Steven Waidelich
Prescriptive Analysis Egress Structural Fire Alarm and
Detection and Smoke Control
Water-Based Suppression
Performance Analysis Design Fires Tenability Human Behavior RSET vs ASET
Slide 3
Applicable Codes
International Building Code 2006 and 2018
National Fire Protection Association(NFPA)
NFPA Standard 101, Life Safety Code
NFPA 13, Standard for the Installation of Sprinkler Systems
NFPA 24, Standard for the Installation of Private Fire Service Mains and their Appurtenances
NFPA 70, National Electric Code (NEC)
NFPA 72 National Fire Alarm Code
Unified Facilities Criteria (UFC)
UFC 1-200-01, General Building Requirement
UFC 3-600-01, Fire Protection Engineering for Facilities
UFC 4-02-01 Mass Notification Systems
Slide 4
Slide 5
Slide 6
Offices -Area A
Atrium -Area B
ConferenceCenter - Area C
Slide 7
Construction type – IIB
Automatic Sprinkler System and a secondarywater supply
Minimum one sprinkler riser or combinationstandpipe system riser
Fire pump
Water supply to required fire pumpsSlide 12
Slide 8
Slide 9
Floor Occupants Per Floor Required No. of Exits Provided No. of Exits
1 676 3 3
2 621 3 3
3 204 2 4
4 314 2 2
5 6 2 2
.
Slide 10
Slide 11
Slide 12
Slide 13
Slide 14
Slide 15
Slide 16
Slide 17
Slide 18
Slide 19
Slide 20
Slide 21
Floor
Total Occupant load (People)
Required Stair Entry Door Width
0.2*Total Occ (inches)
Provided Stair Entry Door Width (inches)
Required Stair Width
0.3*Total Occ (inches)
Provided Stair Width (inches)
1 676 135 297 NA NA
2 621 124 132 186 192
3 204 41 66 61 96
4 314 63 66 94 96
5 6 2 NA 20 NA
Slide 22
Level Maximum Diagonal Measurement (feet)
Required Separation Distance (feet)
Provided Separation Distance (feet)
1 311 104 370
2 306 101 548
3 317 105 259
4 321 106 259
5 NA NA NA
Slide 23
Slide 24
Building:-Has three distinct occupancies-Was constructed with occupancy separations that meet Life Safety Code 101, Chapter 6, Table 6.1.14.4.1 for occupancy fire resistive separations-Was constructed of reinforced concrete-Used metal curtain walls
Windows:-Triple paned, designed to handle up to 100 mph wind
Foundation: -Driven piles with concrete pile caps to distribute the building loads from the reinforced concrete columns for the five-story building
Stairwells: -Reinforced concrete with two-hour fire rated fire walls-On floors one through three, the balcony walls around the open office plan are one-hour fire and smoke rated.
The facility is protected throughout by an automatic sprinkler system and meets the International Building Code requirement for having half the perimeter open to the public way.
Slide 25
Construction Type IIB
Building Height 65 ft.
Phase 1 current area per floor 150,342 ft2
Constructed Building Square Footage
The facility design follows the International Building Code Section 506.2.4 exception and Section 508.4
Slide 26
IBC 2015/ UFC 1-200-01 Building Classification
Construction Type I-IV IIB
Allowable Height 75 ft. 65 ft.
Allowable Area 23,000 23,000
Allowable Stories 4 4
Slide 27
2-hour fire rated walls:Stairways, elevator shafts, and utility shafts
All other areas are fire and smoke barriers
Slide 27
Slide 28
Slide 29
Fire alarm is Class A
Voice evacuation integrated with MNS speaker system
Separate visible appliances
Simplex Annunciator panels are located near each entrance and exit doors, as well as on the outer balcony or in the hallway near each elevator lobby on each floor
Slide 29
Slide 30
Fire Alarm and Mass Notification System
Multi-Candela Addressable Combination Strobe Assembly
Fire alarm panel Simplex 4100U
Slide 31
Duct smoke detectors in the air handling supply and return ducts
Smoke detectors in elevator lobbies, over the main fire alarm panel located in the fire pump and riser room
Manual fire alarm pull stations
Slide 32
Slide 33
Slide 34
Sequence of Operations for Atrium Smoke Exhaust Fans.
.
Slide 35
Slide 36
Building has: Combination automatic wet pipe sprinkler Class I standpipe system Fire Pump – Peerless Model 5AEF12
Horizontal Split Case Pump rated 1000 GPM @ 235 psi
Standby Power Standpipe System:
3 - 6” combination standpipe riser
Slide 37
Automatic Sprinklers
Potter Vane Type Water Flow Alarm
Sprinkler System initiate devices:
Tamper switch
Slide 38
Slide 39
Slide 40
Slide 41
Slide 42
Class I standpipe system ranging between 4 and 6 inch standpipes, located in Stairs 1, 3, 4, and 5
4-way fire department connection
Existing 6” standpipe riser in stair 3 with 2 ½” hose valves on floor landings levels on all levels
Remaining stairwells have 2 ½” hose connections
Two 2 ½” hose valves on the roof on Stair 3 and 4
Slide 44
Slide 45
Prescriptive Analysis Prescriptive analysis was designed and met
requirement for building intended occupant loads and use.
Occupants are using the building outside of the design and current use does not for safe use for event occupancies in the atrium
Egress
Structural Fire Alarm and Detection
and Smoke Control Water-Based Suppression
Slide 46
521mod0 - Slide 47
Life Safety Compliance Options (2018 NFPA 101 4.4) Design Fire Scenario 1 is an atrium design fire involving an electrical fire
igniting a portable stage. the impact to egress and substantial number of people exposed to the
fire. Design Fire Scenario 2 on the second-floor reception mezzanine, involves
refreshments using chaffing dishes and has a Sterno can overturning and igniting the table. This scenario was considered due to its location and impacts
Design Fire Scenario 3 is a single workstation fire that was considered due to the 100 plus workstations on any given floor. a traveling fire, and again it was shown to not be a factor for impact to the
staff or surrounding area for egress.
