equipment inspection report

14
EQUIPMENT INSPECTION REPORT (4) CATERPILLAR GENSETS FOR TOKYO TRADING CORPORATION 3400 TOWN POINT DRIVE SUITE 140 KENNESAW GA 30144 UNITED STATES EFFECTIVE DATE: 4/7/2011 April 6, 2011 RIZWAN SATTAR EMAIL: [email protected] Re: Equipment Inspection Report – (4) Caterpillar Gensets Dear Mr. Sattar In accordance with your recent request, The asset listing provided to us, prior to the inspection, included (4) 2007Caterpillar diesel powered gensets Model 3516B Prime 1825ekW (2281 kVA)gensets. They werespec’d with elevating transformers, 4 battery start system and capable of generating 1825ekW(2281 kVA) of electricity. Commonly, these are referred to as 2 meg machines. Upon inspection, Thomas Industries found instead (4) 2007 Caterpillar diesel powered gensets Model C32, spec’d to produce only 910 ekW of power. Additionally, the gensets had a standard Caterpillar electrical package, not the elaborate package described on the provided asset list. They were all spec’d identically. Diesel powered Caterpillar Model C32 ACERT 910 ekW 1372 HP (1023.0kw) Twin Turbos Dual battery start system Full radiator system Generator Model SR4B-CD 60 Hertz, 480 volt, 3 phase, 1137kva (910kw) Full multi door access steel engine house

Upload: kashif-iqbal

Post on 02-Dec-2014

76 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Equipment Inspection Report

EQUIPMENT INSPECTION REPORT(4) CATERPILLAR GENSETS

FORTOKYO TRADING CORPORATION3400 TOWN POINT DRIVE SUITE 140KENNESAW GA 30144 UNITED STATES

EFFECTIVE DATE: 4/7/2011April 6, 2011RIZWAN SATTAR EMAIL: [email protected]

Re: Equipment Inspection Report – (4) Caterpillar GensetsDear Mr. Sattar In accordance with your recent request, The asset listing provided to us, prior to the inspection, included (4) 2007Caterpillar diesel powered gensets Model 3516B Prime 1825ekW (2281 kVA)gensets. They werespec’d with elevating transformers, 4 battery start system and capable of generating 1825ekW(2281 kVA) of electricity. Commonly, these are referred to as 2 meg machines. Upon inspection, Thomas Industries found instead (4) 2007 Caterpillar diesel powered gensets Model C32, spec’d to produce only 910 ekW of power. Additionally, the gensets had a standard Caterpillar electrical package, not the elaborate package described on the provided asset list.

They were all spec’d identically.Diesel poweredCaterpillar Model C32 ACERT910 ekW1372 HP (1023.0kw)Twin TurbosDual battery start systemFull radiator systemGenerator Model SR4B-CD60 Hertz, 480 volt, 3 phase, 1137kva (910kw)Full multi door access steel engine houseAll of the gensets were in the same condition and all are sitting on steel frames. The frames are180” x 72”. The house dimensions are 260”L x 104” W x 106”H. Due to the width, the units will need to travel under wide/oversize permits. Thomas Industries was unable to verify hours as no ignition key was produced nor was battery/electric condition available. All units have the air filters, air intake elbows and fittings, brackets and spring loaded shock absorbing mounting blocks dismantled and in the engine houses.

Equipment Inspection Report - (4) Caterpillar Gensets

Page 2: Equipment Inspection Report

EQUIPMENT SPECIFICATIONS1 CATERPILLAR C32(910KW)SYC01307 G5C00920 CAT00C32ASXC01446 2083 (2007) 910 KW (1137KVA)SKID-RAIL MOUNTEDDIESEL POWEREDGENERATOR SET, 1372HPDIESEL ENGINE (C32ACERT), FULL RADIATOR,TWIN TURBOS, DUALBATTERY SYSTEM, 3PHASE, 480 VOLTS, 60HERTZ, GENERATORMODEL SR4B-CD

2 CATERPILLAR C32(910KW)SYC01294 G5C00921 CAT00C32LSXC01447 2071 (2007) 910 KW (1137KVA)SKID-RAIL MOUNTEDDIESEL POWEREDGENERATOR SET, 1372HPDIESEL ENGINE (C32ACERT), FULL RADIATOR,TWIN TURBOS, DUALBATTERY SYSTEM, 3PHASE, 480 VOLTS, 60HERTZ, GENERATORMODEL SR4B-CD

3 CATERPILLAR C32(910KW)SYC01292 G5C00912 CAT00C32TSXC01440 2082 (2007) 910 KW (1137KVA)SKID-RAIL MOUNTEDDIESEL POWEREDGENERATOR SET, 1372HPDIESEL ENGINE (C32ACERT), FULL RADIATOR,TWIN TURBOS, DUALBATTERY SYSTEM, 3PHASE, 480 VOLTS, 60HERTZ, GENERATORMODEL SR4B-CD, STEELMULTI DOOR ACCESSENGINE HOUSE (260"L x104"W x 106"H)

Page 3: Equipment Inspection Report

4 CATERPILLAR C32(910KW)STC01293 G5C00922 CAT00C32HSXC01448 2037 (2007) 910 KW (1137KVA)SKID-RAIL MOUNTEDDIESEL POWEREDGENERATOR SET, 1372HPDIESEL ENGINE (C32ACERT), FULL RADIATOR,TWIN TURBOS, DUALBATTERY SYSTEM, 3PHASE, 480 VOLTS, 60HERTZ, GENERATORMODEL SR4B-CD, STEELMULTI DOOR ACCESSENGINE HOUSE (260"L x104"W x 106"H)

Page 4: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar Gensets

EQUIPMENT PHOTOGRAPHS

Page 5: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar GensetsEQUIPMENT PHOTOGRAPHS

Page 6: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar GensetsEQUIPMENT PHOTOGRAPHS

Page 7: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar GensetsEQUIPMENT PHOTOGRAPHS

Page 8: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar Gensets

EQUIPMENT PHOTOGRAPHS

Page 9: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar Gensets

EQUIPMENT PHOTOGRAPHS

Page 10: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar GensetsEQUIPMENT PHOTOGRAPHS

Page 11: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar GensetsEQUIPMENT PHOTOGRAPHS

Page 12: Equipment Inspection Report

Equipment Inspection Report - (4) Caterpillar GensetsEQUIPMENT PHOTOGRAPHS