engineering data...design manual rweq-tatju · tatja, 208 / 230 v rweq-taydu · tayda, 460 v...
TRANSCRIPT
Design ManualRWEQ-TATJU · TATJA, 208 / 230 VRWEQ-TAYDU · TAYDA, 460 V RWEQ-TAYCU, 575 V
EDUS301864B-D202009
Engineering Data
Heat Pump 60 HzHeat Recovery 60 Hz
EDU
S301864B-D
ENG
INEER
ING
DA
TA VR
V T-Series Water C
ooled System H
/P & H
/R 60 H
z DESIG
N M
AN
UA
L
1
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Table of Contents
1. FeaturesandBenefits ................................................................................32. Nomenclature .............................................................................................43. Model Names .............................................................................................8
3.1 Outside Units ....................................................................................83.2 Indoor Units .....................................................................................103.3 Branch Selector Unit ....................................................................... 113.4 Air Treatment Equipment ................................................................ 11
4. External Appearance ................................................................................124.1 Outside Units ..................................................................................124.2 Indoor Units .....................................................................................134.3 Branch Selector Unit .......................................................................144.4 Air Treatment Equipment ................................................................14
5. Outside Unit Combination ........................................................................156. Interchangeability .....................................................................................167. Capacity Range ........................................................................................17
7.1 Connection Ratio ............................................................................177.2 Indoor Unit Connection Capacity ....................................................187.3 Limitation of Capacity Index for Heat Recovery ..............................19
8. Specifications ...........................................................................................208.1 RWEQ-TATJU / TATJA ....................................................................208.2 RWEQ-TAYDU / TAYDA ..................................................................348.3 RWEQ-TAYCU ................................................................................48
9. Dimensions ...............................................................................................6210. Service Space ..........................................................................................6511. Center of Gravity ......................................................................................6612. Piping Diagrams .......................................................................................6713. Wiring Diagrams .......................................................................................6814. Field Wiring ..............................................................................................74
14.1 Heat Pump ......................................................................................7414.2 Heat Recovery ................................................................................77
15. Electrical Characteristics ..........................................................................8016. Operation Limits .......................................................................................83
16.1 Heat Pump ......................................................................................8316.2 Heat Recovery ................................................................................84
17. Operation Limits (Antifreeze Usage) ........................................................8517.1 Heat Pump ......................................................................................8517.2 Heat Recovery ................................................................................86
2
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
18. Sound Levels (Reference Data) ...............................................................8719. Accessories ..............................................................................................90
19.1 Optional Accessories ......................................................................9020. Selection Procedure .................................................................................91
20.1 Selection Procedure ........................................................................9121. Instructions for Antifreeze Usage .............................................................97
21.1 Instruction of Setting Water (Brine) Lower Flow Limit % for Variable Flow System ......................................................................97
22. Caution for Refrigerant Leaks ..................................................................9922.1 Introduction .....................................................................................9922.2 Procedure for Checking Maximum Concentration ........................100
23. Safety Devices Setting ...........................................................................10223.1 FXFQ-T .........................................................................................10223.2 FXZQ-TA .......................................................................................10223.3 FXUQ-P .........................................................................................10223.4 FXEQ-P .........................................................................................10223.5 FXDQ-M ........................................................................................10323.6 FXSQ-TA .......................................................................................10323.7 FXMQ-PB ......................................................................................10323.8 FXMQ-M .......................................................................................10323.9 FXHQ-M ........................................................................................10423.10 FXAQ-P .......................................................................................10423.11 FXLQ-M, FXNQ-M .......................................................................10423.12 FXTQ-TA .....................................................................................104
Appendix......................................................................................................1051. Introduction .............................................................................................106
1.1 ED Book List .................................................................................1061.2 Publication List of Engineering Data for VRV Products ................107
3
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
1. Features and Benefits
•Wideofferingwith8,10and12tonsinglemoduleandupto36¹tonswithmulti-module• Flexible System design with increased diversity up to 150%² • Up to 50%² and 38%² reduction in space and weight respectively to install systems of similar
capacity when compared to RWEYQ-PC series •Triple-stackcapabletodeliverupto36¹tonsin3.2m(10.5ft.)ceilingheight•Flexibleandeasyinstallationwithfieldselectabletoporfrontrefrigerantconnections•Designflexibilitywithlongpipinglengthsupto300m(980ft.)total(165m(540ft.)max.linear
liquid piping length) and up to 30 m (100 ft.) vertical separation between indoor units• Engineered with heat rejection cancelation technology³ to minimize mechanical room
conditioning requirements•YearroundcomfortandenergyefficiencybycombiningVRV and Variable Refrigerant
Temperature (VRT) technologies•2-9Vvariablewaterflowcontrollogicasstandardtoincreasewatersidesystemoperationalefficiencies
• Refrigerant cooled inverter technology to deliver consistent and reliable printed circuit board operations
• Factory ships ready for Geothermal applications •Easycommissioningwithabilitytoprogramsettingsoffsiteusingnewconfiguratortool•3-digit7-segmentdigitaldisplayontheunitforimprovedandfasterconfiguration,commissioning,
and troubleshooting• Engineered for easy service with drop-down electrical box to access key components• Seamless integration to full suite of Daikin Control Solutions for complete system control• Backed by 10 year parts limited warranty and 10 years replacement compressor limited
warranty *
¹-35.5tonfor575Vunits²-Modelspecific,checkproductspecificationfordetails³-Refertoinstallationmanualforfieldsettingsrequiredtoactivatethisfeature* Complete warranty details available from local distributor or manufacturer's representative
4
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
2. Nomenclature
Outside Unit
Standard symbolU: North American modelsA: Minor revision for North American models
Power supply symbolTJ: 3 phase, 208/230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 Hz
Indicates minor change category
Indicates major design category
Capacity indication in cooling
RefrigerantQ: R410A
Indicates that this is aRWE: Heat pump / Heat recovery water cooled
Q YC UT A432RWE
5
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Indoor Unit
M 54 VJPB UX QF
Standard symbolU: United States of America
Power supply symbolVJ: 1 phase, 208/230 V, 60 HzSBL: 1 phase, 120 V, 60 Hz
Indicates major design category
Capacity indication in cooling05: 5,800 Btu/h 18: 18,000 Btu/h 48: 48,000 Btu/h07: 7,500 Btu/h 24: 24,000 Btu/h 54: 54,000 Btu/h09: 9,500 Btu/h 30: 30,000 Btu/h 60: 60,000 Btu/h12: 12,000 Btu/h 36: 36,000 Btu/h 72: 72,000 Btu/h15: 15,000 Btu/h 42: 42,000 Btu/h 96: 96,000 Btu/h
RefrigerantQ: R410A
ShapeF: Ceiling mounted cassette (Round flow with sensing)Z: VISTA™ 2 × 2 cassette unitU: 4-way blow ceiling-suspendedE: One way blow cassetteD: Slim ceiling mounted ductS: MSP concealed ducted unitM: Ceiling mounted ductH: Ceiling suspendedA: Wall mountedL: Floor standingN: Concealed floor standingT: Air handling unit (FXTQ)
Series categoryX: Inverter
Unit categoryF: Indoor unit for air cooled typeC: Cased coil unit
6
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Branch Selector Unit
Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz
Indicates major design category
Capacity indication36: 36,000 Btu/h60: 60,000 Btu/h96: 96,000 Btu/h
Refrigerant: R410A
Unit categoryBS: Branch selector unit
BS T VJQ 36
Single Branch Selector Unit
Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz
Indicates major design category
Capacity indication of connectable indoor units per branch 54: 54,000 Btu/h
Refrigerant: R410A
Number of branches4: 4 branches 6: 6 branches 8: 8 branches10: 10 branches12: 12 branches
Unit categoryBSF: Branch Selector unit (Flex series)BS: Branch selector unit (Standard series)
BS T VJQ4 54
Multi Branch Selector Unit
7
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Air Treatment Equipment
M 48 VJ UM FX QF
Standard symbolU: United States of America
Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz
Outdoor air processing unit
Indicates major design category
Capacity indication in cooling48: 48,000 Btu/h72: 72,000 Btu/h96: 96,000 Btu/h
RefrigerantQ: R410A
ShapeM: Ceiling mounted duct
Series categoryX: Inverter
Unit categoryF: Indoor unit for air cooled type
Outdoor Air Processing Unit
UG300V A M VJ
Standard symbolU: United States of America
Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz
Indicates major design category
Airflow rate (H)300: 300 cfm 600: 600 cfm470: 470 cfm 1200: 1,200 cfm
Mounted type
Air
Ventilation
Energy Recovery Ventilator (VAM series)
8
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
3. Model Names3.1 Outside Units
Capacity range 8 ton 10 ton 12 ton 16 ton 18 ton 20 ton 22 ton Power supply, StandardCapacity index 96 120 144 192 216 240 264
Heat pump / Heat recovery 208/230 V RWEQ 96TA 120TA 144TA 192TA 216TA 240TA 264TA TJU, TJAHeat pump / Heat recovery 460 V RWEQ 96TA 120TA 144TA 192TA 216TA 240TA 264TA YDU, YDAHeat pump / Heat recovery 575 V RWEQ 96TA 120TA 144TA 192TA 216TA 240TA 264TA YCU
Capacity range 24 ton 26 ton 28 ton 30 ton 32 ton 34 ton 36 ton * Power supply, StandardCapacity index 288 312 336 360 384 408 432
Heat pump / Heat recovery 208/230 V RWEQ 288TA 312TA 336TA 360TA 384TA 408TA 432TA TJU, TJAHeat pump / Heat recovery 460 V RWEQ 288TA 312TA 336TA 360TA 384TA 408TA 432TA YDU, YDAHeat pump / Heat recovery 575 V RWEQ 288TA 312TA 336TA 360TA 384TA 408TA 432TA YCU
* 35.5 ton for 575 V units
TJ: 3 phase, 208/230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 Hz
Heat Pump / Heat Recovery 208/230 V
Model name RWEQ96TATJU RWEQ120TATJU RWEQ144TATJUOutside unit 1 RWEQ96TATJU RWEQ120TATJU RWEQ144TATJU
Model name RWEQ192TATJU RWEQ216TATJU RWEQ240TATJU RWEQ264TATJU RWEQ288TATJUOutside unit 1 RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU RWEQ144TATJUOutside unit 2 RWEQ96TATJU RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU
Model name RWEQ312TATJU RWEQ336TATJU RWEQ360TATJU RWEQ384TATJU RWEQ408TATJU RWEQ432TATJUOutside unit 1 RWEQ120TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU RWEQ144TATJU RWEQ144TATJUOutside unit 2 RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU RWEQ144TATJUOutside unit 3 RWEQ96TATJU RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU
Model name RWEQ96TATJA RWEQ120TATJA RWEQ144TATJAOutside unit 1 RWEQ96TATJA RWEQ120TATJA RWEQ144TATJA
Model name RWEQ192TATJA RWEQ216TATJA RWEQ240TATJA RWEQ264TATJA RWEQ288TATJAOutside unit 1 RWEQ96TATJA RWEQ120TATJA RWEQ120TATJA RWEQ144TATJA RWEQ144TATJAOutside unit 2 RWEQ96TATJA RWEQ96TATJA RWEQ120TATJA RWEQ120TATJA RWEQ144TATJA
Model name RWEQ312TATJA RWEQ336TATJA RWEQ360TATJA RWEQ384TATJA RWEQ408TATJA RWEQ432TATJAOutside unit 1 RWEQ120TATJA RWEQ120TATJA RWEQ120TATJA RWEQ144TATJA RWEQ144TATJA RWEQ144TATJAOutside unit 2 RWEQ96TATJA RWEQ120TATJA RWEQ120TATJA RWEQ120TATJA RWEQ144TATJA RWEQ144TATJAOutside unit 3 RWEQ96TATJA RWEQ96TATJA RWEQ120TATJA RWEQ120TATJA RWEQ120TATJA RWEQ144TATJA
9
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Heat Pump / Heat Recovery 460 V
Model name RWEQ96TAYDU RWEQ120TAYDU RWEQ144TAYDUOutside unit 1 RWEQ96TAYDU RWEQ120TAYDU RWEQ144TAYDU
Model name RWEQ192TAYDU RWEQ216TAYDU RWEQ240TAYDU RWEQ264TAYDU RWEQ288TAYDUOutside unit 1 RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ144TAYDUOutside unit 2 RWEQ96TAYDU RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU
Model name RWEQ312TAYDU RWEQ336TAYDU RWEQ360TAYDU RWEQ384TAYDU RWEQ408TAYDU RWEQ432TAYDUOutside unit 1 RWEQ120TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ144TAYDU RWEQ144TAYDUOutside unit 2 RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ144TAYDUOutside unit 3 RWEQ96TAYDU RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU
Model name RWEQ96TAYDA RWEQ120TAYDA RWEQ144TAYDAOutside unit 1 RWEQ96TAYDA RWEQ120TAYDA RWEQ144TAYDA
Model name RWEQ192TAYDA RWEQ216TAYDA RWEQ240TAYDA RWEQ264TAYDA RWEQ288TAYDAOutside unit 1 RWEQ96TAYDA RWEQ120TAYDA RWEQ120TAYDA RWEQ144TAYDA RWEQ144TAYDAOutside unit 2 RWEQ96TAYDA RWEQ96TAYDA RWEQ120TAYDA RWEQ120TAYDA RWEQ144TAYDA
Model name RWEQ312TAYDA RWEQ336TAYDA RWEQ360TAYDA RWEQ384TAYDA RWEQ408TAYDA RWEQ432TAYDAOutside unit 1 RWEQ120TAYDA RWEQ120TAYDA RWEQ120TAYDA RWEQ144TAYDA RWEQ144TAYDA RWEQ144TAYDAOutside unit 2 RWEQ96TAYDA RWEQ120TAYDA RWEQ120TAYDA RWEQ120TAYDA RWEQ144TAYDA RWEQ144TAYDAOutside unit 3 RWEQ96TAYDA RWEQ96TAYDA RWEQ120TAYDA RWEQ120TAYDA RWEQ120TAYDA RWEQ144TAYDA
Heat Pump / Heat Recovery 575 V
Model name RWEQ96TAYCU RWEQ120TAYCU RWEQ144TAYCUOutside unit 1 RWEQ96TAYCU RWEQ120TAYCU RWEQ144TAYCU
Model name RWEQ192TAYCU RWEQ216TAYCU RWEQ240TAYCU RWEQ264TAYCU RWEQ288TAYCUOutside unit 1 RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU RWEQ144TAYCUOutside unit 2 RWEQ96TAYCU RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU
Model name RWEQ312TAYCU RWEQ336TAYCU RWEQ360TAYCU RWEQ384TAYCU RWEQ408TAYCU RWEQ432TAYCUOutside unit 1 RWEQ120TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU RWEQ144TAYCU RWEQ144TAYCUOutside unit 2 RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU RWEQ144TAYCUOutside unit 3 RWEQ96TAYCU RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU
10
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
3.2 Indoor Units
Capacity range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power supply, StandardCapacity index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96
Ceiling mounted cassette (Roundflowwithsensing)type
FXFQ — 07T 09T 12T 15T 18T — 24T 30T 36T — 48T — — — —
VJU
VISTA™ 2 × 2 cassette unit FXZQ 05TA 07TA 09TA 12TA 15TA 18TA — — — — — — — — — —4-way blow ceiling-suspended type FXUQ — — — — — — 18P 24P 30P 36P — — — — — —
One way blow cassette type FXEQ — 07P 09P 12P 15P 18P — 24P — — — — — — — —Slim ceiling mounted duct type FXDQ — 07M 09M 12M — 18M — 24M — — — — — — — —
MSP concealed ducted unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA — 24TA 30TA 36TA — 48TA 54TA — — —Ceiling mounted duct type (Middle and high static pressure)
FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — —
Ceiling mounted duct type FXMQ — — — — — — — — — — — — — — 72M 96MCeiling suspended type FXHQ — — — 12M — — — 24M — 36M — — — — — —Wall mounted type FXAQ — 07P 09P 12P — 18P — 24P — — — — — — — —Floor standing type FXLQ — 07M 09M 12M — 18M — 24M — — — — — — — —Concealedfloorstandingtype FXNQ — 07M 09M 12M — 18M — 24M — — — — — — — —
Air handling unit FXTQ— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUA— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUD
11
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
3.3 Branch Selector Unit3.3.1 Single Branch Selector Unit
Series Model name Power supply, StandardHeat recovery BSQ 36T 60T 96T VJ
Note: No interchangeability between BSVQ-PVJU and BSQ-TVJ.
