Series LFTP300 Trap Primer  Size: 1  ⁄ 2"  The Series LFTP300 operates by sensing the pressure drop in the supply line from downstream fixtures or appliances. The pres- sure reduction above the Valve Disc (2) causes the disk to move upward opening the Lower Disc Seal (4) and closing off the Upper Disc Seal (1). With the Lower Disc Seal (4) open the stored air pressure in the Air Chamber (5) pushes a portion of the contained volume of water from the lower chamber out through the opening beneath the Lower Disc Seal (4) to prime the trap. When there is no longer a demand in the supply line and the full line pressure is restored, the Valve Disc (2) lowers, opening the Upper Disc Seal, allowing flow through the One Way Seal (3), seating the Lower Disc Seal (4) and recharging the Air Chamber (5) for the next pressure drop cycle. The Series LFTP300 incorporates a built in vacuum breaker (6) which does not satisfy compliance to ASME  A112.1.2. The Series LFTP300 featur es Lead Free* construction to comply with Lead Free* installation requirement s.  This Engineering Sheet is not intended to replace the produ ct installation and safety information available or the experience of a trained product insta ller. Please refer to the produc t installation instructions for further information. Models • LFTP300T - Threaded Inlet and Outlet Connect • LFTP300S - Solder Inlet and Threaded Outlet Connect Features • Built in Vacuum Breaker Ports (6) Specifications  A trap primer shall be installed in plumbing systems to prevent floor drain traps from losing their water seal by evaporation. Maintaining the water seal will prevent the backflow of sewer gas into the buildings or rooms where the traps are installed. Trap primers are specified in various plumbing codes such as IAPMO, Southern Standard Building Code, National Standard Plumbing Code and many state and local plumbing codes in U.S.A. and Canada. The device shall meet the requirements of ASSE Standard 1018. Lead Free* Trap Primer Series LFTP300 shall be constructed using Lead Free* materials. Lead Free Trap Primers shall comply with state codes and standards, where applicable, requiring reduced lead content. Watts Series LFTP300T (threaded), or LFTP300S (solder).  For Residential and Comme rcial Applications ES-LFTP300 Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location ––––––––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––– Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––  Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative –––––––––––––––––––––––––––––––––––––––– Model LFTP300T Model LFTP300S Upper Disc Seal (1) Supply Valve Disc (2) One Way Seal (3) Lower Disc Seal (4) Air Chamber (5) To Trap LEAD FREE NOTICE Inquire with governing authorities for local installation requirements. *The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight. Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with- out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold. Vacuum Breaker Ports (6)

Upload: watts

Post on 14-Apr-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ES-LFTP300

7/27/2019 ES-LFTP300

http://slidepdf.com/reader/full/es-lftp300 1/2

Series LFTP300Trap Primer 

Size: 1 ⁄ 2" The Series LFTP300 operates by sensing the pressure drop inthe supply line from downstream fixtures or appliances. The pres-sure reduction above the Valve Disc (2) causes the disk to moveupward opening the Lower Disc Seal (4) and closing off the UpperDisc Seal (1). With the Lower Disc Seal (4) open the stored airpressure in the Air Chamber (5) pushes a portion of the containedvolume of water from the lower chamber out through the openingbeneath the Lower Disc Seal (4) to prime the trap. When there isno longer a demand in the supply line and the full line pressure isrestored, the Valve Disc (2) lowers, opening the Upper Disc Seal,allowing flow through the One Way Seal (3), seating the LowerDisc Seal (4) and recharging the Air Chamber (5) for the nextpressure drop cycle. The Series LFTP300 incorporates a built invacuum breaker (6) which does not satisfy compliance to ASME

 A112.1.2. The Series LFTP300 features Lead Free* construction tocomply with Lead Free* installation requirements.

 This Engineering Sheet is not intended to replace the productinstallation and safety information available or the experience of atrained product installer. Please refer to the product installation

instructions for further information.

Models• LFTP300T - Threaded Inlet and Outlet Connect

• LFTP300S - Solder Inlet and Threaded Outlet Connect

Features• Built in Vacuum Breaker Ports (6)

Specifications A trap primer shall be installed in plumbing systems to preventfloor drain traps from losing their water seal by evaporation.Maintaining the water seal will prevent the backflow of sewer gasinto the buildings or rooms where the traps are installed. Trapprimers are specified in various plumbing codes such as IAPMO,Southern Standard Building Code, National Standard PlumbingCode and many state and local plumbing codes in U.S.A.and Canada. The device shall meet the requirements of ASSEStandard 1018. Lead Free* Trap Primer Series LFTP300 shall beconstructed using Lead Free* materials. Lead Free Trap Primersshall comply with state codes and standards, where applicable,requiring reduced lead content. Watts Series LFTP300T (threaded), or LFTP300S (solder).

 For Residential and Commercial Applications

ES-LFTP300

Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location ––––––––––––––––––––––––––––––––––––––––– Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

 Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––

Model LFTP300T Model LFTP300S

Upper Disc Seal (1)

Supply

Valve Disc (2)

One Way Seal (3)

Lower Disc Seal (4)

Air Chamber (5)

To Trap

LEAD FREE*

NOTICE 

Inquire with governing authorities for local installation requirements. *The wetted surface of this product contacted by consumablewater contains less than 0.25% of lead by weight.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,

please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-

out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Vacuum BreakerPorts (6)

Page 2: ES-LFTP300

7/27/2019 ES-LFTP300

http://slidepdf.com/reader/full/es-lftp300 2/2

StandardsMaterialsLead Free Adapter

Brass Body

EPDM Seals

PressureMaximum supply pressure: 125psi.Minimum supply pressure must exceed 25psi.

Operating Requirements Activates with a 10psig pressure drop between 25-125psi. Mustbe installed on a cold water line serving a frequently used fixture.For proper trap priming, minimum flows must exceed those statedin the flow chart.

Dimensions – Weights

1 1/4[32 mm]

 

4 5/16[110 mm]

 

B

A

Model LFTP300T Model LFTP300S

Flow ChartInLeT PreSSUre 25 50 75 100 125

*gPM 1.1 1.6 2.0 2.3 2.4

*LPM 4.2 6.1 7.6 8.7 9.1

*Minimum cold flow required for proper trap priming.

  1 1/4[32 mm]

  4 1/4[107 mm]

 

A

B

MODeL SIze DIMenSIOnS WeIghT

 A B

in. in. mm in. mm lbs. kgs.

LFTP300T 1  ⁄  2 45  ⁄  16 110 11  ⁄  4 32 .97 .44

LFTP300S 1  ⁄  2 41  ⁄  4 107 11  ⁄  4 32 .92 .42

ES-LFTP300 1339 © 2013 Watts

USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca

 A Watts Water Technologies Company 

1018

 Tested and approved in conformance with Standard1018 of the American Society of Sanitary Engineers.Listed by IAPMO.

B125.3