epoxy mica coupling capacitor installation manual · electrical diagnostic innovations ... 8.1...

21
Copyright © VibroSystM Inc., 2013 Epoxy Mica Coupling Capacitor - Installation Manual P/N: 9477-09I1A-100 EPOXY MICA COUPLING CAPACITOR Installation Manual

Upload: vanbao

Post on 25-May-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

Copyright © VibroSystM Inc., 2013 Epoxy Mica Coupling Capacitor - Installation ManualP/N: 9477-09I1A-100

EPOXY MICA COUPLING CAPACITOR

Installation Manual

Page 2: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

Epoxy Mica Coupling Capacitor - Installation Manual

Page 3: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

2

Dynamic Ratings, Inc www.dynamicratings.com

Electrical Diagnostic Innovations www.elec-di.com

7308 Aspen Lane N #137 +1 612-963-0974

Brooklyn Park, MN 55428

INSTALLATION OF EPOXY MICA COUPLING CAPACITORS

VERSION @.1 JUNE 2010

Page 4: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

2 Smarter Solutions For Today and Tomorrow

TABLE OF CONTENTS

1.0 Introduction ............................................................................................................................... 3

2.0 Main Technical data for DYNMAIC RATINGS couplers ............................................................. 5

3.0 Capacitor Installation Locations ................................................................................................ 6

4. Primary connections and grounding ........................................................................................... 8

5. Secondary connections................................................................................................................ 9

6. Recommended tools and materials .......................................................................................... 10

7. Installing the coupler ................................................................................................................. 10

High Voltage connections: ......................................................................................................... 10

Ground connections: .................................................................................................................. 11

8. Detailed installation instructions .............................................................................................. 11

8.1 Preparation of Coax Cable ................................................................................................... 11

8.2. Mounting of the Capacitor ................................................................................................ 12

8.3. Installation using insulating boot ..................................................................................... 13

8.4 Taping the Connection instead of using the boot. ............................................................... 14

9. Couplers on hydro-generators ................................................................................................. 17

10. Couplers on large generators .................................................................................................. 17

11. Coupler connections in bus ducts ........................................................................................... 17

12. Coupler connection in transformers ....................................................................................... 17

Appendix A ..................................................................................................................................... 18

APPENDIX B - Sample Installtion Pictures ...................................................................................... 19

Page 5: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

3 Smarter Solutions For Today and Tomorrow

1.0 INTRODUCTION

An epoxy-mica coupling capacitor (coupler) is a device for sensitive detection of the partialdischarges in the electrical insulation of medium voltage AC apparatus, such as switchgears, motors, generators, transformers and other auxiliary medium voltage equipment.

Refer to the nameplate for the rating of the coupler and compare the rating with theequipment voltage class before attempting installation!

TO PERFORM INSTALLATION OF THE PRODUCT DESCRIBED IN THIS INSTRUCTION MANUAL, THE SUBJECT ELECTRICAL EQUIPMENT HAS TO BE DEENERGIZED AND SUITABLY SAFEGUARDED. ALL WORK HAS TO BE PERFORMED BY PERSONELL WHO AREQUALIFIED TO WORK ON HIGH-VOLTAGE ELECTRICAL EQUIPMENT WHILE STRICTLY ADHERING TO THE LOCAL SAFETY REGULATIONS.DISCLAIMER AND INDEMNIFICATION

Any person, firm or individual who installs or arranges for any other person, firm or individual, other than DYNMAIC RATINGS., to install the PDA capacitive coupler system, shall assume all risks and damages relating to or arising out of such installation.

DYNMAIC RATINGS. hereby disclaims any responsibility or obligation whatsoever for or in connection with the installation of the PDA capacitive coupler system.

The purchaser shall indemnify and save DYNMAIC RATINGS. harmless against any and all liabilities, losses, damages, claims, suits and expenses of whatsoever kind and nature imposed or asserted against DYNMAIC RATINGS. relating to or arising out of the installation of the PDA capacitive coupler system.

COPYRIGHT NOTICE

Page 6: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

4 Smarter Solutions For Today and Tomorrow

The information contained in this document is confidential and the property of DYNMAIC RATINGS. Photocopied or electronic reproduction in whole or in part without the written consent of DYNMAIC RATINGS. is strictly prohibited. This document shall not be sold, transferred or otherwise made available to any third party. Failure to comply with the copyright notice will result in penalties as prescribed by law.

Page 7: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

5 Smarter Solutions For Today and Tomorrow

2.0 MAIN TECHNICAL DATA FOR DYNMAIC RATINGS COUPLERS

Dynamic Ratings supplies three voltage levels of epoxy mica coupling capacitors.