VJ: 1 phase, 208 / 230 V, 60 Hz
3.3.2 Multi Branch Selector UnitFlex Series
Series Model name Power supply, standardHeat recovery BSF 4Q54T 6Q54T 8Q54T VJ
Note:No interchangeability between BSV-Q36PVJU and BSF-Q54TVJ.
VJ: 1 phase, 208/230 V, 60 Hz
Standard Series
Series Model name Power supply, standardHeat recovery BS 4Q54T 6Q54T 8Q54T 10Q54T 12Q54T VJ
Note:No interchangeability between BSV-Q36PVJU and BS-Q54TVJ.
VJ: 1 phase, 208/230 V, 60 Hz
3.4 Air Treatment EquipmentOutdoor Air Processing Unit
Series Model name Power supply, StandardFXMQ 48MF 72MF 96MF VJU
VJ: 1 phase, 208 / 230 V, 60 HzU(VJU): Standard symbol
Energy Recovery Ventilator (VAM series)
Series Model name Power supply, StandardVAM 300G 470G 600G 1200G VJU
VJ: 1 phase, 208 / 230 V, 60 HzU(VJU): Standard symbol
12
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
4. External Appearance4.1 Outside UnitsSingle Outside Units
RWEQ96TAYDU / TAYDARWEQ120TAYDU / TAYDARWEQ144TAYDU / TAYDA
8, 10, 12 ton
RWEQ96TATJU / TATJARWEQ120TATJU / TATJARWEQ144TATJU / TATJA
RWEQ96TAYCURWEQ120TAYCURWEQ144TAYCU
Double Outside Units
RWEQ192TAYDU / TAYDA RWEQ264TAYDU / TAYDARWEQ216TAYDU / TAYDA RWEQ288TAYDU / TAYDARWEQ240TAYDU / TAYDA
RWEQ192TAYCU RWEQ264TAYCURWEQ216TAYCU RWEQ288TAYCURWEQ240TAYCU
RWEQ192TATJU / TATJA RWEQ264TATJU / TATJARWEQ216TATJU / TATJA RWEQ288TATJU / TATJARWEQ240TATJU / TATJA
16, 18, 20, 22, 24 ton
Triple Outside Units
26, 28, 30, 32, 34, 36 * ton
RWEQ312TAYDU / TAYDA RWEQ384TAYDU / TAYDARWEQ336TAYDU / TAYDA RWEQ408TAYDU / TAYDARWEQ360TAYDU / TAYDA RWEQ432TAYDU / TAYDA
RWEQ312TAYCU RWEQ384TAYCURWEQ336TAYCU RWEQ408TAYCURWEQ360TAYCU RWEQ432TAYCU
RWEQ312TATJU / TATJA RWEQ384TATJU / TATJARWEQ336TATJU / TATJA RWEQ408TATJU / TATJARWEQ360TATJU / TATJA RWEQ432TATJU / TATJA
* 35.5 ton for 575 V units
13
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
4.2 Indoor Units
Ceilingmountedcassette(Roundflowwithsensing)type
FXFQ-T
Shown with BYCQ125B-W1
Ceiling mounted duct type
FXMQ-M
VISTA™ 2 × 2 cassette unit
FXZQ-TA
Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S
Ceiling suspended type
FXHQ-M
4-way blow ceiling-suspended type
FXUQ-P
Wall mounted type
FXAQ-P
One way blow cassette type
FXEQ-P
Floor standing type
FXLQ-M
Slim ceiling mounted duct type
FXDQ-M
Concealedfloorstandingtype
FXNQ-M
MSP concealed ducted unit
FXSQ-TA
Air handling unit
FXTQ-TA
Ceiling mounted duct type (Middle and high static pressure)
FXMQ-PB
14
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
4.3 Branch Selector Unit4.3.1 Single Branch Selector Unit
Single port
BSQ36TVJBSQ60TVJBSQ96TVJ
4.3.2 Multi Branch Selector UnitFlex Series
BSF4Q54TVJ BSF6Q54TVJ BSF8Q54TVJ
Standard Series
BS4Q54TVJ BS6Q54TVJBS8Q54TVJ
BS10Q54TVJBS12Q54TVJ
4.4 Air Treatment Equipment
Outdoor air processing unit
FXMQ-MF
Energy recovery ventilator (VAM series)
VAM-G
15
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
5. Outside Unit Combination
Model nameSystem capacity Number of
unitsModule Outside unit multi connection piping
kit *1Ton HP kW 96 120 144RWEQ96TATJU / TATJARWEQ96TAYDU / TAYDARWEQ96TAYCU
8 10.0 28.1 1 l
—RWEQ120TATJU / TATJARWEQ120TAYDU / TAYDARWEQ120TAYCU
10 12.5 35.2 1 l
RWEQ144TATJU / TATJA RWEQ144TAYDU / TAYDARWEQ144TAYCU
12 15.0 42.2 1 l
RWEQ192TATJU / TATJARWEQ192TAYDU / TAYDARWEQ192TAYCU
16 20.0 56.3 2 ll
Heat pump: BHFP22T84UHeat recovery: BHFP26T84U
RWEQ216TATJU / TATJARWEQ216TAYDU / TAYDARWEQ216TAYCU
18 22.5 63.3 2 l l
RWEQ240TATJU / TATJARWEQ240TAYDU / TAYDARWEQ240TAYCU
20 25.0 70.3 2 ll
RWEQ264TATJU / TATJARWEQ264TAYDU / TAYDARWEQ264TAYCU
22 27.5 77.4 2 l l
RWEQ288TATJU / TATJARWEQ288TAYDU / TAYDARWEQ288TAYCU
24 30.0 84.4 2 ll
RWEQ312TATJU / TATJARWEQ312TAYDU / TAYDARWEQ312TAYCU
26 32.5 91.4 3 ll l
Heat pump: BHFP22T126UHeat recovery: BHFP26T126U
RWEQ336TATJU / TATJARWEQ336TAYDU / TAYDARWEQ336TAYCU
28 35.0 98.5 3 l ll
RWEQ360TATJU / TATJARWEQ360TAYDU / TAYDARWEQ360TAYCU
30 37.5 105.5 3 lll
RWEQ384TATJU / TATJARWEQ384TAYDU / TAYDARWEQ384TAYCU
32 40.0 112.5 3 ll l
RWEQ408TATJU / TATJARWEQ408TAYDU / TAYDARWEQ408TAYCU
34 42.5 119.6 3 l ll
RWEQ432TATJU / TATJARWEQ432TAYDU / TAYDARWEQ432TAYCU
36 *2 45.0 126.6 3 lll
Note:*1. For multiple connection, the outside unit multi connection piping kit (separately sold) is required.*2. 35.5 ton for 575 V units
16
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
6. Interchangeability
Branch selector unit
Outside unit
T-series branch selector unit (Reference)P-series branch selector unit
Single branch selector unit
Multi branch selector unitSingle branch selector unit
Multi branch selector unitFlex series Standard
series
BSQ36TVJBSQ60TVJBSQ96TVJ
BSF4Q54TVJBSF6Q54TVJBSF8Q54TVJ
BS4Q54TVJBS6Q54TVJBS8Q54TVJBS10Q54TVJBS12Q54TVJ
BSVQ36PVJUBSVQ60PVJUBSVQ96PVJU
BSV4Q36PVJUBSV6Q36PVJU
Heat recovery Heat pump RWEQ-TA
RWEQ-TATJURWEQ-TATJA Connectable Connectable Connectable Connectable Connectable
RWEQ-TAYDURWEQ-TAYDA Connectable Connectable Connectable Connectable Connectable
RWEQ-TAYCU Connectable Connectable Connectable Connectable Connectable
Note:Combination of P-series and T-series of Branch selector units in a single system is not permitted. Combining the two series may cause malfunction.
17
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
7. Capacity Range7.1 Connection Ratio
Connection ratio =Total capacity index of the indoor units
Capacity index of the outside units
TypeMin.
connection ratio
Max. connection ratio
Types of connected indoor units Type of connected air treatment equipment
When using only FXDQ, FXMQ-PB,
FXAQ, FXSQ07-54T
When using at least one FXFQ07/09,
FXZQ05T,FXSQ05T
Other indoor unit models
FXMQ-MF
When FXMQ-MF is only connected
When FXMQ-MF and indoor units are
connectedSingle outside units
50%150% *1
150% *1 150% *1100% 100% *3*4Double outside units 130% 130%
Triple outside units 150% *1 130% *2 130% *2
Note:*1.Iftheoperationalcapacityofindoorunitsismorethan130%,lowairflowoperationisenforcedinalltheindoorunits.Thiscanbeabolished
throughfieldsettings.*2. 120% for RWEQ432TATJU/TAYDU/TAYCU, RWEQ432TATJA/TAYDA*3. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air
processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outside units. And the connection ratio must not exceed 100%.*4. It is permitted to use a maximum connection ratio of 130% in some circumstances – please contact your local Daikin representative for further
details.*5. For indoor units used for cooling only (do not connect to Branch selector unit when using for heat recovery), total capacity index of cooling only
indoor units must be 50% or less than the total capacity index of the indoor units.
18
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
7.2 Indoor Unit Connection Capacity
Type Ton Capacity index Model name Combination
Outside unit multi connection piping kit
*1
Total capacity index of connectable indoor
units *2
Maximum number of connectable indoor
units
Single outside units
8 96 RWEQ96TA RWEQ96TA—
48 to 124 (144) 1610 120 RWEQ120TA RWEQ120TA 60 to 156 (180) 2012 144 RWEQ144TA RWEQ144TA 72 to 187 (216) 24
Double outside units
16 192 RWEQ192TA RWEQ96TA+RWEQ96TA
Heat pump: BHFP22T84U
Heat recovery: BHFP26T84U
96 to 249 (288) 33
18 216 RWEQ216TA RWEQ96TA+RWEQ120TA 108 to 280 (324) 37
20 240 RWEQ240TA RWEQ120TA+RWEQ120TA 120 to 312 (360) 41
22 264 RWEQ264TA RWEQ120TA+RWEQ144TA 132 to 343 (396) 45
24 288 RWEQ288TA RWEQ144TA+RWEQ144TA 144 to 374 (432) 49
Triple outside units
26 312 RWEQ312TARWEQ96TA+RWEQ96TA+RWEQ120TA
Heat pump: BHFP22T126U
Heat recovery: BHFP26T126U
156 to 405 (468) 54
28 336 RWEQ336TARWEQ96TA+RWEQ120TA+RWEQ120TA
168 to 436 (504) 58
30 360 RWEQ360TARWEQ120TA+RWEQ120TA+RWEQ120TA
180 to 468 (540) 62
32 384 RWEQ384TARWEQ120TA+RWEQ120TA+RWEQ144TA
192 to 499 (576) 64
34 408 RWEQ408TARWEQ120TA+RWEQ144TA+RWEQ144TA
204 to 530 (612) 64
36 *4 432 RWEQ432TARWEQ144TA+RWEQ144TA+RWEQ144TA
216 to 561 (648) 64
Note:*1. For multiple connection, the outside unit multi connection piping kit (separately sold) is required.*2. Values inside brackets are based on connection of indoor units rated at maximum capacity, 150% for single outside units, 150% for double
outside units, and 150% for triple outside units.*3. For indoor units used for cooling only (do not connect to Branch selector unit when using for heat recovery), total capacity index of cooling only
indoor units must be 50% or less than the total capacity index of the indoor units.*4. 35.5 ton for 575 V units
19
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
7.3 Limitation of Capacity Index for Heat Recovery7.3.1 Single Branch Selector Unit
Model BSQ36TVJ BSQ60TVJ BSQ96TVJMaximum number of connectable indoor units 4 8 8Total capacity index of connectable indoor units unit ≤ 36 36 < unit ≤ 60 60 < unit ≤ 96
7.3.2 Multi Branch Selector UnitFlex series
Model BSF4Q54TVJ BSF6Q54TVJ BSF8Q54TVJMaximum number of connectable indoor units per branch 5 5 5
Number of branches 4 6 8Maximum capacity index of connectable indoor units per branch (H1) 54 or less 54 or less 54 or less
Series configuration
Maximum capacity index of connectable indoor units per branch selector unit
144 or less 162 or less 162 or less
Maximum capacity index of total connectable indoor units under branch selector units connected in series (H2)
230 or less 230 or less 230 or less
Parallel configuration
Maximum capacity index of connectable indoor units 144 or less 216 or less 290 or less
Standard series
Model BS4Q54TVJ BS6Q54TVJ BS8Q54TVJ BS10Q54TVJ BS12Q54TVJMaximum number of connectable indoor units per branch 5 5 5 5 5
Number of branches 4 6 8 10 12Maximum capacity index of connectable indoor units 144 or less 216 or less 290 or less 290 or less 290 or less
Maximum capacity index of connectable indoor units per branch (H1) 54 or less 54 or less 54 or less 54 or less 54 or less
Note:H1. When the total capacity of indoor units to be connected downstream is larger than 54 (Max. 96), use a junction pipe kit (KHRP26A250T,
optional parts) to join two connections downstream from the Branch selector unit.H2. The total number of ports of Branch Selector units connected in series must be no more than 12 ports.