Slide 48
Design fires were selected as to meet NFPA 101 performance based designs:◦ The atrium fire was selected due to the location and most likely
for a fire to occur.◦ The mezzanine fire was selected based on the location and
potential for egress to be impacted due to the open balcony and conference center being interconnected to the space.
◦ The third design fire is the single workstation, also called cubicles. Selected due to construction and location of exits. In addition
the potential to spread be for the sprinklers are activated to control the fire.
Slide 49
Fuel Material Orientation
Scenario 1 – Atrium Fire Carpet, Plywood. Horizontal with Podium vertical orientation
Scenario 2 – Mezzanine Fire High Density Polyethene Horizontal orientation
Scenario 3- 3rd Floor Office area signal workstation
Particle Board desk, with plastic laminate
Horizontal particle board desk with plastic laminate.
Plastic and Textile Laminate Vertical orientation
Slide 50
Scenario 1 was chosen.It is an atrium design fire involving an electrical short igniting a portable stage
Slide 51
Slide 52
U.S. Air Force General Joseph L. Lengyel, Chief of the National Guard Bureau and member of the Joints Chiefs of Staff, addresses Air National Guard Airmen and civilians March 26, 2018 at Joint Base Andrews, Maryland. Lengyel discussed the National Defense Strategy and how ANGRC members work to implement it.(Air National Guard photo by Master Sgt. Marvin R. Preston/Released Slide 53
Slide 54
Stage Located on First Floor. Photo U.S. Air National Guard photo/Tech. Sgt. John E. Hillier.
Slide 55
Atrium fuel package◦ Stage has a back drape made of fire resistive
polyethylene and cotton◦ Stage floor is constructed on carpet tiles covering
plywood ◦ Carpet is of unknown mixed, but assumed to be ◦ Ignition source is assumed to be an electrical source
igniting the stage floor◦ Podium is assumed to be plywood with melamine oak
laminate.
�̇�𝑄 𝑡𝑡 = 𝛼𝛼𝑡𝑡2
𝛼𝛼 = 𝐻𝐻𝐻𝐻𝐻𝐻𝐻𝐻𝐻𝐻𝐻𝐻 � 𝑉𝑉𝑠𝑠2 � 𝜋𝜋t= 160 Seconds (from Slide 57)
Slide 56
Slide 57
Slide 58
Slide 59
5 Stories, 4 occupied131’ x 285’ business occupancies2 stairways North & SouthStairs are 48” clear widthStair doors are 33” clear widthStairs are 7” x 11”Landings have 4’ x 8’ floorFirst Floor Exit sign is LEDCorridor is 6 ft. wide48-7=41” w/boundary layer
Maximum flow Stairs 18.5 person/min/ft.18.5 x 3.42 63 person/min36” door specification24 person/min/ftEffective width 24” x 2=48 person/min
Speed on stairs212-2.86 ft./minx212x0.175)12x 1.85=22.2 ft. + (2x4)=30.2 ft.38.2/105=0.36 min/floor
Time 40 minutes-calculated; 5-7 minutes during drills-actual
Slide 60
Slide 61
Slide 62
Total Evacuation TimesEquation 2: RSET = 𝑡𝑡𝑑𝑑 + 𝑡𝑡𝑎𝑎 + 𝑡𝑡𝑜𝑜 + 𝑡𝑡𝑖𝑖 + 𝑡𝑡𝑒𝑒+ 𝑡𝑡𝑒𝑒
Floor Detection and Notification
Time,
𝑡𝑡𝑑𝑑 + 𝑡𝑡𝑎𝑎(sec)
Pre-movement and Action Time,
𝑡𝑡𝑜𝑜 + 𝑡𝑡𝑖𝑖(sec)
Travel
Time,
𝑡𝑡𝑒𝑒(sec)
Stairs Travel Time
𝑡𝑡𝑒𝑒(sec)
RSET Total Time
(sec)
1.5 times RSET
(sec)
1st 35 60 40 0 135 202
2nd 35 60 101 14 210 315
*3rd floor balcony
35 60 33 269 397 596
Note: *Third and Fourth Floor are combined.
Tenability Criteria
Slide 63
Smoke Density of 0.15 [1/m] (SFPE Handbook Table 61.3)
Visibility of 6.8M (SFPE Handbook Table 61.3) Temperature of 55oC (pg. 2377 of SFPE Handbook)Determine smoke layer heightoMore than 6 feet above floor
• Method 3-LSC Section 5.2.2o Less than 6 feet in any space
• Method 2-LSC Section 5.2.2
Slide 64
Slide 65
Slide 66
Slide 67
Slide 68
Slide 69
Slide 70
Slide 71
Scenario demonstrated the current design for non assembly activities is properly designed.
The scenario shows with the stage and combustible the current smoke removal system and egress component through the stairway doors is not adequate.
The scenario shows the stairway width while adequate for non atrium events, cannot support occupant loads greater than 330 person.
Toxicity levels are modeled showing HCN, and CO levels below the incapacitant levels, and death.
Slide 72
Performance-Based Analysis Performance-based design analysis with the atrium
fire has smoke on the 3rd floor , while visibility is sufficient for evacuation, it will slow the evacuation
Exit capacity is does not meet the occupant loads when atrium events are held.
The stairway doors are designed for 149 persons where the occupant load is assumed to have an occupant load of 774 people.
First floor has ample exit capacity even with the obstructed south end of the atrium.