essentia project artica platform no frost 60 cm...

57
0 Essentia Project Artica Platform No Frost 60 cm Appliances 2011 Event Ca’Maiano, May 2011 Presenter Piotr Kelm Francesco Nieli

Upload: doantu

Post on 22-Jul-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

0

Essentia Project

Artica Platform

No Frost 60 cm Appliances

2011

EventCa’Maiano, May 2011

Presenter

Piotr Kelm

Francesco Nieli

Legend and User Interface

Legend

MID Indesit Interface(SQG_CL_29)

MID H/A Interface(SQG_CL_30)

Entry Interface (SQG_CL_28)

THR3 Interface (SQG_CL_32)

2

Functions

3

“ECO” or “I Care” Function:An optimal temperature for food storage can be set which also

gives energy savings.

When this function is selected the appliance will cycle in order to

achieve this reduced energy consumption.

“ICE PARTY” function:

Used, for example, for rapidly chilling a bottle of wine.

To prevent the bottle freezing and breaking, two signals (one

acoustic, one visual) will remind you that a bottle has been

placed in the freezer and that the optimal temperature has been

reached.

Functions

“HOLIDAY” function:

Manages the refrigerator and freezer compartments separately.

The freezer continues to operate normally while the fridge

operates at a temperature of around “+12°C” which means the

fridge door can be kept closed, preventing the formation of

unpleasant odours whilst reducing energy consumption.

4

SUPER COOL Function:

Rapidly chills food placed in the fridge without exposing food

already stored to thermal excursion.

When this function is selected, the refrigerator starts a special

procedure that delivers cooling to the fridge compartment,

lowering the temperature to around “+2°C”.

SUPER FREEZE function:

Freezes food rapidly, enabling longer storage.

There are two options:

24 hours: in this case the symbol remains steadily lit; 48 hours:

in this case the symbol flashes for the first 24 hours and

changes to steadily lit for the last 24 hours.

In the first case, the appliance may end the function on

completion of the 24 hours.

Functions

5

Functioning logic

Artica FULL & Artica Entry – No Frost Appliances

6

Artica FULL – No Frost Appliance

I2C

connection

Artica Entry – No Frost Appliance

Artica FULL & Artica Entry - “Normal” Functioning

7

Description• This function is active when no other function is activated from the

user interface.

• The fridge air probe determines when to start and stop chilling the

fridge compartment, based on the temperature setting made by the

user with the user interface.

When the fridge compartment needs to be cooled, the compressor

is activated, the fan switched on and the damper opened.

• The freezer air probe determines when to start and stop chilling the

freezer compartment, based on the temperature setting made with

the control panel.

When the freezer compartment needs to be cooled, the

compressor is activated and the fan switched on. The damper

remains closed.

• When the fridge door is opened during a cooling demand from the

fridge compartment, the damper is closed and the freezer fan is

switched off if there is no cooling demand from the freezer. When

the fridge door is closed, the damper is re-opened and the fan is

switched back on again.

• In the event of a black-out, when the power supply is restored,

normal appliance functioning is also restored.

Artica FULL & Artica Entry - “ECO” Function

8

Description• The function is activated and disabled by pressing the relative

button or turning both knobs to the corresponding symbol on theuser interface.

• When the “ECO” function is active, the temperatures of +5°C inthe fridge compartment and -18°C in the freezer compartment areautomatically set.

• The fridge air probe determines when to start and stop chillingthe fridge compartment based on the temperature setting on thedisplay board.

• When the fridge compartment needs to be cooled, thecompressor is activated, the fan switched on and the damperopened.

• At the end of every cooling demand from the fridge compartment,the freezer compartment is always cooled by closure of thedamper with the freezer fan running for a fixed time, which canvary depending on the setting File, from a minimum of 5min to amaximum of 33min.

• The freezer air probe determines when to start and stop chillingthe freezer compartment based on the temperature readings.