The total number of indoor units connected to Branch Selector units in series must be no more than 30 units. Thistotalincludestheports/indoorunitsofthefirstBranchSelectorintheseries.
High and low pressuregas pipingSuction gas pipingLiquid piping
Indoor unit(Heating)
Indoor unit(Cooling)
Indoor unit*(Cooling only)
Heat Recovery operation!
* For indoor units used for cooling only (do not connect to Branch selector unit when using for heat recovery), total capacity index of cooling only indoor units must be 50% or less than the total capacity index of the indoor units.
Branch Selector unit
Branch Selector unit
Heat Recovery
Outside unit
20
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
8. Specifications8.1 RWEQ-TATJU / TATJARWEQ96TATJU / TATJA
Model RWEQ96TATJU RWEQ96TATJAPower supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)96,000 (28.1)
Rated 92,000 (27.0)
H2 Heating capacityNominal Btu/h
(kW)108,000 (31.7)
Rated 103,000 (30.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 544 (15.4)
Number of revolutions r/min 4,542
Motor output × Number of units kW 4.7 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/8 (9.5) C1220T (Brazing connection)Suction gas pipe in. (mm) f7/8 (22.2) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f7/8 (22.2) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 432.1 (196) 434.3 (197)H6 Sound pressure level (Reference data) dB(A) 54
H6 Sound power level (Reference data) dB 71
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 15-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 (7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109377G C: 4D127020Sound level C: 4D109785A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.:86°F (30°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
21
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ120TATJU / TATJA
Model RWEQ120TATJU RWEQ120TATJAPower supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)120,000 (35.2)
Rated 114,000 (33.4)
H2 Heating capacityNominal Btu/h
(kW)135,000 (39.6)
Rated 129,000 (37.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 (19.0)
Number of revolutions r/min 5,592
Motor output × Number of units kW 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 (198) 438.7 (199)H6 Sound pressure level (Reference data) dB(A) 55
H6 Sound power level (Reference data) dB 72
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 12-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109378G C: 4D127021Sound level C: 4D109786A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
22
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ144TATJU / TATJA
Model RWEQ144TATJU RWEQ144TATJAPower supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)144,000 (42.2)
Rated 138,000 (40.4)
H2 Heating capacityNominal Btu/h
(kW)162,000 (47.5)
Rated 154,000 (45.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 848 (24.0)
Number of revolutions r/min 7,080
Motor output × Number of units kW 7.4 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f7/8 (22.2) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 (198) 438.7 (199)H6 Sound pressure level (Reference data) dB(A) 60.5
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 11-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109379F C: 4D127022Sound level C: 4D109787A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW)4. There are some cases where capacity decreases depending on operating states.
23
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ192TATJU / TATJA
Model (Combination Unit) RWEQ192TATJU RWEQ192TATJA
Model (Independent Unit) RWEQ96TATJURWEQ96TATJU
RWEQ96TATJARWEQ96TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)192,000 (56.3)
Rated 184,000 (53.9)
H2 Heating capacityNominal Btu/h
(kW)216,000 (63.3)
Rated 206,000 (60.4)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 551 + 551 (15.6 + 15.6)
Number of revolutions r/min 4,602 + 4,602
Motor output × Number of units kW 4.8 × 1 + 4.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 432.1 + 432.1 (196 + 196) 434.3 + 434.3 (197 + 197)H6 Sound pressure level (Reference data) dB(A) 57
H6 Sound power level (Reference data) dB 74
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 8-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 + 17.4 (7.9 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109380G C: 4D127023Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.
24
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ216TATJU / TATJA
Model (Combination Unit) RWEQ216TATJU RWEQ216TATJA
Model (Independent Unit) RWEQ120TATJURWEQ96TATJU
RWEQ120TATJARWEQ96TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)216,000 (63.3)
Rated 206,000 (60.4)
H2 Heating capacityNominal Btu/h
(kW)243,000 (71.2)
Rated 232,000 (68.0)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 + 669 (19.0 + 19.0)
Number of revolutions r/min 5,592 + 5,592
Motor output × Number of units kW 5.8 × 1 + 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 432.1 (198 + 196) 438.7 + 434.3 (199 + 197)H6 Sound pressure level (Reference data) dB(A) 57.5
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 7-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 (9.6 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109381H C: 4D127024Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
25
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ240TATJU / TATJA
Model (Combination Unit) RWEQ240TATJU RWEQ240TATJA
Model (Independent Unit) RWEQ120TATJURWEQ120TATJU
RWEQ120TATJARWEQ120TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)240,000 (70.3)
Rated 228,000 (66.8)
H2 Heating capacityNominal Btu/h
(kW)270,000 (79.1)
Rated 258,000 (75.6)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 708 + 708 (20.0 + 20.0)
Number of revolutions r/min 5,910 + 5,910
Motor output × Number of units kW 6.2 × 1 + 6.2 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 (198 + 198) 438.7 + 438.7 (199 + 199)H6 Sound pressure level (Reference data) dB(A) 58
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 6-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109382H C: 4D127025Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.
26
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ264TATJU / TATJA
Model (Combination Unit) RWEQ264TATJU RWEQ264TATJA
Model (Independent Unit) RWEQ144TATJURWEQ120TATJU
RWEQ144TATJARWEQ120TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)264,000 (77.4)
Rated 252,000 (73.9)
H2 Heating capacityNominal Btu/h
(kW)297,000 (87.0)
Rated 284,000 (83.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 860 + 860 (24.3 + 24.3)
Number of revolutions r/min 7,182 + 7,182
Motor output × Number of units kW 7.5 × 1 + 7.5 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 (198 + 198) 438.7 + 438.7 (199 + 199)H6 Sound pressure level (Reference data) dB(A) 61.5
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 6-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109383G C: 4D127026Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
27
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ288TATJU / TATJA
Model (Combination Unit) RWEQ288TATJU RWEQ288TATJA
Model (Independent Unit) RWEQ144TATJURWEQ144TATJU
RWEQ144TATJARWEQ144TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)288,000 (84.4)
Rated 274,000 (80.3)
H2 Heating capacityNominal Btu/h
(kW)324,000 (95.0)
Rated 308,000 (90.3)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 961 + 961 (27.2 + 27.2)
Number of revolutions r/min 8,028 + 8,028
Motor output × Number of units kW 8.4 × 1 + 8.4 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 (198 + 198) 438.7 + 438.7 (199 + 199)H6 Sound pressure level (Reference data) dB(A) 63.5
H6 Sound power level (Reference data) dB 78
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 5-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109384G C: 4D127027Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 24. There are some cases where capacity decreases depending on operating states.
28
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ312TATJU / TATJA
Model (Combination Unit) RWEQ312TATJU RWEQ312TATJA
Model (Independent Unit)RWEQ120TATJURWEQ96TATJURWEQ96TATJU
RWEQ120TATJARWEQ96TATJARWEQ96TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)312,000 (91.4)
Rated 298,000 (87.3)
H2 Heating capacityNominal Btu/h
(kW)351,000 (102.9)
Rated 334,000 (97.9)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 + 669 + 669 (19.0 + 19.0 + 19.0)
Number of revolutions r/min 5,592 + 5,592 + 5,592
Motor output × Number of units kW 5.8 × 1 + 5.8 × 1 + 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 432.1 + 432.1 (198 + 196 + 196) 438.7 + 434.3 + 434.3 (199 + 197 + 197)H6 Sound pressure level (Reference data) dB(A) 59
H6 Sound power level (Reference data) dB 76
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 5-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 + 17.4 (9.6 + 7.9 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109385G C: 4D127028Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.
29
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ336TATJU / TATJA
Model (Combination Unit) RWEQ336TATJU RWEQ336TATJA
Model (Independent Unit)RWEQ120TATJURWEQ120TATJURWEQ96TATJU
RWEQ120TATJARWEQ120TATJARWEQ96TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)336,000 (98.5)
Rated 320,000 (93.8)
H2 Heating capacityNominal Btu/h
(kW)378,000 (110.8)
Rated 360,000 (105.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 688 + 688 + 688 (19.5 + 19.5 + 19.5)
Number of revolutions r/min 5,748 + 5,748 + 5,748
Motor output × Number of units kW 6.0 × 1 + 6.0 × 1 + 6.0 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 + 432.1 (198 + 198 + 196) 438.7 + 438.7 + 434.3 (199 + 199 + 197)H6 Sound pressure level (Reference data) dB(A) 59.5
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 17.4 (9.6 + 9.6 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109386H C: 4D127029Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 2 + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
30
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ360TATJU / TATJA
Model (Combination Unit) RWEQ360TATJU RWEQ360TATJA
Model (Independent Unit)RWEQ120TATJURWEQ120TATJURWEQ120TATJU
RWEQ120TATJARWEQ120TATJARWEQ120TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)360,000 (105.5)
Rated 342,000 (100.2)
H2 Heating capacityNominal Btu/h
(kW)405,000 (118.7)
Rated 386,000 (113.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 825 + 825 + 825 (23.4 + 23.4 + 23.4)
Number of revolutions r/min 6,888 + 6,888 + 6,888
Motor output × Number of units kW 7.2 × 1 + 7.2 × 1 + 7.2 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198) 438.7 + 438.7 + 438.7 (199 + 199 + 199)H6 Sound pressure level (Reference data) dB(A) 60
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109387H C: 4D127030Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 34. There are some cases where capacity decreases depending on operating states.
31
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ384TATJU / TATJA
Model (Combination Unit) RWEQ384TATJU RWEQ384TATJA
Model (Independent Unit)RWEQ144TATJURWEQ120TATJURWEQ120TATJU
RWEQ144TATJARWEQ120TATJARWEQ120TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)384,000 (112.5)
Rated 366,000 (107.3)
H2 Heating capacityNominal Btu/h
(kW)432,000 (126.6)
Rated 410,000 (120.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 860 + 860 + 860 (24.3 + 24.3 + 24.3)
Number of revolutions r/min 7,182 + 7,182 + 7,182
Motor output × Number of units kW 7.5 × 1 + 7.5 × 1 + 7.5 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198) 438.7 + 438.7 + 438.7 (199 + 199 + 199)H6 Sound pressure level (Reference data) dB(A) 62
H6 Sound power level (Reference data) dB 78
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D111941F C: 4D127042Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.
32
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ408TATJU / TATJA
Model (Combination Unit) RWEQ408TATJU RWEQ408TATJA
Model (Independent Unit)RWEQ144TATJURWEQ144TATJURWEQ120TATJU
RWEQ144TATJARWEQ144TATJARWEQ120TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)408,000 (119.6)
Rated 388,000 (113.7)
H2 Heating capacityNominal Btu/h
(kW)459,000 (134.5)
Rated 435,000 (127.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 1,006 + 1,006 + 884 (28.5 + 28.5 + 25.0)
Number of revolutions r/min 8,400 + 8,400 + 7,386
Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 7.7 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198) 438.7 + 438.7 + 438.7 (199 + 199 + 199)H6 Sound pressure level (Reference data) dB(A) 64
H6 Sound power level (Reference data) dB 79
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D111942F C: 4D127043Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 2 + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
33
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ432TATJU / TATJA
Model (Combination Unit) RWEQ432TATJU RWEQ432TATJA
Model (Independent Unit)RWEQ144TATJURWEQ144TATJURWEQ144TATJU
RWEQ144TATJARWEQ144TATJARWEQ144TATJA
Power supply 3 phase, 208/230 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)432,000 (126.6)
Rated 410,000 (120.2)
H2 Heating capacityNominal Btu/h
(kW)486,000 (142.4)
Rated 460,000 (134.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 1,006 + 1,006 + 1,006 (28.5 + 28.5 + 28.5)
Number of revolutions r/min 8,400 + 8,400 + 8,400
Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 8.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198) 438.7 + 438.7 + 438.7 (199 + 199 + 199)H6 Sound pressure level (Reference data) dB(A) 65
H6 Sound power level (Reference data) dB 80
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TATJA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D111943E C: 4D127044Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 34. There are some cases where capacity decreases depending on operating states.
34
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
8.2 RWEQ-TAYDU / TAYDARWEQ96TAYDU / TAYDA
Model RWEQ96TAYDU RWEQ96TAYDAPower supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)96,000 (28.1)
Rated 92,000 (27.0)
H2 Heating capacityNominal Btu/h
(kW)108,000 (31.7)
Rated 103,000 (30.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 544 (15.4)
Number of revolutions r/min 4,542
Motor output × Number of units kW 4.7 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/8 (9.5) C1220T (Brazing connection)Suction gas pipe in. (mm) f7/8 (22.2) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f7/8 (22.2) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 438.7 (199) 440.9 (200)H6 Sound pressure level (Reference data) dB(A) 54
H6 Sound power level (Reference data) dB 71
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 15-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 (7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109388G C: 4D127031Sound level C: 4D109785A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
35
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ120TAYDU / TAYDA
Model RWEQ120TAYDU RWEQ120TAYDAPower supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)120,000 (35.2)
Rated 114,000 (33.4)
H2 Heating capacityNominal Btu/h
(kW)135,000 (39.6)
Rated 129,000 (37.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 (19.0)
Number of revolutions r/min 5,592
Motor output × Number of units kW 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 (201) 445.3 (202)H6 Sound pressure level (Reference data) dB(A) 55
H6 Sound power level (Reference data) dB 72
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 12-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109389G C: 4D127032Sound level C: 4D109786A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
36
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ144TAYDU / TAYDA
Model RWEQ144TAYDU RWEQ144TAYDAPower supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)144,000 (42.2)
Rated 138,000 (40.4)
H2 Heating capacityNominal Btu/h
(kW)162,000 (47.5)
Rated 154,000 (45.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 848 (24.0)
Number of revolutions r/min 7,080
Motor output × Number of units kW 7.4 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f7/8 (22.2) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 (201) 445.3 (202)H6 Sound pressure level (Reference data) dB(A) 60.5
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 11-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109390F C: 4D127033Sound level C: 4D109787A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW)4. There are some cases where capacity decreases depending on operating states.
