evaluation the effect of washing on the heat transfer

12
University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Architectural Engineering -- Faculty Publications Architectural Engineering and Construction, Durham School of 2018 Evaluation e Effect Of Washing On e Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers Mehdi Mehrabi University of Nebraska - Lincoln, [email protected] David Yuill University of Nebraska-Lincoln, [email protected] Follow this and additional works at: hp://digitalcommons.unl.edu/archengfacpub Part of the Architectural Engineering Commons , Construction Engineering Commons , Environmental Design Commons , and the Other Engineering Commons is Article is brought to you for free and open access by the Architectural Engineering and Construction, Durham School of at DigitalCommons@University of Nebraska - Lincoln. It has been accepted for inclusion in Architectural Engineering -- Faculty Publications by an authorized administrator of DigitalCommons@University of Nebraska - Lincoln. Mehrabi, Mehdi and Yuill, David, "Evaluation e Effect Of Washing On e Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers" (2018). Architectural Engineering -- Faculty Publications. 139. hp://digitalcommons.unl.edu/archengfacpub/139

Upload: others

Post on 16-Oct-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Evaluation The Effect Of Washing On The Heat Transfer

University of Nebraska - LincolnDigitalCommons@University of Nebraska - Lincoln

Architectural Engineering -- Faculty Publications Architectural Engineering and Construction,Durham School of

2018

Evaluation The Effect Of Washing On The HeatTransfer Capacity And Air-Side Flow Resistance OfAir Cooled CondensersMehdi MehrabiUniversity of Nebraska - Lincoln, [email protected]

David YuillUniversity of Nebraska-Lincoln, [email protected]

Follow this and additional works at: http://digitalcommons.unl.edu/archengfacpub

Part of the Architectural Engineering Commons, Construction Engineering Commons,Environmental Design Commons, and the Other Engineering Commons

This Article is brought to you for free and open access by the Architectural Engineering and Construction, Durham School of atDigitalCommons@University of Nebraska - Lincoln. It has been accepted for inclusion in Architectural Engineering -- Faculty Publications by anauthorized administrator of DigitalCommons@University of Nebraska - Lincoln.

Mehrabi, Mehdi and Yuill, David, "Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance OfAir Cooled Condensers" (2018). Architectural Engineering -- Faculty Publications. 139.http://digitalcommons.unl.edu/archengfacpub/139

Page 2: Evaluation The Effect Of Washing On The Heat Transfer

Purdue UniversityPurdue e-PubsInternational Refrigeration and Air ConditioningConference School of Mechanical Engineering

2018

Evaluation The Effect Of Washing On The HeatTransfer Capacity And Air-Side Flow Resistance OfAir Cooled CondensersMehdi MehrabiUniversity Of Nebraska-Lincoln, [email protected]

David P. YuillUniversity of Nebraska-Lincoln, [email protected]

Follow this and additional works at: https://docs.lib.purdue.edu/iracc

This document has been made available through Purdue e-Pubs, a service of the Purdue University Libraries. Please contact [email protected] foradditional information.Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/Herrick/Events/orderlit.html

Mehrabi, Mehdi and Yuill, David P., "Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow ResistanceOf Air Cooled Condensers" (2018). International Refrigeration and Air Conditioning Conference. Paper 1884.https://docs.lib.purdue.edu/iracc/1884

Page 3: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 1

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow

Resistance of Air Cooled Condensers

Mehdi Mehrabi1*, David Yuill1

1 University of Nebraska-Lincoln, Architectural Engineering

Omaha, NE, USA

[email protected]

[email protected]

* Corresponding Author

ABSTRACT Air cooled condensers are commonly used in rooftop units and residential air-conditioners to reject heat outdoors.

Airborne particles in the environment, such as dust, grass, leaves, seeds, and anthropogenic agents, can foul the air

side of the condensers. Therefore, it is common practice to regularly clean the air side of condensers. Seven fouled

wavy fin, and two fouled spine fin condensers from residential condensing units were collected at the end of their

service lives, and examined in the laboratory to study the effect of the fouling on heat transfer capacity and air-side

flow resistance. A test apparatus was designed and built to investigate the flow resistance and heat transfer of these

coils before and after cleaning. After testing each condenser in the fouled condition, the fouling material was collected

and its mass was measured. Then, the coil was washed with water and tested again in the test apparatus. Finally, to

investigate the effectiveness of commercial detergents, these coils were cleaned with a detergent and tested again.