• When the freezer compartment needs to be cooled, thecompressor is activated and the freezer fan switched on

• In the event of a black-out, when the power supply is restored,appliance functioning in ECO mode is also restored.

Artica FULL & Artica Entry - “Holiday” function

9

Description• The function is activated and disabled by pressing the

button on the user interface or turning the knob to the

corresponding symbol.

• The fridge air probe determines when to start and stop

chilling the fridge compartment at warmer temperatures

than for normal function (+12°C).

• The freezer air probe determines when to start and stop

chilling the freezer compartment with the temperature

threshold set at -18°C.

• In the event of a black-out, when the power supply is

restored, this function is also restored.

Artica FULL & Artica Entry - “Super Cool” function

10

Description• The function is activated by pressing the relative button and can

be exited manually by pressing the button again or automatically:

after a maximum set timeout of 12 hours.

after three compressor ON cycles at a steady set

temperature of +2°C.

• The fridge air probe determines when to start and stop chilling

the fridge compartment at lower temperatures than for normal

function (+2°C).

• The freezer air probe determines when to start and stop chilling

the freezer compartment based on the temperature setting made

by the user.

• At the end of the function, the appliance returns to normal

functioning.

• In the event of a black-out, when the power supply is restored,

this function is also restored.

Artica FULL & Artica Entry - “Super Freeze 24h” function

11

Description• The function is activated by pressing the relative button on the control

panel and can be disabled: manually by pressing the button again or

automatically after 24 hours max.

• When the function is activated, the appliance runs a defrost cycle

if and only if the appliance has accumulated at least 3 hours of

compressor ON since the last defrost cycle performed.

• The fridge air probe determines when to start and stop chilling the

fridge compartment, based on the temperature setting made by the

user.

• The freezer compartment is cooled continuously for 24 hours

• In the event of a black-out, when the power supply is restored, th

Super Freeze function is also restored.

Important:

Super Freeze 48 hours is not available. The appliance will complete

the function automatically based on time and NEVER due to

reaching a set temperature as was the case with previous platforms.

Artica FULL & Artica Entry - “Ice Party” function

12

Description• The function is activated by pressing the relative button

on the user interface and can be disabled manually by

pressing the button again or automatically after 30

minutes.

• The fridge air probe determines when to start and stop

chilling the fridge compartment, based on the

temperature setting made using the control panel.

• The freezer compartment chills continuously (compressor

ON) for 30 minutes, activating the compressor and the

freezer fan. After this time, an acoustic signal sounds to

remind the user to remove the bottle.

• In the event of a black-out, when the power supply is

restored, the alarm is activated, prompting removal of the

bottle.

Artica FULL & Artica Entry - “A1” alarm

13

Description• The “A1” alarm is only displayed if there is no Pre-Fault or Fault.

• The alarm is activated when the temperature measured by the freezer air probe is such

that food might be damaged. In this case, it is advisable to use food immediately or cook

it and then refreeze it.

• When an alarm condition occurs, it is indicated on the user interface with the message

“A1” or the simultaneous flashing of the “Super Cool” & “Super Freeze” LEDs, in

addition to an acoustic signal.

The buzzer can be muted by opening and closing the refrigerator door.

• The alarm can be reset by switching the appliance off using the control panel.

• Fridge compartment function remains the same as during normal functioning.

• The freezer compartment functions at temperatures that will not refreeze the food stored

inside (0°C).

• Defrost cycles are forced every 2 hours.

NB: The thresholds are the same as the Cooling 2005/2008 platform.

Always avoid unplugging the appliance: switch off using the U.I.

T1 = 2 1/2 Hours

T2 = 24 Hours

T3 = 120 Hours

A2 threshold

A1 threshold

Check threshold

Artica FULL & Artica Entry - “A2” alarm

14

Description• The “A2” alarm is only displayed if there is no Pre-Fault or Fault.