37
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ192TAYDU / TAYDA
Model (Combination Unit) RWEQ192TAYDU RWEQ192TAYDA
Model (Independent Unit) RWEQ96TAYDURWEQ96TAYDU
RWEQ96TAYDARWEQ96TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)192,000 (56.3)
Rated 184,000 (53.9)
H2 Heating capacityNominal Btu/h
(kW)216,000 (63.3)
Rated 206,000 (60.4)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 551 + 551 (15.6 + 15.6)
Number of revolutions r/min 4,602 + 4,602
Motor output × Number of units kW 4.8 × 1 + 4.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 438.7 + 438.7 (199 + 199) 440.9 + 440.9 (200 + 200)H6 Sound pressure level (Reference data) dB(A) 57
H6 Sound power level (Reference data) dB 74
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 8-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 + 17.4 (7.9 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109391G C: 4D127034Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.
38
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ216TAYDU / TAYDA
Model (Combination Unit) RWEQ216TAYDU RWEQ216TAYDA
Model (Independent Unit) RWEQ120TAYDURWEQ96TAYDU
RWEQ120TAYDARWEQ96TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)216,000 (63.3)
Rated 206,000 (60.4)
H2 Heating capacityNominal Btu/h
(kW)243,000 (71.2)
Rated 232,000 (68.0)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 + 669 (19.0 + 19.0)
Number of revolutions r/min 5,592 + 5,592
Motor output × Number of units kW 5.8 × 1 + 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 438.7 (201 + 199) 445.3 + 440.9 (202 + 200)H6 Sound pressure level (Reference data) dB(A) 57.5
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 7-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 (9.6 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109392H C: 4D127035Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
39
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ240TAYDU / TAYDA
Model (Combination Unit) RWEQ240TAYDU RWEQ240TAYDA
Model (Independent Unit) RWEQ120TAYDURWEQ120TAYDU
RWEQ120TAYDARWEQ120TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)240,000 (70.3)
Rated 228,000 (66.8)
H2 Heating capacityNominal Btu/h
(kW)270,000 (79.1)
Rated 258,000 (75.6)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 708 + 708 (20.0 + 20.0)
Number of revolutions r/min 5,910 + 5,910
Motor output × Number of units kW 6.2 × 1 + 6.2 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 (201 + 201) 445.3 + 445.3 (202 + 202)H6 Sound pressure level (Reference data) dB(A) 58
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 6-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109393H C: 4D127036Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.
40
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ264TAYDU / TAYDA
Model (Combination Unit) RWEQ264TAYDU RWEQ264TAYDA
Model (Independent Unit) RWEQ144TAYDURWEQ120TAYDU
RWEQ144TAYDARWEQ120TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)264,000 (77.4)
Rated 252,000 (73.9)
H2 Heating capacityNominal Btu/h
(kW)297,000 (87.0)
Rated 284,000 (83.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 860 + 860 (24.3 + 24.3)
Number of revolutions r/min 7,182 + 7,182
Motor output × Number of units kW 7.5 × 1 + 7.5 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 (201 + 201) 445.3 + 445.3 (202 + 202)H6 Sound pressure level (Reference data) dB(A) 61.5
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 6-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109394G C: 4D127037Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
41
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ288TAYDU / TAYDA
Model (Combination Unit) RWEQ288TAYDU RWEQ288TAYDA
Model (Independent Unit) RWEQ144TAYDURWEQ144TAYDU
RWEQ144TAYDARWEQ144TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)288,000 (84.4)
Rated 274,000 (80.3)
H2 Heating capacityNominal Btu/h
(kW)324,000 (95.0)
Rated 308,000 (90.3)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 961 + 961 (27.2 + 27.2)
Number of revolutions r/min 8,028 + 8,028
Motor output × Number of units kW 8.4 × 1 + 8.4 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 (201 + 201) 445.3 + 445.3 (202 + 202)H6 Sound pressure level (Reference data) dB(A) 63.5
H6 Sound power level (Reference data) dB 78
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 5-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109395G C: 4D127038Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 24. There are some cases where capacity decreases depending on operating states.
42
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ312TAYDU / TAYDA
Model (Combination Unit) RWEQ312TAYDU RWEQ312TAYDA
Model (Independent Unit)RWEQ120TAYDURWEQ96TAYDURWEQ96TAYDU
RWEQ120TAYDARWEQ96TAYDARWEQ96TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)312,000 (91.4)
Rated 298,000 (87.3)
H2 Heating capacityNominal Btu/h
(kW)351,000 (102.9)
Rated 334,000 (97.9)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 + 669 + 669 (19.0 + 19.0 + 19.0)
Number of revolutions r/min 5,592 + 5,592 + 5,592
Motor output × Number of units kW 5.8 × 1 + 5.8 × 1 + 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 438.7 + 438.7 (201 + 199 + 199) 445.3 + 440.9 + 440.9 (202 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 59
H6 Sound power level (Reference data) dB 76
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 5-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 + 17.4 (9.6 + 7.9 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109396G C: 4D127039Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.
43
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ336TAYDU / TAYDA
Model (Combination Unit) RWEQ336TAYDU RWEQ336TAYDA
Model (Independent Unit)RWEQ120TAYDURWEQ120TAYDURWEQ96TAYDU
RWEQ120TAYDARWEQ120TAYDARWEQ96TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)336,000 (98.5)
Rated 320,000 (93.8)
H2 Heating capacityNominal Btu/h
(kW)378,000 (110.8)
Rated 360,000 (105.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 688 + 688 + 688 (19.5 + 19.5 + 19.5)
Number of revolutions r/min 5,748 + 5,748 + 5,748
Motor output × Number of units kW 6.0 × 1 + 6.0 × 1 + 6.0 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 + 438.7 (201 + 201 + 199) 445.3 + 445.3 + 440.9 (202 + 202 + 200)H6 Sound pressure level (Reference data) dB(A) 59.5
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 17.4 (9.6 + 9.6 + 7.9)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109397H C: 4D127040Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 2 + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
44
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ360TAYDU / TAYDA
Model (Combination Unit) RWEQ360TAYDU RWEQ360TAYDA
Model (Independent Unit)RWEQ120TAYDURWEQ120TAYDURWEQ120TAYDU
RWEQ120TAYDARWEQ120TAYDARWEQ120TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)360,000 (105.5)
Rated 342,000 (100.2)
H2 Heating capacityNominal Btu/h
(kW)405,000 (118.7)
Rated 386,000 (113.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 825 + 825 + 825 (23.4 + 23.4 + 23.4)
Number of revolutions r/min 6,888 + 6,888 + 6,888
Motor output × Number of units kW 7.2 × 1 + 7.2 × 1 + 7.2 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201) 445.3 + 445.3 + 445.3 (202 + 202 + 202)H6 Sound pressure level (Reference data) dB(A) 60
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D109398H C: 4D127041Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 34. There are some cases where capacity decreases depending on operating states.
45
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ384TAYDU / TAYDA
Model (Combination Unit) RWEQ384TAYDU RWEQ384TAYDA
Model (Independent Unit)RWEQ144TAYDURWEQ120TAYDURWEQ120TAYDU
RWEQ144TAYDARWEQ120TAYDARWEQ120TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)384,000 (112.5)
Rated 366,000 (107.3)
H2 Heating capacityNominal Btu/h
(kW)432,000 (126.6)
Rated 410,000 (120.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 860 + 860 + 860 (24.3 + 24.3 + 24.3)
Number of revolutions r/min 7,182 + 7,182 + 7,182
Motor output × Number of units kW 7.5 × 1 + 7.5 × 1 + 7.5 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201) 445.3 + 445.3 + 445.3 (202 + 202 + 202)H6 Sound pressure level (Reference data) dB(A) 62
H6 Sound power level (Reference data) dB 78
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D111944F C: 4D127050Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.
46
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ408TAYDU / TAYDA
Model (Combination Unit) RWEQ408TAYDU RWEQ408TAYDA
Model (Independent Unit)RWEQ144TAYDURWEQ144TAYDURWEQ120TAYDU
RWEQ144TAYDARWEQ144TAYDARWEQ120TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)408,000 (119.6)
Rated 388,000 (113.7)
H2 Heating capacityNominal Btu/h
(kW)459,000 (134.5)
Rated 435,000 (127.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 1,006 + 1,006 + 884 (28.5 + 28.5 + 25.0)
Number of revolutions r/min 8,400 + 8,400 + 7,386
Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 7.7 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201) 445.3 + 445.3 + 445.3 (202 + 202 + 202)H6 Sound pressure level (Reference data) dB(A) 64
H6 Sound power level (Reference data) dB 79
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D111945F C: 4D127045Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 2 + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
47
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ432TAYDU / TAYDA
Model (Combination Unit) RWEQ432TAYDU RWEQ432TAYDA
Model (Independent Unit)RWEQ144TAYDURWEQ144TAYDURWEQ144TAYDU
RWEQ144TAYDARWEQ144TAYDARWEQ144TAYDA
Power supply 3 phase, 460 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)432,000 (126.6)
Rated 410,000 (120.2)
H2 Heating capacityNominal Btu/h
(kW)486,000 (142.4)
Rated 460,000 (134.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 1,006 + 1,006 + 1,006 (28.5 + 28.5 + 28.5)
Number of revolutions r/min 8,400 + 8,400 + 8,400
Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 8.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201) 445.3 + 445.3 + 445.3 (202 + 202 + 202)H6 Sound pressure level (Reference data) dB(A) 65
H6 Sound power level (Reference data) dB 80
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose
RWEQ-TAYDA only Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (water line) (ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D111946E C: 4D127046Sound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 34. There are some cases where capacity decreases depending on operating states.
48
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
8.3 RWEQ-TAYCURWEQ96TAYCU
Model RWEQ96TAYCUPower supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)96,000 (28.1)
Rated 92,000 (27.0)
H2 Heating capacityNominal Btu/h
(kW)108,000 (31.7)
Rated 103,000 (30.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 544 (15.4)
Number of revolutions r/min 4,542
Motor output × Number of units kW 4.7 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/8 (9.5) C1220T (Brazing connection)Suction gas pipe in. (mm) f7/8 (22.2) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f7/8 (22.2) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 436.5 (198)H6 Sound pressure level (Reference data) dB(A) 54
H6 Sound power level (Reference data) dB 71
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 15-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 (7.9)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117549BSound level C: 4D109785A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,50ft.(15.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
49
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ120TAYCU
Model RWEQ120TAYCUPower supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)120,000 (35.2)
Rated 114,000 (33.4)
H2 Heating capacityNominal Btu/h
(kW)135,000 (39.6)
Rated 129,000 (37.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 (19.0)
Number of revolutions r/min 5,592
Motor output × Number of units kW 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 (200)H6 Sound pressure level (Reference data) dB(A) 55
H6 Sound power level (Reference data) dB 72
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 12-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117550BSound level C: 4D109786A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:25ft.(7.6m)forductedindoorunits,75ft.(23m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
50
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ144TAYCU
Model RWEQ144TAYCUPower supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)144,000 (42.2)
Rated 138,000 (40.4)
H2 Heating capacityNominal Btu/h
(kW)162,000 (47.5)
Rated 154,000 (45.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 848 (24.0)
Number of revolutions r/min 7,080
Motor output × Number of units kW 7.4 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f7/8 (22.2) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 (200)H6 Sound pressure level (Reference data) dB(A) 60.5
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 11-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117551BSound level C: 4D109787A
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW)4. There are some cases where capacity decreases depending on operating states.
51
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ192TAYCU
Model (Combination Unit) RWEQ192TAYCU
Model (Independent Unit) RWEQ96TAYCURWEQ96TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)192,000 (56.3)
Rated 184,000 (53.9)
H2 Heating capacityNominal Btu/h
(kW)216,000 (63.3)
Rated 206,000 (60.4)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 551 + 551 (15.6 + 15.6)
Number of revolutions r/min 4,602 + 4,602
Motor output × Number of units kW 4.8 × 1 + 4.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 436.5 + 436.5 (198 + 198)H6 Sound pressure level (Reference data) dB(A) 57
H6 Sound power level (Reference data) dB 74
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 8-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 + 17.4 (7.9 + 7.9)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117552BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.
52
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ216TAYCU
Model (Combination Unit) RWEQ216TAYCU
Model (Independent Unit) RWEQ120TAYCURWEQ96TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)216,000 (63.3)
Rated 206,000 (60.4)
H2 Heating capacityNominal Btu/h
(kW)243,000 (71.2)
Rated 232,000 (68.0)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 + 669 (19.0 + 19.0)
Number of revolutions r/min 5,592 + 5,592
Motor output × Number of units kW 5.8 × 1 + 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 436.5 (200 + 198)H6 Sound pressure level (Reference data) dB(A) 57.5
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 7-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 (9.6 + 7.9)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117553BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
53
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ240TAYCU
Model (Combination Unit) RWEQ240TAYCU
Model (Independent Unit) RWEQ120TAYCURWEQ120TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)240,000 (70.3)
Rated 228,000 (66.8)
H2 Heating capacityNominal Btu/h
(kW)270,000 (79.1)
Rated 258,000 (75.6)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 708 + 708 (20.0 + 20.0)
Number of revolutions r/min 5,910 + 5,910
Motor output × Number of units kW 6.2 × 1 + 6.2 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 (200 + 200)H6 Sound pressure level (Reference data) dB(A) 58
H6 Sound power level (Reference data) dB 75
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 6-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117554BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.
54
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ264TAYCU
Model (Combination Unit) RWEQ264TAYCU
Model (Independent Unit) RWEQ144TAYCURWEQ120TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)264,000 (77.4)
Rated 252,000 (73.9)
H2 Heating capacityNominal Btu/h
(kW)297,000 (87.0)
Rated 284,000 (83.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 860 + 860 (24.3 + 24.3)
Number of revolutions r/min 7,182 + 7,182
Motor output × Number of units kW 7.5 × 1 + 7.5 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 (200 + 200)H6 Sound pressure level (Reference data) dB(A) 61.5
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 6-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117555BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
55
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ288TAYCU
Model (Combination Unit) RWEQ288TAYCU
Model (Independent Unit) RWEQ144TAYCURWEQ144TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)288,000 (84.4)
Rated 274,000 (80.3)
H2 Heating capacityNominal Btu/h
(kW)324,000 (95.0)
Rated 308,000 (90.3)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 961 + 961 (27.2 + 27.2)
Number of revolutions r/min 8,028 + 8,028
Motor output × Number of units kW 8.4 × 1 + 8.4 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 (200 + 200)H6 Sound pressure level (Reference data) dB(A) 63.5
H6 Sound power level (Reference data) dB 78
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 5-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117556BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 24. There are some cases where capacity decreases depending on operating states.