Surprisingly, the results show that the effect of washing on the heat transfer capacity of the coil is very small, and in

some cases, the fouled condenser performed better before cleaning than afterward. Similarly, cleaning the coils with

detergent had negligible differences compared with the effects from cleaning with water only, and in some cases, the

detergent caused performance degradation in terms of flow resistance and heat transfer.

1. INTRODUCTION Airside fouling deposition on condensers is widely believed to degrade the performance of air conditioners. There are

a few scientific documentation about the effects of cleaning the fouling of field heat exchangers. Ahn et al. (2003) and

Ahn and Lee (2005) studied the fouling on evaporator and condenser samples of window air conditioners for some

seaside inns. In evaporators, particulate fouling was the dominant agent, and in condensers, corrosion was the

dominant agent because of the presence of chloride in the environment. Lankinen et al. (2003) tested a three-pass

compact heat exchanger by injecting pure quartz and ASHRAE standard test dust. With ASHRAE standard test dust,

the overall heat transfer decreased by 8 to 18% while the airside pressure drop increased about 200%. The effect of

pure quartz’s on thermal and hydraulic performance was negligible. Pak et al. (2005) tested six condensers clean as

received, after injection of ASHRAE standard test dust, and after cleaning. The fouling mostly deposited on the coil

front side. Fouling had a more significant effect on the pressure drop than the heat transfer. The original performance

of the coils was entirely recovered after washing the coils.

Yang et al. (2007) tested four different coils under varying loads of fouling agents. In many cases, the decrease in heat

transfer was less than the uncertainty of the measurements while the impact of fouling on pressure drop was significant.

In one case, a moderate amount of fouling increased the heat transfer.

Ali and Ismail (2008) studied the effect of airside fouling on a plate fin and tube evaporator. The fouling material was

gathered from the field, on the surface of condensing units. They imposed 100, 200, and 300 grams of the fouling

material. The fouling on the front side was found to contain fibers and dust particles, and the rear side was free of

fiber. Pu et al. (2009 and 2010) studied the effects of biofouling on three fin and tube heat exchangers. They found

that biofouling might increase the heat transfer when it covered less than 10% of the surface area, due to increases in

Page 4: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 2

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

local air velocity.

Bell and Groll (2010 and 2011) tested a plate fin and two microchannel coils, using ASHRAE test dust and Arizona

road test dust. The microchannel coils were more sensitive to fouling than the plate-fin coil. Bell et al. (2011) tested a

hybrid dry cooler by injecting ASHRAE standard test dust in two 300 g increments. In the dry coil condition, the

effect of fouling on heat transfer with airflow rate held constant was negligible.

The two main effects of airside fouling are the buildup of material that can impose an additional conductive resistance

on the coil surface, and the change of the aerodynamic shape of airflow paths through the coil. The changes to the

aerodynamics may cause changes to the convection from the surfaces, in particular by inducing turbulence, which can

enhance the heat transfer, as reported by Yang et al. (2007) and Pu et al. (2009 and 2010). For uncontrolled fan (i.e.

constant speed) condensers, according to the majority of the literature, the dominant effect on the overall heat transfer

is caused by the reduction of the airflow rate. This reduction has a detrimental effect on convection, and also reduces

the log mean temperature difference (LMTD) between the refrigerant and air.

In the current paper, nine field-deployed condensers were collected from the Omaha area. Figure 1 shows the collected

condensing units, and Table 1 shows the specifications of the collected condensing units. Two of the condensers are

spine fin coils, and the others are plate fins. The two spine fin coils are indicated by S1 and S2 in this paper. The seven

plate fin coils are indicated from P1 to P7. For the most fouled spine and plate fin coil, S1 and P7, tests were done on

two sides of the condenser coil (named S1-1, S1-2, P7-1, and P7-2).

Figure 1: Collected condensers

Page 5: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 3

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

Table 1: Specifications of the condensers

Co

nd

enser N

ame

Man

ufactu

ring

Date

No

min

al Co

olin

g

Cap

acity (to

ns)

Tu

be D

iameter

(in.)

Fin

Ty

pe

No

. of R

ow

s

Fin

s per in

ch

Net F

ace Area

(sq. ft.)