• The alarm is activated when the temperature measured by the freezer air probe is so

high or has remained above the safety threshold for so long that all the food stored in the

freezer compartment needs to be thrown away.

• The alarm condition is indicated on the user interface with the message “A2” or the

simultaneous flashing of the “Super Cool”, “Power Supply” and “Super Freeze”

LEDs, in addition to an acoustic signal.

• The buzzer can be muted by opening and closing the refrigerator door.

• To reset the alarm, switch the appliance off.

• Fridge compartment function remains the same as during normal functioning.

• The freezer compartment attempts to reach a temperature of “­12°C” in order to avoid

unpleasant odours inside the freezer compartment.

• Defrost cycles are forced every 2 hours.

NB: The thresholds are the same as the Cooling 2005/2008 platform.

Always avoid unplugging the appliance: switch off using the U.I.

T1 = 2 1/2 Hours

T2 = 24 Hours

T3 = 120 Hours

A2 threshold

A1 threshold

Check threshold

Artica FULL & Artica Entry - Defrost cycle

15

Start of the defrost cycle is dependent on:• Duration of last defrost

• Time of fridge door opening (every 5 cumulative minutes of door open time

reduces the start of the next defrost cycle by one hour)

• Compressor ON time (10 / 12 hours)

• Actual time between 2 defrost cycles (minimum 10 hours / maximum 48 hours)

Defrost cycles activated by particular circumstances• In the event of Alarms “A1” and “A2”, a defrost cycle is carried out every 2 hours.

• If the Door Open Alarm remains active for more than 30 minutes, a defrost cycle will be

performed every 2 hours until the door is closed (Alarm Reset)

• In the event of activation of the Super Freeze Function, if at least 3 cumulative hours of

Compressor ON have passed since the last defrost cycle.

• If the Fridge Air Probe registers a value above +14.5°C for 30 consecutive minutes (this

function is not available when the Holiday Function is active).

ON

OFF(A)

(B)

(C) (E)

(D)

Heating elementsFreezer fan Damper

Compressor

Artica FULL & Artica Entry - Defrost cycle

16

Description• (A) - All loads are disabled and the defrost heating elements are switched on.

• (B) - The heating elements switch off when the freezer evaporator probe reaches +17°C

or after 50 minutes (Defrost Time Out).

• (C) - As soon as the heating elements switch off, the freezer fan activates for 5 seconds in

order to deliver warm air to the cold air inlet pipe from the freezer compartment into the

fridge compartment. Everything else remains switched off during this time.

• (D) - All the loads remain disabled for around 12 minutes to allow the water to flow into the

compressor drawer.

• (E) - The compressor is switched on to cool the evaporator that was heated up during

defrosting until a temperature of -18°C is reached.

ON

OFF(A)

(B)

(C) (E)

(D)

Heating elementsFreezer fan Damper

Compressor

Artica FULL & Artica Entry - Compatibility of Functions

17

SET FUNCTION

FUNCTION TO BE SET

|

ECO / I CARE SUPER FREEZE SUPER COOL HOLIDAYICE PARTY / BOTTLE

CHILL

ECO / I CARE -

ECO / I CARE can be

activated but will start on

completion of SUPER

FREEZE

ECO / I CARE can be

activated but will start on

completion of SUPER

COOL

Disables Holiday

ECO / I CARE can be

activated but will start on

completion of ICE PARTY

/ BOTTLE CHILL

SUPER FREEZESF takes precedence. At

the end, ECO is restored.- OK CANNOT BE SET

SF can be activated but

will start on completion of

ICE PARTY / BOTTLE

CHILL

SUPER COOLSC takes precedence. At

the end, ECO is restored.OK - CANNOT BE SET

SC can be activated but

will start on completion of

ICE PARTY / BOTTLE

CHILL

HOLIDAY Disables ECO / I CARE

HOLIDAY can be activated

but will start on

completion of SF

HOLIDAY can be activated

but will start on

completion of SC

-

HOLIDAY takes

precedence and ends ICE

PARTY / BOTTLE CHILL

(indicated on the

display/acoustic signal)