56
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ312TAYCU
Model (Combination Unit) RWEQ312TAYCU
Model (Independent Unit)RWEQ120TAYCURWEQ96TAYCURWEQ96TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)312,000 (91.4)
Rated 298,000 (87.3)
H2 Heating capacityNominal Btu/h
(kW)351,000 (102.9)
Rated 334,000 (97.9)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 669 + 669 + 669 (19.0 + 19.0 + 19.0)
Number of revolutions r/min 5,592 + 5,592 + 5,592
Motor output × Number of units kW 5.8 × 1 + 5.8 × 1 + 5.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 436.5 + 436.5 (200 + 198 + 198)H6 Sound pressure level (Reference data) dB(A) 59
H6 Sound power level (Reference data) dB 76
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 5-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 + 17.4 (9.6 + 7.9 + 7.9)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117557BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.
57
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ336TAYCU
Model (Combination Unit) RWEQ336TAYCU
Model (Independent Unit)RWEQ120TAYCURWEQ120TAYCURWEQ96TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)336,000 (98.5)
Rated 320,000 (93.8)
H2 Heating capacityNominal Btu/h
(kW)378,000 (110.8)
Rated 360,000 (105.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 688 + 688 + 688 (19.5 + 19.5 + 19.5)
Number of revolutions r/min 5,748 + 5,748 + 5,748
Motor output × Number of units kW 6.0 × 1 + 6.0 × 1 + 6.0 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 + 436.5 (200 + 200 + 198)H6 Sound pressure level (Reference data) dB(A) 59.5
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 17.4 (9.6 + 9.6 + 7.9)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117558BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 2 + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.
58
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ360TAYCU
Model (Combination Unit) RWEQ360TAYCU
Model (Independent Unit)RWEQ120TAYCURWEQ120TAYCURWEQ120TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)360,000 (105.5)
Rated 342,000 (100.2)
H2 Heating capacityNominal Btu/h
(kW)405,000 (118.7)
Rated 386,000 (113.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 825 + 825 + 825 (23.4 + 23.4 + 23.4)
Number of revolutions r/min 6,888 + 6,888 + 6,888
Motor output × Number of units kW 7.2 × 1 + 7.2 × 1 + 7.2 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 60
H6 Sound power level (Reference data) dB 77
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117559BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:50ft.(15.5m)forductedindoorunits,100ft.(30.5m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 34. There are some cases where capacity decreases depending on operating states.
59
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ384TAYCU
Model (Combination Unit) RWEQ384TAYCU
Model (Independent Unit)RWEQ144TAYCURWEQ120TAYCURWEQ120TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)384,000 (112.5)
Rated 366,000 (107.3)
H2 Heating capacityNominal Btu/h
(kW)432,000 (126.6)
Rated 410,000 (120.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 860 + 860 + 860 (24.3 + 24.3 + 24.3)
Number of revolutions r/min 7,182 + 7,182 + 7,182
Motor output × Number of units kW 7.5 × 1 + 7.5 × 1 + 7.5 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 62
H6 Sound power level (Reference data) dB 78
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117560BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.
60
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ408TAYCU
Model (Combination Unit) RWEQ408TAYCU
Model (Independent Unit)RWEQ144TAYCURWEQ144TAYCURWEQ120TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)408,000 (119.6)
Rated 388,000 (113.7)
H2 Heating capacityNominal Btu/h
(kW)459,000 (134.5)
Rated 435,000 (127.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 1,006 + 1,006 + 884 (28.5 + 28.5 + 25.0)
Number of revolutions r/min 8,400 + 8,400 + 7,386
Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 7.7 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 64
H6 Sound power level (Reference data) dB 79
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117561BSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.
Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 2 + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.
61
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ432TAYCU
Model (Combination Unit) RWEQ432TAYCU
Model (Independent Unit)RWEQ144TAYCURWEQ144TAYCURWEQ144TAYCU
Power supply 3 phase, 575 V, 60 Hz
H1 Cooling capacityNominal Btu/h
(kW)426,000 (124.8)
Rated 410,000 (120.2)
H2 Heating capacityNominal Btu/h
(kW)486,000 (142.4)
Rated 460,000 (134.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type
Compressor
Type Hermetically sealed scroll type
Displacement ft.³/h (m³/h) 1,006 + 1,006 + 1,006 (28.5 + 28.5 + 28.5)
Number of revolutions r/min 8,400 + 8,400 + 8,400
Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 8.8 × 1
Starting method Soft start
Connecting pipes
Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-
Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)
Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 65
H6 Sound power level (Reference data) dB 80
Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse
Capacity control % 4-100
RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve
Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain
hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor (waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)
Drawing No.Specification C: 4D117562CSound level —
Note:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)
Equivalentpipinglength:75ft.(23m)forductedindoorunits,150ft.(45.7m)fornon-ductedindoorunits,leveldifference:0ft.(0m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.
During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 34. There are some cases where capacity decreases depending on operating states.
62
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
9. Dimensions
RWEQ96 - 144TATJU / TAYDU / TAYCU · RWEQ96 - 144TATJA / TAYDA
3D10
9305
B
63
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ192 - 288TATJU / TAYDU / TAYCU · RWEQ192 - 288TATJA / TAYDA
3D11
2152
B
64
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ312 - 432TATJU / TAYDU / TAYCU · RWEQ312 - 432TATJA / TAYDA
3D11
2153
B
65
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
10. Service Space
RWEQ96 - 432TATJU / TAYDU / TAYCU · RWEQ96 - 432TATJA / TAYDA
3D
1093
04B
66
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
11. Center of Gravity
RWEQ96 - 144TATJU · RWEQ96 - 144TATJA
RWEQ96 - 144TAYDU / TAYCU · RWEQ96 - 144TAYDA4D109344A
Unit. in. (mm)
4D109345A
Unit. in. (mm)
67
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
12. Piping Diagrams
RWEQ96 - 144TATJU / TAYDU / TAYCU · RWEQ96 - 144TATJA / TAYDA
4D109343B
68
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
13. Wiring Diagrams
RWEQ96 - 144TATJU · RWEQ96 - 144TATJA
4D10
8929
D
69
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ96 - 144TATJU · RWEQ96 - 144TATJA (continued)
4D10
8929
D
70
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ96 - 144TAYDU · RWEQ96 - 144TAYDA
4D10
8930
D
71
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ96 - 144TAYDU · RWEQ96 - 144TAYDA (continued)
4D10
8930
D
72
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ96 - 144TAYCU
4D11
7733
A
73
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ96 - 144TAYCU (continued)
4D11
7733
A
74
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
14. Field Wiring14.1 Heat PumpRWEQ96 - 144TATJU / TAYDU / TAYCU · RWEQ96 - 144TATJA / TAYDA
C: 3
D12
0276
[Ope
ratio
n sy
stem
: Hea
t pum
p]
Not
es:
1) A
ll w
iring
, com
pone
nts
and
mat
eria
ls to
be
proc
ured
on
the
site
mus
t com
ply
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.2)
Use
cop
per c
ondu
ctor
s on
ly.
3) A
s fo
r det
ails
, see
wiri
ng d
iagr
am.
4) F
ield
wiri
ng d
iagr
am is
to b
e us
ed a
s a
guid
elin
e on
ly.
W
iring
sho
uld
com
ply
with
app
licab
le lo
cal a
nd n
atio
nal c
odes
.5)
Uni
t sha
ll be
gro
unde
d in
com
plia
nce
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.6)
Wiri
ng s
how
n is
gen
eral
poi
nts-
of-c
onne
ctio
n gu
ides
onl
y an
d is
not
inte
nded
for o
r to
incl
ude
all d
etai
ls fo
r a s
peci
fic in
stal
latio
n.7)
Be
sure
to in
stal
l a s
witc
h an
d a
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8) In
stal
l a m
ain
switc
h th
at c
an in
terr
upt a
ll th
e po
wer
sou
rces
in a
n in
tegr
ated
man
ner b
ecau
se th
is s
yste
m c
onsi
sts
of th
e eq
uipm
ent u
tiliz
ing
the
mul
tiple
pow
er s
ourc
es.
9) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lost
pha
se, m
omen
tary
bla
ckou
t or t
he p
ower
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed p
hase
pro
tect
ion
circ
uit l
ocal
ly.
R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor a
nd o
ther
par
ts.
75
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ192 - 288TATJU / TAYDU / TAYCU · RWEQ192 - 288TATJA / TAYDA
C: 3
D12
0277
[Ope
ratio
n sy
stem
: Hea
t pum
p]
Not
es:
1) A
ll w
iring
, com
pone
nts
and
mat
eria
ls to
be
proc
ured
on
the
site
mus
t com
ply
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.2)
Use
cop
per c
ondu
ctor
s on
ly.
3) A
s fo
r det
ails
, see
wiri
ng d
iagr
am.
4) F
ield
wiri
ng d
iagr
am is
to b
e us
ed a
s a
guid
elin
e on
ly.
W
iring
sho
uld
com
ply
with
app
licab
le lo
cal a
nd n
atio
nal c
odes
.5)
Uni
t sha
ll be
gro
unde
d in
com
plia
nce
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.6)
Wiri
ng s
how
n is
gen
eral
poi
nts-
of-c
onne
ctio
n gu
ides
onl
y an
d is
not
inte
nded
for o
r to
incl
ude
all d
etai
ls fo
r a s
peci
fic in
stal
latio
n.7)
Be
sure
to in
stal
l a s
witc
h an
d a
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8) In
stal
l a m
ain
switc
h th
at c
an in
terr
upt a
ll th
e po
wer
sou
rces
in a
n in
tegr
ated
man
ner b
ecau
se th
is s
yste
m c
onsi
sts
of th
e e q
uipm
ent u
tiliz
ing
the
mul
tiple
pow
er s
ourc
es.
9) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lost
pha
se, m
omen
tary
bla
ckou
t or t
he p
ower
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed p
hase
pro
tect
ion
circ
uit l
ocal
ly.
R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor a
nd o
ther
par
ts.
76
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ312 - 432TATJU / TAYDU / TAYCU · RWEQ312 - 432TATJA / TAYDA
C: 3
D10
9399
[Ope
ratio
n sy
stem
: Hea
t pum
p]
Not
es:
1) A
ll w
iring
, com
pone
nts
and
mat
eria
ls to
be
proc
ured
on
the
site
mus
t com
ply
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.2)
Use
cop
per c
ondu
ctor
s on
ly.
3) A
s fo
r det
ails
, see
wiri
ng d
iagr
am.
4) F
ield
wiri
ng d
iagr
am is
to b
e us
ed a
s a
guid
elin
e on
ly.
W
iring
sho
uld
com
ply
with
app
licab
le lo
cal a
nd n
atio
nal c
odes
.5)
Uni
t sha
ll be
gro
unde
d in
com
plia
nce
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.6)
Wiri
ng s
how
n is
gen
eral
poi
nts-
of-c
onne
ctio
n gu
ides
onl
y an
d is
not
inte
nded
for o
r to
incl
ude
all d
etai
ls fo
r a s
peci
fic in
stal
latio
n.7)
Be
sure
to in
stal
l a s
witc
h an
d a
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8) In
stal
l a m
ain
switc
h th
at c
an in
terr
upt a
ll th
e po
wer
sou
rces
in a
n in
tegr
ated
man
ner b
ecau
se th
is s
yste
m c
onsi
sts
of th
e e q
uipm
ent u
tiliz
ing
the
mul
tiple
pow
er s
ourc
es.
9) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lost
pha
se, m
omen
tary
bla
ckou
t or t
he p
ower
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed p
hase
pro
tect
ion
circ
uit l
ocal
ly.
R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor a
nd o
ther
par
ts.
77
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
14.2 Heat RecoveryRWEQ96 - 144TATJU / TAYDU / TAYCU · RWEQ96 - 144TATJA / TAYDA
C: 3
D12
0278
[Ope
ratio
n sy
stem
: Hea
t rec
over
y]
Not
es 1
) All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
ed o
n th
e si
te m
ust c
ompl
y w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
2)
Use
cop
per c
ondu
ctor
s on
ly.
3)
As
for d
etai
ls, s
ee w
iring
dia
gram
.
4) F
ield
wiri
ng d
iagr
am is
to b
e us
ed a
s a
guid
elin
e on
ly.
Wiri
ng s
houl
d co
mpl
y w
ith a
pplic
able
loca
l and
nat
iona
l cod
es.
5)
Uni
t sha
ll be
gro
unde
d in
com
plia
nce
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.
6) W
iring
sho
wn
is g
ener
al p
oint
s-of
-con
nect
ion
guid
es o
nly
and
is n
ot in
tend
ed fo
r or t
o in
clud
e al
l det
ails
for a
spe
cific
inst
alla
tion.
7)
Be
sure
to in
stal
l a s
witc
h an
d a
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8)
Inst
all a
mai
n sw
itch
that
can
inte
rrup
t all
the
pow
er s
ourc
es in
an
inte
grat
ed m
anne
r bec
ause
this
sys
tem
con
sist
s of
the
equi
pmen
t util
izin
g th
e m
ultip
le p
ower
sou
rces
.
9) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lost
pha
se, m
omen
tary
bla
ckou
t or t
he p
ower
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed p
hase
pro
tect
ion
circ
uit l
ocal
ly.
Run
ning
the
prod
uct i
n re
vers
ed p
hase
may
bre
ak th
e co
mpr
esso
r and
oth
er p
arts
.
78
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ192 - 288TATJU / TAYDU / TAYCU · RWEQ192 - 288TATJA / TAYDA
C: 3
D12
0279
[Ope
ratio
n sy
stem
: Hea
t rec
over
y]
Not
es 1
) All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
ed o
n th
e si
te m
ust c
ompl
y w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
2)
Use
cop
per c
ondu
ctor
s on
ly.
3)
As
for d
etai
ls, s
ee w
iring
dia
gram
.
