 / 254 15.85 / 403 18.85 / 479
ADM 16 16 15.85 / 400 10.0 / 254 17.85 / 453 20.85 / 530
ADM 18 18 17.85 / 451 12.0 / 305 19.85 / 504 22.85 / 580
ADM 20 20 19.85 / 502 12.0 / 305 21.85 / 555 24.85 / 631
ADM 22 22 21.85 / 552 14.0 / 356 23.85 / 606 26.85 / 682
ADM 24 24 23.85 / 603 14.0 / 356 25.85 / 657 28.85 / 733
ADM 26 26 25.85 / 654 16.0 / 406 27.85 / 707 30.85 / 784
ADM 28 28 27.85 / 705 16.0 / 406 29.85 / 758 32.85 / 834
ADM 30 30 29.85 / 756 16.0 / 406 31.85 / 809 34.85 / 885
ADM 32 32 31.85 / 806 16.0 / 406 33.85 / 860 36.85 / 936
ADM 34 34 33.85 / 857 18.0 / 457 35.85 / 911 38.85 / 987
ADM 36 36 35.85 / 908 18.0 / 457 37.85 / 961 40.85 / 1038
Model Stack ID in / mm
Dim. A in / mm
Dim. B in / mm
Dim. C in / mm
ADF 4 4 3.94 / 100 4.88 / 124 8.86 / 225
ADF 6 6 5.91 / 150 6.85 / 174 10.83 / 275
ADF 8 8 7.87 / 200 8.82 / 224 12.80 / 325
ADF 10 10 9.84 / 250 10.79 / 274 14.76 / 375
ADF 12 12 11.81 / 300 12.76 / 324 16.73 / 425
ADF 14 14 13.78 / 350 14.72 / 374 18.70 / 475
ADF 16 16 15.75 / 400 16.69 / 424 20.67 / 525
ADF 18 18 18.00 / 457 19.00 / 483 23.00 / 584
ADF 20 20 20.00 / 508 21.00 / 533 25.00 / 635
ADF 22 22 22.00 / 559 23.00 / 584 27.00 / 686
ADF 24 24 24.00 / 610 25.00 / 635 29.00 / 737
ADF 26 26 26.00 / 660 27.00 / 686 31.00 / 787
ADF 28 28 28.00 / 711 29.00 / 737 33.00 / 838
ADF 30 30 30.00 / 762 31.00 / 787 35.00 / 889
ADF 32 32 32.00 / 813 33.00 / 838 37.00 / 940
ADF 34 34 34.00 / 864 35.00 / 889 39.00 / 991
ADF 36 36 36.00 / 914 37.00 / 940 41.00 / 1041
6.0˝
ØA
Nameplate
C
ØB
Nameplate
ADM
ADF
Other sizes available upon request.
2. SPECIFICATIONS AND DIMENSIONS
2.1 DIMENSIONS AND CAPACITIES
5
3903005 03.22
Draft Hood
Appliance
Damper
Boiler FlueConnection
BarometricDamper
Damper
ADF
V-Band
VentSection
3. MECHANICAL INSTALLATION
3.1 GENERALThe ADM has male-male slip connections. Install the ADM in the vent system at least one vent diameter (B) plus one foot above an appliance outlet and at least three vent diameters away from any tee or elbow.
The ADF has standard flanged connections. Install using the accompanying V-Band and a gasket seal. Install the ADF in the vent system at least one vent diameter (A) plus one foot above an appliance outlet and at least three vent diameters away from any tee or elbow as shown in the figures on the right.
DO NOT COVER ACTUATOR WITH INSULATION.THE ADM AND ADF ARE FOR INSTALLATION WITH GAS-FIRED OR OIL-FIRED EQUIPMENT ONLY.
MINIMUM CLEARANCE TO COMBUSTIBLE IS 18”.
6
3903005 03.22
N L1
H L2
On/Off wiring for TFX120-S
On/Off wiring for TFX120-S
120 VAC
0˚ to 95˚
S1
1 Neutral
2 Hot
NC
NO
S2
S3
On/Off wiring for TFX24-S
24 VAC Transformer
S1NC
1 Common
NO
S2
S3 0˚ to 95˚
On/Off wiring for TFX24-S
2 + Hot
4. ELECTRICAL INSTALLATION
4.1 WIRING
Wire that actuator for 2 wire/ 2 position operation as shown in Figure 1 (120 VAC) and Figure 2 (24 VAC) on the right.
The actuator should be set for clockwise (CW) rotation and should fail to the ADM/ADF open postiion. Verify settings of the actuator before installation.
Verify voltage of actuator before connecting to a power supply. Acuator will run on either 120VAC or 24VAC/VDC.
Vérifiez la tension de l’actionneur avant de le connecter à une source d’alimentation. Acuator fonctionnera sur 120VAC ou 24VAC / VDC.
!
DANGERTurn off electrical power before servicing. Contact with live electric components can cause shock or death.
Éteignez l’alimentation électrique avant de procéder à l’entretien. Le contact avec des composants électriques sous tension peut provoquer un choc ou la mort.
Fig. 1 120 VAC Actuator
Fig. 2 24 VAC/VDC Actuator
7
3903005 03.22
5. MAINTENANCE
5.1 GENERALAnnual maintenance is recommended. During the maintenance check, verify the damper blade is in the correct position (the indicator on the damper rod will show the position of the damper blade). Check that the damper rod is firmly secured by the actuator and tighten fasteners if necessary.
ENERVEX Inc.1685 Bluegrass Lakes Parkway Alpharetta, GA 30004USA
P: 770.587.3238 F: 770.587.4731 T: 800.255.2923 [email protected] www.enervex.com
3903
005
03.