ICE PARTY / BOTTLE

CHILL

At the end, ECO is

restored.OK OK CANNOT BE SET -

CHANGE TEMP. Disables ECOOK (only Fridge Temp. can

be changed)

OK (only Freezer Temp.

can be changed)Disables Holiday OK

THR3

18

THR3 NF – No Frost Appliance(Electronic thermostat)

THR3 – “Normal” Functioning

19

Description• The fridge damper is mechanical.

• The freezer air probe determines when the compressor comes on and off in order to

stop chilling the freezer compartment depending on the setting of the knob on the

control panel.

Fridge door:• Management of fridge door alarm when it is left open for more than 2 minutes

• The alarm is signalled visually by the flashing fridge light.

• The alarm is reset when the door is closed.

• Once the door has been open for 30 minutes, a defrost cycle is activated every 2

hours.

THR3 - Defrost cycle

20

Start of the defrost cycle depends on:• Duration of last defrost

• Time of fridge door opening (every 5 cumulative minutes reduces the start of

the next defrost cycle by one hour)

• Total compressor ON time since last defrost (10 / 12 hours)

• Actual time between 2 defrost cycles (minimum 10 hours – maximum 48

hours)

On

Off

(A)

(B)

(E)

(D)

(F)

Heating elementsFreezer fan

Compressor

(G)(C)

THR3 - Defrost cycle

21

Defrost Cycle:• (A) - Start of defrost, the fan runs for 4 minutes

• (B) - All the loads are disabled

• (C) - The defrost heating element switches on.

• (D) - The heating element switches off when the freezer evaporator probe

reaches the preset value of 17°C or the maximum set time of 70 minutes has

elapsed.

• (E) - When the heating element switches off the fan runs for 20 seconds.

• (F) - All the loads remain disabled for around 10 minutes to allow the water to flow

into the compressor drawer.

• (G) - The compressor is switched on to cool the coil that has heated up during

defrosting until a temperature of -18°C is reached.

On

Off

(A)

(B)

(E)

(D)

(F)

Heating elementsFreezer fan

Compressor

(G)(C)

22

Components

23

Components

Temperature Probes:The “NTC” Temperature Probes have

the same settings used in the Cooling platform

2005/2008. There are 3:

1. Refrigerator air probe: Which measures

the temperature inside the refrigerator

compartment and relays to the main board

any cooling demand and/or the fact that the

thermostat temperature has been reached.

2. Freezer air probe: Which measures the

temperature inside the freezer compartment

and relays to the main board any cooling

demand and/or the fact that the thermostat

temperature has been reached.

3. Evaporator probe: manages the end of the

defrost cycle by detecting when the set

temperature of +17°C is reached.

IMPORTANT:

The ohm values for checking that the probes are in good working order are the same

used until now since the probes remain unchanged.

1

3

2

24

Temperature Probes:As in Platform 2005/2008, in the event of

malfunction (short circuit or open circuit) of one

or more probes, the appliance will start cycling,

using internal compressor ON/OFF tables

based on the choices made by the user with the

user interface.

IMPORTANT:

The ohm values for checking that the probes are in good working order are the same

used until now since the probes remain unchanged.

Temperatures

(degrees C)

Impedance

(Ohms)

Components

25

Heating elements:Defrosting is performed by the defrost heating

elements. One element covers both sides of the

freezer evaporator with an extension designed to

avoid use of the foam-protected drip tray heating

element used on the previous platform, and a

second element surrounds the foam-protected

air return pipeline.

The evaporator heating element used in three-

drawer appliances and that used in four-drawer

appliances differ in length, nonetheless they

have the same reference value for checking

correct operation (see table below).