4) F
ield
wiri
ng d
iagr
am is
to b
e us
ed a
s a
guid
elin
e on
ly.
Wiri
ng s
houl
d co
mpl
y w
ith a
pplic
able
loca
l and
nat
iona
l cod
es.
5)
Uni
t sha
ll be
gro
unde
d in
com
plia
nce
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.
6) W
iring
sho
wn
is g
ener
al p
oint
s-of
-con
nect
ion
guid
es o
nly
and
is n
ot in
tend
ed fo
r or t
o in
clud
e al
l det
ails
for a
spe
cific
inst
alla
tion.
7)
Be
sure
to in
stal
l a s
witc
h an
d a
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8)
Inst
all a
mai
n sw
itch
that
can
inte
rrup
t all
the
pow
er s
ourc
es in
an
inte
grat
ed m
anne
r bec
ause
this
sys
tem
con
sist
s of
the
equi
pmen
t util
izin
g th
e m
ultip
le p
ower
sou
rces
.
9) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lost
pha
se, m
omen
tary
bla
ckou
t or t
he p
ower
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed p
hase
pro
tect
ion
circ
uit l
ocal
ly.
Run
ning
the
prod
uct i
n re
vers
ed p
hase
may
bre
ak th
e co
mpr
esso
r and
oth
er p
arts
.
79
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ312 - 432TATJU / TAYDU / TAYCU · RWEQ312 - 432TATJA / TAYDA
C: 3
D10
9406
[Ope
ratio
n sy
stem
: Hea
t rec
over
y]
Not
es 1
) All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
ed o
n th
e si
te m
ust c
ompl
y w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
2)
Use
cop
per c
ondu
ctor
s on
ly.
3)
As
for d
etai
ls, s
ee w
iring
dia
gram
.
4) F
ield
wiri
ng d
iagr
am is
to b
e us
ed a
s a
guid
elin
e on
ly.
Wiri
ng s
houl
d co
mpl
y w
ith a
pplic
able
loca
l and
nat
iona
l cod
es.
5)
Uni
t sha
ll be
gro
unde
d in
com
plia
nce
with
the
appl
icab
le lo
cal a
nd n
atio
nal c
odes
.
6) W
iring
sho
wn
is g
ener
al p
oint
s-of
-con
nect
ion
guid
es o
nly
and
is n
ot in
tend
ed fo
r or t
o in
clud
e al
l det
ails
for a
spe
cific
inst
alla
tion.
7)
Be
sure
to in
stal
l a s
witc
h an
d a
fuse
/bre
aker
to th
e po
wer
line
of e
ach
piec
e of
equ
ipm
ent.
8)
Inst
all a
mai
n sw
itch
that
can
inte
rrup
t all
the
pow
er s
ourc
es in
an
inte
grat
ed m
anne
r bec
ause
this
sys
tem
con
sist
s of
the
equi
pmen
t util
izin
g th
e m
ultip
le p
ower
sou
rces
.
9) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lost
pha
se, m
omen
tary
bla
ckou
t or t
he p
ower
goe
s on
and
off
whi
le th
e pr
oduc
t is
oper
atin
g, a
ttach
a re
vers
ed p
hase
pro
tect
ion
circ
uit l
ocal
ly.
Run
ning
the
prod
uct i
n re
vers
ed p
hase
may
bre
ak th
e co
mpr
esso
r and
oth
er p
arts
.
80
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
15. Electrical Characteristics
RWEQ96 - 432TATJU · RWEQ96 - 432TATJA
Model name Units Power supply CompressorSCCR
Combination unit Independent unit Hz Volts Voltage range MCA MOP RLA
RWEQ96TATJU 60 208 / 230Max. 253 V
28.8 35 19.0
SCCR kA rms, Symmetrical
@600 V MAX: 5
Min. 187 V
RWEQ120TATJU 60 208 / 230Max. 253 V
36.5 45 20.9Min. 187 V
RWEQ144TATJU 60 208 / 230Max. 253 V
44.6 50 29.4Min. 187 V
RWEQ192TATJURWEQ96TATJU
60 208 / 230Max. 253 V
28.8 + 28.8 35 + 35 19.0 + 19.0RWEQ96TATJU Min. 187 V
RWEQ216TATJURWEQ96TATJU
60 208 / 230Max. 253 V
28.8 + 36.5 35 + 45 19.0 + 20.9RWEQ120TATJU Min. 187 V
RWEQ240TATJURWEQ120TATJU
60 208 / 230Max. 253 V
36.5 + 36.5 45 + 45 20.9 + 20.9RWEQ120TATJU Min. 187 V
RWEQ264TATJURWEQ120TATJU
60 208 / 230Max. 253 V
36.5 + 44.6 45 + 50 20.9 + 29.4RWEQ144TATJU Min. 187 V
RWEQ288TATJURWEQ144TATJU
60 208 / 230Max. 253 V
44.6 + 44.6 50 + 50 29.4 + 29.4RWEQ144TATJU Min. 187 V
RWEQ312TATJURWEQ96TATJU
60 208 / 230Max. 253 V
28.8 + 28.8 + 36.5 35 + 35 + 45 19.0 + 19.0 + 20.9RWEQ96TATJUMin. 187 VRWEQ120TATJU
RWEQ336TATJURWEQ96TATJU
60 208 / 230Max. 253 V
28.8 + 36.5 + 36.5 35 + 45 + 45 19.0 + 20.9 + 20.9RWEQ120TATJUMin. 187 VRWEQ120TATJU
RWEQ360TATJURWEQ120TATJU
60 208 / 230Max. 253 V
36.5 + 36.5 + 36.5 45 + 45 + 45 20.9 + 20.9 + 20.9RWEQ120TATJUMin. 187 VRWEQ120TATJU
RWEQ384TATJURWEQ120TATJU
60 208 / 230Max. 253 V
36.5 + 36.5 + 44.6 45 + 45 + 50 20.9 + 20.9 + 29.4RWEQ120TATJUMin. 187 VRWEQ144TATJU
RWEQ408TATJURWEQ120TATJU
60 208 / 230Max. 253 V
36.5 + 44.6 + 44.6 45 + 50 + 50 20.9 + 29.4 + 29.4RWEQ144TATJUMin. 187 VRWEQ144TATJU
RWEQ432TATJURWEQ144TATJU
60 208 / 230Max. 253 V
44.6 + 44.6 + 44.6 50 + 50 + 50 29.4 + 29.4 + 29.4RWEQ144TATJUMin. 187 VRWEQ144TATJU
Note:1. RLA is based on the following conditions.
Indoor temp. 80.6°FDB (27°CDB) / 66.2°FWB (19°CWB) Entering water temp. 86°F (30°C)
2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.
3. Maximum allowable voltage variation between phases is 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.
Symbol:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protective Device (A)RLA: Rated Load Amps. (A)SCCR: Short-Circuit Current Rating
3D109376C 3D127049
81
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ96 - 432TAYDU · RWEQ96 - 432TAYDA
Model name Units Power supply CompressorSCCR
Combination unit Independent unit Hz Volts Voltage range MCA MOP RLA
RWEQ96TAYDU 60 460Max. 506 V
13.0 15 8.6
SCCR kA rms, Symmetrical
@600 V MAX: 5
Min. 414 V
RWEQ120TAYDU 60 460Max. 506 V
16.5 20 9.4Min. 414 V
RWEQ144TAYDU 60 460Max. 506 V
20.2 25 13.3Min. 414 V
RWEQ192TAYDURWEQ96TAYDU
60 460Max. 506 V
13.0 + 13.0 15 + 15 8.6 + 8.6RWEQ96TAYDU Min. 414 V
RWEQ216TAYDURWEQ96TAYDU
60 460Max. 506 V
13.0 + 16.5 15 + 20 8.6 + 9.4RWEQ120TAYDU Min. 414 V
RWEQ240TAYDURWEQ120TAYDU
60 460Max. 506 V
16.5 + 16.5 20 + 20 9.4 + 9.4RWEQ120TAYDU Min. 414 V
RWEQ264TAYDURWEQ120TAYDU
60 460Max. 506 V
16.5 + 20.2 20 + 25 9.4 + 13.3RWEQ144TAYDU Min. 414 V
RWEQ288TAYDURWEQ144TAYDU
60 460Max. 506 V
20.2 + 20.2 25 + 25 13.3 + 13.3RWEQ144TAYDU Min. 414 V
RWEQ312TAYDURWEQ96TAYDU
60 460Max. 506 V
13.0 + 13.0 + 16.5 15 + 15 + 20 8.6 + 8.6 + 9.4RWEQ96TAYDUMin. 414 VRWEQ120TAYDU
RWEQ336TAYDURWEQ96TAYDU
60 460Max. 506 V
13.0 + 16.5 + 16.5 15 + 20 + 20 8.6 + 9.4 + 9.4RWEQ120TAYDUMin. 414 VRWEQ120TAYDU
RWEQ360TAYDURWEQ120TAYDU
60 460Max. 506 V
16.5 + 16.5 + 16.5 20 + 20 + 20 9.4 + 9.4 + 9.4RWEQ120TAYDUMin. 414 VRWEQ120TAYDU
RWEQ384TAYDURWEQ120TAYDU
60 460Max. 506 V
16.5 + 16.5 + 20.2 20 + 20 + 25 9.4 + 9.4 + 13.3RWEQ120TAYDUMin. 414 VRWEQ144TAYDU
RWEQ408TAYDURWEQ120TAYDU
60 460Max. 506 V
16.5 + 20.2 + 20.2 20 + 25 + 25 9.4 + 13.3 + 13.3RWEQ144TAYDUMin. 414 VRWEQ144TAYDU
RWEQ432TAYDURWEQ144TAYDU
60 460Max. 506 V
20.2 + 20.2 + 20.2 25 + 25 + 25 13.3 + 13.3 + 13.3RWEQ144TAYDUMin. 414 VRWEQ144TAYDU
Note:1. RLA is based on the following conditions.
Indoor temp. 80.6°FDB (27°CDB) / 66.2°FWB (19°CWB) Entering water temp. 86°F (30°C)
2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.
3. Maximum allowable voltage variation between phases is 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.
Symbol:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protective Device (A)RLA: Rated Load Amps. (A)SCCR: Short-Circuit Current Rating
3D109357C 3D127049
82
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ96 - 432TAYCU
Model name Units Power supply CompressorSCCR
Combination unit Independent unit Hz Volts Voltage range MCA MOP RLA
RWEQ96TAYCU 60 575Max. 632 V
13.0 15 6.9
SCCR kA rms, Symmetrical
@600 V MAX: 5
Min. 518 V
RWEQ120TAYCU 60 575Max. 632 V
16.3 20 7.5Min. 518 V
RWEQ144TAYCU 60 575Max. 632 V
19.9 25 10.6Min. 518 V
RWEQ192TAYCURWEQ96TAYCU
60 575Max. 632 V
13.0 + 13.0 15 + 15 6.9 + 6.9RWEQ96TAYCU Min. 518 V
RWEQ216TAYCURWEQ96TAYCU
60 575Max. 632 V
13.0 + 16.3 15 + 20 6.9 + 7.5RWEQ120TAYCU Min. 518 V
RWEQ240TAYCURWEQ120TAYCU
60 575Max. 632 V
16.3 + 16.3 20 + 20 7.5 + 7.5RWEQ120TAYCU Min. 518 V
RWEQ264TAYCURWEQ120TAYCU
60 575Max. 632 V
16.3 + 19.9 20 + 25 7.5 + 10.6RWEQ144TAYCU Min. 518 V
RWEQ288TAYCURWEQ144TAYCU
60 575Max. 632 V
19.9 + 19.9 25 + 25 10.6 + 10.6RWEQ144TAYCU Min. 518 V
RWEQ312TAYCURWEQ96TAYCU
60 575Max. 632 V
13.0 + 13.0 + 16.3 15 + 15 + 20 6.9 + 6.9 + 7.5RWEQ96TAYCUMin. 518 VRWEQ120TAYCU
RWEQ336TAYCURWEQ96TAYCU
60 575Max. 632 V
13.0 + 16.3 + 16.3 15 + 20 + 20 6.9 + 7.5 + 7.5RWEQ120TAYCUMin. 518 VRWEQ120TAYCU
RWEQ360TAYCURWEQ120TAYCU
60 575Max. 632 V
16.3 + 16.3 + 16.3 20 + 20 + 20 7.5 + 7.5 + 7.5RWEQ120TAYCUMin. 518 VRWEQ120TAYCU
RWEQ384TAYCURWEQ120TAYCU
60 575Max. 632 V
16.3 + 16.3 + 19.9 20 + 20 + 25 7.5 + 7.5 + 10.6RWEQ120TAYCUMin. 518 VRWEQ144TAYCU
RWEQ408TAYCURWEQ120TAYCU
60 575Max. 632 V
16.3 + 19.9 + 19.9 20 + 25 + 25 7.5 + 10.6 + 10.6RWEQ144TAYCUMin. 518 VRWEQ144TAYCU
RWEQ432TAYCURWEQ144TAYCU
60 575Max. 632 V
19.9 + 19.9 + 19.9 25 + 25 + 25 10.6 + 10.6 + 10.6RWEQ144TAYCUMin. 518 VRWEQ144TAYCU
Note:1. RLA is based on the following conditions.
Indoor temp. 80.6°FDB (27°CDB) / 66.2°FWB (19°CWB) Entering water temp. 86°F (30°C)
2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.