Common Parameters

Operating Temperature - 40o C to 150o C.

Construction Epoxy Mica

Mounting Vertical or Horizontal

Diameter, inches/cm 3.5/9.1Sensitivity, pC < 1Capacitance, pF 80 + 2 pF

Frequency Range 0.5 MHz to 500 MHz

Voltage Rating (kV)

AC Hipot (kV) BIL (kV) Height (mm / Inch) with mounting base

Mass (kg)

8 20 75 86/3.38 0.9518 40 100 126/5.7 1.428 65 175 185/7.25 2.1

Additional Specifications

Meets ANSI/IEEE C37.20.2) Electrical Tracking Resistance Easily withstands 30 kV for 1500 hours (IEEE 1043) Voltage Endurance Test Dielectric Strength: 775 V/mil Insulating boots are provided to reduce installation time since no taping is required High Temperature Silicone jumper cable is provided for connection to the high voltage. Resists cracking and is extremely flexible compared to standard jumper cable

Page 8: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

6 Smarter Solutions For Today and Tomorrow

Unlike many other capacitor installations, the Dynamic Ratings capacitor is grounded at the point of installation and not at an external termination box. The Dynamic Ratings protection is located at the capacitor. This provides a couple of key advantages.

A. Additional Safety to operating and testing personnel. If the protection located in the termination box fails, high voltage can appear at the test terminals that could produce a life threatening shock.

B. Provides for better signal propagation for better measurements. There is no concern in looping cables or making sure they lie on a grounded surface.

3.0 CAPACITOR INSTALLATION LOCATIONS

Since there are no standards in designs of motors and generators, the location of mounting the capacitors always varies. Each installation must be evaluated to determine the best location. In all instances, the capacitor is connected from each phase to ground. In addition, Radio frequency current transformers (RFCTs) for motors and cable connected generators or a set of additional capacitors on large generators can be installed to determine pulse direction. Also, Dynamic Ratings uses the existing RTDs in the windings as PD sensors. Refer to our Application Guides and other documentation for additional information.

It is desirable to locate the capacitor as close as possible to the machine windings in the machine termination box and to keep the cable connecting the capacitor to the HV bus as short as possible. Additional length on the cable can greatly attenuate the PD signals and lower sensitivity. Typically capacitors installed at the line terminals only cover approximately 15% of the winding closest to the terminations. Any PD occurring deeper in the winding will not be detected. This is why Dynamic Ratings uses the RTDs as additional sensing point. Refer to our web site (www.dynamicratings.com) or contact Dynamic Ratings for additional information on this topic.

The following illustrations show sensor configurations and preferred methods of capacitor installation. IN ALL CASES, USE COMMON SENSE AND BE PRACTICAL. DO NOT COMPLETELY REDO A MOTOR TERMINATION BOX JUST TO COMPLY WITH THE RECOMMENDATIONS.

Page 9: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

7 Smarter Solutions For Today and Tomorrow

Preferred method Alternate method

Page 10: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

8 Smarter Solutions For Today and Tomorrow

4. PRIMARY CONNECTIONS AND GROUNDING

To ensure minimum inductance, all primary connections should be as short as possible.The coupler can be installed in the following ways:

A) Directly attached to metal cabinet floors, walls or ceilings. When using this optionyou need to d r i l l ho le s or cut into t he metal surface or install a spacer, so theoutgoing coaxial cable from the secondary terminals of the coupler on is groundedand provide sufficient space for the coax wire.

B) Attached with the custom-made ground bars or brackets at least 1” wide, or strongenough to support the capacitor and connections. The bus bars and brackets shouldbe as short as possible and directly grounded on both ends to the frame.

C) If ground bonding of the mounting surface is questionable, use additional ground wire to the ground bus or grounded frame. Always check the integrity of the coupler ground before energizing.

D) The connections to the primary (high voltage) circuits should be no longer than 2-3’and made of a bus bar with a cross-section not less than 1 x 0.1” or of A non-shieldedhigh voltage bare or insulated conductor of a size not less than #4 AWG should be used. Excessive length of cables should be trimmed to minimum.

E) The conductors must be routed to ensure proper clearances between thegrounded and live parts, as required by appropriate ANSI standards covering theequipment enclosures in which the coupler is being installed. As an example of a ruleof thumb for a system rated 15 kV, the ground clearances for the bare conductorsshould be at least 6 “and the clearances between the live parts of different phasesat least 8”. Use of appropriate barriers or insulated conductors mayallow significant reduction of such clearances but requires dielectric testing ofthe equipment before returning to operation.

F) The connections must be free of partial discharges and corona. Avoid sharp edges; if connections should be taped, use proper semi-conductive and grading tapesto avoid local concentration of electric stresses that can cause partial discharges.