Electrical characteristics:• Operating voltage.: 220 - 240 Volts

• Impedance……….: approx. 302.5 Ohm

• At 220 Volts, it has a power rating of: approx. 160 Watts

• At 240 Volts, it has a power rating of: approx. 190 Watts

Components

26

LED indicators:There are 2 connected in series, so

when one LED is damaged, the other

will not switch on and, as a result, both

will need to be replaced. In the event

of malfunction, they must both be

replaced (they cannot be tested

using a multimeter)

Thermal fuse:

Two thermal fuses (one for each

phase of impedance) provide

additional protection during automatic

defrosting.

N.B.: Opens when a temperature of

72°C is reached (Cannot be reset)

Components

27

Freezer Fan (radial type):The radial fan has the capacity to extract

cooled air from the front (green arrow) and to

direct it radially, therefore 90° with respect to

the motor arrangement.

The freezer fan switches on along with the

compressor every time there is a cooling

demand from the fridge or freezer

compartment, circulating warmer air in order to

cool it through contact with the evaporator coil.

It is located at the top of the freezer

compartment and operates at one speed only.

It runs on 12V constant voltage.

The freezer fan starts running as soon as the

compressor switches on.

Components

28

Refrigerator Compartment Multiflow:The fridge multiflow ensures correct air distribution

throughout the fridge compartment by means of

variable diameter vent outlets.

Depending on the height of the fridge

compartment, there are various levels of

cooling:

• height 1750mm: - Electronic 3 levels

- Mechanical 2 levels

• height 1875mm: - Electronic 4 levels

- Mechanical 3 levels

• height 2000mm: - Electronic 5 levels

- Mechanical 4 levels

Cold air exiting

Warm air returning

Components

29

Freezer air outlet vents

Freezer air outlet vents

Freezer multiflow

Air return vents

Cold air exiting

Warm air returning

Freezer Compartment Multiflow:

The freezer multiflow also has the task

of distributing air, in this case

throughout the freezer compartment.

There are different versions of

freezer multiflows:

• 3-drawer electronic appliances:

2 open levels (4 open vents)

• 3-drawer mechanical appliances:

3 open levels (6 open vents)

• 4-drawer electronic and mechanical

appliances: 4 open levels (8 open

vents)

In all cases there are two vents at the

bottom for drawing in air and

channeling it to the evaporator coil.

Components

30

External Air Flow (Fridge Compartment Cooling):Cold air is forced by the radial fan through the smallest

channel (blue arrow) passing through the damper, and is

distributed through the fridge compartment by the multiflow.

Fridge inlet duct

Fridge return duct

Warm air is forced out of the fridge compartment through the longer channel to

the bottom of the freezer compartment, where it comes into contact with the

evaporator coil and is cooled once again.

Components

31

Fridge inlet duct

Fridge return duct

Evaporator coil

Freezer multiflow

Fan unit

Components

32

Stepper DamperAlthough the damper is of the stepper type,

it is used like a standard On/Off damper;

fully closed or fully open (90°).

It runs on 12V constant voltage and opens

to let air cooled by the freezer evaporator

pass; this air is then forced back into the

fridge compartment by the freezer cooling

fan each time there is a cooling demand

from the fridge compartment.

Important: The damper is managed

with a single replacement part (KIT)

together with the polystyrene of the

fridge multiflow NOT TO BE

DISMANTLED !!!

The damper opens and closes immediately upon a cooling demand from the fridge

compartment. The only exception is if the ECO (I CARE) function is selected and the

appliance has a Full or Entry board: in this case the damper opens after approx. 35

seconds. Closure, on the other hand, is immediate.

Components

33

Evaporator Cover in PolystyreneThe polystyrene cover is designed to channel /

force air through the evaporator structure in

order to guarantee cooling of air.

It is also very important during defrosting for

insulating warm air in the evaporator area.

It also secures the drip tray in place.