3. Maximum allowable voltage variation between phases is 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.
Symbol:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protective Device (A)RLA: Rated Load Amps. (A)SCCR: Short-Circuit Current Rating
4D117563
83
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
16. Operation Limits16.1 Heat PumpRWEQ96 - 432TATJU / TAYDU / TAYCU · RWEQ96 - 432TATJA / TAYDA
3D109400
84
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
16.2 Heat RecoveryRWEQ96 - 432TATJU / TAYDU / TAYCU · RWEQ96 - 432TATJA / TAYDA
C: 3D109407
85
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
17. Operation Limits (Antifreeze Usage)17.1 Heat PumpRWEQ96 - 432TATJU / TAYDU / TAYCU · RWEQ96 - 432TATJA / TAYDA
3D109408A
86
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
17.2 Heat RecoveryRWEQ96 - 432TATJU / TAYDU / TAYCU · RWEQ96 - 432TATJA / TAYDA
C: 3D109409B
87
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
18. Sound Levels (Reference Data)
RWEQ96TATJU / TAYDU / TAYCU · RWEQ96TATJA / TAYDA
4D109785A
88
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ120TATJU / TAYDU / TAYCU · RWEQ120TATJA / TAYDA
4D109786A
89
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
RWEQ144TATJU / TAYDU / TAYCU · RWEQ144TATJA / TAYDA
4D109787A
90
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
19. Accessories19.1 Optional AccessoriesRWEQ96 - 432TATJU / TAYDU / TAYCU · RWEQ96 - 432TATJA / TAYDA
Optional accessories
RWEQ96TATJURWEQ96TAYDURWEQ96TAYCURWEQ96TATJARWEQ96TAYDA
RWEQ120TATJURWEQ120TAYDURWEQ120TAYCURWEQ120TATJARWEQ120TAYDA
RWEQ144TATJURWEQ144TAYDURWEQ144TAYCURWEQ144TATJARWEQ144TAYDA
RWEQ192 - 288TATJURWEQ192 - 288TAYDURWEQ192 - 288TAYCURWEQ192 - 288TATJARWEQ192 - 288TAYDA
RWEQ312 - 432TATJURWEQ312 - 432TAYDURWEQ312 - 432TAYCURWEQ312 - 432TATJARWEQ312 - 432TAYDA
Cool / Heat selector (Note 2) KRC19-26A6ABC I/P printed circuit board BRP2A81Fixing box KJB111A
Distributive piping
REFNET header
for 3 pipes
(Max.8 branch)KHRP25M33H9KHRP25M33HA
(Max.8 branch)KHRP25M33H9 KHRP25M33HA KHRP25M72H9 KHRP25M72HA
(Max.8 branch)KHRP25M33H9 KHRP25M33HAKHRP25M72H9 KHRP25M72HA
KHRP25M73HU9 KHRP25M73HUA
for 2 pipes
(Max.4 branch) KHRP26M22H9KHRP26M22HA
(Max.8 branch)KHRP26M33H9KHRP26M33HA
(Max.4 branch) KHRP26M22H9 KHRP26M22HA
(Max.8 branch)KHRP26M33H9 KHRP26M33HAKHRP26M72H9 KHRP26M72HA
(Max.4 branch) KHRP26M22H9 KHRP26M22HA
(Max.8 branch) KHRP26M33H9 KHRP26M33HA KHRP26M72H9 KHRP26M72HA
KHRP26M73HU9 KHRP26M73HUA
REFNET joint
for 3 pipes
KHRP25A22T9 KHRP25A33T9KHRP25A22TA KHRP25A33TA
KHRP25A22T9 KHRP25A22TA KHRP25A33T9 KHRP25A33TA
KHRP25M72TU9 KHRP25M72TUA
KHRP25A22T9 KHRP25A22TA KHRP25A33T9 KHRP25A33TA
KHRP25M72TU9 KHRP25M72TUA KHRP25M73TU9 KHRP25M73TUA
for 2 pipes
KHRP26A22T9 KHRP26A33T9KHRP26A22TA KHRP26A33TA
KHRP26A22T9 KHRP26A22TA KHRP26A33T9 KHRP26A33TA
KHRP26M72TU9 KHRP26M72TUA
KHRP26A22T9 KHRP26A22TA KHRP26A33T9 KHRP26A33TA
KHRP26M72TU9 KHRP26M72TUA KHRP26M73TU9 KHRP26M73TUA
Outside unit multi connection piping kit
for 3 pipes — — BHFP26T84U BHFP26T126U
for 2 pipes — — BHFP22T84U BHFP22T126U
External control adaptor for outside unit DTA104A62
Note:1. Refer to the latest drawing.2. In the case of heat recovery system.
Cool / Heat selector cannot be connected.
C: 3D109401B C: 3D127047
91
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
20. Selection Procedure20.1 Selection Procedure20.1.1 Flowchart
Confirm that the number of indoor units connected to the outside unit is within limitation.
Provisionally select outside unit type and size based on limitation of connection ratio
Correct cooling & heating capacity of the outside unit for the following items
VRV system selection is complete.
Corrected capacity of the outside unit ≥ Required total heat load to the outside unit
2) Use the system peak load1) Use the sum of the peak load of each room
Define required total heat load to outside unit
Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units
Yes
No
-Piping length, level difference-Piping heat loss-Safety factor for the outside unit
-Entering water temperature-Indoor air temperature-Connection ratio
Given Conditions:· Indoor unit design temperature and humidity· Outside unit entering water temperature and water flow rates· Required heat load of each room· System peak load (if necessary)· Piping length, level difference· Specifications of indoor units (type and number)
Define safety factor for the indoor units and outside unit
[1] Given conditions
[2] Selection of indoor units
[3] Selection of outside unit
-Antifreeze ratio
-Water flow rate
92
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
20.1.2 Selection Example
The following is a selection example based on total heat load for cooling.
Room ARoom H Room G
Room F
E mooRB mooRRoom C Room D
Floor plan
[1] Given conditions-Design conditionsIndoorairtemperature:67°FWB/80°FDB,Outdoorenteringwatertemperature:85°Fandwaterflowrateof25gpm.
-Determine peak load of each room (and system peak load if necessary)
-Required heat load of each room
From the above heat load calculation, the maximum heat load for the system (system peak load) is 173.2 MBH.
-Safety factorIn this example, safety factor is not used. (i. e., safety factor = 1.0)
[2] Selection of indoor unitsCalculate total heat capacity of indoor units corrected for indoor air temperature.In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.
Time Room A Room B Room C Room D Room E Room F Room G Room H Total9:00 16.4 16.5 10.4 10.4 30.9 30.8 10.0 10.0 135.4
12:00 22.4 24.4 17.3 17.3 25.1 23.2 13.7 13.7 157.114:00 30.7 32.2 16.8 16.8 24.9 23.4 14.2 14.2 173.216:00 36.1 36.4 13.3 13.3 21.5 21.2 13.0 13.0 167.8
Total heat load (MBH)
Level difference10 ft.
Select VRV indoor units FXMQ-PB series for each room.
Equivalent pipe length 100 ft.
93
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Capacity table of indoor unitCooling Capacity
Model
Indoor air temp.°FWB (Te: 43°F (6°C))61 64 67 70 72 75
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH
FXMQ07PBVJU 5.7 5.5 6.4 5.9 7.2 6.1 7.3 6.5 7.4 5.8 7.6 5.8 FXMQ09PBVJU 7.5 6.9 8.5 7.3 9.5 7.8 9.7 8.1 9.8 7.1 10.0 7.2FXMQ12PBVJU 9.5 8.5 10.7 9.1 12.0 9.7 12.2 10.0 12.4 9.2 12.6 9.2FXMQ15PBVJU 11.2 10.2 12.7 10.7 14.2 11.4 14.5 11.6 14.7 11.5 14.9 9.6 FXMQ18PBVJU 14.2 13.9 16.1 14.7 18.0 15.6 18.4 16.1 18.6 14.6 18.9 12.1FXMQ24PBVJU 19.0 16.5 21.5 17.7 24.0 18.8 24.5 19.2 24.8 17.9 25.3 20.1FXMQ30PBVJU 23.7 20.8 26.8 22.3 30.0 23.8 30.6 24.4 31.0 22.5 31.6 22.5FXMQ36PBVJU 28.4 25.0 32.2 26.9 36.0 28.8 36.7 30.0 37.2 27.7 37.9 27.7FXMQ48PBVJU 37.9 31.3 43.0 33.6 48.0 35.8 49.0 36.9 49.6 34.7 50.5 33.2FXMQ54PBVJU 42.6 35.2 48.3 37.8 54.0 40.3 55.1 41.5 55.8 39.0 56.8 37.4
TC: Total capacity: MBHSHC: Sensible heat capacity: MBH
Selection results of indoor units
Room A Room B Room C Room D Room E Room F Room G Room HMax. heat load (MBH) 36.1 36.4 17.3 17.3 30.9 30.8 14.1 14.1
Selected IDU FXMQ48PBVJU FXMQ48PBVJU FXMQ18PBVJU FXMQ18PBVJU FXMQ36PBVJU FXMQ36PBVJU FXMQ15PBVJU FXMQ15PBVJUCorrected TC (MBH) 48.0 48.0 18.0 18.0 36.0 36.0 14.2 14.2
∗In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.
[3] Selection of outside unit[3] –1 Define the required total heat load from the indoor units to the outside unitDefinetherequiredtotalheatload(A)basedon(1)thesumofthepeakloadofeachroomor(2)thesystempeakload.In this example, select an outside unit by (2).Therefore, (A) = 173.2 MBH
94
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
[3] –2 Provisionally select outside unit(1) Calculate CI (Capacity Index) of the selected indoor units.
CI of VRV indoor units CI of FXMQ15PBVJU = 15 CI of FXMQ18PBVJU = 18 CI of FXMQ36PBVJU = 36 CI of FXMQ48PBVJU = 48
Capacity Range 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 7.5 9.5 12 15 18 20 24 30 36 42 48 54 72 96
Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB —
5 ton60
— — VJU
0.5 ton5.8
—
Calculate the total CI of the indoor units.Total CI = 15 × 2 + 18 × 2 + 36 × 2 + 48 × 2 = 234
(2) Provisionally select an outside unit based on the total CI of the indoor units
The connection ratio of RWEQ-TA shall be between 50% and 150%.As the total CI of the indoor units is 234, outside units from 16 ton to 36 ton are connectable.Start from 16 ton which is the smallest outside unit.
(3) Confirm that the number of the connected indoor units is within the limitation.
The number of the connected indoor units = 8The max. number of connectable indoor units of 16 ton outside unit = 33
95
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
[3] –3 Calculate the corrected capacity of the outside unit.-Calculate the connection ratio of the system.Total CI = 234, CI of RWEQ192TATJU = 192Connection ratio = 234 / 192 = 122%
-Usingthecapacitytableoftheoutsideunit,calculatethecapacity(B)correctedforoutsideenteringwatertemperature,waterflowrate,indoorairtemperature, and connection ratio.
*Incasetheoutsideenteringwatertemperature,waterflowrate,theindoorairtemperature,ortheconnectionratiofallsbetweentemperatureslisted in the table, calculate the capacity by interpolation.
120% 122% 130%
228 (B) 232
Connection ratio
Cooling capacity
RWEQ192TATJU / TAYDU / TAYCU · RWEQ192TATJA / TAYDA — Cooling RWEQ192TATJU / TAYDU / TAYCU · RWEQ192TATJA / TAYDA — Cooling (continued)
(B) = 228 + (232 – 228) × (122 – 120) / (130 – 120) = 228.8
96
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
-Confirmcapacitycorrectionfactorbypipinglengthandleveldifference(K1)
(K1) = 0.984
0.984
10
100
-Calculate capacity correction factor by piping heat loss (K2)(K2) = 1 + (heat loss factor per feet of piping × (equivalent piping length – 25 ft.)) / 100
In cooling mode, heat loss factor per feet at 93°F is calculated as below.(R) Heat loss factor per feet = 0.072*2 + (0.098*1 – 0.072*2) × (93*3 – 86*4) / (95*5 – 86*4) = 0.0922
Using “Equivalent piping length = 100 ft” and “Heat loss factor per feet = 0.0922”, (K2) = 1 + (0.0922 × (100 – 25)) / 100 = 1.07
Cooling Ambient temperature
Heat loss factor per feet of piping (%)
41°F 50°F 59°F 68°F 77°F 86°F*4 93°F*3 95°F*5 104°F0.000 0.000 0.013 0.030 0.046 0.072*2 (R) 0.098*1 0.125
erutarepmet tneibmAgnitaeH
Heat loss factor per feet of piping (%)
5°F 14°F 23°F 32°F 41°F 50°F 59°F 68°F0.328 0.305 0.282 0.256 0.233 0.210 0.187 0.161
-Calculate capacity correction factor by antifreeze loss (K3)It is 1.0 when using water.Antifreeze Correction Factor
Ethylene Glycol Propylene Glycol
Cooling Capacity
10% 0.998
Cooling Capacity
10% 0.99220% 0.994 20% 0.98830% 0.990 30% 0.98340% 0.985 40% 0.97450% 0.980 50% 0.968
Heating Capacity
10% 0.993
Heating Capacity
10% 0.98520% 0.989 20% 0.98230% 0.986 30% 0.97840% 0.982 40% 0.97050% 0.979 50% 0.966
CA12A095B-Calculate the corrected capacity of RWEQ216TATJU by using (K1), (K2) and (K3).Corrected capacity of RWEQ216TATJU = (B) × (K1) × (K3) / (K2)Therefore (C) = 228.8 × 0.984 × 1.0 / 1.07 = 210 MBH
If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.If (C) < (A), return to Procedure [3]–2 and provisionally select a larger outside unit.In this example, 210 MBH (C) > 173.2 MBH (A), so there is no need to select a larger outside unit.
97
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
21. Instructions for Antifreeze Usage21.1 Instruction of Setting Water (Brine) Lower Flow Limit % for Variable Flow System
Pleasesetthefieldsetting[2-24]accordingtolocalpump/valveinstallationsituationandoperatevariableflowcontrol.
[2-24-0]:VariableflowcontrolfunctionisOFF.(default)[2-24-1]: One pump/valve per module
Pump/valve on secondary units remain ON when secondary units are OFF.[2-24-3]: One pump/valve per module
Pump/valve on secondary units are OFF when secondary units are OFF.Please connect the valve/pump for each unit.
Sub2 Sub1 Main
H/E H/E
Pump
Pump Operation
Indoor unit
Outside unitOutside unitOutside unit
H/E
H/E : Heat exchanger
[2-24-2]: One pump/valve per system
Sub2 Sub1 Main
H/E H/E H/E
Pump
Pump Operation
Indoor unit
Outside unitOutside unitOutside unit
98
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Pleasesetthefieldsetting[2-25]sothattheminimumwatervolumedoesnotgodownbelow13.2gpm(50L/min).Whenusingbrineatenteringwatertemperatureof50˚F(10˚C)orless,pleasesettheminimumwaterflowlimitto21.2gpm(80L/min)ormore.lowerlimitwater(brine)flowratesettingforvariablewaterflow
[2-25] Flow%ofmaxflowrate DC output (V)
— 0%(thermo-off) 2.0
0 10% 2.71 20% 3.42 30% 4.13 40% 4.8
4(default) 50% 5.55 60% 6.26 70% 6.97 80% 7.6— 90% 8.3
— 100%(Localmaxflowrate) 9.0
Whentheunitstoporthermo-off,theDCoutputis2.0V.