S1 Mar-93 3.5 3/8 Spine 1 24 16.12

S2 May-03 4 3/8 Spine 1 24 13.75

P1 Jun-01 3 5/16 Herringbone wavy – Slit louver 2 22 16.04 (15.56 inner coil)

P2 May-06 3 5/16 Herringbone wavy – Slit louver 1 22 18.67

P3 NA 2.5 3/8 Herringbone wavy – Offset louver 1 20 10.2

P4 Jan-01 2.5 5/16 Herringbone wavy – Slit louver 1 18 13.22

P5 Dec-90 2.5 3/8 Herringbone wavy – Slit louver 1 20 9.2

P6 Sep-01 2.5 5/16 Herringbone wavy – Slit louver 1.36 18 15.21 (5.44 inner coil)

P7 Jul-92 2.5 3/8 Herringbone wavy – Slit louver 1 16 15.8

2. METHODOLOGY First, the coils were disconnected and separated from the condensing units. The test method involves the use of hot

water, rather than refrigerant inside the tubes, because it can be controlled more easily to repeatable conditions. Then,

1.55 square feet of the air side of each coil was tested in a test apparatus that is shown in Figure 2. The test area

reasonably represents the surface of the condenser except the curved sections, which could have different internal

airflow patterns. Although in-situ airflow patterns may be different, we do not believe that this effect would change

the outcome of the experiments with this apparatus. The apparatus was developed for another research project and is

fully described in Mehrabi and Yuill (2018a), including a full discussion of the measurement uncertainty and

instrument specifications. The other surfaces of the coil were well insulated during the tests. The air side section of

the test apparatus includes a wind tunnel in a draw-through configuration, and two air straighteners before and after

the coil. The water side section consists of a water loop that passes hot water through the coil (Figure 2).

Figure 2: Test apparatus configuration

Page 6: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 4

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

On the water side section of test apparatus, RTD sensors are installed before and after the coil. On the airside

downstream, nine RTD sensors are installed to get the average temperature. On the upstream side an RTD sensor is

installed to measure the intake, which is at room temperature. Water flow rate, airflow rate, fan speed, coil air side

pressure drop, room relative humidity and absolute pressure are measured with laboratory grade sensors. Air side and

water side heat transfer, which should agree, are calculated from Equations (1) and (2).

𝑄𝑎 = �̇�𝑎(ℎ𝑎,𝑜 − ℎ𝑎,𝑖) (1)

𝑄𝑤 = �̇�𝑤(ℎ𝑤,𝑖 − ℎ𝑤,𝑜) (2)

where a and w indicate the air side and water side, �̇� is mass flow rate, and hi and ho are inlet and outlet enthalpies.

Uncertainty analysis showed that the propagated sensor measurement uncertainty in the heat transfer calculation is

less than 1% on the water side, and about 3% on the air side.

For each coil under test, the coil pressure drop and heat transfer were measured at three different airflow rates. One

airflow rate is the rate associated with the manufacturer’s nominal face velocity for the condensing unit, if available.

A higher and a lower flow rate was tested to provide more generalized results.

After the initial test, the coil was removed from the test apparatus, and fouling material was collected from the coil

test area as much as possible, using tweezers, small brushes, and similar instruments. After all possible fouling was

removed and stored, the coil’s air side was washed with water, then dried. After drying, the coil was installed on the

test apparatus again and retested.

After testing the washed coil, the coil was removed again from the test apparatus and washed with detergent. After

drying, the coil was installed on the test apparatus and tested a third time.

In each condition, the coil pressure drop and heat transfer were measured at constant airflow, at the same flow rate as

the fouled coil tests, as well as constant fan speed. In this way, the two effects of fouling discussed earlier – changes

to heat conduction and changes to convection cause by airflow rate – can be isolated. During testing, if the fan speed

differs by less than one percent for the matched air flow rate and matched fan speed tests, only the matched fan speed

test was conducted. The tests at constant airflow rate mimic the effect of fouling for constant airflow condensers, and

the tests at constant fan speed mimic the effect on typical condensers, which have constant speed motors. The constant

speed tests assume that the fan curve for our fan matches the fan curve for the condensing unit within the working

region, which is the case. Within the small performance region of the tests, the variations in fan characteristics between

typical condenser fans and the test apparatus fan are negligible.

To compare the effect of washing on different capacity coils, the measured airflow rate, pressure drop, and calculated

heat transfer are normalized.

Normalized Value = Current value / Measured value in nominal working condition (3)

The nominal working condition in this paper is the condition in nominal airflow rate as mentioned by the manufacturer

(if available) for each coil. The nominal heat transfer and nominal pressure drop are the values in fouled coil condition

as received.

3- RESULTS Visual observations on the collected coils show that most of the fouling collects on the coil’s face, while the rear side

appears clean. It seems that fibers have a significant effect on the fouling deposition. The collected fibers on the coil’s

face trap other small particles. For the nine coils in this sample, there was no correlation between the visually apparent

fouling level on the coil, and its service life.