IMPORTANT:1.NEVER pull the polystyrene cover if there is

ice attached AS IT MAY BREAK

2.If the polystyrene cover is removed, always

ensure it is fitted properly back in place

afterwards to guarantee correct appliance

operation

Components

34

Compressor:When the appliance is switched on for the first time, the compressor only starts after

8 minutes.

Between one start-up and the next one there is a minimum safety time of 8 minutes.

Situations in which the compressor remains off even in the presence

of a cooling demand:1. When the electronic protection device is in operation

2. When the electric protection device (Clixon) is activated

3. After the end of defrosting

4. After completion of the "Super Freeze" function

Components

35

Components - VERY IMPORTANT:Electronic Appliances:In these appliances, the damper and the multiflow

polystyrene are managed with a single KIT NOT TO BE

DISMANTLED in order to avoid any leakage of air remaining

after reassembly, which might result in poor appliance

operation.

Electromechanical Appliances:In these appliances, the damper, the multiflow polystyrene,

the damper knob and the plastic cover are managed with a

single KIT NOT TO BE DISMANTLED in order to avoid any

leakage of air remaining after reassembly, which might result in

poor appliance operation.

Components

36

Wiring Diagrams

Entry Wiring Diagram(SQG_CL_310)

THR3 Wiring Diagram(SQG_CL_311)

FULL Wiring Diagram (SQG_CL_312)

Internal Connection

Wiring Diagram

37

Serviceability

Artica FULL – Demo Mode

38

Activating Demo Mode:Start with the appliance off.

To activate the function, press the buttons

“ECO/I CARE” and “HOLIDAY”

simultaneously for 6 seconds. “dE” and

“On” will appear on the display together with

an acoustic signal confirming activation.

Disabling Demo Mode:Switch the product off.

Press the buttons “ECO/I CARE” and

“HOLIDAY” simultaneously for 6 seconds.

“dE” and “OFF” will appear on the display.

N.B.: If the appliance is unplugged or

there is a black-out, the function is

automatically switched off.

Artica FULL - Autotest Procedure

39

Autotest Activation:The function can be activated only with the

appliance turned OFF by pressing the buttons

HOLIDAY, SUPER COOL and SUPER

FREEZE simultaneously for 6 seconds.

Autotest Deactivation:The appliance can exit the autotest procedure

in 3 different ways:

1.After 255 seconds (duration of procedure)

2.By switching on the appliance (using On/Off

button)

3.By unplugging the appliance from the mains

socket

Artica Entry - Autotest Procedure

40

Autotest: activationThe function is activated by turning both knobs to OFF and long-pressing

(for 6 seconds) the Super Freeze button.

Autotest Deactivation:The appliance can exit the autotest procedure in 3 different ways:

1.After 255 seconds (duration of procedure)

2.By switching on the appliance (using the Freezer On/Off knob)

3.By unplugging the appliance from the mains socket

N.B.: The DEMO function is not available in models with this control panel.

Artica FULL & Artica Entry - Autotest Procedure

41

Step Duration Action Light Notes1 5 seconds Pause OFF

2 1 second Probe check OFFIf the probes have not failed, skip to step 3.

If the probes have failed, skip to step 6

3 4 seconds Pause OFF

4 125 secondsFZ fan ON

Heating element ON (*)Damper open

OFF

5 120 secondsFZ fan ON

Heating element ON (*)Damper closed

OFF Skip to step 8

6 125 secondsFZ fan ON

Heating element ON (*)Damper open

Flashing

7 120 secondsFZ fan ON

Heating element ON (*)Damper closed

Flashing

8 Autotest closes

Autotest procedure (Full and Entry board)

(*) Important: Bear in mind that the heating elements are connected in parallel so, in

the event only one of them is interrupted, this Fault will not be detected and the Autotest

procedure will finish without signalling any problems.com

Any Last Fault or Non Critical Fault will be shown on the display for the first 20 seconds

after Autotest activation, after which the cycle starts as follows:

Artica FULL & Artica Entry – Critical and Non-critical Faults

42

Critical Faults:These are faults which prevent the appliance from functioning because they

involve a major functional component, for example: Main board, setting file,

solenoid valve.