[Example]Whenthelocal100%flowrate= 39.6 gpm (150 L/min) usingwater,Whenthewaterflowoperatesinproportion to the voltage. 2.0 V: 0%- 9.0 V: 100% Lower limit case 13.2 gpm (50 L/min) for using water.
(b)13.2 gpm (lower limit water volume)
(a)39.6 gpm (local 100% flow rate)= 0.33 33%
Please select the closest setting with a value of 33% or more. set to [2-25-3] (40%)So,lowerflowratewillbe(c)15.8gpm(60L/min)And DC output range is (d) 4.8-9.0 V
100% Water (brine) volume
9.0 V
DC Output(2-9 V)
0%
2.0 V
5.5 V
80%
7.6 V
50%
(Default) DC output range5.5-9.0 V
Water volume39.615.8
(a)(b)
100%
9.0 V
0%
2.0 V
4.8 V
40%13.233%
(c)
(d)DC output range4.8-9.0 V
(gpm)
DC Output(2-9 V)
lower limit
99
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
22. Caution for Refrigerant Leaks22.1 Introduction
Points to note in connection with refrigerant leaks
The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.
The VRV System, like other air conditioning systems, uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant.Neverthelesscaremustbetakentoensurethatairconditioningfacilitiesareinstalledinaroomwhichissufficientlylarge.Thisassuresthat the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.
Maximum concentration levelThe maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is lb./1000 ft.³ (the weight in Ibs. of the refrigerant gas in 1 ft.³ volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.
Direction of therefrigerant flow
Room where refrigerant leak has occurred(outflow of all the refrigerant from the system)
Pay special attention to places, such as basements, etc. where refrigerant can stay, since refrigerant is heavier than air.
100
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
22.2 Procedure for Checking Maximum Concentration
Check the maximum concentration in accordance with steps 1 to 4 below and take whatever action is necessary.
Step1: Calculate the amount of refrigerant (lbs.) charged to each system separately.
Note:Where a single refrigerant facility is divided onto 2 entirely independent refrigerant systems then use the amounts of refrigerant with which each separate system of charged.
Step 2: Calculate the smallest room volume (ft.³)In case like the following, calculate the volume of (a), (b) as a single room or as the smallest room.(a) Where there are no smaller room divisions.
(b)Wherethereisaroomdivisionbutthereisanopeningbetweentheroomssufficientlylargetopermitafreeflowofairbackandforth.
(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15% or moreofthefloorarea.)
(c) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target.
101
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Step 3: Calculate the refrigerant density using the results of the calculations in step 1 and 2 above.
Total volume of refrigerantin the refrigerant system
≤Maximumconcentrationlevel(lbs./ft.³)Size (ft.³) of the smallest room inwhich there is an indoor unitinstalled
If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so on until the result falls short of the concentration level.
Step 4: Dealing with the situations where the result exceeds the maximum concentration level.Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system design.Please consult Daikin supplier.
102
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
23. Safety Devices Setting23.1 FXFQ-T
Model FXFQ07TVJU FXFQ09TVJU FXFQ12TVJU FXFQ15TVJU FXFQ18TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F (°C) – – – – –Fan motor thermal protector °F (°C) – – – – –Fan motor thermal fuse °F (°C) – – – – –
Model FXFQ24TVJU FXFQ30TVJU FXFQ36TVJU FXFQ48TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F (°C) – – – –Fan motor thermal protector °F (°C) – – – –Fan motor thermal fuse °F (°C) – – – –
C: 3D086932C
23.2 FXZQ-TA
Model FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F (°C) – – – – – –Fan motor thermal protector °F (°C) – – – – – –Drain pump fuse °F (°C) – – – – – –
C: 4D110603
23.3 FXUQ-P
Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F (°C) – – – –Fan motor thermal protector °F (°C) – – – –Fan motor thermal fuse °F (°C) – – – –
C: 3D090213
23.4 FXEQ-P
Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJUPrinted circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector °F (°C)OFF: 223±9
(106±5)ON: 205±27
(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
OFF: 223±9 (106±5)
ON: 205±27(96±15)
OFF: 223±9(106±5)
ON: 205±27(96±15)
C: 4D098709
103
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
23.5 FXDQ-M
Model FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJUPrinted circuit board fuse A1P 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal protector °F OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
OFF: 266±9ON: 181±27
C: 3D051758
23.6 FXSQ-TA
Model FXSQ05TAVJU FXSQ07TAVJU FXSQ09TAVJU FXSQ12TAVJU FXSQ15TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) — — — — —
Model FXSQ18TAVJU FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) — — — — — —
3D112398
23.7 FXMQ-PB
Model FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)
Model FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)
C: 3D086916B
23.8 FXMQ-M
Model FXMQ72MVJU FXMQ96MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – –
Fan motor thermal protector °F OFF: 275±14(ON: 189±27)
OFF: 275±14(ON: 189±27)
104
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
23.9 FXHQ-M
Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – – –
Fan motor thermal protector °F OFF: 266±9ON: 176±36
OFF: 266±9ON: 176±36
OFF: 266±9ON: 176±36
C: 3D049334A
23.10 FXAQ-P
Model FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F – – – – –Fan motor thermal protector °F – – – – –
C: 4D047085D
23.11 FXLQ-M, FXNQ-M
Model FXLQ07MVJUFXNQ07MVJU
FXLQ09MVJUFXNQ09MVJU
FXLQ12MVJUFXNQ12MVJU
FXLQ18MVJUFXNQ18MVJU
FXLQ24MVJUFXNQ24MVJU
Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal protector °F (°C)OFF: 275±18
(135±10)ON: 248 (120)
or less
OFF: 275±18(135±10)
ON: 248 (120)or less
OFF: 275±18(135±10)
ON: 248 (120)or less
OFF: 275±18(135±10)
ON: 248 (120)or less
OFF: 275±18(135±10)
ON: 248 (120)or less
C: 3D045646B
23.12 FXTQ-TA
Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUAModel (with factory disconnect) FXTQ09TAVJUD FXTQ12TAVJUD FXTQ18TAVJUD FXTQ24TAVJUD FXTQ30TAVJUD
Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector
Model FXTQ36TAVJUA FXTQ42TAVJUA FXTQ48TAVJUA FXTQ54TAVJUA FXTQ60TAVJUAModel (with factory disconnect) FXTQ36TAVJUD FXTQ42TAVJUD FXTQ48TAVJUD FXTQ54TAVJUD FXTQ60TAVJUD
Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector
105
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Appendix
1. Introduction .............................................................................................1061.1 ED Book List .................................................................................1061.2 Publication List of Engineering Data for VRV Products ................107
106
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
1. Introduction1.1 ED Book List
Design Manual ..................................................... RWEQ-TA ...... EDUS301864B-D (This booklet)
Capacity Table Book ............................................ RWEQ-TA ......EDUS301864A-C
Installation ........................................................... RWEQ-TA ........EDUS301864-N
Indoor Units
Ceiling Mounted Cassette Type (Round Flow with Sensing) ....... FXFQ-T ..... EDUS391400A-F14
VISTA™ 2 × 2 Cassette Unit .................................. FXZQ-TA ........ EDUS391776A-F9
4-Way Blow Ceiling-Suspended Type ....................... FXUQ-P ........ EDUS391437-F15
One Way Blow Cassette Type ................................ FXEQ-P ........ EDUS391533-F16
Slim Ceiling Mounted Duct Type ............................. FXDQ-M ........... EDUS39-600-F2
MSP Concealed Duct Unit ..................................... FXSQ-TA ...... EDUS391777A-F17
Ceiling Mounted Duct Type .................................... FXMQ-PB ........ EDUS391503A-F4
Ceiling Mounted Duct Type .................................... FXMQ-M ....... EDUS39-900A-F11
Ceiling Suspended Type ........................................ FXHQ-M ........... EDUS39-600-F5
WallMountEdType .............................................. FXAQ-P .......... EDUS391100-F6
Floor Standing Type / Concealed Floor Standing Type ........ FXLQ-MFXNQ-M .......... EDUS391502-F7
Air Handling Unit .................................................. FXTQ-TA .... Engineering Data FXTQ-TA
Air Treatment Equipment
Outdoor Air Processing Unit ................................... FXMQ-MF ....... EDUS39-900A-F10
Energy Recovery Ventilator .................................... VAM-G ............. EDUS711116A
Branch Selector Unit ........................................... BSQ-TBSF-Q54TBS-Q54T
......EDUS391434A-B
Controls .......................................................................................... EDUS721909A-T
Remote Controller
Navigation Remote Controller ................................. BRC1E73 ............... EDUS721438
107
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
1.2 Publication List of Engineering Data for VRV Products
Shaded sections indicate Engineering Data Book/s published for this series.Timing of publication is subject to change without notice.
Outdoor UnitRefrigerant Category Product series Type Volts Model name Area Book category Book No. Published in
R410A
Air cooled
VRV IV-X
H/R208/230 V460 V575 V
REYQ-XATJA, XAYDA, XAYCA USA Canada
Design manual EDUS371848B-D Sep.2020
Capacity table EDUS371848A-C Jan.2020
H/P
208/230 V460 V RXYQ-XATJA, XAYDA USA
CanadaDesign manual EDUS341923A-D Oct.2020Capacity table EDUS341923-C Nov.2019
575 V RXYQ-XAYCA CanadaDesign manual EDUS341928A-D Oct.2020Capacity table EDUS341928-C Nov.2019
VRV IV
H/R
208/230 V460 V REYQ-TATJA, TAYDA USA
CanadaDesign manual EDUS371704C-D
Feb.2020Capacity table EDUS371704C-C
575 V REYQ-TAYCA CanadaDesign manual EDUS371706C-DCapacity table EDUS371706C-C
H/P
208/230 V 460 V RXYQ-TATJA, TAYDA USA
CanadaDesign manual EDUS341703B-D
Jan.2020Capacity table EDUS341703B-C
575 V RXYQ-TAYCA CanadaDesign manual EDUS341824A-DCapacity table EDUS341824A-C
VRV Aurora
H/R208/230 V460 V575 V
RELQ-TATJA, TAYDA, TAYCA USACanada
Design manual EDUS371705D-D Sep.2020
Capacity table EDUS371705C-C Feb.2020
H/P208/230 V460 V575 V
RXLQ-TATJA, TAYDA, TAYCA USACanada
Design manual EDUS341819A-DJan.2020
Capacity table EDUS341819A-C
VRV IV-S H/P 208/230 V RXTQ36TAVJ9ARXTQ48/60TAVJUA
USA Canada
Design manual EDUS331608C-DFeb.2020
Capacity table EDUS331608C-C
VRV LIFE H/P 208/230 V RXSQ-TAVJUA USA Canada
Design manual EDUS331721A-DFeb.2020
Capacity table EDUS331721A-CInstallation for all VRV air cooled type Installation EDUS371848-N Aug.2019
Water cooled
VRV-W H/P H/R
208/230 V460 V575 V
RWEQ-TATJU, TAYDU, TAYCU RWEQ-TATJA, TAYDA
USA Canada
Design manual EDUS301864B-D Sep.2020
Capacity table EDUS301864A-C Jan.2020
Installation for all VRV water cooled type Installation EDUS301864-N Aug.2019
Note:C/O: Cooling only, H/P: Heat pump, H/R: Heat recovery
108
RWEQ-TATJU / TAYDU / TAYCU · RWEQ-TATJA / TAYDA EDUS301864B-D
Indoor Unit and Other Products
Refrigerant Product category Product type Model name Area Book No. Published in
R410A
VRV Indoor units
Ceiling Mounted Cassette Type (Round Flow with Sensing) FXFQ07-48TVJU USA EDUS391400B-F14 Jun.2020
VISTA™ 2 x 2 Cassette Unit FXZQ05-18TAVJU USA EDUS391776A-F9 Sep.2020
4-Way Blow Ceiling- Suspended Type FXUQ18-36PVJU USA EDUS391437-F15 May 2015
One Way Blow Cassette Type FXEQ07-24PVJU USA EDUS391533-F16 Oct.2015Slim Ceiling Mounted Duct Type FXDQ07-24MVJU USA EDUS39-600-F2 Sep.2006MSP Concealed Ducted Unit FXSQ05-54TAVJU USA EDUS391777A-F17 Sep.2020
Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503B-F4 Jun.2020
Ceiling Mounted Duct Type FXMQ72/96MVJU USA EDUS39-900A-F11 May 2010Ceiling Suspended Type FXHQ12-36MVJU USA EDUS39-600-F5 Sep.2006Wall Mounted Type FXAQ07-24PVJU USA EDUS391100-F6 Jan.2012Floor Standing Type Concealed Floor Standing Type
FXLQ07-24MVJU FXNQ07-24MVJU USA EDUS391502-F7 Jul.2015
Low-temperature hydrobox HXY48TAVJU USA EDUS392021-F18 Sep.2020
Cased Coil Unit CXTQ24-60TASBLU USA Engineering Data CXTQ-TA —
Air Handling Unit FXTQ09-60TAVJUA FXTQ09-60TAVJUD USA Engineering Data
FXTQ-TA Sep.2016
Outdoor Air Processing Unit FXMQ48-96MFVJU USA EDUS39-900A-F10 May 2010
Branch Selector UnitBSQ-TVJBSF-Q54TVJBS-Q54TVJ
USA EDUS391434A-B Aug.2020
Controls and
networks
Control systems Control devices Adaptors
Please refer to ED Book with No. on the right for applicable models. USA EDUS721909A-T Oct.2020
Navigation remote controller BRC1E73 USA EDUS721438 Apr.2015intelligent Touch Manager DCM601A71, DCM601A72 USA EDUS721212 Oct.2012intelligent Touch Controller DCS601C71 USA EDUS72-608 Dec.2006Interface for use in BACnet® DMS502B71 USA EDUS72-749 Oct.2007
Option for all type Please refer to ED Book with No. on the right for applicable models. USA OHUS07-1 Nov.2007
Energy Recovery Ventilator (VAM) VAM300-1200GVJU USA EDUS711116A Jun.2017
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
©All rights reserved 09/20 FS
●Specifications, designs and other content appearing in this brochure are current as of September 2020 but subject to change without notice.
EDU
S301864B-D
ENG
INEER
ING
DA
TA VR
V T-Series Water C
ooled System H
/P & H
/R 60 H
z DESIG
N M
AN
UA
L