G) Coupler connections to surge capacitors or surge arresters terminalsshould be avoided if possible. Such installation will significantly decrease the sensor sensitivity because these capacitors and arresters have essential stray capacitance, thus reducing the impulse current flowing inside the sensor.

Page 11: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

9 Smarter Solutions For Today and Tomorrow

5. SECONDARY CONNECTIONS

The coupler design requires sufficient free space around the secondary signal connections made to the two inserts at the bottom of coupler. For this reason, the secondary terminals are located to one side of a 3/8” deep recess to allow easier connection to the instrumentation using standard 50-Ohm coaxial cable terminated with crimped-on ring terminals. The signal conductor is terminated by red ring terminal and the shield by blue ring terminal. A standard lengthcable (25’) is included with each coupler as well as connecting hardware and tie wraps.

If the sensors are to be installed on a flat solid surface, an opening has to be provided in thesurface to accommodate the secondary cable. It is recommended that a suitable rubber bushingor grommet be used to protect the cable from sharp edges of the opening. As analternative, asuitable recess in the grounded surface, or a suitable mounting bracket can beprovided to allow the access to the secondary connections.

Note: Avoid application of excessive torque or tension to the coaxial cable connections;secure the cable with cable ties.

Page 12: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

10 Smarter Solutions For Today and Tomorrow

6. RECOMMENDED TOOLS AND MATERIALS

Mounting bolts, nuts, washers and drill bits to mount the capacitor base to a grounded metal structure.

High voltage conductor (bare or insulated) for coupler connection to HV Circuits.Minimum conductor size of #4 is recommended. If the installation kit including 15kV cables was additionally ordered it would be included into the shipment.

The aluminum brackets included in the shipment:

Grounding bars (if necessary) – copper bars with cross-section not less than1“x ¼“.

Coaxial cables (included in the shipment): either of the standard 25’ length or inspools of 1000’ with additional payment for the length in excess of the standard 25feet per sensor, according to the Customer order.

7. INSTALLING THE COUPLER

HIGH VOLTAGE CONNECTIONS:

o By direct connection to HV bus bars (if the bus is covered with an insulatingo Sleeve, or a coating, make sure that the bolt has a good electrical contact to

the conductor);o By connection to HV bus or termination with an insulated conductor

(maximum 4’ length, but make it as short as possible);o By connection to HV bus or termination with a bare stranded or solid

conductor or bus bar.

Page 13: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

11 Smarter Solutions For Today and Tomorrow

GROUND CONNECTIONS:

By direct mounting on grounded surface;By mounting of a group of sensors on a single grounding bar anchoredto the metal cabinet surface with an additional ground wire to assuregood ground connection;By mounting of an coupler on a its bracket anchored to the metalcabinet Surface, if necessary- with an additional ground wire to assuregood ground connection.

Always check electrical connections to HV circuits and ground before Energizingafter capacitor installation. Dielectric tests after installation are preferred.

8. DETAILED INSTALLATION INSTRUCTIONS

8.1 PREPARATION OF COAX CABLE

A. Place one piece of heat shrink insulation over the coax wireB. Strip approximately 1 inch (25 mm) of outer insulation from the wireC. De-braid the shield wire and twist tightlyD. Remove about ¼ inch or 6 mm of insulation from the center conductorE. Crimp the Red ring terminal on the exposed central conductorF. Crimp the Blue ring terminal on the twisted shield wireG. Slip the Heat shrink tubing over the connection as tight as possible and heat to hold

in place.H. Mount the capacitor on to the bracket using two 3/8 inch bolts and lock washers

(provided)I. Make sure the shield wire does not ground to the bracket. J. To ensure proper connection, you should measure 1,500 – 3,000 ohms between the

shield and center conductor from the other end of the cable.

Page 14: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

12 Smarter Solutions For Today and Tomorrow

8.2. MOUNTING OF THE CAPACITOR

A. The coupler mounting base, shown here is to be attached to a convenient position within the termination box, generator or bus duct, using two M8 or 3/8 inch or similar bolts. Drill holes as necessary. Before mounting the base, mount the capacitor to the base and secure the green ground wire to the base using the 6-32 screw and nut provided. Ensure all bolts are secured against vibration. Hardware is not provided for installation of the base.

B. Once the capacitor is mounted, determine what length of the high voltage jumper cable you require. Tightly attach the cable to the top of the capacitor using one 3/8 bolt and lock washer (Provided). If it is more convenient for a short connection, copper strips can be used instead of high voltage cable. This strip should be cut to length and drilled appropriately. Ensure that any expected thermal expansion is allowed for in connection lengths.