They are automatically displayed by the appliance:

Critical faults are displayed ONLY IF THE MAIN BOARD DETECTS A

SIMULTANEOUS TEMPERATURE ALARM (“A1” OR “A2”)

Non-critical Faults:These are faults which, even when present, do not compromise the normal

functioning of the appliance, for example: Fridge fan, multiflow heating element.

THEY ARE NOT AUTOMATICALLY DISPLAYED BY THE APPLIANCE since they

do not pose any hazard or risk compromising appliance operation.

They are displayed for 20 seconds when the autotest procedure is activated.

Artica FULL & Artica Entry – Fault & Last Fault Management

43

Fault :• If CRITICAL, it is automatically displayed and the buzzer sounds. To mute the

buzzer, simply open and shut the fridge door. To RESET THE FAULT, switch the

appliance off at the control panel or unplug it from the mains power supply.

• If NON-CRITICAL, it is displayed only for the first 20 seconds when the Autotest

procedure is started. It is only wiped from the memory once the problem has

been solved and the Autotest procedure re-started and completed.

Last Fault:Displayed for the first 20 seconds when the Autotest procedure is started.

To wipe Last Fault from memory, simply complete the current autotest procedure.

Artica FULL & Artica Entry – Fault & Last Fault Management

44

Important notes.

• Critical Faults are displayed only if an alarm condition is also present at the

same time (“A1” or “A2”).

• In a Pre-Fault condition, functions selected using the user interface are not

activated and the alarms “A1” and “A2” are not displayed until the Fault is

confirmed or rejected.

• Faults take precedence over Alarms “A1” and “A2”

• The “A1” or “A2” alarm is displayed only in the absence of a Pre-Fault or Fault.

• During display of a Critical Fault, all function previously chosen by the user are

cancelled and the freezer compartment starts cycling in an attempt to function at

0°C or -12°C, depending on the alarm condition present along with the Fault.

THR3 - Autotest cycle

45

Autotest Activation:The function is activated by turning the knob on the control panel very quickly from

OFF to maximum then back to OFF

Autotest Deactivation:The appliance can exit the autotest procedure in 3 different ways:

1.After 255 seconds (duration of procedure)

2.By switching on the appliance (using On/Off button)

3.By unplugging the appliance from the mains socket

NB: The DEMO function is not available in models with this control panel.

THR3 - Autotest procedure

46

Autotest sequence for THR3

For 10 seconds, activation of FZ fan, defrost heating element and fridge light.

All loads off for 3 seconds.

Probe check

If one of the two probes has a fault, the fridge light flashes for 5 seconds.

(1 second ON and 1 second OFF)

If everything is OK and there are no probe faults, the fridge light remains ON for 5 seconds.

All loads off for 3 seconds.

Defrost heating element check

If there is a defrost heating element fault, the fridge light flashes for 5 seconds (1 second ON and 1 seconds

OFF).

If everything is OK and there is no probe heating element fault, the fridge light remains ON for 5 seconds.

All loads off for 3 seconds.

Electronic board check

If there is an electronic board fault, the fridge light flashes for 5 seconds (1 second ON and 1 seconds OFF).

If everything is OK and there is no electronic board fault, the fridge light remains ON for 5 seconds.

All loads off for 3 seconds.

Pause for 7 seconds.

FZ air probe check

If there is a fault relating to the FZ air probe, the fridge light flashes for 5 seconds.

(1 second ON and 1 second OFF)

If everything is OK and there is no FZ air probe fault, the fridge light remains ON for 5 seconds.

All loads off for 3 seconds.

FZ evaporator probe check

If there is a fault relating to the FZ evaporator, the fridge light flashes for 5 seconds.