Page 7: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 5

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

Table 2 shows the test condition, nominal values and collected mass of fouling material before washing for each coil.

The �̇�𝑤 value is the water mass flow rate in the coil. The Twi value is the water inlet temperature in nominal condition.

For each coil mw and Twi were kept constant during all the tests.

Table 2: Test condition, nominal values, and collected dust

Coil

�̇�𝑤

[kg/s] Twi [°C]

Nominal

Airflow Rate

[CFM]

Nominal

∆P Coil

[Pa]

Nominal

Qw [kW]

Collected

Dust Before

Washing [g]

S1-1 0.0247 47.7 292 20.9 1.598 12.79

S1-2 0.0248 55.1 298 44.4 2.033 25.88

S2 0.0317 52.0 298 18.8 2.205 0.47

P1 0.0233 55.8 338 21.6 1.374 0.06

P2 0.0287 45.8 289 11.2 1.171 0.29

P3 0.0443 40.2 217 8.6 1.050 0.79

P4 0.0315 45.2 291 10.0 1.374 1.82

P5 0.0450 47.3 334 56.8 1.972 0.07

P6 0.0336 54.0 291 12.2 1.227 0.04

P7-1 0.0343 44.1 292 14.1 1.286 9.75

P7-2 0.0342 44.2 294 16.4 1.110 12.19

Figures 3 and 4 show the test results for spine fin and plate fin coils. The left charts show the normalized pressure

drop versus normalized airflow rate, and the right charts show the normalized waterside heat transfer versus

normalized airflow rate, before and after washing the coils. For example, on the left chart for S1-1 coil in Figure 3, the

red curve shows the fouled test results. As can be seen on this curve, the normalized pressure drop in nominal condition

(normalized airflow rate equal to one) by the definition of Equation 3, is one. The other two points on the red curve

show the values at higher and lower airflow rates. The blue and green curves show the normalized pressure drop after

washing the coil only with water and washing with detergent, respectively.

While the washing has a significant effect on pressure drop as can be seen on the left charts, the fouled and the washed

curves are clustered very tightly on right side charts, which indicates that washing has a negligible effect on heat

transfer. Unexpectedly, for some coils, washing even decreased the heat transfer. For example, for S1-2 coil the heat

transfer slightly increased after washing, even though the pressure drop decreased by 64%.

After washing with detergent, for coils P2 and P4, the pressure drop increased compared to results for washing only

with water. This might be attributed to the fact that the applied basic detergent that is typically used for condensers is

relatively corrosive. For aluminum coils (such as the spine fin coils) manufacturers recommend pH neutral detergents.

After washing the spine fin coils with a no-rinse neutral detergent, the pressure drop slightly increased compared to

washing only with water. Washing with detergent did not have a significant effect on heat transfer compared to

washing with water.

After washing, for most of the coils, the fan speed for constant airflow tests did not change significantly compared to

the fouled tests. Therefore, the constant airflow results can also represent the effect of fouling on typical condensing

units with constant fan speed. However, for coil S1-2 (the dirtiest coil), the fan speed for the constant airflow rate test

differs from the speed in the fouled tests. For this coil, additional tests were done to study the effect of fouling at

constant fan speed condition. For these tests, the pressure drop and heat transfer are higher compared to constant

airflow tests.

Page 8: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 6

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

S1-1 coil

results

S1-2 coil

results

S2 coil

results

Figure 3: Effect of washing the condensers on spine fin coils

Same fan speed

Same Airflow

Page 9: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 7

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

P1 coil

results

P2 coil

results

P3 coil

results

Figure 4 Continued: Effect of washing the condensers on plate fin coils

Page 10: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 8

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

P4 coil

results

P5 coil

results

P6 coil

results

Figure 4 Continued: Effect of washing the condensers on plate fin coils

Page 11: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 9

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

P7-1

P7-2

Figure 4 Continued: Effect of washing the condensers on plate fin coils

DISCUSSION

The results show that the effect of washing on heat transfer capacity of the coils is usually negligible. Unexpectedly,

in some cases washing the coil can decrease the heat transfer. Because it was unexpected, a careful check was made

of all the experimental apparatus to make sure there were no measurement errors, and for two coils that exhibited the

unexpected result, a second portion of the coil was tested. Although it is not possible to determine the cause of the

increased heat transfer capacity from fouling in some of the coils, a plausible explanation is that the fouling material

induces turbulence on the air side, which enhances the heat transfer. This is the reason that coil manufacturers add fin

enhancements to coils, even though they typically increase pressure drop.