Page 15: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

13 Smarter Solutions For Today and Tomorrow

8.3. INSTALLATION USING INSULATING BOOT

In place of tape, Dynamic Ratings provides insulating boots that go over the connection. This is suitable more most applications for motors and switchgear. If the temperature is going to exceed 90o C then taping is recommended. Slip the boot over the high voltage cable and the top of the capacitor. Fasten the boot closes with plastic screws or tie wraps.

Completed Capacitor

Page 16: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

14 Smarter Solutions For Today and Tomorrow

8.4 TAPING THE CONNECTION INSTEAD OF USING THE BOOT.

C. To insulate the cable connection, the following instructions should be followed. In some rare situations it may not be required to insulate the HV connection, but this should only be decided after a full study by an engineer for each situation.

For example, situations where insulation is required include:

The coupler is not well clear of other potentials (inc. earth) and there is not full HV clearance at the top,The coupler top is not absolutely assured that there is no risk of other conductors approaching (inc during a fault).The HV system is insulated in the vicinity of the coupler installation, such as inside a machine, or has insulated bus bars.If there is any policy or preference to insulate HV in the intended mounting position.If there is any vibration risk that the coupler connection may loosen, which the insulation will secure.

D. Smooth the connection point using putty tape (Rotunda 2571), Stretch the tape to 50% elongation and apply under tension pressing down firmly around the bolt/lug.

Rotunda 2571

E. Insulate the connection using 4 half-lapped layers of PIB tape (Rotunda 2501). Stretch the tape to at least 2/3 of its original width. Tapes should cover the top AND the first 19 mm (3/4”) from the top of the Coupler.

Page 17: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

15 Smarter Solutions For Today and Tomorrow

PIB tape application

F. Cover the PIB tapes with two layers of silicone tape. (All layers should half-overlap)

Silicone tape application

Page 18: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

16 Smarter Solutions For Today and Tomorrow

G. Two layers of fiberglass tape should be applied if tape insulated part is to be coated withair-drying varnish (for example, Synthite AC-43, manufactured by John C. Dolph company)

Fiberglass tape application

Page 19: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

17 Smarter Solutions For Today and Tomorrow

9. COUPLERS ON HYDRO-GENERATORS

The easiest way is to connect coupler to the ring bus of the generator. For larger generators two sets of coupler is recommended for better coverage. Each set willservice a half of winding. Coupler should be connected to the ring bus close to the leadsof opposite parallels.

10. COUPLERS ON LARGE GENERATORS

On large generators coupler installation will highly depend on the design of the output leadchamber and the adjacent bus sections. The best way is to install coupler sensors in the leadbushing chamber. If it is not possible, coupler could be installed in the beginning of the adjacentbus section. Additional sets could be installed in the bus duct for noise rejection and busmonitoring purpose.

11. COUPLER CONNECTIONS IN BUS DUCTS

Two sets of three coupler devices each should be installed at both ends of a bus duct for PDdetection. The two sets are necessary for accurate identification of PD site location along a busutilizing a time-of-arrival method.

12. COUPLER CONNECTION IN TRANSFORMERS

Three coupler, one per phase, are typically required at the medium voltage side of a transformer.If the connection is a bus duct, one set of coupler can serve for detection of PD in both thetransformer and the bus duct.

Page 20: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

Dynamic Ratings, Inc www.dynamicratings.com Electrical Diagnostic Innovations www.elec-di.com 7308 Aspen Lane N #137 +1 612-963-0974 Brooklyn Park, MN 55428

APPENDIX A

For proper installation of the PD system, the coaxial cables running from the couplers to the termination box have to be placed inside a conduit. Check the local regulations for the conduit material to be used.

During the machine operation, there is very strong electrical field present in the vicinity of the isophase bus. Since the conduit is always installed close to isophase bus it is highly important that conduit is laid out in such a way to prevent circulating currents from occurring.

In order for PD system to be properly installed, termination box and conduit itself have to be grounded. This has to be done on one and only one place preferably close to the termination box itself. Make sure that coaxial cables conduit is insulated from any other conducting surface (i.e. conduit support holders, I beams, bus duct enclosure, etc.). A rubber hose or few layers of insulation tape can be used to insulate conduit from conduit holders. To insulate conduit from bus duct enclosure, short runs of plastic conduit or plastic bushings can be used.

Page 21: EPOXY MICA COUPLING CAPACITOR Installation Manual · Electrical Diagnostic Innovations  ... 8.1 Preparation of Coax Cable ... Voltage Endurance Test

19 Experts in Diagnostic Monitoring Technologies

APPENDIX B - SAMPLE INSTALLTION PICTURES