(1 second ON and 1 second OFF)

If everything is OK and there is no FZ evaporator fault, the fridge light remains ON for 5 seconds.

All loads off for 3 seconds.

Activation of FZ fan and defrost heating element for 217 seconds.

47

Demo Mode / Autotest / Autotest Sequence / Fault Table

MID Indesit Interface(SQG_CL_29)

MID H/A Interface(SQG_CL_30)

Entry Interface(SQG_CL_28)

Artica Fault Table(SQG_CL_31)

THR3 Interface(SQG_CL_32)

48

Serviceability

For main board programming in the

ARTICA platform, follow one of the

three methods:

1. Using the handheld/FFA (with

MemWriter)

2. Using a PC (in UK)

3. Using a Smart Reader plus the

Smart Card for the rest of the

world (described in SQG_WM_25)

Whichever method is used, refer to

documentation on the relative

technology

Upgrading

Low-End Adapter(TB001328)

49

Serviceability - New programming connector

In appliances with FULL (HIGH) board:1.Remove the cover from the board of the programming connector

2.Insert the LOW END 2007 adapter with the new wiring (C00275571)

3.Insert the Smart Reader or Hardware Key in the LOW END 2007 adapter

4.Proceed as described at “Programming procedure”

50

In appliances with Entry board:1.Connect the LOW END 2007 adapter (with the new C00275571 wiring) to the

connector located in the compressor area

2.Insert the Smart Reader or Hardware Key in the modified LOW END 2007 adapter

3.Proceed as described at “Programming procedure”

N.B.: THR3 boards are not programmable.

Serviceability - New programming connector

51

Disassembly

52

Assembly and Disassembly

Continue removal of fridge multiflow1. Remove the plugs covering the screws

2. Remove the 6 screws fixing the multiflow

3. Move the multiflow forward slightly and

disconnect the damper connector

4. Pull the multiflow at the front

For the damper:5. Separate the polystyrene from the plastic

cover, taking great care not to break it

NB: The damper must be replaced together with

the polystyrene so that during reassembly no

surfaces are left inadequately sealed, allowing

leakage of air resulting in poor appliance

performance.

53

Disassembly of fridge air

return vent:1.Insert a flat blade screwdriver

in the top aperture of the vent

2.Pull the vent towards you

Disassembly of NTC probe housing:To remove the NTC probe housing, exert pressure at the side and dislodge it

from its seat by pulling it towards you. If this proves unsuccessful, insert a flat

blade screwdriver and prise open the catches to release the housing from its

seat (take care not to scratch the appliance internally or break the housing).

Assembly and Disassembly

54

Disassembly of freezer multiflow1.Remove the freezer compartment drawers

2.Unscrew the 6 fixing screws on the multiflow (some

models feature 8 screws, the additional 2 identified in

the photo with yellow circles)

3.Pull the multiflow gently at the bottom to remove it

4.Open the connectors cover by pressing the fixing

clips

5.Release the 2-wire connector from its seat (which

is that of the freezer fan)

TAKE CARE to disconnect the fan connector

before removing it completely.

2

3

4 5

Assembly and Disassembly

55

Disassembly of freezer evaporator:1.Remove the polystyrene cover by pulling it gently at the

sides (as shown in the photo)

2.Once released from its seat, remove it completely

3.Unscrew the 2 screws fixing the evaporator

Important: NEVER pull the polystyrene cover if there

is ice attached AS IT MAY BREAK

1 2

3

Assembly and Disassembly

56

Disassembly of freezer fan:1.Disassemble the freezer multiflow

2.Using a screwdriver, remove the 5 screws

fixing the freezer fan surround

3.Remove the surround (the fan is fixed to the

surround)

4.Using a screwdriver, remove the 4 screws

fixing the freezer fan to the surround

5.Remove the freezer fan

2

3 4 5

Assembly and Disassembly