If washing of a condenser coil provides no clear and significant benefit, maintenance practices for hundreds of millions

of air conditioners may need to be revisited. Thus, this work may have high impact. The sample size should be

increased in future work, to add certainty to the results.

For typical split system condenser fans, the difference in fan curves is small enough that these results, considering the

small changes to the working point caused by typical levels of field fouling, can be considered applicable for any

typical condenser. One factor that has not been considered in the current study is the effect of fouling on condenser

Page 12: Evaluation The Effect Of Washing On The Heat Transfer

2216, Page 10

17th International Refrigeration and Air Conditioning Conference at Purdue, July 9-12, 2018

fan power. This will be examined in future work. Also, the effects on coil capacity, though small, should be considered

in the context of overall system efficiency and capacity. This can be achieved by using generalized results from

multiple laboratory tests of condenser fault testing, presented by Mehrabi and Yuill (2018b).

CONCLUSION The effects of washing the air side fouling of condensers of air conditioners were studied in this paper. Based on the

results, washing does not have a significant effect on heat transfer capacity, even though it significantly decreases the

coil’s air side pressure drop. In some cases, fouling even can increase the heat transfer capacity. Washing with

detergent had no meaningful advantage when compared to washing with water only. In some cases, it even increased

the pressure drop through the coil compared to washing with water. Future work will further examine the ramifications

of these results on overall system performance and maintenance.

REFERENCES Ahn, Y. C., J. M. Cho, H. S. Shin, Y. J. Hwang, C. G. Lee, J. K. Lee and T. W. Kang. 2003. An experimental study

of the air-side particulate fouling in fin-and-tube heat exchangers of air conditioners. Korean Journal of Chemical

Engineering, 20(5), 873-877.

Ahn, Y. C. and J. K. Lee. 2005. Characteristics of air-side particulate fouling materials in finned-tube heat exchangers

of air conditioners. Particulate science and technology, 23(3):297-307.

Ali, A. H. H. and I. M. Ismail. 2008. Evaporator air-side fouling: effect on performance of room air conditioners and

impact on indoor air quality. HVAC&R Research, 14(2):209-219.

Bell, I. H. and E. A. Groll. 2010. Experimental comparison of the impact of air-side particulate fouling on the

thermo-hydraulic performance of microchannel and plate-fin heat exchangers. International Refrigeration and Air

Conditioning Conference at Purdue.

Bell, I. H. and E. A. Groll. 2011. Air-side particulate fouling of microchannel heat exchangers: experimental

comparison of air-side pressure drop and heat transfer with plate-fin heat exchanger. Applied Thermal

Engineering,31(5), 742-749.

Bell, I. H., E. A. Groll and H. König. 2011. Experimental analysis of the effects of particulate fouling on heat

exchanger heat transfer and air-side pressure drop for a hybrid dry cooler. Heat Transfer Engineering, 32(3-4): 264-

271.

Lankinen, R., J. Suihkonen and P. Sarkomaa. 2003. The effect of air side fouling on thermal‐hydraulic

characteristics of a compact heat exchanger. International Journal of Energy Research, 27(4):349-361.

Mehrabi, M., and D.P. Yuill. 2018a. Development of a method for testing air-side fouling effects on outdoor heat

exchangers (RP-1705). 2018 ASHRAE Winter Conference.

Mehrabi, M. and D.P. Yuill. 2018b. Generalized effects of faults on normalized performance variables of air

conditioners and heat pumps. International Journal of Refrigeration 85 (2018): 409-430.

Pak, B. C., E. A. Groll and J. E. Braun. 2005. Impact of fouling and cleaning on plate fin and spine fin heat

exchanger performance. ASHRAE Transactions, 111(1).

Pu, H., G. L. Ding, X. K. Ma, H. T. Hu and Y. F. Gao. 2009. Effects of biofouling on air-side heat transfer and pressure

drop for finned tube heat exchangers. International journal of refrigeration, 32(5), 1032-1040.

Pu, H., G. L. Ding, X. K. Ma, H. T. Hu and Y. F. Gao. 2010. Air-side heat transfer and friction characteristics of

biofouled evaporator under wet conditions. Frontiers of Energy and Power Engineering in China, 4(3), 306-312.

Yang, L., J. E. Braun and E. A. Groll. 2007. The impact of fouling on the performance of filter–evaporator

combinations. International Journal of Refrigeration, 30(3):489-498.